DKSF-PWR-OLD-MIB DEFINITIONS ::= BEGIN
IMPORTS
enterprises,
MODULE-IDENTITY,
OBJECT-TYPE,
Counter32,
Gauge32,
Counter64,
Integer32,
TimeTicks,
NOTIFICATION-TYPE
FROM SNMPv2-SMI
TEXTUAL-CONVENTION,
DisplayString,
TruthValue,
TimeStamp
FROM SNMPv2-TC
snmpTraps
FROM SNMPv2-MIB ;
netPing8Pwr MODULE-IDENTITY
LAST-UPDATED "201508130000Z"
ORGANIZATION "Alentis Electronics"
CONTACT-INFO
"developers@netping.ru"
DESCRIPTION
"Generic MIB for NetPing remote sensing and control"
REVISION "201508130000Z"
DESCRIPTION
"npRelayFlip variable added"
REVISION "201506180000Z"
DESCRIPTION
"npIr branch added"
REVISION "201505280000Z"
DESCRIPTION
"npGsmSendSms variable added"
REVISION "201505060000Z"
DESCRIPTION
"npRelHumidity, npSmoke branches added"
REVISION "201503260000Z"
DESCRIPTION
"npRelayMode values redefined"
REVISION "201311010000Z"
DESCRIPTION
"New npRelay branch; npPwr branch is reduced.
npRelayMode value for logic changed from 4 to 5"
REVISION "201304110000Z"
DESCRIPTION
"partial rewrite for DKSF 48"
REVISION "201205310000Z"
DESCRIPTION
"npPwrRelayState branch was added"
REVISION "201204170000Z"
DESCRIPTION
"npReboot branch was added"
REVISION "201203230000Z"
DESCRIPTION
"Minor changes to IR module for IRC-TRv2"
REVISION "201109230000Z"
DESCRIPTION
"4 IO lines,
Identification is changed from DKSF 52.4 to DKSF 52.5"
REVISION "201103240000Z"
DESCRIPTION
"npIoPulseCounter, npIoSinglePulseDuration, npIoSinglePulseStart is added
Identification is changed from DKSF 52.3 to DKSF 52.4"
REVISION "201010140000Z"
DESCRIPTION
"IR module support"
REVISION "201009200000Z"
DESCRIPTION
"dksf 52.3 subversion"
REVISION "201005310000Z"
DESCRIPTION
"dksf 51.3 subversion"
REVISION "201004140000Z"
DESCRIPTION
"SMIv2-style rewrite"
-- lightcom.48 DKSF-48-4-X-X-1::netPing8Pwr
-- lightcom.54 DKSF-54-1-X-X-1::netPing4Pwr
::= { lightcom 48 }
lightcom OBJECT IDENTIFIER::={enterprises 25728 }
npRelay OBJECT IDENTIFIER::={ lightcom 5500 }
npRelayTable OBJECT-TYPE
SYNTAX SEQUENCE OF NpRelayEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Watchdog and outlet/relay control table"
::= { npRelay 5 }
npRelayEntry OBJECT-TYPE
SYNTAX NpRelayEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Relay/outlet table row"
INDEX { npRelayN }
::= { npRelayTable 1 }
NpRelayEntry ::= SEQUENCE {
npRelayN INTEGER,
npRelayMode INTEGER,
npRelayStartReset INTEGER,
npRelayMemo DisplayString,
npRelayFlip INTEGER,
npRelayState INTEGER,
npRelayPowered INTEGER
}
npRelayN OBJECT-TYPE
SYNTAX INTEGER (1..8)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The N of output relay"
::= { npRelayEntry 1 }
npRelayMode OBJECT-TYPE
SYNTAX INTEGER {
flip(-1),
off(0),
on(1),
watchdog(2),
schedule(3),
scheduleAndWatchdog(4),
logic(5)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Control of relay:
-1 - flip between on(1) and off(0)
0 - manual off
1 - manual on
2 - watchdog
3 - schedule
4 - both schedule and watchdog (while switched on by schedule)
5 - logic"
::={npRelayEntry 2}
npRelayStartReset OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Write 1 to start reset (switch relay off for some time)"
::={npRelayEntry 3}
npRelayMemo OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Relay memo"
::={npRelayEntry 6}
npRelayFlip OBJECT-TYPE
SYNTAX INTEGER {
flip(-1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Write -1 to flip between manual on and manual off states of relay"
::={npRelayEntry 14}
npRelayState OBJECT-TYPE
SYNTAX INTEGER {
off(0),
on(1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Actual relay state at the moment,
regardless of source of control.
