5090 lines
189 KiB
Plaintext

--------------------------------------------------------------------------------
-- Avocent ACS8000 MIB
-- Copyright 2020 Vertiv Co
-- Revision: 2.16.0
-- Last Modified: April 2021
--------------------------------------------------------------------------------
ACS8000-MIB DEFINITIONS ::= BEGIN
IMPORTS
Gauge,TimeTicks,IpAddress,Counter,NetworkAddress
FROM RFC1155-SMI
PhysAddress
FROM RFC1213-MIB
enterprises, MODULE-IDENTITY
FROM SNMPv2-SMI
OBJECT-TYPE, MODULE-IDENTITY, OBJECT-IDENTITY, Integer32
FROM SNMPv2-SMI
DisplayString
FROM SNMPv2-TC
InterfaceIndex, InterfaceIndexOrZero
FROM IF-MIB
TRAP-TYPE
FROM RFC-1215;
--------------------------------------------------------------------------------
-- Object Groupings
--------------------------------------------------------------------------------
--@ Note: every product type should be uniquely identified underneath the
--@ acsProducts object group. Each product should report its unique acsProducts
--@ OBJECT IDENTIFIER in mib-2.system.sysObjectID.
-- enterprises .1.3.6.1.4.1
-- avocent OBJECT IDENTIFIER ::= { enterprises 10418 }
acs MODULE-IDENTITY
LAST-UPDATED "202104190000Z"
ORGANIZATION "Vertiv Co"
CONTACT-INFO "e-mail : support.avocent@vertiv.com
Web : www.vertiv.com
postal : Vertiv Co
4991 Corporate Drive
Huntsville, AL 35805
USA"
DESCRIPTION "This module defines the MIB extensions to ACS80xx products."
REVISION "202104190000Z"
DESCRIPTION "Added acsScheduledTasksTable."
REVISION "202010010000Z"
DESCRIPTION "Added serial and part number information for PDUs."
REVISION "202007010000Z"
DESCRIPTION "Added support for acsModems. Added support for resetting
serial port statistics."
REVISION "201906010000Z"
DESCRIPTION "Added support for sensors"
REVISION "201805010000Z"
DESCRIPTION "Dewpoint sensor type"
REVISION "201711170000Z"
DESCRIPTION "Vertiv updates"
REVISION "201606170000Z"
DESCRIPTION "Added UPS support"
REVISION "201601060000Z"
DESCRIPTION "Ported to acs8000 and that product list"
REVISION "201010100000Z"
DESCRIPTION "Extended acsPowerMgmt to support data monitoring and Avocent PM-PDUs"
REVISION "200709170000Z"
DESCRIPTION "First Draft"
::= { enterprises 10418 26 }
acsProducts OBJECT IDENTIFIER ::= { acs 1 }
acsManagement OBJECT IDENTIFIER ::= { acs 2 }
--
acs8048 OBJECT IDENTIFIER ::= { acsProducts 1 } -- 10418.26.1.1
acs8032 OBJECT IDENTIFIER ::= { acsProducts 2 } -- 10418.26.1.2
acs8016 OBJECT IDENTIFIER ::= { acsProducts 3 } -- 10418.26.1.3
acs8008 OBJECT IDENTIFIER ::= { acsProducts 4 } -- 10418.26.1.4
acs808 OBJECT IDENTIFIER ::= { acsProducts 5 } -- 10418.26.1.5
acs804 OBJECT IDENTIFIER ::= { acsProducts 6 } -- 10418.26.1.6
acs802 OBJECT IDENTIFIER ::= { acsProducts 7 } -- 10418.26.1.7
acsAppliance OBJECT IDENTIFIER ::= { acsManagement 1 } -- 10418.26.2.1
acsSessions OBJECT IDENTIFIER ::= { acsManagement 2 } -- 10418.26.2.2
acsSerialPort OBJECT IDENTIFIER ::= { acsManagement 3 } -- 10418.26.2.3
acsPowerMgmt OBJECT IDENTIFIER ::= { acsManagement 5 } -- 10418.26.2.5
-- objects under acsPowerMgmt
-- acsPowerMgmtNumSerialPorts ::= { acsPowerMgmt 1 }
-- acsPowerMgmtSerialTable ::= { acsPowerMgmt 2 }
-- acsPowerMgmtPDUTable ::= { acsPowerMgmt 3 }
-- acsPowerMgmtTotalNumberOfOutlets ::= { acsPowerMgmt 4 }
-- acsPowerMgmtOutletsTable ::= { acsPowerMgmt 5 }
-- acsPowerMgmtNumberOfOutletGroup ::= { acsPowerMgmt 6 }
-- acsPowerMgmtGroupTable ::= { acsPowerMgmt 7 }
-- acsPowerMgmtPhasesTable ::= { acsPowerMgmt 8 }
-- acsPowerMgmtBanksTable ::= { acsPowerMgmt 9 }
-- acsPowerMgmtEnvMonTable ::= { acsPowerMgmt 10 }
-- acsPowerMgmtOutElecMonTable ::= { acsPowerMgmt 11 }
-- acsPowerMgmtUPSTable ::= { acsPowerMgmt 12 }
-- acsPowerMgmtUPSInputTable ::= { acsPowerMgmt 13 }
-- acsPowerMgmtUPSBypassTable ::= { acsPowerMgmt 14 }
-- acsPowerMgmtUPSBatteryTable ::= { acsPowerMgmt 15 }
-- acsPowerMgmtUPSOutputTable ::= { acsPowerMgmt 16 }
-- acsPowerMgmtUPSEcoModeTable ::= { acsPowerMgmt 17 }
-- acsPowerMgmtUPSOutletGroupTable ::= { acsPowerMgmt 18 }
--
-- Note that traps are defined in a separate trap MIB
--
acsTrapObject OBJECT IDENTIFIER ::= { acsManagement 6 } -- 10418.26.2.6
acsSensors OBJECT IDENTIFIER ::= { acsManagement 7 } -- 10418.26.2.7
acsModems OBJECT IDENTIFIER ::= { acsManagement 8 } -- 10418.26.2.8
--
-- Type Definitions
--
--
-- Each enumeration represents the states of the appliance power supplies.
PowerSupplyState ::= INTEGER
{
statePowerOn(1),
statePowerOff(2),
powerNotInstaled(9999)
}
--
-- Each enumeration represents the speed of the serial port.
SerialPortSpeed ::= INTEGER
{
speed300bps(300),
speed600bps(600),
speed1200bps(1200),
speed2400bps(2400),
speed4800bps(4800),
speed9600bps(9600),
speed19200bps(19200),
speed38400bps(38400),
speed57600bps(57600),
speed115200bps(115200),
speed230400bps(230400),
speed460800bps(460800)
}
--
-- Each enumeration represents the state of the RS-232C signal.
SerialPortSignalState ::=INTEGER
{
up(1),
down(2)
}
--
-- Each enumeration represents the RJ-45 pin-out
SerialPortPinOut ::=INTEGER
{
cyclades(1),
cisco(2),
rs422(3),
rs485(4),
auto(5)
}
--
-- acsAppliance
-- OBJECT IDENTIFIER ::= { acsManagement 1 } 10418.26.2.1
--
acsHostName OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The appliance name"
::= { acsAppliance 1 }
acsProductModel OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..50) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The appliance product model"
::= { acsAppliance 2 }
acsPartNumber OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The part number of this appliance as shown on the label
attached or imprinted on the appliance."
::= { acsAppliance 3 }
acsSerialNumber OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The serial number of this appliance as shown on the label
attached or imprinted on the appliance."
::= { acsAppliance 4 }
acsEIDNumber OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The electronic ID number (EID) of this appliance as shown on the label
attached or imprinted on the appliance."
::= { acsAppliance 5 }
acsBootcodeVersion OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The version of the bootcode of this appliance."
::= { acsAppliance 6 }
acsFirmwareVersion OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The version of the firmware of this appliance."
::= { acsAppliance 7 }
acsPowerSupply OBJECT-IDENTITY
STATUS current
DESCRIPTION
"It gives information about Power Supply of this appliance"
::= { acsAppliance 8 }
acsPowerSupplyNumber OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of the power supplies of this appliance"
::= { acsPowerSupply 1 }
acsPowerSupplyStatePw1 OBJECT-TYPE
SYNTAX PowerSupplyState
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"State of the first power supply"
::= { acsPowerSupply 2 }
acsPowerSupplyStatePw2 OBJECT-TYPE
SYNTAX PowerSupplyState
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"State of the second power supply"
::= { acsPowerSupply 3 }
acsReboot OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
reboot(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A set value of reboot(2) will reboot the appliance.
noAction(1) = always returned in a GET. Does nothing if SET.
reboot(2) = when SET the appliance immediately reboots."
::= { acsAppliance 9 }
--
-- acsScheduledTasksTable
-- OBJECT IDENTIFIER ::= 10418.26.2.1.10
--
acsScheduledTasksTable OBJECT-TYPE
SYNTAX SEQUENCE OF AcsScheduledTasksTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains the list of the scheduled tasks."
::= { acsAppliance 10 }
acsScheduledTasksTableEntry OBJECT-TYPE
SYNTAX AcsScheduledTasksTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"each entry has the information about the scheduled task"
INDEX { acsScheduledTasksTableIndex }
::= { acsScheduledTasksTable 1 }
AcsScheduledTasksTableEntry ::= SEQUENCE {
acsScheduledTasksTableIndex InterfaceIndexOrZero,
acsScheduledTasksTableType INTEGER,
acsScheduledTasksTableName DisplayString,
acsScheduledTasksTableStatus INTEGER,
acsScheduledTasksTableFrequency INTEGER,
acsScheduledTasksTableDay INTEGER,
acsScheduledTasksTableDate Integer32,
acsScheduledTasksTableTime DisplayString,
acsScheduledTasksTableLastStarted DisplayString,
acsScheduledTasksTableLastResult DisplayString,
acsScheduledTasksTableScript DisplayString,
acsScheduledTasksTableIpAddress DisplayString
}
acsScheduledTasksTableIndex OBJECT-TYPE
SYNTAX InterfaceIndexOrZero
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A unique index representing an entry in this table."
::= { acsScheduledTasksTableEntry 1 }
acsScheduledTasksTableType OBJECT-TYPE
SYNTAX INTEGER {
custom(1),
cell-modem-ip-test(2),
cell-modem-signal-check(3),
save-config-cli(4)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The type of the scheduled task."
::= { acsScheduledTasksTableEntry 2 }
acsScheduledTasksTableName OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Name of the scheduled task."
::= { acsScheduledTasksTableEntry 3 }
acsScheduledTasksTableStatus OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
enabled(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"When set to enabled, the task will be run according to the schedule
defined by acsScheduledTasksTableFrequency."
::= { acsScheduledTasksTableEntry 4 }
acsScheduledTasksTableFrequency OBJECT-TYPE
SYNTAX INTEGER {
hourly(1),
daily(2),
weekly(3),
monthly(4)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This object defines how often the task will be run.
When set to hourly(1), the task will be run every hour.
When set to daily(2), the task will be run every day at the time
specified by acsScheduledTasksTableTime.
When set to weekly(3), the task will be run every week on the day
specified by acsScheduledTasksTableDay, at the time
specified by acsScheduledTasksTableTime.
When set to monthly(4), the task will be run every month on the day
specified by acsScheduledTasksTableDate, at the time
specified by acsScheduledTasksTableTime.
"
::= { acsScheduledTasksTableEntry 5 }
acsScheduledTasksTableDay OBJECT-TYPE
SYNTAX INTEGER {
sunday(1),
monday(2),
tuesday(3),
wednesday(4),
thursday(5),
friday(6),
saturday(7)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Only used if acsScheduledTasksTableFrequency is set to weekly(3).
The task will be run every week on this day, at the time
specified by acsScheduledTasksTableTime.
"
::= { acsScheduledTasksTableEntry 6 }
acsScheduledTasksTableDate OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Only used if acsScheduledTasksTableFrequency is set to monthly(4).
The task will be run every month on this day, at the time
specified by acsScheduledTasksTableTime."
::= { acsScheduledTasksTableEntry 7 }
acsScheduledTasksTableTime OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The time of day the task will run. Format must be HH:MM."
::= { acsScheduledTasksTableEntry 8 }
acsScheduledTasksTableLastStarted OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The timestamp of the last time the task started running."
::= { acsScheduledTasksTableEntry 9 }
acsScheduledTasksTableLastResult OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..256) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The result of the last time the task was run."
::= { acsScheduledTasksTableEntry 10 }
acsScheduledTasksTableScript OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..128) )
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The script command used by the task. Only used if
acsScheduledTasksTableType is set to custom(1)."
::= { acsScheduledTasksTableEntry 11 }
acsScheduledTasksTableIpAddress OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The IP address used by the cell-modem-ip task. Not used
by all tasks."
::= { acsScheduledTasksTableEntry 12 }
--
-- acsSessions
-- OBJECT IDENTIFIER ::= { acsManagement 2 } 10418.26.2.2
--
acsActiveSessionsNumberOfSession OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of active sessions."
::= { acsSessions 1 }
acsActiveSessionsTable OBJECT-TYPE
SYNTAX SEQUENCE OF AcsActiveSessionsTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains the list of active sessions."
::= { acsSessions 2 }
acsActiveSessionsTableEntry OBJECT-TYPE
SYNTAX AcsActiveSessionsTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"each entry has the information about the active session"
INDEX { acsActiveSessionsTableIndex }
::= { acsActiveSessionsTable 1 }
AcsActiveSessionsTableEntry ::= SEQUENCE {
acsActiveSessionsTableIndex InterfaceIndexOrZero,
acsActiveSessionsTableUser DisplayString, -- user name
acsActiveSessionsTableGroup DisplayString, -- group name
acsActiveSessionsTableType DisplayString, -- RO/RW-ssh,telnet or web
acsActiveSessionsTableConnection DisplayString, -- type + target name
acsActiveSessionsTableSessionTime DisplayString, -- time of session
acsActiveSessionsTableFrom DisplayString, -- source of the session
acsActiveSessionsTableKill INTEGER
}
acsActiveSessionsTableIndex OBJECT-TYPE
SYNTAX InterfaceIndexOrZero
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A unique index representing an entry in this table."
::= { acsActiveSessionsTableEntry 1 }
acsActiveSessionsTableUser OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The name of the user that opens this session."
::= { acsActiveSessionsTableEntry 2 }
acsActiveSessionsTableGroup OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The name of the group that the user belongs to."
::= { acsActiveSessionsTableEntry 3 }
acsActiveSessionsTableType OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The session type."
::= { acsActiveSessionsTableEntry 4 }
acsActiveSessionsTableConnection OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Connection type."
::= { acsActiveSessionsTableEntry 5 }
acsActiveSessionsTableSessionTime OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Time of the session"
::= { acsActiveSessionsTableEntry 6 }
acsActiveSessionsTableFrom OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The source IP address of the session."
::= { acsActiveSessionsTableEntry 7 }
acsActiveSessionsTableKill OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
killSession(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A set value of killSession(2) will kill the session.
noAction(1) = always returned in a GET. Does nothing if SET.
killSession(2)= when SET the appliance immediately kills the session."
::= { acsActiveSessionsTableEntry 8 }
--
-- acsSerialPort
-- OBJECT IDENTIFIER ::= { acsManagement 3 } 10418.26.2.3
--
acsSerialPortNumberOfPorts OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of Serial Ports (physical serial port plus Aux Port."
::= { acsSerialPort 1 }
acsSerialPortTable OBJECT-TYPE
SYNTAX SEQUENCE OF AcsSerialPortTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains information about serial ports."
::= { acsSerialPort 2 }
acsSerialPortTableEntry OBJECT-TYPE
SYNTAX AcsSerialPortTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"each entry has the information about specific serial port."
INDEX { acsSerialPortTableNumber }
::= { acsSerialPortTable 1 }
AcsSerialPortTableEntry ::= SEQUENCE {
acsSerialPortTableNumber Integer32, -- serial port number
acsSerialPortTableDeviceName DisplayString, -- associated device name
acsSerialPortTableStatus INTEGER, -- status of serial port
acsSerialPortTableName DisplayString, -- associated name
acsSerialPortTableProfile INTEGER, -- configured profile
acsSerialPortTablePinOut SerialPortPinOut, -- configure RJ45 pin-out
acsSerialPortTableComSpeed SerialPortSpeed, -- configured speed
acsSerialPortTableComParity INTEGER, -- configured parity
acsSerialPortTableComDataSize Integer32, -- configured data size
acsSerialPortTableComStopBits Integer32, -- configured stop bits
acsSerialPortTableComFlowControl INTEGER, -- configured flow control
acsSerialPortTableSignalStateDTR SerialPortSignalState, -- state of DTR RS-232C signal
acsSerialPortTableSignalStateDCD SerialPortSignalState, -- state of DCD RS-232C signal
acsSerialPortTableSignalStateRTS SerialPortSignalState, -- state of RTS RS-232C signal
acsSerialPortTableSignalStateCTS SerialPortSignalState, -- state of CTS RS-232C signal
acsSerialPortTableTxBytes Integer32, -- number of transmitted bytes
acsSerialPortTableRxBytes Integer32, -- number of received bytes
acsSerialPortTableFrameError Integer32, -- number of detected frame errors
acsSerialPortTableParityError Integer32, -- number of detected parity errors
acsSerialPortTableBreak Integer32, -- number of detected break
acsSerialPortTableOverrun Integer32, -- number of detected overrun errors
acsSerialPortTableResetCounters INTEGER, -- reset counters for all port statistics
acsSerialPortTableXcvrStatus SerialPortSignalState -- transceiver status
}
acsSerialPortTableNumber OBJECT-TYPE
SYNTAX Integer32 (1..49)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A unique index representing an entry in this table.
