Observium_CE/includes/discovery/sensors/roomalert3e-mib.inc.php

131 lines
6.0 KiB
PHP

<?php
/**
* Observium
*
* This file is part of Observium.
*
* @package observium
* @subpackage discovery
* @copyright (C) Adam Armstrong
*
*/
// ATTENTION! In the SNMP settings of the device, there is a checkbox called [ ] Use 2 digit SNMP.
// If checked, values will be rounded; SNMP will return 20 for 20.4 degrees. If unchecked, values are *1000, so 2040 for 20.4 degrees.
//
// Some Nagios plugins only work with 2 digits mode. We support both formats with this code.
// We will detect the scale based on whether the measured humidity is > 100. This will fail on 4-digit humidity < 1% ;-)
$scale = 1; // Start at 1 for 2 digits setting.
// ROOMALERT3E-MIB::digital-sen1-1.0 = INTEGER: 2475
// ROOMALERT3E-MIB::digital-sen1-2.0 = INTEGER: 7655
// ROOMALERT3E-MIB::digital-sen1-label.0 = STRING: "Internal Sensor"
// ROOMALERT3E-MIB::digital-sen2-1.0 = INTEGER: 2178
// ROOMALERT3E-MIB::digital-sen2-2.0 = INTEGER: 7120
// ROOMALERT3E-MIB::digital-sen2-3.0 = INTEGER: 5720
// ROOMALERT3E-MIB::digital-sen2-4.0 = INTEGER: 7120
// ROOMALERT3E-MIB::digital-sen2-5.0 = INTEGER: 2177
// ROOMALERT3E-MIB::digital-sen2-6.0 = INTEGER: 1322
// ROOMALERT3E-MIB::digital-sen2-7.0 = INTEGER: 5579
// ROOMALERT3E-MIB::digital-sen2-label.0 = STRING: "Ext Sensor 1"
$oids = snmpwalk_cache_oid($device, "digital-sen1-1", [], "ROOMALERT3E-MIB");
foreach ($oids as $index => $entry) {
$descr = $entry['digital-sen1-label'] ?: "Internal Temperature";
if (count($oids) > 1) {
$descr .= " " . ($index + 1);
}
$oid = ".1.3.6.1.4.1.20916.1.9.1.1.1.1.$index";
$value = $entry['digital-sen1-1'];
if ($value > 100) {
$scale = 0.01;
}
//discover_sensor('temperature', $device, $oid, "digital-sen1-1.$index", 'roomalert', $descr, $scale, $value);
}
// Digital sensors -- ARGH, why not digital-sen.1.1.0 instead of digital-sen1-1.0 !
// "Monitor for Temperature, Humidity, Heat Index (Feels Like), Power, Flood/Water, Smoke/Fire, Room Entry, Air Flow, Network Cameras and more."
// Great, now how do I see what sensor is connected over SNMP? Right... No OID for that.
//
// So we'll go by this table:
//
// | Temp sensor | Temp/Humidity sensor | Power Sensor
// --------+--------------------+--------------------------+-----------------
// sen1-1: | Temp in Celsius | Temp in Celsius | Amperes
// sen1-2: | Temp in Fahrenheit | Temp in Fahrenheit | Watts
// sen1-3: | N/A | Humidity | Volts
// sen1-4: | N/A | Heat index in Fahrenheit | Reference Volts
// sen1-5: | N/A | Heat index in Celsius | N/A
$oids = snmpwalk_cache_oid($device, "digital", [], "ROOMALERT3E-MIB");
$index = 0;
for ($i = 1; $i <= 2; $i++) {
if (isset($oids[$index]["digital-sen$i-1"])) {
$name = $oids[$index]["digital-sen$i-label"] ?: "Channel $i";
// Sensor is present.
if (!isset($oids[$index]["digital-sen$i-3"])) {
// Temp sensor
$descr = "$name: Temperature";
$oid = ".1.3.6.1.4.1.20916.1.9.1.1.$i.1.$index";
$value = $oids[$index]["digital-sen$i-1"];
$options = ['rename_rrd' => "roomalert-digital-sen$i-1.$index"];
discover_sensor_ng($device, 'temperature', $mib, "digital-sen$i-1", $oid, $index, $descr, $scale, $value, $options);
} elseif (isset($oids[$index]["digital-sen$i-5"])) {
// Temp/Humidity sensor
$descr = "$name: Temperature";
$oid = ".1.3.6.1.4.1.20916.1.9.1.1.$i.1.$index";
$value = $oids[$index]["digital-sen$i-1"];
$options = ['rename_rrd' => "roomalert-digital-sen$i-1.$index"];
discover_sensor_ng($device, 'temperature', $mib, "digital-sen$i-1", $oid, $index, $descr, $scale, $value, $options);
$descr = "$name: Heat index";
$oid = ".1.3.6.1.4.1.20916.1.9.1.1.$i.5.$index";
$value = $oids[$index]["digital-sen$i-5"];
$options = ['rename_rrd' => "roomalert-digital-sen$i-5.$index"];
discover_sensor_ng($device, 'temperature', $mib, "digital-sen$i-5", $oid, $index, $descr, $scale, $value, $options);
$descr = "$name: Humidity";
$oid = ".1.3.6.1.4.1.20916.1.9.1.1.$i.3.$index";
$value = $oids[$index]["digital-sen$i-3"];
$options = ['rename_rrd' => "roomalert-digital-sen$i-3.$index"];
discover_sensor_ng($device, 'humidity', $mib, "digital-sen$i-3", $oid, $index, $descr, $scale, $value, $options);
$descr = "$name: Dew Point";
$oid = ".1.3.6.1.4.1.20916.1.9.1.1.$i.6.$index";
$value = $oids[$index]["digital-sen$i-6"];
discover_sensor_ng($device, 'dewpoint', $mib, "digital-sen$i-6", $oid, $index, $descr, $scale, $value);
} else {
// Power sensor
$descr = "Channel $i: Current";
$oid = ".1.3.6.1.4.1.20916.1.9.1.1.$i.1.$index";
$value = $oids[$index]["digital-sen$i-1"];
discover_sensor('current', $device, $oid, "digital-sen$i-1.$index", 'roomalert', $descr, $scale, $value);
$descr = "Channel $i: Power";
$oid = ".1.3.6.1.4.1.20916.1.9.1.1.$i.2.$index";
$value = $oids[$index]["digital-sen$i-2"];
discover_sensor('power', $device, $oid, "digital-sen$i-2.$index", 'roomalert', $descr, $scale, $value);
$descr = "Channel $i: Voltage";
$oid = ".1.3.6.1.4.1.20916.1.9.1.1.$i.3.$index";
$value = $oids[$index]["digital-sen$i-3"];
discover_sensor('voltage', $device, $oid, "digital-sen$i-3.$index", 'roomalert', $descr, $scale, $value);
$descr = "Channel $i: Reference voltage";
$oid = ".1.3.6.1.4.1.20916.1.9.1.1.$i.4.$index";
$value = $oids[$index]["digital-sen$i-4"];
discover_sensor('voltage', $device, $oid, "digital-sen$i-4.$index", 'roomalert', $descr, $scale, $value);
}
}
}
// EOF