0 - relay is off
1 - relay is on"
::={npRelayEntry 15}
npRelayPowered OBJECT-TYPE
SYNTAX INTEGER {
no(0),
yes(1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "AC presence on output.
0 - no AC dew to relay switched off or no ac on input
1 - AC is present"
::={npRelayEntry 16}
npPwr OBJECT IDENTIFIER::={ lightcom 5800 }
npPwrTable OBJECT-TYPE
SYNTAX SEQUENCE OF NpPwrEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Watchdog and outlet/relay control table"
::= { npPwr 3 }
npPwrEntry OBJECT-TYPE
SYNTAX NpPwrEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Watchdog control table row"
INDEX { npPwrChannelN }
::= { npPwrTable 1 }
NpPwrEntry ::= SEQUENCE {
npPwrChannelN INTEGER,
npPwrStartReset INTEGER,
npPwrResetsCounter INTEGER,
npPwrRepeatingResetsCounter INTEGER,
npPwrMemo DisplayString
}
npPwrChannelN OBJECT-TYPE
SYNTAX INTEGER (1..4)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The id of watchdog/power channel"
::= { npPwrEntry 1 }
npPwrStartReset OBJECT-TYPE
SYNTAX INTEGER (0..2)
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION "Deprecated in current FW version: Write 1 to start forced reset.
On read:
0 - normal operation
1 - reset is active
2 - reboot pause is active or watchdog is inactive"
::={npPwrEntry 2}
npPwrResetsCounter OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Counter of watchdog resets
Write 0 to clear."
::={npPwrEntry 4}
npPwrRepeatingResetsCounter OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Counter of continous failed
watchdog resets"
::={npPwrEntry 5}
npPwrMemo OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Watchdog channel memo"
::={npPwrEntry 6}
npSmoke OBJECT IDENTIFIER::={lightcom 8200}
npSmokeTable OBJECT-TYPE
SYNTAX SEQUENCE OF NpSmokeEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Smoke Sensors Table"
::= { npSmoke 1 }
npSmokeEntry OBJECT-TYPE
SYNTAX NpSmokeEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Smoke Sensors Table Row"
INDEX { npSmokeSensorN }
::= { npSmokeTable 1 }
NpSmokeEntry ::= SEQUENCE {
npSmokeSensorN INTEGER,
npSmokeStatus INTEGER,
npSmokePower INTEGER,
npSmokeReset INTEGER,
npSmokeMemo DisplayString
}
npSmokeSensorN OBJECT-TYPE
SYNTAX INTEGER (1..4)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The id of 1Wire Smoke sensor, 1 to 4"
::= { npSmokeEntry 1 }
npSmokeStatus OBJECT-TYPE
SYNTAX INTEGER {
ok(0),
alarm(1),
off(4),
failed(5)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Status of Smoke sensor"
::= { npSmokeEntry 2 }
npSmokePower OBJECT-TYPE
SYNTAX INTEGER {
off(0),
on(1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Controls power on Smoke sensor current loop"
::= { npSmokeEntry 3 }
npSmokeReset OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Write 1 to switch off for approx. 10s to reset sensor"
::= { npSmokeEntry 4 }
npSmokeMemo OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Smoke sensor memo"
::= { npSmokeEntry 6 }
npSmokeTraps OBJECT IDENTIFIER::={npSmoke 2}
npSmokeTrapPrefix OBJECT IDENTIFIER::={npSmokeTraps 0}
npSmokeTrapSensorN OBJECT-TYPE
SYNTAX INTEGER (1..4)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The id of 1Wire Smoke sensor, 1 to 4"
::= { npSmokeTraps 1 }
npSmokeTrapStatus OBJECT-TYPE
SYNTAX INTEGER {
ok(0),
alarm(1),
off(4),
failed(5)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "New status of Smoke sensor"
::= { npSmokeTraps 2 }
npSmokeTrapMemo OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Smoke sensor memo"
::= { npSmokeTraps 6 }
npSmokeTrap NOTIFICATION-TYPE
OBJECTS {
npSmokeTrapSensorN,
npSmokeTrapStatus,
npSmokeTrapMemo
}
STATUS current
DESCRIPTION
"Status of 1W Smoke sensor has changed"
::= { npSmokeTrapPrefix 1 }
npThermo OBJECT IDENTIFIER::={lightcom 8800}
npThermoTable OBJECT-TYPE
SYNTAX SEQUENCE OF NpThermoEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Thermo Sensors Table"
::= { npThermo 1 }
npThermoEntry OBJECT-TYPE
