Observium_CE/mibs/powertek/SimplePDU-MIB

3566 lines
113 KiB
Plaintext

-- powertek Simple PDU MIB
-- MIB for Simple PDU
--
-- { iso org(3) dod(6) internet(1) private(4) enterprises(1) powertek(42610)
-- product(1) pdu(4) simple(2)
-- ==============================================================================================
---
--- Revision History
---
--- v0.10 09-Dec-2020 Grace WuCreated
---
---
--- v0.20 05-Feb-2021 Kenneth change OID to simple(2) for pwt(4)
---
---
--- v0.30 20-Feb-2021 Grace Wu
--- 1. pduEmdCurrInfoHumidityStat SYNTAX INTEGER change to normal(1),warning(2),critical(3).
--- 2. pduEmdCurrInfoTempStat SYNTAX INTEGER change to normal(1),warning(2),critical(3).
--- 3. pduEmdCfgEMDAddress change to read-only.
--- 4. pduEmdCfgAppFWVer change to read-only.
--- 6. pduEmdCfgTempCalOffset SYNTAX INTEGER change to fivePointFour(1),fourPointFive(2),
--- threePointSix(3),twoPointSeven(4),onePointEight(5),zeroPointNine(6),zeroPointZero(7),
--- negativeZeroPointNine(8),negativeOnePointEight(9),negativeTwoPointSeven(10),
--- negativeThreePointSix(11),negativeFourPointFive(12),negativeFivePointFour(13).
--- 7. pduEmdCfgHumidityCalOffset SYNTAX INTEGER change to six(1),five(2),four(3),three(4),two(5),
--- one(6),zero(7),negativeOne(8),negativeTwo(9),negativeThree(10),
--- negativeFour(11),negativeFive(12),negativeSix(13).
--- 8. pduDateAndTimeNtpSyncIntervalType change day to 1, month to 2.
--- 9. pduIecViewMgmtGuid change to read-only.
--- 10. pduAccessIpSettingTblAction accept->allow,reject->deny.
--- 11. pduEmdCfgTempCritHigh SYNTAX INTEGER change to 0..650.
--- 12. pduEmdCfgTempCritLow SYNTAX INTEGER change to 0..650.
--- 13. pduEmdCfgTempWarnHigh SYNTAX INTEGER change to 0..650.
--- 14. pduEmdCfgTempWarnLow SYNTAX INTEGER change to 0..650.
--- 15. pduNetServiceRadiusTimeout SYNTAX INTEGER change to 1..99.
--- 16. pduNetServiceRadiusRetry SYNTAX INTEGER change to 1..99.
--- 17. pduSnmpSettingTrapEvtLevel SYNTAX INTEGER change to informational(1),warning(2),critical(3).
--- 18. pduEmailSettingSmtpAuthEn SYNTAX INTEGER change to disabled(1),enabled(2)
--- 19. trap change some description.
---
---
--- v0.40 22-Feb-2021 Grace Wu
--- 1. pduIpv6SettingAddress change to pduIpv6SettingLocalAddress and change to read.
--- 2. add pduIpv6SettingGlobalAddress.
--- 3. pduIpv6SettingPrefix range change from 0-63 to 0-128
---
---
--- v0.50 04-Mar-2021 Grace Wu
--- 1. pduCfgCritOverLoadAlm unit changet to 0.1W, and range change to 0-140800.
--- 2. pduCfgCritLoadBalanceAlm unit changet to 0.1%, and range change to 0-1000.
--- 3. pduCfgWarnOverLoadAlm unit changet to 0.1W, and range change to 0-140800.
--- 4. pduCfgWarnLoadBalanceAlm unit changet to 0.1%, and range change to 0-1000.
--- 5. pduEmdCurrInfoHumidityValue unit changet to 0.1%.
--- 6. pduEmdCfgTempCritHigh add unit 0.1.
--- 7. pduEmdCfgTempCritLow add unit 0.1.
--- 8. pduEmdCfgTempWarnHigh add unit 0.1.
--- 9. pduEmdCfgTempWarnLow add unit 0.1.
--- 10. Critical: Cold boot. -> coldStart.
--- 11. Critical: Warm boot. -> warmStart.
--- 12. add trap pduInletCurrCB2Phase1Warn(71)~pduInletCurrPhase3CB2CritToWarn(82).
--- 13. trap pduInletCurrPhase1Warn(15)~pduInletCurrPhase3CritToWarn(26) name add CB1.
---
---
--- v0.60 12-Mar-2021 Grace Wu
--- 1. remove pduIpv6SettingPrefix.
---
SimplePDU-MIB DEFINITIONS ::= BEGIN
IMPORTS
enterprises,Counter,IpAddress
FROM RFC1155-SMI
OBJECT-TYPE
FROM RFC-1212
DisplayString
FROM RFC1213-MIB
TRAP-TYPE
FROM RFC-1215
PositiveInteger
FROM UPS-MIB
NonNegativeInteger
FROM UPS-MIB;
powertek OBJECT IDENTIFIER ::= { enterprises 42610 }
product OBJECT IDENTIFIER ::= { powertek 1 }
pdu OBJECT IDENTIFIER ::= { product 4 }
simple OBJECT IDENTIFIER ::= { pdu 2 }
pduObjects OBJECT IDENTIFIER ::= { simple 1 }
pduTraps OBJECT IDENTIFIER ::= { simple 2 }
-- ==========================================================================
-- top level structure
-- ==========================================================================
pduSumOverview OBJECT IDENTIFIER ::= { pduObjects 1 }
pduPowMgmt OBJECT IDENTIFIER ::= { pduObjects 2 }
pduSettings OBJECT IDENTIFIER ::= { pduObjects 3 }
pduAdvanced OBJECT IDENTIFIER ::= { pduObjects 4 }
-- ===========================================================================
--
-- pduSumOverview
-- Summary Overview
-- .1.3.6.1.4.1.42610.1.4.4.1.1
--
-- ===========================================================================
pduSysOverview OBJECT IDENTIFIER ::= { pduSumOverview 1 }
pduNetConnect OBJECT IDENTIFIER ::= { pduSumOverview 2 }
-- ===========================================================================
--
-- pduSysOverview Group
-- .1.3.6.1.4.1.42610.1.4.4.1.1.1
--
-- ===========================================================================
pduOverview OBJECT IDENTIFIER ::= { pduSysOverview 1 }
pduInputStat OBJECT IDENTIFIER ::= { pduSysOverview 2 }
-- ===========================================================================
--
-- pduOverview Group
-- .1.3.6.1.4.1.42610.1.4.4.1.1.1.1
--
-- ===========================================================================
pduOverviewSystemAgenetVersion OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The firmware version of the device."
::= { pduOverview 1 }
pduOverviewPduTypeName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The type name of PDU."
::= { pduOverview 2 }
-- ===========================================================================
--
-- pduInputStat Group
-- .1.3.6.1.4.1.42610.1.4.4.1.1.1.2
--
-- ===========================================================================
pduInputStatTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduInputStatEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list to display information of input status."
::= { pduInputStat 1}
pduInputStatEntry OBJECT-TYPE
SYNTAX PduInputStatEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list to display information of input status."
INDEX { pduInputStatPhaseIndex }
::= { pduInputStatTable 1 }
PduInputStatEntry ::=
SEQUENCE {
pduInputStatPhaseIndex
INTEGER,
pduInputStatVoltage
INTEGER,
pduInputStatActivePower
INTEGER,
pduInputStatApparentPower
INTEGER,
pduInputStatCB1Current
INTEGER,
pduInputStatCB2Current
INTEGER,
pduInputStatTotalCurrent
INTEGER,
pduInputStatStatus
INTEGER
}
pduInputStatPhaseIndex OBJECT-TYPE
SYNTAX INTEGER (0..3)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a input status entry."
::= { pduInputStatEntry 1 }
pduInputStatVoltage OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1V"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The voltage of input status."
::= { pduInputStatEntry 2 }
pduInputStatActivePower OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1W"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The active power of input status."
::= { pduInputStatEntry 3}
pduInputStatApparentPower OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1VA"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The apparent power of input status."
::= { pduInputStatEntry 4}
pduInputStatCB1Current OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.01A"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The circuit breaker 1 of input status."
::= { pduInputStatEntry 5}
pduInputStatCB2Current OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.01A"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The circuit breaker 2 of input status."
::= { pduInputStatEntry 6}
pduInputStatTotalCurrent OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.01A"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The total circuit of input status."
::= { pduInputStatEntry 7}
pduInputStatStatus OBJECT-TYPE
SYNTAX INTEGER {
normal(1),
warning(2),
critical(3)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The status of input status."
::= { pduInputStatEntry 8}
pduInputStatLoadBalanceVal OBJECT-TYPE
SYNTAX INTEGER
UNITS "%"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The load balance value of input status."
::= { pduInputStat 2}
pduInputStatLoadBalanceStatus OBJECT-TYPE
SYNTAX INTEGER {
normal(1),
warning(2),
critical(3)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The load balance status of input status."
::= { pduInputStat 3}
pduInputStatResidualCurVal OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.01A"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The residual current value of input status."
::= { pduInputStat 4}
pduInputStatResidualCurStatus OBJECT-TYPE
SYNTAX INTEGER {
normal(1),
warning(2),
critical(3)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The residual current status of input status."
::= { pduInputStat 5}
-- ===========================================================================
--
-- end of pduSysOverview Group
--
-- ===========================================================================
-- ===========================================================================
--
-- pduNetConnect Group
-- .1.3.6.1.4.1.42610.1.4.4.1.1.2
--
-- ===========================================================================
pduNetConnectTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduNetConnectEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list to display information of network connect."
