ALPHA-INVERTER-SYS-MIB DEFINITIONS ::= BEGIN
--==========================================================================
--
-- Alpha Technologies Ltd.
-- Copyright 2014
--
--==========================================================================
IMPORTS
MODULE-IDENTITY, OBJECT-TYPE
FROM SNMPv2-SMI
ScaledNumber, simple
FROM ALPHA-RESOURCE-MIB
MODULE-COMPLIANCE, OBJECT-GROUP
FROM SNMPv2-CONF;
inverterSystem MODULE-IDENTITY
LAST-UPDATED "201602290000Z"
ORGANIZATION "Alpha Technologies Ltd."
CONTACT-INFO
"Alpha Technologies Ltd.
7700 Riverfront Gate
Burnaby, BC V5J 5M4
Canada
Tel: 1-604-436-5900
Fax: 1-604-436-1233"
DESCRIPTION
"
This MIB provides a flat list of data points available from the Cordex HP controller
to present information of one Inverter System.
"
REVISION "201602290000Z" -- February 29, 2016
DESCRIPTION
"General revision."
::= { simple 3 }
--==========================================================================
-- Subfolders for Phase, AC Input and DC Input groups.
--==========================================================================
phaseGroup OBJECT IDENTIFIER ::= { inverterSystem 80 }
acInputGroup OBJECT IDENTIFIER ::= { inverterSystem 81 }
dcInputGroup OBJECT IDENTIFIER ::= { inverterSystem 82 }
-- Inverter System data points
invTotalAcOutputPowerVa OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total output power summed from all the phases (VA)."
::= { inverterSystem 1 }
invSysAverageLoadingOfInstalledPowerVa OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The average output loading of all phases (% VA). "
::= { inverterSystem 2 }
invSysAverageDcInputToOutputPowerRatio OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The percentage of the output that is taken from the DC input (%)."
::= { inverterSystem 3 }
invSysSystemMode OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The mode of the system. See manual for decoding the number."
::= { inverterSystem 4 }
invSysPhase1OutputPowerVa OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total output power from the phase 1 (VA)."
::= { inverterSystem 5 }
invSysPhase2OutputPowerVa OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total output power from phase 2 (VA)."
::= { inverterSystem 6 }
invSysPhase3OutputPowerVa OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total output power from the phase 3 (VA)."
::= { inverterSystem 7 }
invSysAverageOutputVoltageMeasured OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The average output voltage of all the phases (V)."
::= { inverterSystem 8 }
invSysEnabledDisconnects OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of disconnects that are enabled."
::= { inverterSystem 9 }
invSysActivatedDisconnects OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of disconnects that are active."
::= { inverterSystem 10 }
invSysTotalDCInputCurrent OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Total DC input current for the inverter system (A)."
::= { inverterSystem 11 }
invSysAverageDcInputVoltage OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average DC input voltage reading for the inverter system (V)."
::= { inverterSystem 12 }
invSysTotalDcInputPower OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Total DC input power reading for the inverter system (W)."
::= { inverterSystem 13 }
invSysSystemOnBypass OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"True when the bypass switch is on. The AC input from the grid is fed to the AC load directly."
::= { inverterSystem 14 }
invSysTotalAcInputPowerVa OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Total AC input power reading of the Inverter System (VA)."
