SYNLINK-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
MODULE-IDENTITY, OBJECT-TYPE,
|
|
enterprises, Integer32, NOTIFICATION-TYPE, IpAddress
|
|
FROM SNMPv2-SMI
|
|
DisplayString, TruthValue, TEXTUAL-CONVENTION
|
|
FROM SNMPv2-TC
|
|
OBJECT-GROUP, MODULE-COMPLIANCE, NOTIFICATION-GROUP
|
|
FROM SNMPv2-CONF;
|
|
|
|
--inetAddressType, InetAddress, InetPortNumber
|
|
-- FROM INET-ADDRESS-MIB
|
|
-- sysContact, sysName, sysLocation
|
|
-- FROM RFC1213-MIB;
|
|
|
|
synlink MODULE-IDENTITY
|
|
LAST-UPDATED "202311010000Z" -- November 1, 2023
|
|
ORGANIZATION "Synaccess Networks Inc"
|
|
CONTACT-INFO "
|
|
Author: Engineering Dept.
|
|
Synaccess Networks
|
|
postal: 8147 E Evans Rd Ste 3,
|
|
Scottsdale, AZ 85260
|
|
email: support@synaccess-net.com
|
|
"
|
|
DESCRIPTION "MIB File for SynLink PDUs SNMP functionality"
|
|
REVISION "202003300000Z"
|
|
DESCRIPTION "Init"
|
|
::= { synaccess 4 }
|
|
|
|
synaccess OBJECT IDENTIFIER ::= { enterprises 21728 }
|
|
|
|
device OBJECT IDENTIFIER ::= { synlink 1 }
|
|
inlets OBJECT IDENTIFIER ::= { synlink 2 }
|
|
banks OBJECT IDENTIFIER ::= { synlink 4 }
|
|
outlets OBJECT IDENTIFIER ::= { synlink 5 }
|
|
groups OBJECT IDENTIFIER ::= { synlink 6 }
|
|
sensors OBJECT IDENTIFIER ::= { synlink 7 }
|
|
logs OBJECT IDENTIFIER ::= { synlink 8 }
|
|
events OBJECT IDENTIFIER ::= { synlink 9 }
|
|
conformance OBJECT IDENTIFIER ::= { synlink 10 }
|
|
|
|
RelayEnumeration ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Relay States"
|
|
SYNTAX INTEGER { open(0),
|
|
closed(1)
|
|
}
|
|
|
|
synLinkModel OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..12))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The model number of SynLink PDU"
|
|
::= { device 1 }
|
|
|
|
enclosureSerialNumber OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..12))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Serial number of SynLink PDU Controller and Enclosure"
|
|
::= { device 2 }
|
|
|
|
controllerSerialNumber OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..12))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Serial number of SynLink PDU Controller and Enclosure"
|
|
::= { device 3 }
|
|
|
|
inletConfiguration OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..20))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Either 'standard', 'dualcircuit', or 'ats'"
|
|
::= { device 4 }
|
|
|
|
numOutlets OBJECT-TYPE
|
|
SYNTAX Integer32 (0..3)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of outlets on PDU"
|
|
::= { device 5 }
|
|
|
|
numBanks OBJECT-TYPE
|
|
SYNTAX Integer32 (0..3)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of banks currently connected"
|
|
::= { device 6 }
|
|
|
|
phase OBJECT-TYPE
|
|
SYNTAX Integer32 (0..3)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"1 for single phase. 2 for 3 phase delta. 3 for 3 phase wye."
|
|
::= { device 7 }
|
|
|
|
numInlets OBJECT-TYPE
|
|
SYNTAX Integer32 (0..3)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of Inlets. Either 1 or 2. ATS Dual inlets count as a single inlet."
|
|
::= { device 8 }
|
|
|
|
outletPwrMeasurementsSupported OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Describes if individual outlet current measurements is supported"
|
|
::= { device 9 }
|
|
|
|
outletSwitchingSupported OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Describes if individual outlet switching is supported"
|
|
::= { device 10 }
|
|
|
|
deviceName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User defined name for device"
|
|
::= { device 11 }
|
|
|
|
deviceIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"IP Address for device."
|
|
::= { device 12 }
|
|
|
|
--
|
|
|
|
inletTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF InletSchema
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table of all inlets entries. Inlet Entry includes information about plug type, power capacity number of poles and more."
|
|
::= { inlets 1 }
|
|
|
|
inletEntry OBJECT-TYPE
|
|
SYNTAX InletSchema
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Inlet Object for an individual inlet instance."
|
|
INDEX { inletIndex }
|
|
::= { inletTable 1 }
|
|
|
|
|
|
inletIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Which number inlet it is."
|
|
::= { inletEntry 1 }
|
|
|
|
inletType OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Describes which type of setup the inlet is part of. Single for one input plug. Double for two simultaneously used input plugs. ATS (Auto Transfer Switch) for 2 inputs with primary and secondary redundancy."
|
|
::= { inletEntry 2 }
|
|
|
|
inletPlug OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The type of Inlet Plug Connector."
