Observium_CE/mibs/racktivity/ES-RACKTIVITY-MIB

4805 lines
133 KiB
Plaintext

--********************************************************************************
--* Racktivity n.v. 2011 *
--* This is autogenerated code with RTS0019: RMCP Code Generator V0.3.2 *
--* This code is generated on : 23/04/2014 15:33:37(UTC) *
--* With parameters: <version> <arguments> <gen Master code> *
--********************************************************************************
ES-RACKTIVITY-MIB DEFINITIONS ::= BEGIN
IMPORTS
TimeTicks, Unsigned32, Integer32, IpAddress, MODULE-IDENTITY, NOTIFICATION-TYPE,
OBJECT-TYPE, enterprises
FROM SNMPv2-SMI
OBJECT-GROUP, MODULE-COMPLIANCE, NOTIFICATION-GROUP
FROM SNMPv2-CONF
TEXTUAL-CONVENTION, DisplayString, MacAddress
FROM SNMPv2-TC;
esRACKTIVITYMIB MODULE-IDENTITY
LAST-UPDATED "201404230333Z"
ORGANIZATION "Racktivity"
CONTACT-INFO "http://www.racktivity.com"
DESCRIPTION "The MIB module for the Racktivity Devices"
REVISION "201404230333Z"
DESCRIPTION "Initial version"
::= { enterprises 34097 9 }
Version ::= TEXTUAL-CONVENTION
DISPLAY-HINT "1d.1d.1d.1d"
STATUS current
DESCRIPTION "Displays a version number"
SYNTAX OCTET STRING (SIZE (4))
racktivity OBJECT IDENTIFIER
::= { enterprises 34097 }
racktivityNotif OBJECT IDENTIFIER
::= { esRACKTIVITYMIB 0 }
Utenth ::= TEXTUAL-CONVENTION
DISPLAY-HINT "d-1"
STATUS current
DESCRIPTION "0.1"
SYNTAX Unsigned32
Uhundredth ::= TEXTUAL-CONVENTION
DISPLAY-HINT "d-2"
STATUS current
DESCRIPTION "0.01"
SYNTAX Unsigned32
Uthousandth ::= TEXTUAL-CONVENTION
DISPLAY-HINT "d-3"
STATUS current
DESCRIPTION "0.001"
SYNTAX Unsigned32
Stenth ::= TEXTUAL-CONVENTION
DISPLAY-HINT "d-1"
STATUS current
DESCRIPTION "0.1"
SYNTAX Integer32
Shundredth ::= TEXTUAL-CONVENTION
DISPLAY-HINT "d-2"
STATUS current
DESCRIPTION "0.01"
SYNTAX Integer32
Sthousandth ::= TEXTUAL-CONVENTION
DISPLAY-HINT "d-3"
STATUS current
DESCRIPTION "0.001"
SYNTAX Integer32
EVENTFLAGS ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION "enumeration of all eventflags possible"
SYNTAX INTEGER {
sNMPTrapOff(0),
sNMPTrapOn(1)
}
CURPORTSTATE ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION "enumeration of all port states possible"
SYNTAX INTEGER {
portOff(0),
portOnNoWarning(1),
portOff1(2),
portOnWithWarningCurrent(3),
portOff2(4),
portOnWithWarningPower(5),
portOff3(6),
portOnWithWarningCurrentAndPower(7),
portOffWithError(8),
portOnNoWarning1(9),
portOffWithError1(10),
portOnWithWarningCurrent1(11),
portOffWithError2(12),
portOnWithWarningPower1(13),
portOffWithError3(14),
portOnWithWarnCurrentAndPower1(15),
portOffWithDelayOn(16),
portOnNoWarning2(17),
portOffWithDelayOn1(18),
portOnWithWarningCurrent2(19),
portOffWithDelayOn2(20),
portOnWithWarningPower2(21),
portOffWithDelayOn3(22),
portOnWithWarnCurrentAndPower2(23)
}
masterModule OBJECT IDENTIFIER
::= { esRACKTIVITYMIB 77 }
eMasterTable OBJECT-TYPE
SYNTAX SEQUENCE OF EMasterEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"NO_INFO"
::= { masterModule 1 }
eMasterEntry OBJECT-TYPE
SYNTAX EMasterEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"NO_INFO"
INDEX { masterModuleIndex, masterIndex }
::= { eMasterTable 1 }
EMasterEntry ::= SEQUENCE {
mGeneralModuleStatus Unsigned32,
mSpecificModuleStatus Unsigned32,
mCurrentTime TimeTicks,
mVoltage Uhundredth,
mTemperature Utenth,
mCurrentIP IpAddress,
mTotalCurrent Uthousandth,
mTotalRealPower Unsigned32,
mTotalActiveEnergy Uthousandth,
mLineCurrent Uthousandth,
mFuseCurrent Uthousandth,
mCurrentSubNetMask IpAddress,
mCurrentDNSServer IpAddress,
mCurrentStdGateway IpAddress,
mUPSPresent Unsigned32,
mUPSStatus Unsigned32,
mUPSEstimatedRunTime Unsigned32,
mUPSBatteryLevel Utenth,
mHighCurrent Stenth,
mUpsCommunicationStatus Unsigned32,
mHighPower Shundredth,
mTotalHighCurrent Stenth,
mTotalHighPower Shundredth,
mPositiveEnergy Uthousandth,
mNegativeEnergy Uthousandth,
mTotalPositiveEnergy Uthousandth,
mTotalNegativeEnergy Uthousandth,
mCloudStatus Unsigned32,
mStatus Unsigned32,
mModuleName DisplayString,
mFirmwareVersion Version,
mHardwareVersion Version,
mFirmwareID DisplayString,
mHardwareID DisplayString,
mRackName DisplayString,
mRackPosition DisplayString,
mIPAddress IpAddress,
mSubNetMask IpAddress,
mStdGateWay IpAddress,
mDnsServer IpAddress,
mMAC MacAddress,
mDHCPEnable Unsigned32,
mNTPServer IpAddress,
mUseDefaultNTPServer Unsigned32,
mUseNTP Unsigned32,
mSNMPTrapRecvIP IpAddress,
mSNMPTrapRecvPort Unsigned32,
mSNMPControl Unsigned32,
mECSServer IpAddress,
mUseECSServer Unsigned32,
mDisplayLock Unsigned32,
mDisplayTimeOn Unsigned32,
mMaxVoltageWarning Uhundredth,
mMinVoltageWarning Uhundredth,
mMinTemperatureWarning Utenth,
mMaxTemperatureWarning Utenth,
mGeneralEventEnable EVENTFLAGS,
mSNMPSysContact DisplayString,
mCurrentWarningEvent EVENTFLAGS,
mPowerWarningEvent EVENTFLAGS,
mTotalCurrentWarningEvent EVENTFLAGS,
mTotalPowerWarningEvent EVENTFLAGS,
mVoltageWarningEvent EVENTFLAGS,
mTemperatureWarningEvent EVENTFLAGS,
mDisplayBrightness Unsigned32,
mECSServerPort Unsigned32,
mExternalSensorLabel DisplayString,
mHttpsOnly Unsigned32,
mTelnetSsl Unsigned32,
mCookieTimeToLive Unsigned32,
mLineCurrentWarningThreshold Uthousandth,
mLineCurrentOffThreshold Uthousandth,
mLineCurrentWarningEvent EVENTFLAGS,
mLineCurrentOffEvent EVENTFLAGS,
mFuseCurrentWarningThreshold Uthousandth,
mFuseCurrentOffThreshold Uthousandth,
mFuseCurrentWarningEvent EVENTFLAGS,
mFuseCurrentOffEvent EVENTFLAGS,
mDeviceID DisplayString,
mDeviceVersion Version,
mSysName DisplayString,
mElectricalTopology Unsigned32,
mFusePortTopology Unsigned32,
mLineFuseTopology Unsigned32,
mSSOIPAddress IpAddress,
mSSOLoginCredentials DisplayString,
mSSOGracefullShutdown DisplayString,
mUPSWarningLevel Utenth,
mUPSOffLevel Utenth,
mMaxHighCurrentWarning Stenth,
mUpsMonitoringProtocol Unsigned32,
mUpsEmergencyThreshold Utenth,
mUpsRecoveryThreshold Utenth,
mUpsEventFlags EVENTFLAGS,
mRecoveryPowerThreshold Unsigned32,
mMinHighCurrentWarning Stenth,
mMinHighPowerWarning Shundredth,
mMaxHighPowerWarning Shundredth,
mHeartbeatInterval Unsigned32,
mMinTotalHighCurrentWarning Stenth,
mMaxTotalHighCurrentWarning Stenth,
mMinTotalHighPowerWarning Shundredth,
mMaxTotalHighPowerWarning Shundredth,
mCloudState Unsigned32,
mSensorBias Integer32,
mDaisyChainDeviceMode Unsigned32,
mSNMPTrapUser Unsigned32,
mUSMUser DisplayString,
mUSMAuthPassphrase DisplayString,
mUSMPrivPassphrase DisplayString,
mSNMPV2GetSetEnable Unsigned32,
mSNMPV3GetSetEnable Unsigned32,
mUSMAuthPassphraseLength Unsigned32,
mUSMPrivPassphraseLength Unsigned32,
mSNMPTrapEnable Unsigned32,
mLDAPAttribute DisplayString,
mLDAPPath DisplayString,
mLDAPAdminGroupName DisplayString,
mLDAPRestrictedGroupName DisplayString,
mLDAPGuestGroupName DisplayString,
mLDAPEnable Unsigned32,
mLDAPLoginWrapper DisplayString,
mLDAPServer DisplayString,
mLocalAuthEnable Unsigned32,
masterIndex Integer32,
masterModuleIndex Integer32
}
masterIndex OBJECT-TYPE
SYNTAX Integer32 (1..8)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Index for the selected Master Module"
::= { eMasterEntry 65537 }
masterModuleIndex OBJECT-TYPE
SYNTAX Integer32 (1..8)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Selected Master Module"
::= { eMasterEntry 65538 }
mGeneralModuleStatus OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"General status of a module."
::= { eMasterEntry 1 }
mSpecificModuleStatus OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Specific status of a module."
::= { eMasterEntry 2 }
mCurrentTime OBJECT-TYPE
SYNTAX TimeTicks
UNITS "UNIX"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets or sets the current time (not possible when NTP is enabled). (unit: UNIX)"
::= { eMasterEntry 3 }
mVoltage OBJECT-TYPE
SYNTAX Uhundredth
UNITS "V"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the voltage of a power module. (unit: 0.01V)"
::= { eMasterEntry 4 }
mTemperature OBJECT-TYPE
SYNTAX Utenth
UNITS "K"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the current temperature of a temperature sensor. (unit: 0.1K)"
::= { eMasterEntry 11 }
mCurrentIP OBJECT-TYPE
SYNTAX IpAddress
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the current IP address. To set the IP address, use IPADDR instead."
::= { eMasterEntry 14 }
mTotalCurrent OBJECT-TYPE
SYNTAX Uthousandth
UNITS "A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the total current of a power module. (unit: 0.001A)"
::= { eMasterEntry 17 }
mTotalRealPower OBJECT-TYPE
SYNTAX Unsigned32
UNITS "W"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the total power level of a power module. (unit: W)"
::= { eMasterEntry 18 }
mTotalActiveEnergy OBJECT-TYPE
SYNTAX Uthousandth
UNITS "kWh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the total energy of a power module. (unit: 0.001kWh)"
::= { eMasterEntry 20 }
mLineCurrent OBJECT-TYPE
SYNTAX Uthousandth (0..65535)
UNITS "A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the current line current. (unit: 0.001A)"
::= { eMasterEntry 32 }
mFuseCurrent OBJECT-TYPE
SYNTAX Uthousandth (0..65535)
UNITS "A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the current through a fuse. (unit: 0.001A)"
::= { eMasterEntry 33 }
mCurrentSubNetMask OBJECT-TYPE
SYNTAX IpAddress
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the current subnet mask. To set the subnet mask use SNMSK instead."
::= { eMasterEntry 34 }
mCurrentDNSServer OBJECT-TYPE
SYNTAX IpAddress
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the current DNS server. To set the DNS server use DNSSRV instead."
::= { eMasterEntry 35 }
mCurrentStdGateway OBJECT-TYPE
SYNTAX IpAddress
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the current standard gateway. To set the standard gateway use STDGW instead."
::= { eMasterEntry 36 }
mUPSPresent OBJECT-TYPE
SYNTAX Unsigned32 (0..1)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Checks if a UPS is present."
::= { eMasterEntry 37 }
mUPSStatus OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the working status of a UPS (if its working on its batteries or not)."
::= { eMasterEntry 38 }
mUPSEstimatedRunTime OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
UNITS "min"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the estimated run time of a UPS. (unit: min)"
::= { eMasterEntry 39 }
mUPSBatteryLevel OBJECT-TYPE
SYNTAX Utenth (0..1000)
UNITS "%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current UPS battery level. (unit: 0.1%)"
::= { eMasterEntry 40 }
mHighCurrent OBJECT-TYPE
SYNTAX Stenth
UNITS "A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current for high values (unit: 0.1A)"
::= { eMasterEntry 41 }
mUpsCommunicationStatus OBJECT-TYPE
SYNTAX Unsigned32 (0..1)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status information of communication with the UPS"
::= { eMasterEntry 42 }
mHighPower OBJECT-TYPE
SYNTAX Shundredth (-32768..32767)
UNITS "kW"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The power for high values (unit: 0.01kW)"
::= { eMasterEntry 43 }
mTotalHighCurrent OBJECT-TYPE
SYNTAX Stenth (0..65535)
UNITS "A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current for high values (unit: 0.1A)"
::= { eMasterEntry 44 }
mTotalHighPower OBJECT-TYPE
SYNTAX Shundredth (-32768..32767)
UNITS "kW"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The power for high values (unit: 0.01kW)"
::= { eMasterEntry 45 }
mPositiveEnergy OBJECT-TYPE
SYNTAX Uthousandth (0..4294967295)
UNITS "kWh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the positive energy used by an outlet. (unit: 0.001kWh)"
::= { eMasterEntry 46 }
mNegativeEnergy OBJECT-TYPE
SYNTAX Uthousandth (0..4294967295)
UNITS "kWh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the negative energy used by an outlet. (unit: 0.001kWh)"
::= { eMasterEntry 47 }
mTotalPositiveEnergy OBJECT-TYPE
SYNTAX Uthousandth (0..4294967295)
UNITS "kWh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the positive energy of the module. (unit: 0.001kWh)"
::= { eMasterEntry 48 }
mTotalNegativeEnergy OBJECT-TYPE
SYNTAX Uthousandth (0..4294967295)
UNITS "kWh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the negative energy of the module. (unit: 0.001kWh)"
::= { eMasterEntry 49 }
mCloudStatus OBJECT-TYPE
SYNTAX Unsigned32 (0..255)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the status of the connection with the cloud. 0 = Idle state; 1 = Disabled; 2 = Initialising; 3 = Initialising - No connection; 4 = Initialising - No key; 5 = Connection Ok; 6 = Connection Failed; 7 = Connection Failed - No key."