::= { pduNetConnect 1}
pduNetConnectEntry OBJECT-TYPE
SYNTAX PduNetConnectEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list to display information of input status."
INDEX { pduNetConnectIndex }
::= { pduNetConnectTable 1 }
PduNetConnectEntry ::=
SEQUENCE {
pduNetConnectIndex
INTEGER,
pduNetConnectAddr
DisplayString,
pduNetConnectType
INTEGER,
pduNetConnectUserName
DisplayString
}
pduNetConnectIndex OBJECT-TYPE
SYNTAX INTEGER (0..16)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a network connect entry."
::= { pduNetConnectEntry 1}
pduNetConnectAddr OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The source host address of network connect."
::= { pduNetConnectEntry 2}
pduNetConnectType OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The connection type of network connect."
::= { pduNetConnectEntry 3}
pduNetConnectUserName OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The user name of network connect."
::= { pduNetConnectEntry 4}
-- ===========================================================================
--
-- end of pduNetConnect Group
--
-- ===========================================================================
-- ===========================================================================
--
-- end of pduSumOverview
--
-- ===========================================================================
-- ===========================================================================
--
-- pduPowMgmt
-- Power Management
-- .1.3.6.1.4.1.42610.1.4.4.1.2
--
-- ===========================================================================
pduInletCfg OBJECT IDENTIFIER ::= { pduPowMgmt 1 }
pduEnvMon OBJECT IDENTIFIER ::= { pduPowMgmt 2 }
-- ===========================================================================
--
-- pduInletCfg Group
-- .1.3.6.1.4.1.42610.1.4.4.1.2.1
--
-- ===========================================================================
pduPhaseLoadMgmt OBJECT IDENTIFIER ::= { pduInletCfg 1 }
pduCfg OBJECT IDENTIFIER ::= { pduInletCfg 2 }
pduStat OBJECT IDENTIFIER ::= { pduInletCfg 3 }
-- ===========================================================================
--
-- pduPhaseLoadMgmt Group
-- .1.3.6.1.4.1.42610.1.4.4.1.2.1.1
--
-- ===========================================================================
pduPhaseLoadMgmtTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduPhaseLoadMgmtEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list to display information of input status."
::= { pduPhaseLoadMgmt 1}
pduPhaseLoadMgmtEntry OBJECT-TYPE
SYNTAX PduPhaseLoadMgmtEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list to display information of input status."
INDEX { pduPhaseLoadMgmtPhaseIndex }
::= { pduPhaseLoadMgmtTable 1 }
PduPhaseLoadMgmtEntry ::=
SEQUENCE {
pduPhaseLoadMgmtPhaseIndex
INTEGER,
pduPhaseLoadMgmtCurrentTotal
INTEGER,
pduPhaseLoadMgmtVoltage
INTEGER,
pduPhaseLoadMgmtFrequency
INTEGER,
pduPhaseLoadMgmtPowerFactor
INTEGER,
pduPhaseLoadMgmtPowerActiveApparent
DisplayString,
pduPhaseLoadMgmtReactivePower
INTEGER,
pduPhaseLoadMgmtStatus
INTEGER
}
pduPhaseLoadMgmtPhaseIndex OBJECT-TYPE
SYNTAX INTEGER (0..3)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a load management entry."
::= { pduPhaseLoadMgmtEntry 1 }
pduPhaseLoadMgmtCurrentTotal OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.01A"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Current Total(CB1/CB2) of load management."
::= { pduPhaseLoadMgmtEntry 2 }
pduPhaseLoadMgmtVoltage OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1V"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Voltage of load management."
::= { pduPhaseLoadMgmtEntry 3}
pduPhaseLoadMgmtFrequency OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.01Hz"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Frequency of load management."
::= { pduPhaseLoadMgmtEntry 4}
pduPhaseLoadMgmtPowerFactor OBJECT-TYPE
SYNTAX INTEGER
UNITS "%"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Power Factor of load management."
::= { pduPhaseLoadMgmtEntry 5}
pduPhaseLoadMgmtPowerActiveApparent OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Power(0.1W/0.1VA) Active/Apparent of load management."
::= { pduPhaseLoadMgmtEntry 6}
pduPhaseLoadMgmtReactivePower OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1var"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Reactive Power of load management."
::= { pduPhaseLoadMgmtEntry 7}
pduPhaseLoadMgmtStatus OBJECT-TYPE
SYNTAX INTEGER {
normal(1),
warning(2),
critical(3)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Status of load management."
::= { pduPhaseLoadMgmtEntry 8}
-- ===========================================================================
--
-- pduCfg Group
-- .1.3.6.1.4.1.42610.1.4.4.1.2.1.2
--
-- ===========================================================================
pduCfgCritOverLoadAlm OBJECT-TYPE
SYNTAX INTEGER (0..140800)
UNITS "0.1W"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The critical over load alarm threshold."
::= { pduCfg 1}
pduCfgCritLoadBalanceAlm OBJECT-TYPE
SYNTAX INTEGER (0..1000)
UNITS "0.1%"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The critical load balance alarm threshold."
::= { pduCfg 2}
pduCfgCritOverCurrAlmCB1Ph1 OBJECT-TYPE
SYNTAX INTEGER (0..3200)
UNITS "0.01A"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The critical over current alarm CB1 threshold of phase 1."
::= { pduCfg 3}
pduCfgCritOverCurrAlmCB1Ph2 OBJECT-TYPE
SYNTAX INTEGER (0..3200)
UNITS "0.01A"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The critical over current alarm CB1 threshold of phase 2."
::= { pduCfg 4}
pduCfgCritOverCurrAlmCB1Ph3 OBJECT-TYPE
SYNTAX INTEGER (0..3200)
UNITS "0.01A"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The critical over current alarm CB1 threshold of phase 3."
::= { pduCfg 5}
pduCfgCritOverCurrAlmCB2Ph1 OBJECT-TYPE
SYNTAX INTEGER (0..3200)
UNITS "0.01A"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The critical over current alarm CB2 threshold of phase 1."
::= { pduCfg 6}
pduCfgCritOverCurrAlmCB2Ph2 OBJECT-TYPE
SYNTAX INTEGER (0..3200)
UNITS "0.01A"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The critical over current alarm CB2 threshold of phase 2."
::= { pduCfg 7}
pduCfgCritOverCurrAlmCB2Ph3 OBJECT-TYPE
SYNTAX INTEGER (0..3200)
UNITS "0.01A"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The critical over current alarm CB2 threshold of phase 3."
::= { pduCfg 8}
pduCfgCritOverTotalCurrAlm OBJECT-TYPE
SYNTAX INTEGER (0..3200)
UNITS "0.01A"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The critical over total current alarm threshold."
::= { pduCfg 9}
pduCfgCritOverVolAlm OBJECT-TYPE
SYNTAX INTEGER (0..3500)
UNITS "0.1V"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The critical over voltage alarm threshold."
::= { pduCfg 10}
pduCfgWarnOverLoadAlm OBJECT-TYPE
SYNTAX INTEGER (0..140800)
UNITS "0.1W"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The warning over load alarm threshold."
::= { pduCfg 11}
pduCfgWarnLoadBalanceAlm OBJECT-TYPE
SYNTAX INTEGER (0..1000)
UNITS "0.1%"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The warning load balance alarm threshold."
::= { pduCfg 12}
pduCfgWarnOverCurrAlmCB1Ph1 OBJECT-TYPE
SYNTAX INTEGER (0..3200)
UNITS "0.01A"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The warning over current alarm CB1 threshold of phase 1."
::= { pduCfg 13}
pduCfgWarnOverCurrAlmCB1Ph2 OBJECT-TYPE
SYNTAX INTEGER (0..3200)
UNITS "0.01A"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The warning over current alarm CB1 threshold of phase 2."
::= { pduCfg 14}
pduCfgWarnOverCurrAlmCB1Ph3 OBJECT-TYPE
SYNTAX INTEGER (0..3200)
UNITS "0.01A"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The warning over current alarm CB1 threshold of phase 3."
::= { pduCfg 15}
pduCfgWarnOverCurrAlmCB2Ph1 OBJECT-TYPE
SYNTAX INTEGER (0..3200)
UNITS "0.01A"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The warning over current alarm CB2 threshold of phase 1."
::= { pduCfg 16}
pduCfgWarnOverCurrAlmCB2Ph2 OBJECT-TYPE
SYNTAX INTEGER (0..3200)
UNITS "0.01A"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The warning over current alarm CB2 threshold of phase 2."
::= { pduCfg 17}
pduCfgWarnOverCurrAlmCB2Ph3 OBJECT-TYPE
SYNTAX INTEGER (0..3200)
UNITS "0.01A"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The warning over current alarm CB2 threshold of phase 3."
::= { pduCfg 18}
pduCfgWarnOverTotalCurrAlm OBJECT-TYPE
SYNTAX INTEGER (0..3200)
UNITS "0.01A"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The warning over total current alarm threshold."
::= { pduCfg 19}
pduCfgWarnOverVolAlm OBJECT-TYPE
SYNTAX INTEGER (0..3500)
UNITS "0.1V"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The warning over voltage alarm threshold."
::= { pduCfg 20}
-- ===========================================================================
--
-- pduStat Group
-- .1.3.6.1.4.1.42610.1.4.4.1.2.1.3
--
-- ===========================================================================
pduStatPower OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1W"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The status of power value."
::= { pduStat 1}
pduStatPowerStat OBJECT-TYPE
SYNTAX INTEGER {
normal(1),
warning(2),
critical(3)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The status of power."
::= { pduStat 2}
pduStatTotalEnergy OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.01kWh"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The status of total energy."
::= { pduStat 3}
pduStatTotalEnergyRecord OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The status of total energy record."