It is the number of the serial port. For AUX port,
the number will be the number of physical serial ports plus 1."
::= { acsSerialPortTableEntry 1 }
acsSerialPortTableDeviceName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..25))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The associated device name for the serial port."
::= { acsSerialPortTableEntry 2 }
acsSerialPortTableStatus OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
idle(2),
inUse(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The status of the serial port:
disabled(1) = it was configured as disable.
idle(2) = there is not any session opened in this port.
inUse(3) = there is session(s) opened in this port."
::= { acsSerialPortTableEntry 3 }
acsSerialPortTableName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..25))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Name associated with this serial port."
::= { acsSerialPortTableEntry 4 }
acsSerialPortTableProfile OBJECT-TYPE
SYNTAX INTEGER {
casProfile(1),
tsProfile(2),
dialInProfile(3),
powerProfile(4)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Configured profile for this serial port."
::= { acsSerialPortTableEntry 5 }
acsSerialPortTablePinOut OBJECT-TYPE
SYNTAX SerialPortPinOut
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"RJ45 Pin-out configured for this serial port."
::= { acsSerialPortTableEntry 6 }
acsSerialPortTableComSpeed OBJECT-TYPE
SYNTAX SerialPortSpeed
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Speed configured for this serial port."
::= { acsSerialPortTableEntry 7 }
acsSerialPortTableComParity OBJECT-TYPE
SYNTAX INTEGER {
none(1),
odd(2),
even(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Parity configured for this serial port."
::= { acsSerialPortTableEntry 8 }
acsSerialPortTableComDataSize OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Data Size configured for this serial port."
::= { acsSerialPortTableEntry 9 }
acsSerialPortTableComStopBits OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of Stop Bits configured for this serial port."
::= { acsSerialPortTableEntry 10 }
acsSerialPortTableComFlowControl OBJECT-TYPE
SYNTAX INTEGER {
none(1),
hardware(2),
software(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Flow Control configured for this serial port."
::= { acsSerialPortTableEntry 11 }
acsSerialPortTableSignalStateDTR OBJECT-TYPE
SYNTAX SerialPortSignalState
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"State of the DTR RS-232C signal."
::= { acsSerialPortTableEntry 12 }
acsSerialPortTableSignalStateDCD OBJECT-TYPE
SYNTAX SerialPortSignalState
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"State of the DCD RS-232C signal."
::= { acsSerialPortTableEntry 13 }
acsSerialPortTableSignalStateRTS OBJECT-TYPE
SYNTAX SerialPortSignalState
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"State of the RTS RS-232C signal."
::= { acsSerialPortTableEntry 14 }
acsSerialPortTableSignalStateCTS OBJECT-TYPE
SYNTAX SerialPortSignalState
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"State of the CTS RS-232C signal."
::= { acsSerialPortTableEntry 15 }
acsSerialPortTableTxBytes OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of transmited bytes by the serial port."
::= { acsSerialPortTableEntry 16 }
acsSerialPortTableRxBytes OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of received bytes by the serial port."
::= { acsSerialPortTableEntry 17 }
acsSerialPortTableFrameError OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of frame error detected in the serial port."
::= { acsSerialPortTableEntry 18 }
acsSerialPortTableParityError OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of parity error detected in the serial port."
::= { acsSerialPortTableEntry 19 }
acsSerialPortTableBreak OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of break detected in the serial port."
::= { acsSerialPortTableEntry 20 }
acsSerialPortTableOverrun OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of overrun error detected in the serial port."
::= { acsSerialPortTableEntry 21 }
acsSerialPortTableResetCounters OBJECT-TYPE
SYNTAX INTEGER {
no-action(1),
resetCounters(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Resets counters for all statistics for this serial port.
Resets the countes for TxBytes, RxBytes, frame errors,
parity errors, breaks, and overrun errors."
::= { acsSerialPortTableEntry 22 }
acsSerialPortTableXcvrStatus OBJECT-TYPE
SYNTAX SerialPortSignalState
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Activity status of the RS232 transceiver."
::= { acsSerialPortTableEntry 23 }
--
-- acsPowerMgmt
-- OBJECT IDENTIFIER ::= { acsManagement 5 } 10418.26.2.5
--
acsPowerMgmtNumSerialPorts OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of Serial Ports that has PDU connected on the appliance."
::= { acsPowerMgmt 1 }
acsPowerMgmtSerialTable OBJECT-TYPE
SYNTAX SEQUENCE OF AcsPowerMgmtSerialTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Information about each serial port thas has PDU connect."
::= { acsPowerMgmt 2 }
acsPowerMgmtSerialTableEntry OBJECT-TYPE
SYNTAX AcsPowerMgmtSerialTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Information about each serial port thas has PDU connect."
INDEX { acsPowerMgmtSerialTableIndex }
::= { acsPowerMgmtSerialTable 1 }
AcsPowerMgmtSerialTableEntry ::= SEQUENCE {
acsPowerMgmtSerialTableIndex InterfaceIndex,
acsPowerMgmtSerialTablePortNumber Integer32,
acsPowerMgmtSerialTableDeviceName DisplayString,
acsPowerMgmtSerialTableNumberPDUs Integer32,
acsPowerMgmtSerialTableNumberUPS Integer32
}
acsPowerMgmtSerialTableIndex OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The index of the register."
::= { acsPowerMgmtSerialTableEntry 1 }
acsPowerMgmtSerialTablePortNumber OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of the serial port when the PDU is connected."
::= { acsPowerMgmtSerialTableEntry 2 }
acsPowerMgmtSerialTableDeviceName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The device name of this serial port."
::= { acsPowerMgmtSerialTableEntry 3 }
acsPowerMgmtSerialTableNumberPDUs OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Total number of units connected in this serial port."
::= { acsPowerMgmtSerialTableEntry 4 }
acsPowerMgmtSerialTableNumberUPS OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Total number of UPS devices connected to this serial port."
::= { acsPowerMgmtSerialTableEntry 5 }
acsPowerMgmtPDUTable OBJECT-TYPE
SYNTAX SEQUENCE OF AcsPowerMgmtPDUTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains the list of detected PDUs."
::= { acsPowerMgmt 3 }
acsPowerMgmtPDUTableEntry OBJECT-TYPE
SYNTAX AcsPowerMgmtPDUTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"each entry has the information about the PDU."
INDEX { acsPowerMgmtPDUTablePortNumber, acsPowerMgmtPDUTablePduIndex }
::= { acsPowerMgmtPDUTable 1 }
AcsPowerMgmtPDUTableEntry ::= SEQUENCE {
acsPowerMgmtPDUTablePortNumber InterfaceIndex, -- number of serial port
acsPowerMgmtPDUTablePduIndex InterfaceIndexOrZero,
acsPowerMgmtPDUTablePduId DisplayString, -- PDU identification
acsPowerMgmtPDUTablePortName DisplayString, -- Serial Port Name
acsPowerMgmtPDUTableModel DisplayString, -- PDU model
acsPowerMgmtPDUTableVendor DisplayString, -- Vendor
acsPowerMgmtPDUTableFirmwareVersion DisplayString, -- Firmware Version
acsPowerMgmtPDUTableNumberOfOutlets Integer32,
acsPowerMgmtPDUTableCurrentNOS Integer32, -- OBSOLETED number of current sensors
acsPowerMgmtPDUTableCurrent1Value Integer32, -- OBSOLETED actual value for current of the sensor 1
acsPowerMgmtPDUTableCurrent1Max Integer32, -- OBSOLETED max value for current of the sensor 1
acsPowerMgmtPDUTableCurrent2Value Integer32, -- OBSOLETED actual value for current of the sensor 2
acsPowerMgmtPDUTableCurrent2Max Integer32, -- OBSOLETED max value for current of the sensor 2
acsPowerMgmtPDUTableCurrent3Value Integer32, -- OBSOLETED actual value for current of the sensor 3
acsPowerMgmtPDUTableCurrent3Max Integer32, -- OBSOLETED max value for current of the sensor 3
acsPowerMgmtPDUTableTemperatureNOS Integer32, -- OBSOLETED number of temperature sensors
acsPowerMgmtPDUTableTemperature1Value Integer32, -- OBSOLETED actual value for Temperature 1
acsPowerMgmtPDUTableTemperature1Max Integer32, -- OBSOLETED max value for Temperature 1
acsPowerMgmtPDUTableTemperature2Value Integer32, -- OBSOLETED actual value for Temperaturet 2
acsPowerMgmtPDUTableTemperature2Max Integer32, -- OBSOLETED max value for Temperature 2
acsPowerMgmtPDUTableTemperature3Value Integer32, -- OBSOLETED actual value for Temperature 3
acsPowerMgmtPDUTableTemperature3Max Integer32, -- OBSOLETED max value for Temperature 3
acsPowerMgmtPDUTableHumidityNOS Integer32, -- OBSOLETED humidity number of humidity sensors
acsPowerMgmtPDUTableHumidity1Value Integer32, -- OBSOLETED actual value for Humidity of the sensor 1
acsPowerMgmtPDUTableHumidity1Max Integer32, -- OBSOLETED max value for Humidityof the sensor 1
acsPowerMgmtPDUTableHumidity2Value Integer32, -- OBSOLETED actual value for Humidity of the sensor 2
acsPowerMgmtPDUTableHumidity2Max Integer32, -- OBSOLETED max value for Humidity of the sensor 2
acsPowerMgmtPDUTableHumidity3Value Integer32, -- OBSOLETED actual value for Humidity of the sensor 3
acsPowerMgmtPDUTableHumidity3Max Integer32, -- OBSOLETED max value for Humidity of the sensor 3
acsPowerMgmtPDUTableVoltageNOS Integer32, -- OBSOLETED number of voltage sensor
acsPowerMgmtPDUTableVoltage1Value Integer32, -- OBSOLETED actual value for Voltage of the sensor 1
acsPowerMgmtPDUTableVoltage1Max Integer32, -- OBSOLETED max value for Voltage of the sensor 1
acsPowerMgmtPDUTableVoltage2Value Integer32, -- OBSOLETED actual value for Voltage of the sensor 2
acsPowerMgmtPDUTableVoltage2Max Integer32, -- OBSOLETED max value for Voltaget of the sensor 2
acsPowerMgmtPDUTableVoltage3Value Integer32, -- OBSOLETED actual value for Voltage of the sensor 3
acsPowerMgmtPDUTableVoltage3Max Integer32, -- OBSOLETED max value for Voltage of the sensor 3
acsPowerMgmtPDUTableNumberOfPhases Integer32, -- number of phases (single or 3-phases)
acsPowerMgmtPDUTableNumberOfBanks Integer32, -- number of banks
acsPowerMgmtPDUTableCurrentValue Integer32, -- actual value of PDU current sensor
acsPowerMgmtPDUTableCurrentMax Integer32, -- max detected value of current sensor
acsPowerMgmtPDUTableCurrentMin Integer32, -- min detected value of current sensor
acsPowerMgmtPDUTableCurrentAvg Integer32, -- average value for current sensor
acsPowerMgmtPDUTableCurrentReset INTEGER, -- reset max, min and avg values
acsPowerMgmtPDUTableVoltageType INTEGER, -- type of PDU voltage
acsPowerMgmtPDUTableVoltageValue Integer32, -- actual value of PDU voltage
acsPowerMgmtPDUTableVoltageMax Integer32, -- max value of voltage sensor
acsPowerMgmtPDUTableVoltageMin Integer32, -- min value of voltage sensor
acsPowerMgmtPDUTableVoltageAvg Integer32, -- avg value of voltage sensor
acsPowerMgmtPDUTableVoltageReset INTEGER, -- reset max, min and avg values
acsPowerMgmtPDUTablePowerType INTEGER, -- type of PDU power consumption
acsPowerMgmtPDUTablePowerValue Integer32, -- actual value of PDU power consumption
acsPowerMgmtPDUTablePowerMax Integer32, -- max value
acsPowerMgmtPDUTablePowerMin Integer32, -- min value
acsPowerMgmtPDUTablePowerAvg Integer32, -- average value
acsPowerMgmtPDUTablePowerReset INTEGER, -- reset max, min and avg values
acsPowerMgmtPDUTablePowerFactorType INTEGER, -- type of PDU power factor
acsPowerMgmtPDUTablePowerFactorValue Integer32, -- actual value of PDU power factor
acsPowerMgmtPDUTablePowerFactorMax Integer32, -- max value for power factor
acsPowerMgmtPDUTablePowerFactorMin Integer32, -- min value for power factor
acsPowerMgmtPDUTablePowerFactorAvg Integer32, -- avg value for power factor
acsPowerMgmtPDUTablePowerFactorReset INTEGER, -- reset max, min and avg values
acsPowerMgmtPDUTableAlarm INTEGER, -- status of PDU alarm
acsPowerMgmtPDUTableEnvSensors Integer32, -- number of environmental sensors
acsPowerMgmtPDUTableAgentSerialNumber DisplayString, -- agent serial number
acsPowerMgmtPDUTablePduModelNumber DisplayString, -- PDU model number
acsPowerMgmtPDUTablePduSerialNumber DisplayString, -- PDU serial number
acsPowerMgmtPDUTablePduPartNumber DisplayString -- PDU part number
}
acsPowerMgmtPDUTablePortNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of serial port when the PDU is connected."
::= { acsPowerMgmtPDUTableEntry 1 }
acsPowerMgmtPDUTablePduIndex OBJECT-TYPE
SYNTAX InterfaceIndexOrZero
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A PDU position in the chain."
::= { acsPowerMgmtPDUTableEntry 2 }
acsPowerMgmtPDUTablePduId OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"PDU identification."
::= { acsPowerMgmtPDUTableEntry 3 }
acsPowerMgmtPDUTablePortName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Name of serial port when the PDU is connected."
::= { acsPowerMgmtPDUTableEntry 4 }
acsPowerMgmtPDUTableModel OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Model of the PDU."
::= { acsPowerMgmtPDUTableEntry 5 }
acsPowerMgmtPDUTableVendor OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Vendor of the PDU."
::= { acsPowerMgmtPDUTableEntry 6 }
acsPowerMgmtPDUTableFirmwareVersion OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Version of the PDU firmware."
::= { acsPowerMgmtPDUTableEntry 7 }
acsPowerMgmtPDUTableNumberOfOutlets OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of outlets of the PDU."
::= { acsPowerMgmtPDUTableEntry 8 }
acsPowerMgmtPDUTableCurrentNOS OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Number of current sensors in the PDU."
::= { acsPowerMgmtPDUTableEntry 9 }
acsPowerMgmtPDUTableCurrent1Value OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Current of the sensor 1 in this PDU unit in AMP.
The value of this object is the actual current in
AMP * 10. You need to translate the readed value
(Ex. : value is 5, the current is 0.5 AMP.)"
::= { acsPowerMgmtPDUTableEntry 10 }
acsPowerMgmtPDUTableCurrent1Max OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"Maximum current of the sensor 1 in this PDU unit in AMP.
When the PDU does not have support for maximum value,
the value will be 0.
The value of this object is the actual current in
AMP * 10. You need to translate the readed value
(Ex. : value is 5, the current is 0.5 AMP.)
Clear this value, set it with Zero value."
::= { acsPowerMgmtPDUTableEntry 11 }
acsPowerMgmtPDUTableCurrent2Value OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Current of the sensor 2 in this PDU unit in AMP.
The value of this object is the actual current in
AMP * 10. You need to translate the readed value
(Ex. : value is 5, the current is 0.5 AMP.)"
::= { acsPowerMgmtPDUTableEntry 12 }
acsPowerMgmtPDUTableCurrent2Max OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"Maximum current of the sensor 2 in this PDU unit in AMP.
When the PDU does not have support for maximum value,
the value will be 0.
The value of this object is the actual current in
AMP * 10. You need to translate the readed value
(Ex. : value is 5, the current is 0.5 AMP.)
Clear this value, set it with Zero value."
::= { acsPowerMgmtPDUTableEntry 13}
acsPowerMgmtPDUTableCurrent3Value OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Current of the sensor 3 in this PDU unit in AMP.
The value of this object is the actual current in
AMP * 10. You need to translate the readed value
(Ex. : value is 5, the current is 0.5 AMP.)"
::= { acsPowerMgmtPDUTableEntry 14 }
acsPowerMgmtPDUTableCurrent3Max OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"Maximum current of the sensor 3 in this PDU unit in AMP.
When the PDU does not have support for maximum value,
the value will be 0.
The value of this object is the actual current in
AMP * 10. You need to translate the readed value
(Ex. : value is 5, the current is 0.5 AMP.)
Clear this value, set it with Zero value."
::= { acsPowerMgmtPDUTableEntry 15 }
acsPowerMgmtPDUTableTemperatureNOS OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Number of temperature sensors in the PDU."
::= { acsPowerMgmtPDUTableEntry 16 }
acsPowerMgmtPDUTableTemperature1Value OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Temperature of this PM unit in Celsius degrees.