SYNTAX NpThermoEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Thermo Sensors Table Row"
INDEX { npThermoSensorN }
::= { npThermoTable 1 }
NpThermoEntry ::= SEQUENCE {
npThermoSensorN INTEGER,
npThermoValue INTEGER,
npThermoStatus INTEGER,
npThermoLow INTEGER,
npThermoHigh INTEGER,
npThermoMemo DisplayString
}
npThermoSensorN OBJECT-TYPE
SYNTAX INTEGER (1..8)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The id of temperature sensor, 1 to 8"
::= { npThermoEntry 1 }
npThermoValue OBJECT-TYPE
SYNTAX INTEGER (-60..280)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Temperature, deg.C"
::= { npThermoEntry 2 }
npThermoStatus OBJECT-TYPE
SYNTAX INTEGER {
failed(0),
low(1),
norm(2),
high(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Temperature status (0=fault, 1=underheat, 2=normal, 3=overheat)"
::= { npThermoEntry 3 }
npThermoLow OBJECT-TYPE
SYNTAX INTEGER (-60..280)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Bottom margin of normal temperature range, deg.C"
::= { npThermoEntry 4 }
npThermoHigh OBJECT-TYPE
SYNTAX INTEGER (-60..280)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Top margin of normal temperature range, deg.C"
::= { npThermoEntry 5 }
npThermoMemo OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "T channel memo"
::= { npThermoEntry 6 }
npThermoTraps OBJECT IDENTIFIER::={npThermo 2}
npThermoTrapPrefix OBJECT IDENTIFIER::={npThermoTraps 0}
npThermoTrapSensorN OBJECT-TYPE
SYNTAX INTEGER (1..8)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The id of temperature sensor, 1 to 8"
::= { npThermoTraps 1 }
npThermoTrapValue OBJECT-TYPE
SYNTAX INTEGER (-60..280)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Temperature, deg.C"
::= { npThermoTraps 2 }
npThermoTrapStatus OBJECT-TYPE
SYNTAX INTEGER {
failed(0),
low(1),
norm(2),
high(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Temperature status (0=fault, 1=underheat, 2=normal, 3=overheat)"
::= { npThermoTraps 3 }
npThermoTrapLow OBJECT-TYPE
SYNTAX INTEGER (-60..280)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Bottom margin of normal temperature range, deg.C"
::= { npThermoTraps 4 }
npThermoTrapHigh OBJECT-TYPE
SYNTAX INTEGER (-60..280)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Top margin of normal temperature range, deg.C"
::= { npThermoTraps 5 }
npThermoTrapMemo OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "T channel memo"
::= { npThermoTraps 6 }
npThermoTrap NOTIFICATION-TYPE
OBJECTS {
npThermoTrapSensorN,
npThermoTrapValue,
npThermoTrapStatus,
npThermoTrapLow,
npThermoTrapHigh,
npThermoTrapMemo
}
STATUS current
DESCRIPTION
"Status of Thermo sensor is changed (crossing of normal temp. range)"
::= { npThermoTrapPrefix 1 }
npIo OBJECT IDENTIFIER::={lightcom 8900}
npIoTable OBJECT-TYPE
SYNTAX SEQUENCE OF NpIoEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Digital Input/output Table"
::= { npIo 1 }
npIoEntry OBJECT-TYPE
SYNTAX NpIoEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Digital Input/output Table Row"
INDEX { npIoLineN }
::= { npIoTable 1 }
NpIoEntry ::= SEQUENCE {
npIoLineN INTEGER,
npIoLevelIn INTEGER,
npIoLevelOut INTEGER,
npIoMemo DisplayString,
npIoPulseCounter Counter32,
npIoSinglePulseDuration INTEGER,
npIoSinglePulseStart INTEGER
}
npIoLineN OBJECT-TYPE
SYNTAX INTEGER (1..4)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of IO line, from 1 to max supported"
::= { npIoEntry 1 }
npIoLevelIn OBJECT-TYPE
SYNTAX INTEGER (0..1)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Input level, 0 or 1"
::= { npIoEntry 2 }
npIoLevelOut OBJECT-TYPE
SYNTAX INTEGER (0..1)
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Output level, 0 or 1"
::= { npIoEntry 3 }
npIoMemo OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "IO line memo"
::= { npIoEntry 6 }
npIoPulseCounter OBJECT-TYPE
SYNTAX Counter32
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Pulse Counter on IO input line (counts positive fronts)
Write 0 to reset."