::= { pduStat 4}
pduStatPh1Energy OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.01kWh"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The phase 1 status of total energy."
::= { pduStat 5}
pduStatPh1EnergyRecord OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The phase 1 status of total energy record."
::= { pduStat 6}
pduStatPh2Energy OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.01kWh"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The phase 2 status of total energy."
::= { pduStat 7}
pduStatPh2EnergyRecord OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The phase 2 status of total energy record."
::= { pduStat 8}
pduStatPh3Energy OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.01kWh"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The phase 3 status of total energy."
::= { pduStat 9}
pduStatPh3EnergyRecord OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The phase 3 status of total energy record."
::= { pduStat 10}
pduStatLoadBalance OBJECT-TYPE
SYNTAX INTEGER
UNITS "%"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The status of load balance."
::= { pduStat 11}
pduStatLoadBalanceStat OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The status of load balance."
::= { pduStat 12}
pduStatTotalEnergyCln OBJECT-TYPE
SYNTAX INTEGER {
doNothing(1),
reset(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Clean total energy status."
::= { pduStat 13}
pduStatPh1EnergyCln OBJECT-TYPE
SYNTAX INTEGER {
doNothing(1),
reset(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Clean phase 1 energy status."
::= { pduStat 14}
pduStatPh2EnergyCln OBJECT-TYPE
SYNTAX INTEGER {
doNothing(1),
reset(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Clean phase 2 energy status."
::= { pduStat 15}
pduStatPh3EnergyCln OBJECT-TYPE
SYNTAX INTEGER {
doNothing(1),
reset(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Clean phase 3 energy status."
::= { pduStat 16}
-- ===========================================================================
--
-- end of pduInletCfg Group
--
-- ===========================================================================
-- ===========================================================================
--
-- pduEnvMon Group
-- .1.3.6.1.4.1.42610.1.4.4.1.2.2
--
-- ===========================================================================
pduEmdCurrInfo OBJECT IDENTIFIER ::= { pduEnvMon 1 }
pduEmdCfg OBJECT IDENTIFIER ::= { pduEnvMon 2 }
-- ===========================================================================
--
-- pduEmdCurrInfo Group
-- .1.3.6.1.4.1.42610.1.4.4.1.2.2.1
--
-- ===========================================================================
pduEmdCurrInfoTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduEmdCurrInfoEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list to display current information of EMD."
::= { pduEmdCurrInfo 1}
pduEmdCurrInfoEntry OBJECT-TYPE
SYNTAX PduEmdCurrInfoEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list to display current information of EMD."
INDEX { pduEmdCurrInfoEmdStatIndex }
::= { pduEmdCurrInfoTable 1 }
PduEmdCurrInfoEntry ::=
SEQUENCE {
pduEmdCurrInfoEmdStatIndex
INTEGER,
pduEmdCurrInfoHumidityName
DisplayString,
pduEmdCurrInfoHumidityStat
INTEGER,
pduEmdCurrInfoHumidityValue
INTEGER,
pduEmdCurrInfoTempName
DisplayString,
pduEmdCurrInfoTempStat
INTEGER,
pduEmdCurrInfoTempValue
INTEGER,
pduEmdCurrInfoAlm1Name
DisplayString,
pduEmdCurrInfoAlm1Stat
INTEGER,
pduEmdCurrInfoAlm2Name
DisplayString,
pduEmdCurrInfoAlm2Stat
INTEGER,
pduEmdCurrInfoLocName
DisplayString,
pduEmdCurrInfoAddress
INTEGER
}
pduEmdCurrInfoEmdStatIndex OBJECT-TYPE
SYNTAX INTEGER (0..8)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a current EMD status information."
::= { pduEmdCurrInfoEntry 1 }
pduEmdCurrInfoHumidityName OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The humidity name of EMD status."
::= { pduEmdCurrInfoEntry 2 }
pduEmdCurrInfoHumidityStat OBJECT-TYPE
SYNTAX INTEGER {
normal(1),
warning(2),
critical(3)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The humidity status of EMD status."
::= { pduEmdCurrInfoEntry 3 }
pduEmdCurrInfoHumidityValue OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1%"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The humidity value of EMD status."
::= { pduEmdCurrInfoEntry 4 }
pduEmdCurrInfoTempName OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The temperature name of EMD status."
::= { pduEmdCurrInfoEntry 5 }
pduEmdCurrInfoTempStat OBJECT-TYPE
SYNTAX INTEGER {
normal(1),
warning(2),
critical(3)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The temperature status of EMD status."
::= { pduEmdCurrInfoEntry 6 }
pduEmdCurrInfoTempValue OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The temperature value of EMD status."
::= { pduEmdCurrInfoEntry 7 }
pduEmdCurrInfoAlm1Name OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The alarm 1 name of EMD status."
::= { pduEmdCurrInfoEntry 8 }
pduEmdCurrInfoAlm1Stat OBJECT-TYPE
SYNTAX INTEGER {
normal(1),
alert(2)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The alarm 1 status of EMD status."
::= { pduEmdCurrInfoEntry 9 }
pduEmdCurrInfoAlm2Name OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The alarm 2 name of EMD status."
::= { pduEmdCurrInfoEntry 10 }
pduEmdCurrInfoAlm2Stat OBJECT-TYPE
SYNTAX INTEGER {
normal(1),
alert(2)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The alarm 2 status of EMD status."
::= { pduEmdCurrInfoEntry 11 }
pduEmdCurrInfoLocName OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The location name of EMD status."
::= { pduEmdCurrInfoEntry 12 }
pduEmdCurrInfoAddress OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The address of EMD status."
::= { pduEmdCurrInfoEntry 13 }
-- ===========================================================================
--
-- pduEmdCfg Group
-- .1.3.6.1.4.1.42610.1.4.4.1.2.2.2
--
-- ===========================================================================
pduEmdCfgTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduEmdCfgEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list to display EMD configuration."
::= { pduEmdCfg 1}
pduEmdCfgEntry OBJECT-TYPE
SYNTAX PduEmdCfgEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list to display EMD configuration."
INDEX { pduEmdCfgEMDIndex }
::= { pduEmdCfgTable 1 }
PduEmdCfgEntry ::=
SEQUENCE {
pduEmdCfgEMDIndex
INTEGER,
pduEmdCfgEMDName
DisplayString,
pduEmdCfgEMDAddress
INTEGER,
pduEmdCfgAppFWVer
DisplayString,
pduEmdCfgLocName
DisplayString,
pduEmdCfgAlm1Name
DisplayString,
pduEmdCfgAlm2Name
DisplayString,
pduEmdCfgAlm1Type
INTEGER,
pduEmdCfgAlm2Type
INTEGER,
pduEmdCfgTempSenName
DisplayString,
pduEmdCfgTempCritHigh
INTEGER,
pduEmdCfgTempCritHighType
INTEGER,
pduEmdCfgTempCritLow
INTEGER,
pduEmdCfgTempCritLowType
INTEGER,
pduEmdCfgTempWarnHigh
INTEGER,
pduEmdCfgTempWarnHighType
INTEGER,
pduEmdCfgTempWarnLow
INTEGER,
pduEmdCfgTempWarnLowType
INTEGER,
pduEmdCfgTempCalOffset
INTEGER,
pduEmdCfgHumiditySenName
DisplayString,
pduEmdCfgHumidityCritHigh
INTEGER,
pduEmdCfgHumidityCritHighType
INTEGER,
pduEmdCfgHumidityCritLow
INTEGER,
pduEmdCfgHumidityCritLowType
INTEGER,
pduEmdCfgHumidityWarnHigh
INTEGER,
pduEmdCfgHumidityWarnHighType
INTEGER,
pduEmdCfgHumidityWarnLow
INTEGER,
pduEmdCfgHumidityWarnLowType
INTEGER,
pduEmdCfgHumidityCalOffset
INTEGER
}
pduEmdCfgEMDIndex OBJECT-TYPE
SYNTAX INTEGER (0..8)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a EMD configuration."
::= { pduEmdCfgEntry 1 }
pduEmdCfgEMDName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The name of EMD configuration."
::= { pduEmdCfgEntry 2 }
pduEmdCfgEMDAddress OBJECT-TYPE
SYNTAX INTEGER (1..247)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The address of EMD configuration."
::= { pduEmdCfgEntry 3 }
pduEmdCfgAppFWVer OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The application firmware version of EMD configuration."
::= { pduEmdCfgEntry 4 }
pduEmdCfgLocName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The location name of EMD configuration."
::= { pduEmdCfgEntry 5 }
pduEmdCfgAlm1Name OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The alarm 1 name of EMD configuration."
::= { pduEmdCfgEntry 6 }
pduEmdCfgAlm2Name OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The alarm 2 name of EMD configuration."
::= { pduEmdCfgEntry 7 }
pduEmdCfgAlm1Type OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
normalOpen(2),
normalClose(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The alarm 1 type of EMD configuration."
::= { pduEmdCfgEntry 8 }
pduEmdCfgAlm2Type OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
normalOpen(2),
normalClose(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The alarm 2 type of EMD configuration."
::= { pduEmdCfgEntry 9 }
pduEmdCfgTempSenName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The temperature sensor name of EMD configuration."
::= { pduEmdCfgEntry 10 }
pduEmdCfgTempCritHigh OBJECT-TYPE
SYNTAX INTEGER (0..650)
UNITS "0.1"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The temperature critical high value of EMD configuration."
::= { pduEmdCfgEntry 11 }
pduEmdCfgTempCritHighType OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
enabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The temperature critical high type of EMD configuration."
::= { pduEmdCfgEntry 12 }
pduEmdCfgTempCritLow OBJECT-TYPE
SYNTAX INTEGER (0..650)
UNITS "0.1"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The temperature critical low value of EMD configuration."
