-- MIB file for Ethernet Gateway 4, created 10-Apr-2019 by EDR
-- REVISED 3-Dec-2019 for enterprise use
-- REVISED 9-Jul-2020 Signal Strength in Percent and not dBm
EGW4MIB DEFINITIONS ::= BEGIN
IMPORTS
enterprises
FROM RFC1155-SMI
OBJECT-TYPE
FROM RFC-1212
TRAP-TYPE
FROM RFC-1215
DisplayString
FROM RFC1213-MIB
TEXTUAL-CONVENTION
FROM SNMPv2-TC;
manufacturer OBJECT IDENTIFIER ::= { enterprises 41542 }
EGW4 OBJECT IDENTIFIER ::= { manufacturer 2 }
-- DESCRIPTION
-- "The EGW4 is a product supporting the delivery of data from wireless
-- sensor devices over an Ethernet connection through the SNMP v1 protocol
-- and others. This gateway is major release version 4."
EGW4GatewaySpecificInfo OBJECT IDENTIFIER ::= { EGW4 1 }
-- DESCRIPTION
-- "The EGW4 reports certain information specific to the particular
-- gateway device, which are reported under this hierarchy."
--
-- Gateway-specific section
--
EGW4GatewayID OBJECT-TYPE
SYNTAX Unsigned32
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The serial number identifier of the gateway device assigned and
programmed by the manufacturer. This will ordinarily be printed
on a label on the housing of the device."
::= {EGW4GatewaySpecificInfo 1}
EGW4GatewayFirmwareVerNo OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The version number of the firmware of the gateway device. Note that
this can change upon a firmware update."
::= {EGW4GatewaySpecificInfo 2}
EGW4GatewaySensorDeviceCount OBJECT-TYPE
SYNTAX INTEGER(0..256)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The number of sensors registered to the gateway, i.e. on its netlist.
Note that this can change as sensors are added or removed."
::= {EGW4GatewaySpecificInfo 3}
EGW4GatewayTrapIPAddr OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The configured destination IP address for trap messages from this
gateway."
::= {EGW4GatewaySpecificInfo 4}
EGW4GatewaySensorTrapPort OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The configured IP port for trap messages from this gateway."
::= {EGW4GatewaySpecificInfo 5}
--
-- Definitions of sensor-specific informational types
--
EGW4SensorID ::= TEXTUAL-CONVENTION
STATUS mandatory
DESCRIPTION
"The serial number identifier of the sensor device assigned and
programmed by the manufacturer. This will ordinarily be printed
on a label on the housing of the device."
SYNTAX Unsigned32
EGW4SensorRegistrationIndex ::= TEXTUAL-CONVENTION
STATUS mandatory
DESCRIPTION
"The index number of a sensor device in a gateway's sensor
registration list. This is determined by the order in which a set
of sensors has been registered, but will not change so long as
the list remains fixed. This is included for legacy applications:
please consider using the more convenient
EGW4SensorInfoTranslatedFormat and
EGW4SensorInfoBySensorID hierarchies."
SYNTAX INTEGER(0..255)
EGW4DatumNo ::= TEXTUAL-CONVENTION
STATUS mandatory
DESCRIPTION
"The datum number of a sequence of data readings from a sensor. The
range of this type depends upon the number of datums reported by
a sensor device. Thus, a 3-axis accelerometer sensor might report
three datums for the X, Y and Z axes, and the datums would range
from 1 to 3. For a simple temperature sensor reporting one
reading, this value would always be 1."
SYNTAX INTEGER(1..8)
EGW4SensorDeviceType ::= TEXTUAL-CONVENTION
STATUS mandatory
DESCRIPTION
"The textual description of the type of the sensor device."
SYNTAX OCTET STRING
EGW4DatumNumber ::= TEXTUAL-CONVENTION
STATUS mandatory
DESCRIPTION
"The number of a datum in a set of datums comprising a sensor reading.
For sensors reporting one datum, this will always be one. Otherwise
it will be a number between 1 and the number of datums reported by
the particular type of sensor."
SYNTAX INTEGER
EGW4SensorDeviceReadingTranslatedValue ::= TEXTUAL-CONVENTION
STATUS mandatory
DESCRIPTION
"The value of a sensor reading, in textual format, translated
according to sensor and datum types. These formats can include
integers, fixed-point, and binary values. In several examples:
a pulse counter might report '12345', a current sensor might report
'1.43', and a door closed sensor might report 'Yes'."