::= { eMasterEntry 56 }
mStatus OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"status of a module"
::= { eMasterEntry 1000 }
mModuleName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the module name."
::= { eMasterEntry 10001 }
mFirmwareVersion OBJECT-TYPE
SYNTAX Version
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the version of the module's firmware."
::= { eMasterEntry 10002 }
mHardwareVersion OBJECT-TYPE
SYNTAX Version
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the version of a module's hardware."
::= { eMasterEntry 10003 }
mFirmwareID OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the ID of the module's firmware."
::= { eMasterEntry 10004 }
mHardwareID OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the ID of a module's hardware."
::= { eMasterEntry 10005 }
mRackName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the name of the rack."
::= { eMasterEntry 10006 }
mRackPosition OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the position in the rack."
::= { eMasterEntry 10007 }
mIPAddress OBJECT-TYPE
SYNTAX IpAddress
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the IP address (when DHCP is disabled)."
::= { eMasterEntry 10011 }
mSubNetMask OBJECT-TYPE
SYNTAX IpAddress
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the subnet mask (when DHCP is disabled)."
::= { eMasterEntry 10012 }
mStdGateWay OBJECT-TYPE
SYNTAX IpAddress
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the standard gateway (when DHCP is disabled)."
::= { eMasterEntry 10013 }
mDnsServer OBJECT-TYPE
SYNTAX IpAddress
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the IP address of the used DNS server (when DHCP is disabled)."
::= { eMasterEntry 10014 }
mMAC OBJECT-TYPE
SYNTAX MacAddress
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the MAC address of a master module."
::= { eMasterEntry 10015 }
mDHCPEnable OBJECT-TYPE
SYNTAX Unsigned32 (0..1)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables, disables or defaults DHCP. Set to 1 to enable DHCP, or 0 to disable DHCP."
::= { eMasterEntry 10016 }
mNTPServer OBJECT-TYPE
SYNTAX IpAddress
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the NTP (Network Time Protocol) server IP address."
::= { eMasterEntry 10017 }
mUseDefaultNTPServer OBJECT-TYPE
SYNTAX Unsigned32 (0..1)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables, disables or defaults the usage of the default NTP (Network Time Protocol) server (pool.ntp.org)."
::= { eMasterEntry 10018 }
mUseNTP OBJECT-TYPE
SYNTAX Unsigned32 (0..1)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables, disables or defaults NTP (Network Time Protocol). Set to 1 to enable NTP, or 0 to disable NTP."
::= { eMasterEntry 10019 }
mSNMPTrapRecvIP OBJECT-TYPE
SYNTAX IpAddress
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the SNMP trap receiver IP address."
::= { eMasterEntry 10020 }
mSNMPTrapRecvPort OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the SNMP tap receiver port."
::= { eMasterEntry 10021 }
mSNMPControl OBJECT-TYPE
SYNTAX Unsigned32 (0..1)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables, disables or defaults write access over SNMP. Set to 1 to disable write access, or 0 to enable write access."
::= { eMasterEntry 10024 }
mECSServer OBJECT-TYPE
SYNTAX IpAddress
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the ECS (Energy Cloud Sentinel) server IP address."
::= { eMasterEntry 10028 }
mUseECSServer OBJECT-TYPE
SYNTAX Unsigned32 (0..1)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables, disables or defaults the use of an ECS (Energy Cloud Sentinel) server. Set to 1 to enable or 0 to disable."
::= { eMasterEntry 10029 }
mDisplayLock OBJECT-TYPE
SYNTAX Unsigned32 (0..255)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the display lock. If the display is locked, you can still view information on the display, but you are not allowed to change settings through the menu system."
::= { eMasterEntry 10031 }
mDisplayTimeOn OBJECT-TYPE
SYNTAX Unsigned32 (0..255)
UNITS "min"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the display sleep timer. If the display is inactive for longer than this time, the display turns off to save power. Time is in minutes. (unit: min)"
::= { eMasterEntry 10032 }
mMaxVoltageWarning OBJECT-TYPE
SYNTAX Uhundredth (0..65535)
UNITS "V"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the maximum voltage warning level. (unit: 0.01V)"
::= { eMasterEntry 10047 }
mMinVoltageWarning OBJECT-TYPE
SYNTAX Uhundredth (0..65535)
UNITS "V"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the minimum voltage warning level. (unit: 0.01V)"
::= { eMasterEntry 10049 }
mMinTemperatureWarning OBJECT-TYPE
SYNTAX Utenth (2232..4732)
UNITS "K"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the minimum temperature warning level (use DEF accessor to reset). (unit: 0.1K)"
::= { eMasterEntry 10052 }
mMaxTemperatureWarning OBJECT-TYPE
SYNTAX Utenth (2232..4732)
UNITS "K"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the maximum temperature warning level (use DEF accessor to reset). (unit: 0.1K)"
::= { eMasterEntry 10053 }
mGeneralEventEnable OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults general events. If set to 0, no events will be generated. Set to 1 to generate events on media indicated by the event bitfields."
::= { eMasterEntry 10074 }
mSNMPSysContact OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the SNMP contact information."
::= { eMasterEntry 10075 }
mCurrentWarningEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the outlet current warning level is exceeded."
::= { eMasterEntry 10078 }
mPowerWarningEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the power warning level is exceeded."
::= { eMasterEntry 10080 }
mTotalCurrentWarningEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the total outlet current warning level is exceeded."
::= { eMasterEntry 10082 }
mTotalPowerWarningEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the total power warning level is exceeded."
::= { eMasterEntry 10084 }
mVoltageWarningEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the voltage warning level is exceeded."
::= { eMasterEntry 10086 }
mTemperatureWarningEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the temperature warning level is exceeded."
::= { eMasterEntry 10087 }
mDisplayBrightness OBJECT-TYPE
SYNTAX Unsigned32 (0..255)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the display brightness (if supported)."
::= { eMasterEntry 10098 }
mECSServerPort OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the ECS (Energy Cloud Sentinel) server port."
::= { eMasterEntry 10106 }
mExternalSensorLabel OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the external sensor label. External sensors can be connected to Energy Sensors."
::= { eMasterEntry 10109 }
mHttpsOnly OBJECT-TYPE
SYNTAX Unsigned32 (0..1)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the use of HTTPS (secure HTTP). Set to 1 to enable HTTPS only, or 0 to also enable HTTP."
::= { eMasterEntry 10127 }
mTelnetSsl OBJECT-TYPE
SYNTAX Unsigned32 (0..1)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the use of Telnet SSL (secure Telnet). Set to 1 to enable Telnet SSL, or 0 to disable Telnet SSL)."
::= { eMasterEntry 10128 }
mCookieTimeToLive OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
UNITS "min"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The TTL (Time To Live) of the website cookie. (unit: min)"
::= { eMasterEntry 10130 }
mLineCurrentWarningThreshold OBJECT-TYPE
SYNTAX Uthousandth (0..65535)
UNITS "A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets the warning threshold of the linecurrent. (unit: 0.001A)"
::= { eMasterEntry 10131 }
mLineCurrentOffThreshold OBJECT-TYPE
SYNTAX Uthousandth (0..65535)
UNITS "A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets the off threshold of the linecurrent. (unit: 0.001A)"
::= { eMasterEntry 10132 }
mLineCurrentWarningEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the linecurrent warning level is exceeded."
::= { eMasterEntry 10133 }
mLineCurrentOffEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the linecurrent off level is exceeded."
::= { eMasterEntry 10134 }
mFuseCurrentWarningThreshold OBJECT-TYPE
SYNTAX Uthousandth (0..32000)
UNITS "A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the maximum current warning threshold per fuse. (unit: 0.001A)"
::= { eMasterEntry 10142 }
mFuseCurrentOffThreshold OBJECT-TYPE
SYNTAX Uthousandth (0..32000)
UNITS "A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the maximum current off threshold per fuse. (unit: 0.001A)"
::= { eMasterEntry 10143 }
mFuseCurrentWarningEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the fusecurrent warning threshold is exceeded."
::= { eMasterEntry 10144 }
mFuseCurrentOffEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the fusecurrent off threshold is exceeded."
::= { eMasterEntry 10145 }
mDeviceID OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The ID of the device."
::= { eMasterEntry 10150 }
mDeviceVersion OBJECT-TYPE
SYNTAX Version
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The version of the device."
::= { eMasterEntry 10151 }
mSysName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The full name of the device."
::= { eMasterEntry 10152 }
mElectricalTopology OBJECT-TYPE
SYNTAX Unsigned32 (0..2)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the electrical topology of the unit."
::= { eMasterEntry 10153 }
mFusePortTopology OBJECT-TYPE
SYNTAX Unsigned32 (0..6)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the topology between the outlets and fuses."
::= { eMasterEntry 10154 }
mLineFuseTopology OBJECT-TYPE
SYNTAX Unsigned32 (0..3)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the topology between the inlet (cable or connection) and the fuses."
::= { eMasterEntry 10155 }
mSSOIPAddress OBJECT-TYPE
SYNTAX IpAddress
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets the IP address of an SSO (Smart Style Office)."
::= { eMasterEntry 10156 }
mSSOLoginCredentials OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets the login credentials of an SSO (Smart Style Office)."
::= { eMasterEntry 10157 }
mSSOGracefullShutdown OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets the string to send if the UPS' battery level is below the set threshold."
::= { eMasterEntry 10158 }
mUPSWarningLevel OBJECT-TYPE
SYNTAX Utenth (0..1000)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the graceful shutdown threshold of a UPS."
::= { eMasterEntry 10159 }
mUPSOffLevel OBJECT-TYPE
SYNTAX Utenth (0..1000)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the threshold of a UPS to set outlets off."
::= { eMasterEntry 10160 }
mMaxHighCurrentWarning OBJECT-TYPE
SYNTAX Stenth (-32768..32767)
UNITS "A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets sets or defaults the maximum high current warning level. (unit: 0.1A)"
::= { eMasterEntry 10165 }
mUpsMonitoringProtocol OBJECT-TYPE
SYNTAX Unsigned32 (0..1)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Disables/Enables UPS monitoring and selects the protocol used for UPS monitoring. 0 = Disabled; 1 = Use old APC protocol"
::= { eMasterEntry 10167 }
mUpsEmergencyThreshold OBJECT-TYPE
SYNTAX Utenth (0..1000)
UNITS "%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"When the UPS battery level goes below this threshold a shutdown request will be sent to all agents (unit: 0.1%)"
::= { eMasterEntry 10168 }
mUpsRecoveryThreshold OBJECT-TYPE
SYNTAX Utenth (0..1000)
UNITS "%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"When the UPS battery level goes above this threshold a outlets will be powered on as configured by the user (unit: 0.1%)"
::= { eMasterEntry 10169 }
mUpsEventFlags OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Event flags for events related to the UPS monitoring"
::= { eMasterEntry 10170 }
mRecoveryPowerThreshold OBJECT-TYPE
SYNTAX Unsigned32 (20..4000)
UNITS "W"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"When the UPS was on battery and it went below UPSEMERGTHRES, the outlets that have a load below the RECOVPOWERTHRES will be power cycled once the UPS is back on mains power and exceeds UPSRECOVTHRES (unit: W)"
::= { eMasterEntry 10171 }
mMinHighCurrentWarning OBJECT-TYPE
SYNTAX Stenth (-32768..32767)
UNITS "A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets sets or defaults the minimum high current warning level. (unit: 0.1A)"
::= { eMasterEntry 10176 }
mMinHighPowerWarning OBJECT-TYPE
SYNTAX Shundredth (-32768..32767)
UNITS "kW"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets sets or defaults the power min high current warning level. (unit: 0.01kW)"
::= { eMasterEntry 10177 }
mMaxHighPowerWarning OBJECT-TYPE
SYNTAX Shundredth (-32768..32767)
UNITS "kW"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets sets or defaults the power max high current warning level. (unit: 0.01kW)"
::= { eMasterEntry 10178 }
mHeartbeatInterval OBJECT-TYPE
SYNTAX Unsigned32 (0..255)
UNITS "s"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Interval (in seconds) between 2 heartbeat SNMP traps, Set to 0 to disable (unit: s)"
::= { eMasterEntry 10179 }
mMinTotalHighCurrentWarning OBJECT-TYPE
SYNTAX Stenth (-32768..32767)
UNITS "A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets sets or defaults the maximum high current warning level. (unit: 0.1A)"
::= { eMasterEntry 10180 }
mMaxTotalHighCurrentWarning OBJECT-TYPE
SYNTAX Stenth (-32768..32767)
UNITS "A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets sets or defaults the maximum high current warning level. (unit: 0.1A)"
::= { eMasterEntry 10181 }
mMinTotalHighPowerWarning OBJECT-TYPE
SYNTAX Shundredth (-32768..32767)
UNITS "kW"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets sets or defaults the power min high current warning level. (unit: 0.01kW)"
::= { eMasterEntry 10182 }
mMaxTotalHighPowerWarning OBJECT-TYPE
SYNTAX Shundredth (-32768..32767)
UNITS "kW"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets sets or defaults the power max high current warning level. (unit: 0.01kW)"
::= { eMasterEntry 10183 }
mCloudState OBJECT-TYPE
SYNTAX Unsigned32 (0..2)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set if the device needs to push info to the init cloud (val=0) or to the normal cloud (val=1)"
::= { eMasterEntry 10208 }
mSensorBias OBJECT-TYPE
SYNTAX Integer32 (-32768..32767)
UNITS "mV"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"get or set the DC sensor bias (unit: mV)"
::= { eMasterEntry 10210 }
mDaisyChainDeviceMode OBJECT-TYPE
SYNTAX Unsigned32 (0..4)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"allowed modes: 0: standalone (master without daisy chain slaves) 1: daisy chain master 2: daisy chain slave 1 3: daisy chain slave 2 4: daisy chain slave 3"
::= { eMasterEntry 10211 }
mSNMPTrapUser OBJECT-TYPE
SYNTAX Unsigned32 (0..4)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the SNMP tap user out of the user list."