::= { pduEmdCfgEntry 13 }
pduEmdCfgTempCritLowType OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
enabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The temperature critical low type of EMD configuration."
::= { pduEmdCfgEntry 14 }
pduEmdCfgTempWarnHigh OBJECT-TYPE
SYNTAX INTEGER (0..650)
UNITS "0.1"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The temperature warning high value of EMD configuration."
::= { pduEmdCfgEntry 15 }
pduEmdCfgTempWarnHighType OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
enabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The temperature warning high type of EMD configuration."
::= { pduEmdCfgEntry 16 }
pduEmdCfgTempWarnLow OBJECT-TYPE
SYNTAX INTEGER (0..650)
UNITS "0.1"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The temperature warning low value of EMD configuration."
::= { pduEmdCfgEntry 17 }
pduEmdCfgTempWarnLowType OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
enabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The temperature warning low type of EMD configuration."
::= { pduEmdCfgEntry 18 }
pduEmdCfgTempCalOffset OBJECT-TYPE
SYNTAX INTEGER {
fivePointFour(1),
fourPointFive(2),
threePointSix(3),
twoPointSeven(4),
onePointEight(5),
zeroPointNine(6),
zeroPointZero(7),
negativeZeroPointNine(8),
negativeOnePointEight(9),
negativeTwoPointSeven(10),
negativeThreePointSix(11),
negativeFourPointFive(12),
negativeFivePointFour(13)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The temperature calibration offset of EMD configuration."
::= { pduEmdCfgEntry 19 }
pduEmdCfgHumiditySenName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The humidity sensor name of EMD configuration."
::= { pduEmdCfgEntry 20 }
pduEmdCfgHumidityCritHigh OBJECT-TYPE
SYNTAX INTEGER (0..1000)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The humidity critical high value of EMD configuration."
::= { pduEmdCfgEntry 21 }
pduEmdCfgHumidityCritHighType OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
enabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The humidity critical high type of EMD configuration."
::= { pduEmdCfgEntry 22 }
pduEmdCfgHumidityCritLow OBJECT-TYPE
SYNTAX INTEGER (0..1000)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The humidity critical low value of EMD configuration."
::= { pduEmdCfgEntry 23 }
pduEmdCfgHumidityCritLowType OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
enabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The humidity critical low type of EMD configuration."
::= { pduEmdCfgEntry 24 }
pduEmdCfgHumidityWarnHigh OBJECT-TYPE
SYNTAX INTEGER (0..1000)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The humidity warning high value of EMD configuration."
::= { pduEmdCfgEntry 25 }
pduEmdCfgHumidityWarnHighType OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
enabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The humidity warning high type of EMD configuration."
::= { pduEmdCfgEntry 26 }
pduEmdCfgHumidityWarnLow OBJECT-TYPE
SYNTAX INTEGER (0..1000)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The humidity warning low value of EMD configuration."
::= { pduEmdCfgEntry 27 }
pduEmdCfgHumidityWarnLowType OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
enabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The humidity warning low type of EMD configuration."
::= { pduEmdCfgEntry 28 }
pduEmdCfgHumidityCalOffset OBJECT-TYPE
SYNTAX INTEGER {
six(1),
five(2),
four(3),
three(4),
two(5),
one(6),
zero(7),
negativeOne(8),
negativeTwo(9),
negativeThree(10),
negativeFour(11),
negativeFive(12),
negativeSix(13)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The humidity calibration offset of EMD configuration."
::= { pduEmdCfgEntry 29 }
-- ===========================================================================
--
-- end of pduEnvMon Group
--
-- ===========================================================================
-- ===========================================================================
--
-- end of pduPowMgmt
--
-- ===========================================================================
-- ===========================================================================
--
-- pduSettings
-- Settings
-- .1.3.6.1.4.1.42610.1.4.4.1.3
--
-- ===========================================================================
pduGeneralSet OBJECT IDENTIFIER ::= { pduSettings 1 }
pduIecViewMgmt OBJECT IDENTIFIER ::= { pduSettings 2 }
pduTcpIp OBJECT IDENTIFIER ::= { pduSettings 3 }
pduAccessIpSetting OBJECT IDENTIFIER ::= { pduSettings 4 }
pduSecurity OBJECT IDENTIFIER ::= { pduSettings 5 }
pduNetService OBJECT IDENTIFIER ::= { pduSettings 6 }
pduSnmpSetting OBJECT IDENTIFIER ::= { pduSettings 7 }
pduEmailSetting OBJECT IDENTIFIER ::= { pduSettings 8 }
pduUserSetting OBJECT IDENTIFIER ::= { pduSettings 9 }
-- ===========================================================================
--
-- pduGeneralSet Group
-- .1.3.6.1.4.1.42610.1.4.4.1.3.1
--
-- ===========================================================================
pduSysAdm OBJECT IDENTIFIER ::= { pduGeneralSet 1 }
pduDateAndTime OBJECT IDENTIFIER ::= { pduGeneralSet 2 }
-- ===========================================================================
--
-- pduSysAdm Group
-- .1.3.6.1.4.1.42610.1.4.4.1.3.1.1
--
-- ===========================================================================
pduSysAdmSysName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The name of system."
::= { pduSysAdm 1 }
pduSysAdmSysContact OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The contact of system."
::= { pduSysAdm 2 }
pduSysAdmSysLocation OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The location of system."
::= { pduSysAdm 3 }
pduSysAdmLogInterval OBJECT-TYPE
SYNTAX INTEGER (1..28800)
UNITS "sec"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The log interval of system."
::= { pduSysAdm 4 }
pduSysAdmWebRefresh OBJECT-TYPE
SYNTAX INTEGER (5..300)
UNITS "sec"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The web refresh interval of system."
::= { pduSysAdm 5 }
pduSysAdmWebTimeout OBJECT-TYPE
SYNTAX INTEGER (1..3600)
UNITS "sec"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The web timeout interval of system."
::= { pduSysAdm 6 }
-- ===========================================================================
--
-- pduDateAndTime Group
-- .1.3.6.1.4.1.42610.1.4.4.1.3.1.2
--
-- ===========================================================================
pduDateAndTimeCurrDateAndTime OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The current date and time in agent."
::= { pduDateAndTime 1 }
pduDateAndTimeTimeZone OBJECT-TYPE
SYNTAX INTEGER {
gMT-1200InternationalDateLineWest(1),
gMT-1200Eniwetok-Kwajalein(2),
gMT-1100MidwayIsland-Samoa(3),
gMT-1000Hawaii(4),
gMT-0900Alaska(5),
gMT-0800PacificTime-Tijuana(6),
gMT-0700Arizona-MountainTime(7),
gMT-0700Chihuahua-LaPaz-Mazatlan(8),
gMT-0700MountainTime(9),
gMT-0600CentralAmerica(10),
gMT-0600CentralTime(11),
gMT-0600Guadalajara-MexicoCity-Monterrey(12),
gMT-0600Saskatchewan(13),
gMT-0500Bogota-Lima-Quito(14),
gMT-0500EasternTime(15),
gMT-0500Indiana(16),
gMT-0400AtlanticTime(17),
gMT-0400Caracas-LaPaz(18),
gMT-0400Santiago(19),
gMT-0330Newfoundland(20),
gMT-0300Brasilia(21),
gMT-0300BuenosAires-Georgetown(22),
gMT-0300Greenland(23),
gMT-0200Mid-Atlantic(24),
gMT-0100Azores(25),
gMT-0100CapeVerdeIs(26),
gMT-0000Casablanca-Monrovia(27),
gMT-0000GreenwichMeanTime-Dublin-Edinburgh-Lisbon-London(28),
gMT0100Amsterdam-Berlin-Bern-Rome-Stockholm-Vienna(29),
gMT0100Belgrade-Bratislava-Budapest-Ljubljana-Prague(30),
gMT0100Brussels-Copenhagen-Madrid-Paris(31),
gMT0100Sarajevo-Skopje-Warsaw-Zagreb(32),
gMT0100WestCentralAfrica(33),
gMT0200Athens-Istanbul-Minsk(34),
gMT0200Bucharest(35),
gMT0200Cairo(36),
gMT0200Harare-Pretoria(37),
gMT0200Helsinki-Kyiv-Riga-Sofia-Tallinn-Vilnius(38),
gMT0200Jerusalem(39),
gMT0300Baghdad(40),
gMT0300Kuwait-Riyadh(41),
gMT0300Moscow-StPetersburg-Volgograd(42),
gMT0300Nairobi(43),
gMT0330Tehran(44),
gMT0400AbuDhabi-Muscat(45),
gMT0400Baku-Tbilisi-Yerevan(46),
gMT0430Kabul(47),
gMT0500Ekaterinburg(48),
gMT0500Islamabad-Karachi-Tashkent(49),
gMT0530Bombay-Calcutta(50),
gMT0530Chennai-Kolkata-Mumbai-NewDelhi(51),
gMT0545Kathmandu(52),
gMT0600Almaty-Novosibirsk(53),
gMT0600Astana-Dhaka(54),
gMT0600SriJayawardenepura(55),
gMT0630Rangoon(56),
gMT0700Bangkok-Hanoi-Jakarta(57),
gMT0700Krasnoyarsk(58),
gMT0800Beijing-Chongqing-HongKong-Urumqi(59),
gMT0800Irkutsk-UlaanBataar(60),
gMT0800KualaLumpur-Singapore(61),
gMT0800Perth(62),
gMT0800Taipei(63),
gMT0900Osaka-Sapporo-Tokyo(64),
gMT0900Seoul(65),
gMT0900Yakutsk(66),
gMT0930Adelaide(67),
gMT0930Darwin(68),
gMT1000Brisbane(69),
gMT1000Canberra-Melbourne-Sydney(70),
gMT1000Guam-PortMoresby(71),
gMT1000Hobart(72),
gMT1000Vladivostok(73),
gMT1100Magadan-SolomonIs-NewCaledonia(74),
gMT1200Auckland-Wellington(75),
gMT1200Fiji-Kamchatka-MarshallIs(76),
gMT1300NukuAlofa(77)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Time Zone to use when synchronize with NTP server."