SYNTAX OCTET STRING
EGW4SensorDeviceReadingTranslatedUnits ::= TEXTUAL-CONVENTION
STATUS mandatory
DESCRIPTION
"The units or scale of value of a sensor reading, reported in textual
format. In several examples: a pulse counter might report 'Count',
a current sensor might report 'A', and a door sensor might report
'Closed'."
SYNTAX OCTET STRING
EGW4SensorDeviceReadingValuesAll ::= TEXTUAL-CONVENTION
STATUS mandatory
DESCRIPTION
"All of the datums for the most recent reading of the sensor device,
separated by commas, in textual format. For example, a report for a
temperature and humidity sensor might read '20.3, 35' indicating
20.3 degrees at 35 percent humidity. If only one datum is reported
by a sensor device, e.g. for a simple temperature sensor, it will be
reported singly with no commas."
SYNTAX OCTET STRING
EGW4SensorDeviceReadingUnitsAll ::= TEXTUAL-CONVENTION
STATUS mandatory
DESCRIPTION
"All of the units corresponding to the datums for the most recent
reading of the sensor device, separated by commas, in textual
format. For example, for a sensor reporting temperature and
humidity this might read 'degrees C, %RH'"
SYNTAX OCTET STRING
EGW4SensorDeviceReadingUntranslated ::= TEXTUAL-CONVENTION
STATUS mandatory
DESCRIPTION
"The untranslated data block received from a sensor, in hexadecimal
format. This may be used where a translating function isn't yet
present, and for development purposes. Most users should use the
translated values delivered in the format of
EGW4SensorDeviceReadingValuesAll."
SYNTAX OCTET STRING
EGW4SensorDeviceReadingU32Value ::= TEXTUAL-CONVENTION
STATUS mandatory
DESCRIPTION
"Either a single sensor value of up to 32 bits, or half of a
64-bit value. Thus where a sensor value is reportable in a
single Unsigned32, one OID is sufficient to gather that value.
Where more than 32 bits are needed, the value is reported in two
successive values of type EGW4SensorDeviceReadingU32Value.
Where a set of datums is reported, those datums are reported
beginning with the lowest-numbered OID proceeding sequentially
through the highest. Thus were a sensor to report a single-bit
value A followed by 32-bit and a 64 bit ones B and C, and where
OIDS x.10 through x.17 were used for reporting values, the value A
would be encoded in x.10, B in x.11 and C in x.12 (low-order bits)
and x.13 (high-order bits). These values are merely converted
from sensor-specific internal formats to integers, and not beyond
to human-readable formats.
Furthermore, where for a sensor datums extend only part-way through
the available U32Value OIDs, the ones unused may be filled with 0.
Where an SNMP walk is performed, the gateway may not traverse these
unused OIDs."
SYNTAX Unsigned32
EGW4SensorDeviceReadingAge ::= TEXTUAL-CONVENTION
STATUS mandatory
DESCRIPTION
"The age of the sensor report received most recently from a sensor.
That time is reported as the number of seconds between the time of
the sensor report and the time this information is requested."
SYNTAX Unsigned32
EGW4SensorDeviceReadingAlarming ::= TEXTUAL-CONVENTION
STATUS mandatory
DESCRIPTION
"Either 'Alarming' or 'Not alarming'. A device will report an alarm
if it is programmed with a threshold found to be exceeded. Examples:
a temperature sensor for a refrigeration unit can be programmed to
alarm if the measured temperature rises above a threshold, and
a door sensor might alarm if a security door is opened."
SYNTAX OCTET STRING
--
-- Sensor-specific section, translated format
--
EGW4SensorInfoTranslatedFormatTable OBJECT-TYPE
SYNTAX SEQUENCE OF EGW4SensorInfoTranslatedFormatEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The (conceptual) table containing sensor-specific information in an
easy-to-use translated string format, indexed by sensor ID is reported
under this hierarchy. Sensor data is translated by the gateway from
sensor-internal format to human-readable and scriptable values. Use of
this format is preferred for most users. The gateway will report the
most current information received from sensors, according to their
programmed reporting period or heartbeat. When using this section
through getRequests or getNextRequests, successive polling is required
to keep sensor data current. This table can change as sensors are
added or removed. If queried, this OID will return the number of rows
in the table, which is the number of sensors registered to this gateway."
::= { EGW4 2 }
-- Table portion consisting of non-datum-specific info
EGW4SensorInfoTranslatedFormatEntry OBJECT-TYPE
SYNTAX EGW4SensorInfoTranslatedFormatEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"An entry (conceptual row) in the Translated Format Table containing
the latest sensor state for a single sensor."