::= { eMasterEntry 10212 }
mUSMUser OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the SNMP USM security user"
::= { eMasterEntry 10213 }
mUSMAuthPassphrase OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the SNMP USM authentication passphrase (Always MD5)"
::= { eMasterEntry 10214 }
mUSMPrivPassphrase OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the SNMP USM private passphrase (Always AES)"
::= { eMasterEntry 10215 }
mSNMPV2GetSetEnable OBJECT-TYPE
SYNTAX Unsigned32 (0..1)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the SNMP V2 Enable for get ,set or walk but not for traps."
::= { eMasterEntry 10216 }
mSNMPV3GetSetEnable OBJECT-TYPE
SYNTAX Unsigned32 (0..1)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the SNMP V3 Enable for get ,set or walk but not for traps."
::= { eMasterEntry 10217 }
mUSMAuthPassphraseLength OBJECT-TYPE
SYNTAX Unsigned32 (0..16)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the SNMP USM authentication passphrase length"
::= { eMasterEntry 10218 }
mUSMPrivPassphraseLength OBJECT-TYPE
SYNTAX Unsigned32 (0..16)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the SNMP USM private passphrase length"
::= { eMasterEntry 10219 }
mSNMPTrapEnable OBJECT-TYPE
SYNTAX Unsigned32 (0..1)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the SNMP Trap Enable per trap account"
::= { eMasterEntry 10222 }
mLDAPAttribute OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Attribute linked to the LDAPFilter"
::= { eMasterEntry 10227 }
mLDAPPath OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Relative Path to be used for the LDAPFilter"
::= { eMasterEntry 10228 }
mLDAPAdminGroupName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"GroupName for Admin Credentials in LDAP"
::= { eMasterEntry 10229 }
mLDAPRestrictedGroupName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"GroupName for Restricted Credentials in LDAP"
::= { eMasterEntry 10230 }
mLDAPGuestGroupName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"GroupName for Guest Credentials in LDAP"
::= { eMasterEntry 10231 }
mLDAPEnable OBJECT-TYPE
SYNTAX Unsigned32 (0..1)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enable or disable login via LDAP credentials"
::= { eMasterEntry 10232 }
mLDAPLoginWrapper OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Wrapper for login in with LDAP"
::= { eMasterEntry 10233 }
mLDAPServer OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"NO_INFO"
::= { eMasterEntry 10235 }
mLocalAuthEnable OBJECT-TYPE
SYNTAX Unsigned32 (0..1)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set if local authentication is still possible if LDAP is enabled"
::= { eMasterEntry 10236 }
powerModule OBJECT IDENTIFIER
::= { esRACKTIVITYMIB 80 }
ePowerTable OBJECT-TYPE
SYNTAX SEQUENCE OF EPowerEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"NO_INFO"
::= { powerModule 1 }
ePowerEntry OBJECT-TYPE
SYNTAX EPowerEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"NO_INFO"
INDEX { powerModuleIndex, powerIndex }
::= { ePowerTable 1 }
EPowerEntry ::= SEQUENCE {
pGeneralModuleStatus Unsigned32,
pSpecificModuleStatus Unsigned32,
pCurrentTime TimeTicks,
pVoltage Uhundredth,
pFrequency Uthousandth,
pCurrent Uthousandth,
pPower Unsigned32,
pStatePortCur CURPORTSTATE,
pActiveEnergy Uthousandth,
pApparentEnergy Uthousandth,
pTemperature Utenth,
pApparentPower Unsigned32,
pPowerFactor Unsigned32,
pTotalCurrent Uthousandth,
pTotalRealPower Unsigned32,
pTotalApparentPower Unsigned32,
pTotalActiveEnergy Uthousandth,
pTotalApparentEnergy Uthousandth,
pTotalPowerFactor Unsigned32,
pTimeOnline Unsigned32,
pTotalHarmonicDistortion Utenth,
pPhase Unsigned32,
pBigCurrent Unsigned32,
pBigPower Uthousandth,
pBigApparentPower Uthousandth,
pDetectedPhase Unsigned32,
pModuleName DisplayString,
pFirmwareVersion Version,
pHardwareVersion Version,
pFirmwareID DisplayString,
pHardwareID DisplayString,
pPortName DisplayString,
pPortState Unsigned32,
pCurrentPriorOff Unsigned32,
pDelayOn Unsigned32,
pMaxCurrentOff Uthousandth,
pMaxCurrentWarning Uthousandth,
pMaxPowerOff Unsigned32,
pMaxPowerWarning Unsigned32,
pMaxTotalCurrentOff Uthousandth,
pMaxTotalCurrentWarning Uthousandth,
pMaxTotalPowerOff Unsigned32,
pMaxTotalPowerWarning Unsigned32,
pMaxVoltageWarning Uhundredth,
pMinVoltageWarning Uhundredth,
pMinTemperatureWarning Utenth,
pMaxTemperatureWarning Utenth,
pPortStateEvent EVENTFLAGS,
pCurrentOffEvent EVENTFLAGS,
pCurrentWarningEvent EVENTFLAGS,
pPowerOffEvent EVENTFLAGS,
pPowerWarningEvent EVENTFLAGS,
pTotalCurrentOffEvent EVENTFLAGS,
pTotalCurrentWarningEvent EVENTFLAGS,
pTotalPowerOffEvent EVENTFLAGS,
pTotalPowerWarningEvent EVENTFLAGS,
pVoltageWarningEvent EVENTFLAGS,
pTemperatureWarningEvent EVENTFLAGS,
pMaxOverheatingOff Utenth,
pOverheatingOffEvent EVENTFLAGS,
pPowerCycleTime Unsigned32,
pExternalSensorLabel DisplayString,
pMaxOverheatingWarning Utenth,
pOverheatingWarningEvent EVENTFLAGS,
pMicroIntTimeThreshold Utenth,
pMicroIntEvent EVENTFLAGS,
pSoftFuseCurrentThreshold Unsigned32,
pSoftFuseDelay Unsigned32,
pSoftFuseEvent EVENTFLAGS,
pPhaseShiftEvent EVENTFLAGS,
pSchedulePortOnTime Unsigned32,
pSchedulePortOffTime Unsigned32,
pEnableSchedulePort Unsigned32,
pBlockSetPortOff Unsigned32,
pSchedulePortChangeEvent EVENTFLAGS,
pAgentIP IpAddress,
pAgentPort Unsigned32,
pAgentCommunicationEventFlags EVENTFLAGS,
pAlwaysOn Unsigned32,
pGenericTransducerParameters Integer32,
pMaxBigCurrentWarning Unsigned32,
pMaxBigPowerWarning Uthousandth,
pGroupNumber Unsigned32,
pPhaseLink Unsigned32,
pCurrentSensorSelector Unsigned32,
pMinBigCurrentWarning Unsigned32,
powerIndex Integer32,
powerModuleIndex Integer32
}
powerIndex OBJECT-TYPE
SYNTAX Integer32 (1..8)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Index for the selected Power Module"
::= { ePowerEntry 65537 }
powerModuleIndex OBJECT-TYPE
SYNTAX Integer32 (1..8)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Selected Power Module"
::= { ePowerEntry 65538 }
pGeneralModuleStatus OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"General status of a module."
::= { ePowerEntry 1 }
pSpecificModuleStatus OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Specific status of a module."
::= { ePowerEntry 2 }
pCurrentTime OBJECT-TYPE
SYNTAX TimeTicks
UNITS "UNIX"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets or sets the current time (not possible when NTP is enabled). (unit: UNIX)"
::= { ePowerEntry 3 }
pVoltage OBJECT-TYPE
SYNTAX Uhundredth
UNITS "V"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the voltage of a power module. (unit: 0.01V)"
::= { ePowerEntry 4 }
pFrequency OBJECT-TYPE
SYNTAX Uthousandth
UNITS "Hz"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the frequency of the input voltage of a power module. (unit: 0.001Hz)"
::= { ePowerEntry 5 }
pCurrent OBJECT-TYPE
SYNTAX Uthousandth
UNITS "A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the current of an outlet. (unit: 0.001A)"
::= { ePowerEntry 6 }
pPower OBJECT-TYPE
SYNTAX Unsigned32
UNITS "W"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the power of an outlet. (unit: W)"
::= { ePowerEntry 7 }
pStatePortCur OBJECT-TYPE
SYNTAX CURPORTSTATE
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the current state of an outlet. To toggle an outlet use PORTSTAT (CLI) or pPortstate (SNMP) (GUID 10035) instead."
::= { ePowerEntry 8 }
pActiveEnergy OBJECT-TYPE
SYNTAX Uthousandth
UNITS "kWh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the energy used by an outlet. (unit: 0.001kWh)"
::= { ePowerEntry 9 }
pApparentEnergy OBJECT-TYPE
SYNTAX Uthousandth
UNITS "kVAh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the apparent energy used by an outlet. (unit: 0.001kVAh)"
::= { ePowerEntry 10 }
pTemperature OBJECT-TYPE
SYNTAX Utenth
UNITS "K"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the current temperature of a temperature sensor. (unit: 0.1K)"
::= { ePowerEntry 11 }
pApparentPower OBJECT-TYPE
SYNTAX Unsigned32
UNITS "VA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the apparent power of an outlet. (unit: VA)"
::= { ePowerEntry 15 }
pPowerFactor OBJECT-TYPE
SYNTAX Unsigned32
UNITS "%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the power factor of an outlet. (unit: %)"
::= { ePowerEntry 16 }
pTotalCurrent OBJECT-TYPE
SYNTAX Uthousandth
UNITS "A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the total current of a power module. (unit: 0.001A)"
::= { ePowerEntry 17 }
pTotalRealPower OBJECT-TYPE
SYNTAX Unsigned32
UNITS "W"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the total power level of a power module. (unit: W)"
::= { ePowerEntry 18 }
pTotalApparentPower OBJECT-TYPE
SYNTAX Unsigned32
UNITS "VA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the total apparent power of a power module. (unit: VA)"
::= { ePowerEntry 19 }
pTotalActiveEnergy OBJECT-TYPE
SYNTAX Uthousandth
UNITS "kWh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the total energy of a power module. (unit: 0.001kWh)"
::= { ePowerEntry 20 }
pTotalApparentEnergy OBJECT-TYPE
SYNTAX Uthousandth
UNITS "kVAh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the total apparent energy of a power module. (unit: 0.001kVAh)"
::= { ePowerEntry 21 }
pTotalPowerFactor OBJECT-TYPE
SYNTAX Unsigned32
UNITS "%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the total power factor of a power module. (unit: %)"
::= { ePowerEntry 22 }
pTimeOnline OBJECT-TYPE
SYNTAX Unsigned32
UNITS "s"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the amount of seconds since the last reset. (unit: s)"
::= { ePowerEntry 24 }
pTotalHarmonicDistortion OBJECT-TYPE
SYNTAX Utenth (0..1000)
UNITS "%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"total harmonic distortion - outlet (unit: 0.1%)"
::= { ePowerEntry 50 }
pPhase OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
UNITS "degr"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"the phase between 2 waves (unit: degr)"
::= { ePowerEntry 51 }
pBigCurrent OBJECT-TYPE
SYNTAX Unsigned32
UNITS "A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the current of an outlet. (unit: 0.0001A)"
::= { ePowerEntry 52 }
pBigPower OBJECT-TYPE
SYNTAX Uthousandth
UNITS "W"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the power of an outlet. (unit: 0.001W)"
::= { ePowerEntry 53 }
pBigApparentPower OBJECT-TYPE
SYNTAX Uthousandth
UNITS "VA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the apparent power of an outlet. (unit: 0.001VA)"
::= { ePowerEntry 54 }
pDetectedPhase OBJECT-TYPE
SYNTAX Unsigned32 (0..255)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gives the best matching Phase per currentsensor. Updated every 8s. returnes 255 if no good phaselink is found"
::= { ePowerEntry 55 }
pModuleName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the module name."
::= { ePowerEntry 10001 }
pFirmwareVersion OBJECT-TYPE
SYNTAX Version
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the version of the module's firmware."
::= { ePowerEntry 10002 }
pHardwareVersion OBJECT-TYPE
SYNTAX Version
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the version of a module's hardware."
::= { ePowerEntry 10003 }
pFirmwareID OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the ID of the module's firmware."
::= { ePowerEntry 10004 }
pHardwareID OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the ID of a module's hardware."
::= { ePowerEntry 10005 }
pPortName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the name of an outlet."
::= { ePowerEntry 10034 }
pPortState OBJECT-TYPE
SYNTAX Unsigned32 (0..2)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Sets the state of an outlet: 0=OFF, 1=ON, 2=POWER CYCLE. To get the state of an outlet use CPORTSTAT (CLI) or pStatePortCur (SNMP) (GUID 8) instead."
