ENVSEMS2D DEFINITIONS ::= BEGIN
IMPORTS
NOTIFICATION-GROUP, OBJECT-GROUP FROM SNMPv2-CONF
MODULE-IDENTITY, OBJECT-TYPE,
NOTIFICATION-TYPE, enterprises,
Integer32 FROM SNMPv2-SMI
DisplayString, TEXTUAL-CONVENTION FROM SNMPv2-TC;
UtfDisplay ::= TEXTUAL-CONVENTION
DISPLAY-HINT "t"
STATUS current
SYNTAX DisplayString
envSems MODULE-IDENTITY
LAST-UPDATED "201403251400Z"
ORGANIZATION "Network Technologies Inc."
CONTACT-INFO
"Network Technologies Inc.
Postal: 1275 Danner Dr,
Aurora, OH 442022
US
Tel: 330-562-7070
Fax: 330-562-1999
WEB: www.networktechinc.com"
DESCRIPTION
"ENVIROMUX-SEMS-2D MIB file."
REVISION "201403251400Z"
DESCRIPTION "Rev. 1.02- added support to change relay status using SNMP"
REVISION "201211121400Z"
DESCRIPTION "Rev. 1.01 - added remote inputs and remote relays"
REVISION "201201050000Z"
DESCRIPTION "Rev. 1.00 - initial version"
::= { hardware 9 }
-- the root of the subtree for Network Technologies Inc
nti OBJECT IDENTIFIER ::= { enterprises 3699 }
-- subtree for products
products OBJECT IDENTIFIER ::= { nti 1 }
hardware OBJECT IDENTIFIER ::= { products 1 }
software OBJECT IDENTIFIER ::= { products 2 }
otherProduct OBJECT IDENTIFIER ::= { hardware 200 }
-- ipdus2 subtree
masterUnit OBJECT IDENTIFIER ::= { envSems 1 }
envTraps OBJECT IDENTIFIER ::= { envSems 100 }
hostSystem OBJECT IDENTIFIER ::= { masterUnit 1 }
users OBJECT IDENTIFIER ::= { masterUnit 2 }
groups OBJECT IDENTIFIER ::= { masterUnit 3 }
dewPointSensors OBJECT IDENTIFIER ::= { masterUnit 4 }
extSensors OBJECT IDENTIFIER ::= { masterUnit 5 }
digInputs OBJECT IDENTIFIER ::= { masterUnit 6 }
ipDevices OBJECT IDENTIFIER ::= { masterUnit 7 }
outRelays OBJECT IDENTIFIER ::= { masterUnit 8 }
pwrSupplies OBJECT IDENTIFIER ::= { masterUnit 9 }
events OBJECT IDENTIFIER ::= { masterUnit 10 }
smartAlerts OBJECT IDENTIFIER ::= { masterUnit 11 }
remoteInputs OBJECT IDENTIFIER ::= { masterUnit 12 }
remoteRelays OBJECT IDENTIFIER ::= { masterUnit 13 }
envGroups OBJECT IDENTIFIER ::= { masterUnit 200 }
-- groups
sysGroup OBJECT-GROUP
OBJECTS { sysTime, sysEnterpriseName, sysEnterpriseLocation, sysEnterpriseContact, sysEnterprisePhone }
STATUS current
DESCRIPTION "System parameters group"
::= {envGroups 1}
extSensorsGrp OBJECT-GROUP
OBJECTS { extSensorIndex, extSensorType, extSensorDescription, extSensorConnector, extSensorGroupNb, extSensorGroup,
extSensorValue, extSensorUnit, extSensorUnitName, extSensorStatus, extSensorMinThreshold, extSensorMaxThreshold }
STATUS current
DESCRIPTION "External sensors group"
::= {envGroups 3}
digInputsGrp OBJECT-GROUP
OBJECTS { digInputIndex, digInputType, digInputDescription, digInputConnector, digInputGroupNb, digInputGroup,
digInputValue, digInputStatus, digInputNormalValue }
STATUS current
DESCRIPTION "Dry contacts group"
::= {envGroups 5}
ipDeviceGrp OBJECT-GROUP
OBJECTS { ipDeviceIndex, ipDeviceAddress, ipDeviceDescription, ipDeviceGroupNb, ipDeviceGroup, ipDeviceTimeout, ipDeviceRetries,
ipDeviceValue, ipDeviceStatus }
STATUS current
DESCRIPTION "IP devices group"
::= {envGroups 6}
outRelaysGrp OBJECT-GROUP
OBJECTS { outRelayIndex, outRelayDescription, outRelayStatus }
STATUS current
DESCRIPTION "Dry contacts group"
::= {envGroups 7}
miscTrapFields OBJECT-GROUP
OBJECTS { envTrapDescription, envTrapValue }
STATUS current
DESCRIPTION "General Information Traps"
::= {envGroups 8}
extSensorTrapGrp NOTIFICATION-GROUP
NOTIFICATIONS { extSensor1Trap, extSensor2Trap, extSensor3Trap, extSensor4Trap }
STATUS current
DESCRIPTION "External Sensors Traps Group"
::= {envGroups 10}
digInputTrapGrp NOTIFICATION-GROUP
NOTIFICATIONS { digInput1Trap, digInput2Trap, digInput3Trap, digInput4Trap, digInput5Trap }
STATUS current
DESCRIPTION "External Sensors Traps Group"
::= {envGroups 12}
ipDeviceTrapGrp NOTIFICATION-GROUP
NOTIFICATIONS { ipDevice1Trap, ipDevice2Trap, ipDevice3Trap, ipDevice4Trap, ipDevice5Trap, ipDevice6Trap, ipDevice7Trap, ipDevice8Trap,
ipDevice9Trap, ipDevice10Trap, ipDevice11Trap, ipDevice12Trap, ipDevice13Trap, ipDevice14Trap, ipDevice15Trap, ipDevice16Trap }
STATUS current
DESCRIPTION "IP Device Traps Group"
::= {envGroups 13}
miscNotificationGrp NOTIFICATION-GROUP
NOTIFICATIONS { evLogFileTrap, dataLogFileTrap, remoteDataLogFileTrap}
STATUS current
DESCRIPTION "Other Traps Group"
::= {envGroups 14}
pwrSuppliesGrp NOTIFICATION-GROUP