::= { npIoEntry 9 }
npIoSinglePulseDuration OBJECT-TYPE
SYNTAX INTEGER (100..25500)
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Set duration of single pulse on IO output line,
100ms to 25500ms, min. step is 100ms"
::= { npIoEntry 12 }
npIoSinglePulseStart OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Write 1 to start single pulse on IO output.
Output will be inverted for time, specified by npIoSinglePulseDuration"
::= { npIoEntry 13 }
npIoTraps OBJECT IDENTIFIER::={npIo 2}
npIoTrapPrefix OBJECT IDENTIFIER::={npIoTraps 0}
npIoTrapLineN OBJECT-TYPE
SYNTAX INTEGER (1..2)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Trap data, Number of IO line"
::= { npIoTraps 1 }
npIoTrapLevelIn OBJECT-TYPE
SYNTAX INTEGER (0..1)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Trap data, new Input level, 0 or 1"
::= { npIoTraps 2 }
npIoTrapMemo OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Trap data, IO line memo"
::= { npIoTraps 6 }
npIoTrap NOTIFICATION-TYPE
OBJECTS {
npIoTrapLineN,
npIoTrapLevelIn,
npIoTrapMemo
}
STATUS current
DESCRIPTION
"Input state of IO line is changed"
::= { npIoTrapPrefix 1 }
npRelHumidity OBJECT IDENTIFIER::={lightcom 8400}
npRelHumSensor OBJECT IDENTIFIER::={npRelHumidity 2}
npRelHumSensorStatus OBJECT-TYPE
SYNTAX INTEGER {
error(0),
ok(1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Status of the Rel.Humidity Sensor One
1=Normal, 0=Error or Sensor isn't connected"
::= { npRelHumSensor 3 }
npRelHumSensorValueH OBJECT-TYPE
SYNTAX INTEGER (0..100)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Relative humidity value, %"
::= { npRelHumSensor 2 }
npRelHumSensorValueT OBJECT-TYPE
SYNTAX INTEGER (-60..200)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Sensor temperature, deg.C"
::= { npRelHumSensor 4 }
npRelHumSensorStatusH OBJECT-TYPE
SYNTAX INTEGER {
sensorFailed(0),
belowSafeRange(1),
inSafeRange(2),
aboveSafeRange(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Status of Relative Humiduty"
::= { npRelHumSensor 5 }
npRelHumSafeRangeHigh OBJECT-TYPE
SYNTAX INTEGER (0..100)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Relative Humidity safe range, top margin, %RH"
::= { npRelHumSensor 7 }
npRelHumSafeRangeLow OBJECT-TYPE
SYNTAX INTEGER (0..100)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Relative Humidity safe range, bottom margin, %RH"
::= { npRelHumSensor 8 }
npRelHumSensorValueT100 OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Sensor temperature, deg.C * 100 (fixed point two decimal places)
Used to get access to the fractional part of T value"
::= { npRelHumSensor 9 }
npRelHumTraps OBJECT IDENTIFIER::={npRelHumidity 9}
npRelHumTrapPrefix OBJECT IDENTIFIER::={npRelHumTraps 0}
npRelHumTrap NOTIFICATION-TYPE
OBJECTS {
npRelHumSensorStatusH,
npRelHumSensorValueH,
npRelHumSafeRangeHigh,
npRelHumSafeRangeLow
}
STATUS current
DESCRIPTION
"Status of Relative Humidity RH sensor has changed!"