The value of this object is the actual temperature in
degrees C * 10. You need to translate the readed value
(Ex. : value is 240, the temperature is 24 Celsius.)
If the temperature measurement is not installed this
value will be 0.
Valid values are 5 to 999 ( 0.5 to 99.9 Celsius)."
::= { acsPowerMgmtPDUTableEntry 17 }
acsPowerMgmtPDUTableTemperature1Max OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"Maximum temperature detected in this PM unit in Celsius degrees.
The value will be Zero when the PDU does not have support for maximum value.
The value of this object is the actual temperature in
degrees C * 10. You need to translate the readed value
(Ex. : value is 240, the temperature is 24 Celsius.)
If the temperature measurement is not installed this
value will be 0.
Valid values are 5 to 999 ( 0.5 to 99.9 Celsius).
Set with Zero value to clear the max. temperature."
::= { acsPowerMgmtPDUTableEntry 18 }
acsPowerMgmtPDUTableTemperature2Value OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Temperature of this PM unit in Celsius degrees.
The value of this object is the actual temperature in
degrees C * 10. You need to translate the readed value
(Ex. : value is 240, the temperature is 24 Celsius.)
If the temperature measurement is not installed this
value will be 0.
Valid values are 5 to 999 ( 0.5 to 99.9 Celsius)."
::= { acsPowerMgmtPDUTableEntry 19 }
acsPowerMgmtPDUTableTemperature2Max OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"Maximum temperature detected in this PM unit in Celsius degrees.
The value will be Zero when the PDU does not have support for maximum value.
The value of this object is the actual temperature in
degrees C * 10. You need to translate the readed value
(Ex. : value is 240, the temperature is 24 Celsius.)
If the temperature measurement is not installed this
value will be 0.
Valid values are 5 to 999 ( 0.5 to 99.9 Celsius).
Set with Zero value to clear the max. temperature."
::= { acsPowerMgmtPDUTableEntry 20 }
acsPowerMgmtPDUTableTemperature3Value OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Temperature of this PM unit in Celsius degrees.
The value of this object is the actual temperature in
degrees C * 10. You need to translate the readed value
(Ex. : value is 240, the temperature is 24 Celsius.)
If the temperature measurement is not installed this
value will be 0.
Valid values are 5 to 999 ( 0.5 to 99.9 Celsius)."
::= { acsPowerMgmtPDUTableEntry 21 }
acsPowerMgmtPDUTableTemperature3Max OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"Maximum temperature detected in this PM unit in Celsius degrees.
The value will be Zero when the PDU does not have support for maximum value.
The value of this object is the actual temperature in
degrees C * 10. You need to translate the readed value
(Ex. : value is 240, the temperature is 24 Celsius.)
If the temperature measurement is not installed this
value will be 0.
Valid values are 5 to 999 ( 0.5 to 99.9 Celsius).
Set with Zero value to clear the max. temperature."
::= { acsPowerMgmtPDUTableEntry 22 }
acsPowerMgmtPDUTableHumidityNOS OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Number of humidity sensors in the PDU."
::= { acsPowerMgmtPDUTableEntry 23 }
acsPowerMgmtPDUTableHumidity1Value OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Humidity of this PM unit .
If the humidity measurement is not installed this
value will be 0."
::= { acsPowerMgmtPDUTableEntry 24 }
acsPowerMgmtPDUTableHumidity1Max OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"Maximum humidity detected in this PM unit.
If the humidity measurement is not installed or the PDU does not have support for maximum value this
value will be 0.
Set with Zero value to clear the max. temperature."
::= { acsPowerMgmtPDUTableEntry 25 }
acsPowerMgmtPDUTableHumidity2Value OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Humidity of this PM unit .
If the humidity measurement is not installed this
value will be 0."
::= { acsPowerMgmtPDUTableEntry 26 }
acsPowerMgmtPDUTableHumidity2Max OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"Maximum humidity detected in this PM unit.
If the humidity measurement is not installed or the PDU does not have support for maximum value this
value will be 0.
Set with Zero value to clear the max. temperature."
::= { acsPowerMgmtPDUTableEntry 27 }
acsPowerMgmtPDUTableHumidity3Value OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Humidity of this PM unit .
If the humidity measurement is not installed this
value will be 0."
::= { acsPowerMgmtPDUTableEntry 28 }
acsPowerMgmtPDUTableHumidity3Max OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"Maximum humidity detected in this PM unit.
If the humidity measurement is not installed or the PDU does not have support for maximum value this
value will be 0.
Set with Zero value to clear the max. temperature."
::= { acsPowerMgmtPDUTableEntry 29 }
acsPowerMgmtPDUTableVoltageNOS OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Number of voltage sensors in the PDU."
::= { acsPowerMgmtPDUTableEntry 30 }
acsPowerMgmtPDUTableVoltage1Value OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Voltage of this sensor in this PDU unit."
::= { acsPowerMgmtPDUTableEntry 31 }
acsPowerMgmtPDUTableVoltage1Max OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"Maximum voltage of this sensor in this PDU unit.
Set with Zero value to clear the maximum voltage."
::= { acsPowerMgmtPDUTableEntry 32 }
acsPowerMgmtPDUTableVoltage2Value OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Voltage of this sensor in this PDU unit."
::= { acsPowerMgmtPDUTableEntry 33 }
acsPowerMgmtPDUTableVoltage2Max OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"Maximum voltage of this sensor in this PDU unit.
Set with Zero value to clear the maximum voltage."
::= { acsPowerMgmtPDUTableEntry 34 }
acsPowerMgmtPDUTableVoltage3Value OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Voltage of this sensor in this PDU unit."
::= { acsPowerMgmtPDUTableEntry 35 }
acsPowerMgmtPDUTableVoltage3Max OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"Maximum voltage of this sensor in this PDU unit.
Set with Zero value to clear the maximum voltage."
::= { acsPowerMgmtPDUTableEntry 36 }
acsPowerMgmtPDUTableNumberOfPhases OBJECT-TYPE
SYNTAX INTEGER {
single-phase (0),
three-phase (3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of phases of this PDU unit."
::= { acsPowerMgmtPDUTableEntry 37 }
acsPowerMgmtPDUTableNumberOfBanks OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of banks of this PDU unit."
::= { acsPowerMgmtPDUTableEntry 38 }
acsPowerMgmtPDUTableCurrentValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of current sensor in this PDU.( A x 10 )"
::= { acsPowerMgmtPDUTableEntry 39 }
acsPowerMgmtPDUTableCurrentMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Max detected value of current sensor in this PDU.( A x 10 )"
::= { acsPowerMgmtPDUTableEntry 40 }
acsPowerMgmtPDUTableCurrentMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Min detected value of current sensor in this PDU.( A x 10 )"
::= { acsPowerMgmtPDUTableEntry 41 }
acsPowerMgmtPDUTableCurrentAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value for current sensor in this PDU.( A x 10 )"
::= { acsPowerMgmtPDUTableEntry 42 }
acsPowerMgmtPDUTableCurrentReset OBJECT-TYPE
SYNTAX INTEGER {
no-action (1),
reset (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Reset max, min and avg values of current."
::= { acsPowerMgmtPDUTableEntry 43 }
acsPowerMgmtPDUTableVoltageType OBJECT-TYPE
SYNTAX INTEGER {
none-sensor (0),
estimated (1),
read (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of voltage values."
::= { acsPowerMgmtPDUTableEntry 44 }
acsPowerMgmtPDUTableVoltageValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of voltage sensor in this PDU unit.( V )"
::= { acsPowerMgmtPDUTableEntry 45 }
acsPowerMgmtPDUTableVoltageMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Max detected value of voltage sensor in this PDU unit.( V )"
::= { acsPowerMgmtPDUTableEntry 46 }
acsPowerMgmtPDUTableVoltageMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Min detected value of voltage sensor in this PDU unit.( V )"
::= { acsPowerMgmtPDUTableEntry 47 }
acsPowerMgmtPDUTableVoltageAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value for voltage sensor in this PDU unit.( V )"
::= { acsPowerMgmtPDUTableEntry 48 }
acsPowerMgmtPDUTableVoltageReset OBJECT-TYPE
SYNTAX INTEGER {
no-action (1),
reset (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Reset max, min and avg values of voltage."
::= { acsPowerMgmtPDUTableEntry 49 }
acsPowerMgmtPDUTablePowerType OBJECT-TYPE
SYNTAX INTEGER {
none-sensor (0),
estimated (1),
read (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of power consumption values.( W x 10 )"
::= { acsPowerMgmtPDUTableEntry 50 }
acsPowerMgmtPDUTablePowerValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of power consumption in this PDU unit.( W x 10 )"
::= { acsPowerMgmtPDUTableEntry 51 }
acsPowerMgmtPDUTablePowerMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Max detected value of power consumption in this PDU unit.( W x 10 )"
::= { acsPowerMgmtPDUTableEntry 52 }
acsPowerMgmtPDUTablePowerMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Min detected value of power consumption in this PDU unit.( W x 10 )"
::= { acsPowerMgmtPDUTableEntry 53 }
acsPowerMgmtPDUTablePowerAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value for power consumption in this PDU unit.( W x 10 )"
::= { acsPowerMgmtPDUTableEntry 54 }
acsPowerMgmtPDUTablePowerReset OBJECT-TYPE
SYNTAX INTEGER {
no-action (1),
reset (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Reset max, min and avg values of power consumption."
::= { acsPowerMgmtPDUTableEntry 55 }
acsPowerMgmtPDUTablePowerFactorType OBJECT-TYPE
SYNTAX INTEGER {
none-sensor (0),
estimated (1),
read (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of power factor values."
::= { acsPowerMgmtPDUTableEntry 56 }
acsPowerMgmtPDUTablePowerFactorValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of power factor in this PDU unit.( PF x 100 )"
::= { acsPowerMgmtPDUTableEntry 57 }
acsPowerMgmtPDUTablePowerFactorMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Max detected value of power factor in this PDU unit.( PF x 100 )"
::= { acsPowerMgmtPDUTableEntry 58 }
acsPowerMgmtPDUTablePowerFactorMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Min detected value of power factor in this PDU unit.( PF x 100 )"
::= { acsPowerMgmtPDUTableEntry 59 }
acsPowerMgmtPDUTablePowerFactorAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value for power factor in this PDU unit.( PF x 100 )"
::= { acsPowerMgmtPDUTableEntry 60 }
acsPowerMgmtPDUTablePowerFactorReset OBJECT-TYPE
SYNTAX INTEGER {
no-action (1),
reset (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Reset max, min and avg values of power factor."
::= { acsPowerMgmtPDUTableEntry 61 }
acsPowerMgmtPDUTableAlarm OBJECT-TYPE
SYNTAX INTEGER {
normal (1),
blow-fuse (2),
hw-ocp (3),
high-critical (4),
high-warning (5),
low-warning (6),
low-critical (7)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Show the PDU alarm status."
::= { acsPowerMgmtPDUTableEntry 62 }
acsPowerMgmtPDUTableEnvSensors OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of environmental sensor in this PDU."
::= { acsPowerMgmtPDUTableEntry 63 }
acsPowerMgmtPDUTableAgentSerialNumber OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial number of the agent."
::= { acsPowerMgmtPDUTableEntry 64 }
acsPowerMgmtPDUTablePduModelNumber OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Model number of the PDU."
::= { acsPowerMgmtPDUTableEntry 65 }
acsPowerMgmtPDUTablePduSerialNumber OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial number of the PDU."
::= { acsPowerMgmtPDUTableEntry 66 }
acsPowerMgmtPDUTablePduPartNumber OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Part number of the PDU."
::= { acsPowerMgmtPDUTableEntry 67 }
acsPowerMgmtTotalNumberOfOutlets OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of outlets managed by the appliance."
::= { acsPowerMgmt 4 }
acsPowerMgmtOutletsTable OBJECT-TYPE
SYNTAX SEQUENCE OF AcsPowerMgmtOutletsTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains the information about outlets."
::= { acsPowerMgmt 5 }
acsPowerMgmtOutletsTableEntry OBJECT-TYPE
SYNTAX AcsPowerMgmtOutletsTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"each entry has the information about the outlet."
INDEX { acsPowerMgmtOutletsTablePortNumber,
acsPowerMgmtOutletsTablePduNumber,
acsPowerMgmtOutletsTableNumber }
::= { acsPowerMgmtOutletsTable 1 }
AcsPowerMgmtOutletsTableEntry ::= SEQUENCE {
acsPowerMgmtOutletsTablePortNumber InterfaceIndex, -- serial port #
acsPowerMgmtOutletsTablePduNumber InterfaceIndex,
acsPowerMgmtOutletsTableNumber InterfaceIndex, -- outlet number in PDU
acsPowerMgmtOutletsTableName DisplayString, -- outlet name
acsPowerMgmtOutletsTableStatus INTEGER, -- outlet status
acsPowerMgmtOutletsTablePowerControl INTEGER, -- manage the outlet
acsPowerMgmtOutletsTablePortName DisplayString, -- serial port name
acsPowerMgmtOutletsTablePduId DisplayString -- PDU ID
}
acsPowerMgmtOutletsTablePortNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial Port number."
::= { acsPowerMgmtOutletsTableEntry 1 }
acsPowerMgmtOutletsTablePduNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Index."
::= { acsPowerMgmtOutletsTableEntry 2 }
acsPowerMgmtOutletsTableNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of the outlet in the PDU."
::= { acsPowerMgmtOutletsTableEntry 3 }
acsPowerMgmtOutletsTableName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Name of the outlet."
::= { acsPowerMgmtOutletsTableEntry 4 }
acsPowerMgmtOutletsTableStatus OBJECT-TYPE
SYNTAX INTEGER {
off(1),
on(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status of the outlet."
::= { acsPowerMgmtOutletsTableEntry 5 }
acsPowerMgmtOutletsTablePowerControl OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
powerOn(2),
powerOff(3),
powerCycle(4),
powerLock(5),
powerUnlock(6)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A set value of power*(2-6) will send command to PDU.
noAction(1) = always returned in a GET. Does nothing if SET.
powerOn(2) = when SET the power On command is sent to PDU.
powerOff(3) = when SET the power Off command is sent to PDU.
powerCycle(4)=when SET the power cycle command is sent to PDU.
powerLock(5)= when SET the power lock command is sent to PDU.
powerUnlock(6)=when SET the power unlock command is sent to PDU.
The powerLock and powerUnlock are valid only for Cyclades-PM PDUs"
::= { acsPowerMgmtOutletsTableEntry 6 }
acsPowerMgmtOutletsTablePortName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial Port Name where the PDU is connected."
::= { acsPowerMgmtOutletsTableEntry 7 }
acsPowerMgmtOutletsTablePduId OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"PDU identification."
::= { acsPowerMgmtOutletsTableEntry 8 }
acsPowerMgmtNumberOfOutletGroup OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of configured group of outlets."
::= { acsPowerMgmt 6 }
acsPowerMgmtGroupTable OBJECT-TYPE
SYNTAX SEQUENCE OF AcsPowerMgmtGroupTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains the information about group of outlets."
::= { acsPowerMgmt 7 }
acsPowerMgmtGroupTableEntry OBJECT-TYPE
SYNTAX AcsPowerMgmtGroupTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"each entry has the information about group of outlets."
INDEX { acsPowerMgmtGroupTableIndex }
::= { acsPowerMgmtGroupTable 1 }
AcsPowerMgmtGroupTableEntry ::= SEQUENCE {
acsPowerMgmtGroupTableIndex InterfaceIndexOrZero,
acsPowerMgmtGroupTableName DisplayString, -- group name
acsPowerMgmtGroupTableStatus INTEGER, -- group status
acsPowerMgmtGroupTablePowerControl INTEGER -- manage the group
}
acsPowerMgmtGroupTableIndex OBJECT-TYPE
SYNTAX InterfaceIndexOrZero
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Index of the group."
::= { acsPowerMgmtGroupTableEntry 1 }
acsPowerMgmtGroupTableName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Name of the group of outlets."
::= { acsPowerMgmtGroupTableEntry 2 }
acsPowerMgmtGroupTableStatus OBJECT-TYPE
SYNTAX INTEGER {
off(1),
on(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status of the group of outlet."
::= { acsPowerMgmtGroupTableEntry 3 }
acsPowerMgmtGroupTablePowerControl OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
powerOn(2),
powerOff(3),
powerCycle(4)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A set value of power*(2-6) will send command to PDU.
noAction(1) = always returned in a GET. Does nothing if SET.
powerOn(2) = when SET the power On command is sent to PDU.
powerOff(3) = when SET the power Off command is sent to PDU.
powerCycle(4)=when SET the power cycle command is sent to PDU."
::= { acsPowerMgmtGroupTableEntry 4 }
acsPowerMgmtPhasesTable OBJECT-TYPE
SYNTAX SEQUENCE OF AcsPowerMgmtPhasesTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains data monitoring of each detected phase."
::= { acsPowerMgmt 8 }
acsPowerMgmtPhasesTableEntry OBJECT-TYPE
SYNTAX AcsPowerMgmtPhasesTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"each entry has the data monitoring about phases."