::= { ePowerEntry 10035 }
pCurrentPriorOff OBJECT-TYPE
SYNTAX Unsigned32 (1..8)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the priority of an outlet. Priority settings are used when 1 or more outlets must be turned off because the total current of a power module was exceeded."
::= { ePowerEntry 10036 }
pDelayOn OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
UNITS "s"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the outlet turn-on delay. Use this to reduce inrush current when the Energy Switch boots. (unit: s)"
::= { ePowerEntry 10037 }
pMaxCurrentOff OBJECT-TYPE
SYNTAX Uthousandth (100..8000)
UNITS "A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the maximum current off level of an outlet. (unit: 0.001A)"
::= { ePowerEntry 10038 }
pMaxCurrentWarning OBJECT-TYPE
SYNTAX Uthousandth (100..8000)
UNITS "A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the maximum current warning level of an outlet. (unit: 0.001A)"
::= { ePowerEntry 10039 }
pMaxPowerOff OBJECT-TYPE
SYNTAX Unsigned32 (20..2000)
UNITS "W"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the maximum power off level of an outlet. (unit: W)"
::= { ePowerEntry 10040 }
pMaxPowerWarning OBJECT-TYPE
SYNTAX Unsigned32 (20..2000)
UNITS "W"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the maximum power warning level of an outlet. (unit: W)"
::= { ePowerEntry 10041 }
pMaxTotalCurrentOff OBJECT-TYPE
SYNTAX Uthousandth (100..16000)
UNITS "A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the total maximum current off level of a power module. (unit: 0.001A)"
::= { ePowerEntry 10042 }
pMaxTotalCurrentWarning OBJECT-TYPE
SYNTAX Uthousandth (100..16000)
UNITS "A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the total maximum current warning level of a power module. (unit: 0.001A)"
::= { ePowerEntry 10043 }
pMaxTotalPowerOff OBJECT-TYPE
SYNTAX Unsigned32 (20..4000)
UNITS "W"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the maximum total power off level. (unit: W)"
::= { ePowerEntry 10044 }
pMaxTotalPowerWarning OBJECT-TYPE
SYNTAX Unsigned32 (20..4000)
UNITS "W"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the maximum total power warning level. (unit: W)"
::= { ePowerEntry 10045 }
pMaxVoltageWarning OBJECT-TYPE
SYNTAX Uhundredth (5000..30000)
UNITS "V"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the maximum voltage warning level. (unit: 0.01V)"
::= { ePowerEntry 10047 }
pMinVoltageWarning OBJECT-TYPE
SYNTAX Uhundredth (5000..30000)
UNITS "V"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the minimum voltage warning level. (unit: 0.01V)"
::= { ePowerEntry 10049 }
pMinTemperatureWarning OBJECT-TYPE
SYNTAX Utenth (2232..4732)
UNITS "K"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the minimum temperature warning level (use DEF accessor to reset). (unit: 0.1K)"
::= { ePowerEntry 10052 }
pMaxTemperatureWarning OBJECT-TYPE
SYNTAX Utenth (2232..4732)
UNITS "K"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the maximum temperature warning level (use DEF accessor to reset). (unit: 0.1K)"
::= { ePowerEntry 10053 }
pPortStateEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the state of an outlet is changed."
::= { ePowerEntry 10076 }
pCurrentOffEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the outlet current off level is exceeded."
::= { ePowerEntry 10077 }
pCurrentWarningEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the outlet current warning level is exceeded."
::= { ePowerEntry 10078 }
pPowerOffEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the power off level is exceeded."
::= { ePowerEntry 10079 }
pPowerWarningEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the power warning level is exceeded."
::= { ePowerEntry 10080 }
pTotalCurrentOffEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the total outlet current off level is exceeded."
::= { ePowerEntry 10081 }
pTotalCurrentWarningEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the total outlet current warning level is exceeded."
::= { ePowerEntry 10082 }
pTotalPowerOffEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the total power off level is exceeded."
::= { ePowerEntry 10083 }
pTotalPowerWarningEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the total power warning level is exceeded."
::= { ePowerEntry 10084 }
pVoltageWarningEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the voltage warning level is exceeded."
::= { ePowerEntry 10086 }
pTemperatureWarningEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the temperature warning level is exceeded."
::= { ePowerEntry 10087 }
pMaxOverheatingOff OBJECT-TYPE
SYNTAX Utenth (2232..4732)
UNITS "K"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the maximum overheat temperature off level. (unit: 0.1K)"
::= { ePowerEntry 10090 }
pOverheatingOffEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the overtemperature off level is exceeded."
::= { ePowerEntry 10091 }
pPowerCycleTime OBJECT-TYPE
SYNTAX Unsigned32 (0..255)
UNITS "s"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the time interval that is used to do a power cycle of an outlet. (unit: s)"
::= { ePowerEntry 10099 }
pExternalSensorLabel OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the external sensor label. External sensors can be connected to Energy Sensors."
::= { ePowerEntry 10109 }
pMaxOverheatingWarning OBJECT-TYPE
SYNTAX Utenth (2232..4732)
UNITS "K"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the overheating temperature warning level. (unit: 0.1K)"
::= { ePowerEntry 10121 }
pOverheatingWarningEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the overheat warning level is exceeded."
::= { ePowerEntry 10122 }
pMicroIntTimeThreshold OBJECT-TYPE
SYNTAX Utenth (10..65535)
UNITS "ms"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The minimum time the voltage must be interrupted before it is seen as a micro interruption (unit: 0.1ms)"
::= { ePowerEntry 10135 }
pMicroIntEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if a microinterruption on the voltage is detected."
::= { ePowerEntry 10136 }
pSoftFuseCurrentThreshold OBJECT-TYPE
SYNTAX Unsigned32 (0..255)
UNITS "A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The threshold of the soft fuse is a factor of the maximum nominal current off (unit: A)"
::= { ePowerEntry 10137 }
pSoftFuseDelay OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
UNITS "ms"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The minimum time the current of an outlet must be above the soft fuse current threshold to switch it off. (unit: ms)"
::= { ePowerEntry 10138 }
pSoftFuseEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if a soft fuse is triggered."
::= { ePowerEntry 10139 }
pPhaseShiftEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if a phase shift on the voltage is detected."
::= { ePowerEntry 10140 }
pSchedulePortOnTime OBJECT-TYPE
SYNTAX Unsigned32 (0..1439)
UNITS "min"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the time for the scheduler to turn on an outlet. (unit: min)"
::= { ePowerEntry 10146 }
pSchedulePortOffTime OBJECT-TYPE
SYNTAX Unsigned32 (0..1439)
UNITS "min"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the time for the scheduler to turn off an outlet. (unit: min)"
::= { ePowerEntry 10147 }
pEnableSchedulePort OBJECT-TYPE
SYNTAX Unsigned32 (0..1)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the scheduler on an outlet. When enabled the scheduling is repeated daily."
::= { ePowerEntry 10148 }
pBlockSetPortOff OBJECT-TYPE
SYNTAX Unsigned32 (0..1)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Prevent outlets to be set off (only delay on and powercycle are still possible)."
::= { ePowerEntry 10161 }
pSchedulePortChangeEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"event if a port has changed state because of the scheduler"
::= { ePowerEntry 10166 }
pAgentIP OBJECT-TYPE
SYNTAX IpAddress
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"IP address of the agent associated to this outlet"
::= { ePowerEntry 10172 }
pAgentPort OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Network port on which the associated agent will listen"
::= { ePowerEntry 10173 }
pAgentCommunicationEventFlags OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Event flags for events related to agent communication"
::= { ePowerEntry 10174 }
pAlwaysOn OBJECT-TYPE
SYNTAX Unsigned32 (0..1)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Outlets marked as Always On can only be power cycled by the user"
::= { ePowerEntry 10175 }
pGenericTransducerParameters OBJECT-TYPE
SYNTAX Integer32 (2000..2000000000)
UNITS "mA/V"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"sets the slope of the transducer transfer function when the generic transducer type is selected (unit: mA/V)"
::= { ePowerEntry 10190 }
pMaxBigCurrentWarning OBJECT-TYPE
SYNTAX Unsigned32 (100..400000000)
UNITS "A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the maximum current warning level of an outlet. (unit: 0.0001A)"
::= { ePowerEntry 10193 }
pMaxBigPowerWarning OBJECT-TYPE
SYNTAX Uthousandth (2000..2000000000)
UNITS "W"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the maximum power warning level of an outlet. (unit: 0.001W)"
::= { ePowerEntry 10194 }
pGroupNumber OBJECT-TYPE
SYNTAX Unsigned32 (0..5)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Group number per port to group ports"
::= { ePowerEntry 10195 }
pPhaseLink OBJECT-TYPE
SYNTAX Unsigned32 (0..8)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Link the current port with a voltage phase"
::= { ePowerEntry 10196 }
pCurrentSensorSelector OBJECT-TYPE
SYNTAX Unsigned32 (0..255)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Selection of the currentsensor connected to port. To enter your own value you need to use 255 and fill in guid 10190."
::= { ePowerEntry 10197 }
pMinBigCurrentWarning OBJECT-TYPE
SYNTAX Unsigned32 (0..400000000)
UNITS "A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the minimum current warning level of a port. (unit: 0.0001A)"
::= { ePowerEntry 10209 }
esnModule OBJECT IDENTIFIER
::= { esRACKTIVITYMIB 65 }
eESNTable OBJECT-TYPE
SYNTAX SEQUENCE OF EESNEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Temperature Humidity Presure Airflow Waterleak"
::= { esnModule 1 }
eESNEntry OBJECT-TYPE
SYNTAX EESNEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Temperature Humidity Presure Airflow Waterleak"
INDEX { esnModuleIndex, esnIndex }
::= { eESNTable 1 }
EESNEntry ::= SEQUENCE {
aGeneralModuleStatus Unsigned32,
aSpecificModuleStatus Unsigned32,
aCurrentTime TimeTicks,
aVoltage Uhundredth,
aStatePortCur CURPORTSTATE,
aTemperature Utenth,
aHumidity Utenth,
aAirflow Utenth,
aDewPoint Utenth,
aPressure Utenth,
aAnalogueInput Unsigned32,
aWaterleak Unsigned32,
aMotionDetected Unsigned32,
aIOPort Unsigned32,
aHighCurrent Stenth,
aHighPower Shundredth,
aModuleName DisplayString,
aFirmwareVersion Version,
aHardwareVersion Version,
aFirmwareID DisplayString,
aHardwareID DisplayString,
aDisplayTimeOn Unsigned32,
aMaxVoltageWarning Uhundredth,
aMinVoltageWarning Uhundredth,
aMinTemperatureWarning Utenth,
aMaxTemperatureWarning Utenth,
aMinHumidityWarning Utenth,
aMaxHumidityWarning Utenth,
aCurrentWarningEvent EVENTFLAGS,
aPowerWarningEvent EVENTFLAGS,
aVoltageWarningEvent EVENTFLAGS,
aTemperatureWarningEvent EVENTFLAGS,
aHumidityWarningEvent EVENTFLAGS,
aDewPointWarning Utenth,
aDewPointWarningEvent EVENTFLAGS,
aDewPointViolationEvent EVENTFLAGS,
aPressureWarningEvent EVENTFLAGS,
aMinPressureWarning Utenth,
aMaxPressureWarning Utenth,
aDisplayBrightness Unsigned32,
aMotionSensitivity Unsigned32,
aExternalSensorLabel DisplayString,
aRelayLabel DisplayString,
aMinAnalogueInputWarning Unsigned32,
aMaxAnalogueInputWarning Unsigned32,
aWaterleakWarning Unsigned32,
aMinAirflowWarning Unsigned32,
aMaxAirflowWarning Unsigned32,
aAnalogueInputWarningEvent EVENTFLAGS,
aWaterleakWarningEvent EVENTFLAGS,
aAirflowWarningEvent EVENTFLAGS,
aRelayAssertActionEvent EVENTFLAGS,
aRelayDeassertActionEvent EVENTFLAGS,
aMotionWarning Unsigned32,
aMotionWarningEvent EVENTFLAGS,
aDeviceID DisplayString,
aDeviceVersion Version,
aSysName DisplayString,
aMaxHighCurrentWarning Stenth,
aMinHighCurrentWarning Stenth,
aMinHighPowerWarning Shundredth,
aMaxHighPowerWarning Shundredth,
aIOPortWarningEvent EVENTFLAGS,
esnIndex Integer32,
esnModuleIndex Integer32
}
esnIndex OBJECT-TYPE
SYNTAX Integer32 (1..8)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Index for the selected ESN Module"
::= { eESNEntry 65537 }
esnModuleIndex OBJECT-TYPE
SYNTAX Integer32 (1..8)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Selected ESN Module"
::= { eESNEntry 65538 }
aGeneralModuleStatus OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"General status of a module."
::= { eESNEntry 1 }
aSpecificModuleStatus OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Specific status of a module."
::= { eESNEntry 2 }
aCurrentTime OBJECT-TYPE
SYNTAX TimeTicks
UNITS "UNIX"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets or sets the current time (not possible when NTP is enabled). (unit: UNIX)"
::= { eESNEntry 3 }
aVoltage OBJECT-TYPE
SYNTAX Uhundredth
UNITS "V"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the voltage of a power module. (unit: 0.01V)"
::= { eESNEntry 4 }
aStatePortCur OBJECT-TYPE
SYNTAX CURPORTSTATE
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the current state of an outlet. To toggle an outlet use PORTSTAT (CLI) or pPortstate (SNMP) (GUID 10035) instead."