NOTIFICATIONS { pwrSupplyIndex, pwrSupplyStatus }
STATUS current
DESCRIPTION "Power supplies group"
::= {envGroups 15}
-- hostSystem subtree
sysTime OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "System time"
::= { hostSystem 1 }
sysEnterpriseName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Enterprise Name"
::= { hostSystem 2 }
sysEnterpriseLocation OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Enterprise Location"
::= { hostSystem 3 }
sysEnterpriseContact OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Enterprise Contact"
::= { hostSystem 4 }
sysEnterprisePhone OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Enterprise Phone"
::= { hostSystem 5 }
-- external Dew point sensors description
dewPointSensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF DewPointSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Table of Dew point sensors entries"
::= { dewPointSensors 1 }
dewPointSensorEntry OBJECT-TYPE
SYNTAX DewPointSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "A dew point sensor entry"
INDEX { dewPointSensorIndex }
::= { dewPointSensorTable 1 }
DewPointSensorEntry ::=
SEQUENCE {
dewPointSensorIndex
Integer32,
dewPointSensorType
INTEGER,
dewPointSensorDescription
DisplayString,
dewPointSensorConnector
Integer32,
dewPointSensorGroupNb
Integer32,
dewPointSensorGroup
DisplayString,
dewPointSensorValue
INTEGER,
dewPointSensorUnit
Integer32,
dewPointSensorUnitName
DisplayString,
dewPointSensorStatus
INTEGER,
dewPointSensorMinThreshold
Integer32,
dewPointSensorMaxThreshold
Integer32
}
dewPointSensorIndex OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION "The index of the Dew point sensor entry 1..4"
::= { dewPointSensorEntry 1 }
dewPointSensorType OBJECT-TYPE
SYNTAX INTEGER { undefined(0), dewPoint(24) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Dew point Sensor Type"
::= { dewPointSensorEntry 2 }
dewPointSensorDescription OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Dew point Sensor Description"
::= { dewPointSensorEntry 3 }
dewPointSensorConnector OBJECT-TYPE
SYNTAX Integer32 (1..16)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Connector where the Dew point sensor is attached"
::= { dewPointSensorEntry 4 }
dewPointSensorGroupNb OBJECT-TYPE
SYNTAX Integer32 (1..8)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Dew point Sensor's Group"
::= { dewPointSensorEntry 5 }
dewPointSensorGroup OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Dew point Sensor's Group Name"
::= { dewPointSensorEntry 6 }
dewPointSensorValue OBJECT-TYPE
SYNTAX INTEGER { closed(0), open(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The value of the Dew point sensor reading. It is presented in tenths of degrees"
::= { dewPointSensorEntry 7 }
dewPointSensorUnit OBJECT-TYPE
SYNTAX Integer32 (0..1)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The measuremnet unit for this sensor. Can be Celsius or Fahrenheit"
::= { dewPointSensorEntry 8 }
dewPointSensorUnitName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The measuremnet unit for this sensor in readable format"
::= { dewPointSensorEntry 9 }
dewPointSensorStatus OBJECT-TYPE
SYNTAX INTEGER {notconnected(0), normal(1), prealert(2), alert(3), acknowledged(4), dismissed(5), disconnected(6) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The status of the Dew point sensor"
::= { dewPointSensorEntry 10 }
dewPointSensorMinThreshold OBJECT-TYPE
SYNTAX Integer32 (0..1000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The value of the sensor lower threshold"
::= { dewPointSensorEntry 11 }
dewPointSensorMaxThreshold OBJECT-TYPE
SYNTAX Integer32 (0..1000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The value of the sensor upper threshold"
::= { dewPointSensorEntry 12 }
-- external sensors description
extSensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF ExtSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Table of external Sensors entries"
::= { extSensors 1 }
extSensorEntry OBJECT-TYPE
SYNTAX ExtSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "An external sensor entry"
INDEX { extSensorIndex }
::= { extSensorTable 1 }
ExtSensorEntry ::=
SEQUENCE {
extSensorIndex
Integer32,
extSensorType
INTEGER,
extSensorDescription
DisplayString,
extSensorConnector
Integer32,
extSensorGroupNb
