6001 lines
162 KiB
Plaintext

-- ----------------------------------------------------------------------
--
-- coniston.sm2
--
-- ----------------------------------------------------------------------
--
-- $Revision$
--
-- $Date$
--
HAWK-I2-MIB DEFINITIONS ::= BEGIN
IMPORTS
MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE, enterprises, Unsigned32
FROM SNMPv2-SMI
-- DisplayString
-- FROM RFC1213-MIB
-- MODULE-COMPLIANCE, OBJECT-GROUP, NOTIFICATION-GROUP
-- FROM SNMPv2-CONF
TEXTUAL-CONVENTION, RowStatus, TruthValue, MacAddress, DateAndTime
FROM SNMPv2-TC
-- InetAddress, InetAddressType
-- FROM INET-ADDRESS-MIB
;
-- 1.3.6.1.4.1.3711
hawki2MIB MODULE-IDENTITY
LAST-UPDATED "202006031200Z" -- 01 June 2020
ORGANIZATION "Panduit Corp."
CONTACT-INFO "Panduit Corp.
Intelligent Management Systems Group
Postal: Panduit Corp.
18900 Panduit Drive
Tinley Park, IL 60487
USA
Tel: +1 708 532-1800/888-506-5400
E-mail: techsupport@panduit.com"
DESCRIPTION
"SmartZone Gateway MIB for the following products:-
- SmartZone Gateway EP022 (PowerHawk 2)
- SmartZone Gateway EP042 (RacKMS)
- SmartZone Gateway EPA064 (Hawk-i 3)
- SmartZone Gateway EPA126 (Eagle-i)
- SmartZone Gateway E24 (Envirohawk 2)
- RMS Compact 2
- SmartZone Network-Enabled Rack PDU"
REVISION "202006031200Z" -- 01 June 2020
DESCRIPTION
"Issue 23
Add G5 PDU type"
REVISION "201902081200Z" -- 08 February 2019
DESCRIPTION
"Issue 22
Add failedStuck state to pduOutOn."
REVISION "201710181200Z" -- 18 October 2017
DESCRIPTION
"Issue 21
Correct the type on trapCode"
REVISION "201702091200Z" -- 09 February 2017
DESCRIPTION
"Issue 20
Correct the ranges on the input thresholds"
REVISION "201701311200Z" -- 31 January 2017
DESCRIPTION
"Issue 19
Add a description line that was missing from the clampVolts comment."
REVISION "201701171200Z" -- 17 January 2017
DESCRIPTION
"Issue 18
Bug 25441 - Make pdunumofoutlets and pdutype read-only"
REVISION "201612061200Z" -- 06 December 2016
DESCRIPTION
"Issue 17
Bug 25471 - Exended lower limits of pduTrapThreshTable Amps and Volts thresholds to permit a value of -1"
REVISION "201608251200Z" -- 25 August 2016
DESCRIPTION
"Issue 16
Bug 25198 - .99 extra quote at line 59 removed "
REVISION "201605191200Z" -- 19 May 2016
DESCRIPTION
"Issue 15
Bug 25179 - .99 aggregate variables are missing from the MIB
pduRMSAmps thresholds were modified to support the aggregate values "
REVISION "201605181200Z" -- 18 May 2016
DESCRIPTION
"Issue 14
SYNTAX of numerous objects adjusted
acuLastCode added to acuCtlTable
pduOutPFactorUTLTrapPer MAX-ACCESS changed from read-only to read-write
pduOutPFactorLTLTrapPer MAX-ACCESS changed from read-only to read-write"
REVISION "201506301200Z" -- 30 June 2015
DESCRIPTION
"Issue 13
ipTHAScaling restricted to permitted values
acuDoorOpenTimeOut range extended to 3600"
REVISION "201506181200Z" -- 18 June 2015
DESCRIPTION
"Issue 12
Inputs channel range extended to 48 (ipSelect,ipTHAChan,ipTHAThreshChan,ipTHATrapEnChan,ipTHATrapPerChan,ipContChan)"
REVISION "201504081200Z" -- 08 April 2015
DESCRIPTION
"Issue 11
ipTHAAutoDetect and ipTHAType made read-only"
REVISION "201406180000Z" -- 18 June 2014
DESCRIPTION
"Issue 10
MODULE-IDENTITY CONTACT-INFO and DESCRIPTION updated
Type IpStackConfiguration added to reflect network configuration.
invDefaultIPAddrType changed to use IpStackConfiguration type.
InputContactState enumeration extended to support unknown state.
ipTHAValue range extended to multiple features
ipContTrapPeriod range extended to match description.
pduOutCycle enumeration extended to support unknown state.
pduPwrSupplyFreq range extended to support detection of device removal.
Increased range of Input value and threshold values (-58.0 F to 374.0 K)
Added SmartZone Network-Enabled Rack PDU support.
Extended MIB for future product planning"
REVISION "201404011200Z" -- 01 April 2014
DESCRIPTION
"Issue 9
Added objects to pduTable, pduMonTable and platformData"
REVISION "201007151200Z" -- 15 July 2010
DESCRIPTION
"Issue 8
Added 3-phase PDU branch"
REVISION "200905011200Z" -- 01 May 2009
DESCRIPTION
"Issue 7
Extension Unit renamed to Expansion Port.
Revised External Unit types for Expansion Port."
REVISION "200806181200Z" -- 18 June 2008
DESCRIPTION
"Issue 6
CLamp configuration added"
REVISION "200802271200Z" -- 27 February 2008
DESCRIPTION
"Issue 5
Change to ORGANIZATION and CONTACT-INFO information
Issue control added"
REVISION "200709071200Z" -- 7 September 2007
DESCRIPTION
"Issue 4
Correct Extension Unit object order and allow its type to be selected on install"
REVISION "200709061200Z" -- 6 September 2007
DESCRIPTION
"Issue 3
Implement updated MIB"
REVISION "200707201200Z" -- 20 July 2007
DESCRIPTION
"Issue 2
Extensions and enhancements for new products"
REVISION "200705111200Z" -- 11 May 2007
DESCRIPTION
"Issue 1
Initial version - adapted from Hawk-i 2 MIB"
::= { sinetica 24 }
DisplayString ::= OCTET STRING
-- This data type is used to model textual information taken
-- from the NVT ASCII character set. (Copied from RFC1213-MIB.)
InetAddressType ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"A value that represents a type of Internet address. (Copied from INET-ADDRESS-MIB.)"
SYNTAX INTEGER {
unknown(0),
ipv4(1),
ipv6(2),
ipv4z(3),
ipv6z(4),
dns(16)
}
InetAddress ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Denotes a generic Internet address. (Copied from INET-ADDRESS-MIB.)"
SYNTAX OCTET STRING (SIZE (0..255))
IpStackConfiguration ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"A value that represents the network stack configuration"
SYNTAX INTEGER {
unknown(0),
ipv4Only(1),
ipv6Only(2),
ipv4AndIpv6(3)
}
ContactState ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Represents the state of a set of contacts."
SYNTAX INTEGER { open(1), closed(2) }
InputContactState ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Represents the state of a set of input contacts."
SYNTAX INTEGER { open(1), closed(2), armed(3), triggered(4), unknown(255) }
RelayState ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Represents the energised state of a relay."
SYNTAX INTEGER { on(1), off(2) }
OutputControlState ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Represents the control setiing for an output."
SYNTAX INTEGER { activate(1), deactivate(2), logic(3) }
EnableState ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Represents the state of an enabling flag."
SYNTAX INTEGER { enabled(1), disabled(2) }
InputDataType ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Represents the type of data read at an input."
SYNTAX INTEGER { autodetect(1), temperature(2), humidity(3), analogue(4), contact(5), inactive(255) }
KeypadEnableState ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Represents the type of keypad enabled."
SYNTAX INTEGER { matrix2x5(1), matrix3x4(2), inactive(255) }
ExternalUnitType ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Represents the type of external unit."
SYNTAX INTEGER {
unknown(0),
acu(1),
keypad(2),
pduEU(3),
enviroHawk2(4),
idm(5),
autoWithTraps(253),
auto(254),
inactive(255) }
sinetica OBJECT IDENTIFIER ::= { enterprises 3711 }
-- 1.3.6.1.4.1.3711.24.1
v1 OBJECT IDENTIFIER ::= { hawki2MIB 1 } -- MIB variant number
-- 1.3.6.1.4.1.3711.24.1.1
objects OBJECT IDENTIFIER ::= { v1 1 }
-- 1.3.6.1.4.1.3711.24.1.2
traps OBJECT IDENTIFIER ::= { v1 2 }
-- BEGIN SECTION PDU2
-- 1.3.6.1.4.1.3711.24.2
v2 OBJECT IDENTIFIER ::= { hawki2MIB 2}
-- END SECTION PDU2
-- {{{ objects group
-- 1.3.6.1.4.1.3711.24.1.1.1
inputs OBJECT IDENTIFIER ::= { objects 1 }
-- 1.3.6.1.4.1.3711.24.1.1.2
outputs OBJECT IDENTIFIER ::= { objects 2 }
-- 1.3.6.1.4.1.3711.24.1.1.4
keypads OBJECT IDENTIFIER ::= { objects 4 }
-- 1.3.6.1.4.1.3711.24.1.1.5
acus OBJECT IDENTIFIER ::= { objects 5 }
-- 1.3.6.1.4.1.3711.24.1.1.6
access OBJECT IDENTIFIER ::= { objects 6 }
-- 1.3.6.1.4.1.3711.24.1.1.7
pdus OBJECT IDENTIFIER ::= { objects 7 }
-- 1.3.6.1.4.1.3711.24.1.1.8
expansion OBJECT IDENTIFIER ::= { objects 8 } -- Expansion Ports
-- 1.3.6.1.4.1.3711.24.1.1.9
clamp OBJECT IDENTIFIER ::= { objects 9 }
-- BEGIN SECTION IDM
-- 1.3.6.1.4.1.3711.24.1.1.10
idm OBJECT IDENTIFIER ::= { objects 10 }
-- END SECTION IDM
-- 1.3.6.1.4.1.3711.24.1.1.11
pdusP2 OBJECT IDENTIFIER ::= { objects 11 }
-- 1.3.6.1.4.1.3711.24.1.1.98
platformData OBJECT IDENTIFIER ::= { objects 98 }
-- 1.3.6.1.4.1.3711.24.1.1.99
inventory OBJECT IDENTIFIER ::= { objects 99 }
-- 1.3.6.1.4.1.3711.24.1.1.100
trapInfo OBJECT IDENTIFIER ::= { objects 100 }
-- }}} End of objects group
-- {{{ inputs group
-- The Hawk-i2 inputs can all be either temperature, humidity, analogue volts or contact state.
-- To deal with this there is one table to deal with all analogue-type inputs (temperature, humidity, analogue volts) and another for the contacts.
-- At any time an input is permitted to have an entry in one table only, depending on which type of input it is currently monitoring.
-- 1.3.6.1.4.1.3711.24.1.1.1.1
ipCommon OBJECT IDENTIFIER ::= { inputs 1 }
-- 1.3.6.1.4.1.3711.24.1.1.1.2
ipTHA OBJECT IDENTIFIER ::= { inputs 2 }
-- 1.3.6.1.4.1.3711.24.1.1.1.3
ipContact OBJECT IDENTIFIER ::= { inputs 3 }
-- {{{ ipCommon group
-- 1.3.6.1.4.1.3711.24.1.1.1.1.1
ipEnable OBJECT IDENTIFIER ::= { ipCommon 1 }
-- {{{ ipEnable group
-- 1.3.6.1.4.1.3711.24.1.1.1.1.1.1
ipSelect OBJECT-TYPE
SYNTAX INTEGER (0..48)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Selects the channel to be enabled or disabled by ipInsert.
A value of 0 selects no channel."
DEFVAL { 0 }
::= { ipEnable 1 }
-- 1.3.6.1.4.1.3711.24.1.1.1.1.1.2
ipInsert OBJECT-TYPE
SYNTAX InputDataType
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Inserts or removes the channel selected by ipSelect -
causes an entry for that channel to be created or deleted in the relevant tables.
- Read behaviour is undefined."
::= { ipEnable 2 }
-- }}} End of ipEnable group
-- }}} End of ipCommon group
-- {{{ ipTHA - i.e. temperature, humidity and analogue Volts monitoring
-- 1.3.6.1.4.1.3711.24.1.1.1.2.1
ipTempScaleFlag OBJECT-TYPE
SYNTAX INTEGER { celsius(1), fahrenheit(2), kelvin(3) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Temperature scale (Celsius/Fahrenheit) for temperature monitoring."
::= { ipTHA 1 }
-- 1.3.6.1.4.1.3711.24.1.1.1.2.2
ipTHATable OBJECT-TYPE
SYNTAX SEQUENCE OF IpTHAEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table giving data for all enabled inputs with analogue-type monitoring."
::= { ipTHA 2 }
-- 1.3.6.1.4.1.3711.24.1.1.1.2.2.1
ipTHAEntry OBJECT-TYPE
SYNTAX IpTHAEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A conceptual row containing information about one analogue-type input."
INDEX { ipTHAChan }
::= { ipTHATable 1 }
IpTHAEntry ::= SEQUENCE {
ipTHAChan INTEGER,
ipTHARS RowStatus,
ipTHAName DisplayString,
ipTHALocn DisplayString,
ipTHAAutoDetect TruthValue,
ipTHAType InputDataType,
ipTHAValue INTEGER,
ipTHAScaling INTEGER,
ipTHAOffset INTEGER,
ipTHAHysteresis INTEGER
}
-- 1.3.6.1.4.1.3711.24.1.1.1.2.2.1.1
ipTHAChan OBJECT-TYPE
SYNTAX INTEGER (0..48)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The input number."
::= { ipTHAEntry 1 }
-- 1.3.6.1.4.1.3711.24.1.1.1.2.2.1.2
ipTHARS OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The analogue-type input table row status."
::= { ipTHAEntry 2 }
-- 1.3.6.1.4.1.3711.24.1.1.1.2.2.1.3
ipTHAName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The name of this input"
::= { ipTHAEntry 3 }
-- 1.3.6.1.4.1.3711.24.1.1.1.2.2.1.4
ipTHALocn OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A system-defined name for the physical location of this input, e.g. MCU."
::= { ipTHAEntry 4 }
-- 1.3.6.1.4.1.3711.24.1.1.1.2.2.1.5
ipTHAAutoDetect OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates that the type of data this input is monitoring is selected automatically."
::= { ipTHAEntry 5 }
-- 1.3.6.1.4.1.3711.24.1.1.1.2.2.1.6
ipTHAType OBJECT-TYPE
SYNTAX InputDataType
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates the type of data this input is monitoring."
::= { ipTHAEntry 6 }
-- 1.3.6.1.4.1.3711.24.1.1.1.2.2.1.7
ipTHAValue OBJECT-TYPE
SYNTAX INTEGER (-999999999 | -99999999 | -17999680 | -10000000 | -9997268 | -580..120000 | 10000000 | 10002732 | 18000320 | 99999999)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current reading in the relevant measurement units.
-999999999 - Input Data Uninitialised
-99999999 - Input Data Under Range
-17999680 - Temperature Data Under Range in F
-10000000 - Temperature Data Under Range in C
-9997268 - Temperature Data Under Range in K
-580..3740 - Valid Range for all input types. Subranges described below:
580..3740 supports Temperature sensors in C, F or K (see ipTempScaleFlag) to a tenth of a degree (-58.0F to 374.0 K)
0..1000 supports Humidity sensors in tenths of a percentage Relative Humidity. (0.0% to 100.0%)
0..120000 supports Analog sensors to tenths of a Volt. (0.0 to 12000.0V)
10000000 - Temperature Data Over Range in C
10002732 - Temperature Data Over Range in K
18000320 - Temperature Data Over Range in F
99999999 - Input Data Over Range"
::= { ipTHAEntry 7 }
-- 1.3.6.1.4.1.3711.24.1.1.1.2.2.1.8
ipTHAScaling OBJECT-TYPE
SYNTAX INTEGER (0 | 1 | 10 | 100 | 1000 | 10000)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Scaling factor for ipTHAValue in units of 0.1 when ipTHAType=analogue."
::= { ipTHAEntry 8 }
-- 1.3.6.1.4.1.3711.24.1.1.1.2.2.1.9
ipTHAOffset OBJECT-TYPE
SYNTAX INTEGER (-1479..2119)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Calibration offset in the same units as for ipTHAValue."
::= { ipTHAEntry 9 }
-- 1.3.6.1.4.1.3711.24.1.1.1.2.2.1.10
ipTHAHysteresis OBJECT-TYPE
SYNTAX INTEGER (-1479..2119)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Hysteresis on threshold levels in the same units as for ipTHAValue."
::= { ipTHAEntry 10 }
-- {{{ ipTHATrapsCfg group
-- 1.3.6.1.4.1.3711.24.1.1.1.2.3
ipTHATrapsCfg OBJECT IDENTIFIER ::= { ipTHA 3 }
-- {{{ ipTHAThreshTable
-- 1.3.6.1.4.1.3711.24.1.1.1.2.3.1
ipTHAThreshTable OBJECT-TYPE
SYNTAX SEQUENCE OF IpTHAThreshEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table listing the trap threshold levels for all enabled inputs with analogue-type monitoring."
::= { ipTHATrapsCfg 1 }
-- 1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1
ipTHAThreshEntry OBJECT-TYPE
SYNTAX IpTHAThreshEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A conceptual row containing threshold information for one analogue-type input."
INDEX { ipTHAThreshChan }
::= { ipTHAThreshTable 1 }
IpTHAThreshEntry ::= SEQUENCE {
ipTHAThreshChan INTEGER,
ipTHAThreshRS RowStatus,
ipTHAUCL INTEGER,
ipTHAUWL INTEGER,
ipTHALWL INTEGER,
ipTHALCL INTEGER,
ipTHADeltaPos Unsigned32,
ipTHADeltaNeg Unsigned32
}
-- 1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1.1
ipTHAThreshChan OBJECT-TYPE
SYNTAX INTEGER (0..48)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The input number."
::= { ipTHAThreshEntry 1 }
-- 1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1.2
ipTHAThreshRS OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The analogue-type input table row status."
::= { ipTHAThreshEntry 2 }
-- 1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1.3
ipTHAUCL OBJECT-TYPE
SYNTAX INTEGER (-300..100000)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The Upper Critical Limit for this input in the same units as for ipTHAValue."
::= { ipTHAThreshEntry 3 }
-- 1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1.4
ipTHAUWL OBJECT-TYPE
SYNTAX INTEGER (-300..100000)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The Upper Warning Limit for this input in the same units as for ipTHAValue."
::= { ipTHAThreshEntry 4 }
-- 1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1.5
ipTHALWL OBJECT-TYPE
SYNTAX INTEGER (-300..100000)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The Lower Warning Limit for this input in the same units as for ipTHAValue."