::= { pduDateAndTime 2 }
pduDateAndTimeDateFormat OBJECT-TYPE
SYNTAX INTEGER {
ddmmyyy(1),
mmddyyyy(2),
yyyymmdd(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Date format."
::= { pduDateAndTime 3 }
pduDateAndTimeSyncMode OBJECT-TYPE
SYNTAX INTEGER {
withComputer(1),
withNTPServer(2),
setManually(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Synchronize mode setting."
::= { pduDateAndTime 4 }
pduDateAndTimeManualDate OBJECT-TYPE
SYNTAX DisplayString (SIZE (10..10))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The date in agent, format is (dd/mm/yyyy)"
::= { pduDateAndTime 5 }
pduDateAndTimeManualTime OBJECT-TYPE
SYNTAX DisplayString (SIZE (8..8))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The time in agent, format is (hh:mm:ss)"
::= { pduDateAndTime 6 }
pduDateAndTimeNtpServer OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..63))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The ip address of NTP server."
::= { pduDateAndTime 7 }
pduDateAndTimeNtpSyncIntervalType OBJECT-TYPE
SYNTAX INTEGER {
day(1),
month(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The sync interval type with NTP server."
::= { pduDateAndTime 8 }
pduDateAndTimeNtpSyncInterval OBJECT-TYPE
SYNTAX INTEGER (1..99)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The sync interval with NTP server."
::= { pduDateAndTime 9 }
pduDateAndTimeNtpTimeDayLightSaving OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
auto(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable the Day Light Saving when synchronize with NTP server."
::= { pduDateAndTime 10 }
-- ===========================================================================
--
-- endof pduGeneralSet Group
--
-- ===========================================================================
-- ===========================================================================
--
-- pduIecViewMgmt Group
-- .1.3.6.1.4.1.42610.1.4.4.1.3.2
--
-- ===========================================================================
pduIecViewMgmtEn OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
enabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable IEC function."
::= { pduIecViewMgmt 1 }
pduIecViewMgmtServer OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..63))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The ip address of IEC server."
::= { pduIecViewMgmt 2 }
pduIecViewMgmtGuid OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The GUID of IEC server."
::= { pduIecViewMgmt 3 }
pduIecViewMgmtPort OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The port number of IEC server."
::= { pduIecViewMgmt 4 }
pduIecViewMgmtPasswd OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..63))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The password of IEC server."
::= { pduIecViewMgmt 5 }
-- ===========================================================================
--
-- end of pduIecViewMgmt Group
--
-- ===========================================================================
-- ===========================================================================
--
-- pduTcpIp Group
-- .1.3.6.1.4.1.42610.1.4.4.1.3.3
--
-- ===========================================================================
pduIpv4Setting OBJECT IDENTIFIER ::= { pduTcpIp 1 }
pduIpv6Setting OBJECT IDENTIFIER ::= { pduTcpIp 2 }
-- ===========================================================================
--
-- pduIpv4Setting Group
-- .1.3.6.1.4.1.42610.1.4.4.1.3.3.1
--
-- ===========================================================================
pduIpv4SettingDhcpEn OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
enabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable DHCP protocol."
::= { pduIpv4Setting 1 }
pduIpv4SettingAddress OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The ip address that NMS can identify the managed device."
::= { pduIpv4Setting 2 }
pduIpv4SettingMask OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Internet address subnet mask."
::= { pduIpv4Setting 3 }
pduIpv4SettingGateway OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The default gateway that allow device managed through routers."
::= { pduIpv4Setting 4 }
pduIpv4SettingDns1 OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Internet address of Primary DNS Server."
::= { pduIpv4Setting 5 }
pduIpv4SettingDns2 OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Internet address of Secondary DNS."
::= { pduIpv4Setting 6 }
-- ===========================================================================
--
-- pduIpv6Setting Group
-- .1.3.6.1.4.1.42610.1.4.4.1.3.3.2
--
-- ===========================================================================
pduIpv6SettingEn OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
enabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable Ipv6 protocol."
::= { pduIpv6Setting 1 }
pduIpv6SettingCfg OBJECT-TYPE
SYNTAX INTEGER {
auto(1),
dhcpv6(2),
manual(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"IPv6 Auto-config, dhcpv6 or Maual setting."
::= { pduIpv6Setting 2 }
pduIpv6SettingLocalAddress OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The ipv6 local address."
::= { pduIpv6Setting 3 }
pduIpv6SettingGlobalAddress OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..63))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The ipv6 global address that NMS can identify the managed device."
::= { pduIpv6Setting 4 }
pduIpv6SettingRouter OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..63))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The default gateway that allow device managed through routers."
::= { pduIpv6Setting 5 }
pduIpv6SettingDns1 OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..63))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Internet address of Primary DNS Server."
::= { pduIpv6Setting 6 }
pduIpv6SettingDns2 OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..63))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Internet address of Secondary DNS."
::= { pduIpv6Setting 7 }
-- ===========================================================================
--
-- end of pduTcpIp Group
--
-- ===========================================================================
-- ===========================================================================
--
-- pduAccessIpSetting Group
-- .1.3.6.1.4.1.42610.1.4.4.1.3.4
--
-- ===========================================================================
pduAccessIpSettingEn OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
enabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable access ip table."
::= { pduAccessIpSetting 1 }
pduAccessIpSettingTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduAccessIpSettingTblEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Display a list of access ip table of master."
::= { pduAccessIpSetting 2}
pduAccessIpSettingTblEntry OBJECT-TYPE
SYNTAX PduAccessIpSettingTblEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Display a list of access ip tablen of master."
INDEX { pduAccessIpSettingTblIndex}
::= { pduAccessIpSettingTable 1 }
PduAccessIpSettingTblEntry ::=
SEQUENCE {
pduAccessIpSettingTblIndex
INTEGER,
pduAccessIpSettingTblAddr
DisplayString,
pduAccessIpSettingTblPrefix
INTEGER,
pduAccessIpSettingTblAction
INTEGER
}
pduAccessIpSettingTblIndex OBJECT-TYPE
SYNTAX INTEGER (0..8)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a access ip entry."
::= { pduAccessIpSettingTblEntry 1 }
pduAccessIpSettingTblAddr OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..63))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The ip address of access ip."
::= { pduAccessIpSettingTblEntry 2 }
pduAccessIpSettingTblPrefix OBJECT-TYPE
SYNTAX INTEGER (0..63)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The prefix length of access ip."
::= { pduAccessIpSettingTblEntry 3 }
pduAccessIpSettingTblAction OBJECT-TYPE
SYNTAX INTEGER {
allow(1),
deny(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The action of access ip."
::= { pduAccessIpSettingTblEntry 4 }
-- ===========================================================================
--
-- end of pduAccessIpSetting Group
--
-- ===========================================================================
-- ===========================================================================
--
-- pduSecurity Group
-- .1.3.6.1.4.1.42610.1.4.4.1.3.5
--
-- ===========================================================================
pduSecurityNetAccessProtectEn OBJECT-TYPE
SYNTAX INTEGER {
disable(1),
enable(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable network access protection function."
::= { pduSecurity 1 }
pduSecuritySshEn OBJECT-TYPE
SYNTAX INTEGER {
disable(1),
enable(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable protect SSH function."
::= { pduSecurity 2 }
pduSecuritySshInterval OBJECT-TYPE
SYNTAX INTEGER {
value5(1),
value10(2),
value20(3),
value30(4),
value100(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The interval of protect SSH."
::= { pduSecurity 3 }
pduSecuritySshTime OBJECT-TYPE
SYNTAX INTEGER {
value1Min(1),
value5Min(2),
value10Min(3),
value30Min(4)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The time of protect SSH."
::= { pduSecurity 4 }
pduSecuritySshBlock OBJECT-TYPE
SYNTAX INTEGER {
value1Min(1),
value30Min(2),
value1Hour(3),
value1Day(4)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The block time of protect SSH."
::= { pduSecurity 5 }
pduSecuritySnmpv3En OBJECT-TYPE
SYNTAX INTEGER {
disable(1),
enable(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable protect SNMPv3 function."
::= { pduSecurity 6 }
pduSecuritySnmpv3Interval OBJECT-TYPE
SYNTAX INTEGER {
value5(1),
value10(2),
value20(3),
value30(4),
value100(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The interval of protect SNMPv3."
::= { pduSecurity 7 }
pduSecuritySnmpv3Time OBJECT-TYPE
SYNTAX INTEGER {
value1Min(1),
value5Min(2),
value10Min(3),
value30Min(4)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The time of protect SNMPv3."
::= { pduSecurity 8 }
pduSecuritySnmpv3Block OBJECT-TYPE
SYNTAX INTEGER {
value1Min(1),
value30Min(2),
value1Hour(3),
value1Day(4)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The block time of protect SNMPv3."
::= { pduSecurity 9 }
pduSecurityHttpEn OBJECT-TYPE
SYNTAX INTEGER {
disable(1),
enable(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable protect HTTP(s) function."
::= { pduSecurity 10 }
pduSecurityHttpInterval OBJECT-TYPE
SYNTAX INTEGER {
value5(1),
value10(2),
value20(3),
value30(4),
value100(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The interval of protect HTTP(s)."