Integer32,
extSensorGroup
DisplayString,
extSensorValue
INTEGER,
extSensorUnit
Integer32,
extSensorUnitName
DisplayString,
extSensorStatus
INTEGER,
extSensorMinThreshold
Integer32,
extSensorMaxThreshold
Integer32
}
extSensorIndex OBJECT-TYPE
SYNTAX Integer32 (1..4)
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION "The index of the external sensor entry 1..4"
::= { extSensorEntry 1 }
extSensorType OBJECT-TYPE
SYNTAX INTEGER { undefined(0), temperature(1), humidity(2), power(3), lowVoltage(4), current(5), aclmvVoltage(6), aclmpVoltage(7), aclmpPower(8),water(9), smoke(10), vibration(11), motion(12), glass(13), door(14), keypad(15), panicButton(16), keyStation(17), digInput(18), light(22), tempHum(513), custom(32767), temperatureCombo(32769), humidityCombo(32770) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Sensor Type"
::= { extSensorEntry 2 }
extSensorDescription OBJECT-TYPE
SYNTAX UtfDisplay
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Sensor Description"
::= { extSensorEntry 3 }
extSensorConnector OBJECT-TYPE
SYNTAX Integer32 (1..2)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Connector where the sensor is attached"
::= { extSensorEntry 4 }
extSensorGroupNb OBJECT-TYPE
SYNTAX Integer32 (1..2)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Sensor's Group"
::= { extSensorEntry 5 }
extSensorGroup OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Sensor's Group Name"
::= { extSensorEntry 6 }
extSensorValue OBJECT-TYPE
SYNTAX INTEGER { closed(0), open(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The value of the external sensor reading. For temperature, voltage, current or low voltage, it is presented in tenths of degrees/volts"
::= { extSensorEntry 7 }
extSensorUnit OBJECT-TYPE
SYNTAX Integer32 (0..1)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The measuremnet unit for this sensor. It is important only for temperature"
::= { extSensorEntry 8 }
extSensorUnitName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The measuremnet unit for this sensor in readable format"
::= { extSensorEntry 9 }
extSensorStatus OBJECT-TYPE
SYNTAX INTEGER {notconnected(0), normal(1), prealert(2), alert(3), acknowledged(4), dismissed(5), disconnected(6) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The status of the sensor"
::= { extSensorEntry 10 }
extSensorMinThreshold OBJECT-TYPE
SYNTAX Integer32 (0..1000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The value of the sensor lower threshold"
::= { extSensorEntry 11 }
extSensorMaxThreshold OBJECT-TYPE
SYNTAX Integer32 (0..1000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The value of the sensor upper threshold"
::= { extSensorEntry 12 }
extSensorAclmTable OBJECT-TYPE
SYNTAX SEQUENCE OF ExtSensorAclmValues
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Table of external Sensors entries"
::= { extSensors 2 }
extSensorAclmValues OBJECT-TYPE
SYNTAX ExtSensorAclmValues
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "An external sensor entry"
INDEX { extSensorAclmIndex }
::= { extSensorAclmTable 1 }
ExtSensorAclmValues ::=
SEQUENCE {
extSensorAclmIndex
Integer32,
extSensorPeakValue
Integer32,
extSensorFrequency
Integer32,
extSensorCurrent
Integer32,
extSensorSpikes
Integer32,
extSensorSwells
Integer32,
extSensorSags
Integer32,
extSensorRelay
INTEGER
}
extSensorAclmIndex OBJECT-TYPE
SYNTAX Integer32 (0..1000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Index of the sensor in the list"
::= { extSensorAclmValues 1 }
extSensorPeakValue OBJECT-TYPE
SYNTAX Integer32 (0..1000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The peak value of the ACLM sensor presensted in tenths of volts/watts"
::= { extSensorAclmValues 2 }
extSensorFrequency OBJECT-TYPE
SYNTAX Integer32 (0..1000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Frequency measured by the ACLM sensor presensted in tenths of Hz"
::= { extSensorAclmValues 3 }
extSensorCurrent OBJECT-TYPE
SYNTAX Integer32 (0..1000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Current measured by the ACLM sensor presensted in tenths of A(mpers)"
::= { extSensorAclmValues 4 }
extSensorSpikes OBJECT-TYPE
SYNTAX Integer32 (0..1000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of spikes read"
::= { extSensorAclmValues 5 }
extSensorSwells OBJECT-TYPE