::= { ipTHAThreshEntry 5 }
-- 1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1.6
ipTHALCL OBJECT-TYPE
SYNTAX INTEGER (-300..100000)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The Lower Critical Limit for this input in the same units as for ipTHAValue."
::= { ipTHAThreshEntry 6 }
-- 1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1.7
ipTHADeltaPos OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Rising rate of change threshold for ipTHAValue in 0.1 units per minute."
::= { ipTHAThreshEntry 7 }
-- 1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1.8
ipTHADeltaNeg OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Falling rate of change threshold for ipTHAValue in 0.1 units per minute."
::= { ipTHAThreshEntry 8 }
-- }}} End of ipTHAThreshTable
-- {{{ ipTHATrapEnTable
-- 1.3.6.1.4.1.3711.24.1.1.1.2.3.2
ipTHATrapEnTable OBJECT-TYPE
SYNTAX SEQUENCE OF IpTHATrapEnEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The table that controls trap enabling for all enabled inputs with analogue-type monitoring."
::= { ipTHATrapsCfg 2 }
-- 1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1
ipTHATrapEnEntry OBJECT-TYPE
SYNTAX IpTHATrapEnEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A conceptual row containing trap enabling information for one analogue-type input."
INDEX { ipTHATrapEnChan }
::= { ipTHATrapEnTable 1 }
IpTHATrapEnEntry ::= SEQUENCE {
ipTHATrapEnChan INTEGER,
ipTHATrapEnRS RowStatus,
ipTHAUCLTrapEn TruthValue,
ipTHAUWLTrapEn TruthValue,
ipTHALWLTrapEn TruthValue,
ipTHALCLTrapEn TruthValue,
ipTHADeltaPosTrapEn TruthValue,
ipTHADeltaNegTrapEn TruthValue
}
-- 1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1.1
ipTHATrapEnChan OBJECT-TYPE
SYNTAX INTEGER (0..48)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The input number."
::= { ipTHATrapEnEntry 1 }
-- 1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1.2
ipTHATrapEnRS OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The analogue-type input table row status."
::= { ipTHATrapEnEntry 2 }
-- 1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1.3
ipTHAUCLTrapEn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables and disables input UCL alarm traps."
::= { ipTHATrapEnEntry 3 }
-- 1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1.4
ipTHAUWLTrapEn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables and disables input UWL alarm traps."
::= { ipTHATrapEnEntry 4 }
-- 1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1.5
ipTHALWLTrapEn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables and disables input LWL alarm traps."
::= { ipTHATrapEnEntry 5 }
-- 1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1.6
ipTHALCLTrapEn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables and disables input LCL alarm traps."
::= { ipTHATrapEnEntry 6 }
-- 1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1.7
ipTHADeltaPosTrapEn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Trap enable flag for ipTHADeltaPos."
::= { ipTHATrapEnEntry 7 }
-- 1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1.8
ipTHADeltaNegTrapEn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Trap enable flag for ipTHADeltaNeg."
::= { ipTHATrapEnEntry 8 }
-- }}} End of ipTHATrapEnTable
-- {{{ ipTHATrapPerTable
-- 1.3.6.1.4.1.3711.24.1.1.1.2.3.3
ipTHATrapPerTable OBJECT-TYPE
SYNTAX SEQUENCE OF IpTHATrapPerEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The table that controls trap repetition for all enabled inputs with analogue-type monitoring."
::= { ipTHATrapsCfg 3 }
-- 1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1
ipTHATrapPerEntry OBJECT-TYPE
SYNTAX IpTHATrapPerEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A conceptual row containing trap repetition information for one analogue-type input."
INDEX { ipTHATrapPerChan }
::= { ipTHATrapPerTable 1 }
IpTHATrapPerEntry ::= SEQUENCE {
ipTHATrapPerChan INTEGER,
ipTHATrapPerRS RowStatus,
ipTHATrapUCLPer Unsigned32,
ipTHATrapUWLPer Unsigned32,
ipTHATrapLWLPer Unsigned32,
ipTHATrapLCLPer Unsigned32,
ipTHATrapDeltaPosPer Unsigned32,
ipTHATrapDeltaNegPer Unsigned32
}
-- 1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1.1
ipTHATrapPerChan OBJECT-TYPE
SYNTAX INTEGER (0..48)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The input number."
::= { ipTHATrapPerEntry 1 }
-- 1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1.2
ipTHATrapPerRS OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The table row status."
::= { ipTHATrapPerEntry 2 }
-- 1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1.3
ipTHATrapUCLPer OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Trap repetition period for ipTHATrapUCL in seconds. A value of 0 disables trap repetition."
::= { ipTHATrapPerEntry 3 }
-- 1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1.4
ipTHATrapUWLPer OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Trap repetition period for ipTHATrapUWL in seconds. A value of 0 disables trap repetition."
::= { ipTHATrapPerEntry 4 }
-- 1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1.5
ipTHATrapLWLPer OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Trap repetition period for ipTHATrapLWL in seconds. A value of 0 disables trap repetition."
::= { ipTHATrapPerEntry 5 }
-- 1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1.6
ipTHATrapLCLPer OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Trap repetition period for ipTHATrapLCL in seconds. A value of 0 disables trap repetition."
::= { ipTHATrapPerEntry 6 }
-- 1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1.7
ipTHATrapDeltaPosPer OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Trap repetition period for ipTHADeltaPos in seconds. A value of 0 disables trap repetition."
::= { ipTHATrapPerEntry 7 }
-- 1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1.8
ipTHATrapDeltaNegPer OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Trap repetition period for ipTHADeltaNeg in seconds. A value of 0 disables trap repetition."
::= { ipTHATrapPerEntry 8 }
-- }}} End of ipTHATrapPerTable
-- }}} End of ipTHATrapsCfg group
-- {{{ ipTHA traps
-- No traps for this branch
-- }}} End of ipTHA traps
-- }}} End of ipTHA
-- {{{ ipContact
-- 1.3.6.1.4.1.3711.24.1.1.1.3.1
ipContTable OBJECT-TYPE
SYNTAX SEQUENCE OF IpContEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table listing the parameters and data for all enabled inputs with contact-type monitoring."
::= { ipContact 1 }
-- 1.3.6.1.4.1.3711.24.1.1.1.3.1.1
ipContEntry OBJECT-TYPE
SYNTAX IpContEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A conceptual row containing information about one contact input."
INDEX { ipContChan }
::= { ipContTable 1 }
IpContEntry ::= SEQUENCE {
ipContChan INTEGER,
ipContRS RowStatus,
ipContName DisplayString,
ipContLocn DisplayString,
ipContAutoDetect TruthValue,
ipContNormState ContactState,
ipContCurrState InputContactState,
ipContTrigMode INTEGER,
ipContReset Unsigned32,
ipContTrapEn INTEGER,
ipContTrapPeriod INTEGER
}
-- 1.3.6.1.4.1.3711.24.1.1.1.3.1.1.1
ipContChan OBJECT-TYPE
SYNTAX INTEGER (0..48)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The input number."
::= { ipContEntry 1 }
-- 1.3.6.1.4.1.3711.24.1.1.1.3.1.1.2
ipContRS OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The contact input table row status."
::= { ipContEntry 2 }
-- 1.3.6.1.4.1.3711.24.1.1.1.3.1.1.3
ipContName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The name of this input"
::= { ipContEntry 3 }
-- 1.3.6.1.4.1.3711.24.1.1.1.3.1.1.4
ipContLocn OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A system-defined name for the physical location of this input, e.g. MCU."
::= { ipContEntry 4 }
-- 1.3.6.1.4.1.3711.24.1.1.1.3.1.1.5
ipContAutoDetect OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Indicates that the type of data this input is monitoring is selected automatically."
::= { ipContEntry 5 }
-- 1.3.6.1.4.1.3711.24.1.1.1.3.1.1.6
ipContNormState OBJECT-TYPE
SYNTAX ContactState
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The normal state for this contact."
::= { ipContEntry 6 }
-- 1.3.6.1.4.1.3711.24.1.1.1.3.1.1.7
ipContCurrState OBJECT-TYPE
SYNTAX InputContactState
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current state of this contact."
::= { ipContEntry 7 }
-- 1.3.6.1.4.1.3711.24.1.1.1.3.1.1.8
ipContTrigMode OBJECT-TYPE
SYNTAX INTEGER { positiveEdge(1), negativeEdge(2), level(3) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The contact trigger mode, level, +ve edge, -ve edge."
::= { ipContEntry 8 }
-- 1.3.6.1.4.1.3711.24.1.1.1.3.1.1.9
ipContReset OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Resets the contact after triggering in edge mode."
::= { ipContEntry 9 }
-- 1.3.6.1.4.1.3711.24.1.1.1.3.1.1.10
ipContTrapEn OBJECT-TYPE
SYNTAX INTEGER { critical(1), warning(2), information(3), disabled(255) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Configure contact input traps."
::= { ipContEntry 10 }
-- 1.3.6.1.4.1.3711.24.1.1.1.3.1.1.11
ipContTrapPeriod OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to 0 disables trap repetition, a value of 30 or higher sets the interval between traps in seconds"
::= { ipContEntry 11 }
-- {{{ ipContact traps
-- No traps for this branch
-- }}} End of ipContact traps
-- }}} End of ipContact
-- }}} End of ip group
-- {{{ outputs group
-- 1.3.6.1.4.1.3711.24.1.1.2.1
opEnable OBJECT IDENTIFIER ::= { outputs 1 }
-- {{{ opEnable group
-- 1.3.6.1.4.1.3711.24.1.1.2.1.1
opSelect OBJECT-TYPE
SYNTAX INTEGER (0..19)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Selects the channel to be enabled or disabled by opEnable.
A value of 0 selects no channel."
DEFVAL { 0 }
::= { opEnable 1 }
-- 1.3.6.1.4.1.3711.24.1.1.2.1.2
opInsert OBJECT-TYPE
SYNTAX EnableState
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the channel selected by opSelect -
causes an entry for that channel to be created or deleted in the relevant tables.
- Read behaviour is undefined."
::= { opEnable 2 }
-- }}} End of opEnable group
-- {{{ opTable
-- 1.3.6.1.4.1.3711.24.1.1.2.2
opTable OBJECT-TYPE
SYNTAX SEQUENCE OF OpEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table listing the parameters and data for all outputs."
::= { outputs 2 }
-- 1.3.6.1.4.1.3711.24.1.1.2.2.1
opEntry OBJECT-TYPE
SYNTAX OpEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A conceptual row containing information about one output."
INDEX { opChan }
::= { opTable 1 }
OpEntry ::= SEQUENCE {
opChan INTEGER,
opRS RowStatus,
opName DisplayString,
opLocn DisplayString,
opNormState RelayState,
opCurrState RelayState,
opOnDelTime Unsigned32,
opOffDelTime Unsigned32,
opBooleanEqn DisplayString,
opTrapEn INTEGER,
opTrapPeriod Unsigned32,
opControlState OutputControlState
}
-- 1.3.6.1.4.1.3711.24.1.1.2.2.1.1
opChan OBJECT-TYPE
SYNTAX INTEGER (0..19)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The output number."
::= { opEntry 1 }
-- 1.3.6.1.4.1.3711.24.1.1.2.2.1.2
opRS OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The contact input table row status."
::= { opEntry 2 }
-- 1.3.6.1.4.1.3711.24.1.1.2.2.1.3
opName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A user-defined name for this output."
::= { opEntry 3 }
-- 1.3.6.1.4.1.3711.24.1.1.2.2.1.4
opLocn OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A system-defined name for the physical location of this output, e.g. MCU."
::= { opEntry 4 }
-- 1.3.6.1.4.1.3711.24.1.1.2.2.1.5
opNormState OBJECT-TYPE
SYNTAX RelayState
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Sets or reads the required normal state of this output."
::= { opEntry 5 }
-- 1.3.6.1.4.1.3711.24.1.1.2.2.1.6
opCurrState OBJECT-TYPE
SYNTAX RelayState
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Reads the current state of this output."
::= { opEntry 6 }
-- 1.3.6.1.4.1.3711.24.1.1.2.2.1.7
opOnDelTime OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Sets the 'on' delay time for this output."
::= { opEntry 7 }
-- 1.3.6.1.4.1.3711.24.1.1.2.2.1.8
opOffDelTime OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Sets the 'off' delay time for this output."
::= { opEntry 8 }
-- 1.3.6.1.4.1.3711.24.1.1.2.2.1.9
opBooleanEqn OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Boolean equation string"
::= { opEntry 9 }
-- 1.3.6.1.4.1.3711.24.1.1.2.2.1.10
opTrapEn OBJECT-TYPE
SYNTAX INTEGER { critical(1), warning(2), information(3), disabled(255) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Configure output traps."
::= { opEntry 10 }
-- 1.3.6.1.4.1.3711.24.1.1.2.2.1.11
opTrapPeriod OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to 0 disables trap repetition, a value of 30 or higher sets the interval between traps in seconds"
::= { opEntry 11 }
-- 1.3.6.1.4.1.3711.24.1.1.2.2.1.12
opControlState OBJECT-TYPE
SYNTAX OutputControlState
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Reads the current control state of an output."
::= { opEntry 12 }
-- }}} End of opTable
-- {{{ outputs traps
-- No traps for this branch
-- }}} End of outputs traps
-- }}} End of outputs group
-- {{{ keypads group
-- 1.3.6.1.4.1.3711.24.1.1.4.1
kpEnable OBJECT IDENTIFIER ::= { keypads 1 }
-- {{{ kpEnable group
-- 1.3.6.1.4.1.3711.24.1.1.4.1.1
kpSelect OBJECT-TYPE
SYNTAX INTEGER (0..24)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Selects the keypad to be enabled or disabled by kpEnable.
A value of 0 selects no keypad."
DEFVAL { 0 }
::= { kpEnable 1 }
-- 1.3.6.1.4.1.3711.24.1.1.4.1.2
kpInsert OBJECT-TYPE
SYNTAX KeypadEnableState
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the keypad selected by kpSelect -
causes an entry for that keypad to be created or deleted in the relevant tables.
- Read behaviour is undefined."
::= { kpEnable 2 }
-- }}} End of kpEnable group
-- {{{ kpTable
-- 1.3.6.1.4.1.3711.24.1.1.4.2
kpCtlTable OBJECT-TYPE
SYNTAX SEQUENCE OF KpCtlEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table listing the parameters and data for the keypads."
::= { keypads 2 }
-- 1.3.6.1.4.1.3711.24.1.1.4.2.1
kpCtlEntry OBJECT-TYPE
SYNTAX KpCtlEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A conceptual row containing information about one keypad."
INDEX { kpNumber }
::= { kpCtlTable 1 }
KpCtlEntry ::= SEQUENCE {
kpNumber INTEGER,
kpRS RowStatus,
kpManufacturer DisplayString,
kpName DisplayString,
kpDoorLatchTimeOut Unsigned32,
kpRtnToStndbyTimeOut INTEGER,
kpEntryCodeValid TruthValue,
kpDoorOpenTimeOut INTEGER,
kpRemoteDoorOpen TruthValue,
kpInUseTrapEn INTEGER
}
-- 1.3.6.1.4.1.3711.24.1.1.4.2.1.1
kpNumber OBJECT-TYPE
SYNTAX INTEGER (1..2)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The keypad number."
::= { kpCtlEntry 1 }
-- 1.3.6.1.4.1.3711.24.1.1.4.2.1.2
kpRS OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The keypad table row status."
::= { kpCtlEntry 2 }
-- 1.3.6.1.4.1.3711.24.1.1.4.2.1.3
kpManufacturer OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The name of the manufacturer of the keypad."
::= { kpCtlEntry 3 }
-- 1.3.6.1.4.1.3711.24.1.1.4.2.1.4
kpName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A name identifying the keypad."
::= { kpCtlEntry 4 }
-- 1.3.6.1.4.1.3711.24.1.1.4.2.1.5
kpDoorLatchTimeOut OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Time-out value in seconds for which the door latch is held open."
::= { kpCtlEntry 5 }
-- 1.3.6.1.4.1.3711.24.1.1.4.2.1.6
kpRtnToStndbyTimeOut OBJECT-TYPE
SYNTAX INTEGER (0..99)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Time-out value in seconds for Return to Standby Mode"
::= { kpCtlEntry 6 }
-- 1.3.6.1.4.1.3711.24.1.1.4.2.1.7
kpEntryCodeValid OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Set if previous keypad entry was valid."
::= { kpCtlEntry 7 }
-- 1.3.6.1.4.1.3711.24.1.1.4.2.1.8
kpDoorOpenTimeOut OBJECT-TYPE
SYNTAX INTEGER (0..99)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Time-out value in seconds for Door Open."
::= { kpCtlEntry 8 }
-- 1.3.6.1.4.1.3711.24.1.1.4.2.1.9
kpRemoteDoorOpen OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to open the door."
::= { kpCtlEntry 9 }
-- 1.3.6.1.4.1.3711.24.1.1.4.2.1.10
kpInUseTrapEn OBJECT-TYPE
SYNTAX INTEGER { critical(1), warning(2), information(3), disabled(255) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"'keypad in use' trap enable"
::= { kpCtlEntry 10 }
-- }}} End of kpTable
-- {{{ keypads traps
-- No traps for this branch
-- }}} End of keypads traps
-- }}} End of keypads group
-- {{{ acus group
-- 1.3.6.1.4.1.3711.24.1.1.5.1
acuEnable OBJECT IDENTIFIER ::= { acus 1 }
-- {{{ acuEnable group
-- 1.3.6.1.4.1.3711.24.1.1.5.1.1
acuSelect OBJECT-TYPE
SYNTAX INTEGER (0..24)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Selects the ACU to be enabled or disabled by acuEnable.
A value of 0 selects no ACU."
DEFVAL { 0 }
::= { acuEnable 1 }
-- 1.3.6.1.4.1.3711.24.1.1.5.1.2
acuInsert OBJECT-TYPE
SYNTAX EnableState
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the ACU selected by acuSelect -
causes an entry for that ACU to be created or deleted in the relevant tables.
- Read behaviour is undefined."
::= { acuEnable 2 }
-- }}} End of acuEnable group
-- {{{ acuTable
-- 1.3.6.1.4.1.3711.24.1.1.5.2
acuCtlTable OBJECT-TYPE
SYNTAX SEQUENCE OF AcuCtlEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table listing the parameters and data for the ACUs."
::= { acus 2 }
-- 1.3.6.1.4.1.3711.24.1.1.5.2.1
acuCtlEntry OBJECT-TYPE
SYNTAX AcuCtlEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A conceptual row containing information about one ACU."