INDEX { acsPowerMgmtPhasesTablePortNumber, acsPowerMgmtPhasesTablePduIndex, acsPowerMgmtPhasesTablePhaseIndex }
::= { acsPowerMgmtPhasesTable 1 }
AcsPowerMgmtPhasesTableEntry ::= SEQUENCE {
acsPowerMgmtPhasesTablePortNumber InterfaceIndex, -- number of serial port
acsPowerMgmtPhasesTablePduIndex InterfaceIndexOrZero, -- number of PDU
acsPowerMgmtPhasesTablePhaseIndex InterfaceIndexOrZero, -- phase index
acsPowerMgmtPhasesTablePhaseName DisplayString, -- Phase Name
acsPowerMgmtPhasesTablePduId DisplayString, -- PDU identification
acsPowerMgmtPhasesTablePortName DisplayString, -- Serial Port Name
acsPowerMgmtPhasesTableCurrentValue Integer32, -- actual value of Phase current sensor
acsPowerMgmtPhasesTableCurrentMax Integer32, -- max detected value of current sensor
acsPowerMgmtPhasesTableCurrentMin Integer32, -- min detected value of current sensor
acsPowerMgmtPhasesTableCurrentAvg Integer32, -- average value for current sensor
acsPowerMgmtPhasesTableCurrentReset INTEGER, -- reset max, min and avg values
acsPowerMgmtPhasesTableVoltageType INTEGER, -- type of phase voltage
acsPowerMgmtPhasesTableVoltageValue Integer32, -- actual value of phase voltage
acsPowerMgmtPhasesTableVoltageMax Integer32, -- max value of voltage sensor
acsPowerMgmtPhasesTableVoltageMin Integer32, -- min value of voltage sensor
acsPowerMgmtPhasesTableVoltageAvg Integer32, -- avg value of voltage sensor
acsPowerMgmtPhasesTableVoltageReset INTEGER, -- reset max, min and avg values
acsPowerMgmtPhasesTablePowerType INTEGER, -- type of phase power consumption
acsPowerMgmtPhasesTablePowerValue Integer32, -- actual value of phase power consumption
acsPowerMgmtPhasesTablePowerMax Integer32, -- max value
acsPowerMgmtPhasesTablePowerMin Integer32, -- min value
acsPowerMgmtPhasesTablePowerAvg Integer32, -- average value
acsPowerMgmtPhasesTablePowerReset INTEGER, -- reset max, min and avg values
acsPowerMgmtPhasesTablePowerFactorType INTEGER, -- type of phase power factor
acsPowerMgmtPhasesTablePowerFactorValue Integer32, -- actual value of phase power factor
acsPowerMgmtPhasesTablePowerFactorMax Integer32, -- max value for power factor
acsPowerMgmtPhasesTablePowerFactorMin Integer32, -- min value for power factor
acsPowerMgmtPhasesTablePowerFactorAvg Integer32, -- avg value for power factor
acsPowerMgmtPhasesTablePowerFactorReset INTEGER, -- reset max, min and avg values
acsPowerMgmtPhasesTableAlarm INTEGER -- phase alarm status
}
acsPowerMgmtPhasesTablePortNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of serial port when the PDU is connected."
::= { acsPowerMgmtPhasesTableEntry 1 }
acsPowerMgmtPhasesTablePduIndex OBJECT-TYPE
SYNTAX InterfaceIndexOrZero
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A PDU position in the chain."
::= { acsPowerMgmtPhasesTableEntry 2 }
acsPowerMgmtPhasesTablePhaseIndex OBJECT-TYPE
SYNTAX InterfaceIndexOrZero
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"phase index in the PDU."
::= { acsPowerMgmtPhasesTableEntry 3 }
acsPowerMgmtPhasesTablePhaseName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"phase name in the PDU."
::= { acsPowerMgmtPhasesTableEntry 4 }
acsPowerMgmtPhasesTablePduId OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"PDU identification."
::= { acsPowerMgmtPhasesTableEntry 5 }
acsPowerMgmtPhasesTablePortName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Name of serial port when the PDU is connected."
::= { acsPowerMgmtPhasesTableEntry 6 }
acsPowerMgmtPhasesTableCurrentValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of current sensor in this phase.( A x 10 )"
::= { acsPowerMgmtPhasesTableEntry 7 }
acsPowerMgmtPhasesTableCurrentMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Max detected value of current sensor in this phase.( A x 10 )"
::= { acsPowerMgmtPhasesTableEntry 8 }
acsPowerMgmtPhasesTableCurrentMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Min detected value of current sensor in this phase.( A x 10 )"
::= { acsPowerMgmtPhasesTableEntry 9 }
acsPowerMgmtPhasesTableCurrentAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value for current sensor in this phase.( A x 10 )"
::= { acsPowerMgmtPhasesTableEntry 10 }
acsPowerMgmtPhasesTableCurrentReset OBJECT-TYPE
SYNTAX INTEGER {
no-action (1),
reset (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Reset max, min and avg values of current."
::= { acsPowerMgmtPhasesTableEntry 11 }
acsPowerMgmtPhasesTableVoltageType OBJECT-TYPE
SYNTAX INTEGER {
none-sensor (0),
estimated (1),
read (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of voltage values."
::= { acsPowerMgmtPhasesTableEntry 12 }
acsPowerMgmtPhasesTableVoltageValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of voltage sensor in this phase.( V )"
::= { acsPowerMgmtPhasesTableEntry 13 }
acsPowerMgmtPhasesTableVoltageMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Max detected value of voltage sensor in this phase.( V )"
::= { acsPowerMgmtPhasesTableEntry 14 }
acsPowerMgmtPhasesTableVoltageMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Min detected value of voltage sensor in this phase.( V )"
::= { acsPowerMgmtPhasesTableEntry 15 }
acsPowerMgmtPhasesTableVoltageAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value for voltage sensor in this phase.( V )"
::= { acsPowerMgmtPhasesTableEntry 16 }
acsPowerMgmtPhasesTableVoltageReset OBJECT-TYPE
SYNTAX INTEGER {
no-action (1),
reset (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Reset max, min and avg values of voltage."
::= { acsPowerMgmtPhasesTableEntry 17 }
acsPowerMgmtPhasesTablePowerType OBJECT-TYPE
SYNTAX INTEGER {
none-sensor (0),
estimated (1),
read (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of power consumption values."
::= { acsPowerMgmtPhasesTableEntry 18 }
acsPowerMgmtPhasesTablePowerValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of power consumption in this phase.( W x 10 )"
::= { acsPowerMgmtPhasesTableEntry 19 }
acsPowerMgmtPhasesTablePowerMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Max detected value of power consumption in this phase.( W x 10 )"
::= { acsPowerMgmtPhasesTableEntry 20 }
acsPowerMgmtPhasesTablePowerMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Min detected value of power consumption in this phase.( W x 10 )"
::= { acsPowerMgmtPhasesTableEntry 21 }
acsPowerMgmtPhasesTablePowerAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value for power consumption in this phase.( W x 10 )"
::= { acsPowerMgmtPhasesTableEntry 22 }
acsPowerMgmtPhasesTablePowerReset OBJECT-TYPE
SYNTAX INTEGER {
no-action (1),
reset (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Reset max, min and avg values of power consumption."
::= { acsPowerMgmtPhasesTableEntry 23 }
acsPowerMgmtPhasesTablePowerFactorType OBJECT-TYPE
SYNTAX INTEGER {
none-sensor (0),
estimated (1),
read (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of power factor values."
::= { acsPowerMgmtPhasesTableEntry 24 }
acsPowerMgmtPhasesTablePowerFactorValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of power factor in this phase.( PF x 100 )"
::= { acsPowerMgmtPhasesTableEntry 25 }
acsPowerMgmtPhasesTablePowerFactorMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Max detected value of power factor in this phase.( PF x 100 )"
::= { acsPowerMgmtPhasesTableEntry 26 }
acsPowerMgmtPhasesTablePowerFactorMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Min detected value of power factor in this phase.( PF x 100 )"
::= { acsPowerMgmtPhasesTableEntry 27 }
acsPowerMgmtPhasesTablePowerFactorAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value for power factor in this phase.( PF x 100 )"
::= { acsPowerMgmtPhasesTableEntry 28 }
acsPowerMgmtPhasesTablePowerFactorReset OBJECT-TYPE
SYNTAX INTEGER {
no-action (1),
reset (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Reset max, min and avg values of power factor."
::= { acsPowerMgmtPhasesTableEntry 29 }
acsPowerMgmtPhasesTableAlarm OBJECT-TYPE
SYNTAX INTEGER {
normal (1),
blow-fuse (2),
hw-ocp (3),
high-critical (4),
high-warning (5),
low-warning (6),
low-critical (7)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Show the phase alarm status."
::= { acsPowerMgmtPhasesTableEntry 30 }
acsPowerMgmtBanksTable OBJECT-TYPE
SYNTAX SEQUENCE OF AcsPowerMgmtBanksTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains data monitoring of each detected bank."
::= { acsPowerMgmt 9 }
acsPowerMgmtBanksTableEntry OBJECT-TYPE
SYNTAX AcsPowerMgmtBanksTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"each entry has the data monitoring about bank."
INDEX { acsPowerMgmtBanksTablePortNumber, acsPowerMgmtBanksTablePduIndex, acsPowerMgmtBanksTableBankIndex }
::= { acsPowerMgmtBanksTable 1 }
AcsPowerMgmtBanksTableEntry ::= SEQUENCE {
acsPowerMgmtBanksTablePortNumber InterfaceIndex, -- number of serial port
acsPowerMgmtBanksTablePduIndex InterfaceIndexOrZero, -- number of PDU
acsPowerMgmtBanksTableBankIndex InterfaceIndexOrZero, -- bank index
acsPowerMgmtBanksTableBankName DisplayString, -- Bank Name
acsPowerMgmtBanksTablePduId DisplayString, -- PDU identification
acsPowerMgmtBanksTablePortName DisplayString, -- Serial Port Name
acsPowerMgmtBanksTableCurrentValue Integer32, -- actual value of bank current sensor
acsPowerMgmtBanksTableCurrentMax Integer32, -- max detected value of current sensor
acsPowerMgmtBanksTableCurrentMin Integer32, -- min detected value of current sensor
acsPowerMgmtBanksTableCurrentAvg Integer32, -- average value for current sensor
acsPowerMgmtBanksTableCurrentReset INTEGER, -- reset max, min and avg values
acsPowerMgmtBanksTableVoltageType INTEGER, -- type of bank voltage
acsPowerMgmtBanksTableVoltageValue Integer32, -- actual value of bank voltage
acsPowerMgmtBanksTableVoltageMax Integer32, -- max value of voltage sensor
acsPowerMgmtBanksTableVoltageMin Integer32, -- min value of voltage sensor
acsPowerMgmtBanksTableVoltageAvg Integer32, -- avg value of voltage sensor
acsPowerMgmtBanksTableVoltageReset INTEGER, -- reset max, min and avg values
acsPowerMgmtBanksTablePowerType INTEGER, -- type of bank power consumption
acsPowerMgmtBanksTablePowerValue Integer32, -- actual value of bank power consumption
acsPowerMgmtBanksTablePowerMax Integer32, -- max value
acsPowerMgmtBanksTablePowerMin Integer32, -- min value
acsPowerMgmtBanksTablePowerAvg Integer32, -- average value
acsPowerMgmtBanksTablePowerReset INTEGER, -- reset max, min and avg values
acsPowerMgmtBanksTablePowerFactorType INTEGER, -- type of bank power factor
acsPowerMgmtBanksTablePowerFactorValue Integer32, -- actual value of bank power factor
acsPowerMgmtBanksTablePowerFactorMax Integer32, -- max value for power factor
acsPowerMgmtBanksTablePowerFactorMin Integer32, -- min value for power factor
acsPowerMgmtBanksTablePowerFactorAvg Integer32, -- avg value for power factor
acsPowerMgmtBanksTablePowerFactorReset INTEGER, -- reset max, min and avg values
acsPowerMgmtBanksTableAlarm INTEGER -- status of bank alarm
}
acsPowerMgmtBanksTablePortNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of serial port when the PDU is connected."
::= { acsPowerMgmtBanksTableEntry 1 }
acsPowerMgmtBanksTablePduIndex OBJECT-TYPE
SYNTAX InterfaceIndexOrZero
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A PDU position in the chain."
::= { acsPowerMgmtBanksTableEntry 2 }
acsPowerMgmtBanksTableBankIndex OBJECT-TYPE
SYNTAX InterfaceIndexOrZero
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Bank index in the PDU."
::= { acsPowerMgmtBanksTableEntry 3 }
acsPowerMgmtBanksTableBankName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Bank name in the PDU."
::= { acsPowerMgmtBanksTableEntry 4 }
acsPowerMgmtBanksTablePduId OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"PDU identification."
::= { acsPowerMgmtBanksTableEntry 5 }
acsPowerMgmtBanksTablePortName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Name of serial port when the PDU is connected."
::= { acsPowerMgmtBanksTableEntry 6 }
acsPowerMgmtBanksTableCurrentValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of current sensor in this bank.( A x 10 )"
::= { acsPowerMgmtBanksTableEntry 7 }
acsPowerMgmtBanksTableCurrentMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Max detected value of current sensor in this bank.( A x 10 )"
::= { acsPowerMgmtBanksTableEntry 8 }
acsPowerMgmtBanksTableCurrentMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Min detected value of current sensor in this bank.( A x 10 )"
::= { acsPowerMgmtBanksTableEntry 9 }
acsPowerMgmtBanksTableCurrentAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value for current sensor in this bank.( A x 10 )"
::= { acsPowerMgmtBanksTableEntry 10 }
acsPowerMgmtBanksTableCurrentReset OBJECT-TYPE
SYNTAX INTEGER {
no-action (1),
reset (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Reset max, min and avg values of current."
::= { acsPowerMgmtBanksTableEntry 11 }
acsPowerMgmtBanksTableVoltageType OBJECT-TYPE
SYNTAX INTEGER {
none-sensor (0),
estimated (1),
read (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of voltage values."
::= { acsPowerMgmtBanksTableEntry 12 }
acsPowerMgmtBanksTableVoltageValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of voltage sensor in this bank.( V )"
::= { acsPowerMgmtBanksTableEntry 13 }
acsPowerMgmtBanksTableVoltageMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Max detected value of voltage sensor in this bank.( V )"
::= { acsPowerMgmtBanksTableEntry 14 }
acsPowerMgmtBanksTableVoltageMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Min detected value of voltage sensor in this bank.( V )"
::= { acsPowerMgmtBanksTableEntry 15 }
acsPowerMgmtBanksTableVoltageAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value for voltage sensor in this bank.( V )"
::= { acsPowerMgmtBanksTableEntry 16 }
acsPowerMgmtBanksTableVoltageReset OBJECT-TYPE
SYNTAX INTEGER {
no-action (1),
reset (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Reset max, min and avg values of voltage."
::= { acsPowerMgmtBanksTableEntry 17 }
acsPowerMgmtBanksTablePowerType OBJECT-TYPE
SYNTAX INTEGER {
none-sensor (0),
estimated (1),
read (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of power consumption values."
::= { acsPowerMgmtBanksTableEntry 18 }
acsPowerMgmtBanksTablePowerValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of power consumption in this bank.( W x 10 )"
::= { acsPowerMgmtBanksTableEntry 19 }
acsPowerMgmtBanksTablePowerMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Max detected value of power consumption in this bank.( W x 10 )"
::= { acsPowerMgmtBanksTableEntry 20 }
acsPowerMgmtBanksTablePowerMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Min detected value of power consumption in this bank.( W x 10 )"
::= { acsPowerMgmtBanksTableEntry 21 }
acsPowerMgmtBanksTablePowerAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value for power consumption in this bank.( W x 10 )"
::= { acsPowerMgmtBanksTableEntry 22 }
acsPowerMgmtBanksTablePowerReset OBJECT-TYPE
SYNTAX INTEGER {
no-action (1),
reset (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Reset max, min and avg values of power consumption."
::= { acsPowerMgmtBanksTableEntry 23 }
acsPowerMgmtBanksTablePowerFactorType OBJECT-TYPE
SYNTAX INTEGER {
none-sensor (0),
estimated (1),
read (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of power factor values."
::= { acsPowerMgmtBanksTableEntry 24 }
acsPowerMgmtBanksTablePowerFactorValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of power factor in this bank.( PF x 100 )"
::= { acsPowerMgmtBanksTableEntry 25 }
acsPowerMgmtBanksTablePowerFactorMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Max detected value of power factor in this bank.( PF x 100 )"
::= { acsPowerMgmtBanksTableEntry 26 }
acsPowerMgmtBanksTablePowerFactorMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Min detected value of power factor in this bank.( PF x 100 )"
::= { acsPowerMgmtBanksTableEntry 27 }
acsPowerMgmtBanksTablePowerFactorAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value for power factor in this bank.( PF x 100 )"
::= { acsPowerMgmtBanksTableEntry 28 }
acsPowerMgmtBanksTablePowerFactorReset OBJECT-TYPE
SYNTAX INTEGER {
no-action (1),
reset (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Reset max, min and avg values of power factor."
::= { acsPowerMgmtBanksTableEntry 29 }
acsPowerMgmtBanksTableAlarm OBJECT-TYPE
SYNTAX INTEGER {
normal (1),
blow-fuse (2),
hw-ocp (3),
high-critical (4),
high-warning (5),
low-warning (6),
low-critical (7)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Show the bank alarm status."