|
|
::={ inletEntry 3 }
|
|
|
|
inletName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User defined name for Inlet"
|
|
::={ inletEntry 4 }
|
|
|
|
inletEnergyAccumulation OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"kWH value to show energy consumption for inlet plug"
|
|
::={ inletEntry 5 }
|
|
|
|
inletPowerFactor OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Power factor value for inlet plug"
|
|
::={ inletEntry 6 }
|
|
|
|
inletPhase OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Possibilities are: Single Phase, 3 Phase Delta, or 3 Phase Wye"
|
|
::={ inletEntry 7 }
|
|
|
|
inletUuid OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unique identifier for Inlet"
|
|
::= { inletEntry 8 }
|
|
|
|
-- 3 phase attributes start --
|
|
|
|
inlet3PhaseBalance OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Percentage of imbalance in 3 phase inlet. Calculated with largest difference of any 2 lines, divided by average current. All times 100."
|
|
::={ inletEntry 9 }
|
|
|
|
inletLine1CurrentRms OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Line 1 of 3 phase inlet Current RMS in Amperes"
|
|
::={ inletEntry 10 }
|
|
|
|
inletLine2CurrentRms OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Line 2 of 3 phase inlet Current RMS in Amperes"
|
|
::={ inletEntry 11 }
|
|
|
|
inletLine3CurrentRms OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Line 3 of 3 phase inlet Current RMS in Amperes"
|
|
::={ inletEntry 12 }
|
|
|
|
-- 3 phase attributes end --
|
|
|
|
-- 1 phase attributes start --
|
|
|
|
inletLineConfiguration OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Applies only to single phase. Options are L-L, L-N, or L-L\N"
|
|
::={ inletEntry 13 }
|
|
|
|
inletActivePower OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Inlet Active Power in watts"
|
|
::={ inletEntry 14 }
|
|
|
|
inletApparentPower OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Inlet Apparent Power in Volt-amperes (VA)"
|
|
::={ inletEntry 15 }
|
|
|
|
inletReactivePower OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Inlet Reactive Power in Volt-Amps-Reactive (VAR)"
|
|
::={ inletEntry 16 }
|
|
|
|
inletCurrentRms OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Inlet current draw in amps"
|
|
::={ inletEntry 17 }
|
|
|
|
inletLineFrequency OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Inlet line frequency in hertz"
|
|
::={ inletEntry 18 }
|
|
|
|
inletVoltageRms OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Inlet voltage RMS in volts"
|
|
::={ inletEntry 19 }
|
|
|
|
-- ats attributes start --
|
|
|
|
atsActiveInlet OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"If inputType is 'ats' then this value will be true if it is the currently used inlet. False if the inlet is not in use."
|
|
::={ inletEntry 20 }
|
|
|
|
atsInletId OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Should be A (primary) or B (secondary) for two ATS inputs"
|
|
::={ inletEntry 21 }
|
|
|
|
atsInletReady OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Whether the Inlet is ready to be used as a power source"
|
|
::={ inletEntry 22 }
|
|
|
|
-- ats attributes end --
|
|
|
|
-- 1 phase attributes end --
|
|
|
|
InletSchema ::= SEQUENCE {
|
|
inletIndex Integer32,
|
|
inletType DisplayString,
|
|
inletPlug DisplayString,
|
|
inletName DisplayString,
|
|
inletEnergyAccumulation Integer32,
|
|
inletPowerFactor Integer32,
|
|
inletPhase DisplayString,
|
|
inletUuid DisplayString,
|
|
inlet3PhaseBalance Integer32,
|
|
inletLine1CurrentRms Integer32,
|
|
inletLine2CurrentRms Integer32,
|
|
inletLine3CurrentRms Integer32,
|
|
inletLineConfiguration DisplayString,
|
|
inletActivePower Integer32,
|
|
inletApparentPower Integer32,
|
|
inletReactivePower Integer32,
|
|
inletCurrentRms Integer32,
|
|
inletLineFrequency Integer32,
|
|
inletVoltageRms Integer32,
|
|
atsActiveInlet TruthValue,
|
|
atsInletId DisplayString,
|
|
atsInletReady TruthValue
|
|
}
|
|
|
|
--
|
|
|
|
|
|
bankTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF BankSchema
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table of bank instances."
|
|
::= { banks 1 }
|
|
|
|
bankEntry OBJECT-TYPE
|
|
SYNTAX BankSchema
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Bank object for a particular outlet bank."
|
|
INDEX { bankIndex }
|
|
::= { bankTable 1 }
|
|
|
|
|
|
bankIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Which number bank it is."
|
|
::= { bankEntry 1 }
|
|
|
|
bankUuid OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unique Identifier for Bank"
|
|
::= { bankEntry 2 }
|
|
|
|
bankOutletSwitchingSupported OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Describes if bank outlets have relays for switching"
|
|
::= { bankEntry 3 }
|
|
|
|
bankOutletMeteringSupported OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Describes if bank outlets can measure individual outlet current in amps"
|
|
::= { bankEntry 4 }
|
|
|
|
bankCurrentRms OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Current RMS of all outlets on bank in Amperes."
|
|
::= { bankEntry 5 }
|
|
|
|
bankVoltage OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Voltage of bank."
|
|
::= { bankEntry 6 }
|
|
|
|
bankLineFrequency OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Line Frequency of bank."
|
|
::= { bankEntry 7 }
|
|
|
|
bankPowerFactor OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Bank Power factor"
|
|
::= { bankEntry 8 }
|
|
|
|
bankLines OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Specific Lines or line configuration which this bank is utilizing"
|
|
::= { bankEntry 9 }
|
|
|
|
bankActivePower OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Active Power of bank."
|
|
::= { bankEntry 10 }
|
|
|
|
bankReactivePower OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reactive Power of bank."
|
|
::= { bankEntry 11 }
|
|
|
|
bankApparentPower OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Apparent Power of bank."