::= { eESNEntry 8 }
aTemperature OBJECT-TYPE
SYNTAX Utenth
UNITS "K"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the current temperature of a temperature sensor. (unit: 0.1K)"
::= { eESNEntry 11 }
aHumidity OBJECT-TYPE
SYNTAX Utenth
UNITS "RH"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the relative humidity. (unit: 0.1RH)"
::= { eESNEntry 12 }
aAirflow OBJECT-TYPE
SYNTAX Utenth
UNITS "m/s"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the current airflow level. (unit: 0.1m/s)"
::= { eESNEntry 23 }
aDewPoint OBJECT-TYPE
SYNTAX Utenth (0..65535)
UNITS "K"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the current dewpoint. Taking the current humidity into consideration, condensation will occur if the temperature drops below this level. (unit: 0.1K)"
::= { eESNEntry 25 }
aPressure OBJECT-TYPE
SYNTAX Utenth
UNITS "hPa"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the atmospheric pressure. (unit: 0.1hPa)"
::= { eESNEntry 26 }
aAnalogueInput OBJECT-TYPE
SYNTAX Unsigned32
UNITS "mV"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the value of an analog input (voltage). (unit: mV)"
::= { eESNEntry 27 }
aWaterleak OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the current state of the water leak sensor."
::= { eESNEntry 28 }
aMotionDetected OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets or resets whether motion has been detected."
::= { eESNEntry 29 }
aIOPort OBJECT-TYPE
SYNTAX Unsigned32 (0..1)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the state of a digital input."
::= { eESNEntry 30 }
aHighCurrent OBJECT-TYPE
SYNTAX Stenth (-32768..32767)
UNITS "A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current for high values (unit: 0.1A)"
::= { eESNEntry 41 }
aHighPower OBJECT-TYPE
SYNTAX Shundredth (-32768..32767)
UNITS "kW"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The power for high values (unit: 0.01kW)"
::= { eESNEntry 43 }
aModuleName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the module name."
::= { eESNEntry 10001 }
aFirmwareVersion OBJECT-TYPE
SYNTAX Version
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the version of the module's firmware."
::= { eESNEntry 10002 }
aHardwareVersion OBJECT-TYPE
SYNTAX Version
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the version of a module's hardware."
::= { eESNEntry 10003 }
aFirmwareID OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the ID of the module's firmware."
::= { eESNEntry 10004 }
aHardwareID OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the ID of a module's hardware."
::= { eESNEntry 10005 }
aDisplayTimeOn OBJECT-TYPE
SYNTAX Unsigned32 (0..255)
UNITS "min"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the display sleep timer. If the display is inactive for longer than this time, the display turns off to save power. Time is in minutes. (unit: min)"
::= { eESNEntry 10032 }
aMaxVoltageWarning OBJECT-TYPE
SYNTAX Uhundredth (0..65535)
UNITS "V"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the maximum voltage warning level. (unit: 0.01V)"
::= { eESNEntry 10047 }
aMinVoltageWarning OBJECT-TYPE
SYNTAX Uhundredth (0..65535)
UNITS "V"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the minimum voltage warning level. (unit: 0.01V)"
::= { eESNEntry 10049 }
aMinTemperatureWarning OBJECT-TYPE
SYNTAX Utenth (2232..4732)
UNITS "K"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the minimum temperature warning level (use DEF accessor to reset). (unit: 0.1K)"
::= { eESNEntry 10052 }
aMaxTemperatureWarning OBJECT-TYPE
SYNTAX Utenth (2232..4732)
UNITS "K"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the maximum temperature warning level (use DEF accessor to reset). (unit: 0.1K)"
::= { eESNEntry 10053 }
aMinHumidityWarning OBJECT-TYPE
SYNTAX Utenth (0..1000)
UNITS "RH"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the minimum relative humidity warning level (use DEF accessor to reset). (unit: 0.1RH)"
::= { eESNEntry 10054 }
aMaxHumidityWarning OBJECT-TYPE
SYNTAX Utenth (0..1000)
UNITS "RH"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the maximum relative humidity warning level (use DEF accessor to reset). (unit: 0.1RH)"
::= { eESNEntry 10055 }
aCurrentWarningEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the outlet current warning level is exceeded."
::= { eESNEntry 10078 }
aPowerWarningEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the power warning level is exceeded."
::= { eESNEntry 10080 }
aVoltageWarningEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the voltage warning level is exceeded."
::= { eESNEntry 10086 }
aTemperatureWarningEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the temperature warning level is exceeded."
::= { eESNEntry 10087 }
aHumidityWarningEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the humidity warning level is exceeded."
::= { eESNEntry 10088 }
aDewPointWarning OBJECT-TYPE
SYNTAX Utenth (0..65535)
UNITS "K"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the dewpoint warning level. If the temperature difference between the current temperature and the dewpoint temperature drops below this value, an event is generated. (unit: 0.1K)"
::= { eESNEntry 10092 }
aDewPointWarningEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the dewpoint warning level is exceeded."
::= { eESNEntry 10093 }
aDewPointViolationEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the dewpoint temperature is reached."
::= { eESNEntry 10094 }
aPressureWarningEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the atmospheric pressure warning level is exceeded."
::= { eESNEntry 10095 }
aMinPressureWarning OBJECT-TYPE
SYNTAX Utenth (0..65535)
UNITS "hPa"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the minimum atmospheric pressure warning level. (unit: 0.1hPa)"
::= { eESNEntry 10096 }
aMaxPressureWarning OBJECT-TYPE
SYNTAX Utenth (0..65535)
UNITS "hPa"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the maximum atmospheric pressure warning level. (unit: 0.1hPa)"
::= { eESNEntry 10097 }
aDisplayBrightness OBJECT-TYPE
SYNTAX Unsigned32 (0..255)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the display brightness (if supported)."
::= { eESNEntry 10098 }
aMotionSensitivity OBJECT-TYPE
SYNTAX Unsigned32 (0..127)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the sensitivity of a motion sensor."
::= { eESNEntry 10107 }
aExternalSensorLabel OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the external sensor label. External sensors can be connected to Energy Sensors."
::= { eESNEntry 10109 }
aRelayLabel OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults an Energy Sensor relay label."
::= { eESNEntry 10110 }
aMinAnalogueInputWarning OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
UNITS "mV"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the lower warning level for an analog input. A warning is generated if this level is exceeded. (unit: mV)"
::= { eESNEntry 10111 }
aMaxAnalogueInputWarning OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the upper warning level for an analog input. A warning is generated if this level is exceeded."
::= { eESNEntry 10112 }
aWaterleakWarning OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the water leak detection state (0 = disabled, other values = enabled)."
::= { eESNEntry 10113 }
aMinAirflowWarning OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the minimum warning level for an airflow sensor. A warning is generated if this level is exceeded."
::= { eESNEntry 10114 }
aMaxAirflowWarning OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the maximum warning level for an airflow sensor. A warning is generated if this level is exceeded."
::= { eESNEntry 10115 }
aAnalogueInputWarningEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the analog input warning level is exceeded."
::= { eESNEntry 10116 }
aWaterleakWarningEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if a water leak is detected."
::= { eESNEntry 10117 }
aAirflowWarningEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the airflow warning level is exceeded."
::= { eESNEntry 10118 }
aRelayAssertActionEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if an Energy Sensor relay is asserted."
::= { eESNEntry 10119 }
aRelayDeassertActionEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if an Energy Sensor relay is deasserted."
::= { eESNEntry 10120 }
aMotionWarning OBJECT-TYPE
SYNTAX Unsigned32 (0..127)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the motion warning threshold."
::= { eESNEntry 10141 }
aMotionWarningEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the motion warning threshold is exceeded."
::= { eESNEntry 10149 }
aDeviceID OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The ID of the device."
::= { eESNEntry 10150 }
aDeviceVersion OBJECT-TYPE
SYNTAX Version
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The version of the device."
::= { eESNEntry 10151 }
aSysName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The full name of the device."
::= { eESNEntry 10152 }
aMaxHighCurrentWarning OBJECT-TYPE
SYNTAX Stenth (-32768..32767)
UNITS "A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets sets or defaults the maximum high current warning level. (unit: 0.1A)"
::= { eESNEntry 10165 }
aMinHighCurrentWarning OBJECT-TYPE
SYNTAX Stenth (-32768..32767)
UNITS "A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets sets or defaults the minimum high current warning level. (unit: 0.1A)"
::= { eESNEntry 10176 }
aMinHighPowerWarning OBJECT-TYPE
SYNTAX Shundredth (-32768..32767)
UNITS "kW"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets sets or defaults the power min high current warning level. (unit: 0.01kW)"
::= { eESNEntry 10177 }
aMaxHighPowerWarning OBJECT-TYPE
SYNTAX Shundredth (-32768..32767)
UNITS "kW"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets sets or defaults the power max high current warning level. (unit: 0.01kW)"
::= { eESNEntry 10178 }
aIOPortWarningEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the IO Port change state."
::= { eESNEntry 10192 }
testmoduleModule OBJECT IDENTIFIER
::= { esRACKTIVITYMIB 89 }
eTestModuleTable OBJECT-TYPE
SYNTAX SEQUENCE OF ETestModuleEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Module to test the R-bus"
::= { testmoduleModule 1 }
eTestModuleEntry OBJECT-TYPE
SYNTAX ETestModuleEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Module to test the R-bus"
INDEX { testmoduleModuleIndex, testmoduleIndex }
::= { eTestModuleTable 1 }
ETestModuleEntry ::= SEQUENCE {
yGeneralModuleStatus Unsigned32,
ySpecificModuleStatus Unsigned32,
yCurrentTime TimeTicks,
yCurrent Uthousandth,
yStatePortCur CURPORTSTATE,
yAnalogueInput Unsigned32,
yModuleName DisplayString,
yFirmwareVersion Version,
yHardwareVersion Version,
yFirmwareID DisplayString,
yHardwareID DisplayString,
testmoduleIndex Integer32,
testmoduleModuleIndex Integer32
}
testmoduleIndex OBJECT-TYPE
SYNTAX Integer32 (1..8)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Index for the selected TestModule Module"
::= { eTestModuleEntry 65537 }
testmoduleModuleIndex OBJECT-TYPE
SYNTAX Integer32 (1..8)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Selected TestModule Module"
::= { eTestModuleEntry 65538 }
yGeneralModuleStatus OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"General status of a module."
::= { eTestModuleEntry 1 }
ySpecificModuleStatus OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Specific status of a module."
::= { eTestModuleEntry 2 }
yCurrentTime OBJECT-TYPE
SYNTAX TimeTicks
UNITS "UNIX"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets or sets the current time (not possible when NTP is enabled). (unit: UNIX)"
::= { eTestModuleEntry 3 }
yCurrent OBJECT-TYPE
SYNTAX Uthousandth
UNITS "A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the current of an outlet. (unit: 0.001A)"
::= { eTestModuleEntry 6 }
yStatePortCur OBJECT-TYPE
SYNTAX CURPORTSTATE
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the current state of an outlet. To toggle an outlet use PORTSTAT (CLI) or pPortstate (SNMP) (GUID 10035) instead."
::= { eTestModuleEntry 8 }
yAnalogueInput OBJECT-TYPE
SYNTAX Unsigned32
UNITS "mV"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the value of an analog input (voltage). (unit: mV)"
::= { eTestModuleEntry 27 }
yModuleName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the module name."
::= { eTestModuleEntry 10001 }
yFirmwareVersion OBJECT-TYPE
SYNTAX Version
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the version of the module's firmware."
::= { eTestModuleEntry 10002 }
yHardwareVersion OBJECT-TYPE
SYNTAX Version
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the version of a module's hardware."
::= { eTestModuleEntry 10003 }
yFirmwareID OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the ID of the module's firmware."
::= { eTestModuleEntry 10004 }
yHardwareID OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the ID of a module's hardware."
::= { eTestModuleEntry 10005 }
pcModule OBJECT IDENTIFIER
::= { esRACKTIVITYMIB 85 }
ePCTable OBJECT-TYPE
SYNTAX SEQUENCE OF EPCEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"NO_INFO"
::= { pcModule 1 }
ePCEntry OBJECT-TYPE
SYNTAX EPCEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"NO_INFO"
INDEX { pcModuleIndex, pcIndex }
::= { ePCTable 1 }
EPCEntry ::= SEQUENCE {
uGeneralModuleStatus Unsigned32,
uSpecificModuleStatus Unsigned32,
uCurrentTime TimeTicks,
uVoltage Uhundredth,
uCurrent Uthousandth,
uStatePortCur CURPORTSTATE,
uTemperature Utenth,
uHumidity Utenth,
uModuleName DisplayString,
uFirmwareVersion Version,
uHardwareVersion Version,
uFirmwareID DisplayString,
uHardwareID DisplayString,
uPortState Unsigned32,
pcIndex Integer32,
pcModuleIndex Integer32
}
pcIndex OBJECT-TYPE
SYNTAX Integer32 (1..8)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Index for the selected PC Module"
::= { ePCEntry 65537 }
pcModuleIndex OBJECT-TYPE
SYNTAX Integer32 (1..8)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Selected PC Module"
::= { ePCEntry 65538 }
uGeneralModuleStatus OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"General status of a module."
::= { ePCEntry 1 }
uSpecificModuleStatus OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Specific status of a module."
::= { ePCEntry 2 }
uCurrentTime OBJECT-TYPE
SYNTAX TimeTicks
UNITS "UNIX"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets or sets the current time (not possible when NTP is enabled). (unit: UNIX)"
::= { ePCEntry 3 }
uVoltage OBJECT-TYPE
SYNTAX Uhundredth (0..65535)
UNITS "V"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the voltage of a power module. (unit: 0.01V)"
::= { ePCEntry 4 }
uCurrent OBJECT-TYPE
SYNTAX Uthousandth (0..65535)
UNITS "A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the current of an outlet. (unit: 0.001A)"
::= { ePCEntry 6 }
uStatePortCur OBJECT-TYPE
SYNTAX CURPORTSTATE
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the current state of an outlet. To toggle an outlet use PORTSTAT (CLI) or pPortstate (SNMP) (GUID 10035) instead."
::= { ePCEntry 8 }
uTemperature OBJECT-TYPE
SYNTAX Utenth (2232..4732)
UNITS "K"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the current temperature of a temperature sensor. (unit: 0.1K)"
::= { ePCEntry 11 }
uHumidity OBJECT-TYPE
SYNTAX Utenth (0..1000)
UNITS "RH"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the relative humidity. (unit: 0.1RH)"
::= { ePCEntry 12 }
uModuleName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the module name."