::= { acsPowerMgmtBanksTableEntry 30 }
acsPowerMgmtEnvMonTable OBJECT-TYPE
SYNTAX SEQUENCE OF AcsPowerMgmtEnvMonTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains data monitoring of each detected environmental sensor."
::= { acsPowerMgmt 10 }
acsPowerMgmtEnvMonTableEntry OBJECT-TYPE
SYNTAX AcsPowerMgmtEnvMonTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"each entry has the data monitoring about environmental sensors."
INDEX { acsPowerMgmtEnvMonTablePortNumber, acsPowerMgmtEnvMonTablePduIndex, acsPowerMgmtEnvMonTableIndex }
::= { acsPowerMgmtEnvMonTable 1 }
AcsPowerMgmtEnvMonTableEntry ::= SEQUENCE {
acsPowerMgmtEnvMonTablePortNumber InterfaceIndex, -- number of serial port
acsPowerMgmtEnvMonTablePduIndex InterfaceIndexOrZero, -- number of PDU
acsPowerMgmtEnvMonTableIndex InterfaceIndexOrZero, -- index
acsPowerMgmtEnvMonTableName DisplayString, -- sensor name
acsPowerMgmtEnvMonTablePduId DisplayString, -- PDU identification
acsPowerMgmtEnvMonTablePortName DisplayString, -- Serial Port Name
acsPowerMgmtEnvMonTableType INTEGER, -- environmental sensor type
acsPowerMgmtEnvMonTableStatus INTEGER, -- state of digital sensor
acsPowerMgmtEnvMonTableValue Integer32, -- value
acsPowerMgmtEnvMonTableMaxValue Integer32 -- max value
}
acsPowerMgmtEnvMonTablePortNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of serial port when the PDU is connected."
::= { acsPowerMgmtEnvMonTableEntry 1 }
acsPowerMgmtEnvMonTablePduIndex OBJECT-TYPE
SYNTAX InterfaceIndexOrZero
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A PDU position in the chain."
::= { acsPowerMgmtEnvMonTableEntry 2 }
acsPowerMgmtEnvMonTableIndex OBJECT-TYPE
SYNTAX InterfaceIndexOrZero
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"envmon sensor index."
::= { acsPowerMgmtEnvMonTableEntry 3 }
acsPowerMgmtEnvMonTableName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"envmon sensor name."
::= { acsPowerMgmtEnvMonTableEntry 4 }
acsPowerMgmtEnvMonTablePduId OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"PDU identification."
::= { acsPowerMgmtEnvMonTableEntry 5 }
acsPowerMgmtEnvMonTablePortName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Name of serial port when the PDU is connected."
::= { acsPowerMgmtEnvMonTableEntry 6 }
acsPowerMgmtEnvMonTableType OBJECT-TYPE
SYNTAX INTEGER {
temp-internal (1),
temperature (2),
humidity (3),
air-flow (4),
smoke (5),
dry-contact (6),
water-level (7),
motion (8),
unplugged (9),
unknown (10),
air-pressure (11),
vibration (12),
vibration-contact (13),
leak(14),
door-contact (15),
dewpoint (16),
ad-converter(17),
voltage(18),
current(19)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The type of environmental monitor."
::= { acsPowerMgmtEnvMonTableEntry 7 }
acsPowerMgmtEnvMonTableStatus OBJECT-TYPE
SYNTAX INTEGER {
normal(1),
triggered(2),
not-applicable(3),
leak(4),
cableFault(5)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Status of digital sensors:
Dry-Contact, Water level, Smoke sensor, Motion sensor, Door-Contact, Leak, A2D.
For Door-Contact, normal(1) = closed, triggered(2) = opened.
For A2D, normal(1) = low, triggered(2) = high.
For Leak, normal(1) = no leak, leak(4) = leak, cableFault(5) = cable fault."
::= { acsPowerMgmtEnvMonTableEntry 8 }
acsPowerMgmtEnvMonTableValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Detected value for envmon sensors. Temperature: C x 10. Humidity: %. Air flow: afu."
::= { acsPowerMgmtEnvMonTableEntry 9 }
acsPowerMgmtEnvMonTableMaxValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Max detected value for envmon sensors. Temperature: C x 10. Humidity: %. Air flow: afu.
Voltage VDC x 100. Current x 100."
::= { acsPowerMgmtEnvMonTableEntry 10 }
acsPowerMgmtOutElecMonTable OBJECT-TYPE
SYNTAX SEQUENCE OF AcsPowerMgmtOutElecMonTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains the information about data monitoring of outlets."
::= { acsPowerMgmt 11 }
acsPowerMgmtOutElecMonTableEntry OBJECT-TYPE
SYNTAX AcsPowerMgmtOutElecMonTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"each entry has the information about the outlet."
INDEX { acsPowerMgmtOutElecMonTablePortNumber,
acsPowerMgmtOutElecMonTablePduNumber,
acsPowerMgmtOutElecMonTableNumber }
::= { acsPowerMgmtOutElecMonTable 1 }
AcsPowerMgmtOutElecMonTableEntry ::= SEQUENCE {
acsPowerMgmtOutElecMonTablePortNumber InterfaceIndex, -- serial port #
acsPowerMgmtOutElecMonTablePduNumber InterfaceIndex,
acsPowerMgmtOutElecMonTableNumber InterfaceIndex, -- outlet number in PDU
acsPowerMgmtOutElecMonTableCurrentValue Integer32, -- actual value for current
acsPowerMgmtOutElecMonTableCurrentMax Integer32, -- max detected value for current
acsPowerMgmtOutElecMonTableCurrentMin Integer32, -- min detected value for current
acsPowerMgmtOutElecMonTableCurrentAvg Integer32, -- average value for current
acsPowerMgmtOutElecMonTableCurrentReset INTEGER, -- reset max, min and avg values of current
acsPowerMgmtOutElecMonTablePowerValue Integer32, -- actual value for power
acsPowerMgmtOutElecMonTablePowerMax Integer32, -- max detected value for power
acsPowerMgmtOutElecMonTablePowerMin Integer32, -- min detected value for power
acsPowerMgmtOutElecMonTablePowerAvg Integer32, -- average value for power
acsPowerMgmtOutElecMonTablePowerReset INTEGER, -- reset max, min and avg values of power
acsPowerMgmtOutElecMonTableVoltageValue Integer32, -- actual value for voltage
acsPowerMgmtOutElecMonTableVoltageMax Integer32, -- max detected value for voltage
acsPowerMgmtOutElecMonTableVoltageMin Integer32, -- min detected value for voltage
acsPowerMgmtOutElecMonTableVoltageAvg Integer32, -- average value for voltage
acsPowerMgmtOutElecMonTableVoltageReset INTEGER, -- reset max, min and avg values of voltage
acsPowerMgmtOutElecMonTablePowerFactorValue Integer32, -- actual value for power factor
acsPowerMgmtOutElecMonTablePowerFactorMax Integer32, -- max detected value for power factor
acsPowerMgmtOutElecMonTablePowerFactorMin Integer32, -- min detected value for power factor
acsPowerMgmtOutElecMonTablePowerFactorAvg Integer32, -- avg value for power factor
acsPowerMgmtOutElecMonTablePowerFactorReset INTEGER, -- reset max, min and avg values of power factor
acsPowerMgmtOutElecMonTableAlarm INTEGER -- outlet alarm status
}
acsPowerMgmtOutElecMonTablePortNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial Port number."
::= { acsPowerMgmtOutElecMonTableEntry 1 }
acsPowerMgmtOutElecMonTablePduNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Index."
::= { acsPowerMgmtOutElecMonTableEntry 2 }
acsPowerMgmtOutElecMonTableNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of the outlet in the PDU."
::= { acsPowerMgmtOutElecMonTableEntry 3 }
acsPowerMgmtOutElecMonTableCurrentValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of outlet current sensor.( A x 10 )"
::= { acsPowerMgmtOutElecMonTableEntry 4 }
acsPowerMgmtOutElecMonTableCurrentMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Max detected value of outlet current sensor.( A x 10 )"
::= { acsPowerMgmtOutElecMonTableEntry 5 }
acsPowerMgmtOutElecMonTableCurrentMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Min detected value of outlet current sensor.( A x 10 )"
::= { acsPowerMgmtOutElecMonTableEntry 6 }
acsPowerMgmtOutElecMonTableCurrentAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value for outlet current sensor.( A x 10 )"
::= { acsPowerMgmtOutElecMonTableEntry 7 }
acsPowerMgmtOutElecMonTableCurrentReset OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
reset(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Reset max, min and avertage values of outlet current."
::= { acsPowerMgmtOutElecMonTableEntry 8 }
acsPowerMgmtOutElecMonTablePowerValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of outlet power comsumption sensor.( W x 10 )"
::= { acsPowerMgmtOutElecMonTableEntry 9 }
acsPowerMgmtOutElecMonTablePowerMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Max detected value of outlet power comsumption sensor.( W x 10 )"
::= { acsPowerMgmtOutElecMonTableEntry 10 }
acsPowerMgmtOutElecMonTablePowerMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Min detected value of outlet power comsumption sensor.( W x 10 )"
::= { acsPowerMgmtOutElecMonTableEntry 11 }
acsPowerMgmtOutElecMonTablePowerAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value for outlet power comsumption sensor.( W x 10 )"
::= { acsPowerMgmtOutElecMonTableEntry 12 }
acsPowerMgmtOutElecMonTablePowerReset OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
reset(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Reset max, min and avertage values of outlet power comsumption."
::= { acsPowerMgmtOutElecMonTableEntry 13 }
acsPowerMgmtOutElecMonTableVoltageValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of outlet voltage sensor.( V )"
::= { acsPowerMgmtOutElecMonTableEntry 14 }
acsPowerMgmtOutElecMonTableVoltageMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Max detected value of outlet voltage sensor.( V )"
::= { acsPowerMgmtOutElecMonTableEntry 15 }
acsPowerMgmtOutElecMonTableVoltageMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Min detected value of outlet voltage sensor.( V )"
::= { acsPowerMgmtOutElecMonTableEntry 16 }
acsPowerMgmtOutElecMonTableVoltageAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value for outlet voltage sensor.( V )"
::= { acsPowerMgmtOutElecMonTableEntry 17 }
acsPowerMgmtOutElecMonTableVoltageReset OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
reset(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Reset max, min and avertage values of outlet voltage."
::= { acsPowerMgmtOutElecMonTableEntry 18 }
acsPowerMgmtOutElecMonTablePowerFactorValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of outlet power-factor sensor.( PF x 100 )"
::= { acsPowerMgmtOutElecMonTableEntry 19 }
acsPowerMgmtOutElecMonTablePowerFactorMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Max detected value of outlet power-factor sensor.( PF x 100 )"
::= { acsPowerMgmtOutElecMonTableEntry 20 }
acsPowerMgmtOutElecMonTablePowerFactorMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Min detected value of outlet power-factor sensor.( PF x 100 )"
::= { acsPowerMgmtOutElecMonTableEntry 21 }
acsPowerMgmtOutElecMonTablePowerFactorAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value for outlet power-factor sensor.( PF x 100 )"
::= { acsPowerMgmtOutElecMonTableEntry 22 }
acsPowerMgmtOutElecMonTablePowerFactorReset OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
reset(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Reset max, min and avertage values of outlet power-factor."
::= { acsPowerMgmtOutElecMonTableEntry 23 }
acsPowerMgmtOutElecMonTableAlarm OBJECT-TYPE
SYNTAX INTEGER {
normal (1),
blow-fuse (2),
hw-ocp (3),
high-critical (4),
high-warning (5),
low-warning (6),
low-critical (7)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Show the outlet alarm status."
::= { acsPowerMgmtOutElecMonTableEntry 24 }
acsPowerMgmtUPSTable OBJECT-TYPE
SYNTAX SEQUENCE OF AcsPowerMgmtUPSTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains the list of detected UPSs."
::= { acsPowerMgmt 12 }
acsPowerMgmtUPSTableEntry OBJECT-TYPE
SYNTAX AcsPowerMgmtUPSTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Each entry has the information about the UPS."
INDEX { acsPowerMgmtUPSTablePortNumber, acsPowerMgmtUPSTableUpsIndex }
::= { acsPowerMgmtUPSTable 1 }
AcsPowerMgmtUPSTableEntry ::= SEQUENCE {
acsPowerMgmtUPSTablePortNumber InterfaceIndex, -- number of serial port
acsPowerMgmtUPSTableUpsIndex InterfaceIndexOrZero,
acsPowerMgmtUPSTableUpsId DisplayString, -- UPS identification
acsPowerMgmtUPSTablePortName DisplayString, -- Serial Port Name or IP address if network device
acsPowerMgmtUPSTableModel DisplayString,
acsPowerMgmtUPSTableVendor DisplayString,
acsPowerMgmtUPSTableFirmwareVersion DisplayString,
acsPowerMgmtUPSTableAgentFirmwareVersion DisplayString,
acsPowerMgmtUPSTableSystemStatus DisplayString,
acsPowerMgmtUPSTableInputBlackOutCount Integer32,
acsPowerMgmtUPSTableInputBrownOutCount Integer32,
acsPowerMgmtUPSTableInletAirTemperature DisplayString,
acsPowerMgmtUPSTableNumberOutletGroups Integer32,
acsPowerMgmtUPSTableUPSSerialNumber DisplayString,
acsPowerMgmtUPSTableUPSManufactureDate DisplayString,
acsPowerMgmtUPSTableAutoRestartDelay Integer32,
acsPowerMgmtUPSTableAutoRestartControl INTEGER,
acsPowerMgmtUPSTableAudibleAlarmControl INTEGER,
acsPowerMgmtUPSTableSilenceAlarm Integer32,
acsPowerMgmtUPSTableInverterState DisplayString,
acsPowerMgmtUPSTableDCConverterStatus DisplayString,
acsPowerMgmtUPSTableShutdownReason DisplayString,
acsPowerMgmtUPSTableUPSTopology DisplayString,
acsPowerMgmtUPSTableBypassInverterInputConfig DisplayString
}
acsPowerMgmtUPSTablePortNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of serial port when the UPS is connected."
::= { acsPowerMgmtUPSTableEntry 1 }
acsPowerMgmtUPSTableUpsIndex OBJECT-TYPE
SYNTAX InterfaceIndexOrZero
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A UPS position in the chain."
::= { acsPowerMgmtUPSTableEntry 2 }
acsPowerMgmtUPSTableUpsId OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"UPS identification."
::= { acsPowerMgmtUPSTableEntry 3 }
acsPowerMgmtUPSTablePortName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Name of serial port or IP address if network device"
::= { acsPowerMgmtUPSTableEntry 4 }
acsPowerMgmtUPSTableModel OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Model of the UPS."
::= { acsPowerMgmtUPSTableEntry 5 }
acsPowerMgmtUPSTableVendor OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Vendor of the UPS."
::= { acsPowerMgmtUPSTableEntry 6 }
acsPowerMgmtUPSTableFirmwareVersion OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Version of the UPS firmware."
::= { acsPowerMgmtUPSTableEntry 7 }
acsPowerMgmtUPSTableAgentFirmwareVersion OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Firmware version of the agent card."
::= { acsPowerMgmtUPSTableEntry 8 }
acsPowerMgmtUPSTableSystemStatus OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System Status of the UPS."
::= { acsPowerMgmtUPSTableEntry 9 }
acsPowerMgmtUPSTableInputBlackOutCount OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of occurrences, since the last reset, where the input
was not qualified to provide power to the system."
::= { acsPowerMgmtUPSTableEntry 10 }
acsPowerMgmtUPSTableInputBrownOutCount OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of occurrences, since the last reset, where the system
input voltage has fallen below a pre-determined threshold for a
specified amount of time."
::= { acsPowerMgmtUPSTableEntry 11 }
acsPowerMgmtUPSTableInletAirTemperature OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Temperature of the inlet air."
::= { acsPowerMgmtUPSTableEntry 12 }
acsPowerMgmtUPSTableNumberOutletGroups OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of Outlet Groups on this UPS"
::= { acsPowerMgmtUPSTableEntry 13 }
acsPowerMgmtUPSTableUPSSerialNumber OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System serial number."
::= { acsPowerMgmtUPSTableEntry 14 }
acsPowerMgmtUPSTableUPSManufactureDate OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Manufacturing date of the system."
::= { acsPowerMgmtUPSTableEntry 15 }
acsPowerMgmtUPSTableAutoRestartDelay OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"If power is lost, the control will delay this amount of
time after power is restored before restarting the unit."
::= { acsPowerMgmtUPSTableEntry 16 }
acsPowerMgmtUPSTableAutoRestartControl OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
enabled(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"When set to enabled, the UPS will automatically restart the load
when utility power is restored after a battery discharge."
::= { acsPowerMgmtUPSTableEntry 17 }
acsPowerMgmtUPSTableAudibleAlarmControl OBJECT-TYPE
SYNTAX INTEGER {
off(1),
on(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Audible alarm control."
::= { acsPowerMgmtUPSTableEntry 18 }
acsPowerMgmtUPSTableSilenceAlarm OBJECT-TYPE
SYNTAX INTEGER {
noAction(0),
silenceAlarm(1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Silence audible alarm."
::= { acsPowerMgmtUPSTableEntry 19 }
acsPowerMgmtUPSTableInverterState OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Inverter on/off state."
::= { acsPowerMgmtUPSTableEntry 20 }
acsPowerMgmtUPSTableDCConverterStatus OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The operating state of the dc converter."