|
|
::= { bankEntry 12 }
|
|
|
|
bankName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User defined bank name."
|
|
::= { bankEntry 13 }
|
|
|
|
bankBreakerSupported OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"True if bank has an associated over current protector."
|
|
::= { bankEntry 14 }
|
|
|
|
bankBreakerState OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"True if breaker is working and not considered 'tripped'"
|
|
::= { bankEntry 15 }
|
|
|
|
BankSchema ::= SEQUENCE {
|
|
bankIndex Integer32,
|
|
bankUuid DisplayString,
|
|
bankOutletSwitchingSupported TruthValue,
|
|
bankOutletMeteringSupported TruthValue,
|
|
bankCurrentRms Integer32,
|
|
bankVoltage Integer32,
|
|
bankLineFrequency Integer32,
|
|
bankPowerFactor Integer32,
|
|
bankLines DisplayString,
|
|
bankActivePower Integer32,
|
|
bankReactivePower Integer32,
|
|
bankApparentPower Integer32,
|
|
bankName DisplayString,
|
|
bankBreakerSupported TruthValue,
|
|
bankBreakerState TruthValue
|
|
|
|
}
|
|
|
|
outletTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF OutletSchema
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table of outlet instances."
|
|
::= { outlets 1 }
|
|
|
|
outletEntry OBJECT-TYPE
|
|
SYNTAX OutletSchema
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet object for a particular input line."
|
|
INDEX { outletIndex }
|
|
::= { outletTable 1 }
|
|
|
|
outletIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Which number outlet it is."
|
|
::= { outletEntry 1 }
|
|
|
|
outletUuid OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unique identifier for outlet"
|
|
::= { outletEntry 2 }
|
|
|
|
outletName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User defined name for outlet."
|
|
::= { outletEntry 3 }
|
|
|
|
-- outletPwrOnState OBJECT-TYPE
|
|
-- SYNTAX DisplayString
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Can either be on, off, prev (previous). When PDU boots, outlet will be at this state."
|
|
-- ::= { outletEntry 4 }
|
|
|
|
-- outletBankIndex OBJECT-TYPE
|
|
-- SYNTAX Integer32
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Which number outlet within bank."
|
|
-- ::= { outletEntry 5 }
|
|
|
|
outletCurrentRms OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Current RMS in Amperes for individual outlet if supported."
|
|
::= { outletEntry 6 }
|
|
|
|
outletState OBJECT-TYPE
|
|
SYNTAX RelayEnumeration
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of relay. '0' means outlet is off (relay is open). '1' means outlet is on (relay is closed). Set '2' to power cycle outlet."
|
|
::= { outletEntry 7 }
|
|
|
|
outletConnector OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Type of Outlet Receptacle."
|
|
::= { outletEntry 8 }
|
|
|
|
-- outletSetState OBJECT-TYPE
|
|
-- SYNTAX Integer32
|
|
-- MAX-ACCESS read-write
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "'0' for off, '1' to switch on, '3' to power cycle"
|
|
-- ::= { outletEntry 10 }
|
|
|
|
-- outletMaxCurrent OBJECT-TYPE
|
|
-- SYNTAX Integer32
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Maximum current allowed for outlet."
|
|
-- ::= { outletEntry 9 }
|
|
|
|
-- outletReboot OBJECT-TYPE
|
|
-- SYNTAX TruthValue
|
|
-- MAX-ACCESS read-write
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "TODO"
|
|
-- ::= { outletEntry 11 }
|
|
|
|
|
|
OutletSchema ::= SEQUENCE {
|
|
outletIndex Integer32,
|
|
outletUuid DisplayString,
|
|
outletName DisplayString,
|
|
-- outletPwrOnState DisplayString,
|
|
-- outletBankIndex Integer32,
|
|
outletCurrentRms Integer32,
|
|
outletState RelayEnumeration,
|
|
outletConnector DisplayString
|
|
--outletSetState Integer32
|
|
--outletMaxCurrent Integer32,
|
|
--outletReboot TruthValue
|
|
}
|
|
|
|
--
|
|
|
|
groupTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF GroupEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table of all outlet groups entries. "
|
|
::= { groups 1 }
|
|
|
|
groupEntry OBJECT-TYPE
|
|
SYNTAX GroupEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Group Object for a group of outlets."
|
|
INDEX { groupIndex }
|
|
::= { groupTable 1 }
|
|
|
|
|
|
groupIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Which number group it is."
|
|
::= { groupEntry 1 }
|
|
|
|
groupName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User defined name for group"
|
|
::= { groupEntry 2 }
|
|
|
|
groupUuid OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unique identifier for group"
|
|
::= { groupEntry 3 }
|
|
|
|
groupSetState OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Set all outlets within state to given state. On for on, off for off."
|
|
::= { groupEntry 4 }
|
|
|
|
groupReboot OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reboot all outlets within a group"
|
|
::= { groupEntry 5 }
|
|
|
|
groupCurrentRms OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Current RMS sum of all outlet current measurements. Available only of outlet metering supported."
|
|
::= { groupEntry 6 }
|
|
|
|
GroupEntry ::= SEQUENCE {
|
|
groupIndex Integer32,
|
|
groupName DisplayString,
|
|
groupUuid DisplayString,
|
|
groupSetState TruthValue,
|
|
groupReboot TruthValue,
|
|
groupCurrentRms Integer32
|
|
}
|
|
|
|
--
|
|
|
|
|
|
sensorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF SensorSchema
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table of Sensor entries."