::= { npRelHumTrapPrefix 1 }
npGsm OBJECT IDENTIFIER::={lightcom 3800}
npGsmInfo OBJECT IDENTIFIER::={npGsm 1}
npGsmFailed OBJECT-TYPE
SYNTAX INTEGER {
ok (0),
failed (1),
fatalError (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Firmware's GSM module status"
::= { npGsmInfo 1 }
npGsmRegistration OBJECT-TYPE
SYNTAX INTEGER {
impossible (0),
homeNetwork (1),
searching (2),
denied (3),
unknown (4),
roaming (5),
infoUpdate (255)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Status of modem registration in GSM network (AT+CREG? result)"
::= { npGsmInfo 2 }
npGsmStrength OBJECT-TYPE
SYNTAX INTEGER (0..255)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "GSM signal strength.
0..31 = 0..100%,
99 = unknown or n/a,
255 = updating info"
::= { npGsmInfo 3 }
npGsmSendSms OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Send arbitrary SMS.
Format: [phone_number,phone_number,...] Message
One to four destination phone numbers
If [] and numbers omitted, mesagge will be sent to preset numbers from SMS setup
Only Latin characters allowed in message body"
::= { npGsmInfo 9 }
npGsmTraps OBJECT IDENTIFIER::={npGsm 2}
npGsmTrapPrefix OBJECT IDENTIFIER::={npGsmTraps 0}
npGsmTrap NOTIFICATION-TYPE
OBJECTS {
npGsmFailed,
npGsmRegistration,
npGsmStrength
}
STATUS current
DESCRIPTION
"GSM modem or SMS firmware problems"
::= { npGsmTrapPrefix 1 }
npBattery OBJECT IDENTIFIER::={ lightcom 3900 }
npBatteryInfo OBJECT IDENTIFIER::={npBattery 1}
npBatteryPok OBJECT-TYPE
SYNTAX INTEGER {
batteryPower (0),
externalPower (1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Power source"
::= { npBatteryInfo 1 }
npBatteryLevel OBJECT-TYPE
SYNTAX INTEGER (0..100)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Battery charge, approximate value, in percent.
Valid only if npBatteryPok = 0"
::= { npBatteryInfo 2 }
npBatteryChg OBJECT-TYPE
SYNTAX INTEGER {
batteryChargingSuspended (0),
batteryFastCharging (1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Battery chargeing status.
0 if charging suspended or battery is full,
1 while LiPo fast charging."
::= { npBatteryInfo 3 }
npIr OBJECT IDENTIFIER::={lightcom 7900}
npIrCtrl OBJECT IDENTIFIER::={npIr 1}
npIrPlayCmd OBJECT-TYPE
SYNTAX INTEGER (1..16)
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Write IR command number to send IR command"
::= { npIrCtrl 1 }
npIrReset OBJECT-TYPE
SYNTAX INTEGER (0..1)
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Write 1 to reset IR transiever.
After reset, send IR command and check npIrStatus."
::= { npIrCtrl 2 }
npIrStatus OBJECT-TYPE
SYNTAX INTEGER {
commandCompleted (0),
protocolError (1),
commandAccepted (2),
errorUnknown (16),
errorBadNumber (17),
errorEmptyRecord (18),
errorFlashChip (19),
errorTimeout (20),
errorExtBusBusy (21)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "IR transiever status"
::= { npIrCtrl 3 }
npReboot OBJECT IDENTIFIER::={ lightcom 911 }
npSoftReboot OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Write 1 to reboot device after
current operations completition"
::= { npReboot 1 }
npResetStack OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Write 1 to re-initialize network
stack"
::= { npReboot 2 }
npForcedReboot OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Write 1 to immediate forced reboot"
::= { npReboot 3 }
END