INDEX { acuNumber }
::= { acuCtlTable 1 }
AcuCtlEntry ::= SEQUENCE {
acuNumber INTEGER,
acuCtlRS RowStatus,
acuManufacturer DisplayString,
acuName DisplayString,
acuDoorLatchTimeOut Unsigned32,
acuRtnToStndbyTimeOut INTEGER,
acuEntryCodeValid TruthValue,
acuDoorOpenTimeOut INTEGER,
acuRemoteDoorOpen TruthValue,
acuInUseTrapEn INTEGER,
acuType DisplayString,
acuAlarms Unsigned32,
acuLastCode DisplayString
}
-- 1.3.6.1.4.1.3711.24.1.1.5.2.1.1
acuNumber OBJECT-TYPE
SYNTAX INTEGER (1..6)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The ACU number."
::= { acuCtlEntry 1 }
-- 1.3.6.1.4.1.3711.24.1.1.5.2.1.2
acuCtlRS OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The ACU table row status."
::= { acuCtlEntry 2 }
-- 1.3.6.1.4.1.3711.24.1.1.5.2.1.3
acuManufacturer OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The name of the manufacturer of the ACU."
::= { acuCtlEntry 3 }
-- 1.3.6.1.4.1.3711.24.1.1.5.2.1.4
acuName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A name identifying the ACU."
::= { acuCtlEntry 4 }
-- 1.3.6.1.4.1.3711.24.1.1.5.2.1.5
acuDoorLatchTimeOut OBJECT-TYPE
SYNTAX Unsigned32 (0..999)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Time-out value in seconds for which the door latch is held open."
::= { acuCtlEntry 5 }
-- 1.3.6.1.4.1.3711.24.1.1.5.2.1.6
acuRtnToStndbyTimeOut OBJECT-TYPE
SYNTAX INTEGER (0..999)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Time-out value in seconds for Return to Standby Mode"
::= { acuCtlEntry 6 }
-- 1.3.6.1.4.1.3711.24.1.1.5.2.1.7
acuEntryCodeValid OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Set if previous ACU entry was valid."
::= { acuCtlEntry 7 }
-- 1.3.6.1.4.1.3711.24.1.1.5.2.1.8
acuDoorOpenTimeOut OBJECT-TYPE
SYNTAX INTEGER (0..3600)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Time-out value in seconds for Door Open."
::= { acuCtlEntry 8 }
-- 1.3.6.1.4.1.3711.24.1.1.5.2.1.9
acuRemoteDoorOpen OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to open the door."
::= { acuCtlEntry 9 }
-- 1.3.6.1.4.1.3711.24.1.1.5.2.1.10
acuInUseTrapEn OBJECT-TYPE
SYNTAX INTEGER { critical(1), warning(2), information(3), disabled(255) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"'ACU in use' trap enable"
::= { acuCtlEntry 10 }
-- 1.3.6.1.4.1.3711.24.1.1.5.2.1.11
acuType OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A string identifying the ACU type."
::= { acuCtlEntry 11 }
-- 1.3.6.1.4.1.3711.24.1.1.5.2.1.12
acuAlarms OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A bit field flagging ACU alarms."
::= { acuCtlEntry 12 }
-- 1.3.6.1.4.1.3711.24.1.1.5.2.1.13
acuLastCode OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The last key code read from the ACU. After this is consumed, write an empty string to clear the contents."
::= { acuCtlEntry 13 }
-- }}} End of acuTable
-- {{{ acus traps
-- No traps for this branch
-- }}} End of acus traps
-- }}} End of acus group
-- {{{ access group
-- 1.3.6.1.4.1.3711.24.1.1.6.1
accUserCtl OBJECT IDENTIFIER ::= { access 1 }
-- {{{ accUserCtl group
-- 1.3.6.1.4.1.3711.24.1.1.6.1.1
accUserInstance OBJECT-TYPE
SYNTAX INTEGER (0..20)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A value of 0 causes an access user to be created in the relevant tables.
A non-zero value causes the nominated access user table entries to be deleted."
::= { accUserCtl 1 }
-- {{{ accUserTable
-- 1.3.6.1.4.1.3711.24.1.1.6.1.2
accUserTable OBJECT-TYPE
SYNTAX SEQUENCE OF AccUserEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table controlling the access users."
::= { accUserCtl 2 }
-- 1.3.6.1.4.1.3711.24.1.1.6.1.2.1
accUserEntry OBJECT-TYPE
SYNTAX AccUserEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A conceptual row containing information about one ACU user."
INDEX { accUserNumber }
::= { accUserTable 1 }
AccUserEntry ::= SEQUENCE {
accUserNumber Unsigned32,
accUserRS RowStatus,
accUserName DisplayString,
accUserCode OCTET STRING,
accUserPrivileges DisplayString,
accUserExpires DisplayString
}
-- 1.3.6.1.4.1.3711.24.1.1.6.1.2.1.1
accUserNumber OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The the access user-table entry number."
::= { accUserEntry 1 }
-- 1.3.6.1.4.1.3711.24.1.1.6.1.2.1.2
accUserRS OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The access user table row status."
::= { accUserEntry 2 }
-- 1.3.6.1.4.1.3711.24.1.1.6.1.2.1.3
accUserName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A name identifying the access user."
::= { accUserEntry 3 }
-- 1.3.6.1.4.1.3711.24.1.1.6.1.2.1.4
accUserCode OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..15))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The user's access code."
::= { accUserEntry 4 }
-- 1.3.6.1.4.1.3711.24.1.1.6.1.2.1.5
accUserPrivileges OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The ACUs and keypads that the user is allowed to gain access through - comma-separated numerical strings."
::= { accUserEntry 5 }
-- 1.3.6.1.4.1.3711.24.1.1.6.1.2.1.6
accUserExpires OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A text string which specifies when the access code in the row expires. The format is defined by the application."
::= { accUserEntry 6 }
-- }}} End of accUserTable
-- 1.3.6.1.4.1.3711.24.1.1.6.1.3
accUserSetup OBJECT-TYPE
SYNTAX OCTET STRING
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A free form octet string for programming accUserTable. The format is defined by the application."
::= { accUserCtl 3 }
-- 1.3.6.1.4.1.3711.24.1.1.6.1.4
accUserCodeLen OBJECT-TYPE
SYNTAX INTEGER (1..15)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A value of the PIN code length"
::= { accUserCtl 4 }
-- }}} End of accUserCtl group
-- {{{ pdus group
-- 1.3.6.1.4.1.3711.24.1.1.7.1
pduCommon OBJECT IDENTIFIER ::= { pdus 1 }
-- 1.3.6.1.4.1.3711.24.1.1.7.2
pduOutlets OBJECT IDENTIFIER ::= { pdus 2 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3
pduMonitor OBJECT IDENTIFIER ::= { pdus 3 }
-- 1.3.6.1.4.1.3711.24.1.1.7.4
pduGangs OBJECT IDENTIFIER ::= { pdus 4 }
-- {{{ pduCommon group
-- 1.3.6.1.4.1.3711.24.1.1.7.1.1
pdusEnable OBJECT IDENTIFIER ::= { pduCommon 1 }
-- {{{ pduEnable group
-- 1.3.6.1.4.1.3711.24.1.1.7.1.1.1
pduSelect OBJECT-TYPE
SYNTAX INTEGER (0..24)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Selects the PDU to be enabled or disabled by pduInsert.
A value of 0 selects no PDU."
DEFVAL { 0 }
::= { pdusEnable 1 }
-- 1.3.6.1.4.1.3711.24.1.1.7.1.1.2
pduInsert OBJECT-TYPE
SYNTAX EnableState
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the PDU selected by pduSelect -
causes an entry for that PDU to be created or deleted in the relevant tables.
- Read behaviour is undefined."
::= { pdusEnable 2 }
-- }}} End of pduEnable group
-- {{{ pduTable
-- 1.3.6.1.4.1.3711.24.1.1.7.1.2
pduTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table containing information about each enabled PDU."
::= { pduCommon 2 }
-- 1.3.6.1.4.1.3711.24.1.1.7.1.2.1
pduEntry OBJECT-TYPE
SYNTAX PduEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A conceptual row containing information about one PDU."
INDEX { pduNumber }
::= { pduTable 1 }
PduEntry ::= SEQUENCE {
pduNumber Unsigned32,
pduRS RowStatus,
pduName DisplayString,
pduOutEn TruthValue,
pduMonEn TruthValue,
pduCommsFail INTEGER,
pduType INTEGER,
pduMode INTEGER,
pduNumControl Unsigned32,
pduOutletMonMode INTEGER,
pduNumOutlets Unsigned32,
pduFwVersCPU DisplayString,
pduFwVersMeter DisplayString,
pduNumOfCctBrks INTEGER
}
-- 1.3.6.1.4.1.3711.24.1.1.7.1.2.1.1
pduNumber OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU number."
::= { pduEntry 1 }
-- 1.3.6.1.4.1.3711.24.1.1.7.1.2.1.2
pduRS OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU table row status."
::= { pduEntry 2 }
-- 1.3.6.1.4.1.3711.24.1.1.7.1.2.1.3
pduName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A string identifying the PDU."
::= { pduEntry 3}
-- 1.3.6.1.4.1.3711.24.1.1.7.1.2.1.4
pduOutEn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables/disables PDU power outlet control - causes an entry for outlets to be created in each relevant PDU table."
::= {pduEntry 4 }
-- 1.3.6.1.4.1.3711.24.1.1.7.1.2.1.5
pduMonEn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables/disables PDU power monitoring - causes an entry for monitoring to be created in each relevant PDU table."
::= {pduEntry 5 }
-- 1.3.6.1.4.1.3711.24.1.1.7.1.2.1.6
pduCommsFail OBJECT-TYPE
SYNTAX INTEGER { commsGood(1), commsFailed(2), commsBadData(3)}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates comms. status for the PDU."
::= {pduEntry 6 }
-- 1.3.6.1.4.1.3711.24.1.1.7.1.2.1.7
pduType OBJECT-TYPE
SYNTAX INTEGER { rs232PduMk1(1),
rs232PduTpt(2),
rs485PduTpt(3),
rs232CLAmp(4),
rs485CLAmp(5),
rs232PduMk2(6),
rs485PduMk2(7),
rs485PduMk3(8),
rs232G5(9),
virtual(253),
none(254),
unknown(255) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates the type of device connected."
::= {pduEntry 7 }
-- 1.3.6.1.4.1.3711.24.1.1.7.1.2.1.8
pduMode OBJECT-TYPE
SYNTAX INTEGER { singlePhase(1),
twoPhase(2),
threePhaseStar(3),
threePhaseDelta(4),
aggregate(253),
none(254),
unknown(255) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates the phase circuit topology."
::= {pduEntry 8 }
-- 1.3.6.1.4.1.3711.24.1.1.7.1.2.1.9
pduNumControl OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates the number of controlled outlets."
::= {pduEntry 9 }
-- 1.3.6.1.4.1.3711.24.1.1.7.1.2.1.10
pduOutletMonMode OBJECT-TYPE
SYNTAX INTEGER { currentOnly(1),
allParameters(2),
none(254),
unknown(255)}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates the monitor mode."
::= {pduEntry 10 }
-- 1.3.6.1.4.1.3711.24.1.1.7.1.2.1.11
pduNumOutlets OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates the number of monitored outlets."
::= {pduEntry 11 }
pduFwVersCPU OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A string identifying the PDU processor firmware version."
::= { pduEntry 12}
pduFwVersMeter OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A string identifying the PDU meter firmware version."
::= { pduEntry 13}
-- 1.3.6.1.4.1.3711.24.1.1.7.1.2.1.14
pduNumOfCctBrks OBJECT-TYPE
SYNTAX INTEGER (0..9)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Indicates the number of monitored branch circuits."
::= { pduEntry 14 }
-- }}} End of pduTable
pdusMinMaxPeriod OBJECT-TYPE
SYNTAX INTEGER { periodNull(0), period15Minutes(15), period30Minutes(30), period60Minutes(60) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Configures the polling period for the PDU max/min values."
::= { pduCommon 3 }
-- }}} End of pduCommon group
-- {{{ pduOutlets group
-- 1.3.6.1.4.1.3711.24.1.1.7.2.1
pduOutAll OBJECT IDENTIFIER ::= { pduOutlets 1 }
-- {{{ pduOutAll group
-- 1.3.6.1.4.1.3711.24.1.1.7.2.1.1
pduOutCycleAll OBJECT-TYPE
SYNTAX INTEGER { up(1), down(2) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Sets the required state of all power outlets on all connected PDUs."
::= { pduOutAll 1 }
-- 1.3.6.1.4.1.3711.24.1.1.7.2.1.2
pduOutCycleAllPwd OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Controls access to setting the required state of all power outlets on all connected PDUs."
::= { pduOutAll 2 }
-- 1.3.6.1.4.1.3711.24.1.1.7.2.1.3
pduOutCycleAllAbort OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Abort command for pduOutCycleAll."
::= { pduOutAll 3 }
-- 1.3.6.1.4.1.3711.24.1.1.7.2.1.4
pduOutGlobalCycleDelay OBJECT-TYPE
SYNTAX Unsigned32 (1 .. 60)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Sets the delay period for pduOutCycleAll and pduOutCycle commands before they start to execute."
::= { pduOutAll 4 }
-- 1.3.6.1.4.1.3711.24.1.1.7.2.1.5
pduOutGlobalRebootTime OBJECT-TYPE
SYNTAX Unsigned32 (5..300)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Sets the off to on delay period for a pdu outlet reboot."
::= { pduOutAll 5 }
-- 1.3.6.1.4.1.3711.24.1.1.7.2.1.6
pduOutGlobalCycleAbortTime OBJECT-TYPE
SYNTAX Unsigned32 (0..60)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Time delay to abort power outlet setting task."
::= { pduOutAll 6 }
-- }}} End of pduOutAll group
-- {{{ pduOutTable
-- 1.3.6.1.4.1.3711.24.1.1.7.2.2
pduOutCmnTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduOutCmnEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table containing information about the power outlets of all PDUs enabled for outlet control."
::= { pduOutlets 2 }
-- 1.3.6.1.4.1.3711.24.1.1.7.2.2.1
pduOutCmnEntry OBJECT-TYPE
SYNTAX PduOutCmnEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A conceptual row containing information about the power outlets of one PDU."
INDEX { pduOutCmnPduNumber }
::= { pduOutCmnTable 1 }
PduOutCmnEntry ::= SEQUENCE {
pduOutCmnPduNumber Unsigned32,
pduOutCmnRS RowStatus,
pduNumOfOutlets Unsigned32,
pduOutCycle INTEGER,
pduOutCyclePwd DisplayString,
pduOutCycleAbortTask Unsigned32,
pduOutCycleAbortTime Unsigned32
}
-- 1.3.6.1.4.1.3711.24.1.1.7.2.2.1.1
pduOutCmnPduNumber OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU number."
::= { pduOutCmnEntry 1 }
-- 1.3.6.1.4.1.3711.24.1.1.7.2.2.1.2
pduOutCmnRS OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU table row status."
::= { pduOutCmnEntry 2 }
-- 1.3.6.1.4.1.3711.24.1.1.7.2.2.1.3
pduNumOfOutlets OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of switchable outlets on the PDU - determines the number of entries to be created in the outlet table for the relevant PDU."
::= { pduOutCmnEntry 3 }
-- 1.3.6.1.4.1.3711.24.1.1.7.2.2.1.4
pduOutCycle OBJECT-TYPE
SYNTAX INTEGER { up(1), down(2), unknown(255) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Sets the required state of all power outlets on the PDU."
::= { pduOutCmnEntry 4 }
-- 1.3.6.1.4.1.3711.24.1.1.7.2.2.1.5
pduOutCyclePwd OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Password controling access to setting the required state of all power outlets on the PDU."
::= { pduOutCmnEntry 5 }
-- 1.3.6.1.4.1.3711.24.1.1.7.2.2.1.6
pduOutCycleAbortTask OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Abort power outlet setting task."
::= { pduOutCmnEntry 6 }
-- 1.3.6.1.4.1.3711.24.1.1.7.2.2.1.7
pduOutCycleAbortTime OBJECT-TYPE
SYNTAX Unsigned32 (0..60)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Time delay to abort power outlet setting task."
::= { pduOutCmnEntry 7 }
-- }}} End of pduOutCmnTable
-- {{{ pduOutTable
-- 1.3.6.1.4.1.3711.24.1.1.7.2.3
pduOutTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduOutEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table listing the states and descriptions for each outlet on the PDU."
::= { pduOutlets 3 }
-- 1.3.6.1.4.1.3711.24.1.1.7.2.3.1
pduOutEntry OBJECT-TYPE
SYNTAX PduOutEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A row containing information about one PDU outlet."
INDEX { pduOutPduNumber, pduOutNumber }
::= { pduOutTable 1 }
PduOutEntry ::= SEQUENCE {
pduOutPduNumber Unsigned32,
pduOutNumber Unsigned32,
pduOutRS RowStatus,
pduOutName DisplayString,
pduOutOn INTEGER,
pduOutPwd DisplayString,
pduOutCycleDelay Unsigned32,
pduOutRebootPeriod Unsigned32,
pduOutRMSAmpsValue Unsigned32,
pduOutRMSAmpsSurge Unsigned32,
pduOutRMSAmpsPeak Unsigned32,
pduOutRMSAmpsPkRst Unsigned32,
pduOutMeanKVAValue Unsigned32,
pduOutKWHrValue Unsigned32,
pduOutPFactorValue Unsigned32,
pduOutRMSAmpsUTL INTEGER,
pduOutRMSAmpsLTL INTEGER,
pduOutRMSAmpsUTLTrapEn TruthValue,
pduOutRMSAmpsLTLTrapEn TruthValue,
pduOutRMSAmpsUTLTrapPer Unsigned32,
pduOutRMSAmpsLTLTrapPer Unsigned32
}
-- 1.3.6.1.4.1.3711.24.1.1.7.2.3.1.1
pduOutPduNumber OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU number on which the outlet resides."
::= { pduOutEntry 1 }
-- 1.3.6.1.4.1.3711.24.1.1.7.2.3.1.2
pduOutNumber OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The outlet number."
::= { pduOutEntry 2 }
-- 1.3.6.1.4.1.3711.24.1.1.7.2.3.1.3
pduOutRS OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU table row status."
::= { pduOutEntry 3 }
-- 1.3.6.1.4.1.3711.24.1.1.7.2.3.1.4
pduOutName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A name identifying the outlet."
::= { pduOutEntry 4 }
-- 1.3.6.1.4.1.3711.24.1.1.7.2.3.1.5
pduOutOn OBJECT-TYPE
SYNTAX INTEGER { on(1), off(2), reboot(3), unknown(4), failedStuck(5)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The current state for this outlet."
::= { pduOutEntry 5 }
-- 1.3.6.1.4.1.3711.24.1.1.7.2.3.1.6
pduOutPwd OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The password for this outlet."
::= { pduOutEntry 6 }
-- 1.3.6.1.4.1.3711.24.1.1.7.2.3.1.7
pduOutCycleDelay OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The on/off delay for this outlet in seconds."