|
|
::= { sensors 1 }
|
|
|
|
sensorEntry OBJECT-TYPE
|
|
SYNTAX SensorSchema
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sensor instance."
|
|
INDEX { sensorIndex }
|
|
::= { sensorTable 1 }
|
|
|
|
sensorIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of sensor"
|
|
::= { sensorEntry 1 }
|
|
|
|
sensorType OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Type of sensor. hum_temp for humidity & temp sensor"
|
|
::= { sensorEntry 2 }
|
|
|
|
sensorTemp OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature if supported in celsius. sensorTempOffset is added to raw value to generate output of this OID."
|
|
::= { sensorEntry 3 }
|
|
|
|
sensorHumidity OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Humidity if supported in percentage humidity. sensorHumidityOffset is added to raw value to generate output of this OID."
|
|
::= { sensorEntry 4 }
|
|
|
|
sensorTempOffset OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Offset for temperature. Signed value."
|
|
::= { sensorEntry 5 }
|
|
|
|
sensorHumidityOffset OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Offset for humidity. Signed Value"
|
|
::= { sensorEntry 6 }
|
|
|
|
sensorName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User defined name for sensor"
|
|
::= { sensorEntry 7 }
|
|
|
|
SensorSchema ::= SEQUENCE {
|
|
sensorIndex Integer32,
|
|
sensorType DisplayString,
|
|
sensorTemp Integer32,
|
|
sensorHumidity Integer32,
|
|
sensorTempOffset Integer32,
|
|
sensorHumidityOffset Integer32,
|
|
sensorName DisplayString
|
|
}
|
|
--
|
|
|
|
|
|
powerLogTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PowerLogSchema
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table of all logging metric related to power"
|
|
::= { logs 1 }
|
|
|
|
powerLogEntry OBJECT-TYPE
|
|
SYNTAX PowerLogSchema
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Instance of logging metric"
|
|
INDEX { pwrLogIndex }
|
|
::= { powerLogTable 1 }
|
|
|
|
|
|
pwrLogIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"ID for log entry"
|
|
::= { powerLogEntry 1 }
|
|
|
|
pwrLogType OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Type of logging metric. Can be "
|
|
::= { powerLogEntry 2 }
|
|
|
|
pwrLogValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Various types. Current values."
|
|
::= { powerLogEntry 3 }
|
|
|
|
PowerLogSchema ::= SEQUENCE {
|
|
pwrLogIndex Integer32,
|
|
pwrLogType DisplayString, -- change to custom enum
|
|
pwrLogValue Integer32
|
|
}
|
|
--
|
|
|
|
environmentLogTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF EnvironmentLogSchema
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table of all logging metric related to temperature and humidity"
|
|
::= { logs 2 }
|
|
|
|
environmentLogEntry OBJECT-TYPE
|
|
SYNTAX EnvironmentLogSchema
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Instance of logging metric"
|
|
INDEX { envLogIndex }
|
|
::= { environmentLogTable 1 }
|
|
|
|
|
|
envLogIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"ID for log entry"
|
|
::= { environmentLogEntry 1 }
|
|
|
|
envLogType OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Type of logging metric. Can be temp or humidity"
|
|
::= { environmentLogEntry 2 }
|
|
|
|
envLogValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Either temp in celsius or humidity in percentage"
|
|
::= { environmentLogEntry 3 }
|
|
|
|
EnvironmentLogSchema ::= SEQUENCE {
|
|
envLogIndex Integer32,
|
|
envLogType DisplayString, -- change to custom enum
|
|
envLogValue Integer32
|
|
}
|
|
|
|
|
|
eventTriggers OBJECT IDENTIFIER ::= { events 2 }
|
|
|
|
eventTriggerTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF EventTriggerSchema
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table of all Event Triggers"
|
|
::= { eventTriggers 1 }
|
|
|
|
eventTriggerEntry OBJECT-TYPE
|
|
SYNTAX EventTriggerSchema
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Instance of Event Trigger"
|
|
INDEX { eventTriggerIndex }
|
|
::= { eventTriggerTable 1 }
|
|
|
|
eventTriggerIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"ID for event trigger entry"
|
|
::= { eventTriggerEntry 1 }
|
|
|
|
eventType OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Type of event. Can be any of traps. (Show Table)"
|
|
::= { eventTriggerEntry 2 }
|
|
|
|
eventCode OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unique code for event"
|
|
::= { eventTriggerEntry 3 }
|
|
|
|
eventName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Used defined name for event trigger."
|
|
::= { eventTriggerEntry 4 }
|
|
|
|
eventTriggerAttr1 OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"First Attribute. See Event Table for details on specified Attr."
|
|
::= { eventTriggerEntry 5 }
|
|
|
|
eventTriggerAttr2 OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Second Attribute. See Event Table for details on specified Attr."
|
|
::= { eventTriggerEntry 6 }
|
|
|
|
eventTriggerAttr3 OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Third Attribute. See Event Table for details on specified Attr."