INDEX { EGW4SensorInfoTranslatedFormatSensorDeviceID }
::= { EGW4SensorInfoTranslatedFormatTable 1 }
EGW4SensorInfoTranslatedFormatEntry ::= SEQUENCE {
EGW4SensorInfoTranslatedFormatSensorDeviceID EGW4SensorID,
EGW4SensorInfoTranslatedFormatSensorDeviceType EGW4SensorDeviceType,
EGW4SensorInfoTranslatedFormatSensorDeviceReadingValuesAll EGW4SensorDeviceReadingValuesAll,
EGW4SensorInfoTranslatedFormatSensorDeviceReadingUnitsAll EGW4SensorDeviceReadingUnitsAll,
EGW4SensorInfoTranslatedFormatSensorDeviceRptUT EGW4SensorDeviceReadingUntranslated,
EGW4SensorInfoTranslatedFormatSensorDeviceReadingTime DisplayString,
EGW4SensorInfoTranslatedFormatSensorDeviceReadingAge EGW4SensorDeviceReadingAge,
EGW4SensorInfoTranslatedFormatSensorDeviceTypeNo DisplayString,
EGW4SensorInfoTranslatedFormatSensorDeviceRFStrength DisplayString,
EGW4SensorInfoTranslatedFormatSensorDeviceActive DisplayString,
EGW4SensorInfoTranslatedFormatSensorDeviceAlarming EGW4SensorDeviceReadingAlarming,
EGW4SensorInfoTranslatedFormatSensorDeviceVoltage DisplayString,
EGW4SensorInfoTranslatedFormatSensorDeviceWDIndexNo DisplayString
}
EGW4SensorInfoTranslatedFormatSensorDeviceID OBJECT-TYPE
SYNTAX EGW4SensorID
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The serial number identifier of the sensor device assigned and
programmed by the manufacturer. This will ordinarily be printed
on a label on the housing of the device."
::= { EGW4SensorInfoTranslatedFormatEntry 1 }
EGW4SensorInfoTranslatedFormatSensorDeviceType OBJECT-TYPE
SYNTAX EGW4SensorDeviceType
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The textual description of the type of the sensor device."
::= {EGW4SensorInfoTranslatedFormatEntry 2 }
EGW4SensorInfoTranslatedFormatSensorDeviceReadingValuesAll OBJECT-TYPE
SYNTAX EGW4SensorDeviceReadingValuesAll
ACCESS read-only
STATUS mandatory
DESCRIPTION
"All of the datums for the most recent reading of the sensor device,
separated by commas, in textual format. For example, a report for a
temperature and humidity sensor might read '20.3, 35' indicating
20.3 degrees at 35 percent humidity. If only one datum is reported
by a sensor device, e.g. for a simple temperature sensor, it will be
reported singly with no commas. The use of this OID is recommended
for most users, rather than the single value ones, because all values
can be retrieved atomically from a sensor in one SNMP request."
::= {EGW4SensorInfoTranslatedFormatEntry 3 }
EGW4SensorInfoTranslatedFormatSensorDeviceReadingUnitsAll OBJECT-TYPE
SYNTAX EGW4SensorDeviceReadingUnitsAll
ACCESS read-only
STATUS mandatory
DESCRIPTION
"All of the units corresponding to the datums for the most recent
reading of the sensor device, separated by commas, in textual
format. For example, for a sensor reporting temperature and
humidity this might read 'degrees C, %RH'"
::= {EGW4SensorInfoTranslatedFormatEntry 4 }
EGW4SensorInfoTranslatedFormatSensorDeviceRptUT OBJECT-TYPE
SYNTAX EGW4SensorDeviceReadingUntranslated
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The untranslated data block received from a sensor, in hexadecimal
format. This may be used where a translating function isn't yet
present, and for development purposes. Most users should use the
translated values delivered in the format of
EGW4SensorDeviceReadingValuesAll."
::= {EGW4SensorInfoTranslatedFormatEntry 5 }
EGW4SensorInfoTranslatedFormatSensorDeviceReadingTime OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The time of the sensor report received most recently from a sensor.
That time is reported as the number of seconds elapsed since the epoch
of the gateway, which is presently Jan. 1, 2010."
::= {EGW4SensorInfoTranslatedFormatEntry 6 }
EGW4SensorInfoTranslatedFormatSensorDeviceReadingAge OBJECT-TYPE
SYNTAX EGW4SensorDeviceReadingAge
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The age of the sensor report received most recently from a sensor.
That time is reported as the number of seconds between the time of
the sensor report and the time this information is requested."