::= { pduSecurity 11 }
pduSecurityHttpTime OBJECT-TYPE
SYNTAX INTEGER {
value1Min(1),
value5Min(2),
value10Min(3),
value30Min(4)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The time of protect HTTP(s)."
::= { pduSecurity 12 }
pduSecurityHttpBlock OBJECT-TYPE
SYNTAX INTEGER {
value1Min(1),
value30Min(2),
value1Hour(3),
value1Day(4)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The block time of protect HTTP(s)."
::= { pduSecurity 13 }
-- ===========================================================================
--
-- pduNetService Group
-- .1.3.6.1.4.1.42610.1.4.4.1.3.6
--
-- ===========================================================================
pduNetServiceSsh OBJECT IDENTIFIER ::= { pduNetService 1 }
pduNetServiceSsl OBJECT IDENTIFIER ::= { pduNetService 2 }
pduNetServicePing OBJECT IDENTIFIER ::= { pduNetService 3 }
pduNetServiceModbus OBJECT IDENTIFIER ::= { pduNetService 4 }
pduNetServiceRadius OBJECT IDENTIFIER ::= { pduNetService 5 }
-- ===========================================================================
--
-- pduNetServiceSsh Group
-- .1.3.6.1.4.1.42610.1.4.4.1.3.6.1
--
-- ===========================================================================
pduNetServiceSshEn OBJECT-TYPE
SYNTAX INTEGER {
disable(1),
enable(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable SSH Server Service."
::= { pduNetServiceSsh 1 }
pduNetServiceSshPort OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Port Number of SSH Server Service."
::= { pduNetServiceSsh 2 }
-- ===========================================================================
--
-- pduNetServiceSsl Group
-- .1.3.6.1.4.1.42610.1.4.4.1.3.6.2
--
-- ===========================================================================
pduNetServiceSslEn OBJECT-TYPE
SYNTAX INTEGER {
disable(1),
enable(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable secure connection(SSL) service."
::= { pduNetServiceSsl 1 }
pduNetServiceSslPort OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Port Number of secure connection(SSL) service."
::= { pduNetServiceSsl 2 }
pduNetServiceSslForce OBJECT-TYPE
SYNTAX INTEGER {
disable(1),
enable(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Use force secure connection(SSL) Only."
::= { pduNetServiceSsl 3 }
-- ===========================================================================
--
-- pduNetServicePing Group
-- .1.3.6.1.4.1.42610.1.4.4.1.3.6.3
--
-- ===========================================================================
pduNetServicePingEn OBJECT-TYPE
SYNTAX INTEGER {
disable(1),
enable(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable to response to PING request."
::= { pduNetServicePing 1 }
-- ===========================================================================
--
-- pduNetServiceModbus Group
-- .1.3.6.1.4.1.42610.1.4.4.1.3.6.4
--
-- ===========================================================================
pduNetServiceModbusEn OBJECT-TYPE
SYNTAX INTEGER {
disable(1),
enable(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable Modbus Server Service."
::= { pduNetServiceModbus 1 }
pduNetServiceModbusPort OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Port Number of Modbus Server Service."
::= { pduNetServiceModbus 2 }
-- ===========================================================================
--
-- pduNetServiceRadius Group
-- .1.3.6.1.4.1.42610.1.4.4.1.3.6.5
--
-- ===========================================================================
pduNetServiceRadiusEn OBJECT-TYPE
SYNTAX INTEGER {
disable(1),
enable(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable RADIUS Client Service."
::= { pduNetServiceRadius 1 }
pduNetServiceRadiusIp OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..63))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The IP Address of RADIUS Client Service."
::= { pduNetServiceRadius 2 }
pduNetServiceRadiusPort OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Port Number of RADIUS Client Service."
::= { pduNetServiceRadius 3 }
pduNetServiceRadiusSecKey OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..63))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Secret Key of RADIUS Client Service."
::= { pduNetServiceRadius 4 }
pduNetServiceRadiusTimeout OBJECT-TYPE
SYNTAX INTEGER (1..99)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Timeout Interval of RADIUS Client Service in seconds."
::= { pduNetServiceRadius 5 }
pduNetServiceRadiusRetry OBJECT-TYPE
SYNTAX INTEGER (1..99)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Retry Times of RADIUS Client Service."
::= { pduNetServiceRadius 6 }
-- ===========================================================================
--
-- endof pduNetService Group
--
-- ===========================================================================
-- ===========================================================================
--
-- pduSnmpSetting Group
-- .1.3.6.1.4.1.42610.1.4.4.1.3.7
--
-- ===========================================================================
pduSnmpSettingAgent OBJECT IDENTIFIER ::= { pduSnmpSetting 1 }
pduSnmpSettingv3Usm OBJECT IDENTIFIER ::= { pduSnmpSetting 2 }
pduSnmpSettingTrap OBJECT IDENTIFIER ::= { pduSnmpSetting 3 }
-- ===========================================================================
--
-- pduSnmpSettingAgent Group
-- .1.3.6.1.4.1.42610.1.4.4.1.3.7.1
--
-- ===========================================================================
pduSnmpSettingAgentEn OBJECT-TYPE
SYNTAX INTEGER {
disable(1),
enable(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable SNMP Server Service."
::= { pduSnmpSettingAgent 1 }
pduSnmpSettingAgentPort OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Port Number of SNMP Server Service."
::= { pduSnmpSettingAgent 2 }
pduSnmpSettingAgentComRead OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Community Read of SNMP Server Service."
::= { pduSnmpSettingAgent 3 }
pduSnmpSettingAgentComWrite OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Community Write of SNMP Server Service."
::= { pduSnmpSettingAgent 4 }
-- ===========================================================================
--
-- pduSnmpSettingv3Usm Group
-- .1.3.6.1.4.1.42610.1.4.4.1.3.7.2
--
-- ===========================================================================
pduSnmpSettingv3UsmUserName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The User Name of snmpv3 USM setting."
::= { pduSnmpSettingv3Usm 1 }
pduSnmpSettingv3UsmAuthPasswd OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Auth-Protocol password of snmpv3 USM setting."
::= { pduSnmpSettingv3Usm 2 }
pduSnmpSettingv3UsmAuthMode OBJECT-TYPE
SYNTAX INTEGER {
md5(1),
sha(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Auth-Protocol mode of snmpv3 USM setting."
::= { pduSnmpSettingv3Usm 3 }
pduSnmpSettingv3UsmPrivPasswd OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Priv-Protocol Password of snmpv3 USM setting."
::= { pduSnmpSettingv3Usm 4 }
pduSnmpSettingv3UsmPrivMode OBJECT-TYPE
SYNTAX INTEGER {
des(1),
aes(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Priv-Protocol mode of snmpv3 USM setting."
::= { pduSnmpSettingv3Usm 5 }
pduSnmpSettingv3UsmSecurityLevel OBJECT-TYPE
SYNTAX INTEGER {
noAuthNoPriv(1),
authNoPriv(2),
authPriv(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The security level of snmpv3 USM setting."
::= { pduSnmpSettingv3Usm 6 }
-- ===========================================================================
--
-- pduSnmpSettingTrap Group
-- .1.3.6.1.4.1.42610.1.4.4.1.3.7.3
--
-- ===========================================================================
pduSnmpSettingTrapTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduSnmpSettingTrapEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list to setting trap table."
::= { pduSnmpSettingTrap 1}
pduSnmpSettingTrapEntry OBJECT-TYPE
SYNTAX PduSnmpSettingTrapEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list to setting trap table."
INDEX { pduSnmpSettingTrapIndex }
::= { pduSnmpSettingTrapTable 1 }
PduSnmpSettingTrapEntry ::=
SEQUENCE {
pduSnmpSettingTrapIndex
INTEGER,
pduSnmpSettingTrapRcvrAddress
DisplayString,
pduSnmpSettingTrapEvtLevel
INTEGER,
pduSnmpSettingTrapVer
INTEGER,
pduSnmpSettingTrapDesc
DisplayString
}
pduSnmpSettingTrapIndex OBJECT-TYPE
SYNTAX INTEGER (0..8)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a trap receiver entry."
::= { pduSnmpSettingTrapEntry 1 }
pduSnmpSettingTrapRcvrAddress OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The IP address of the manager to send a trap to."
::= { pduSnmpSettingTrapEntry 2 }
pduSnmpSettingTrapEvtLevel OBJECT-TYPE
SYNTAX INTEGER {
informational(1),
warning(2),
critical(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The severity level of traps to be received by this manager."
::= { pduSnmpSettingTrapEntry 3 }
pduSnmpSettingTrapVer OBJECT-TYPE
SYNTAX INTEGER {
v1(1),
v2(2),
v3(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The SNMP Trap version of trap receivers."
::= { pduSnmpSettingTrapEntry 4 }
pduSnmpSettingTrapDesc OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Description of trap receivers."
::= { pduSnmpSettingTrapEntry 5 }
-- ===========================================================================
--
-- end of pduSnmpSetting Group
--
-- ===========================================================================
-- ===========================================================================
--
-- pduEmailSetting Group
-- .1.3.6.1.4.1.42610.1.4.4.1.3.8
--
-- ===========================================================================
pduEmailSettingSmtp OBJECT IDENTIFIER ::= { pduEmailSetting 1 }
pduEmailSettingNotify OBJECT IDENTIFIER ::= { pduEmailSetting 2 }
-- ===========================================================================
--
-- pduEmailSettingSmtp Group
-- .1.3.6.1.4.1.42610.1.4.4.1.3.8.1
--
-- ===========================================================================
pduEmailSettingSmtpIp OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..63))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The address of Email server."
::= { pduEmailSettingSmtp 1 }
pduEmailSettingSmtpPort OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The UDP port for Email Server."