|
|
::= { eventTriggerEntry 7 }
|
|
|
|
eventIsTriggered OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Describes whether or not the trigger has met it's threshold"
|
|
::={ eventTriggerEntry 8 }
|
|
|
|
eventTriggeredTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds that this event has been triggered"
|
|
::={ eventTriggerEntry 9 }
|
|
|
|
EventTriggerSchema ::= SEQUENCE {
|
|
eventTriggerIndex Integer32,
|
|
eventType DisplayString, -- create table
|
|
eventCode Integer32,
|
|
eventName DisplayString,
|
|
eventTriggerAttr1 DisplayString,
|
|
eventTriggerAttr2 DisplayString,
|
|
eventTriggerAttr3 DisplayString,
|
|
eventIsTriggered TruthValue,
|
|
eventTriggeredTime Integer32
|
|
}
|
|
|
|
eventTraps OBJECT IDENTIFIER ::= { events 0 }
|
|
|
|
|
|
autopingTimeout NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"event description"
|
|
::= { eventTraps 1 }
|
|
|
|
line1CurrentMaxThreshold NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
inletLine1CurrentRms,
|
|
inletName,
|
|
inletPlug,
|
|
inletType,
|
|
inletLineConfiguration,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Line 1 Max current trigger"
|
|
::={ eventTraps 2 }
|
|
|
|
line2CurrentMaxThreshold NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
inletLine2CurrentRms,
|
|
inletName,
|
|
inletPlug,
|
|
inletType,
|
|
inletLineConfiguration,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Line 2 Max current trigger"
|
|
::={ eventTraps 3 }
|
|
|
|
line3CurrentMaxThreshold NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
inletLine3CurrentRms,
|
|
inletName,
|
|
inletPlug,
|
|
inletType,
|
|
inletLineConfiguration,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Line 3 Max current trigger"
|
|
::={ eventTraps 4 }
|
|
|
|
line1CurrentMinThreshold NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
inletLine1CurrentRms,
|
|
inletName,
|
|
inletPlug,
|
|
inletType,
|
|
inletLineConfiguration,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Line 1 Max current trigger"
|
|
::={ eventTraps 5 }
|
|
|
|
line2CurrentMinThreshold NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
inletLine2CurrentRms,
|
|
inletName,
|
|
inletPlug,
|
|
inletType,
|
|
inletLineConfiguration,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Line 1 Max current trigger"
|
|
::={ eventTraps 6 }
|
|
|
|
line3CurrentMinThreshold NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
inletLine3CurrentRms,
|
|
inletName,
|
|
inletPlug,
|
|
inletType,
|
|
inletLineConfiguration,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Line 1 Max current trigger"
|
|
::={ eventTraps 7 }
|
|
|
|
inletCurrentMaxThreshold NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
inletCurrentRms,
|
|
inletName,
|
|
inletPlug,
|
|
inletType,
|
|
inletLineConfiguration,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Inlet Max Current Threshold Trigger. Applies to single phase PDUs Only"
|
|
::={ eventTraps 8 }
|
|
|
|
inletCurrentMinThreshold NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
inletCurrentRms,
|
|
inletName,
|
|
inletPlug,
|
|
inletType,
|
|
inletLineConfiguration,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Inlet Max Current Threshold Trigger. Applies to single phase PDUs Only"
|
|
::={ eventTraps 9 }
|
|
|
|
inletVoltageMaxThreshold NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
inletVoltageRms,
|
|
inletName,
|
|
inletPlug,
|
|
inletType,
|
|
inletLineConfiguration,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"event description"
|
|
::= { eventTraps 10 }
|
|
|
|
inletVoltageMinThreshold NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
inletVoltageRms,
|
|
inletName,
|
|
inletPlug,
|
|
inletType,
|
|
inletLineConfiguration,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"event description"
|
|
::= { eventTraps 11 }
|
|
|
|
inletLineFrequencyMaxThreshold NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
inletLineFrequency,
|
|
inletName,
|
|
inletPlug,
|
|
inletType,
|
|
inletLineConfiguration,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"event description"
|
|
::= { eventTraps 12 }
|
|
|
|
inletLineFrequencyMinThreshold NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
inletLineFrequency,
|
|
inletName,
|
|
inletPlug,
|
|
inletType,
|
|
inletLineConfiguration,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"event description"
|
|
::= { eventTraps 13 }
|
|
|
|
inletPowerFactorMinThreshold NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
inletPowerFactor,
|
|
inletName,
|
|
inletPlug,
|
|
inletType,
|
|
inletLineConfiguration,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"event description"
|
|
::= { eventTraps 14 }
|
|
|
|
inletActiveEnergyMaxThreshold NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
inletEnergyAccumulation,
|
|
inletName,
|
|
inletPlug,
|
|
inletType,
|
|
inletLineConfiguration,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"event description"
|
|
::= { eventTraps 15 }
|
|
|
|
inletActivePowerMaxThreshold NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
inletActivePower,