::= {EGW4SensorInfoTranslatedFormatEntry 7 }
EGW4SensorInfoTranslatedFormatSensorDeviceTypeNo OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The manufacturer's type number that identifies the kind of sensor."
::= {EGW4SensorInfoTranslatedFormatEntry 8 }
EGW4SensorInfoTranslatedFormatSensorDeviceRFStrength OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The signal strength, in percent, of the radio link between the gateway
and the particular sensor, as measured at the time of the most recent
sensor report."
::= {EGW4SensorInfoTranslatedFormatEntry 9 }
EGW4SensorInfoTranslatedFormatSensorDeviceActive OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Either 'Active' or '' (an empty string). A sensor will be reported
active if it has recently communicated with the gateway since the last
reboot. If a sensor device does not show active, it is likely because
(1) the sensor lacks a power source, (2) the sensor is not in
proximity to the gateway, or (3) the gateway has recently been
powered on, and the sensor hasn't yet communicated."
::= {EGW4SensorInfoTranslatedFormatEntry 10 }
EGW4SensorInfoTranslatedFormatSensorDeviceAlarming OBJECT-TYPE
SYNTAX EGW4SensorDeviceReadingAlarming
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Either 'Alarming' or 'Not alarming'. A device will report an alarm
if it is programmed with a threshold found to be exceeded. Examples:
a temperature sensor for a refrigeration unit can be programmed to
alarm if the measured temperature rises above a threshold, and
a door sensor might alarm if a security door is opened."
::= {EGW4SensorInfoTranslatedFormatEntry 11 }
EGW4SensorInfoTranslatedFormatSensorDeviceVoltage OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The value of the voltage of the supply powering a sensor device.
Ordinarily this will report the voltage at the battery terminals of
a sensor. It is provided mainly so batteries can be changed when
depleted."
::= {EGW4SensorInfoTranslatedFormatEntry 12 }
EGW4SensorInfoTranslatedFormatSensorDeviceWDIndexNo OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index number of the sensor in the gateway's sensor registration
table. This is the number used in referencing the sensor in the
EGW4SensorInformationBySensorRegisOrder
hierarchy."
::= {EGW4SensorInfoTranslatedFormatEntry 13 }
-- Table portion consisting of datum-specific info (single values and units addressed by device ID and datum)
EGW4SensorInfoTranslatedFormatByDatumNumberEntry OBJECT-TYPE
SYNTAX EGW4SensorInfoTranslatedFormatByDatumNumberEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"An entry (conceptual row) in the Translated Format Table containing
the sensor datums, indexed by a sensor ID and datum number."
INDEX { EGW4SensorInfoTranslatedFormatSensorDeviceID,
EGW4SensorInfoTranslatedFormatByDatumNumberDatumNumber }
::= { EGW4SensorInfoTranslatedFormatTable 2 }
EGW4SensorInfoTranslatedFormatByDatumNumberEntry ::= SEQUENCE {
EGW4SensorInfoTranslatedFormatByDatumNumberSensorDeviceID EGW4SensorID,
EGW4SensorInfoTranslatedFormatByDatumNumberDatumNumber EGW4DatumNumber,
EGW4SensorInfoTranslatedFormatByDatumNumberReadingValue EGW4SensorDeviceReadingTranslatedValue,
EGW4SensorInfoTranslatedFormatByDatumNumberReadingUnits EGW4SensorDeviceReadingTranslatedUnits
}
EGW4SensorInfoTranslatedFormatByDatumNumberSensorDeviceID OBJECT-TYPE
SYNTAX EGW4SensorID
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The serial number identifier of the sensor device assigned and
programmed by the manufacturer. This will ordinarily be printed
on a label on the housing of the device."
::= { EGW4SensorInfoTranslatedFormatByDatumNumberEntry 1 }
EGW4SensorInfoTranslatedFormatByDatumNumberDatumNumber OBJECT-TYPE
SYNTAX EGW4DatumNumber
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The number of a datum in a set of datums comprising a sensor reading.
For sensors reporting one datum, this will always be one. Otherwise
it will be a number between 1 and the number of datums reported by
the particular type of sensor."
::= { EGW4SensorInfoTranslatedFormatByDatumNumberEntry 2 }
EGW4SensorInfoTranslatedFormatByDatumNumberReadingValue OBJECT-TYPE
SYNTAX EGW4SensorDeviceReadingTranslatedValue
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The value of a sensor reading, in textual format, translated
according to sensor and datum types. These formats can include
integers, fixed-point, and binary values. In several examples:
a pulse counter might report '12345', a current sensor might report
'1.43', and a door sensor might report 'closed'."