::= { ePCEntry 10001 }
uFirmwareVersion OBJECT-TYPE
SYNTAX Version
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the version of the module's firmware."
::= { ePCEntry 10002 }
uHardwareVersion OBJECT-TYPE
SYNTAX Version
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the version of a module's hardware."
::= { ePCEntry 10003 }
uFirmwareID OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the ID of the module's firmware."
::= { ePCEntry 10004 }
uHardwareID OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the ID of a module's hardware."
::= { ePCEntry 10005 }
uPortState OBJECT-TYPE
SYNTAX Unsigned32 (0..1)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Sets the state of an outlet: 0=OFF, 1=ON, 2=POWER CYCLE. To get the state of an outlet use CPORTSTAT (CLI) or pStatePortCur (SNMP) (GUID 8) instead."
::= { ePCEntry 10035 }
energymonitorModule OBJECT IDENTIFIER
::= { esRACKTIVITYMIB 69 }
eEnergyMonitorTable OBJECT-TYPE
SYNTAX SEQUENCE OF EEnergyMonitorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"NO_INFO"
::= { energymonitorModule 1 }
eEnergyMonitorEntry OBJECT-TYPE
SYNTAX EEnergyMonitorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"NO_INFO"
INDEX { energymonitorModuleIndex, energymonitorIndex }
::= { eEnergyMonitorTable 1 }
EEnergyMonitorEntry ::= SEQUENCE {
eGeneralModuleStatus Unsigned32,
eSpecificModuleStatus Unsigned32,
eCurrentTime TimeTicks,
eVoltage Uhundredth,
eFrequency Uthousandth,
eCurrent Uthousandth,
ePower Unsigned32,
eActiveEnergy Uthousandth,
eApparentEnergy Uthousandth,
eTemperature Utenth,
eApparentPower Unsigned32,
ePowerFactor Unsigned32,
eTotalCurrent Uthousandth,
eTotalRealPower Unsigned32,
eTotalApparentPower Unsigned32,
eTotalActiveEnergy Uthousandth,
eTotalApparentEnergy Uthousandth,
eTotalPowerFactor Unsigned32,
eTimeOnline Unsigned32,
eTotalHarmonicDistortion Utenth,
eModuleName DisplayString,
eFirmwareVersion Version,
eHardwareVersion Version,
eFirmwareID DisplayString,
eHardwareID DisplayString,
eMaxCurrentWarning Uthousandth,
eMaxPowerWarning Unsigned32,
eMaxTotalCurrentWarning Uthousandth,
eMaxTotalPowerWarning Unsigned32,
eMaxVoltageWarning Uhundredth,
eMinVoltageWarning Uhundredth,
eMinTemperatureWarning Utenth,
eMaxTemperatureWarning Utenth,
eCurrentWarningEvent EVENTFLAGS,
ePowerWarningEvent EVENTFLAGS,
eTotalCurrentWarningEvent EVENTFLAGS,
eTotalPowerWarningEvent EVENTFLAGS,
eVoltageWarningEvent EVENTFLAGS,
eTemperatureWarningEvent EVENTFLAGS,
eMicroIntTimeThreshold Utenth,
eMicroIntEvent EVENTFLAGS,
energymonitorIndex Integer32,
energymonitorModuleIndex Integer32
}
energymonitorIndex OBJECT-TYPE
SYNTAX Integer32 (1..8)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Index for the selected EnergyMonitor Module"
::= { eEnergyMonitorEntry 65537 }
energymonitorModuleIndex OBJECT-TYPE
SYNTAX Integer32 (1..8)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Selected EnergyMonitor Module"
::= { eEnergyMonitorEntry 65538 }
eGeneralModuleStatus OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"General status of a module."
::= { eEnergyMonitorEntry 1 }
eSpecificModuleStatus OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Specific status of a module."
::= { eEnergyMonitorEntry 2 }
eCurrentTime OBJECT-TYPE
SYNTAX TimeTicks
UNITS "UNIX"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets or sets the current time (not possible when NTP is enabled). (unit: UNIX)"
::= { eEnergyMonitorEntry 3 }
eVoltage OBJECT-TYPE
SYNTAX Uhundredth
UNITS "V"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the voltage of a power module. (unit: 0.01V)"
::= { eEnergyMonitorEntry 4 }
eFrequency OBJECT-TYPE
SYNTAX Uthousandth
UNITS "Hz"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the frequency of the input voltage of a power module. (unit: 0.001Hz)"
::= { eEnergyMonitorEntry 5 }
eCurrent OBJECT-TYPE
SYNTAX Uthousandth
UNITS "A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the current of an outlet. (unit: 0.001A)"
::= { eEnergyMonitorEntry 6 }
ePower OBJECT-TYPE
SYNTAX Unsigned32
UNITS "W"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the power of an outlet. (unit: W)"
::= { eEnergyMonitorEntry 7 }
eActiveEnergy OBJECT-TYPE
SYNTAX Uthousandth
UNITS "kWh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the energy used by an outlet. (unit: 0.001kWh)"
::= { eEnergyMonitorEntry 9 }
eApparentEnergy OBJECT-TYPE
SYNTAX Uthousandth
UNITS "kVAh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the apparent energy used by an outlet. (unit: 0.001kVAh)"
::= { eEnergyMonitorEntry 10 }
eTemperature OBJECT-TYPE
SYNTAX Utenth
UNITS "K"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the current temperature of a temperature sensor. (unit: 0.1K)"
::= { eEnergyMonitorEntry 11 }
eApparentPower OBJECT-TYPE
SYNTAX Unsigned32
UNITS "VA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the apparent power of an outlet. (unit: VA)"
::= { eEnergyMonitorEntry 15 }
ePowerFactor OBJECT-TYPE
SYNTAX Unsigned32
UNITS "%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the power factor of an outlet. (unit: %)"
::= { eEnergyMonitorEntry 16 }
eTotalCurrent OBJECT-TYPE
SYNTAX Uthousandth
UNITS "A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the total current of a power module. (unit: 0.001A)"
::= { eEnergyMonitorEntry 17 }
eTotalRealPower OBJECT-TYPE
SYNTAX Unsigned32
UNITS "W"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the total power level of a power module. (unit: W)"
::= { eEnergyMonitorEntry 18 }
eTotalApparentPower OBJECT-TYPE
SYNTAX Unsigned32
UNITS "VA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the total apparent power of a power module. (unit: VA)"
::= { eEnergyMonitorEntry 19 }
eTotalActiveEnergy OBJECT-TYPE
SYNTAX Uthousandth
UNITS "kWh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the total energy of a power module. (unit: 0.001kWh)"
::= { eEnergyMonitorEntry 20 }
eTotalApparentEnergy OBJECT-TYPE
SYNTAX Uthousandth
UNITS "kVAh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the total apparent energy of a power module. (unit: 0.001kVAh)"
::= { eEnergyMonitorEntry 21 }
eTotalPowerFactor OBJECT-TYPE
SYNTAX Unsigned32
UNITS "%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the total power factor of a power module. (unit: %)"
::= { eEnergyMonitorEntry 22 }
eTimeOnline OBJECT-TYPE
SYNTAX Unsigned32
UNITS "s"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the amount of seconds since the last reset. (unit: s)"
::= { eEnergyMonitorEntry 24 }
eTotalHarmonicDistortion OBJECT-TYPE
SYNTAX Utenth (0..1000)
UNITS "%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"total harmonic distortion - outlet (unit: 0.1%)"
::= { eEnergyMonitorEntry 50 }
eModuleName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the module name."
::= { eEnergyMonitorEntry 10001 }
eFirmwareVersion OBJECT-TYPE
SYNTAX Version
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the version of the module's firmware."
::= { eEnergyMonitorEntry 10002 }
eHardwareVersion OBJECT-TYPE
SYNTAX Version
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the version of a module's hardware."
::= { eEnergyMonitorEntry 10003 }
eFirmwareID OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the ID of the module's firmware."
::= { eEnergyMonitorEntry 10004 }
eHardwareID OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the ID of a module's hardware."
::= { eEnergyMonitorEntry 10005 }
eMaxCurrentWarning OBJECT-TYPE
SYNTAX Uthousandth (100..8000)
UNITS "A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the maximum current warning level of an outlet. (unit: 0.001A)"
::= { eEnergyMonitorEntry 10039 }
eMaxPowerWarning OBJECT-TYPE
SYNTAX Unsigned32 (20..2000)
UNITS "W"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the maximum power warning level of an outlet. (unit: W)"
::= { eEnergyMonitorEntry 10041 }
eMaxTotalCurrentWarning OBJECT-TYPE
SYNTAX Uthousandth (100..16000)
UNITS "A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the total maximum current warning level of a power module. (unit: 0.001A)"
::= { eEnergyMonitorEntry 10043 }
eMaxTotalPowerWarning OBJECT-TYPE
SYNTAX Unsigned32 (20..4000)
UNITS "W"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the maximum total power warning level. (unit: W)"
::= { eEnergyMonitorEntry 10045 }
eMaxVoltageWarning OBJECT-TYPE
SYNTAX Uhundredth (5000..30000)
UNITS "V"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the maximum voltage warning level. (unit: 0.01V)"
::= { eEnergyMonitorEntry 10047 }
eMinVoltageWarning OBJECT-TYPE
SYNTAX Uhundredth (5000..30000)
UNITS "V"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the minimum voltage warning level. (unit: 0.01V)"
::= { eEnergyMonitorEntry 10049 }
eMinTemperatureWarning OBJECT-TYPE
SYNTAX Utenth (2232..4732)
UNITS "K"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the minimum temperature warning level (use DEF accessor to reset). (unit: 0.1K)"
::= { eEnergyMonitorEntry 10052 }
eMaxTemperatureWarning OBJECT-TYPE
SYNTAX Utenth (2232..4732)
UNITS "K"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the maximum temperature warning level (use DEF accessor to reset). (unit: 0.1K)"
::= { eEnergyMonitorEntry 10053 }
eCurrentWarningEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the outlet current warning level is exceeded."
::= { eEnergyMonitorEntry 10078 }
ePowerWarningEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the power warning level is exceeded."
::= { eEnergyMonitorEntry 10080 }
eTotalCurrentWarningEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the total outlet current warning level is exceeded."
::= { eEnergyMonitorEntry 10082 }
eTotalPowerWarningEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the total power warning level is exceeded."
::= { eEnergyMonitorEntry 10084 }
eVoltageWarningEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the voltage warning level is exceeded."
::= { eEnergyMonitorEntry 10086 }
eTemperatureWarningEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the temperature warning level is exceeded."
::= { eEnergyMonitorEntry 10087 }
eMicroIntTimeThreshold OBJECT-TYPE
SYNTAX Utenth (10..65535)
UNITS "ms"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The minimum time the voltage must be interrupted before it is seen as a micro interruption (unit: 0.1ms)"
::= { eEnergyMonitorEntry 10135 }
eMicroIntEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if a microinterruption on the voltage is detected."
::= { eEnergyMonitorEntry 10136 }
threephasepowerModule OBJECT IDENTIFIER
::= { esRACKTIVITYMIB 66 }
eThreePhasePowerTable OBJECT-TYPE
SYNTAX SEQUENCE OF EThreePhasePowerEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"NO_INFO"
::= { threephasepowerModule 1 }
eThreePhasePowerEntry OBJECT-TYPE
SYNTAX EThreePhasePowerEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"NO_INFO"
INDEX { threephasepowerModuleIndex, threephasepowerIndex }
::= { eThreePhasePowerTable 1 }
EThreePhasePowerEntry ::= SEQUENCE {
threephasepowerIndex Integer32,
threephasepowerModuleIndex Integer32
}
threephasepowerIndex OBJECT-TYPE
SYNTAX Integer32 (1..8)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Index for the selected ThreePhasePower Module"
::= { eThreePhasePowerEntry 65537 }
threephasepowerModuleIndex OBJECT-TYPE
SYNTAX Integer32 (1..8)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Selected ThreePhasePower Module"
::= { eThreePhasePowerEntry 65538 }
measuring3phaseModule OBJECT IDENTIFIER
::= { esRACKTIVITYMIB 81 }
eMeasuring3PhaseTable OBJECT-TYPE
SYNTAX SEQUENCE OF EMeasuring3PhaseEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"NO_INFO"
::= { measuring3phaseModule 1 }
eMeasuring3PhaseEntry OBJECT-TYPE
SYNTAX EMeasuring3PhaseEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"NO_INFO"
INDEX { measuring3phaseModuleIndex, measuring3phaseIndex }
::= { eMeasuring3PhaseTable 1 }
EMeasuring3PhaseEntry ::= SEQUENCE {
qGeneralModuleStatus Unsigned32,
qSpecificModuleStatus Unsigned32,
qCurrentTime TimeTicks,
qVoltage Uhundredth,
qFrequency Uthousandth,
qActiveEnergy Uthousandth,
qApparentEnergy Uthousandth,
qTemperature Utenth,
qPowerFactor Unsigned32,
qTimeOnline Unsigned32,
qIOPort Unsigned32,
qTotalHarmonicDistortion Utenth,
qPhase Unsigned32,
qBigCurrent Unsigned32,
qBigPower Uthousandth,
qBigApparentPower Uthousandth,
qStatus Unsigned32,
qModuleName DisplayString,
qFirmwareVersion Version,
qHardwareVersion Version,
qFirmwareID DisplayString,
qHardwareID DisplayString,
qPortState Unsigned32,
qMaxVoltageWarning Uhundredth,
qMinVoltageWarning Uhundredth,
qMinTemperatureWarning Utenth,
qMaxTemperatureWarning Utenth,
qPortStateEvent EVENTFLAGS,
qCurrentWarningEvent EVENTFLAGS,
qPowerWarningEvent EVENTFLAGS,
qVoltageWarningEvent EVENTFLAGS,
qTemperatureWarningEvent EVENTFLAGS,
qMicroIntTimeThreshold Utenth,
qMicroIntEvent EVENTFLAGS,
qDeviceID DisplayString,
qDeviceVersion Version,
qMaxBigCurrentWarning Unsigned32,
qMaxBigPowerWarning Uthousandth,
qCurrentSensorSelector Unsigned32,
qMinBigCurrentWarning Unsigned32,
qkWhMode Unsigned32,
measuring3phaseIndex Integer32,
measuring3phaseModuleIndex Integer32
}
measuring3phaseIndex OBJECT-TYPE
SYNTAX Integer32 (1..8)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Index for the selected Measuring3Phase Module"
::= { eMeasuring3PhaseEntry 65537 }
measuring3phaseModuleIndex OBJECT-TYPE
SYNTAX Integer32 (1..8)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Selected Measuring3Phase Module"
::= { eMeasuring3PhaseEntry 65538 }
qGeneralModuleStatus OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"General status of a module."