::= { inverterSystem 18 }
-- Phase Group
invSysAcPhaseCount OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"
"
::= { phaseGroup 1 }
invSysAcPhaseTable OBJECT-TYPE
SYNTAX SEQUENCE OF InvSysAcPhaseEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"
"
::= { phaseGroup 2 }
invSysAcPhaseEntry OBJECT-TYPE
SYNTAX InvSysAcPhaseEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"
"
INDEX { invSysAcPhaseCount }
::= { invSysAcPhaseTable 1 }
InvSysAcPhaseEntry ::= SEQUENCE {
invSysAcPhaseAcOutputPowerVa ScaledNumber,
invSysAcPhaseOutputVoltageMeasured ScaledNumber,
invSysAcPhaseOutputCurrent ScaledNumber,
invSysAcPhaseFrequency ScaledNumber,
invSysAcPhaseLoadingOfInstalledPowerVa ScaledNumber,
invSysAcPhaseNumberOfModulesOn ScaledNumber,
invSysAcPhaseLoadingOfInstalledPowerWatts ScaledNumber,
invSysAcPhaseDcInputToOutputPowerRatioMeasured ScaledNumber,
invSysAcPhaseAcInputPowerWatts ScaledNumber,
invSysAcPhaseAcInputPowerVa ScaledNumber,
invSysAcPhaseAcOutputPowerWatts ScaledNumber,
invSysAcPhaseDCInputPowerWatts ScaledNumber,
invSysAcPhaseNumberOfRedundantModulesMeasured ScaledNumber,
invSysAcPhaseNumberOfModulesDetected ScaledNumber,
invSysAcPhaseNumberOfModulesOff ScaledNumber,
invSysAcPhaseNumberOfModulesFailed ScaledNumber
}
invSysAcPhaseAcOutputPowerVa OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The power of the AC output (VA)."
::= { invSysAcPhaseEntry 1 }
invSysAcPhaseOutputVoltageMeasured OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The output voltage of the phase or inverter (V)."
::= { invSysAcPhaseEntry 2 }
invSysAcPhaseOutputCurrent OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The output current of the phase or inverter (A)."
::= { invSysAcPhaseEntry 3 }
invSysAcPhaseFrequency OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Frequency to which the inverters will lock (Hz)."
::= { invSysAcPhaseEntry 4 }
invSysAcPhaseLoadingOfInstalledPowerVa OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The ratio of output load to installed power (%VA)."
::= { invSysAcPhaseEntry 5 }
invSysAcPhaseNumberOfModulesOn OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of inverters that are On and can deliver power."
::= { invSysAcPhaseEntry 6 }
invSysAcPhaseLoadingOfInstalledPowerWatts OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The ratio of output load to installed power (% W)."
::= { invSysAcPhaseEntry 7 }
invSysAcPhaseDcInputToOutputPowerRatioMeasured OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The measured percentage of DC input power to output power(%). Under light or no load this value will not computed accurately."
::= { invSysAcPhaseEntry 8 }
invSysAcPhaseAcInputPowerWatts OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The power drawn by the AC input (W)."
::= { invSysAcPhaseEntry 9 }
invSysAcPhaseAcInputPowerVa OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The power drawn by the AC input (VA)."
::= { invSysAcPhaseEntry 10 }
invSysAcPhaseAcOutputPowerWatts OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The power of the AC output (W)."
::= { invSysAcPhaseEntry 11 }
invSysAcPhaseDCInputPowerWatts OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The power drawn by the DC input (W)."
::= { invSysAcPhaseEntry 12 }
invSysAcPhaseNumberOfRedundantModulesMeasured OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of inverters currently unneeded by the load."
::= { invSysAcPhaseEntry 13 }
invSysAcPhaseNumberOfModulesDetected OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of inverters assigned to this phase that the T2S has detected."
::= { invSysAcPhaseEntry 14 }
invSysAcPhaseNumberOfModulesOff OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of inverters that are manually turned off."
::= { invSysAcPhaseEntry 15 }
invSysAcPhaseNumberOfModulesFailed OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of inverters that have failed and cannot deliver power."