|
|
inletName,
|
|
inletPlug,
|
|
inletType,
|
|
inletLineConfiguration,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"event description"
|
|
::= { eventTraps 16 }
|
|
|
|
inletActivePowerMinThreshold NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
inletActivePower,
|
|
inletName,
|
|
inletPlug,
|
|
inletType,
|
|
inletLineConfiguration,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"event description"
|
|
::= { eventTraps 17 }
|
|
|
|
|
|
inletApparentPowerMaxThreshold NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
inletApparentPower,
|
|
inletName,
|
|
inletPlug,
|
|
inletType,
|
|
inletLineConfiguration,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"event description"
|
|
::= { eventTraps 18 }
|
|
|
|
inletApparentPowerMinThreshold NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
inletApparentPower,
|
|
inletName,
|
|
inletPlug,
|
|
inletType,
|
|
inletLineConfiguration,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"event description"
|
|
::= { eventTraps 19 }
|
|
|
|
|
|
inletReactivePowerMaxThreshold NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
inletReactivePower,
|
|
inletName,
|
|
inletPlug,
|
|
inletType,
|
|
inletLineConfiguration,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"event description"
|
|
::= { eventTraps 20 }
|
|
|
|
inletReactivePowerMinThreshold NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
inletReactivePower,
|
|
inletName,
|
|
inletPlug,
|
|
inletType,
|
|
inletLineConfiguration,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"event description"
|
|
::= { eventTraps 21 }
|
|
|
|
inlet3phaseImbalance NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
inlet3PhaseBalance,
|
|
inletName,
|
|
inletPlug,
|
|
inletType,
|
|
inletLineConfiguration,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"event description"
|
|
::= { eventTraps 22 }
|
|
|
|
|
|
bankBreakerTrip NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
bankCurrentRms,
|
|
bankName,
|
|
bankLines,
|
|
bankUuid,
|
|
bankBreakerState,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"event description"
|
|
::= { eventTraps 23 }
|
|
|
|
bankCurrentMaxThreshold NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
bankCurrentRms,
|
|
bankName,
|
|
bankLines,
|
|
bankUuid,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"event description"
|
|
::= { eventTraps 24 }
|
|
|
|
bankCurrentMinThreshold NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
bankCurrentRms,
|
|
bankName,
|
|
bankLines,
|
|
bankUuid,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"event description"
|
|
::= { eventTraps 25 }
|
|
|
|
bankVoltageMaxThreshold NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
bankVoltage,
|
|
bankName,
|
|
bankLines,
|
|
bankUuid,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"event description"
|
|
::= { eventTraps 26 }
|
|
|
|
bankVoltageMinThreshold NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
bankVoltage,
|
|
bankName,
|
|
bankLines,
|
|
bankUuid,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"event description"
|
|
::= { eventTraps 27 }
|
|
|
|
bankLineFrequencyMaxThreshold NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
bankLineFrequency,
|
|
bankName,
|
|
bankLines,
|
|
bankUuid,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"event description"
|
|
::= { eventTraps 28 }
|
|
|
|
bankLineFrequencyMinThreshold NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
bankLineFrequency,
|
|
bankName,
|
|
bankLines,
|
|
bankUuid,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"event description"
|
|
::= { eventTraps 29 }
|
|
|
|
bankPowerfactorMinThreshold NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
bankPowerFactor,
|
|
bankName,
|
|
bankLines,
|
|
bankUuid,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"event description"
|
|
::= { eventTraps 30 }
|
|
|
|
--bankActiveEnergyMaxThreshold NOTIFICATION-TYPE
|
|
-- OBJECTS {
|
|
-- deviceName,
|
|
-- deviceIpAddress,
|
|
-- bankActiveEnergy,
|
|
-- bankName,
|
|
-- bankLines,
|
|
-- bankUuid,
|
|
-- eventType,
|
|
-- eventCode,
|
|
-- eventName,
|
|
-- eventTriggerAttr1,
|
|
-- eventTriggerAttr2,
|
|
-- eventTriggerAttr3
|
|
-- }
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "event description"
|
|
-- ::= { eventTraps 31 }
|
|
|
|
bankActivePowerMaxThreshold NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
bankActivePower,
|
|
bankName,
|
|
bankLines,
|
|
bankUuid,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"event description"
|
|
::= { eventTraps 32 }
|
|
|
|
bankActivePowerMinThreshold NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
bankActivePower,
|
|
bankName,
|
|
bankLines,
|
|
bankUuid,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"event description"
|
|
::= { eventTraps 33 }
|
|
|
|
bankApparentPowerMaxThreshold NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
bankApparentPower,
|
|
bankName,
|
|
bankLines,
|
|
bankUuid,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"event description"
|
|
::= { eventTraps 34 }
|
|
|
|