::= { pduOutEntry 7 }
-- 1.3.6.1.4.1.3711.24.1.1.7.2.3.1.8
pduOutRebootPeriod OBJECT-TYPE
SYNTAX Unsigned32 (5..300)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The pduOutOn reboot off period for this outlet in seconds."
::= { pduOutEntry 8 }
-- 1.3.6.1.4.1.3711.24.1.1.7.2.3.1.9
pduOutRMSAmpsValue OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"RMS current value at the outlet in 0.1 Amps"
::= { pduOutEntry 9 }
-- 1.3.6.1.4.1.3711.24.1.1.7.2.3.1.10
pduOutRMSAmpsSurge OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Maximum value of pduOutRMSAmpsValue for another outlet to be switched on in 0.1 Amps"
::= { pduOutEntry 10 }
-- 1.3.6.1.4.1.3711.24.1.1.7.2.3.1.11
pduOutRMSAmpsPeak OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Maximum value of pduOutRMSAmpsValue since reset in 0.1 Amps"
::= { pduOutEntry 11 }
-- 1.3.6.1.4.1.3711.24.1.1.7.2.3.1.12
pduOutRMSAmpsPkRst OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Resets value of pduOutRMSAmpsPeak to current value of pduOutRMSAmpsValue"
::= { pduOutEntry 12 }
-- 1.3.6.1.4.1.3711.24.1.1.7.2.3.1.13
pduOutMeanKVAValue OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Mean kVA value at the outlet in 0.1 kVA"
::= { pduOutEntry 13 }
-- 1.3.6.1.4.1.3711.24.1.1.7.2.3.1.14
pduOutKWHrValue OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"kWhr value at the outlet in 0.1 kWhr"
::= { pduOutEntry 14 }
-- 1.3.6.1.4.1.3711.24.1.1.7.2.3.1.15
pduOutPFactorValue OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Power factor value at the outlet in 0.01 units"
::= { pduOutEntry 15 }
-- 1.3.6.1.4.1.3711.24.1.1.7.2.3.1.16
pduOutRMSAmpsUTL OBJECT-TYPE
SYNTAX INTEGER (-10..500)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Upper threshold of pduOutRMSAmpsValue in 0.1 Amps"
::= { pduOutEntry 16 }
-- 1.3.6.1.4.1.3711.24.1.1.7.2.3.1.17
pduOutRMSAmpsLTL OBJECT-TYPE
SYNTAX INTEGER (-10..500)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Lower threshold of pduOutRMSAmpsValue in 0.1 Amps"
::= { pduOutEntry 17 }
-- 1.3.6.1.4.1.3711.24.1.1.7.2.3.1.18
pduOutRMSAmpsUTLTrapEn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Trap enable flag for pduOutRMSAmpsUTL."
::= { pduOutEntry 18 }
-- 1.3.6.1.4.1.3711.24.1.1.7.2.3.1.19
pduOutRMSAmpsLTLTrapEn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Trap enable flag for pduOutRMSAmpsLTL."
::= { pduOutEntry 19 }
-- 1.3.6.1.4.1.3711.24.1.1.7.2.3.1.20
pduOutRMSAmpsUTLTrapPer OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Trap repetition period for pduOutRMSAmpsUTL."
::= { pduOutEntry 20 }
-- 1.3.6.1.4.1.3711.24.1.1.7.2.3.1.21
pduOutRMSAmpsLTLTrapPer OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Trap repetition period for pduOutRMSAmpsLTL."
::= { pduOutEntry 21 }
-- }}} End of pduOutEntry
-- }}} End of pduOut group
-- {{{ pduMonitor group
-- {{{ pduMonTable
-- 1.3.6.1.4.1.3711.24.1.1.7.3.1
pduMonTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduMonEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table containing monitor information for all PDUs enabled for monitoring."
::= { pduMonitor 1 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.1.1
pduMonEntry OBJECT-TYPE
SYNTAX PduMonEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A conceptual row containing monitor information for one PDU."
INDEX { pduMonPduNumber }
::= { pduMonTable 1 }
PduMonEntry ::= SEQUENCE {
pduMonPduNumber Unsigned32,
pduMonRS RowStatus,
pduRMSVoltsValue INTEGER,
pduRMSAmpsValue INTEGER,
pduTotalEnergyValue INTEGER,
pduMeanKVAValue INTEGER,
pduMeanKWattsValue INTEGER,
pduPwrFactorValue INTEGER,
pduPwrSupplyFreq INTEGER,
pduPhaseVoltsValue INTEGER,
pduPhaseAmpsValue INTEGER,
pduPhaseEnergyValue INTEGER,
pduPhaseKVAValue INTEGER,
pduPhaseKWattsValue INTEGER,
pduPhasePwrFactorValue INTEGER,
pduCircuitName DisplayString,
pduCctKVAMax INTEGER,
pduCctKVAMaxTime DisplayString,
pduCctKVAMin INTEGER,
pduCctKVAMinTime DisplayString,
pduCctAmpsMax INTEGER,
pduCctAmpsMaxTime DisplayString,
pduCctAmpsMin INTEGER,
pduCctAmpsMinTime DisplayString,
pduCctStatSagSet TruthValue,
pduCctStatSagCount Unsigned32,
pduCctStatSagTime DisplayString,
pduCctStatPkVoltsSet TruthValue,
pduCctStatPkVoltsCount Unsigned32,
pduCctStatPkVoltsTime DisplayString,
pduCctStatPwrLossSet TruthValue,
pduCctStatPwrLossCount Unsigned32,
pduCctStatPwrLossTime DisplayString,
pduCctPermKVAMax INTEGER,
pduCctPermKVAMaxTime DisplayString,
pduCctPermAmpsMax INTEGER,
pduCctPermAmpsMaxTime DisplayString
}
-- 1.3.6.1.4.1.3711.24.1.1.7.3.1.1.1
pduMonPduNumber OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU number."
::= { pduMonEntry 1 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.1.1.2
pduMonRS OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU table row status."
::= { pduMonEntry 2 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.1.1.3
pduRMSVoltsValue OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"RMS Volts across load in Volts"
::= { pduMonEntry 3 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.1.1.4
pduRMSAmpsValue OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"RMS current through load in 0.1 Amps"
::= { pduMonEntry 4 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.1.1.5
pduTotalEnergyValue OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Total energy supplied to load in 0.1 kWh"
::= { pduMonEntry 5 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.1.1.6
pduMeanKVAValue OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Kilo Volt-Amperes supplied to load in 0.1 kVA"
::= { pduMonEntry 6 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.1.1.7
pduMeanKWattsValue OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Kilo Watts supplied to load in 0.1 kW"
::= { pduMonEntry 7 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.1.1.8
pduPwrFactorValue OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Power factor of load in 0.01"
::= { pduMonEntry 8 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.1.1.9
pduPwrSupplyFreq OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Power supply frequency in 0.1Hz"
::= { pduMonEntry 9 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.1.1.10
pduPhaseVoltsValue OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"RMS Volts across phase in Volts"
::= { pduMonEntry 10 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.1.1.11
pduPhaseAmpsValue OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"RMS current supplied by phase in 0.1 Amps"
::= { pduMonEntry 11 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.1.1.12
pduPhaseEnergyValue OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Total energy supplied by phase in 0.1 kWh"
::= { pduMonEntry 12 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.1.1.13
pduPhaseKVAValue OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Apparent power supplied by phase in 0.1 kVA"
::= { pduMonEntry 13 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.1.1.14
pduPhaseKWattsValue OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"True power supplied by phase in 0.1 kW"
::= { pduMonEntry 14 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.1.1.15
pduPhasePwrFactorValue OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Power factor of phase in 0.01"
::= { pduMonEntry 15 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.1.1.16
pduCircuitName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A string identifying the circuit."
::= { pduMonEntry 16}
pduCctKVAMax OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Maximum apparent power in circuit for measurment period in 0.1 kVA"
::= { pduMonEntry 17 }
pduCctKVAMaxTime OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Timestamp for maximum apparent power in circuit"
::= { pduMonEntry 18 }
pduCctKVAMin OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Minimum apparent power in circuit for measurment period in 0.1 kVA"
::= { pduMonEntry 19 }
pduCctKVAMinTime OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Timestamp for mniimum apparent power in circuit"
::= { pduMonEntry 20 }
pduCctAmpsMax OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Maximum current in circuit for measurment period in 0.1 kVA"
::= { pduMonEntry 21 }
pduCctAmpsMaxTime OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Timestamp for maximum current in circuit"
::= { pduMonEntry 22 }
pduCctAmpsMin OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Minimum current in circuit for measurment period in 0.1 kVA"
::= { pduMonEntry 23 }
pduCctAmpsMinTime OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Timestamp for minimum current in circuit"
::= { pduMonEntry 24 }
pduCctStatSagSet OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Sag status is set in this circuit"
::= { pduMonEntry 25 }
pduCctStatSagCount OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Sag status count in this circuit"
::= { pduMonEntry 26 }
pduCctStatSagTime OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Timestamp for sag status in this circuit"
::= { pduMonEntry 27 }
pduCctStatPkVoltsSet OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Peak Volts status is set in this circuit"
::= { pduMonEntry 28 }
pduCctStatPkVoltsCount OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Peak Volts status count in this circuit"
::= { pduMonEntry 29 }
pduCctStatPkVoltsTime OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Timestamp for Peak Volts status in this circuit"
::= { pduMonEntry 30 }
pduCctStatPwrLossSet OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Power Loss status is set in this circuit"
::= { pduMonEntry 31 }
pduCctStatPwrLossCount OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Power Loss status count in this circuit"
::= { pduMonEntry 32 }
pduCctStatPwrLossTime OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Timestamp for Power Loss status in this circuit"
::= { pduMonEntry 33 }
pduCctPermKVAMax OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Maximum apparent power in circuit since last reset in 0.1 kVA"
::= { pduMonEntry 34 }
pduCctPermKVAMaxTime OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Timestamp for maximum apparent power in circuit since last reset"
::= { pduMonEntry 35 }
pduCctPermAmpsMax OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Minimum apparent power in circuit since last reset in 0.1 kVA"
::= { pduMonEntry 36 }
pduCctPermAmpsMaxTime OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Timestamp for minimum apparent power in circuit since last reset"
::= { pduMonEntry 37 }
-- }}} End of pduMonTable
-- {{{ pduTrapThreshTable
-- 1.3.6.1.4.1.3711.24.1.1.7.3.2
pduTrapThreshTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduTrapThreshEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table containing information about the trap threshold values for all PDUs enabled for monitoring."
::= { pduMonitor 2 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.2.1
pduTrapThreshEntry OBJECT-TYPE
SYNTAX PduTrapThreshEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A conceptual row containing information about the trap threshold values for one PDU."
INDEX { pduTrapThreshPduNumber }
::= { pduTrapThreshTable 1 }
PduTrapThreshEntry ::= SEQUENCE {
pduTrapThreshPduNumber Unsigned32,
pduTrapThreshRS RowStatus,
pduRMSVoltsUCL INTEGER,
pduRMSVoltsUWL INTEGER,
pduRMSVoltsLWL INTEGER,
pduRMSVoltsLCL INTEGER,
pduRMSAmpsUCL INTEGER,
pduRMSAmpsUWL INTEGER,
pduRMSAmpsLWL INTEGER,
pduRMSAmpsLCL INTEGER,
pduEnergyUCL Unsigned32,
pduEnergyUWL Unsigned32,
pduMeanKVAUCL INTEGER,
pduMeanKVAUWL INTEGER,
pduMeanKVALWL INTEGER,
pduMeanKVALCL INTEGER,
pduMeanKWattsUCL INTEGER,
pduMeanKWattsUWL INTEGER,
pduMeanKWattsLWL INTEGER,
pduMeanKWattsLCL INTEGER,
pduPwrFactorUTL INTEGER,
pduPwrFactorLTL INTEGER
}
-- 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.1
pduTrapThreshPduNumber OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU number."
::= { pduTrapThreshEntry 1 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.2
pduTrapThreshRS OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU table row status."
::= { pduTrapThreshEntry 2 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.3
pduRMSVoltsUCL OBJECT-TYPE
SYNTAX INTEGER (-10..500)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"rms UCL value in volts"
::= { pduTrapThreshEntry 3 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.4
pduRMSVoltsUWL OBJECT-TYPE
SYNTAX INTEGER (-10..500)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"rms UWL value in volts"
::= { pduTrapThreshEntry 4 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.5
pduRMSVoltsLWL OBJECT-TYPE
SYNTAX INTEGER (-10..500)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"rms LWL value in volts"
::= { pduTrapThreshEntry 5 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.6
pduRMSVoltsLCL OBJECT-TYPE
SYNTAX INTEGER (-10..500)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"rms LCL value in volts"
::= { pduTrapThreshEntry 6 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.7
pduRMSAmpsUCL OBJECT-TYPE
SYNTAX INTEGER (-10..5000)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"rms UCL value in 0.1 amps"
::= { pduTrapThreshEntry 7 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.8
pduRMSAmpsUWL OBJECT-TYPE
SYNTAX INTEGER (-10..5000)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"rms UWL value in 0.1 amps"
::= { pduTrapThreshEntry 8 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.9
pduRMSAmpsLWL OBJECT-TYPE
SYNTAX INTEGER (-10..5000)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"rms LWL value in 0.1 amps"
::= { pduTrapThreshEntry 9 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.10
pduRMSAmpsLCL OBJECT-TYPE
SYNTAX INTEGER (-10..5000)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"rms LCL value in 0.1 amps"
::= { pduTrapThreshEntry 10 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.11
pduEnergyUCL OBJECT-TYPE
SYNTAX Unsigned32 (0..4294967290)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Total energy UCL value in 0.1 kWh"
::= { pduTrapThreshEntry 11 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.12
pduEnergyUWL OBJECT-TYPE
SYNTAX Unsigned32 (0..4294967290)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Total energy UWL value in 0.1 kWh"
::= { pduTrapThreshEntry 12 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.13
pduMeanKVAUCL OBJECT-TYPE
SYNTAX INTEGER (0..999990)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Mean kVA UCL value in 0.1 kVA"
::= { pduTrapThreshEntry 13 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.14
pduMeanKVAUWL OBJECT-TYPE
SYNTAX INTEGER (0..999990)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Mean kVA UWL value in 0.1 kVA"
::= { pduTrapThreshEntry 14 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.15
pduMeanKVALWL OBJECT-TYPE
SYNTAX INTEGER (0..999990)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Mean kVA LWL value in 0.1 kVA"
::= { pduTrapThreshEntry 15 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.16
pduMeanKVALCL OBJECT-TYPE
SYNTAX INTEGER (0..999990)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Mean kVA LCL value in 0.1 kVA"
::= { pduTrapThreshEntry 16 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.17
pduMeanKWattsUCL OBJECT-TYPE
SYNTAX INTEGER (0..100000)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Mean power UCL value in 0.1 kW"
::= { pduTrapThreshEntry 17 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.18
pduMeanKWattsUWL OBJECT-TYPE
SYNTAX INTEGER (0..100000)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Mean power UWL value in 0.1 kW"
::= { pduTrapThreshEntry 18 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.19
pduMeanKWattsLWL OBJECT-TYPE
SYNTAX INTEGER (0..100000)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Mean power LWL value in 0.1 kW"
::= { pduTrapThreshEntry 19 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.20
pduMeanKWattsLCL OBJECT-TYPE
SYNTAX INTEGER (0..100000)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Mean power LCL value in 0.1 kW"
::= { pduTrapThreshEntry 20 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.21
pduPwrFactorUTL OBJECT-TYPE
SYNTAX INTEGER (0..100)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Power factor UTL value in 0.01"
::= { pduTrapThreshEntry 21 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.2.1.22
pduPwrFactorLTL OBJECT-TYPE
SYNTAX INTEGER (0..100)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Power factor LTL value in 0.01"
::= { pduTrapThreshEntry 22 }
-- }}} End of pduTrapThreshTable
-- {{{ pduTrapEnTable
-- 1.3.6.1.4.1.3711.24.1.1.7.3.3
pduTrapEnTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduTrapEnEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The table which controls threshold value trap enabling for all PDUs enabled for monitoring."
::= { pduMonitor 3 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.3.1
pduTrapEnEntry OBJECT-TYPE
SYNTAX PduTrapEnEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A conceptual row containing information about one PDU."
INDEX { pduTrapEnPduNumber }
::= { pduTrapEnTable 1 }
PduTrapEnEntry ::= SEQUENCE {
pduTrapEnPduNumber Unsigned32,
pduTrapEnRS RowStatus,
pduRMSVoltsUCLTrapEn TruthValue,
pduRMSVoltsUWLTrapEn TruthValue,
pduRMSVoltsLWLTrapEn TruthValue,
pduRMSVoltsLCLTrapEn TruthValue,
pduRMSAmpsUCLTrapEn TruthValue,
pduRMSAmpsUWLTrapEn TruthValue,
pduRMSAmpsLWLTrapEn TruthValue,
pduRMSAmpsLCLTrapEn TruthValue,
pduEnergyUCLTrapEn TruthValue,
pduEnergyUWLTrapEn TruthValue,
pduMeanKVAUCLTrapEn TruthValue,
pduMeanKVAUWLTrapEn TruthValue,
pduMeanKVALWLTrapEn TruthValue,
pduMeanKVALCLTrapEn TruthValue,
pduMeanKWattsUCLTrapEn TruthValue,
pduMeanKWattsUWLTrapEn TruthValue,
pduMeanKWattsLWLTrapEn TruthValue,
pduMeanKWattsLCLTrapEn TruthValue,
pduPwrFactorUTLTrapEn TruthValue,
pduPwrFactorLTLTrapEn TruthValue
}
-- 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.1
pduTrapEnPduNumber OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU number."
::= { pduTrapEnEntry 1 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.2
pduTrapEnRS OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU table row status."
::= { pduTrapEnEntry 2 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.3
pduRMSVoltsUCLTrapEn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables Volts UCL trap."
::= { pduTrapEnEntry 3 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.4
pduRMSVoltsUWLTrapEn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables UWL Volts trap."
::= { pduTrapEnEntry 4 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.5
pduRMSVoltsLWLTrapEn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables LWL Volts trap."
::= { pduTrapEnEntry 5 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.6
pduRMSVoltsLCLTrapEn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables LCL Volts trap."
::= { pduTrapEnEntry 6 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.7
pduRMSAmpsUCLTrapEn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables UCL current trap."
::= { pduTrapEnEntry 7 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.8
pduRMSAmpsUWLTrapEn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables UWL current trap."
::= { pduTrapEnEntry 8 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.9
pduRMSAmpsLWLTrapEn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables LWL current trap."
::= { pduTrapEnEntry 9 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.10
pduRMSAmpsLCLTrapEn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables LCL current trap."