::= { invSysAcPhaseEntry 16 }
-- AC Input Group
invSysAcInputCount OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"
"
::= { acInputGroup 1 }
invSysAcInputTable OBJECT-TYPE
SYNTAX SEQUENCE OF InvSysAcInputEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"
"
::= { acInputGroup 2 }
invSysAcInputEntry OBJECT-TYPE
SYNTAX InvSysAcInputEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"
"
INDEX { invSysAcInputCount }
::= { invSysAcInputTable 1 }
InvSysAcInputEntry ::= SEQUENCE {
invSysAcInputInputVoltage ScaledNumber,
invSysAcInputInputCurrent ScaledNumber,
invSysAcInputFrequency ScaledNumber,
invSysAcInputAcInputPowerVa ScaledNumber,
invSysAcInputNumberOfModulesOn ScaledNumber,
invSysAcInputAcInputPowerWatts ScaledNumber,
invSysAcInputNumberOfModulesDetected ScaledNumber,
invSysAcInputNumberOfModulesOff ScaledNumber,
invSysAcInputNumberOfModulesFailed ScaledNumber
}
invSysAcInputInputVoltage OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The input voltage of the inverter or group (V)."
::= { invSysAcInputEntry 1 }
invSysAcInputInputCurrent OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The input current of the inverter or group (A)."
::= { invSysAcInputEntry 2 }
invSysAcInputFrequency OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The frequency of the input voltage and current of the inverter or group (Hz)."
::= { invSysAcInputEntry 3 }
invSysAcInputAcInputPowerVa OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The power drawn by the AC input (VA)."
::= { invSysAcInputEntry 4 }
invSysAcInputNumberOfModulesOn OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of inverters that are On and can deliver power."
::= { invSysAcInputEntry 5 }
invSysAcInputAcInputPowerWatts OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The power drawn by the AC input (W)."
::= { invSysAcInputEntry 6 }
invSysAcInputNumberOfModulesDetected OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of inverters assigned to this phase that the T2S has detected."
::= { invSysAcInputEntry 7 }
invSysAcInputNumberOfModulesOff OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of inverters that are manually turned off."
::= { invSysAcInputEntry 8 }
invSysAcInputNumberOfModulesFailed OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of inverters that have failed and cannot deliver power."
::= { invSysAcInputEntry 9 }
-- DC Input Group
invSysDcInputCount OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"
"
::= { dcInputGroup 1 }
invSysDcInputTable OBJECT-TYPE
SYNTAX SEQUENCE OF InvSysDcInputEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"
"
::= { dcInputGroup 2 }
invSysDcInputEntry OBJECT-TYPE
SYNTAX InvSysDcInputEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"
"
INDEX { invSysDcInputCount }
::= { invSysDcInputTable 1 }
InvSysDcInputEntry ::= SEQUENCE {
invSysDcInputInputVoltage ScaledNumber,
invSysDcInputInputCurrent ScaledNumber,
invSysDcInputDcInputPowerWatts ScaledNumber,
invSysDcInputNumberOfModulesOn ScaledNumber,
invSysDcInputNumberOfModulesOff ScaledNumber,
invSysDcInputNumberOfModulesFailed ScaledNumber,
invSysDcInputNumberOfModulesDetected ScaledNumber
}
invSysDcInputInputVoltage OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The input voltage of the inverter or group (V)."
::= { invSysDcInputEntry 1 }
invSysDcInputInputCurrent OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The input current of the inverter or group (A)."
::= { invSysDcInputEntry 2 }
invSysDcInputDcInputPowerWatts OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The power drawn by the DC input (W)."
::= { invSysDcInputEntry 3 }
invSysDcInputNumberOfModulesOn OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of inverters that are On and can deliver power."
::= { invSysDcInputEntry 4 }
invSysDcInputNumberOfModulesOff OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of inverters that are manually turned off."
::= { invSysDcInputEntry 5 }
invSysDcInputNumberOfModulesFailed OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of inverters that have failed and cannot deliver power."
::= { invSysDcInputEntry 6 }
invSysDcInputNumberOfModulesDetected OBJECT-TYPE
SYNTAX ScaledNumber
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of inverters assigned to this phase that the T2S has detected."
::= { invSysDcInputEntry 7 }
END