SYNTAX Integer32 (0..1000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of swells read"
::= { extSensorAclmValues 6 }
extSensorSags OBJECT-TYPE
SYNTAX Integer32 (0..1000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of sags read"
::= { extSensorAclmValues 7 }
extSensorRelay OBJECT-TYPE
SYNTAX INTEGER { closed(0), open(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Relay status"
::= { extSensorAclmValues 8 }
-- dry contacts description
digInputTable OBJECT-TYPE
SYNTAX SEQUENCE OF DryContactEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Table of external Sensors entries"
::= { digInputs 1 }
digInputEntry OBJECT-TYPE
SYNTAX DryContactEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "A dry contact entry"
INDEX { digInputIndex }
::= { digInputTable 1 }
DryContactEntry ::=
SEQUENCE {
digInputIndex
Integer32,
digInputType
INTEGER,
digInputDescription
DisplayString,
digInputConnector
Integer32,
digInputGroupNb
Integer32,
digInputGroup
DisplayString,
digInputValue
INTEGER,
digInputStatus
INTEGER,
digInputNormalValue
INTEGER
}
digInputIndex OBJECT-TYPE
SYNTAX Integer32 (1..5)
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION "The index of the external sensor entry 1..4"
::= { digInputEntry 1 }
digInputType OBJECT-TYPE
SYNTAX INTEGER { digInput(18) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Sensor Type. Only dry contact type will be used"
::= { digInputEntry 2 }
digInputDescription OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Sensor Description"
::= { digInputEntry 3 }
digInputConnector OBJECT-TYPE
SYNTAX Integer32 (1..2)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Connector where the sensor is attached"
::= { digInputEntry 4 }
digInputGroupNb OBJECT-TYPE
SYNTAX Integer32 (1..2)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Sensor's Group"
::= { digInputEntry 5 }
digInputGroup OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Sensor's Group Name"
::= { digInputEntry 6 }
digInputValue OBJECT-TYPE
SYNTAX INTEGER { closed(0), open(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The value of the dry contact reading."
::= { digInputEntry 7 }
digInputStatus OBJECT-TYPE
SYNTAX INTEGER {notconnected(0), normal(1), prealert(2), alert(3), acknowledged(4), dismissed(5), disconnected(6) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The status of the sensor"
::= { digInputEntry 8 }
digInputNormalValue OBJECT-TYPE
SYNTAX INTEGER { closed(0), open(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The normal value of the dry contact reading"
::= { digInputEntry 9 }
-- remote inputs description
remoteInputTable OBJECT-TYPE
SYNTAX SEQUENCE OF RemoteInputEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Table of Remote Inputs entries"
::= { remoteInputs 1 }
remoteInputEntry OBJECT-TYPE
SYNTAX RemoteInputEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "A remote input entry"
INDEX { remoteInputIndex }
::= { remoteInputTable 1 }
RemoteInputEntry ::=
SEQUENCE {
remoteInputIndex
Integer32,
remoteInputType
INTEGER,
remoteInputDescription
DisplayString,
remoteInputConnector
Integer32,
remoteInputGroupNb
Integer32,
remoteInputGroup
DisplayString,
remoteInputValue
INTEGER,
remoteInputStatus
INTEGER,
remoteInputNormalValue
INTEGER
}
remoteInputIndex OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION "The index of the remote input entry 1..4"
::= { remoteInputEntry 1 }
remoteInputType OBJECT-TYPE
SYNTAX INTEGER { remoteInput(18) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Sensor Type. Remote input contact type will be used"
::= { remoteInputEntry 2 }
remoteInputDescription OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Sensor Description"
::= { remoteInputEntry 3 }
remoteInputConnector OBJECT-TYPE
SYNTAX Integer32 (1..256)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Connector where the sensor is attached"
::= { remoteInputEntry 4 }
remoteInputGroupNb OBJECT-TYPE
SYNTAX Integer32 (1..8)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Sensor's Group"
::= { remoteInputEntry 5 }
remoteInputGroup OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Sensor's Group Name"
::= { remoteInputEntry 6 }
remoteInputValue OBJECT-TYPE
SYNTAX INTEGER { closed(0), open(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The value of the remote input reading."