::= { pduTrapEnEntry 10 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.11
pduEnergyUCLTrapEn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables UCL total energy trap."
::= { pduTrapEnEntry 11 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.12
pduEnergyUWLTrapEn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables UWL total energy trap."
::= { pduTrapEnEntry 12 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.13
pduMeanKVAUCLTrapEn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables mean kVA UCL trap."
::= { pduTrapEnEntry 13 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.14
pduMeanKVAUWLTrapEn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables mean kVA UWL trap."
::= { pduTrapEnEntry 14 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.15
pduMeanKVALWLTrapEn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables mean kVA LWL trap."
::= { pduTrapEnEntry 15 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.16
pduMeanKVALCLTrapEn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables mean kVA LCL trap."
::= { pduTrapEnEntry 16 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.17
pduMeanKWattsUCLTrapEn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables mean power UCL trap."
::= { pduTrapEnEntry 17 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.18
pduMeanKWattsUWLTrapEn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables mean power UWL trap."
::= { pduTrapEnEntry 18 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.19
pduMeanKWattsLWLTrapEn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables mean power LWL trap."
::= { pduTrapEnEntry 19 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.20
pduMeanKWattsLCLTrapEn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables mean power LCL trap."
::= { pduTrapEnEntry 20 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.21
pduPwrFactorUTLTrapEn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables power factor UTL trap."
::= { pduTrapEnEntry 21 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.3.1.22
pduPwrFactorLTLTrapEn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables power factor LTL trap."
::= { pduTrapEnEntry 22 }
-- }}} End of pduTrapEnTable
-- {{{ pduTrapPerTable
-- 1.3.6.1.4.1.3711.24.1.1.7.3.4
pduTrapPerTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduTrapPerEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The table which controls threshold value trap repetition for all PDUs enabled for monitoring."
::= { pduMonitor 4 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.4.1
pduTrapPerEntry OBJECT-TYPE
SYNTAX PduTrapPerEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A conceptual row containing information about one PDU."
INDEX { pduTrapPduNumber }
::= { pduTrapPerTable 1 }
PduTrapPerEntry ::= SEQUENCE {
pduTrapPduNumber Unsigned32,
pduTrapPerRS RowStatus,
pduRMSVoltsUCLTrapPer Unsigned32,
pduRMSVoltsUWLTrapPer Unsigned32,
pduRMSVoltsLWLTrapPer Unsigned32,
pduRMSVoltsLCLTrapPer Unsigned32,
pduRMSAmpsUCLTrapPer Unsigned32,
pduRMSAmpsUWLTrapPer Unsigned32,
pduRMSAmpsLWLTrapPer Unsigned32,
pduRMSAmpsLCLTrapPer Unsigned32,
pduEnergyUCLTrapPer Unsigned32,
pduEnergyUWLTrapPer Unsigned32,
pduMeanKVAUCLTrapPer Unsigned32,
pduMeanKVAUWLTrapPer Unsigned32,
pduMeanKVALWLTrapPer Unsigned32,
pduMeanKVALCLTrapPer Unsigned32,
pduMeanKWattsUCLTrapPer Unsigned32,
pduMeanKWattsUWLTrapPer Unsigned32,
pduMeanKWattsLWLTrapPer Unsigned32,
pduMeanKWattsLCLTrapPer Unsigned32,
pduPwrFactorUTLTrapPer Unsigned32,
pduPwrFactorLTLTrapPer Unsigned32
}
-- 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.1
pduTrapPduNumber OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU number."
::= { pduTrapPerEntry 1 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.2
pduTrapPerRS OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU table row status."
::= { pduTrapPerEntry 2 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.3
pduRMSVoltsUCLTrapPer OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Sets UCL Volts trap repeat rate in seconds"
::= { pduTrapPerEntry 3 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.4
pduRMSVoltsUWLTrapPer OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Sets UWL Volts trap repeat rate in seconds"
::= { pduTrapPerEntry 4 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.5
pduRMSVoltsLWLTrapPer OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Sets LWL Volts trap repeat rate in seconds"
::= { pduTrapPerEntry 5 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.6
pduRMSVoltsLCLTrapPer OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Sets LCL Volts trap repeat rate in seconds"
::= { pduTrapPerEntry 6 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.7
pduRMSAmpsUCLTrapPer OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Sets UCL current trap repeat rate in seconds"
::= { pduTrapPerEntry 7 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.8
pduRMSAmpsUWLTrapPer OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Sets UWL current trap repeat rate in seconds"
::= { pduTrapPerEntry 8 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.9
pduRMSAmpsLWLTrapPer OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Sets LWL current trap repeat rate in seconds"
::= { pduTrapPerEntry 9 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.10
pduRMSAmpsLCLTrapPer OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Sets LCL current trap repeat rate in seconds"
::= { pduTrapPerEntry 10 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.11
pduEnergyUCLTrapPer OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Sets UCL total energy trap repeat rate in seconds"
::= { pduTrapPerEntry 11 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.12
pduEnergyUWLTrapPer OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Sets UWL total energy trap repeat rate in seconds"
::= { pduTrapPerEntry 12 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.13
pduMeanKVAUCLTrapPer OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Sets mean kVA UCL trap repeat rate in seconds"
::= { pduTrapPerEntry 13 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.14
pduMeanKVAUWLTrapPer OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Sets mean kVA UWL trap repeat rate in seconds"
::= { pduTrapPerEntry 14 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.15
pduMeanKVALWLTrapPer OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Sets mean kVA LWL trap repeat rate in seconds"
::= { pduTrapPerEntry 15 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.16
pduMeanKVALCLTrapPer OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Sets mean kVA LCL trap repeat rate in seconds"
::= { pduTrapPerEntry 16 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.17
pduMeanKWattsUCLTrapPer OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Sets mean power UCL trap repeat rate in seconds"
::= { pduTrapPerEntry 17 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.18
pduMeanKWattsUWLTrapPer OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Sets mean power UWL trap repeat rate in seconds"
::= { pduTrapPerEntry 18 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.19
pduMeanKWattsLWLTrapPer OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Sets mean power LWL trap repeat rate in seconds"
::= { pduTrapPerEntry 19 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.20
pduMeanKWattsLCLTrapPer OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Sets mean power LCL trap repeat rate in seconds"
::= { pduTrapPerEntry 20 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.21
pduPwrFactorUTLTrapPer OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Sets power factor UTL trap repeat rate in seconds"
::= { pduTrapPerEntry 21 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.4.1.22
pduPwrFactorLTLTrapPer OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Sets power factor LTL trap repeat rate in seconds"
::= { pduTrapPerEntry 22 }
-- }}} End of pduTrapPerTable
-- {{{ pduMon3PhTable
-- 1.3.6.1.4.1.3711.24.1.1.7.3.5
pduMon3PhTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduMon3PhEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table containing monitor information for all 3-phase PDUs enabled for monitoring."
::= { pduMonitor 5 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.5.1
pduMon3PhEntry OBJECT-TYPE
SYNTAX PduMon3PhEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A conceptual row containing monitor information for one 3-phase PDU."
INDEX { pdu3PhPduNumber }
::= { pduMon3PhTable 1 }
PduMon3PhEntry ::= SEQUENCE {
pdu3PhPduNumber Unsigned32,
pdu3PhRS RowStatus,
pdu3PhMode INTEGER,
pdu3PhVoltsC1 INTEGER,
pdu3PhAmpsL1 INTEGER,
pdu3PhVoltsC2 INTEGER,
pdu3PhAmpsL2 INTEGER,
pdu3PhVoltsC3 INTEGER,
pdu3PhAmpsL3 INTEGER,
pdu3PhAmpsAgg INTEGER,
pdu3PhkVAAgg INTEGER,
pdu3PhkWAgg INTEGER,
pdu3PhkVArhAgg Unsigned32,
pdu3PhkWhAgg Unsigned32
}
-- 1.3.6.1.4.1.3711.24.1.1.7.3.5.1.1
pdu3PhPduNumber OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU number."
::= { pduMon3PhEntry 1 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.5.1.2
pdu3PhRS OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU table row status."
::= { pduMon3PhEntry 2 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.5.1.3
pdu3PhMode OBJECT-TYPE
SYNTAX INTEGER { star(1), delta(2), aggregate(253), none(254), unknown(255) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Three phase topology"
::= { pduMon3PhEntry 3 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.5.1.4
pdu3PhVoltsC1 OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Line RMS Volts value in volts"
::= { pduMon3PhEntry 4 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.5.1.5
pdu3PhAmpsL1 OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase RMS current value in 0.1 Amps"
::= { pduMon3PhEntry 5 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.5.1.6
pdu3PhVoltsC2 OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Line RMS Volts value in volts"
::= { pduMon3PhEntry 6 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.5.1.7
pdu3PhAmpsL2 OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase RMS current value in 0.1 Amps"
::= { pduMon3PhEntry 7 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.5.1.8
pdu3PhVoltsC3 OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Line RMS Volts value in volts"
::= { pduMon3PhEntry 8 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.5.1.9
pdu3PhAmpsL3 OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase RMS current value in 0.1 Amps"
::= { pduMon3PhEntry 9 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.5.1.10
pdu3PhAmpsAgg OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Total RMS current value in 0.1 Amps"
::= { pduMon3PhEntry 10 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.5.1.11
pdu3PhkVAAgg OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Total apparent power value in 0.1 kVA"
::= { pduMon3PhEntry 11 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.5.1.12
pdu3PhkWAgg OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Total true power value in 0.1 kVW"
::= { pduMon3PhEntry 12 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.5.1.13
pdu3PhkVArhAgg OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Total re-active energy value in 0.1 kVArh"
::= { pduMon3PhEntry 13 }
-- 1.3.6.1.4.1.3711.24.1.1.7.3.5.1.14
pdu3PhkWhAgg OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Total true energy value in 0.1 kWh"
::= { pduMon3PhEntry 14 }
-- }}} End of pduMonTable
-- }}} End of pduMonitor group
-- {{{ pdus traps
-- No traps for this branch
-- {{{ pdus RMS Volt traps
-- No traps for this branch
-- }}} End of pdus RMS Volt traps
-- {{{ pdus RMS Amp traps
-- No traps for this branch
-- }}} End of pdus RMS Amp traps
-- {{{ pdus Total Energy traps
-- No traps for this branch
-- }}} End of pdus Total Energy traps
-- }}} End of pdus traps
--{{{ pdu gangs
-- 1.3.6.1.4.1.3711.24.1.1.7.4.1
pduGangsEnable OBJECT IDENTIFIER ::= { pduGangs 1 }
-- {{{ pduEnable group
-- 1.3.6.1.4.1.3711.24.1.1.7.4.1.1
pduGangsSelect OBJECT-TYPE
SYNTAX INTEGER (0..24)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Selects the PDU gang to be enabled or disabled by pduEnable.
A value of 0 selects no PDU gang."
DEFVAL { 0 }
::= { pduGangsEnable 1 }
-- 1.3.6.1.4.1.3711.24.1.1.7.4.1.2
pduGangsInsert OBJECT-TYPE
SYNTAX EnableState
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the PDU gang selected by pduGangsSelect -
causes an entry for that PDU gang to be created or deleted in the relevant tables.
- Read behaviour is undefined."
::= { pduGangsEnable 2 }
-- }}} End of pduEnable group
--{{{ pdu gang config
-- 1.3.6.1.4.1.3711.24.1.1.7.4.2
pduGangTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduGangEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table containing information about each pdu gang."
::= { pduGangs 2 }
-- 1.3.6.1.4.1.3711.24.1.1.7.4.2.1
pduGangEntry OBJECT-TYPE
SYNTAX PduGangEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A conceptual row containing information about one pdu gang."
INDEX { pduGangNumber }
::= { pduGangTable 1 }
PduGangEntry ::= SEQUENCE {
pduGangNumber INTEGER,
pduGangRS RowStatus,
pduGangEn INTEGER,
pduGangName DisplayString,
pduGangOn INTEGER,
pduGangPassword DisplayString,
pduGangAbortTask Unsigned32,
pduGangMembers DisplayString
}
-- 1.3.6.1.4.1.3711.24.1.1.7.4.2.1.1
pduGangNumber OBJECT-TYPE
SYNTAX INTEGER (1..24)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The pdu gang number."
::= { pduGangEntry 1 }
-- 1.3.6.1.4.1.3711.24.1.1.7.4.2.1.2
pduGangRS OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The gang table row status."
::= { pduGangEntry 2 }
-- 1.3.6.1.4.1.3711.24.1.1.7.4.2.1.3
pduGangEn OBJECT-TYPE
SYNTAX INTEGER {enabled(1), disabled(2), suspended(3)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Shows whether the gang is enabled(1), disabled(2) or suspended(3) this may have been disabled
by the application e.g. disabled pdu's in the gang, or bad pdu outlet CRC."
::= {pduGangEntry 3 }
-- 1.3.6.1.4.1.3711.24.1.1.7.4.2.1.4
pduGangName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..32))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The name of this gang."
::= {pduGangEntry 4 }
-- 1.3.6.1.4.1.3711.24.1.1.7.4.2.1.5
pduGangOn OBJECT-TYPE
SYNTAX INTEGER {on(1), off(2), mixed(3), reboot(4), na(5)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The current state for this gang.
Only states 1(on) ,2(off) and 4(reboot) can be set."
::= { pduGangEntry 5 }
-- 1.3.6.1.4.1.3711.24.1.1.7.4.2.1.6
pduGangPassword OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..16))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The password required to control this gang."
::= {pduGangEntry 6 }
-- 1.3.6.1.4.1.3711.24.1.1.7.4.2.1.7
pduGangAbortTask OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Abort gang setting task."
::= { pduGangEntry 7 }
-- 1.3.6.1.4.1.3711.24.1.1.7.4.2.1.8
pduGangMembers OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..37))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A string representing the members of a gang.
The format is PDU:OUTLET; e.g. 1:3;4:2;5:12;3:18; up to 6 member pairs"
::= {pduGangEntry 8 }
--}}} end pdu gang config
--{{{ pdu gang control
--}}} end pdu gang control
--}}} end pdu gangs
-- }}} End of pdus group
-- {{{ expansion group
-- 1.3.6.1.4.1.3711.24.1.1.8.1
expEnable OBJECT IDENTIFIER ::= { expansion 1 }
-- {{{ expEnable group
-- 1.3.6.1.4.1.3711.24.1.1.8.1.1
expSelect OBJECT-TYPE
SYNTAX INTEGER (0..2)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Selects the Expansion Port to be enabled or disabled by expInsert.
A value of 0 selects no Expansion Port."
::= { expEnable 1 }
-- 1.3.6.1.4.1.3711.24.1.1.8.1.2
expInsert OBJECT-TYPE
SYNTAX ExternalUnitType
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables or disables the Expansion Port selected by expSelect -
causes an entry for that Expansion Port to be created or deleted in the relevant tables.
- Read behaviour is undefined."
::= { expEnable 2 }
-- }}} End of expEnable group
-- {{{ expTable
-- 1.3.6.1.4.1.3711.24.1.1.8.2
expTable OBJECT-TYPE
SYNTAX SEQUENCE OF ExpEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table containing information about each enabled Expansion Port."
::= { expansion 2 }
-- 1.3.6.1.4.1.3711.24.1.1.8.2.1
expEntry OBJECT-TYPE
SYNTAX ExpEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A conceptual row containing information about one Expansion Port."
INDEX { expNumber }
::= { expTable 1 }
ExpEntry ::= SEQUENCE {
expNumber INTEGER,
expRS RowStatus,
expName DisplayString,
expType ExternalUnitType,
expCommsFail INTEGER
}
-- 1.3.6.1.4.1.3711.24.1.1.8.2.1.1
expNumber OBJECT-TYPE
SYNTAX INTEGER (1..2)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The Expansion Port number; maps to the specific Expansion Port connector."
::= { expEntry 1 }
-- 1.3.6.1.4.1.3711.24.1.1.8.2.1.2
expRS OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The Expansion Port table row status."
::= { expEntry 2 }
-- 1.3.6.1.4.1.3711.24.1.1.8.2.1.3
expName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A string identifying the Expansion Port."
::= { expEntry 3 }
-- 1.3.6.1.4.1.3711.24.1.1.8.2.1.4
expType OBJECT-TYPE
SYNTAX ExternalUnitType
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Indicates the External Unit type."
::= { expEntry 4 }
-- 1.3.6.1.4.1.3711.24.1.1.8.2.1.5
expCommsFail OBJECT-TYPE
SYNTAX INTEGER { commsGood(1), commsFailed(2), commsBadData(3)}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates Comms. Status for the Expansion Port."
::= {expEntry 5 }
-- }}} End of expTable
-- {{{ Expansion Port traps
-- No traps for this branch
-- }}} End of Expansion Port traps
-- }}} End of expansion group
-- {{{ CLamp group
-- {{{ clampTable
-- 1.3.6.1.4.1.3711.24.1.1.9.1
clampTable OBJECT-TYPE
SYNTAX SEQUENCE OF ClampEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table containing information about each detected CL-amp unit."
::= { clamp 1 }
-- 1.3.6.1.4.1.3711.24.1.1.9.1.1
clampEntry OBJECT-TYPE
SYNTAX ClampEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A conceptual row containing information about one CL-amp unit."
INDEX { clampNumber }
::= { clampTable 1 }
ClampEntry ::= SEQUENCE {
clampNumber INTEGER,
clampRS RowStatus,
clampBValue Unsigned32,
clampVolts Unsigned32,
clampPwrFactor Unsigned32,
clampFrequency Unsigned32,
clampWriteParams Unsigned32
}
-- 1.3.6.1.4.1.3711.24.1.1.9.1.1.1
clampNumber OBJECT-TYPE
SYNTAX INTEGER (1..24)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The CL-Amp number; maps to the specific CL-Amp Port."
::= { clampEntry 1 }
-- 1.3.6.1.4.1.3711.24.1.1.9.1.1.2
clampRS OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The CL-Amp table row status."
::= { clampEntry 2 }
-- 1.3.6.1.4.1.3711.24.1.1.9.1.1.3
clampBValue OBJECT-TYPE
SYNTAX Unsigned32 (20000..150000)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Stores the value of the CL-amp unit B Value configuration. This may have been set
by the management station or read from the CL-amp unit depending on recent history.
Value is x 1000."
::= {clampEntry 3 }
-- 1.3.6.1.4.1.3711.24.1.1.9.1.1.4
clampVolts OBJECT-TYPE
SYNTAX Unsigned32 (90..250)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Stores the value of the CL-amp unit Volts configuration. This may have been set
by the management station or read from the CL-amp unit depending on recent history.
Value is in Volts."
::= {clampEntry 4 }
-- 1.3.6.1.4.1.3711.24.1.1.9.1.1.5
clampPwrFactor OBJECT-TYPE
SYNTAX Unsigned32 (0..100)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Stores the value of the CL-amp unit Power Factor configuration. This may have been set
by the management station or read from the CL-amp unit depending on recent history.