::= { pduEmailSettingSmtp 2 }
pduEmailSettingSmtpSender OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..63))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The sender's Email address."
::= { pduEmailSettingSmtp 3 }
pduEmailSettingSmtpSubject OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The prefix string of mail subject"
::= { pduEmailSettingSmtp 4 }
pduEmailSettingSmtpAuthEn OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
enabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable SMTP Authentication."
::= { pduEmailSettingSmtp 5 }
pduEmailSettingSmtpAuthUser OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..63))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The user name of SMTP Authentication."
::= { pduEmailSettingSmtp 6 }
pduEmailSettingSmtpAuthPasswd OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..63))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The password of SMTP Authentication."
::= { pduEmailSettingSmtp 7 }
-- ===========================================================================
--
-- pduEmailSettingNotify Group
-- .1.3.6.1.4.1.42610.1.4.4.1.3.8.2
--
-- ===========================================================================
pduEmailSettingNotifyTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduEmailSettingNotifyEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of managers to send email notification to."
::= { pduEmailSettingNotify 1}
pduEmailSettingNotifyEntry OBJECT-TYPE
SYNTAX PduEmailSettingNotifyEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of managers to send email notification to."
INDEX { pduEmailSettingNotifyIndex }
::= { pduEmailSettingNotifyTable 1 }
PduEmailSettingNotifyEntry ::=
SEQUENCE {
pduEmailSettingNotifyIndex
INTEGER,
pduEmailSettingNotifyRecvAddr
DisplayString,
pduEmailSettingNotifyType
INTEGER,
pduEmailSettingNotifyEvtLev
INTEGER,
pduEmailSettingNotifyDesc
DisplayString
}
pduEmailSettingNotifyIndex OBJECT-TYPE
SYNTAX INTEGER (0..8)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a email notification receiver entry."
::= { pduEmailSettingNotifyEntry 1 }
pduEmailSettingNotifyRecvAddr OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Email address of the manager to send a email notification to."
::= { pduEmailSettingNotifyEntry 2 }
pduEmailSettingNotifyType OBJECT-TYPE
SYNTAX INTEGER {
none(1),
events(2),
eventsStatus(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Email Type of email notification receivers."
::= { pduEmailSettingNotifyEntry 3 }
pduEmailSettingNotifyEvtLev OBJECT-TYPE
SYNTAX INTEGER {
critical(1),
warning(2),
informational(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The severity level of email notification to be received by this manager."
::= { pduEmailSettingNotifyEntry 4 }
pduEmailSettingNotifyDesc OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Description of email notification receivers."
::= { pduEmailSettingNotifyEntry 5 }
-- ===========================================================================
--
-- end of pduEmailSetting Group
--
-- ===========================================================================
-- ===========================================================================
--
-- pduUserSetting Group
-- .1.3.6.1.4.1.42610.1.4.4.1.3.9
--
-- ===========================================================================
pduUserSettingLocal OBJECT IDENTIFIER ::= { pduUserSetting 1 }
pduUserSettingRadius OBJECT IDENTIFIER ::= { pduUserSetting 2 }
pduUserSettingAuthCfg OBJECT IDENTIFIER ::= { pduUserSetting 3 }
-- ===========================================================================
--
-- pduUserSettingLocal Group
-- .1.3.6.1.4.1.42610.1.4.4.1.3.9.1
--
-- ===========================================================================
pduUserSettingLocalTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduUserSettingLocalEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of local user setting."
::= { pduUserSettingLocal 1}
pduUserSettingLocalEntry OBJECT-TYPE
SYNTAX PduUserSettingLocalEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of local user setting."
INDEX { pduUserSettingLocalIndex }
::= { pduUserSettingLocalTable 1 }
PduUserSettingLocalEntry ::=
SEQUENCE {
pduUserSettingLocalIndex
INTEGER,
pduUserSettingLocalUserName
DisplayString,
pduUserSettingLocalPasswd
DisplayString,
pduUserSettingLocalPrivilege
INTEGER
}
pduUserSettingLocalIndex OBJECT-TYPE
SYNTAX INTEGER (0..8)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a local user setting."
::= { pduUserSettingLocalEntry 1 }
pduUserSettingLocalUserName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The user name to a local user."
::= { pduUserSettingLocalEntry 2 }
pduUserSettingLocalPasswd OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The password to a local user."
::= { pduUserSettingLocalEntry 3 }
pduUserSettingLocalPrivilege OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
readOnly(2),
readWrite(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The privilege level to a local user."
::= { pduUserSettingLocalEntry 4 }
-- ===========================================================================
--
-- pduUserSettingRadius Group
-- .1.3.6.1.4.1.42610.1.4.4.1.3.9.2
--
-- ===========================================================================
pduUserSettingRadiusTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduUserSettingRadiusEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of radius user setting."
::= { pduUserSettingRadius 1}
pduUserSettingRadiusEntry OBJECT-TYPE
SYNTAX PduUserSettingRadiusEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of radius user setting."
INDEX { pduUserSettingRadiusIndex }
::= { pduUserSettingRadiusTable 1 }
PduUserSettingRadiusEntry ::=
SEQUENCE {
pduUserSettingRadiusIndex
INTEGER,
pduUserSettingRadiusUserName
DisplayString,
pduUserSettingRadiusPrivilege
INTEGER
}
pduUserSettingRadiusIndex OBJECT-TYPE
SYNTAX INTEGER (0..8)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a radius user setting."
::= { pduUserSettingRadiusEntry 1 }
pduUserSettingRadiusUserName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The user name to a radius user."
::= { pduUserSettingRadiusEntry 2 }
pduUserSettingRadiusPrivilege OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
readOnly(2),
readWrite(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The privilege level to a radius user."
::= { pduUserSettingRadiusEntry 3 }
-- ===========================================================================
--
-- pduUserSettingAuthCfg Group
-- .1.3.6.1.4.1.42610.1.4.4.1.3.9.3
--
-- ===========================================================================
pduUserSettingAuthCfgAdminName OBJECT-TYPE
SYNTAX DisplayString (SIZE (1..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The admin name of system."
::= { pduUserSettingAuthCfg 1 }
pduUserSettingAuthCfgAdminPasswd OBJECT-TYPE
SYNTAX DisplayString (SIZE (1..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The admin password of system."
::= { pduUserSettingAuthCfg 2 }
-- ===========================================================================
--
-- end of pduUserSetting Group
--
-- ===========================================================================
-- ===========================================================================
--
-- end of pduSnmpSetting Group
--
-- ===========================================================================
-- ===========================================================================
--
-- end of pduSettings
--
-- ===========================================================================
-- ===========================================================================
--
-- pduAdvanced
-- Advanced
-- .1.3.6.1.4.1.42610.1.4.4.1.4
--
-- ===========================================================================
pduSyslogSetting OBJECT IDENTIFIER ::= { pduAdvanced 1 }
pduLinksSetting OBJECT IDENTIFIER ::= { pduAdvanced 2 }
-- ===========================================================================
--
-- pduSyslogSetting Group
-- .1.3.6.1.4.1.42610.1.4.4.1.4.1
--
-- ===========================================================================
pduSysEvtLog OBJECT IDENTIFIER ::= { pduSyslogSetting 1 }
pduHisLog OBJECT IDENTIFIER ::= { pduSyslogSetting 2 }
-- ===========================================================================
--
-- pduSysEvtLog Group
-- .1.3.6.1.4.1.42610.1.4.4.1.4.1.1
--
-- ===========================================================================
pduSysEvtLogEn OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
enabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable the transmission event log of the syslog server."
::= { pduSysEvtLog 1 }
pduSysEvtLogIp OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..63))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The address of event log of syslog server."
::= { pduSysEvtLog 2 }
pduSysEvtLogPort OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The port number of event log of syslog Server."
::= { pduSysEvtLog 3 }
-- ===========================================================================
--
-- pduHisLog Group
-- .1.3.6.1.4.1.42610.1.4.4.1.4.1.2
--
-- ===========================================================================
pduHisLogEn OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
enabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable the transmission history log of the syslog server."
::= { pduHisLog 1 }
pduHisLogIp OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..63))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The address of history log of syslog server."
::= { pduHisLog 2 }
pduHisLogPort OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The port number of history log of syslog Server."
::= { pduHisLog 3 }
-- ===========================================================================
--
-- end of pduSyslogSetting Group
--
-- ===========================================================================
-- ===========================================================================
--
-- pduLinksSetting Group
-- .1.3.6.1.4.1.42610.1.4.4.1.4.2
--
-- ===========================================================================
pduLinksSettingTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduLinksSettingEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of radius user setting."
::= { pduLinksSetting 1}
pduLinksSettingEntry OBJECT-TYPE
SYNTAX PduLinksSettingEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of radius user setting."
INDEX { pduLinksSettingIndex }
::= { pduLinksSettingTable 1 }
PduLinksSettingEntry ::=
SEQUENCE {
pduLinksSettingIndex
INTEGER,
pduLinksSettingScreenText
DisplayString,
pduLinksSettingAddress
DisplayString,
pduLinksSettingStatus
INTEGER
}
pduLinksSettingIndex OBJECT-TYPE
SYNTAX INTEGER (0..4)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a external links setting."
::= { pduLinksSettingEntry 1 }
pduLinksSettingScreenText OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The screen text to a external links."
::= { pduLinksSettingEntry 2 }
pduLinksSettingAddress OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The address to a external links."
::= { pduLinksSettingEntry 3 }
pduLinksSettingStatus OBJECT-TYPE
SYNTAX INTEGER {
hide(1),
show(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The status to a external links."