::= { EGW4SensorInfoTranslatedFormatByDatumNumberEntry 3 }
EGW4SensorInfoTranslatedFormatByDatumNumberReadingUnits OBJECT-TYPE
SYNTAX EGW4SensorDeviceReadingTranslatedUnits
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The units or scale of value of a sensor reading, reported in textual
format. In several examples: a pulse counter might report 'Count',
a current sensor might report 'A', and a door sensor might report
'Closed'."
::= { EGW4SensorInfoTranslatedFormatByDatumNumberEntry 4 }
--
-- Sensor-specific section, untranslated legacy format, by sensor ID
--
EGW4SensorInfoBySensorIDTable OBJECT-TYPE
SYNTAX SEQUENCE OF EGW4SensorInfoBySensorIDSensorEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The (conceptual) table containing sensor information in a legacy
untranslated numeric format, addressed by sensor ID. This is provided
for users who need a precise match of the format of the older EGW1
platform. The gateway will report the most current information received
from sensors, according to their programmed reporting period or
heartbeat. A more convenient format to new users is available under
the EGW4SensorInfoTranslatedFormat. If queried, this
OID will return the number of rows in the table, which is the number
of sensors registered to this gateway."
::= { EGW4 3 }
EGW4SensorInfoBySensorIDEntry OBJECT-TYPE
SYNTAX EGW4SensorInfoBySensorIDEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"An entry (conceptual row) in the untranslated by-sensor-ID-order
table containing the latest sensor state for a single sensor."
INDEX { EGW4SensorInfoBySensorIDSensorDeviceID }
::= { EGW4SensorInfoBySensorIDTable 1 }
EGW4SensorInfoBySensorIDEntry ::= SEQUENCE {
EGW4SensorInfoBySensorIDSensorDeviceID Unsigned32,
EGW4SensorInfoBySensorIDSensorDeviceWDIndexNo INTEGER,
EGW4SensorInfoBySensorIDSensorDeviceTypeNo INTEGER,
EGW4SensorInfoBySensorIDSensorDeviceReadingAge Unsigned32,
EGW4SensorInfoBySensorIDSensorDeviceActive INTEGER,
EGW4SensorInfoBySensorIDSensorDeviceAlarming INTEGER,
EGW4SensorInfoBySensorIDSensorDeviceVoltage INTEGER,
EGW4SensorInfoBySensorIDSensorDeviceRFStrength INTEGER,
EGW4SensorInfoBySensorIDSensorDeviceRptUT DisplayString,
EGW4SensorInfoBySensorIDSensorDeviceReadingValue1 EGW4SensorDeviceReadingU32Value,
EGW4SensorInfoBySensorIDSensorDeviceReadingValue2 EGW4SensorDeviceReadingU32Value,
EGW4SensorInfoBySensorIDSensorDeviceReadingValue3 EGW4SensorDeviceReadingU32Value,
EGW4SensorInfoBySensorIDSensorDeviceReadingValue4 EGW4SensorDeviceReadingU32Value,
EGW4SensorInfoBySensorIDSensorDeviceReadingValue5 EGW4SensorDeviceReadingU32Value,
EGW4SensorInfoBySensorIDSensorDeviceReadingValue6 EGW4SensorDeviceReadingU32Value,
EGW4SensorInfoBySensorIDSensorDeviceReadingValue7 EGW4SensorDeviceReadingU32Value,
EGW4SensorInfoBySensorIDSensorDeviceReadingValue8 EGW4SensorDeviceReadingU32Value
}
EGW4SensorInfoBySensorIDSensorDeviceID OBJECT-TYPE
SYNTAX Unsigned32
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The serial number identifier of the sensor device assigned and
programmed by the manufacturer. This will ordinarily be printed
on a label on the housing of the device."
INDEX { EGW4SensorID }
::= {EGW4SensorInfoBySensorIDEntry 1 }
EGW4SensorInfoBySensorIDSensorDeviceWDIndexNo OBJECT-TYPE
SYNTAX INTEGER(0..255)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index number of the sensor in the gateway's sensor registration
table. This is the number used in referencing the sensor in the
EGW4SensorInfoBySensorRegisOrder
hierarchy."
INDEX { EGW4SensorID }
::= {EGW4SensorInfoBySensorIDEntry 2 }
EGW4SensorInfoBySensorIDSensorDeviceTypeNo OBJECT-TYPE
SYNTAX INTEGER(1..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The manufacturer's type number that identifies the kind of sensor."