::= { acsPowerMgmtUPSTableEntry 21 }
acsPowerMgmtUPSTableShutdownReason OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The reason for the most recent shutdown."
::= { acsPowerMgmtUPSTableEntry 22 }
acsPowerMgmtUPSTableUPSTopology OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"UPS Topology."
::= { acsPowerMgmtUPSTableEntry 23 }
acsPowerMgmtUPSTableBypassInverterInputConfig OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Input source configuration for the bypass and inverter."
::= { acsPowerMgmtUPSTableEntry 24 }
--
-- acsPowerMgmtUPSInputTable ::= { acsPowerMgmt 13 }
--
acsPowerMgmtUPSInputTable OBJECT-TYPE
SYNTAX SEQUENCE OF AcsPowerMgmtUPSInputTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains the information about UPS inputs."
::= { acsPowerMgmt 13 }
acsPowerMgmtUPSInputTableEntry OBJECT-TYPE
SYNTAX AcsPowerMgmtUPSInputTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"each entry has the information about the UPS inputs."
INDEX { acsPowerMgmtUPSInputTablePortNumber,
acsPowerMgmtUPSInputTableUpsIndex }
::= { acsPowerMgmtUPSInputTable 1 }
AcsPowerMgmtUPSInputTableEntry ::= SEQUENCE {
acsPowerMgmtUPSInputTablePortNumber InterfaceIndex, -- serial port #
acsPowerMgmtUPSInputTableUpsIndex InterfaceIndex,
acsPowerMgmtUPSInputTableFrequency DisplayString,
acsPowerMgmtUPSInputTableRMSVoltageL1N DisplayString,
acsPowerMgmtUPSInputTableRMSVoltageL1L2 DisplayString,
acsPowerMgmtUPSInputTableRMSVoltageL2N DisplayString,
acsPowerMgmtUPSInputTableRMSCurrentL1 DisplayString,
acsPowerMgmtUPSInputTableRMSCurrentL2 DisplayString,
acsPowerMgmtUPSInputTableMaxVoltageL1N DisplayString,
acsPowerMgmtUPSInputTableMinVoltageL1N DisplayString,
acsPowerMgmtUPSInputTableMaxVoltageL2N DisplayString,
acsPowerMgmtUPSInputTableMinVoltageL2N DisplayString,
acsPowerMgmtUPSInputTableNominalVoltage DisplayString,
acsPowerMgmtUPSInputTableNominalFrequency DisplayString,
acsPowerMgmtUPSInputTableNominalCurrent DisplayString,
acsPowerMgmtUPSInputTableEnergy DisplayString,
acsPowerMgmtUPSInputTablePowerFactorL1N DisplayString,
acsPowerMgmtUPSInputTablePowerFactorL2N DisplayString
}
acsPowerMgmtUPSInputTablePortNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial Port number."
::= { acsPowerMgmtUPSInputTableEntry 1 }
acsPowerMgmtUPSInputTableUpsIndex OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Index."
::= { acsPowerMgmtUPSInputTableEntry 2 }
acsPowerMgmtUPSInputTableFrequency OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Input Frequency."
::= { acsPowerMgmtUPSInputTableEntry 3 }
acsPowerMgmtUPSInputTableRMSVoltageL1N OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"RMS Voltage L1-N."
::= { acsPowerMgmtUPSInputTableEntry 4 }
acsPowerMgmtUPSInputTableRMSVoltageL1L2 OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"RMS Voltage L1L2."
::= { acsPowerMgmtUPSInputTableEntry 5 }
acsPowerMgmtUPSInputTableRMSVoltageL2N OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"RMS Voltage L2N."
::= { acsPowerMgmtUPSInputTableEntry 6 }
acsPowerMgmtUPSInputTableRMSCurrentL1 OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"RMS Current for L1."
::= { acsPowerMgmtUPSInputTableEntry 7 }
acsPowerMgmtUPSInputTableRMSCurrentL2 OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"RMS Current for L2."
::= { acsPowerMgmtUPSInputTableEntry 8 }
acsPowerMgmtUPSInputTableMaxVoltageL1N OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Input Max Voltage measurement for Line L1-N since the last reset."
::= { acsPowerMgmtUPSInputTableEntry 9 }
acsPowerMgmtUPSInputTableMinVoltageL1N OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Input Min Voltage measurement for Line L1-N since the last reset."
::= { acsPowerMgmtUPSInputTableEntry 10 }
acsPowerMgmtUPSInputTableMaxVoltageL2N OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Input Max Voltage measurement for Line L2-N since the last reset."
::= { acsPowerMgmtUPSInputTableEntry 11 }
acsPowerMgmtUPSInputTableMinVoltageL2N OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Input Min Voltage measurement for Line L1-N since the last reset."
::= { acsPowerMgmtUPSInputTableEntry 12 }
acsPowerMgmtUPSInputTableNominalVoltage OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Input nominal voltage."
::= { acsPowerMgmtUPSInputTableEntry 13 }
acsPowerMgmtUPSInputTableNominalFrequency OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Input nominal frequency."
::= { acsPowerMgmtUPSInputTableEntry 14 }
acsPowerMgmtUPSInputTableNominalCurrent OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Input nominal current."
::= { acsPowerMgmtUPSInputTableEntry 15 }
acsPowerMgmtUPSInputTableEnergy OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Input Energy."
::= { acsPowerMgmtUPSInputTableEntry 16 }
acsPowerMgmtUPSInputTablePowerFactorL1N OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Input Power Factor for Line 1."
::= { acsPowerMgmtUPSInputTableEntry 17 }
acsPowerMgmtUPSInputTablePowerFactorL2N OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Input Power Factor for Line 2."
::= { acsPowerMgmtUPSInputTableEntry 18 }
--
-- acsPowerMgmtUPSBypassTable ::= { acsPowerMgmt 14 }
--
acsPowerMgmtUPSBypassTable OBJECT-TYPE
SYNTAX SEQUENCE OF AcsPowerMgmtUPSBypassTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains the information about UPS bypass."
::= { acsPowerMgmt 14 }
acsPowerMgmtUPSBypassTableEntry OBJECT-TYPE
SYNTAX AcsPowerMgmtUPSBypassTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"each entry has the information about the UPS bypass."
INDEX { acsPowerMgmtUPSBypassTablePortNumber,
acsPowerMgmtUPSBypassTableUpsIndex }
::= { acsPowerMgmtUPSBypassTable 1 }
AcsPowerMgmtUPSBypassTableEntry ::= SEQUENCE {
acsPowerMgmtUPSBypassTablePortNumber InterfaceIndex, -- serial port #
acsPowerMgmtUPSBypassTableUpsIndex InterfaceIndex,
acsPowerMgmtUPSBypassTableRMSVoltageL1N DisplayString,
acsPowerMgmtUPSBypassTableRMSVoltageL1L2 DisplayString,
acsPowerMgmtUPSBypassTableRMSVoltageL2N DisplayString,
acsPowerMgmtUPSBypassTableRMSCurrent DisplayString,
acsPowerMgmtUPSBypassTableRMSCurrentL2 DisplayString,
acsPowerMgmtUPSBypassTableInputFrequency DisplayString,
acsPowerMgmtUPSBypassTableNominalVoltage DisplayString
}
acsPowerMgmtUPSBypassTablePortNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial Port number."
::= { acsPowerMgmtUPSBypassTableEntry 1 }
acsPowerMgmtUPSBypassTableUpsIndex OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Index."
::= { acsPowerMgmtUPSBypassTableEntry 2 }
acsPowerMgmtUPSBypassTableRMSVoltageL1N OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"RMS Voltage L1N."
::= { acsPowerMgmtUPSBypassTableEntry 3 }
acsPowerMgmtUPSBypassTableRMSVoltageL1L2 OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"RMS Voltage L1L2."
::= { acsPowerMgmtUPSBypassTableEntry 4 }
acsPowerMgmtUPSBypassTableRMSVoltageL2N OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"RMS Voltage L2N."
::= { acsPowerMgmtUPSBypassTableEntry 5 }
acsPowerMgmtUPSBypassTableRMSCurrent OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"RMS Current."
::= { acsPowerMgmtUPSBypassTableEntry 6 }
acsPowerMgmtUPSBypassTableRMSCurrentL2 OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"RMS Current."
::= { acsPowerMgmtUPSBypassTableEntry 7 }
acsPowerMgmtUPSBypassTableInputFrequency OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Bypass Input Frequency."
::= { acsPowerMgmtUPSBypassTableEntry 8 }
acsPowerMgmtUPSBypassTableNominalVoltage OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Bypass Nominal Voltage."
::= { acsPowerMgmtUPSBypassTableEntry 9 }
--
-- acsPowerMgmtUPSBatteryTable ::= { acsPowerMgmt 15 }
--
acsPowerMgmtUPSBatteryTable OBJECT-TYPE
SYNTAX SEQUENCE OF AcsPowerMgmtUPSBatteryTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains the information about UPS battery."
::= { acsPowerMgmt 15 }
acsPowerMgmtUPSBatteryTableEntry OBJECT-TYPE
SYNTAX AcsPowerMgmtUPSBatteryTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"each entry has the information about the UPS bypass."
INDEX { acsPowerMgmtUPSBatteryTablePortNumber,
acsPowerMgmtUPSBatteryTableUpsIndex }
::= { acsPowerMgmtUPSBatteryTable 1 }
AcsPowerMgmtUPSBatteryTableEntry ::= SEQUENCE {
acsPowerMgmtUPSBatteryTablePortNumber InterfaceIndex, -- serial port #
acsPowerMgmtUPSBatteryTableUpsIndex InterfaceIndex,
acsPowerMgmtUPSBatteryTableDCBusVoltage DisplayString,
acsPowerMgmtUPSBatteryTableTimeRemaining DisplayString,
acsPowerMgmtUPSBatteryTablePercentageCharge DisplayString,
acsPowerMgmtUPSBatteryTableChargeStatus DisplayString,
acsPowerMgmtUPSBatteryTableLowBatteryWarningTime INTEGER,
acsPowerMgmtUPSBatteryTableTestResult DisplayString,
acsPowerMgmtUPSBatteryTableDCBusNominalVoltage DisplayString,
acsPowerMgmtUPSBatteryTableNominalBatteryCapacity DisplayString,
acsPowerMgmtUPSBatteryTableBatteryFloatVoltage DisplayString,
acsPowerMgmtUPSBatteryTableBatteryCabinetType DisplayString,
acsPowerMgmtUPSBatteryTableBatteryNumberOfEBC DisplayString,
acsPowerMgmtUPSBatteryTableBatteryRating DisplayString,
acsPowerMgmtUPSBatteryTableBatteryDischargeTime DisplayString,
acsPowerMgmtUPSBatteryTableBatteryChargeCompensating DisplayString,
acsPowerMgmtUPSBatteryTableBatteryChargerState DisplayString,
acsPowerMgmtUPSBatteryTableStartBatteryTest INTEGER,
acsPowerMgmtUPSBatteryTableBatteryStatus DisplayString,
acsPowerMgmtUPSBatteryTableBatteryTotalDischargeTime DisplayString,
acsPowerMgmtUPSBatteryTableBatteryDischargeCount DisplayString,
acsPowerMgmtUPSBatteryTableBatteryCurrent DisplayString
}
acsPowerMgmtUPSBatteryTablePortNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial Port number."
::= { acsPowerMgmtUPSBatteryTableEntry 1 }
acsPowerMgmtUPSBatteryTableUpsIndex OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Index."
::= { acsPowerMgmtUPSBatteryTableEntry 2 }
acsPowerMgmtUPSBatteryTableDCBusVoltage OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"DC Bus Voltage"
::= { acsPowerMgmtUPSBatteryTableEntry 3 }
acsPowerMgmtUPSBatteryTableTimeRemaining OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The calculated available time on battery."
::= { acsPowerMgmtUPSBatteryTableEntry 4 }
acsPowerMgmtUPSBatteryTablePercentageCharge OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Battery Percentage Charge."
::= { acsPowerMgmtUPSBatteryTableEntry 5 }
acsPowerMgmtUPSBatteryTableChargeStatus OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Battery Charge Status."
::= { acsPowerMgmtUPSBatteryTableEntry 6 }
acsPowerMgmtUPSBatteryTableLowBatteryWarningTime OBJECT-TYPE
SYNTAX INTEGER (2..30)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"When battery time remaining falls to, or below, this value
(minutes) the low battery alarm is activated."
::= { acsPowerMgmtUPSBatteryTableEntry 7 }
acsPowerMgmtUPSBatteryTableTestResult OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The outcome of the previous battery test."
::= { acsPowerMgmtUPSBatteryTableEntry 8 }
acsPowerMgmtUPSBatteryTableDCBusNominalVoltage OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Battery DC Bus Nominal Voltage."
::= { acsPowerMgmtUPSBatteryTableEntry 9 }
acsPowerMgmtUPSBatteryTableNominalBatteryCapacity OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Nominal Battery Capacity."
::= { acsPowerMgmtUPSBatteryTableEntry 10 }
acsPowerMgmtUPSBatteryTableBatteryFloatVoltage OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Battery Float Voltage."
::= { acsPowerMgmtUPSBatteryTableEntry 11 }
acsPowerMgmtUPSBatteryTableBatteryCabinetType OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Battery Cabinet Type."
::= { acsPowerMgmtUPSBatteryTableEntry 12 }
acsPowerMgmtUPSBatteryTableBatteryNumberOfEBC OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of Extended Battery Cabinets installed."
::= { acsPowerMgmtUPSBatteryTableEntry 13 }
acsPowerMgmtUPSBatteryTableBatteryRating OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Battery Rating."
::= { acsPowerMgmtUPSBatteryTableEntry 14 }
acsPowerMgmtUPSBatteryTableBatteryDischargeTime OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Time on battery operation for this discharge"
::= { acsPowerMgmtUPSBatteryTableEntry 15 }
acsPowerMgmtUPSBatteryTableBatteryChargeCompensating OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Battery charge algorithm changed due to battery temperature."
::= { acsPowerMgmtUPSBatteryTableEntry 16 }
acsPowerMgmtUPSBatteryTableBatteryChargerState OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Battery charger state."
::= { acsPowerMgmtUPSBatteryTableEntry 17 }
acsPowerMgmtUPSBatteryTableStartBatteryTest OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
start(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Command to initate a manual battery test."
::= { acsPowerMgmtUPSBatteryTableEntry 18 }
acsPowerMgmtUPSBatteryTableBatteryStatus OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Battery Status."
::= { acsPowerMgmtUPSBatteryTableEntry 19 }
acsPowerMgmtUPSBatteryTableBatteryTotalDischargeTime OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Cumulative battery discharge time."
::= { acsPowerMgmtUPSBatteryTableEntry 20 }
acsPowerMgmtUPSBatteryTableBatteryDischargeCount OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
" Total number of battery discharges."
::= { acsPowerMgmtUPSBatteryTableEntry 21 }
acsPowerMgmtUPSBatteryTableBatteryCurrent OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
" Current at the battery input terminals. In charging mode,
the current will be a positive value. In discharging mode,
the current will be a negative value."
::= { acsPowerMgmtUPSBatteryTableEntry 22 }
--
-- acsPowerMgmtUPSOutputTable ::= { acsPowerMgmt 16 }
--
acsPowerMgmtUPSOutputTable OBJECT-TYPE
SYNTAX SEQUENCE OF AcsPowerMgmtUPSOutputTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains the information about UPS output."
::= { acsPowerMgmt 16 }
acsPowerMgmtUPSOutputTableEntry OBJECT-TYPE
SYNTAX AcsPowerMgmtUPSOutputTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Each entry has the information about the UPS output."
INDEX { acsPowerMgmtUPSOutputTablePortNumber,
acsPowerMgmtUPSOutputTableUpsIndex }
::= { acsPowerMgmtUPSOutputTable 1 }
AcsPowerMgmtUPSOutputTableEntry ::= SEQUENCE {
acsPowerMgmtUPSOutputTablePortNumber InterfaceIndex, -- serial port #
acsPowerMgmtUPSOutputTableUpsIndex InterfaceIndex,
acsPowerMgmtUPSOutputTableApparentPower DisplayString,
acsPowerMgmtUPSOutputTableFrequency DisplayString,
acsPowerMgmtUPSOutputTablePercentPower DisplayString,
acsPowerMgmtUPSOutputTablePercentPowerL1 DisplayString,
acsPowerMgmtUPSOutputTablePercentPowerL2 DisplayString,
acsPowerMgmtUPSOutputTablePower DisplayString,
acsPowerMgmtUPSOutputTableRMSCurrentL1 DisplayString,
acsPowerMgmtUPSOutputTableRMSCurrentL2 DisplayString,
acsPowerMgmtUPSOutputTableRMSVoltageL1N DisplayString,
acsPowerMgmtUPSOutputTableRMSVoltageL2N DisplayString,
acsPowerMgmtUPSOutputTableRMSVoltageL1L2 DisplayString,
acsPowerMgmtUPSOutputOffDelay INTEGER,
acsPowerMgmtUPSOutputOnDelay INTEGER,
acsPowerMgmtUPSOutputCycleDelay INTEGER,
acsPowerMgmtUPSOutputTableMaxVoltageL1 DisplayString,
acsPowerMgmtUPSOutputTableMinVoltageL1 DisplayString,
acsPowerMgmtUPSOutputTableMaxVoltageL2 DisplayString,
acsPowerMgmtUPSOutputTableMinVoltageL2 DisplayString,
acsPowerMgmtUPSOutputTableNominalVoltage DisplayString,
acsPowerMgmtUPSOutputTablePowerNominalFrequency DisplayString,
acsPowerMgmtUPSOutputTablePowerApparentPowerRating DisplayString,
acsPowerMgmtUPSOutputTablePowerNominalPowerFactor DisplayString,
acsPowerMgmtUPSOutputTablePowerPowerFactorCorrection DisplayString,
acsPowerMgmtUPSOutputTablePowerL1 DisplayString,
acsPowerMgmtUPSOutputTablePowerL2 DisplayString,
acsPowerMgmtUPSOutputTableApparentPowerL1 DisplayString,
acsPowerMgmtUPSOutputTableApparentPowerL2 DisplayString,
acsPowerMgmtUPSOutputTablePowerFactorL1 DisplayString,
acsPowerMgmtUPSOutputTablePowerFactorL2 DisplayString
}
acsPowerMgmtUPSOutputTablePortNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial Port number."