::= { pduLinksSettingEntry 4 }
-- ===========================================================================
--
-- end of pduLinksSetting Group
--
-- ===========================================================================
-- ===========================================================================
--
-- end of pduAdvanced
--
-- ===========================================================================
-- ===========================================================================
--
-- pduTraps
-- Grouping all ispro traps here.
--
-- ===========================================================================
pduSysColdBoot TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"coldStart"
::= 1
pduSysWarmBoot TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"warmStart"
::= 2
pduSysEMDRestore TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Informational: EMD communication restored."
::= 3
pduSysEMDLost TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Warning: EMD communication lost."
::= 4
pduSysInletRestore TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Informational: Inlet communication restored."
::= 5
pduSysInletLost TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Warning: Inlet communication lost."
::= 6
pduInletLoadWarn TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Warning: Inlet load was higher than warning set point."
::= 7
pduInletLoadWarnToNormal TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Informational: Inlet load was not higher than warning set point."
::= 8
pduInletLoadCritical TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Critical: Inlet load was higher than critical set point."
::= 9
pduInletLoadCritToWarn TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Informational: Inlet load was not higher than critical set point."
::= 10
pduInletLoadBalanceWarn TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Warning: Inlet load balance was higher than warning set point."
::= 11
pduInletLoadBalanceWarnToNormal TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Informational: Inlet load balance was not higher than warning set point."
::= 12
pduInletLoadBalanceCritical TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Critical: Inlet load balance was higher than critical set point."
::= 13
pduInletLoadBalanceCritToWarn TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Informational: Inlet load balance was not higher than critical set point."
::= 14
pduInletCurrPhase1CB1Warn TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Warning: Inlet CB1 phase1 current was higher than warning set point."
::= 15
pduInletCurrPhase1CB1WarnToNormal TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Informational: Inlet CB1 phase1 current was not higher than warning set point."
::= 16
pduInletCurrPhase1CB1Critical TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Critical: Inlet CB1 phase1 current was higher than critical set point."
::= 17
pduInletCurrPhase1CB1CritToWarn TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Informational: Inlet CB1 phase1 current was not higher than critical set point."
::= 18
pduInletCurrPhase2CB1Warn TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Warning: Inlet CB1 phase2 current was higher than warning set point."
::= 19
pduInletCurrPhase2CB1WarnToNormal TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Informational: Inlet CB1 phase2 current was not higher than warning set point."
::= 20
pduInletCurrPhase2CB1Critical TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Critical: Inlet CB1 phase2 current was higher than critical set point."
::= 21
pduInletCurrPhase2CB1CritToWarn TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Informational: Inlet CB1 phase2 current was not higher than critical set point."
::= 22
pduInletCurrPhase3CB1Warn TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Warning: Inlet CB1 phase3 current was higher than warning set point."
::= 23
pduInletCurrPhase3CB1WarnToNormal TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Informational: Inlet CB1 phase3 current was not higher than warning set point."
::= 24
pduInletCurrPhase3CB1Critical TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Critical: Inlet CB1 phase3 current was higher than critical set point."
::= 25
pduInletCurrPhase3CB1CritToWarn TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Informational: Inlet CB1 phase3 current was not higher than critical set point."
::= 26
pduInletTotalCurrPhase1Warn TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Warning: Inlet phase1 total current was higher than warning set point."
::= 27
pduInletTotalCurrPhase1WarnToNormal TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Informational: Inlet phase1 total current was not higher than warning set point."
::= 28
pduInletTotalCurrPhase1Critical TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Critical: Inlet phase1 total current was higher than critical set point."
::= 29
pduInletTotalCurrPhase1CritToWarn TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Informational: Inlet phase1 total current was not higher than critical set point."
::= 30
pduInletTotalCurrPhase2Warn TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Warning: Inlet phase2 total current was higher than warning set point."
::= 31
pduInletTotalCurrPhase2WarnToNormal TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Informational: Inlet phase2 total current was not higher than warning set point."
::= 32
pduInletTotalCurrPhase2Critical TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Critical: Inlet phase2 total current was higher than critical set point."
::= 33
pduInletTotalCurrPhase2CritToWarn TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Informational: Inlet phase2 total current was not higher than critical set point."
::= 34
pduInletTotalCurrPhase3Warn TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Warning: Inlet phase3 total current was higher than warning set point."
::= 35
pduInletTotalCurrPhase3WarnToNprmal TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Informational: Inlet phase3 total current was not higher than warning set point."
::= 36
pduInletTotalCurrPhase3Critical TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Critical: Inlet phase3 total current was higher than critical set point."
::= 37
pduInletTotalCurrPhase3CritToWarn TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Informational: Inlet phase3 total current was not higher than critical set point."
::= 38
pduInletVoltPhase1Warn TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Warning: Inlet total phase1 voltage was higher than warning set point."
::= 39
pduInletVoltPhase1WarnToNormal TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Informational: Inlet phase1 voltage was not higher than warning set point."
::= 40
pduInletVoltPhase1Critical TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Critical: Inlet phase1 voltage was higher than critical set point."
::= 41
pduInletVoltPhase1CritToWarn TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Informational: Inlet phase1 voltage was not higher than critical set point."
::= 42
pduInletVoltPhase2Warn TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Warning: Inlet phase2 voltage was higher than warning set point."
::= 43
pduInletVoltPhase2WarnToNormal TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Informational: Inlet phase2 voltage was not higher than warning set point."
::= 44
pduInletVoltPhase2Critical TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Critical: Inlet phase2 voltage was higher than critical set point."
::= 45
pduInletVoltPhase2CritToWarn TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Informational: Inlet phase2 voltage was not higher than critical set point."
::= 46
pduInletVoltPhase3Warn TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Warning: Inlet phase3 voltage was higher than warning set point."
::= 47
pduInletVoltPhase3WarnToNormal TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Informational: Inlet phase3 voltage was not higher than warning set point."
::= 48
pduInletVoltPhase3Critical TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Critical: Inlet phase3 voltage was higher than critical set point."
::= 49
pduInletVoltPhase3CritToWarn TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Informational: Inlet phase3 voltage was not higher than critical set point."
::= 50
pduEmdTempOverHighWarn TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Warning: temperature was higher than temperature warning set point."
::= 51
pduEmdTempNotOverHighWarn TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Informational: temperature was not higher than temperature warning set point."
::= 52
pduEmdTempOverHighCrit TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Critical: temperature was higher than temperature critical set point."
::= 53
pduEmdTempNotOverHighCrit TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Informational: temperature was not higher than temperature critical set point."
::= 54
pduEmdTempUnderLowWarn TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Warning: temperature was lower than temperature warning set point."
::= 55
pduEmdTempNotUnderLowWarn TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Informational: temperature was not lower than temperature warning set point."
::= 56
pduEmdTempUnderLowCrit TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Critical: temperature was lower than temperature critical set point."
::= 57
pduEmdTempNotUnderLowCrit TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Informational: temperature was not lower than temperature critical set point."
::= 58
pduEmdHumiOverHighWarn TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Warning: humidity was higher than humidity warning set point."
::= 59
pduEmdHumiNotOverHighWarn TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Informational: humidity was not higher than humidity warning set point."
::= 60
pduEmdHumiOverHighCrit TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Critical: humidity was higher than humidity critical set point."
::= 61
pduEmdHumiNotOverHighCrit TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Informational: humidity was not higher than humidity critical set point."
::= 62
pduEmdHumiUnderLowWarn TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Warning: humidity was lower than humidity warning set point."
::= 63
pduEmdHumiNotUnderLowWarn TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Informational: humidity was not lower than humidity warning set point."
::= 64
pduEmdHumiUnderLowCrit TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Critical: humidity was lower than humidity critical set point."
::= 65
pduEmdHumiNotUnderLowCrit TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Informational: humidity was not lower than humidity critical set point."
::= 66
pduAlarm1Triggered TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Critical: Alarm 1 has triggered."
::= 67
pduAlarm1Normal TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Informational: Alarm 1 has returned to normal."
::= 68
pduAlarm2Triggered TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Critical: Alarm 2 has triggered."
::= 69
pduAlarm2Normal TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Informational: Alarm 2 has returned to normal."
::= 70
pduInletCurrPhase1CB2Warn TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Warning: Inlet CB2 phase1 current was higher than warning set point."
::= 71
pduInletCurrPhase1CB2WarnToNormal TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Informational: Inlet CB2 phase1 current was not higher than warning set point."
::= 72
pduInletCurrPhase1CB2Critical TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Critical: Inlet CB2 phase1 current was higher than critical set point."
::= 73
pduInletCurrPhase1CB2CritToWarn TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Informational: Inlet CB2 phase1 current was not higher than critical set point."
::= 74
pduInletCurrPhase2CB2Warn TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Warning: Inlet CB2 phase2 current was higher than warning set point."
::= 75
pduInletCurrPhase2CB2WarnToNormal TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Informational: Inlet CB2 phase2 current was not higher than warning set point."
::= 76
pduInletCurrPhase2CB2Critical TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Critical: Inlet CB2 phase2 current was higher than critical set point."
::= 77
pduInletCurrPhase2CB2CritToWarn TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Informational: Inlet CB2 phase2 current was not higher than critical set point."
::= 78
pduInletCurrPhase3CB2Warn TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Warning: Inlet CB2 phase3 current was higher than warning set point."
::= 79
pduInletCurrPhase3CB2WarnToNormal TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Informational: Inlet CB2 phase3 current was not higher than warning set point."
::= 80
pduInletCurrPhase3CB2Critical TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Critical: Inlet CB2 phase3 current was higher than critical set point."
::= 81
pduInletCurrPhase3CB2CritToWarn TRAP-TYPE
ENTERPRISE pduTraps
DESCRIPTION
"Informational: Inlet CB2 phase3 current was not higher than critical set point."
::= 82
END