::= { remoteInputEntry 7 }
remoteInputStatus OBJECT-TYPE
SYNTAX INTEGER {notconnected(0), normal(1), prealert(2), alert(3), acknowledged(4), dismissed(5), disconnected(6) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The status of the sensor"
::= { remoteInputEntry 8 }
remoteInputNormalValue OBJECT-TYPE
SYNTAX INTEGER { closed(0), open(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The normal value of the remote input reading"
::= { remoteInputEntry 9 }
-- IP Devices description
ipDeviceTable OBJECT-TYPE
SYNTAX SEQUENCE OF IpDeviceEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Table of IP Devices entries"
::= { ipDevices 1 }
ipDeviceEntry OBJECT-TYPE
SYNTAX IpDeviceEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "An IP Device entry"
INDEX { ipDeviceIndex }
::= { ipDeviceTable 1 }
IpDeviceEntry ::=
SEQUENCE {
ipDeviceIndex
Integer32,
ipDeviceAddress
DisplayString,
ipDeviceDescription
DisplayString,
ipDeviceGroupNb
Integer32,
ipDeviceGroup
DisplayString,
ipDeviceTimeout
Integer32,
ipDeviceRetries
Integer32,
ipDeviceValue
INTEGER,
ipDeviceStatus
INTEGER
}
ipDeviceIndex OBJECT-TYPE
SYNTAX Integer32 (1..8)
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION "The index of the IP Device entry 1..8"
::= { ipDeviceEntry 1 }
ipDeviceAddress OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "IP Device URL"
::= { ipDeviceEntry 2 }
ipDeviceDescription OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "IP Device Description"
::= { ipDeviceEntry 3 }
ipDeviceGroupNb OBJECT-TYPE
SYNTAX Integer32 (1..2)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Index of the group the IP Device belongs to"
::= { ipDeviceEntry 4 }
ipDeviceGroup OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Name of the group the IP Device belongs to"
::= { ipDeviceEntry 5 }
ipDeviceTimeout OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "IP Device ping timeout (in seconds)"
::= { ipDeviceEntry 6 }
ipDeviceRetries OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of ping retries to the IP device, until responding"
::= { ipDeviceEntry 7 }
ipDeviceValue OBJECT-TYPE
SYNTAX INTEGER { notResponding(0), responding(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Responding status"
::= { ipDeviceEntry 8 }
ipDeviceStatus OBJECT-TYPE
SYNTAX INTEGER {notconnected(0), normal(1), prealert(2), alert(3), acknowledged(4), dismissed(5), disconnected(6) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Alarm status of the IP Device"
::= { ipDeviceEntry 9 }
-- outRelays description
outRelayTable OBJECT-TYPE
SYNTAX SEQUENCE OF OutRelayEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Table of output relays"
::= { outRelays 1 }
outRelayEntry OBJECT-TYPE
SYNTAX OutRelayEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "An output relay entry"
INDEX { outRelayIndex }
::= { outRelayTable 1 }
OutRelayEntry ::=
SEQUENCE {
outRelayIndex
Integer32,
outRelayDescription
DisplayString,
outRelayStatus
INTEGER
}
outRelayIndex OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION "The index of relay"
::= { outRelayEntry 1 }
outRelayDescription OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Desciption/name associated with the output relay"
::= { outRelayEntry 2 }
outRelayStatus OBJECT-TYPE
SYNTAX INTEGER { active(0), inactive(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION "The status of the output relay"
::= { outRelayEntry 3 }
-- remoteRelays description
remoteRelayTable OBJECT-TYPE
SYNTAX SEQUENCE OF RemoteRelayEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Table of remote relays"
::= { remoteRelays 1 }
remoteRelayEntry OBJECT-TYPE
SYNTAX RemoteRelayEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "An output relay entry"
INDEX { remoteRelayIndex }
::= { remoteRelayTable 1 }
RemoteRelayEntry ::=