INDEX { EGW4SensorID }
::= {EGW4SensorInfoBySensorIDEntry 3 }
EGW4SensorInfoBySensorIDSensorDeviceReadingAge OBJECT-TYPE
SYNTAX Unsigned32
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The age of the sensor report received most recently from a sensor.
That time is reported as the number of seconds between the time of
the sensor report and the time this information is requested."
INDEX { EGW4SensorID }
::= {EGW4SensorInfoBySensorIDEntry 4 }
EGW4SensorInfoBySensorIDSensorDeviceActive OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Either 1 (active) or 0 (inactive). A sensor will be reported active
if it has recently communicated with the gateway since the last
reboot. If a sensor device does not show active, it is likely because
(1) the sensor lacks a power source, (2) the sensor is not in
proximity to the gateway, or (3) the gateway has recently been
powered on, and the sensor hasn't yet communicated."
INDEX { EGW4SensorID }
::= {EGW4SensorInfoBySensorIDEntry 5 }
EGW4SensorInfoBySensorIDSensorDeviceAlarming OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Either 1 (alarming) or 0 (not alarming)'. A device will report an
alarm if it is programmed with a threshold found to be exceeded.
Examples: a temperature sensor for a refrigeration unit can be
programmed to alarm if the measured temperature rises above a
threshold, and a door sensor might alarm if a security door is opened."
INDEX { EGW4SensorID }
::= {EGW4SensorInfoBySensorIDEntry 6 }
EGW4SensorInfoBySensorIDSensorDeviceVoltage OBJECT-TYPE
SYNTAX INTEGER(0..255)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"A value representing the voltage of the supply powering a sensor
device. Ordinarily this will report the voltage at the battery
terminals of a sensor. It is provided mainly so batteries can be
changed when depleted. The formula for calculating the voltage from
this number is: voltage=(150 + v) / 10.0."
INDEX { EGW4SensorID }
::= {EGW4SensorInfoBySensorIDEntry 7 }
EGW4SensorInfoBySensorIDSensorDeviceRFStrength OBJECT-TYPE
SYNTAX INTEGER(-128..127)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The signal strength, in percent, of the radio link between the gateway
and the particular sensor, as measured at the time of the most recent
sensor report."
INDEX { EGW4SensorID }
::= {EGW4SensorInfoBySensorIDEntry 8 }
EGW4SensorInfoBySensorIDSensorDeviceRptUT OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The untranslated data block received from a sensor, in hexadecimal
format. This may be used where a translating function isn't yet
present, and for development purposes. Most users should use the
translated values delivered in the format of
EGW4SensorDeviceReadingValuesAll."
INDEX { EGW4SensorID }
::= {EGW4SensorInfoBySensorIDEntry 9 }
EGW4SensorInfoBySensorIDSensorDeviceReadingValue1 OBJECT-TYPE
SYNTAX EGW4SensorDeviceReadingU32Value
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The value of a single sensor reading, or one half of a 64-bit reading,
in integer format, not translated to human-readable form. See
EGW4SensorDeviceReadingU32Value for further explanation."
INDEX { EGW4SensorID }
::= {EGW4SensorInfoBySensorIDEntry 10 }
EGW4SensorInfoBySensorIDSensorDeviceReadingValue2 OBJECT-TYPE
SYNTAX EGW4SensorDeviceReadingU32Value
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The value of a single sensor reading, or one half of a 64-bit reading,
in integer format, not translated to human-readable form. See
EGW4SensorDeviceReadingU32Value for further explanation."
INDEX { EGW4SensorID }
::= {EGW4SensorInfoBySensorIDEntry 11 }
EGW4SensorInfoBySensorIDSensorDeviceReadingValue3 OBJECT-TYPE
SYNTAX EGW4SensorDeviceReadingU32Value
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The value of a single sensor reading, or one half of a 64-bit reading,
in integer format, not translated to human-readable form. See
EGW4SensorDeviceReadingU32Value for further explanation."
INDEX { EGW4SensorID }
::= {EGW4SensorInfoBySensorIDEntry 12 }
EGW4SensorInfoBySensorIDSensorDeviceReadingValue4 OBJECT-TYPE
SYNTAX EGW4SensorDeviceReadingU32Value
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The value of a single sensor reading, or one half of a 64-bit reading,
in integer format, not translated to human-readable form. See
EGW4SensorDeviceReadingU32Value for further explanation."