::= { acsPowerMgmtUPSOutputTableEntry 1 }
acsPowerMgmtUPSOutputTableUpsIndex OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Index."
::= { acsPowerMgmtUPSOutputTableEntry 2 }
acsPowerMgmtUPSOutputTableApparentPower OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"DC Bus Voltage"
::= { acsPowerMgmtUPSOutputTableEntry 3 }
acsPowerMgmtUPSOutputTableFrequency OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Output frequency."
::= { acsPowerMgmtUPSOutputTableEntry 4 }
acsPowerMgmtUPSOutputTablePercentPower OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The system output power as a percentage of the rated capacity."
::= { acsPowerMgmtUPSOutputTableEntry 5 }
acsPowerMgmtUPSOutputTablePercentPowerL1 OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The system output power on line L1 as a percentage of the rated capacity."
::= { acsPowerMgmtUPSOutputTableEntry 6 }
acsPowerMgmtUPSOutputTablePercentPowerL2 OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The system output power on line L2 as a percentage of the rated capacity."
::= { acsPowerMgmtUPSOutputTableEntry 7 }
acsPowerMgmtUPSOutputTablePower OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The sum total power of all system output phases."
::= { acsPowerMgmtUPSOutputTableEntry 8 }
acsPowerMgmtUPSOutputTableRMSCurrentL1 OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System output RMS current for line L1."
::= { acsPowerMgmtUPSOutputTableEntry 9 }
acsPowerMgmtUPSOutputTableRMSCurrentL2 OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System output RMS current for line L2."
::= { acsPowerMgmtUPSOutputTableEntry 10 }
acsPowerMgmtUPSOutputTableRMSVoltageL1N OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The system output RMS voltage."
::= { acsPowerMgmtUPSOutputTableEntry 11 }
acsPowerMgmtUPSOutputTableRMSVoltageL2N OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The system output RMS voltage."
::= { acsPowerMgmtUPSOutputTableEntry 12 }
acsPowerMgmtUPSOutputTableRMSVoltageL1L2 OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The system output RMS voltage."
::= { acsPowerMgmtUPSOutputTableEntry 13 }
acsPowerMgmtUPSOutputOffDelay OBJECT-TYPE
SYNTAX INTEGER (0..300)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Turns the UPS output off after the number of seconds specified.
When a value is written to this object the output will be turned
off after the specified time has elapsed and the output will
remain off."
::= { acsPowerMgmtUPSOutputTableEntry 14 }
acsPowerMgmtUPSOutputOnDelay OBJECT-TYPE
SYNTAX INTEGER (0..300)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Turns the UPS output on after the number of seconds specified.
When a value is written to this object the output will be turned
on after the specified time has elapsed."
::= { acsPowerMgmtUPSOutputTableEntry 15 }
acsPowerMgmtUPSOutputCycleDelay OBJECT-TYPE
SYNTAX INTEGER (0..300)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Turns the UPS off and then back on after the number of seconds specified.
When a value is written to this object the output will turned off immediately
and then turned back on after the specified time has elapsed."
::= { acsPowerMgmtUPSOutputTableEntry 16 }
acsPowerMgmtUPSOutputTableMaxVoltageL1 OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The maximum system output voltage measurement for line 1 since the last reset."
::= { acsPowerMgmtUPSOutputTableEntry 17 }
acsPowerMgmtUPSOutputTableMinVoltageL1 OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The minimum system output voltage measurement for line 1 since the last reset."
::= { acsPowerMgmtUPSOutputTableEntry 18 }
acsPowerMgmtUPSOutputTableMaxVoltageL2 OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The maximum system output voltage measurement for line 21 since the last reset."
::= { acsPowerMgmtUPSOutputTableEntry 19 }
acsPowerMgmtUPSOutputTableMinVoltageL2 OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The minimum system output voltage measurement for line 2 since the last reset."
::= { acsPowerMgmtUPSOutputTableEntry 20 }
acsPowerMgmtUPSOutputTableNominalVoltage OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The nominal (or rated) system output voltage."
::= { acsPowerMgmtUPSOutputTableEntry 21 }
acsPowerMgmtUPSOutputTablePowerNominalFrequency OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The nominal (or rated) system output frequency."
::= { acsPowerMgmtUPSOutputTableEntry 22 }
acsPowerMgmtUPSOutputTablePowerApparentPowerRating OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Output apparent power rating."
::= { acsPowerMgmtUPSOutputTableEntry 23 }
acsPowerMgmtUPSOutputTablePowerNominalPowerFactor OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The nominal (or rated) system power factor."
::= { acsPowerMgmtUPSOutputTableEntry 24 }
acsPowerMgmtUPSOutputTablePowerPowerFactorCorrection OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The state of the power factor correction circuitry of the system."
::= { acsPowerMgmtUPSOutputTableEntry 25 }
acsPowerMgmtUPSOutputTablePowerL1 OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The system output power on line 1."
::= { acsPowerMgmtUPSOutputTableEntry 26 }
acsPowerMgmtUPSOutputTablePowerL2 OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The system output power on line 2."
::= { acsPowerMgmtUPSOutputTableEntry 27 }
acsPowerMgmtUPSOutputTableApparentPowerL1 OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The system output apparent power on line 1."
::= { acsPowerMgmtUPSOutputTableEntry 28 }
acsPowerMgmtUPSOutputTableApparentPowerL2 OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The system output apparent power on line 2."
::= { acsPowerMgmtUPSOutputTableEntry 29 }
acsPowerMgmtUPSOutputTablePowerFactorL1 OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The system output power factor on line 1."
::= { acsPowerMgmtUPSOutputTableEntry 30 }
acsPowerMgmtUPSOutputTablePowerFactorL2 OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The system output power factor on line 2."
::= { acsPowerMgmtUPSOutputTableEntry 31 }
--
-- acsPowerMgmtUPSEcoModeTable ::= { acsPowerMgmt 17 }
--
acsPowerMgmtUPSEcoModeTable OBJECT-TYPE
SYNTAX SEQUENCE OF AcsPowerMgmtUPSEcoModeTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains the information about UPS ECO Mode."
::= { acsPowerMgmt 17 }
acsPowerMgmtUPSEcoModeTableEntry OBJECT-TYPE
SYNTAX AcsPowerMgmtUPSEcoModeTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"each entry has the information about the UPS ECO Mode."
INDEX { acsPowerMgmtUPSBypassTablePortNumber,
acsPowerMgmtUPSBypassTableUpsIndex }
::= { acsPowerMgmtUPSEcoModeTable 1 }
AcsPowerMgmtUPSEcoModeTableEntry ::= SEQUENCE {
acsPowerMgmtUPSEcoModeTablePortNumber InterfaceIndex, -- serial port #
acsPowerMgmtUPSEcoModeTableUpsIndex InterfaceIndex,
acsPowerMgmtUPSEcoModeTableStatus DisplayString,
acsPowerMgmtUPSEcoModeTableStateControl INTEGER
}
acsPowerMgmtUPSEcoModeTablePortNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial Port number."
::= { acsPowerMgmtUPSEcoModeTableEntry 1 }
acsPowerMgmtUPSEcoModeTableUpsIndex OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Index."
::= { acsPowerMgmtUPSEcoModeTableEntry 2 }
acsPowerMgmtUPSEcoModeTableStatus OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Current ECO Mode Status."
::= { acsPowerMgmtUPSEcoModeTableEntry 3 }
acsPowerMgmtUPSEcoModeTableStateControl OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
enable(2),
disable(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enable or disable ECO mode."
::= { acsPowerMgmtUPSEcoModeTableEntry 4 }
--
-- acsPowerMgmtUPSOutletGroupTable ::= { acsPowerMgmt 18 }
--
acsPowerMgmtUPSOutletGroupTable OBJECT-TYPE
SYNTAX SEQUENCE OF AcsPowerMgmtUPSOutletGroupTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains the UPS Outlet Group Information."
::= { acsPowerMgmt 18 }
acsPowerMgmtUPSOutletGroupTableEntry OBJECT-TYPE
SYNTAX AcsPowerMgmtUPSOutletGroupTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Each entry has the UPS outlet group information."
INDEX { acsPowerMgmtUPSOutletGroupTablePortNumber,
acsPowerMgmtUPSOutletGroupTableUpsIndex,
acsPowerMgmtUPSOutletGroupTableNumber }
::= { acsPowerMgmtUPSOutletGroupTable 1 }
AcsPowerMgmtUPSOutletGroupTableEntry ::= SEQUENCE {
acsPowerMgmtUPSOutletGroupTablePortNumber InterfaceIndex, -- serial port #
acsPowerMgmtUPSOutletGroupTableUpsIndex InterfaceIndex,
acsPowerMgmtUPSOutletGroupTableNumber InterfaceIndex,
acsPowerMgmtUPSOutletGroupTableLabel DisplayString,
acsPowerMgmtUPSOutletGroupTableState DisplayString,
acsPowerMgmtUPSOutletGroupTablePowerControl INTEGER -- manage the outlet group
}
acsPowerMgmtUPSOutletGroupTablePortNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial Port number."
::= { acsPowerMgmtUPSOutletGroupTableEntry 1 }
acsPowerMgmtUPSOutletGroupTableUpsIndex OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Index."
::= { acsPowerMgmtUPSOutletGroupTableEntry 2 }
acsPowerMgmtUPSOutletGroupTableNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of the outletgroup in the UPS."
::= { acsPowerMgmtUPSOutletGroupTableEntry 3 }
acsPowerMgmtUPSOutletGroupTableLabel OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"User-defined label for the outlet group."
::= { acsPowerMgmtUPSOutletGroupTableEntry 4 }
acsPowerMgmtUPSOutletGroupTableState OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"User-defined label for the outlet group."
::= { acsPowerMgmtUPSOutletGroupTableEntry 5 }
acsPowerMgmtUPSOutletGroupTablePowerControl OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
powerOn(2),
powerOff(3),
powerCycle(4)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A set value of power(2-6) will send command to the UPS.
noAction(1) = always returned in a GET. Does nothing if SET.
powerOn(2) = when SET the power On command is sent to UPS.
powerOff(3) = when SET the power Off command is sent to UPS.
powerCycle(4)=when SET the power cycle command is sent to UPS."
::= { acsPowerMgmtUPSOutletGroupTableEntry 6 }
--
-- acsSensors
-- OBJECT IDENTIFIER ::= { acsManagement 7 } 10418.26.2.7
--
acsSensorsInternalCurrentCPUTemperature OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current CPU temperature in degrees Celsius."
::= { acsSensors 1 }
acsSensorsInternalMaxCPUTemperature OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The CPU temperature in degrees Celsius that, if exceeded,
will generate an event notification."
::= { acsSensors 2 }
acsSensorsInternalMaxCPUTemperatureThreshold OBJECT-TYPE
SYNTAX Integer32 (0..4)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The CPU temperature threshold in degrees Celsius below the
maximum CPU temperature. When the temperature exceeds the
Maximum Temperature plus Threshold, an event notification
will be generated. When the temperature falls below the
Maximum Temperature minus Threshold, an event notification
that the console system has returned to normal operating
temperature will be generated."
::= { acsSensors 3 }
acsSensorsInternalMinCPUTemperature OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The CPU temperature in degrees Celsius that, if the
CPU temperature falls below, will generate an event notification."
::= { acsSensors 4 }
acsSensorsInternalMinCPUTemperatureThreshold OBJECT-TYPE
SYNTAX Integer32 (0..4)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The CPU temperature threshold in degrees Celsius above the
minimum CPU temperature."
::= { acsSensors 5 }
acsSensorsInternalCurrentBoardTemperature OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current board temperature in degrees Celsius."
::= { acsSensors 6 }
acsSensorsInternalMaxBoardTemperature OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The board temperature in degrees Celsius that, if exceeded,
will generate an event notification."
::= { acsSensors 7 }
acsSensorsInternalMaxBoardTemperatureThreshold OBJECT-TYPE
SYNTAX Integer32 (0..4)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The board temperature threshold in degrees Celsius below the
maximum board temperature. When the temperature exceeds the
Maximum Temperature plus Threshold, an event notification
will be generated. When the temperature falls below the
Maximum Temperature minus Threshold, an event notification
that the console system has returned to normal operating
temperature will be generated."
::= { acsSensors 8 }
acsSensorsInternalMinBoardTemperature OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The board temperature in degrees Celsius that, if the
board temperature falls below, will generate an event notification."
::= { acsSensors 9 }
acsSensorsInternalMinBoardTemperatureThreshold OBJECT-TYPE
SYNTAX Integer32 (0..4)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The board temperature threshold in degrees Celsius above the
minimum board temperature."
::= { acsSensors 10 }
acsSensorsVoltagePSInternal OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PS Internal Supply voltage [0.95v ~ 1.05v] x 100."
::= { acsSensors 11 }
acsSensorsVoltagePLInternal OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PL Internal Supply voltage [0.95v ~ 1.05v] x 100."
::= { acsSensors 12 }
acsSensorsVoltagePSAuxiliary OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PS Auxiliary Supply voltage [1.71v ~ 1.89v] x 100."
::= { acsSensors 13 }
acsSensorsVoltagePLAuxiliary OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PL Auxiliary Supply voltage [1.71v ~ 1.89v] x 100."
::= { acsSensors 14 }
acsSensorsVoltagePSDDR3 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PS DDR3 Supply voltage [1.31v ~ 1.39v] x 100."
::= { acsSensors 15 }
acsSensorsVoltagePLBlockRam OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PL Block RAM Supply voltage [0.95v ~ 1.05v] x 100."
::= { acsSensors 16 }
acsSensorsVoltagePowerSupply1 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The Power Supply 1 voltage [11.06v ~ 12.98v] x 100."
::= { acsSensors 17 }
acsSensorsVoltagePowerSupply2 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The Power Supply 2 voltage [11.06v ~ 12.98v] x 100."
::= { acsSensors 18 }
acsSensors1WireUpdateControl OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
update(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A set value of update(2) will refresh the 1-wire sensor list."
::= { acsSensors 19 }
acsSensors1WireTable OBJECT-TYPE
SYNTAX SEQUENCE OF AcsSensors1WireTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains the list of detected external 1-wire sensors."
::= { acsSensors 20 }
acsSensors1WireTableEntry OBJECT-TYPE
SYNTAX AcsSensors1WireTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Each entry has the information about the external 1-wire sensor."
INDEX { acsSensors1WireTableIndex }
::= { acsSensors1WireTable 1 }
AcsSensors1WireTableEntry ::= SEQUENCE {
acsSensors1WireTableIndex Integer32,
acsSensors1WireTableName DisplayString,
acsSensors1WireTableLocation DisplayString,
acsSensors1WireTableAddress DisplayString,
acsSensors1WireTableType INTEGER,
acsSensors1WireTableUnit INTEGER,
acsSensors1WireTableValue DisplayString,
acsSensors1WireTableValueMax Integer32,
acsSensors1WireTableValueMin Integer32,
acsSensors1WireTableValueAvg Integer32,
acsSensors1WireTableValueLowWarning Integer32,
acsSensors1WireTableValueLowCritical Integer32,
acsSensors1WireTableValueHighWarning Integer32,
acsSensors1WireTableValueHighCritical Integer32,
acsSensors1WireTableReset INTEGER,
acsSensors1WireTableAnalogAlarm INTEGER,
acsSensors1WireTableContactAlarm1 INTEGER,
acsSensors1WireTableContactAlarm2 INTEGER,
acsSensors1WireTableContactAlarm3 INTEGER,
acsSensors1WireTableLeakFilterTime INTEGER,
acsSensors1WireTableLeakAlarm INTEGER,
acsSensors1WireTableLeakCableFailAlarm INTEGER
}
acsSensors1WireTableIndex OBJECT-TYPE
SYNTAX Integer32 (1..20)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Index of detected 1-wire sensor."
::= { acsSensors1WireTableEntry 1 }
acsSensors1WireTableName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Name of the 1-wire sensor."
::= { acsSensors1WireTableEntry 2 }
acsSensors1WireTableLocation OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Location of the 1-wire sensor."
::= { acsSensors1WireTableEntry 3 }
acsSensors1WireTableAddress OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Address of the 1-wire sensor."