::= { eMeasuring3PhaseEntry 1 }
qSpecificModuleStatus OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Specific status of a module."
::= { eMeasuring3PhaseEntry 2 }
qCurrentTime OBJECT-TYPE
SYNTAX TimeTicks
UNITS "UNIX"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets or sets the current time (not possible when NTP is enabled). (unit: UNIX)"
::= { eMeasuring3PhaseEntry 3 }
qVoltage OBJECT-TYPE
SYNTAX Uhundredth
UNITS "V"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the voltage of a power module. (unit: 0.01V)"
::= { eMeasuring3PhaseEntry 4 }
qFrequency OBJECT-TYPE
SYNTAX Uthousandth
UNITS "Hz"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the frequency of the input voltage of a power module. (unit: 0.001Hz)"
::= { eMeasuring3PhaseEntry 5 }
qActiveEnergy OBJECT-TYPE
SYNTAX Uthousandth
UNITS "kWh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the energy used by an outlet. (unit: 0.001kWh)"
::= { eMeasuring3PhaseEntry 9 }
qApparentEnergy OBJECT-TYPE
SYNTAX Uthousandth
UNITS "kVAh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the apparent energy used by an outlet. (unit: 0.001kVAh)"
::= { eMeasuring3PhaseEntry 10 }
qTemperature OBJECT-TYPE
SYNTAX Utenth
UNITS "K"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the current temperature of a temperature sensor. (unit: 0.1K)"
::= { eMeasuring3PhaseEntry 11 }
qPowerFactor OBJECT-TYPE
SYNTAX Unsigned32
UNITS "%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the power factor of an outlet. (unit: %)"
::= { eMeasuring3PhaseEntry 16 }
qTimeOnline OBJECT-TYPE
SYNTAX Unsigned32
UNITS "s"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the amount of seconds since the last reset. (unit: s)"
::= { eMeasuring3PhaseEntry 24 }
qIOPort OBJECT-TYPE
SYNTAX Unsigned32 (0..1)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the state of a digital input."
::= { eMeasuring3PhaseEntry 30 }
qTotalHarmonicDistortion OBJECT-TYPE
SYNTAX Utenth (0..1000)
UNITS "%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"total harmonic distortion - outlet (unit: 0.1%)"
::= { eMeasuring3PhaseEntry 50 }
qPhase OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
UNITS "degr"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"the phase between 2 waves (unit: degr)"
::= { eMeasuring3PhaseEntry 51 }
qBigCurrent OBJECT-TYPE
SYNTAX Unsigned32
UNITS "A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the current of an outlet. (unit: 0.0001A)"
::= { eMeasuring3PhaseEntry 52 }
qBigPower OBJECT-TYPE
SYNTAX Uthousandth
UNITS "W"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the power of an outlet. (unit: 0.001W)"
::= { eMeasuring3PhaseEntry 53 }
qBigApparentPower OBJECT-TYPE
SYNTAX Uthousandth
UNITS "VA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the apparent power of an outlet. (unit: 0.001VA)"
::= { eMeasuring3PhaseEntry 54 }
qStatus OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"status of a module"
::= { eMeasuring3PhaseEntry 1000 }
qModuleName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the module name."
::= { eMeasuring3PhaseEntry 10001 }
qFirmwareVersion OBJECT-TYPE
SYNTAX Version
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the version of the module's firmware."
::= { eMeasuring3PhaseEntry 10002 }
qHardwareVersion OBJECT-TYPE
SYNTAX Version
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the version of a module's hardware."
::= { eMeasuring3PhaseEntry 10003 }
qFirmwareID OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the ID of the module's firmware."
::= { eMeasuring3PhaseEntry 10004 }
qHardwareID OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the ID of a module's hardware."
::= { eMeasuring3PhaseEntry 10005 }
qPortState OBJECT-TYPE
SYNTAX Unsigned32 (0..1)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Sets the state of an outlet: 0=OFF, 1=ON, 2=POWER CYCLE. To get the state of an outlet use CPORTSTAT (CLI) or pStatePortCur (SNMP) (GUID 8) instead."
::= { eMeasuring3PhaseEntry 10035 }
qMaxVoltageWarning OBJECT-TYPE
SYNTAX Uhundredth (5000..30000)
UNITS "V"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the maximum voltage warning level. (unit: 0.01V)"
::= { eMeasuring3PhaseEntry 10047 }
qMinVoltageWarning OBJECT-TYPE
SYNTAX Uhundredth (5000..30000)
UNITS "V"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the minimum voltage warning level. (unit: 0.01V)"
::= { eMeasuring3PhaseEntry 10049 }
qMinTemperatureWarning OBJECT-TYPE
SYNTAX Utenth (2232..4732)
UNITS "K"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the minimum temperature warning level (use DEF accessor to reset). (unit: 0.1K)"
::= { eMeasuring3PhaseEntry 10052 }
qMaxTemperatureWarning OBJECT-TYPE
SYNTAX Utenth (2232..4732)
UNITS "K"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the maximum temperature warning level (use DEF accessor to reset). (unit: 0.1K)"
::= { eMeasuring3PhaseEntry 10053 }
qPortStateEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the state of an outlet is changed."
::= { eMeasuring3PhaseEntry 10076 }
qCurrentWarningEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the outlet current warning level is exceeded."
::= { eMeasuring3PhaseEntry 10078 }
qPowerWarningEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the power warning level is exceeded."
::= { eMeasuring3PhaseEntry 10080 }
qVoltageWarningEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the voltage warning level is exceeded."
::= { eMeasuring3PhaseEntry 10086 }
qTemperatureWarningEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if the temperature warning level is exceeded."
::= { eMeasuring3PhaseEntry 10087 }
qMicroIntTimeThreshold OBJECT-TYPE
SYNTAX Utenth (10..65535)
UNITS "ms"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The minimum time the voltage must be interrupted before it is seen as a micro interruption (unit: 0.1ms)"
::= { eMeasuring3PhaseEntry 10135 }
qMicroIntEvent OBJECT-TYPE
SYNTAX EVENTFLAGS
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the SNMP trap if a microinterruption on the voltage is detected."
::= { eMeasuring3PhaseEntry 10136 }
qDeviceID OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The ID of the device."
::= { eMeasuring3PhaseEntry 10150 }
qDeviceVersion OBJECT-TYPE
SYNTAX Version
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The version of the device."
::= { eMeasuring3PhaseEntry 10151 }
qMaxBigCurrentWarning OBJECT-TYPE
SYNTAX Unsigned32 (100..400000000)
UNITS "A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the maximum current warning level of an outlet. (unit: 0.0001A)"
::= { eMeasuring3PhaseEntry 10193 }
qMaxBigPowerWarning OBJECT-TYPE
SYNTAX Uthousandth (2000..2000000000)
UNITS "W"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the maximum power warning level of an outlet. (unit: 0.001W)"
::= { eMeasuring3PhaseEntry 10194 }
qCurrentSensorSelector OBJECT-TYPE
SYNTAX Unsigned32 (0..255)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Selection of the currentsensor connected to port. To enter your own value you need to use 255 and fill in guid 10190."
::= { eMeasuring3PhaseEntry 10197 }
qMinBigCurrentWarning OBJECT-TYPE
SYNTAX Unsigned32 (0..400000000)
UNITS "A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the minimum current warning level of a port. (unit: 0.0001A)"
::= { eMeasuring3PhaseEntry 10209 }
qkWhMode OBJECT-TYPE
SYNTAX Unsigned32 (0..2)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set the mode when to count kWh, 0 = always, 1 = only positive, 2= only negative"
::= { eMeasuring3PhaseEntry 10234 }
displaymoduleModule OBJECT IDENTIFIER
::= { esRACKTIVITYMIB 68 }
eDisplayModuleTable OBJECT-TYPE
SYNTAX SEQUENCE OF EDisplayModuleEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"NO_INFO"
::= { displaymoduleModule 1 }
eDisplayModuleEntry OBJECT-TYPE
SYNTAX EDisplayModuleEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"NO_INFO"
INDEX { displaymoduleModuleIndex, displaymoduleIndex }
::= { eDisplayModuleTable 1 }
EDisplayModuleEntry ::= SEQUENCE {
dGeneralModuleStatus Unsigned32,
dSpecificModuleStatus Unsigned32,
dCurrentTime TimeTicks,
dTemperature Utenth,
dTimeOnline Unsigned32,
dModuleName DisplayString,
dFirmwareVersion Version,
dHardwareVersion Version,
dFirmwareID DisplayString,
dHardwareID DisplayString,
dMinTemperatureWarning Utenth,
dMaxTemperatureWarning Utenth,
dDisplayAllDevices Unsigned32,
displaymoduleIndex Integer32,
displaymoduleModuleIndex Integer32
}
displaymoduleIndex OBJECT-TYPE
SYNTAX Integer32 (1..8)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Index for the selected DisplayModule Module"
::= { eDisplayModuleEntry 65537 }
displaymoduleModuleIndex OBJECT-TYPE
SYNTAX Integer32 (1..8)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Selected DisplayModule Module"
::= { eDisplayModuleEntry 65538 }
dGeneralModuleStatus OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"General status of a module."
::= { eDisplayModuleEntry 1 }
dSpecificModuleStatus OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Specific status of a module."
::= { eDisplayModuleEntry 2 }
dCurrentTime OBJECT-TYPE
SYNTAX TimeTicks
UNITS "UNIX"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets or sets the current time (not possible when NTP is enabled). (unit: UNIX)"
::= { eDisplayModuleEntry 3 }
dTemperature OBJECT-TYPE
SYNTAX Utenth
UNITS "K"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the current temperature of a temperature sensor. (unit: 0.1K)"
::= { eDisplayModuleEntry 11 }
dTimeOnline OBJECT-TYPE
SYNTAX Unsigned32
UNITS "s"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the amount of seconds since the last reset. (unit: s)"
::= { eDisplayModuleEntry 24 }
dModuleName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the module name."
::= { eDisplayModuleEntry 10001 }
dFirmwareVersion OBJECT-TYPE
SYNTAX Version
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the version of the module's firmware."
::= { eDisplayModuleEntry 10002 }
dHardwareVersion OBJECT-TYPE
SYNTAX Version
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the version of a module's hardware."
::= { eDisplayModuleEntry 10003 }
dFirmwareID OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the ID of the module's firmware."
::= { eDisplayModuleEntry 10004 }
dHardwareID OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Gets the ID of a module's hardware."
::= { eDisplayModuleEntry 10005 }
dMinTemperatureWarning OBJECT-TYPE
SYNTAX Utenth (2232..4732)
UNITS "K"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the minimum temperature warning level (use DEF accessor to reset). (unit: 0.1K)"
::= { eDisplayModuleEntry 10052 }
dMaxTemperatureWarning OBJECT-TYPE
SYNTAX Utenth (2232..4732)
UNITS "K"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Gets, sets or defaults the maximum temperature warning level (use DEF accessor to reset). (unit: 0.1K)"
::= { eDisplayModuleEntry 10053 }
dDisplayAllDevices OBJECT-TYPE
SYNTAX Unsigned32 (0..1)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"If a display need to show all devices or just a small list"
::= { eDisplayModuleEntry 10237 }
errorValueTooHighRaised NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"This trap is sent when an element goes above the specified error threshold indicating the maximum value for this element"
::= { racktivityNotif 16 }
errorValueTooLowRaised NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"This trap is sent when an element goes below the specified error threshold indicating the minimum value for this element"
::= { racktivityNotif 17 }
errorRaised NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"This trap is sent when an element gets into an error state"
::= { racktivityNotif 18 }
errorValueTooHighCleared NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"This trap is sent when an element goes below the specified error threshold indicating the maximum value for this element"
::= { racktivityNotif 19 }
errorValueTooLowCleared NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"This trap is sent when an element goes above the specified error threshold indicating the minimum value for this element"
::= { racktivityNotif 20 }
errorCleared NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"This trap is sent when an element recovers from an error state"
::= { racktivityNotif 21 }
warningValueTooHighRaised NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"This trap is sent when an element goes above the specified warning threshold indicating the maximum value for this element"
::= { racktivityNotif 48 }
warningValueTooLowRaised NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"This trap is sent when an element goes below the specified warning threshold indicating the minimum value for this element"
::= { racktivityNotif 49 }
warningRaised NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"This trap is sent when an element gets into an warning state"
::= { racktivityNotif 50 }
warningValueTooHighCleared NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"This trap is sent when an element goes below the specified warning threshold indicating the maximum value for this element"
::= { racktivityNotif 51 }
warningValueTooLowCleared NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"This trap is sent when an element goes above the specified warning threshold indicating the minimum value for this element"
::= { racktivityNotif 52 }
warningCleared NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"This trap is sent when an element recovers from an warning state"
::= { racktivityNotif 53 }
infoValueTooHighRaised NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"This trap is sent when an element goes above a specified threshold indicating the maximum value for this element"
::= { racktivityNotif 80 }
infoPortStateChanged NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"This trap is sent when a port changes state for any reason"
::= { racktivityNotif 96 }
infoReset NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"This trap is sent when a module is reboot"
::= { racktivityNotif 97 }
infoValueTooLowRaised NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"This trap is sent when an element goes below a specified threshold indicating the minimum value for this element"
::= { racktivityNotif 81 }
infoRaised NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"This trap is sent when an element gets into a specific state"
::= { racktivityNotif 82 }
infoValueTooHighCleared NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"This trap is sent when an element goes below a specified threshold indicating the maximum value for this element"
::= { racktivityNotif 83 }
infoValueTooLowCleared NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"This trap is sent when an element goes above a specified threshold indicating the minimum value for this element"
::= { racktivityNotif 84 }
infoCleared NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"This trap is sent when an element recovers from a specific state"
::= { racktivityNotif 85 }
infoUpgrade NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"This trap is sent when upgrade or downgrade of firmware is completed"
::= { racktivityNotif 98 }
warningMicroInterruption NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"This event is raised when a micro interruption is detected above a threshold time"
::= { racktivityNotif 54 }
warningPhaseShift NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"This event is raised when a phase shift is detected above a threshold"
::= { racktivityNotif 55 }
infoPortSchedule NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"This trap is sent when a port changes state because of a scheduling"
::= { racktivityNotif 99 }
infoHeartbeat NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"This trap is sent when a heartbeat has occurred"
::= { racktivityNotif 100 }
-- conformance statements
esRacktivityConformance OBJECT IDENTIFIER ::= { esRACKTIVITYMIB 2 }
esRacktivityMIBGroups OBJECT IDENTIFIER ::= { esRacktivityConformance 1 }
esRacktivityMIBCompliances OBJECT IDENTIFIER ::= { esRacktivityConformance 2 }
esRacktivityConpliance MODULE-COMPLIANCE
STATUS current
DESCRIPTION
"The compliance statements for a Racktivity device."