Value is x100."
::= {clampEntry 5 }
-- 1.3.6.1.4.1.3711.24.1.1.9.1.1.6
clampFrequency OBJECT-TYPE
SYNTAX Unsigned32 (450..650)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Stores the value of the CL-amp unit Frequency configuration. This may have been set
by the management station or read from the CL-amp unit depending on recent history.
Value is Hz x10."
::= {clampEntry 6 }
-- 1.3.6.1.4.1.3711.24.1.1.9.1.1.15
clampWriteParams OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"When written to, sends the configuration values stored in this table for writing to the CL-amp unit."
::= {clampEntry 15 }
-- }}} End of clampTable
-- {{{ CLamp traps
-- No traps for this branch
-- }}} End of CLamp traps
-- }}} End of CLamp group
-- BEGIN SECTION IDM
-- {{{ IDM group
-- {{{ idmTable
idmTable OBJECT-TYPE
SYNTAX SEQUENCE OF IdmEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table containing information about IDMs"
::= { idm 1 }
idmEntry OBJECT-TYPE
SYNTAX IdmEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A conceptual row containing information about one IDM."
INDEX { idmNumber }
::= { idmTable 1 }
IdmEntry ::= SEQUENCE {
idmNumber INTEGER,
idmRS RowStatus,
idmVersion DisplayString,
idmStatus INTEGER
}
idmNumber OBJECT-TYPE
SYNTAX INTEGER (1..2)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The IDM number; maps to the specific IDM Port."
::= { idmEntry 1 }
idmRS OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The IDM table row status."
::= { idmEntry 2 }
idmVersion OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Version information returned by the IDM."
::= {idmEntry 3 }
idmStatus OBJECT-TYPE
SYNTAX INTEGER { enabled(1), disabled(2), unknown(255)}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates status of the IDM."
::= {idmEntry 4 }
-- }}} End of idmTable
-- {{{ IDM traps
-- No traps for this branch
-- }}} End of IDM traps
-- }}} End of IDM group
-- END SECTION IDM
-- BEGIN SECTION PDUP2
-- {{{ pdusP2 group
-- 1.3.6.1.4.1.3711.24.1.1.11.1
pduP2BrCct OBJECT IDENTIFIER ::= { pdusP2 1 }
-- {{{ pduP2BrCctTable group
-- 1.3.6.1.4.1.3711.24.1.1.11.1.1
pduP2BrCctMonitorTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduP2BrCctMonitorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table giving branch circuit monitoring information for all PDUs."
::= { pduP2BrCct 1 }
-- 1.3.6.1.4.1.3711.24.1.1.11.1.1.1
pduP2BrCctMonitorEntry OBJECT-TYPE
SYNTAX PduP2BrCctMonitorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A conceptual row containing information about branch circuit monitoring."
INDEX { pduP2BrCktMonPduNumber, pduP2BrCktMonBrCctNumber }
::= { pduP2BrCctMonitorTable 1 }
PduP2BrCctMonitorEntry ::= SEQUENCE {
pduP2BrCktMonPduNumber Unsigned32,
pduP2BrCktMonBrCctNumber Unsigned32,
pduP2BrCktMonRS RowStatus,
pduP2BrCktMonBrCctID DisplayString,
pduP2BrCktMonBrCctPhases DisplayString,
pduP2BrCktMonBrCctCurrent Unsigned32,
pduP2BrCktMonBrCctPeakCurrent Unsigned32,
pduP2BrCktMonBrCctPeakCurrentTimestamp UnsignedTimeTicks,
pduP2BrCktMonBrCctBreakerStatus BranchCircuitStatusType,
pduP2BrCktMonBrCctBreakerConfig BranchCircuitConfigType,
pduP2BrCktMonBrCctBreakerTripState BranchCircuitStatusType,
pduP2BrCktMonBrCctBreakerContinuousLoadRatingAmps Unsigned32,
pduP2BrCktMonBrCctBreakerTripRatingAmps Unsigned32,
pduP2BrCktMonBrCctBreakerOutletMap DisplayString,
pduP2BrCktCircuitCurrentUCL INTEGER,
pduP2BrCktCircuitCurrentUWL INTEGER,
pduP2BrCktCircuitCurrentLWL INTEGER,
pduP2BrCktCircuitCurrentLCL INTEGER,
pduP2BrCktCircuitCurrentUCLTrapEn TruthValue,
pduP2BrCktCircuitCurrentUWLTrapEn TruthValue,
pduP2BrCktCircuitCurrentLWLTrapEn TruthValue,
pduP2BrCktCircuitCurrentLCLTrapEn TruthValue,
pduP2BrCktCircuitCurrentUCLTrapPer Unsigned32,
pduP2BrCktCircuitCurrentUWLTrapPer Unsigned32,
pduP2BrCktCircuitCurrentLWLTrapPer Unsigned32,
pduP2BrCktCircuitCurrentLCLTrapPer Unsigned32
}
-- 1.3.6.1.4.1.3711.24.1.1.11.1.1.1.1
pduP2BrCktMonPduNumber OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU index number."
::= { pduP2BrCctMonitorEntry 1 }
-- 1.3.6.1.4.1.3711.24.1.1.11.1.1.1.2
pduP2BrCktMonBrCctNumber OBJECT-TYPE
SYNTAX Unsigned32 (1..9)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Branch Circuit Number."
::= { pduP2BrCctMonitorEntry 2 }
-- 1.3.6.1.4.1.3711.24.1.1.11.1.1.1.3
pduP2BrCktMonRS OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The branch circuit monitor table row status."
::= { pduP2BrCctMonitorEntry 3 }
-- 1.3.6.1.4.1.3711.24.1.1.11.1.1.1.4
pduP2BrCktMonBrCctID OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The PDU Branch Circuit ID."
::= { pduP2BrCctMonitorEntry 4 }
-- 1.3.6.1.4.1.3711.24.1.1.11.1.1.1.5
pduP2BrCktMonBrCctPhases OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The PDU Branch Circuit Phases."
::= { pduP2BrCctMonitorEntry 5 }
-- 1.3.6.1.4.1.3711.24.1.1.11.1.1.1.6
pduP2BrCktMonBrCctCurrent OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Branch Circuit Current. The value precision is thousandths e.g. a value of 1001 is 1.001 Amps."
::= { pduP2BrCctMonitorEntry 6 }
-- 1.3.6.1.4.1.3711.24.1.1.11.1.1.1.7
pduP2BrCktMonBrCctPeakCurrent OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Branch Circuit Peak Current. The value precision is hundredths e.g. a value of 1001 is 1.001 Amps."
::= { pduP2BrCctMonitorEntry 7 }
-- 1.3.6.1.4.1.3711.24.1.1.11.1.1.1.8
pduP2BrCktMonBrCctPeakCurrentTimestamp OBJECT-TYPE
SYNTAX UnsignedTimeTicks
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Branch Circuit Peak Current Timestamp."
::= { pduP2BrCctMonitorEntry 8 }
-- 1.3.6.1.4.1.3711.24.1.1.11.1.1.1.9
pduP2BrCktMonBrCctBreakerStatus OBJECT-TYPE
SYNTAX BranchCircuitStatusType
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Branch Circuit Breaker Status."
::= { pduP2BrCctMonitorEntry 9 }
-- 1.3.6.1.4.1.3711.24.1.1.11.1.1.1.10
pduP2BrCktMonBrCctBreakerConfig OBJECT-TYPE
SYNTAX BranchCircuitConfigType
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The PDU Branch Circuit Breaker Config."
::= { pduP2BrCctMonitorEntry 10 }
-- 1.3.6.1.4.1.3711.24.1.1.11.1.1.1.11
pduP2BrCktMonBrCctBreakerTripState OBJECT-TYPE
SYNTAX BranchCircuitStatusType
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Branch Circuit Breaker Trip State."
::= { pduP2BrCctMonitorEntry 11 }
-- 1.3.6.1.4.1.3711.24.1.1.11.1.1.1.12
pduP2BrCktMonBrCctBreakerContinuousLoadRatingAmps OBJECT-TYPE
SYNTAX Unsigned32 (1..100000)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The PDU Branch Circuit Breaker Continuous Load Rating Amps.The value precision is thousandths e.g. a value of 1001 is 1.001 Amps."
::= { pduP2BrCctMonitorEntry 12 }
-- 1.3.6.1.4.1.3711.24.1.1.11.1.1.1.13
pduP2BrCktMonBrCctBreakerTripRatingAmps OBJECT-TYPE
SYNTAX Unsigned32 (1..100000)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The PDU Branch Circuit Breaker Trip Rating Amps. The value precision is thousandths e.g. a value of 1001 is 1.001 Amps."
::= { pduP2BrCctMonitorEntry 13 }
-- 1.3.6.1.4.1.3711.24.1.1.11.1.1.1.14
pduP2BrCktMonBrCctBreakerOutletMap OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A string representing the outlets of a branch circuit.
The format is comma separated list of outlets; e.g. 8,9,10,11,12"
::= { pduP2BrCctMonitorEntry 14 }
-- 1.3.6.1.4.1.3711.24.1.1.11.1.1.1.15
pduP2BrCktCircuitCurrentUCL OBJECT-TYPE
SYNTAX INTEGER (-1000..100000)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
" Circuit Current UCL. The value precision is thousandths e.g. a value of 1001 is 1.001 Amps."
::= { pduP2BrCctMonitorEntry 15 }
-- 1.3.6.1.4.1.3711.24.1.1.11.1.1.1.16
pduP2BrCktCircuitCurrentUWL OBJECT-TYPE
SYNTAX INTEGER (-1000..100000)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
" Circuit Current UWL. The value precision is thousandths e.g. a value of 1001 is 1.001 Amps."
::= { pduP2BrCctMonitorEntry 16 }
-- 1.3.6.1.4.1.3711.24.1.1.11.1.1.1.17
pduP2BrCktCircuitCurrentLWL OBJECT-TYPE
SYNTAX INTEGER (-1000..100000)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
" Circuit Current LWL. The value precision is thousandths e.g. a value of 1001 is 1.001 Amps."
::= { pduP2BrCctMonitorEntry 17 }
-- 1.3.6.1.4.1.3711.24.1.1.11.1.1.1.18
pduP2BrCktCircuitCurrentLCL OBJECT-TYPE
SYNTAX INTEGER (-1000..100000)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
" Circuit Current LCL. The value precision is thousandths e.g. a value of 1001 is 1.001 Amps."
::= { pduP2BrCctMonitorEntry 18 }
-- 1.3.6.1.4.1.3711.24.1.1.11.1.1.1.19
pduP2BrCktCircuitCurrentUCLTrapEn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Trap enable flag for pduP2BrCktCircuitCurrentUCL."
::= { pduP2BrCctMonitorEntry 19 }
-- 1.3.6.1.4.1.3711.24.1.1.11.1.1.1.20
pduP2BrCktCircuitCurrentUWLTrapEn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Trap enable flag for pduP2BrCktCircuitCurrentUWL."
::= { pduP2BrCctMonitorEntry 20 }
-- 1.3.6.1.4.1.3711.24.1.1.11.1.1.1.21
pduP2BrCktCircuitCurrentLWLTrapEn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Trap enable flag for pduP2BrCktCircuitCurrentLWL."
::= { pduP2BrCctMonitorEntry 21 }
-- 1.3.6.1.4.1.3711.24.1.1.11.1.1.1.22
pduP2BrCktCircuitCurrentLCLTrapEn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Trap enable flag for pduP2BrCktCircuitCurrentLCL."
::= { pduP2BrCctMonitorEntry 22 }
-- 1.3.6.1.4.1.3711.24.1.1.11.1.1.1.23
pduP2BrCktCircuitCurrentUCLTrapPer OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Trap repetition period for pduP2BrCktCircuitCurrentUCL."
::= { pduP2BrCctMonitorEntry 23 }
-- 1.3.6.1.4.1.3711.24.1.1.11.1.1.1.24
pduP2BrCktCircuitCurrentUWLTrapPer OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Trap repetition period for pduP2BrCktCircuitCurrentUWL."
::= { pduP2BrCctMonitorEntry 24 }
-- 1.3.6.1.4.1.3711.24.1.1.11.1.1.1.25
pduP2BrCktCircuitCurrentLWLTrapPer OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Trap repetition period for pduP2BrCktCircuitCurrentLWL."
::= { pduP2BrCctMonitorEntry 25 }
-- 1.3.6.1.4.1.3711.24.1.1.11.1.1.1.26
pduP2BrCktCircuitCurrentLCLTrapPer OBJECT-TYPE
SYNTAX Unsigned32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Trap repetition period for pduP2BrCktCircuitCurrentLCL."
::= { pduP2BrCctMonitorEntry 26 }
-- }}} End of pduP2CircuitMonitorTable table
-- }}} End of pduP2Common group
-- END SECTION PDUP2
-- {{{ platformData group
-- 1.3.6.1.4.1.3711.24.1.1.98.1
platHwType OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Hardware type."
::= { platformData 1 }
-- 1.3.6.1.4.1.3711.24.1.1.98.2
platFwRev OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Firmware revision number."
::= { platformData 2 }
-- 1.3.6.1.4.1.3711.24.1.1.98.3
platBootldrRev OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Bootloader revision number."
::= { platformData 3 }
platModelName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Model name."
::= { platformData 4 }
-- }}} End of platformData group
-- {{{ inventory group
-- 1.3.6.1.4.1.3711.24.1.1.99.1
invProdSignature OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Product data signature."
::= { inventory 1 }
-- 1.3.6.1.4.1.3711.24.1.1.99.2
invProdFormatVer OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Product data format version."
::= { inventory 2 }
-- 1.3.6.1.4.1.3711.24.1.1.99.3
invManufCode OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Manufacturer code."
::= { inventory 3 }
-- 1.3.6.1.4.1.3711.24.1.1.99.4
invOrderNum OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Order number."
::= { inventory 4 }
-- 1.3.6.1.4.1.3711.24.1.1.99.5
invBatchNum OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Batch number."
::= { inventory 5 }
-- 1.3.6.1.4.1.3711.24.1.1.99.6
invProdTestTime OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Data and time of production test."
::= { inventory 6 }
-- 1.3.6.1.4.1.3711.24.1.1.99.7
invUnitName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Unit name."
::= { inventory 7 }
-- 1.3.6.1.4.1.3711.24.1.1.99.8
invUnitPartNum OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Unit part number."
::= { inventory 8 }
-- 1.3.6.1.4.1.3711.24.1.1.99.9
invHwRevision OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Hardware revision number."
::= { inventory 9 }
-- 1.3.6.1.4.1.3711.24.1.1.99.10
invFwRevision OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Firmware revision number."
::= { inventory 10 }
-- 1.3.6.1.4.1.3711.24.1.1.99.11
invSerialNum OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial number."
::= { inventory 11 }
-- 1.3.6.1.4.1.3711.24.1.1.99.12
invDefaultIPAddrType OBJECT-TYPE
SYNTAX IpStackConfiguration
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The configuration of the network stack."
::= { inventory 12 }
-- 1.3.6.1.4.1.3711.24.1.1.99.13
invDefaultIPAddr OBJECT-TYPE
SYNTAX InetAddress
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Default unit IP address."
::= { inventory 13 }
-- 1.3.6.1.4.1.3711.24.1.1.99.14
invDefaultSubNetMask OBJECT-TYPE
SYNTAX InetAddress
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Default unit sub-network mask."
::= { inventory 14 }
-- 1.3.6.1.4.1.3711.24.1.1.99.15
invDefaultGWAddr OBJECT-TYPE
SYNTAX InetAddress
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Default unit default gateway address."
::= { inventory 15 }
-- 1.3.6.1.4.1.3711.24.1.1.99.16
invMacAddr OBJECT-TYPE
SYNTAX MacAddress
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Unit medium access control (MAC) address."
::= { inventory 16 }
-- 1.3.6.1.4.1.3711.24.1.1.99.20
invOk OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Confirms that the inventory record isn't corrupted."
::= { inventory 20 }
-- 1.3.6.1.4.1.3711.24.1.1.99.50
invInputCount OBJECT-TYPE
SYNTAX INTEGER (0..24)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The maximum number of inputs that can be connected to the unit"
::= { inventory 50 }
-- 1.3.6.1.4.1.3711.24.1.1.99.51
invOutputCount OBJECT-TYPE
SYNTAX INTEGER (0..24)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The maximum number of outputs that can be connected to the unit"
::= { inventory 51 }
-- 1.3.6.1.4.1.3711.24.1.1.99.52
invKeypadCount OBJECT-TYPE
SYNTAX INTEGER (0..2)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The maximum number of keypads that can be connected to the unit"
::= { inventory 52 }
-- 1.3.6.1.4.1.3711.24.1.1.99.53
invAcuCount OBJECT-TYPE
SYNTAX INTEGER (0..6)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The maximum number of ACU's that can be connected to the unit"
::= { inventory 53 }
-- 1.3.6.1.4.1.3711.24.1.1.99.54
invAccessUserCount OBJECT-TYPE
SYNTAX INTEGER (0..20)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The maximum number of user entries on the unit"
::= { inventory 54 }
-- 1.3.6.1.4.1.3711.24.1.1.99.55
invPduCount OBJECT-TYPE
SYNTAX INTEGER (0..6)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The maximum number of PDU's that can be connected to the unit"
::= { inventory 55 }
-- }}} End of inventory group
-- {{{ trapInfo group
-- 1.3.6.1.4.1.3711.24.1.1.100.1
trapCode OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A decimal number to be carried on notifications of types 1 to 4 identifying the event which caused it.
The format of this number is BBEEffCCT where
BB is the number of the relevant MIB branch.
EE indicates what type of event caused the notification. This value is dependent upon branch number and implementation.
CC is the channel number which was the source of the notification.
T discriminates the type of data, e.g. temperature. This value is dependent upon branch number and implementation.
ff future use.
Fields are packed with leading zeros and are set to zero if not relevant to a particular notification."
::= { trapInfo 1 }
-- 1.3.6.1.4.1.3711.24.1.1.100.2
trapDescription OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A string to be carried on notifications of types 1 to 4 identifying the event which caused it.
The format of this string is as follows.
Field 1 - type of notification, e.g. warning, critical, etc.
Field 2 - data source, e.g. inputs. Generally this relates to a particular MIB branch.
Field 3 - channel number, e.g. input 1.
Field 4 - event, i.e. what caused the trap.
Field 5 - value at which the event occured, e.g. 900, indicating 90% humidity.
Field 6 - type of data, e.g. relative humidity
Fields are omitted if not relevant to a particular notification."
::= { trapInfo 2 }
-- }}} End of trapInfo group
-- {{{ Generic traps
-- 1.3.6.1.4.1.3711.24.1.2.1
alarmCritical NOTIFICATION-TYPE
OBJECTS { trapCode, trapDescription }
STATUS current
DESCRIPTION
"Critical alarm."