bankApparentPowerMinThreshold NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
bankApparentPower,
|
|
bankName,
|
|
bankLines,
|
|
bankUuid,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"event description"
|
|
::= { eventTraps 35 }
|
|
|
|
bankReactivePowerMaxThreshold NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
bankReactivePower,
|
|
bankName,
|
|
bankLines,
|
|
bankUuid,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"event description"
|
|
::= { eventTraps 36 }
|
|
|
|
bankReactivePowerMinThreshold NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
bankReactivePower,
|
|
bankName,
|
|
bankLines,
|
|
bankUuid,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"event description"
|
|
::= { eventTraps 37 }
|
|
|
|
outletCurrentMaxThreshold NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
outletCurrentRms,
|
|
outletName,
|
|
outletState,
|
|
outletConnector,
|
|
outletUuid,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"event description"
|
|
::= { eventTraps 38 }
|
|
|
|
outletCurrentMinThreshold NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
outletCurrentRms,
|
|
outletName,
|
|
outletState,
|
|
outletConnector,
|
|
outletUuid,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"event description"
|
|
::= { eventTraps 39 }
|
|
|
|
--groupCurrentMaxThreshold NOTIFICATION-TYPE
|
|
-- OBJECTS {
|
|
-- deviceName,
|
|
-- deviceIpAddress,
|
|
-- groupCurrentRms
|
|
-- }
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "event description"
|
|
-- ::= { eventTraps 40 }
|
|
|
|
--groupCurrentMinThreshold NOTIFICATION-TYPE
|
|
-- OBJECTS {
|
|
-- deviceName,
|
|
-- deviceIpAddress,
|
|
-- groupCurrentRms
|
|
-- }
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "event description"
|
|
-- ::= { eventTraps 41 }
|
|
|
|
|
|
temperatureMaxThreshold NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
sensorTemp,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"event description"
|
|
::= { eventTraps 42 }
|
|
|
|
temperatureMinThreshold NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
sensorTemp,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"event description"
|
|
::= { eventTraps 43 }
|
|
|
|
humidityMaxThreshold NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
sensorHumidity,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"event description"
|
|
::= { eventTraps 44 }
|
|
|
|
humidityMinThreshold NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
sensorHumidity,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"event description"
|
|
::= { eventTraps 45 }
|
|
|
|
scheduledTime NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"event description"
|
|
::= { eventTraps 46 }
|
|
|
|
scheduledInterval NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"event description"
|
|
::= { eventTraps 47 }
|
|
|
|
atsInletSwitchedToSecondary NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
atsActiveInlet,
|
|
atsInletId,
|
|
atsInletReady,
|
|
inletName,
|
|
inletPlug,
|
|
inletType,
|
|
inletLineConfiguration,
|
|
eventType,
|
|
eventCode,
|
|
eventName
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"event description"
|
|
::= { eventTraps 48 }
|
|
|
|
atsInletSwitchedToPrimary NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
atsActiveInlet,
|
|
atsInletId,
|
|
atsInletReady,
|
|
inletName,
|
|
inletPlug,
|
|
inletType,
|
|
inletLineConfiguration,
|
|
eventType,
|
|
eventCode,
|
|
eventName
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"event description"
|
|
::= { eventTraps 49 }
|
|
|
|
atsInletSecondaryPowerLoss NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
atsActiveInlet,
|
|
atsInletId,
|
|
atsInletReady,
|
|
inletName,
|
|
inletPlug,
|
|
inletType,
|
|
inletLineConfiguration,
|
|
eventType,
|
|
eventCode,
|
|
eventName
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"event description"
|
|
::= { eventTraps 50 }
|
|
|
|
atsInletSecondaryPowerRestored NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
deviceName,
|
|
deviceIpAddress,
|
|
atsActiveInlet,
|
|
atsInletId,
|
|
atsInletReady,
|
|
inletName,
|
|
inletPlug,
|
|
inletType,
|
|
inletLineConfiguration,
|
|
eventType,
|
|
eventCode,
|
|
eventName
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"event description"
|
|
::= { eventTraps 51 }
|
|
|
|
|
|
|
|
|
|
|
|
synLinkGroups OBJECT IDENTIFIER ::= { conformance 1 }
|
|
|
|
synLinkDeviceGroup OBJECT-GROUP
|
|
OBJECTS {
|
|
synLinkModel,
|
|
enclosureSerialNumber,
|
|
controllerSerialNumber,
|
|
inletConfiguration,
|
|
numOutlets,
|
|
numBanks,
|
|
phase,
|
|
numInlets,
|
|
outletPwrMeasurementsSupported,
|
|
outletSwitchingSupported,
|
|
deviceName,
|
|
deviceIpAddress
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device Objects Group"
|
|
::= { synLinkGroups 1 }
|
|
|
|
synLinkInletGroup OBJECT-GROUP
|
|
OBJECTS {
|
|
inletType,
|
|
inletPlug,
|
|
inletName,
|
|
inletEnergyAccumulation,
|
|
inletPowerFactor,
|
|
inletPhase,
|
|
inletUuid,
|
|
inlet3PhaseBalance,
|
|
inletLine1CurrentRms,
|
|
inletLine2CurrentRms,
|
|