SEQUENCE {
remoteRelayIndex
Integer32,
remoteRelayDescription
DisplayString,
remoteRelayStatus
INTEGER
}
remoteRelayIndex OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION "The index of relay"
::= { remoteRelayEntry 1 }
remoteRelayDescription OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Desciption/name associated with the remote relay"
::= { remoteRelayEntry 2 }
remoteRelayStatus OBJECT-TYPE
SYNTAX INTEGER { active(0), inactive(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION "The status of the remote relay"
::= { remoteRelayEntry 3 }
-- powerSupply description
pwrSupplyTable OBJECT-TYPE
SYNTAX SEQUENCE OF PwrSupplyEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Table of power supplies"
::= { pwrSupplies 1 }
pwrSupplyEntry OBJECT-TYPE
SYNTAX PwrSupplyEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "An output relay entry"
INDEX { pwrSupplyIndex }
::= { pwrSupplyTable 1 }
PwrSupplyEntry ::=
SEQUENCE {
pwrSupplyIndex
Integer32,
pwrSupplyStatus
INTEGER
}
pwrSupplyIndex OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION "The index of power supply"
::= { pwrSupplyEntry 1 }
pwrSupplyStatus OBJECT-TYPE
SYNTAX INTEGER { failed(0), ok(1), na(2) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The status of the output relay"
::= { pwrSupplyEntry 2 }
-- events description
eventTable OBJECT-TYPE
SYNTAX SEQUENCE OF EventEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Table of events"
::= { events 1 }
eventEntry OBJECT-TYPE
SYNTAX EventEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "An event entry"
INDEX { eventIndex }
::= { eventTable 1 }
EventEntry ::=
SEQUENCE {
eventIndex
Integer32,
eventDescription
DisplayString,
eventStatus
INTEGER
}
eventIndex OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION "The index of the event"
::= { eventEntry 1 }
eventDescription OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Desciption/name associated with the event"
::= { eventEntry 2 }
eventStatus OBJECT-TYPE
SYNTAX INTEGER { normal(1), alert(3), acknowledged(4), dismissed(5) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The status of the event"
::= { eventEntry 3 }
-- smartAlerts description
smartAlertTable OBJECT-TYPE
SYNTAX SEQUENCE OF SmartAlertEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Table of smartAlerts"
::= { smartAlerts 1 }
smartAlertEntry OBJECT-TYPE
SYNTAX SmartAlertEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "A smartAlert entry"
INDEX { smartAlertIndex }
::= { smartAlertTable 1 }
SmartAlertEntry ::=
SEQUENCE {
smartAlertIndex
Integer32,
smartAlertDescription
DisplayString,
smartAlertStatus
INTEGER
}
smartAlertIndex OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION "The index of the smartAlert"
::= { smartAlertEntry 1 }
smartAlertDescription OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Desciption/name associated with the smartAlert"
::= { smartAlertEntry 2 }
smartAlertStatus OBJECT-TYPE
SYNTAX INTEGER { normal(1), alert(3), acknowledged(4), dismissed(5) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The status of the smartAlert"
::= { smartAlertEntry 3 }
-- Trap Definitions
extSensorsTraps OBJECT IDENTIFIER ::= { envTraps 5 }
waterSensorsTraps OBJECT IDENTIFIER ::= { envTraps 6 }
digInputsTraps OBJECT IDENTIFIER ::= { envTraps 7 }
ipDevicesTraps OBJECT IDENTIFIER ::= { envTraps 8 }
outRelaysTraps OBJECT IDENTIFIER ::= { envTraps 9 }
envTrapDescription OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Message issued together with the trap to explain the reason the trap was sent"
::= { envTraps 100 }
envTrapValue OBJECT-TYPE
SYNTAX Integer32 (-1000..1000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Message issued together with the trap to retrieve a value"
::= { envTraps 101 }
-- sensor traps