::= { traps 1 }
-- 1.3.6.1.4.1.3711.24.1.2.2
alarmWarning NOTIFICATION-TYPE
OBJECTS { trapCode, trapDescription }
STATUS current
DESCRIPTION
"Warning alarm."
::= { traps 2 }
-- 1.3.6.1.4.1.3711.24.1.2.3
alarmInformation NOTIFICATION-TYPE
OBJECTS { trapCode, trapDescription }
STATUS current
DESCRIPTION
"Information alarm."
::= { traps 3 }
-- 1.3.6.1.4.1.3711.24.1.2.1.4
alarmCleared NOTIFICATION-TYPE
OBJECTS { trapCode, trapDescription }
STATUS current
DESCRIPTION
"Alarm cleared."
::= { traps 4 }
-- }}} End of Generic traps
-- BEGIN SECTION PDU2
-- 1.3.6.1.4.1.3711.24.2.1
objects2 OBJECT IDENTIFIER ::= { v2 1 }
-- 1.3.6.1.4.1.3711.24.2.2
traps2 OBJECT IDENTIFIER ::= { v2 2 }
-- {{{ objects group2
-- 1.3.6.1.4.1.3711.24.2.1.1
pdus2 OBJECT IDENTIFIER ::= { objects2 1 }
-- }}} End of objects group2
UnsignedTimeTicks ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Date/Time in 1/100th seconds since Jan 1, 1970 00:00 UTC to
avoid timezone issues. Will wrap around in 2106. If converted
to Signed32, wraps around 2038-01-19 3:14AM UTC."
SYNTAX Unsigned32
WiringTopologyType ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Represents the connectivity topology inside the device."
SYNTAX INTEGER {
disabled(1), -- no monitoring
singlePhase(2), -- 1L + N + E
twoPhase(3), -- 2L + E
threePhaseStar(4), -- 3L + N + E
threePhaseDelta(5), -- 3L + E
deltaWithNeutral(6), -- 3L + N + E
none(254), -- device does not support power distribution
unknown(255) -- device has forgotten its factory configuration
}
CktRefName ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Denotes a Main Circuit Reference Identifier."
SYNTAX OCTET STRING (SIZE (0..31))
BranchCircuitStatusType ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Represents the status of the branch circuit."
SYNTAX INTEGER {
closeOn(1), -- ???
openOff(2), -- ???
invalidFeature(255) -- ???
}
BranchCircuitConfigType ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Represents the configuration of the branch circuit."
SYNTAX INTEGER {
closeOn(1), -- ???
openOff(2), -- ???
invalidFeature(255) -- ???
}
ControlledOutletStatusType ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Represents the status of the controlled outlet."
SYNTAX INTEGER {
on(1), -- ???
off(2), -- ???
lastKnownState(3), -- ???
timeDelayOn(4) -- ???
}
-- {{{ pdus2 group
-- 1.3.6.1.4.1.3711.24.2.1.1.1
pdu2Common OBJECT IDENTIFIER ::= { pdus2 1 }
-- }}} End of pdus2 group
-- {{{ pdu2Common group
-- {{{ pdu2Table table
-- 1.3.6.1.4.1.3711.24.2.1.1.1.1
pdu2Table OBJECT-TYPE
SYNTAX SEQUENCE OF Pdu2Entry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table giving data for all PDUs."
::= { pdu2Common 1 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.1.1
pdu2Entry OBJECT-TYPE
SYNTAX Pdu2Entry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A conceptual row containing information about all PDUs."
INDEX { pdu2PduNumber }
::= { pdu2Table 1 }
Pdu2Entry ::= SEQUENCE {
pdu2PduNumber Unsigned32,
pdu2RS RowStatus,
pdu2WiringTopology WiringTopologyType,
pdu2PhaseTopology DisplayString
}
-- 1.3.6.1.4.1.3711.24.2.1.1.1.1.1.1
pdu2PduNumber OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU index number."
::= { pdu2Entry 1 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.1.1.2
pdu2RS OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU table row status."
::= { pdu2Entry 2 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.1.1.3
pdu2WiringTopology OBJECT-TYPE
SYNTAX WiringTopologyType
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU wiring topology description."
::= { pdu2Entry 3 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.1.1.4
pdu2PhaseTopology OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The PDU phase topology description."
::= { pdu2Entry 4 }
-- }}} End of pdu2Table table
-- {{{ custDataTable table
-- 1.3.6.1.4.1.3711.24.2.1.1.1.2
pdu2CustDataTable OBJECT-TYPE
SYNTAX SEQUENCE OF Pdu2CustDataEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table giving customer entered metadata for all PDUs"
::= { pdu2Common 2 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.2.1
pdu2CustDataEntry OBJECT-TYPE
SYNTAX Pdu2CustDataEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A conceptual row containing information about customer metadata."
INDEX { pdu2CustDataPduNumber }
::= { pdu2CustDataTable 1 }
Pdu2CustDataEntry ::= SEQUENCE {
pdu2CustDataPduNumber Unsigned32,
pdu2CustDataRS RowStatus,
pdu2CustDataMainCktRefOverall CktRefName,
pdu2CustDataMainCktRefCktA CktRefName,
pdu2CustDataMainCktRefCktB CktRefName,
pdu2CustDataMainCktRefCktC CktRefName
}
-- 1.3.6.1.4.1.3711.24.2.1.1.1.2.1.1
pdu2CustDataPduNumber OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU index number."
::= { pdu2CustDataEntry 1 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.2.1.2
pdu2CustDataRS OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The customer metadata table row status."
::= { pdu2CustDataEntry 2 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.2.1.3
pdu2CustDataMainCktRefOverall OBJECT-TYPE
SYNTAX CktRefName
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Overall reference string"
::= { pdu2CustDataEntry 3 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.2.1.4
pdu2CustDataMainCktRefCktA OBJECT-TYPE
SYNTAX CktRefName
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Circuit-A reference string"
::= { pdu2CustDataEntry 4 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.2.1.5
pdu2CustDataMainCktRefCktB OBJECT-TYPE
SYNTAX CktRefName
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Circuit-B reference string"
::= { pdu2CustDataEntry 5 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.2.1.6
pdu2CustDataMainCktRefCktC OBJECT-TYPE
SYNTAX CktRefName
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Circuit-C reference string"
::= { pdu2CustDataEntry 6 }
-- }}} End of custData table
-- {{{ pdu2InputAggregateTable table
-- 1.3.6.1.4.1.3711.24.2.1.1.1.3
pdu2InputAggregateTable OBJECT-TYPE
SYNTAX SEQUENCE OF Pdu2InputAggregateEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table giving input aggregation information for all PDUs."
::= { pdu2Common 3 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.3.1
pdu2InputAggregateEntry OBJECT-TYPE
SYNTAX Pdu2InputAggregateEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A conceptual row containing information about input aggregation."
INDEX { pdu2IpAggPduNumber }
::= { pdu2InputAggregateTable 1 }
Pdu2InputAggregateEntry ::= SEQUENCE {
pdu2IpAggPduNumber Unsigned32,
pdu2IpAggRS RowStatus,
pdu2IpAggAggregatekWh Unsigned32,
pdu2IpAggAggregatekVA Unsigned32,
pdu2IpAggAggregatekW Unsigned32,
pdu2IpAggAggregatePF Unsigned32,
pdu2IpAggAggregateCurrent Unsigned32,
pdu2IpAggAggregateNeutralCurrent Unsigned32,
pdu2IpAggAggregateEarthCurrent Unsigned32
}
-- 1.3.6.1.4.1.3711.24.2.1.1.1.3.1.1
pdu2IpAggPduNumber OBJECT-TYPE
SYNTAX Unsigned32 --(0..1)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU index number."
::= { pdu2InputAggregateEntry 1 }
-- 1.3.6.1.4.1.3711.24.2.1.1.3.1.2
pdu2IpAggRS OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The input aggregate table row status."
::= { pdu2InputAggregateEntry 2 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.3.1.3
pdu2IpAggAggregatekWh OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Aggregate kWh. The value precision is hundredths e.g. a value of 101 is 1.01 kWh."
::= { pdu2InputAggregateEntry 3 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.3.1.4
pdu2IpAggAggregatekVA OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Aggregate kVA. The value precision is hundredths e.g. a value of 101 is 1.01 kVA."
::= { pdu2InputAggregateEntry 4 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.3.1.5
pdu2IpAggAggregatekW OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Aggregate kW. The value precision is hundredths e.g. a value of 101 is 1.01 kW."
::= { pdu2InputAggregateEntry 5 }
-- 1.3.6.1.4.1.3711.24.2.1.1.3.1.6
pdu2IpAggAggregatePF OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Aggregate PF. The value precision is thousandths e.g. a value of 1001 is 1.001 PF."
::= { pdu2InputAggregateEntry 6 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.3.1.7
pdu2IpAggAggregateCurrent OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Aggregate Current. The value precision is thousandths e.g. a value of 1001 is 1.001 Amps."
::= { pdu2InputAggregateEntry 7 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.3.1.1.8
pdu2IpAggAggregateNeutralCurrent OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Aggregate Neutral Current. The value precision is thousandths e.g. a value of 1001 is 1.001 Amps."
::= { pdu2InputAggregateEntry 8 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.3.1.1.9
pdu2IpAggAggregateEarthCurrent OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Aggregate Earth Current. The value precision is thousandths e.g. a value of 101 is 1.001 Amps."
::= { pdu2InputAggregateEntry 9 }
-- }}} End of pdu2InputAggregateTable table
-- {{{ pdu2PhaseMonitorTable table
-- 1.3.6.1.4.1.3711.24.2.1.1.1.4
pdu2PhaseMonitorTable OBJECT-TYPE
SYNTAX SEQUENCE OF Pdu2PhaseMonitorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table giving phase monitoring information data for all PDUs"
::= { pdu2Common 4 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.4.1
pdu2PhaseMonitorEntry OBJECT-TYPE
SYNTAX Pdu2PhaseMonitorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A conceptual row containing information about phase monitoring."
INDEX { pdu2PhMonPduNumber, pdu2PhMonPhaseNumber }
::= { pdu2PhaseMonitorTable 1 }
Pdu2PhaseMonitorEntry ::= SEQUENCE {
pdu2PhMonPduNumber Unsigned32,
pdu2PhMonPhaseNumber Unsigned32,
pdu2PhMonRS RowStatus,
pdu2PhMonLineID DisplayString,
pdu2PhMonPhaseToNeutralVoltage Unsigned32,
pdu2PhMonPhaseCurrent Unsigned32,
pdu2PhMonPhasekVA Unsigned32,
pdu2PhMonPhasePeakkVA Unsigned32,
pdu2PhMonPhasePeakkVATimestamp UnsignedTimeTicks,
pdu2PhMonPhasekW Unsigned32,
pdu2PhMonPhasePF Unsigned32,
pdu2PhMonPhasekWh Unsigned32,
pdu2PhMonPhasekVAr Unsigned32,
pdu2PhMonPhaseCrestFactor Unsigned32,
pdu2PhMonPhaseTHD Unsigned32
}
-- 1.3.6.1.4.1.3711.24.2.1.1.1.4.1.1
pdu2PhMonPduNumber OBJECT-TYPE
SYNTAX Unsigned32 --(0..1)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU index number."
::= { pdu2PhaseMonitorEntry 1 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.4.1.2
pdu2PhMonPhaseNumber OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU phase Number."
::= { pdu2PhaseMonitorEntry 2 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.4.1.3
pdu2PhMonRS OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The phase monitor table row status."
::= { pdu2PhaseMonitorEntry 3 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.4.1.4
pdu2PhMonLineID OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Line ID."
::= { pdu2PhaseMonitorEntry 4 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.4.1.5
pdu2PhMonPhaseToNeutralVoltage OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Phase To Neutral Voltage. The value precision is tenths e.g. a value of 101 is 10.1 V."
::= { pdu2PhaseMonitorEntry 5 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.4.1.6
pdu2PhMonPhaseCurrent OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Phase Current. The value precision is thousandths e.g. a value of 1001 is 1.001 Amps."
::= { pdu2PhaseMonitorEntry 6 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.4.1.7
pdu2PhMonPhasekVA OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Phase kVA. The value precision is hundredths e.g. a value of 101 is 1.01 kVA."
::= { pdu2PhaseMonitorEntry 7 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.4.1.8
pdu2PhMonPhasePeakkVA OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Phase Peak KVA. The value precision is hundredths e.g. a value of 101 is 1.01 kVA."
::= { pdu2PhaseMonitorEntry 8 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.4.1.9
pdu2PhMonPhasePeakkVATimestamp OBJECT-TYPE
SYNTAX UnsignedTimeTicks
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Phase Peak KVA Timestamp."
::= { pdu2PhaseMonitorEntry 9 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.4.1.10
pdu2PhMonPhasekW OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Phase hkW. The value precision is hundredths e.g. a value of 101 is 1.01 kW."
::= { pdu2PhaseMonitorEntry 10 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.4.1.11
pdu2PhMonPhasePF OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Phase PF. The value precision is thousandths e.g. a value of 1001 is 1.001 PF."
::= { pdu2PhaseMonitorEntry 11 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.4.1.12
pdu2PhMonPhasekWh OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Phase hkWh. The value precision is hundredths e.g. a value of 101 is 1.01 kWh."
::= { pdu2PhaseMonitorEntry 12 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.4.1.13
pdu2PhMonPhasekVAr OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Phase kVAr. The value precision is hundredths e.g. a value of 101 is 1.01 kVAr."
::= { pdu2PhaseMonitorEntry 13 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.4.1.14
pdu2PhMonPhaseCrestFactor OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Phase Crest Factor. The value precision is thousandths of percent e.g. a value of 999 is 99.9%."
::= { pdu2PhaseMonitorEntry 14 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.4.1.15
pdu2PhMonPhaseTHD OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Phase THD (Total Harmonic Distortion). The value precision is thousandths of percent e.g. a value of 999 is 99.9%."
::= { pdu2PhaseMonitorEntry 15 }
-- }}} End of pdu2PhaseMonitorTable table
-- {{{ pdu2CircuitMonitorTable table
-- 1.3.6.1.4.1.3711.24.2.1.1.1.5
pdu2CircuitMonitorTable OBJECT-TYPE
SYNTAX SEQUENCE OF Pdu2CircuitMonitorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table giving circuit monitoring information for all PDUs."
::= { pdu2Common 5 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.5.1
pdu2CircuitMonitorEntry OBJECT-TYPE
SYNTAX Pdu2CircuitMonitorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A conceptual row containing information about circuit monitoring."
INDEX { pdu2CktMonPduNumber, pdu2CktMonCircuitNumber }
::= { pdu2CircuitMonitorTable 1 }
Pdu2CircuitMonitorEntry ::= SEQUENCE {
pdu2CktMonPduNumber Unsigned32,
pdu2CktMonCircuitNumber Unsigned32,
pdu2CktMonRS RowStatus,
pdu2CktMonLineID DisplayString,
pdu2CktMonLineToLineVoltage Unsigned32,
pdu2CktMonLineToLineCurrent Unsigned32,
pdu2CktMonLineToLineKVA Unsigned32,
pdu2CktMonLineToLinePeakkVA Unsigned32,
pdu2CktMonLineToLinePeakkVATimestamp UnsignedTimeTicks,
pdu2CktMonLineToLinekW Unsigned32,
pdu2CktMonLineToLinePF Unsigned32,
pdu2CktMonLineToLinekVAr Unsigned32
}
-- 1.3.6.1.4.1.3711.24.2.1.1.1.5.1.1
pdu2CktMonPduNumber OBJECT-TYPE
SYNTAX Unsigned32 --(0..1)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU index number."
::= { pdu2CircuitMonitorEntry 1 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.5.1.2
pdu2CktMonCircuitNumber OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Circuit Number."
::= { pdu2CircuitMonitorEntry 2 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.5.1.3
pdu2CktMonRS OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The circuit monitor table row status."
::= { pdu2CircuitMonitorEntry 3 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.5.1.4
pdu2CktMonLineID OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Line ID."
::= { pdu2CircuitMonitorEntry 4 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.5.1.5
pdu2CktMonLineToLineVoltage OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Circuit To Neutral Voltage. The value precision is tenths e.g. a value of 101 is 10.1 V."
::= { pdu2CircuitMonitorEntry 5 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.5.1.6
pdu2CktMonLineToLineCurrent OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Circuit Current. The value precision is thousandths e.g. a value of 1001 is 1.001 Amps."
::= { pdu2CircuitMonitorEntry 6 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.5.1.7
pdu2CktMonLineToLineKVA OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Circuit kVA. The value precision is hundredths e.g. a value of 101 is 1.01 kVA."
::= { pdu2CircuitMonitorEntry 7 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.5.1.8
pdu2CktMonLineToLinePeakkVA OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Circuit Peak KVA. The value precision is hundredths e.g. a value of 101 is 1.01 kVA."
::= { pdu2CircuitMonitorEntry 8 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.5.1.9
pdu2CktMonLineToLinePeakkVATimestamp OBJECT-TYPE
SYNTAX UnsignedTimeTicks
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Circuit Peak hKVA Timestamp."
::= { pdu2CircuitMonitorEntry 9 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.5.1.10
pdu2CktMonLineToLinekW OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Circuit hkW. The value precision is hundredths e.g. a value of 101 is 1.01 kW."
::= { pdu2CircuitMonitorEntry 10 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.5.1.11
pdu2CktMonLineToLinePF OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Circuit PF. The value precision is thousandths e.g. a value of 1001 is 1.001 PF."
::= { pdu2CircuitMonitorEntry 11 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.5.1.12
pdu2CktMonLineToLinekVAr OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Circuit kVAr. The value precision is hundredths e.g. a value of 101 is 1.01 kVAr."
::= { pdu2CircuitMonitorEntry 12 }
-- }}} End of pdu2CircuitMonitorTable table
-- {{{ pdu2BranchCircuitMonitorTable table
-- 1.3.6.1.4.1.3711.24.2.1.1.1.6
pdu2BranchCircuitMonitorTable OBJECT-TYPE
SYNTAX SEQUENCE OF Pdu2BranchCircuitMonitorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table giving branch circuit monitoring information for all PDUs."
::= { pdu2Common 6 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.6.1
pdu2BranchCircuitMonitorEntry OBJECT-TYPE
SYNTAX Pdu2BranchCircuitMonitorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A conceptual row containing information about branch circuit monitoring."