::= { acsSensors1WireTableEntry 4 }
acsSensors1WireTableType OBJECT-TYPE
SYNTAX INTEGER {
sensor-unknown(0),
external-temperature(1),
external-humidity(2),
door-contact(3),
dry-contact(4),
leak(5),
differential-pressure(6)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of 1-wire sensor."
::= { acsSensors1WireTableEntry 5 }
acsSensors1WireTableUnit OBJECT-TYPE
SYNTAX INTEGER {
notApplicable(0),
celsius(1),
fahrenheit(2),
percent(3),
pa(4)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The unit of the 1-wire sensor.
notApplicable(0) = used for contact or leak sensor
celsius(1) = used for temperature sensor
fahrenheit(2) = used for temperature sensor
percent(3) = used for humidity sensor
pascal(4) = used for differential pressure sensor."
::= { acsSensors1WireTableEntry 6 }
acsSensors1WireTableValue OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Current sensor reading."
::= { acsSensors1WireTableEntry 7 }
acsSensors1WireTableValueMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Maximum sensor reading detected. Unit is specified in acsSensors1WireTableUnit."
::= { acsSensors1WireTableEntry 8 }
acsSensors1WireTableValueMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Minimum sensor reading detected. Unit is specified in acsSensors1WireTableUnit."
::= { acsSensors1WireTableEntry 9 }
acsSensors1WireTableValueAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Average sensor reading detected. Unit is specified in acsSensors1WireTableUnit."
::= { acsSensors1WireTableEntry 10 }
acsSensors1WireTableValueLowWarning OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "If the sensor value falls below this value, an event notification
will be generated. Unit is specified in acsSensors1WireTableUnit."
::= { acsSensors1WireTableEntry 11 }
acsSensors1WireTableValueLowCritical OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION "If the sensor value falls below this value, an event notification
will be generated. Unit is specified in acsSensors1WireTableUnit."
::= { acsSensors1WireTableEntry 12 }
acsSensors1WireTableValueHighWarning OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION "If the sensor value rises above this value, an event notification
will be generated. Unit is specified in acsSensors1WireTableUnit."
::= { acsSensors1WireTableEntry 13 }
acsSensors1WireTableValueHighCritical OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION "If the sensor value rises above this value, an event notification
will be generated. Unit is specified in acsSensors1WireTableUnit."
::= { acsSensors1WireTableEntry 14 }
acsSensors1WireTableReset OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
reset(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A set value of update(2) will reset the 1-wire sensor min/max/avg values."
::= { acsSensors1WireTableEntry 15 }
acsSensors1WireTableAnalogAlarm OBJECT-TYPE
SYNTAX INTEGER {
notApplicable(0),
disabled(1),
enabled(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Status of the 1-wire analog sensor alarm.
Used for temperature, humidity, and differential pressure sensors only.
For all other sensor types the value notApplicable(0) will be returned."
::= { acsSensors1WireTableEntry 16 }
acsSensors1WireTableContactAlarm1 OBJECT-TYPE
SYNTAX INTEGER {
notApplicable(0),
disabled(1),
alarmWhenOpen(2),
alarmWhenClosed(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Status of the 1-wire contact sensor alarm.
Used for door and dry contact sensors only.
For all other sensor types the value notApplicable(0) will be returned."
::= { acsSensors1WireTableEntry 17 }
acsSensors1WireTableContactAlarm2 OBJECT-TYPE
SYNTAX INTEGER {
notApplicable(0),
disabled(1),
alarmWhenOpen(2),
alarmWhenClosed(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Status of the 1-wire contact sensor alarm.
Used for door and dry contact sensors only.
For all other sensor types the value notApplicable(0) will be returned."
::= { acsSensors1WireTableEntry 18 }
acsSensors1WireTableContactAlarm3 OBJECT-TYPE
SYNTAX INTEGER {
notApplicable(0),
disabled(1),
alarmWhenOpen(2),
alarmWhenClosed(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Status of the 1-wire contact sensor alarm.
Used for door and dry contact sensors only.
For all other sensor types the value notApplicable(0) will be returned."
::= { acsSensors1WireTableEntry 19 }
acsSensors1WireTableLeakFilterTime OBJECT-TYPE
SYNTAX INTEGER {
notApplicable(0),
filter-time-15(1),
filter-time-30(2),
filter-time-60(3),
filter-time-120(4)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Leak filter time in seconds."
::= { acsSensors1WireTableEntry 20 }
acsSensors1WireTableLeakAlarm OBJECT-TYPE
SYNTAX INTEGER {
notApplicable(0),
disabled(1),
enabled(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Status of the leak alarm for the leak sensor.
Used for leak sensors only.
For all other sensor types the value notApplicable(0) will be returned."
::= { acsSensors1WireTableEntry 21 }
acsSensors1WireTableLeakCableFailAlarm OBJECT-TYPE
SYNTAX INTEGER {
notApplicable(0),
disabled(1),
enabled(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Status of the cable fail alarm for the leak sensor.
Used for leak sensors only.
For all other sensor types the value notApplicable(0) will be returned."
::= { acsSensors1WireTableEntry 22 }
acsSensorsDigitalInTable OBJECT-TYPE
SYNTAX SEQUENCE OF AcsSensorsDigitalInTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains the list of Digital In sensors."
::= { acsSensors 21 }
acsSensorsDigitalInTableEntry OBJECT-TYPE
SYNTAX AcsSensorsDigitalInTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Each entry has the information about the Digital In sensor."
INDEX { acsSensorsDigitalInTablePosition }
::= { acsSensorsDigitalInTable 1 }
AcsSensorsDigitalInTableEntry ::= SEQUENCE {
acsSensorsDigitalInTablePosition Integer32,
acsSensorsDigitalInTableName DisplayString,
acsSensorsDigitalInTableLocation DisplayString,
acsSensorsDigitalInTableType INTEGER,
acsSensorsDigitalInTableValue INTEGER,
acsSensorsDigitalInTableAlarm INTEGER
}
acsSensorsDigitalInTablePosition OBJECT-TYPE
SYNTAX Integer32 (1..4)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Position of the Digital In sensor."
::= { acsSensorsDigitalInTableEntry 1 }
acsSensorsDigitalInTableName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Name of the Digital In sensor."
::= { acsSensorsDigitalInTableEntry 2 }
acsSensorsDigitalInTableLocation OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Location of the Digital In sensor."
::= { acsSensorsDigitalInTableEntry 3 }
acsSensorsDigitalInTableType OBJECT-TYPE
SYNTAX INTEGER {
custom(0),
vibration(1),
smoke-ad-s(2),
leak-sn-l(3),
door(4),
motion-ad-im(5)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Configurable type of Digital In sensor."
::= { acsSensorsDigitalInTableEntry 4 }
acsSensorsDigitalInTableValue OBJECT-TYPE
SYNTAX INTEGER {
undefined(0),
open(1),
closed(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Value of the Digital In sensor."
::= { acsSensorsDigitalInTableEntry 5 }
acsSensorsDigitalInTableAlarm OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
alarmWhenOpen(2),
alarmWhenClosed(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Status of the Digital In sensor alarm."
::= { acsSensorsDigitalInTableEntry 6 }
--
-- acsModems
-- OBJECT IDENTIFIER ::= { acsManagement 8 } 10418.26.2.8
--
acsModemsNumberOfModems OBJECT-TYPE
SYNTAX Integer32 (0..64)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of modems, including auxiliary port built-in modems,
pluggable USB modems, and serial port modems."
::= { acsModems 1 }
acsModemsTable OBJECT-TYPE
SYNTAX SEQUENCE OF AcsModemsTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains information about the ACS modems,
including auxiliary port built-in modem, pluggable USB
modems, and serial port modems."
::= { acsModems 2 }
acsModemsTableEntry OBJECT-TYPE
SYNTAX AcsModemsTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Each entry has the information about a specific modem."
INDEX { acsModemsTableNumber }
::= { acsModemsTable 1 }
AcsModemsTableEntry ::= SEQUENCE {
acsModemsTableNumber Integer32,
acsModemsTableDeviceName DisplayString,
acsModemsTableStatus INTEGER,
acsModemsTableProfile INTEGER,
acsModemsTablePhoneNumber DisplayString,
acsModemsTableComSpeed INTEGER,
acsModemsTableInitChat DisplayString,
acsModemsTablePppAddressConfig INTEGER,
acsModemsTableLocalIpv4Address DisplayString,
acsModemsTableRemoteIpv4Address DisplayString,
acsModemsTableLocalIPv6Address DisplayString,
acsModemsTableRemoteIPv6Address DisplayString,
acsModemsTablePppAuthentication INTEGER,
acsModemsTablePppRemoteUsername DisplayString,
acsModemsTablePppRemotePassphrase DisplayString,
acsModemsTableChapInterval INTEGER,
acsModemsTableChapMaxChallenge INTEGER,
acsModemsTableChapRestart INTEGER,
acsModemsTablePppIdleTimeout INTEGER,
acsModemsTableModel DisplayString,
acsModemsTableCellProvider DisplayString,
acsModemsTableCellRegistration DisplayString,
acsModemsTableCCID DisplayString,
acsModemsTableIMSI DisplayString,
acsModemsTableIMEI DisplayString,
acsModemsTableCellStatus DisplayString,
acsModemsTableAPN DisplayString,
acsModemsTableMtuSize INTEGER,
acsModemsTableReplaceDefaultRoute INTEGER,
acsModemsTablePersistMode INTEGER,
acsModemsTableSignalQualityCheck INTEGER,
acsModemsTableSignalQualityDisplay DisplayString,
acsModemsTableSIMStatus INTEGER,
acsModemsTableSIMPINEntry DisplayString,
acsModemsTableSIMUnlockCodeEntry DisplayString,
acsModemsTableCellTestLastStarted DisplayString,
acsModemsTableCellTestLastResult DisplayString
}
acsModemsTableNumber OBJECT-TYPE
SYNTAX Integer32 (1..49)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A unique index representing an entry in this table.
"
::= { acsModemsTableEntry 1 }
acsModemsTableDeviceName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..25))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The associated device name for the modem."
::= { acsModemsTableEntry 2 }
acsModemsTableStatus OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
enabled(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disbles the modem."
::= { acsModemsTableEntry 3 }
acsModemsTableProfile OBJECT-TYPE
SYNTAX INTEGER {
unconfigured(1),
dialIn(2),
dialOut(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The modem profile. For an integrated cell modem, only dial-out(3) is valid."
::= { acsModemsTableEntry 4 }
acsModemsTablePhoneNumber OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..25))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The dial-out phone number. Only supported if acsModemsTableProfile is
set to dial-out(3). Not used for integrated cellular modem."
::= { acsModemsTableEntry 5 }
acsModemsTableComSpeed OBJECT-TYPE
SYNTAX INTEGER {
speed1200(1200),
speed2400(2400),
speed4800(4800),
speed9600(9600),
speed19200(19200),
speed38400(38400),
speed57600(57600),
speed115200(115200),
speed230400(230400),
speed460800(460800),
speed921600(921600)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The modem speed. Speeds above 230400 not supported by serial port modems."
::= { acsModemsTableEntry 6 }
acsModemsTableInitChat OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..1200))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Modem initialization string."
::= { acsModemsTableEntry 7 }
acsModemsTablePppAddressConfig OBJECT-TYPE
SYNTAX INTEGER {
notApplicable(0),
none(1),
local(2),
remote(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Supported only if acsModemsTableProfile is set to dial-out(2).
If none(1) or remote(3) is set, then the IP address fields will be cleared.
When at least one IP address is set, this value will be local(2).
If remote(3) is set, the remote peer should send both IP addresses (local
and remote) during negotiation."
::= { acsModemsTableEntry 8 }
acsModemsTableLocalIpv4Address OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..46))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Configures the local IPv4 address for the PPP connection."
::= { acsModemsTableEntry 9 }
acsModemsTableRemoteIpv4Address OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..46))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Configures the remote IPv4 address for the PPP connection."
::= { acsModemsTableEntry 10 }
acsModemsTableLocalIPv6Address OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..46))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Configures the local IPv6 address for the PPP connection."
::= { acsModemsTableEntry 11 }
acsModemsTableRemoteIPv6Address OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..46))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Configures the remote IPv6 address for the PPP connection."
::= { acsModemsTableEntry 12 }
acsModemsTablePppAuthentication OBJECT-TYPE
SYNTAX INTEGER {
noAuth(1),
localPap(2),
localChap(3),
localEap(4),
remoteChap(5),
remotePap(6)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Configure the PPP authentication protocol. If this is set to remoteChap(5) or
remotePap(6), then you must also set acsModemsTablePppRemoteUsername
and acsModemsTablePppRemotePassphrase."
::= { acsModemsTableEntry 13 }
acsModemsTablePppRemoteUsername OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Only used if acsModemsTablePppAuthentication is set to
remoteChap(5) or remotePap(6)."
::= { acsModemsTableEntry 14 }
acsModemsTablePppRemotePassphrase OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Only used if acsModemsTablePppAuthentication is set to
remoteChap(5) or remotePap(6)."
::= { acsModemsTableEntry 15 }
acsModemsTableChapInterval OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"CHAP Interval in seconds. Default is 0.
Not used for integrated cellular modem."
::= { acsModemsTableEntry 16 }
acsModemsTableChapMaxChallenge OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"CHAP Max Challenge value in seconds. Default is 10 seconds.
Not used for integrated cellular modem."
::= { acsModemsTableEntry 17 }
acsModemsTableChapRestart OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"CHAP Restart value in seconds. Default is 3 seconds.
Not used for integrated cellular modem."
::= { acsModemsTableEntry 18 }
acsModemsTablePppIdleTimeout OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"PPP idle timeout value in seconds. Default is 0.
Not used for integrated cellular modem."
::= { acsModemsTableEntry 19 }
acsModemsTableModel OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Modem vendor model name. Only used for integrated cellular modem."
::= { acsModemsTableEntry 20 }
acsModemsTableCellProvider OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Cellular modem service provider. Only used for integrated cellular modem."
::= { acsModemsTableEntry 21 }
acsModemsTableCellRegistration OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Cellular modem network registration. Only used for integrated cellular modem."
::= { acsModemsTableEntry 22 }
acsModemsTableCCID OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SIM integrated circuit card identifier. Only used for integrated
cellular modem."
::= { acsModemsTableEntry 23 }
acsModemsTableIMSI OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"International mobile subscriber identity. Only used for integrated
cellular modem."
::= { acsModemsTableEntry 24 }
acsModemsTableIMEI OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"International mobile equipment identity. Only used for integrated
cellular modem."
::= { acsModemsTableEntry 25 }
acsModemsTableCellStatus OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..80))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Shows the status of the cellular modem. Only used for integrated
cellular modem."
::= { acsModemsTableEntry 26 }
acsModemsTableAPN OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..40))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Access point name. Only used for integrated cellular modem."
::= { acsModemsTableEntry 27 }
acsModemsTableMtuSize OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The maxiumum transmission unit size for use by the integrated cellular modem."
::= { acsModemsTableEntry 28 }
acsModemsTableReplaceDefaultRoute OBJECT-TYPE
SYNTAX INTEGER {
notApplicable(0),
disabled(1),
enabled(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"If this is set to enabled(2), then the integrated cellular modem
becomes the default gateway. Only used for integrated cellular
modem."
::= { acsModemsTableEntry 29 }
acsModemsTablePersistMode OBJECT-TYPE
SYNTAX INTEGER {
notApplicable(0),
disabled(1),
enabled(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"If this is set to 'yes' then the integrated cellular modem connection persists.
Only used for integrated cellular modem."
::= { acsModemsTableEntry 30 }
acsModemsTableSignalQualityCheck OBJECT-TYPE
SYNTAX INTEGER {
notApplicable(0),
no-action (1),
signalCheck (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Check the signal quality of the integrated cellular modem. This
turns on the modem transceiver to get the signal. The signal quality can be read
in acsModemsTableSignalQualityDisplay."
::= { acsModemsTableEntry 31 }
acsModemsTableSignalQualityDisplay OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..80))
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Displays the last read signal quality of the integrated cellular modem.
To refresh this value write signalCheck(2) to acsModemsTableSignalQualityCheck."
::= { acsModemsTableEntry 32 }
acsModemsTableSIMStatus OBJECT-TYPE
SYNTAX INTEGER {
unknown(0),
ready(1),
waitingForPIN(2),
waitingForUnlockCode(3),
errorReadingSIM(4)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status of the modem SIM card. Only used for integrated cellular modem."
::= { acsModemsTableEntry 33 }
acsModemsTableSIMPINEntry OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..80))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Modem SIM card PIN/Password entry. Writable only if acsModemsTableSIMStatus
returns waitingForPIN(2). Only used for integrated cellular modem."
::= { acsModemsTableEntry 34 }
acsModemsTableSIMUnlockCodeEntry OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..80))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Modem SIM card Unlock Code entry. Writable only if acsModemsTableSIMStatus
returns waitingForUnlockCode(3). Only used for integrated cellular modem."
::= { acsModemsTableEntry 35 }
acsModemsTableCellTestLastStarted OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The timestamp of the last time the Cell Modem IP Test started running.
Only used for integrated cellular modem."
::= { acsModemsTableEntry 36 }
acsModemsTableCellTestLastResult OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..256) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The result of the last time the Cell Modem IP Test was run.
Only used for integrated cellular modem."
::= { acsModemsTableEntry 37 }
END