-- External sensors traps
extSensor1Trap NOTIFICATION-TYPE
OBJECTS { envTrapDescription, extSensorIndex, extSensorDescription, extSensorValue, extSensorUnitName, extSensorStatus }
STATUS current
DESCRIPTION "Trap issued when external sensor 1 (Connector #1) has a notification to send"
::= {extSensorsTraps 0 1 }
extSensor2Trap NOTIFICATION-TYPE
OBJECTS { envTrapDescription, extSensorIndex, extSensorDescription, extSensorValue, extSensorUnitName, extSensorStatus }
STATUS current
DESCRIPTION "Trap issued when external sensor 2 (Connector #1) has a notification to send"
::= {extSensorsTraps 0 2 }
extSensor3Trap NOTIFICATION-TYPE
OBJECTS { envTrapDescription, extSensorIndex, extSensorDescription, extSensorValue, extSensorUnitName, extSensorStatus }
STATUS current
DESCRIPTION "Trap issued when external sensor 3 (Connector #2) has a notification to send"
::= {extSensorsTraps 0 3 }
extSensor4Trap NOTIFICATION-TYPE
OBJECTS { envTrapDescription, extSensorIndex, extSensorDescription, extSensorValue, extSensorUnitName, extSensorStatus }
STATUS current
DESCRIPTION "Trap issued when external sensor 4 (Connector #2) has a notification to send"
::= {extSensorsTraps 0 4 }
-- Dry contacts traps
digInput1Trap NOTIFICATION-TYPE
OBJECTS { envTrapDescription, digInputIndex, digInputDescription, digInputValue, digInputStatus }
STATUS current
DESCRIPTION "Trap issued when dry contact 1 (Connector #1) has a notification to send"
::= {digInputsTraps 0 1 }
digInput2Trap NOTIFICATION-TYPE
OBJECTS { envTrapDescription, digInputIndex, digInputDescription, digInputValue, digInputStatus }
STATUS current
DESCRIPTION "Trap issued when dry contact 2 (Connector #2) has a notification to send"
::= {digInputsTraps 0 2 }
digInput3Trap NOTIFICATION-TYPE
OBJECTS { envTrapDescription, digInputIndex, digInputDescription, digInputValue, digInputStatus }
STATUS current
DESCRIPTION "Trap issued when dry contact 3 (Connector #3) has a notification to send"
::= {digInputsTraps 0 3 }
digInput4Trap NOTIFICATION-TYPE
OBJECTS { envTrapDescription, digInputIndex, digInputDescription, digInputValue, digInputStatus }
STATUS current
DESCRIPTION "Trap issued when dry contact 4 (Connector #4) has a notification to send"
::= {digInputsTraps 0 4 }
digInput5Trap NOTIFICATION-TYPE
OBJECTS { envTrapDescription, digInputIndex, digInputDescription, digInputValue, digInputStatus }
STATUS current
DESCRIPTION "Trap issued when dry contact 5 (Connector #5) has a notification to send"
::= {digInputsTraps 0 5 }
-- IP Devices traps
ipDevice1Trap NOTIFICATION-TYPE
OBJECTS { envTrapDescription, ipDeviceIndex, ipDeviceAddress, ipDeviceDescription, ipDeviceValue, ipDeviceStatus }
STATUS current
DESCRIPTION "Trap issued when IP device #1 has a notification to send"
::= { ipDevicesTraps 0 1 }
ipDevice2Trap NOTIFICATION-TYPE
OBJECTS { envTrapDescription, ipDeviceIndex, ipDeviceAddress, ipDeviceDescription, ipDeviceValue, ipDeviceStatus }
STATUS current
DESCRIPTION "Trap issued when IP device #2 has a notification to send"
::= { ipDevicesTraps 0 2 }
ipDevice3Trap NOTIFICATION-TYPE
OBJECTS { envTrapDescription, ipDeviceIndex, ipDeviceAddress, ipDeviceDescription, ipDeviceValue, ipDeviceStatus }
STATUS current
DESCRIPTION "Trap issued when IP device #3 has a notification to send"
::= { ipDevicesTraps 0 3 }
ipDevice4Trap NOTIFICATION-TYPE
OBJECTS { envTrapDescription, ipDeviceIndex, ipDeviceAddress, ipDeviceDescription, ipDeviceValue, ipDeviceStatus }
STATUS current
DESCRIPTION "Trap issued when IP device #4 has a notification to send"
::= { ipDevicesTraps 0 4 }
ipDevice5Trap NOTIFICATION-TYPE
OBJECTS { envTrapDescription, ipDeviceIndex, ipDeviceAddress, ipDeviceDescription, ipDeviceValue, ipDeviceStatus }
STATUS current
DESCRIPTION "Trap issued when IP device #5 has a notification to send"