INDEX { EGW4SensorID }
::= {EGW4SensorInfoBySensorIDEntry 13 }
EGW4SensorInfoBySensorIDSensorDeviceReadingValue5 OBJECT-TYPE
SYNTAX EGW4SensorDeviceReadingU32Value
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The value of a single sensor reading, or one half of a 64-bit reading,
in integer format, not translated to human-readable form. See
EGW4SensorDeviceReadingU32Value for further explanation."
INDEX { EGW4SensorID }
::= {EGW4SensorInfoBySensorIDEntry 14 }
EGW4SensorInfoBySensorIDSensorDeviceReadingValue6 OBJECT-TYPE
SYNTAX EGW4SensorDeviceReadingU32Value
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The value of a single sensor reading, or one half of a 64-bit reading,
in integer format, not translated to human-readable form. See
EGW4SensorDeviceReadingU32Value for further explanation."
INDEX { EGW4SensorID }
::= {EGW4SensorInfoBySensorIDEntry 15 }
EGW4SensorInfoBySensorIDSensorDeviceReadingValue7 OBJECT-TYPE
SYNTAX EGW4SensorDeviceReadingU32Value
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The value of a single sensor reading, or one half of a 64-bit reading,
in integer format, not translated to human-readable form. See
EGW4SensorDeviceReadingU32Value for further explanation."
INDEX { EGW4SensorID }
::= {EGW4SensorInfoBySensorIDEntry 16 }
EGW4SensorInfoBySensorIDSensorDeviceReadingValue8 OBJECT-TYPE
SYNTAX EGW4SensorDeviceReadingU32Value
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The value of a single sensor reading, or one half of a 64-bit reading,
in integer format, not translated to human-readable form. See
EGW4SensorDeviceReadingU32Value for further explanation."
INDEX { EGW4SensorID }
::= {EGW4SensorInfoBySensorIDEntry 17 }
--
-- Sensor-specific section, untranslated legacy format, by registration order
--
EGW4SensorInfoBySensorRegisOrderTable OBJECT-TYPE
SYNTAX SEQUENCE OF EGW4SensorInfoBySensorRegisOrderSensorEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The (conceptual) table containing an untranslated numeric format,
addressed by sensor registration order starting at 1 and ascending by
one, in a legacy integer format. This is provided for users who need a
precise match of the format and order of the older EGW1 platform.
The gateway will report the most current information received from
sensors, according to their programmed reporting period or heartbeat.
A more convenient format to new users is available under
the EGW4SensorInfoTranslatedFormat. If queried, this
OID will return the number of rows in the table, which is the number
of sensors registered to this gateway."
::= { EGW4 4 }
EGW4SensorInfoBySensorRegisOrderEntry OBJECT-TYPE
SYNTAX EGW4SensorInfoBySensorRegisOrderEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"An entry (conceptual row) in the untranslated by-registration-order
table containing the latest sensor state for a single sensor."
INDEX { EGW4SensorInfoBySensorRegisOrderSensDevID }
::= { EGW4SensorInfoBySensorRegisOrderTable 1 }
EGW4SensorInfoBySensorRegisOrderEntry ::= SEQUENCE {
EGW4SensorInfoBySensorRegisOrderSensorDeviceID Unsigned32,
EGW4SensorInfoBySensorRegisOrderSensorDeviceWDIndexNo INTEGER,
EGW4SensorInfoBySensorRegisOrderSensorDeviceTypeNo INTEGER,
EGW4SensorInfoBySensorRegisOrderSensorDeviceReadingAge Unsigned32,
EGW4SensorInfoBySensorRegisOrderSensorDeviceActive INTEGER,
EGW4SensorInfoBySensorRegisOrderSensorDeviceAlarming INTEGER,
EGW4SensorInfoBySensorRegisOrderSensorDeviceVoltage INTEGER,
EGW4SensorInfoBySensorRegisOrderSensorDeviceRFStrength INTEGER,
EGW4SensorInfoBySensorRegisOrderSensorDeviceRptUT DisplayString,
EGW4SensorInfoBySensorRegisOrderSensorDeviceReadingValue1 EGW4SensorDeviceReadingU32Value,
EGW4SensorInfoBySensorRegisOrderSensorDeviceReadingValue2 EGW4SensorDeviceReadingU32Value,
EGW4SensorInfoBySensorRegisOrderSensorDeviceReadingValue3 EGW4SensorDeviceReadingU32Value,
EGW4SensorInfoBySensorRegisOrderSensorDeviceReadingValue4 EGW4SensorDeviceReadingU32Value,
EGW4SensorInfoBySensorRegisOrderSensorDeviceReadingValue5 EGW4SensorDeviceReadingU32Value,
EGW4SensorInfoBySensorRegisOrderSensorDeviceReadingValue6 EGW4SensorDeviceReadingU32Value,
EGW4SensorInfoBySensorRegisOrderSensorDeviceReadingValue7 EGW4SensorDeviceReadingU32Value,
EGW4SensorInfoBySensorRegisOrderSensorDeviceReadingValue8 EGW4SensorDeviceReadingU32Value
}
EGW4SensorInfoBySensorRegisOrderSensDevID OBJECT-TYPE
SYNTAX Unsigned32
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The serial number identifier of the sensor device assigned and
programmed by the manufacturer. This will ordinarily be printed
on a label on the housing of the device."