MODULE
MANDATORY-GROUPS { esRacktivityMIBGroup, esRacktivityNotificationGroup }
::= { esRacktivityMIBCompliances 1 }
esRacktivityMIBGroup OBJECT-GROUP
OBJECTS {
mGeneralModuleStatus,
mSpecificModuleStatus,
mCurrentTime,
mVoltage,
mTemperature,
mCurrentIP,
mTotalCurrent,
mTotalRealPower,
mTotalActiveEnergy,
mLineCurrent,
mFuseCurrent,
mCurrentSubNetMask,
mCurrentDNSServer,
mCurrentStdGateway,
mUPSPresent,
mUPSStatus,
mUPSEstimatedRunTime,
mUPSBatteryLevel,
mHighCurrent,
mUpsCommunicationStatus,
mHighPower,
mTotalHighCurrent,
mTotalHighPower,
mPositiveEnergy,
mNegativeEnergy,
mTotalPositiveEnergy,
mTotalNegativeEnergy,
mCloudStatus,
mStatus,
mModuleName,
mFirmwareVersion,
mHardwareVersion,
mFirmwareID,
mHardwareID,
mRackName,
mRackPosition,
mIPAddress,
mSubNetMask,
mStdGateWay,
mDnsServer,
mMAC,
mDHCPEnable,
mNTPServer,
mUseDefaultNTPServer,
mUseNTP,
mSNMPTrapRecvIP,
mSNMPTrapRecvPort,
mSNMPControl,
mECSServer,
mUseECSServer,
mDisplayLock,
mDisplayTimeOn,
mMaxVoltageWarning,
mMinVoltageWarning,
mMinTemperatureWarning,
mMaxTemperatureWarning,
mGeneralEventEnable,
mSNMPSysContact,
mCurrentWarningEvent,
mPowerWarningEvent,
mTotalCurrentWarningEvent,
mTotalPowerWarningEvent,
mVoltageWarningEvent,
mTemperatureWarningEvent,
mDisplayBrightness,
mECSServerPort,
mExternalSensorLabel,
mHttpsOnly,
mTelnetSsl,
mCookieTimeToLive,
mLineCurrentWarningThreshold,
mLineCurrentOffThreshold,
mLineCurrentWarningEvent,
mLineCurrentOffEvent,
mFuseCurrentWarningThreshold,
mFuseCurrentOffThreshold,
mFuseCurrentWarningEvent,
mFuseCurrentOffEvent,
mDeviceID,
mDeviceVersion,
mSysName,
mElectricalTopology,
mFusePortTopology,
mLineFuseTopology,
mSSOIPAddress,
mSSOLoginCredentials,
mSSOGracefullShutdown,
mUPSWarningLevel,
mUPSOffLevel,
mMaxHighCurrentWarning,
mUpsMonitoringProtocol,
mUpsEmergencyThreshold,
mUpsRecoveryThreshold,
mUpsEventFlags,
mRecoveryPowerThreshold,
mMinHighCurrentWarning,
mMinHighPowerWarning,
mMaxHighPowerWarning,
mHeartbeatInterval,
mMinTotalHighCurrentWarning,
mMaxTotalHighCurrentWarning,
mMinTotalHighPowerWarning,
mMaxTotalHighPowerWarning,
mCloudState,
mSensorBias,
mDaisyChainDeviceMode,
mSNMPTrapUser,
mUSMUser,
mUSMAuthPassphrase,
mUSMPrivPassphrase,
mSNMPV2GetSetEnable,
mSNMPV3GetSetEnable,
mUSMAuthPassphraseLength,
mUSMPrivPassphraseLength,
mSNMPTrapEnable,
mLDAPAttribute,
mLDAPPath,
mLDAPAdminGroupName,
mLDAPRestrictedGroupName,
mLDAPGuestGroupName,
mLDAPEnable,
mLDAPLoginWrapper,
mLDAPServer,
mLocalAuthEnable,
pGeneralModuleStatus,
pSpecificModuleStatus,
pCurrentTime,
pVoltage,
pFrequency,
pCurrent,
pPower,
pStatePortCur,
pActiveEnergy,
pApparentEnergy,
pTemperature,
pApparentPower,
pPowerFactor,
pTotalCurrent,
pTotalRealPower,
pTotalApparentPower,
pTotalActiveEnergy,
pTotalApparentEnergy,
pTotalPowerFactor,
pTimeOnline,
pTotalHarmonicDistortion,
pPhase,
pBigCurrent,
pBigPower,
pBigApparentPower,
pDetectedPhase,
pModuleName,
pFirmwareVersion,
pHardwareVersion,
pFirmwareID,
pHardwareID,
pPortName,
pPortState,
pCurrentPriorOff,
pDelayOn,
pMaxCurrentOff,
pMaxCurrentWarning,
pMaxPowerOff,
pMaxPowerWarning,
pMaxTotalCurrentOff,
pMaxTotalCurrentWarning,
pMaxTotalPowerOff,
pMaxTotalPowerWarning,
pMaxVoltageWarning,
pMinVoltageWarning,
pMinTemperatureWarning,
pMaxTemperatureWarning,
pPortStateEvent,
pCurrentOffEvent,
pCurrentWarningEvent,
pPowerOffEvent,
pPowerWarningEvent,
pTotalCurrentOffEvent,
pTotalCurrentWarningEvent,
pTotalPowerOffEvent,
pTotalPowerWarningEvent,
pVoltageWarningEvent,
pTemperatureWarningEvent,
pMaxOverheatingOff,
pOverheatingOffEvent,
pPowerCycleTime,
pExternalSensorLabel,
pMaxOverheatingWarning,
pOverheatingWarningEvent,
pMicroIntTimeThreshold,
pMicroIntEvent,
pSoftFuseCurrentThreshold,
pSoftFuseDelay,
pSoftFuseEvent,
pPhaseShiftEvent,
pSchedulePortOnTime,
pSchedulePortOffTime,
pEnableSchedulePort,
pBlockSetPortOff,
pSchedulePortChangeEvent,
pAgentIP,
pAgentPort,
pAgentCommunicationEventFlags,
pAlwaysOn,
pGenericTransducerParameters,
pMaxBigCurrentWarning,
pMaxBigPowerWarning,
pGroupNumber,
pPhaseLink,
pCurrentSensorSelector,
pMinBigCurrentWarning,
aGeneralModuleStatus,
aSpecificModuleStatus,
aCurrentTime,
aVoltage,
aStatePortCur,
aTemperature,
aHumidity,
aAirflow,
aDewPoint,
aPressure,
aAnalogueInput,
aWaterleak,
aMotionDetected,
aIOPort,
aHighCurrent,
aHighPower,
aModuleName,
aFirmwareVersion,
aHardwareVersion,
aFirmwareID,
aHardwareID,
aDisplayTimeOn,
aMaxVoltageWarning,
aMinVoltageWarning,
aMinTemperatureWarning,
aMaxTemperatureWarning,
aMinHumidityWarning,
aMaxHumidityWarning,
aCurrentWarningEvent,
aPowerWarningEvent,
aVoltageWarningEvent,
aTemperatureWarningEvent,
aHumidityWarningEvent,
aDewPointWarning,
aDewPointWarningEvent,
aDewPointViolationEvent,
aPressureWarningEvent,
aMinPressureWarning,
aMaxPressureWarning,
aDisplayBrightness,
aMotionSensitivity,
aExternalSensorLabel,
aRelayLabel,
aMinAnalogueInputWarning,
aMaxAnalogueInputWarning,
aWaterleakWarning,
aMinAirflowWarning,
aMaxAirflowWarning,
aAnalogueInputWarningEvent,
aWaterleakWarningEvent,
aAirflowWarningEvent,
aRelayAssertActionEvent,
aRelayDeassertActionEvent,
aMotionWarning,
aMotionWarningEvent,
aDeviceID,
aDeviceVersion,
aSysName,
aMaxHighCurrentWarning,
aMinHighCurrentWarning,
aMinHighPowerWarning,
aMaxHighPowerWarning,
aIOPortWarningEvent,
yGeneralModuleStatus,
ySpecificModuleStatus,
yCurrentTime,
yCurrent,
yStatePortCur,
yAnalogueInput,
yModuleName,
yFirmwareVersion,
yHardwareVersion,
yFirmwareID,
yHardwareID,
uGeneralModuleStatus,
uSpecificModuleStatus,
uCurrentTime,
uVoltage,
uCurrent,
uStatePortCur,
uTemperature,
uHumidity,
uModuleName,
uFirmwareVersion,
uHardwareVersion,
uFirmwareID,
uHardwareID,
uPortState,
eGeneralModuleStatus,
eSpecificModuleStatus,
eCurrentTime,
eVoltage,
eFrequency,
eCurrent,
ePower,
eActiveEnergy,
eApparentEnergy,
eTemperature,
eApparentPower,
ePowerFactor,
eTotalCurrent,
eTotalRealPower,
eTotalApparentPower,
eTotalActiveEnergy,
eTotalApparentEnergy,
eTotalPowerFactor,
eTimeOnline,
eTotalHarmonicDistortion,
eModuleName,
eFirmwareVersion,
eHardwareVersion,
eFirmwareID,
eHardwareID,
eMaxCurrentWarning,
eMaxPowerWarning,
eMaxTotalCurrentWarning,
eMaxTotalPowerWarning,
eMaxVoltageWarning,
eMinVoltageWarning,
eMinTemperatureWarning,
eMaxTemperatureWarning,
eCurrentWarningEvent,
ePowerWarningEvent,
eTotalCurrentWarningEvent,
eTotalPowerWarningEvent,
eVoltageWarningEvent,
eTemperatureWarningEvent,
eMicroIntTimeThreshold,
eMicroIntEvent,
qGeneralModuleStatus,
qSpecificModuleStatus,
qCurrentTime,
qVoltage,
qFrequency,
qActiveEnergy,
qApparentEnergy,
qTemperature,
qPowerFactor,
qTimeOnline,
qIOPort,
qTotalHarmonicDistortion,
qPhase,
qBigCurrent,
qBigPower,
qBigApparentPower,
qStatus,
qModuleName,
qFirmwareVersion,
qHardwareVersion,
qFirmwareID,
qHardwareID,
qPortState,
qMaxVoltageWarning,
qMinVoltageWarning,
qMinTemperatureWarning,
qMaxTemperatureWarning,
qPortStateEvent,
qCurrentWarningEvent,
qPowerWarningEvent,
qVoltageWarningEvent,
qTemperatureWarningEvent,
qMicroIntTimeThreshold,
qMicroIntEvent,
qDeviceID,
qDeviceVersion,
qMaxBigCurrentWarning,
qMaxBigPowerWarning,
qCurrentSensorSelector,
qMinBigCurrentWarning,
qkWhMode,
dGeneralModuleStatus,
dSpecificModuleStatus,
dCurrentTime,
dTemperature,
dTimeOnline,
dModuleName,
dFirmwareVersion,
dHardwareVersion,
dFirmwareID,
dHardwareID,
dMinTemperatureWarning,
dMaxTemperatureWarning,
dDisplayAllDevices
}
STATUS current
DESCRIPTION
"All accessible objects in a Racktivity device"
::= { esRacktivityMIBGroups 1 }
esRacktivityNotificationGroup NOTIFICATION-GROUP
NOTIFICATIONS
{
errorValueTooHighRaised,
errorValueTooLowRaised,
errorRaised,
errorValueTooHighCleared,
errorValueTooLowCleared,
errorCleared,
warningValueTooHighRaised,
warningValueTooLowRaised,
warningRaised,
warningValueTooHighCleared,
warningValueTooLowCleared,
warningCleared,
infoValueTooHighRaised,
infoPortStateChanged,
infoReset,
infoValueTooLowRaised,
infoRaised,
infoValueTooHighCleared,
infoValueTooLowCleared,
infoCleared,
infoUpgrade,
warningMicroInterruption,
warningPhaseShift,
infoPortSchedule,
infoHeartbeat
}
STATUS current
DESCRIPTION
"All notification that can be sent out by a Racktivity device"
::= { esRacktivityMIBGroups 2 }
END -- end of module esRACKTIVITY.