::= { ipDevicesTraps 0 5 }
ipDevice6Trap NOTIFICATION-TYPE
OBJECTS { envTrapDescription, ipDeviceIndex, ipDeviceAddress, ipDeviceDescription, ipDeviceValue, ipDeviceStatus }
STATUS current
DESCRIPTION "Trap issued when IP device #6 has a notification to send"
::= { ipDevicesTraps 0 6 }
ipDevice7Trap NOTIFICATION-TYPE
OBJECTS { envTrapDescription, ipDeviceIndex, ipDeviceAddress, ipDeviceDescription, ipDeviceValue, ipDeviceStatus }
STATUS current
DESCRIPTION "Trap issued when IP device #7 has a notification to send"
::= { ipDevicesTraps 0 7 }
ipDevice8Trap NOTIFICATION-TYPE
OBJECTS { envTrapDescription, ipDeviceIndex, ipDeviceAddress, ipDeviceDescription, ipDeviceValue, ipDeviceStatus }
STATUS current
DESCRIPTION "Trap issued when IP device #8 has a notification to send"
::= { ipDevicesTraps 0 8 }
ipDevice9Trap NOTIFICATION-TYPE
OBJECTS { envTrapDescription, ipDeviceIndex, ipDeviceAddress, ipDeviceDescription, ipDeviceValue, ipDeviceStatus }
STATUS current
DESCRIPTION "Trap issued when IP device #9 has a notification to send"
::= { ipDevicesTraps 0 9 }
ipDevice10Trap NOTIFICATION-TYPE
OBJECTS { envTrapDescription, ipDeviceIndex, ipDeviceAddress, ipDeviceDescription, ipDeviceValue, ipDeviceStatus }
STATUS current
DESCRIPTION "Trap issued when IP device #10 has a notification to send"
::= { ipDevicesTraps 0 10 }
ipDevice11Trap NOTIFICATION-TYPE
OBJECTS { envTrapDescription, ipDeviceIndex, ipDeviceAddress, ipDeviceDescription, ipDeviceValue, ipDeviceStatus }
STATUS current
DESCRIPTION "Trap issued when IP device #11 has a notification to send"
::= { ipDevicesTraps 0 11 }
ipDevice12Trap NOTIFICATION-TYPE
OBJECTS { envTrapDescription, ipDeviceIndex, ipDeviceAddress, ipDeviceDescription, ipDeviceValue, ipDeviceStatus }
STATUS current
DESCRIPTION "Trap issued when IP device #12 has a notification to send"
::= { ipDevicesTraps 0 12 }
ipDevice13Trap NOTIFICATION-TYPE
OBJECTS { envTrapDescription, ipDeviceIndex, ipDeviceAddress, ipDeviceDescription, ipDeviceValue, ipDeviceStatus }
STATUS current
DESCRIPTION "Trap issued when IP device #13 has a notification to send"
::= { ipDevicesTraps 0 13 }
ipDevice14Trap NOTIFICATION-TYPE
OBJECTS { envTrapDescription, ipDeviceIndex, ipDeviceAddress, ipDeviceDescription, ipDeviceValue, ipDeviceStatus }
STATUS current
DESCRIPTION "Trap issued when IP device #14 has a notification to send"
::= { ipDevicesTraps 0 14 }
ipDevice15Trap NOTIFICATION-TYPE
OBJECTS { envTrapDescription, ipDeviceIndex, ipDeviceAddress, ipDeviceDescription, ipDeviceValue, ipDeviceStatus }
STATUS current
DESCRIPTION "Trap issued when IP device #15 has a notification to send"
::= { ipDevicesTraps 0 15 }
ipDevice16Trap NOTIFICATION-TYPE
OBJECTS { envTrapDescription, ipDeviceIndex, ipDeviceAddress, ipDeviceDescription, ipDeviceValue, ipDeviceStatus }
STATUS current
DESCRIPTION "Trap issued when IP device #16 has a notification to send"
::= { ipDevicesTraps 0 16 }
-- Output Relay trap
outRelay1Trap NOTIFICATION-TYPE
OBJECTS { envTrapDescription, outRelayIndex, outRelayDescription, outRelayStatus }
STATUS current
DESCRIPTION "Trap issued when output relay changes it's status"
::= { outRelaysTraps 0 1 }
-- Event Log file trap
evLogFileTrap NOTIFICATION-TYPE
OBJECTS { envTrapDescription }
STATUS current
DESCRIPTION "Trap issued when the system has an event log file notification to send"
::= { envTraps 0 10 }
-- Data Log file trap
dataLogFileTrap NOTIFICATION-TYPE
OBJECTS { envTrapDescription }
STATUS current
DESCRIPTION "Trap issued when the system has a data log file notification to send (file almost full)"
::= { envTraps 0 11 }
remoteDataLogFileTrap NOTIFICATION-TYPE
OBJECTS { envTrapDescription, envTrapValue }
STATUS current
DESCRIPTION "Trap issued when the system has a data log file reading to send"
::= { envTraps 0 12 }
END