INDEX { pdu2BrCktMonPduNumber, pdu2BrCktMonBranchCircuitNumber }
::= { pdu2BranchCircuitMonitorTable 1 }
Pdu2BranchCircuitMonitorEntry ::= SEQUENCE {
pdu2BrCktMonPduNumber Unsigned32,
pdu2BrCktMonBranchCircuitNumber Unsigned32,
pdu2BrCktMonRS RowStatus,
pdu2BrCktMonBranchCircuitID DisplayString,
pdu2BrCktMonBranchCircuitPhases DisplayString,
pdu2BrCktMonBranchCircuitCurrent Unsigned32,
pdu2BrCktMonBranchCircuitPeakCurrent Unsigned32,
pdu2BrCktMonBranchCircuitPeakCurrentTimestamp UnsignedTimeTicks,
pdu2BrCktMonBranchCircuitBreakerStatus BranchCircuitStatusType,
pdu2BrCktMonBranchCircuitBreakerConfig BranchCircuitConfigType,
pdu2BrCktMonBranchCircuitBreakerTripState BranchCircuitStatusType,
pdu2BrCktMonBranchCircuitBreakerContinuousLoadRatingAmps Unsigned32,
pdu2BrCktMonBranchCircuitBreakerTripRatingAmps Unsigned32
}
-- 1.3.6.1.4.1.3711.24.2.1.1.1.6.1.1
pdu2BrCktMonPduNumber OBJECT-TYPE
SYNTAX Unsigned32 --(0..1)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU index number."
::= { pdu2BranchCircuitMonitorEntry 1 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.6.1.2
pdu2BrCktMonBranchCircuitNumber OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Branch Circuit Number."
::= { pdu2BranchCircuitMonitorEntry 2 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.6.1.3
pdu2BrCktMonRS OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The branch circuit monitor table row status."
::= { pdu2BranchCircuitMonitorEntry 3 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.6.1.4
pdu2BrCktMonBranchCircuitID OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Branch Circuit ID."
::= { pdu2BranchCircuitMonitorEntry 4 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.6.1.5
pdu2BrCktMonBranchCircuitPhases OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Branch Circuit Phases."
::= { pdu2BranchCircuitMonitorEntry 5 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.6.1.6
pdu2BrCktMonBranchCircuitCurrent OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Branch Circuit Current. The value precision is thousandths e.g. a value of 1001 is 1.001 Amps."
::= { pdu2BranchCircuitMonitorEntry 6 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.6.1.7
pdu2BrCktMonBranchCircuitPeakCurrent OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Branch Circuit Peak Current. The value precision is hundredths e.g. a value of 1001 is 1.001 Amps."
::= { pdu2BranchCircuitMonitorEntry 7 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.6.1.8
pdu2BrCktMonBranchCircuitPeakCurrentTimestamp OBJECT-TYPE
SYNTAX UnsignedTimeTicks
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Branch Circuit Peak Current Timestamp."
::= { pdu2BranchCircuitMonitorEntry 8 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.6.1.9
pdu2BrCktMonBranchCircuitBreakerStatus OBJECT-TYPE
SYNTAX BranchCircuitStatusType
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Branch Circuit Breaker Status."
::= { pdu2BranchCircuitMonitorEntry 9 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.6.1.10
pdu2BrCktMonBranchCircuitBreakerConfig OBJECT-TYPE
SYNTAX BranchCircuitConfigType
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The PDU Branch Circuit Breaker Config."
::= { pdu2BranchCircuitMonitorEntry 10 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.6.1.11
pdu2BrCktMonBranchCircuitBreakerTripState OBJECT-TYPE
SYNTAX BranchCircuitStatusType
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Branch Circuit Breaker Trip State."
::= { pdu2BranchCircuitMonitorEntry 11 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.6.1.12
pdu2BrCktMonBranchCircuitBreakerContinuousLoadRatingAmps OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Branch Circuit Breaker Continuous Load Rating Amps."
::= { pdu2BranchCircuitMonitorEntry 12 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.6.1.13
pdu2BrCktMonBranchCircuitBreakerTripRatingAmps OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU Branch Circuit Breaker Trip Rating Amps."
::= { pdu2BranchCircuitMonitorEntry 13 }
-- }}} End of pdu2BranchCircuitMonitorTable table
-- {{{ pdu2OutletMonitorTable table
-- 1.3.6.1.4.1.3711.24.2.1.1.1.7
pdu2OutletMonitorTable OBJECT-TYPE
SYNTAX SEQUENCE OF Pdu2OutletMonitorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table giving outlet monitoring information for all PDUs."
::= { pdu2Common 7 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.7.1
pdu2OutletMonitorEntry OBJECT-TYPE
SYNTAX Pdu2OutletMonitorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A conceptual row containing information about outlet monitoring."
INDEX { pdu2OutMonPduNumber, pdu2OutMonOutletNumber }
::= { pdu2OutletMonitorTable 1 }
Pdu2OutletMonitorEntry ::= SEQUENCE {
pdu2OutMonPduNumber Unsigned32,
pdu2OutMonOutletNumber Unsigned32,
pdu2OutMonRS RowStatus,
pdu2OutMonOutletID DisplayString,
pdu2OutMonOutletVoltage Unsigned32,
pdu2OutMonOutletCurrent Unsigned32,
pdu2OutMonOutletkVA Unsigned32,
pdu2OutMonOutletPeakkVA Unsigned32,
pdu2OutMonOutletPeakkVATimestamp UnsignedTimeTicks,
pdu2OutMonOutletkW Unsigned32,
pdu2OutMonOutletPF Unsigned32,
pdu2OutMonOutletkWh Unsigned32,
pdu2OutMonOutletBranchCircuitID DisplayString,
pdu2OutMonOutletPhaseID DisplayString
}
-- 1.3.6.1.4.1.3711.24.2.1.1.1.7.1.1
pdu2OutMonPduNumber OBJECT-TYPE
SYNTAX Unsigned32 --(0..1)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU index number."
::= { pdu2OutletMonitorEntry 1 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.7.1.2
pdu2OutMonOutletNumber OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU outlet number."
::= { pdu2OutletMonitorEntry 2 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.7.1.3
pdu2OutMonRS OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The outlet monitor table row status."
::= { pdu2OutletMonitorEntry 3 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.7.1.4
pdu2OutMonOutletID OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU outlet ID."
::= { pdu2OutletMonitorEntry 4 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.7.1.5
pdu2OutMonOutletVoltage OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU outlet voltage. The value precision is tenths e.g. a value of 101 is 1.01 V."
::= { pdu2OutletMonitorEntry 5 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.7.1.6
pdu2OutMonOutletCurrent OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU outlet current. The value precision is thousandths e.g. a value of 1001 is 1.001 Amps."
::= { pdu2OutletMonitorEntry 6 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.7.1.7
pdu2OutMonOutletkVA OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU outlet kVA. The value precision is hundredths e.g. a value of 101 is 1.01 kVA."
::= { pdu2OutletMonitorEntry 7 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.7.1.8
pdu2OutMonOutletPeakkVA OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU outlet peak kVA. The value precision is hundredths e.g. a value of 101 is 1.01 kVA."
::= { pdu2OutletMonitorEntry 8 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.7.1.9
pdu2OutMonOutletPeakkVATimestamp OBJECT-TYPE
SYNTAX UnsignedTimeTicks
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU outlet peak kVA timestamp."
::= { pdu2OutletMonitorEntry 9 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.7.1.10
pdu2OutMonOutletkW OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU outlet hkW. The value precision is hundredths e.g. a value of 101 is 1.01 kW."
::= { pdu2OutletMonitorEntry 10 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.7.1.11
pdu2OutMonOutletPF OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU outlet PF. The value precision is thousandths e.g. a value of 1001 is 1.001 PF."
::= { pdu2OutletMonitorEntry 11 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.7.1.12
pdu2OutMonOutletkWh OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU outlet kWh. The value precision is hundredths e.g. a value of 101 is 1.01 kWh."
::= { pdu2OutletMonitorEntry 12 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.7.1.13
pdu2OutMonOutletBranchCircuitID OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU outlet circuit ID."
::= { pdu2OutletMonitorEntry 13 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.7.1.14
pdu2OutMonOutletPhaseID OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU outlet phase ID."
::= { pdu2OutletMonitorEntry 14 }
-- }}} End of pdu2OutletMonitorTable table
-- {{{ pdu2OutletControlTable table
-- 1.3.6.1.4.1.3711.24.2.1.1.1.8
pdu2OutletControlTable OBJECT-TYPE
SYNTAX SEQUENCE OF Pdu2OutletControlEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table giving outlet control information for all PDUs."
::= { pdu2Common 8 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.8.1
pdu2OutletControlEntry OBJECT-TYPE
SYNTAX Pdu2OutletControlEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A conceptual row containing information about outlet control."
INDEX { pdu2OutCtlPduNumber, pdu2OutCtlOutletNumber }
::= { pdu2OutletControlTable 1 }
Pdu2OutletControlEntry ::= SEQUENCE {
pdu2OutCtlPduNumber Unsigned32,
pdu2OutCtlOutletNumber Unsigned32,
pdu2OutCtlRS RowStatus,
pdu2OutCtlControlledOutletID DisplayString,
pdu2OutCtlControlledOutletState ControlledOutletStatusType,
pdu2OutCtlControlledOutletPowerUpState ControlledOutletStatusType,
pdu2OutCtlControlledOutletPowerUpTimeDelay Unsigned32
}
-- 1.3.6.1.4.1.3711.24.2.1.1.1.8.1.1
pdu2OutCtlPduNumber OBJECT-TYPE
SYNTAX Unsigned32 --(0..1)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU index number."
::= { pdu2OutletControlEntry 1 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.8.1.2
pdu2OutCtlOutletNumber OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU outlet number."
::= { pdu2OutletControlEntry 2 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.8.1.3
pdu2OutCtlRS OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The outlet control table row status."
::= { pdu2OutletControlEntry 3 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.8.1.4
pdu2OutCtlControlledOutletID OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU controlled outlet ID."
::= { pdu2OutletControlEntry 4 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.8.1.5
pdu2OutCtlControlledOutletState OBJECT-TYPE
SYNTAX ControlledOutletStatusType
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU controlled outlet state."
::= { pdu2OutletControlEntry 5 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.8.1.6
pdu2OutCtlControlledOutletPowerUpState OBJECT-TYPE
SYNTAX ControlledOutletStatusType
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU controlled outlet power up state."
::= { pdu2OutletControlEntry 6 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.8.1.7
pdu2OutCtlControlledOutletPowerUpTimeDelay OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The PDU controlled outlet power up time delay."
::= { pdu2OutletControlEntry 7 }
-- }}} End of pdu2OutletControlTable table
-- {{{ pdu2ThreshTable
-- 1.3.6.1.4.1.3711.24.2.1.1.1.9
pdu2BranchCircuitThreshTable OBJECT-TYPE
SYNTAX SEQUENCE OF Pdu2BranchCircuitThreshEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table listing the alarm threshold information for each branch circuit."
::= { pdu2Common 9 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.9.1
pdu2BranchCircuitThreshEntry OBJECT-TYPE
SYNTAX Pdu2BranchCircuitThreshEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A conceptual row containing alarm threshold information about one branch circuit."
INDEX { pdu2BrCktThreshPduNumber, pdu2BrCktThreshBranchCircuitNumber }
::= { pdu2BranchCircuitThreshTable 1 }
Pdu2BranchCircuitThreshEntry ::= SEQUENCE {
pdu2BrCktThreshPduNumber Unsigned32,
pdu2BrCktThreshBranchCircuitNumber Unsigned32,
pdu2BrCktThreshRS RowStatus,
pdu2BrCktBranchCircuitCurrentUCL Unsigned32,
pdu2BrCktBranchCircuitCurrentUWL Unsigned32,
pdu2BrCktBranchCircuitCurrentLWL Unsigned32,
pdu2BrCktBranchCircuitCurrentLCL Unsigned32
}
-- 1.3.6.1.4.1.3711.24.2.1.1.1.9.1.1
pdu2BrCktThreshPduNumber OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of the PDU on which the branch circuit resides."
::= { pdu2BranchCircuitThreshEntry 1 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.9.1.2
pdu2BrCktThreshBranchCircuitNumber OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The branch circuit number."
::= { pdu2BranchCircuitThreshEntry 2 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.9.1.3
pdu2BrCktThreshRS OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The table row status."
::= { pdu2BranchCircuitThreshEntry 3 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.9.1.4
pdu2BrCktBranchCircuitCurrentUCL OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Branch Circuit Current UCL. The value precision is thousandths e.g. a value of 1001 is 1.001 Amps."
::= { pdu2BranchCircuitThreshEntry 4 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.9.1.5
pdu2BrCktBranchCircuitCurrentUWL OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Branch Circuit Current UWL. The value precision is thousandths e.g. a value of 1001 is 1.001 Amps."
::= { pdu2BranchCircuitThreshEntry 5 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.9.1.6
pdu2BrCktBranchCircuitCurrentLWL OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Branch Circuit Current LWL. The value precision is thousandths e.g. a value of 1001 is 1.001 Amps."
::= { pdu2BranchCircuitThreshEntry 6 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.9.1.7
pdu2BrCktBranchCircuitCurrentLCL OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Branch Circuit Current LCL. The value precision is thousandths e.g. a value of 1001 is 1.001 Amps."
::= { pdu2BranchCircuitThreshEntry 7 }
-- }}} End of pdu2ThreshTable
-- {{{ pdu2TrapEnTable
-- 1.3.6.1.4.1.3711.24.2.1.1.1.10
pdu2BranchCircuitTrapEnTable OBJECT-TYPE
SYNTAX SEQUENCE OF Pdu2BranchCircuitTrapEnEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table listing the trap enabling information for each branch circuit."
::= { pdu2Common 10 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.10.1
pdu2BranchCircuitTrapEnEntry OBJECT-TYPE
SYNTAX Pdu2BranchCircuitTrapEnEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A conceptual row containing trap enabling information about one branch circuit."
INDEX { pdu2BrCktTrapEnPduNumber, pdu2BrCktTrapEnBranchCircuitNumber }
::= { pdu2BranchCircuitTrapEnTable 1 }
Pdu2BranchCircuitTrapEnEntry ::= SEQUENCE {
pdu2BrCktTrapEnPduNumber Unsigned32,
pdu2BrCktTrapEnBranchCircuitNumber Unsigned32,
pdu2BrCktTrapEnRS RowStatus,
pdu2BrCktBranchCircuitCurrentUCLTrapEn TruthValue,
pdu2BrCktBranchCircuitCurrentUWLTrapEn TruthValue,
pdu2BrCktBranchCircuitCurrentLWLTrapEn TruthValue,
pdu2BrCktBranchCircuitCurrentLCLTrapEn TruthValue
}
-- 1.3.6.1.4.1.3711.24.2.1.1.1.10.1.1
pdu2BrCktTrapEnPduNumber OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of the PDU on which the branch circuit resides."
::= { pdu2BranchCircuitTrapEnEntry 1 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.10.1.2
pdu2BrCktTrapEnBranchCircuitNumber OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The branch circuit number."
::= { pdu2BranchCircuitTrapEnEntry 2 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.10.1.3
pdu2BrCktTrapEnRS OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The table row status."
::= { pdu2BranchCircuitTrapEnEntry 3 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.10.1.4
pdu2BrCktBranchCircuitCurrentUCLTrapEn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Trap enable flag for pdu2BrCktBranchCircuitCurrentUCL."
::= { pdu2BranchCircuitTrapEnEntry 4 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.10.1.5
pdu2BrCktBranchCircuitCurrentUWLTrapEn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Trap enable flag for pdu2BrCktBranchCircuitCurrentUWL."
::= { pdu2BranchCircuitTrapEnEntry 5 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.10.1.6
pdu2BrCktBranchCircuitCurrentLWLTrapEn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Trap enable flag for pdu2BrCktBranchCircuitCurrentLWL."
::= { pdu2BranchCircuitTrapEnEntry 6 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.10.1.7
pdu2BrCktBranchCircuitCurrentLCLTrapEn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Trap enable flag for pdu2BrCktBranchCircuitCurrentLCL."
::= { pdu2BranchCircuitTrapEnEntry 7 }
-- }}} End of pdu2TrapEnTable
-- {{{ pdu2TrapPerTable
-- 1.3.6.1.4.1.3711.24.2.1.1.1.11
pdu2BranchCircuitTrapPerTable OBJECT-TYPE
SYNTAX SEQUENCE OF Pdu2BranchCircuitTrapPerEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table listing the trap repetition periods for each branch circuit on the PDUs."
::= { pdu2Common 11 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.11.1
pdu2BranchCircuitTrapPerEntry OBJECT-TYPE
SYNTAX Pdu2BranchCircuitTrapPerEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A conceptual row containing trap repetition periods for one branch circuit."
INDEX { pdu2BrCktTrapPerPduNumber, pdu2BrCktTrapPerBranchCircuitNumber }
::= { pdu2BranchCircuitTrapPerTable 1 }
Pdu2BranchCircuitTrapPerEntry ::= SEQUENCE {
pdu2BrCktTrapPerPduNumber Unsigned32,
pdu2BrCktTrapPerBranchCircuitNumber Unsigned32,
pdu2BrCktTrapPerRS RowStatus,
pdu2BrCktBranchCircuitCurrentUCLTrapPer Unsigned32,
pdu2BrCktBranchCircuitCurrentUWLTrapPer Unsigned32,
pdu2BrCktBranchCircuitCurrentLWLTrapPer Unsigned32,
pdu2BrCktBranchCircuitCurrentLCLTrapPer Unsigned32
}
-- 1.3.6.1.4.1.3711.24.2.1.1.1.11.1.1
pdu2BrCktTrapPerPduNumber OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of the PDU on which the branch circuit resides."
::= { pdu2BranchCircuitTrapPerEntry 1 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.11.1.2
pdu2BrCktTrapPerBranchCircuitNumber OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The outlet number."
::= { pdu2BranchCircuitTrapPerEntry 2 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.11.1.3
pdu2BrCktTrapPerRS OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The table row status."
::= { pdu2BranchCircuitTrapPerEntry 3 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.11.1.4
pdu2BrCktBranchCircuitCurrentUCLTrapPer OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Trap repetition period for pdu2BrCktBranchCircuitCurrentUCL."
::= { pdu2BranchCircuitTrapPerEntry 4 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.11.1.5
pdu2BrCktBranchCircuitCurrentUWLTrapPer OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Trap repetition period for pdu2BrCktBranchCircuitCurrentUWL."
::= { pdu2BranchCircuitTrapPerEntry 5 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.11.1.6
pdu2BrCktBranchCircuitCurrentLWLTrapPer OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Trap repetition period for pdu2BrCktBranchCircuitCurrentLWL."
::= { pdu2BranchCircuitTrapPerEntry 6 }
-- 1.3.6.1.4.1.3711.24.2.1.1.1.11.1.7
pdu2BrCktBranchCircuitCurrentLCLTrapPer OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Trap repetition period for pdu2BrCktBranchCircuitCurrentLCL."
::= { pdu2BranchCircuitTrapPerEntry 7 }
-- }}} End of pdu2TrapEnTable
-- }}} End of pdu2Common group
-- END SECTION PDU2
END