inletLine3CurrentRms,
|
|
inletLineConfiguration,
|
|
inletActivePower,
|
|
inletApparentPower,
|
|
inletReactivePower,
|
|
inletCurrentRms,
|
|
inletLineFrequency,
|
|
inletVoltageRms,
|
|
atsActiveInlet,
|
|
atsInletId,
|
|
atsInletReady
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Inlet Objects Group"
|
|
::= { synLinkGroups 2 }
|
|
|
|
synLinkBankGroup OBJECT-GROUP
|
|
OBJECTS {
|
|
bankUuid,
|
|
bankOutletSwitchingSupported,
|
|
bankOutletMeteringSupported,
|
|
bankCurrentRms,
|
|
bankVoltage,
|
|
bankLineFrequency,
|
|
bankPowerFactor,
|
|
bankLines,
|
|
bankActivePower,
|
|
bankReactivePower,
|
|
bankApparentPower,
|
|
bankName,
|
|
bankBreakerSupported,
|
|
bankBreakerState
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Bank Objects Group"
|
|
::= { synLinkGroups 4 }
|
|
|
|
synLinkOutletGroup OBJECT-GROUP
|
|
OBJECTS {
|
|
outletUuid,
|
|
outletName,
|
|
--outletPwrOnState,
|
|
--outletBankIndex,
|
|
outletCurrentRms,
|
|
outletState,
|
|
outletConnector
|
|
--outletMaxCurrent,
|
|
--outletSetState
|
|
--outletReboot
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet Objects Group"
|
|
::= { synLinkGroups 5 }
|
|
|
|
synLinkGroupGroup OBJECT-GROUP
|
|
OBJECTS {
|
|
groupName,
|
|
groupUuid,
|
|
groupSetState,
|
|
groupReboot,
|
|
groupCurrentRms
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet Group Objects Group"
|
|
::= { synLinkGroups 6 }
|
|
|
|
synLinkSensorGroup OBJECT-GROUP
|
|
OBJECTS {
|
|
sensorType,
|
|
sensorTemp,
|
|
sensorHumidity,
|
|
sensorTempOffset,
|
|
sensorHumidityOffset,
|
|
sensorName
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sensor Objects Group"
|
|
::= { synLinkGroups 7 }
|
|
|
|
synLinkLogGroup OBJECT-GROUP
|
|
OBJECTS {
|
|
pwrLogType,
|
|
pwrLogValue,
|
|
envLogType,
|
|
envLogValue
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Log Objects Group"
|
|
::= { synLinkGroups 8 }
|
|
|
|
synLinkEventGroup OBJECT-GROUP
|
|
OBJECTS {
|
|
eventType,
|
|
eventCode,
|
|
eventName,
|
|
eventTriggerAttr1,
|
|
eventTriggerAttr2,
|
|
eventTriggerAttr3,
|
|
eventIsTriggered,
|
|
eventTriggeredTime
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Event Triggers Objects Group"
|
|
::= { synLinkGroups 9 }
|
|
|
|
synLinkTrapGroup NOTIFICATION-GROUP
|
|
NOTIFICATIONS {
|
|
autopingTimeout,
|
|
line1CurrentMaxThreshold,
|
|
line2CurrentMaxThreshold,
|
|
line3CurrentMaxThreshold,
|
|
line1CurrentMinThreshold,
|
|
line2CurrentMinThreshold,
|
|
line3CurrentMinThreshold,
|
|
inletCurrentMaxThreshold,
|
|
inletCurrentMinThreshold,
|
|
inletVoltageMaxThreshold,
|
|
inletVoltageMinThreshold,
|
|
inletLineFrequencyMaxThreshold,
|
|
inletLineFrequencyMinThreshold,
|
|
inletPowerFactorMinThreshold,
|
|
inletActiveEnergyMaxThreshold,
|
|
inletActivePowerMaxThreshold,
|
|
inletActivePowerMinThreshold,
|
|
inletApparentPowerMaxThreshold,
|
|
inletApparentPowerMinThreshold,
|
|
inletReactivePowerMaxThreshold,
|
|
inletReactivePowerMinThreshold,
|
|
inlet3phaseImbalance,
|
|
bankBreakerTrip,
|
|
bankCurrentMaxThreshold,
|
|
bankCurrentMinThreshold,
|
|
bankVoltageMaxThreshold,
|
|
bankVoltageMinThreshold,
|
|
bankLineFrequencyMaxThreshold,
|
|
bankLineFrequencyMinThreshold,
|
|
bankPowerfactorMinThreshold,
|
|
--bankActiveEnergyMaxThreshold,
|
|
bankActivePowerMaxThreshold,
|
|
bankActivePowerMinThreshold,
|
|
bankApparentPowerMaxThreshold,
|
|
bankApparentPowerMinThreshold,
|
|
bankReactivePowerMaxThreshold,
|
|
bankReactivePowerMinThreshold,
|
|
outletCurrentMaxThreshold,
|
|
outletCurrentMinThreshold,
|
|
--groupCurrentMaxThreshold,
|
|
--groupCurrentMinThreshold,
|
|
temperatureMaxThreshold,
|
|
temperatureMinThreshold,
|
|
--humidity1MaxThreshold,
|
|
--humidity1MinThreshold,
|
|
scheduledTime,
|
|
scheduledInterval,
|
|
atsInletSwitchedToSecondary,
|
|
atsInletSwitchedToPrimary,
|
|
atsInletSecondaryPowerLoss,
|
|
atsInletSecondaryPowerRestored
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Event Trap Objects Groups"
|
|
::= { synLinkGroups 10 }
|
|
|
|
synLinkCompliances OBJECT IDENTIFIER ::= { conformance 2 }
|
|
|
|
synLinkCompliance MODULE-COMPLIANCE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Requirements for SYNLINK-MIB"
|
|
MODULE
|
|
|
|
GROUP synLinkDeviceGroup
|
|
DESCRIPTION
|
|
"SynLink Device Objects Group"
|
|
|
|
GROUP synLinkInletGroup
|
|
DESCRIPTION
|
|
"SynLink Inlet Objects Group"
|
|
|
|
-- GROUP synLinkLineGroup
|
|
-- DESCRIPTION
|
|
-- "SynLink Line Objects Group"
|
|
|
|
GROUP synLinkBankGroup
|
|
DESCRIPTION
|
|
"SynLink Bank Objects Group"
|
|
|
|
GROUP synLinkOutletGroup
|
|
DESCRIPTION
|
|
"SynLink Outlet Objects Group"
|
|
|
|
GROUP synLinkGroupGroup
|
|
DESCRIPTION
|
|
"SynLink Outlet's Group Objects Group"
|
|
|
|
GROUP synLinkSensorGroup
|
|
DESCRIPTION
|
|
"SynLink Sensor Objects Group"
|
|
|
|
GROUP synLinkLogGroup
|
|
DESCRIPTION
|
|
"SynLink Log Objects Group"
|
|
|
|
GROUP synLinkEventGroup
|
|
DESCRIPTION
|
|
"SynLink Event Triggers Group"
|
|
|
|
GROUP synLinkTrapGroup
|
|
DESCRIPTION
|
|
"SynLink Traps Group"
|
|
|
|
::= { synLinkCompliances 1 }
|
|
|
|
END
|
|
|