INDEX { EGW4SensorRegistrationIndex }
::= {EGW4SensorInfoBySensorRegisOrderEntry 1 }
EGW4SensorInfoBySensorRegisOrderSensDevWDIndexNo OBJECT-TYPE
SYNTAX INTEGER(0..255)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index number of the sensor in the gateway's sensor registration
table. This is the number used in referencing the sensor in the
EGW4SensorInfoBySensorRegisOrder hierarchy."
INDEX { EGW4SensorRegistrationIndex }
::= {EGW4SensorInfoBySensorRegisOrderEntry 2 }
EGW4SensorInfoBySensorRegisOrderSensDevTypeNo OBJECT-TYPE
SYNTAX INTEGER(1..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The manufacturer's type number that identifies the kind of sensor."
INDEX { EGW4SensorRegistrationIndex }
::= {EGW4SensorInfoBySensorRegisOrderEntry 3 }
EGW4SensorInfoBySensorRegisOrderSensDevReadingAge OBJECT-TYPE
SYNTAX Unsigned32
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The age of the sensor report received most recently from a sensor.
That time is reported as the number of seconds between the time of
the sensor report and the time this information is requested."
INDEX { EGW4SensorRegistrationIndex }
::= {EGW4SensorInfoBySensorRegisOrderEntry 4 }
EGW4SensorInfoBySensorRegisOrderSensDevActive OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Either 1 (active) or 0 (inactive). A sensor will be reported active
if it has recently communicated with the gateway since the last
reboot. If a sensor device does not show active, it is likely because
(1) the sensor lacks a power source, (2) the sensor is not in
proximity to the gateway, or (3) the gateway has recently been
powered on, and the sensor hasn't yet communicated."
INDEX { EGW4SensorRegistrationIndex }
::= {EGW4SensorInfoBySensorRegisOrderEntry 5 }
EGW4SensorInfoBySensorRegisOrderSensDevAlarming OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Either 1 (alarming) or 0 (not alarming)'. A device will report an
alarm if it is programmed with a threshold found to be exceeded.
Examples: a temperature sensor for a refrigeration unit can be
programmed to alarm if the measured temperature rises above a
threshold, and a door sensor might alarm if a security door is opened."
INDEX { EGW4SensorRegistrationIndex }
::= {EGW4SensorInfoBySensorRegisOrderEntry 6 }
EGW4SensorInfoBySensorRegisOrderSensDevVoltage OBJECT-TYPE
SYNTAX INTEGER(0..255)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"A value representing the voltage of the supply powering a sensor
device. Ordinarily this will report the voltage at the battery
terminals of a sensor. It is provided mainly so batteries can be
changed when depleted. The formula for calculating the voltage from
this number is: voltage=(150 + v) / 10.0."
INDEX { EGW4SensorRegistrationIndex }
::= {EGW4SensorInfoBySensorRegisOrderEntry 7 }
EGW4SensorInfoBySensorRegisOrderSensDevRFStrength OBJECT-TYPE
SYNTAX INTEGER(-128..127)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The signal strength, in percent, of the radio link between the gateway
and the particular sensor, as measured at the time of the most recent
sensor report."
INDEX { EGW4SensorRegistrationIndex }
::= {EGW4SensorInfoBySensorRegisOrderEntry 8 }
EGW4SensorInfoBySensorRegisOrderSensDevRptUT OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The untranslated data block received from a sensor, in hexadecimal
format. This may be used where a translating function isn't yet
present, and for development purposes. Most users should use the
translated values delivered in the format of
EGW4SensorDeviceReadingValuesAll."
INDEX { EGW4SensorRegistrationIndex }
::= {EGW4SensorInfoBySensorRegisOrderEntry 9 }
EGW4SensorInfoBySensorRegisOrderSensDevReadingVl1 OBJECT-TYPE
SYNTAX EGW4SensorDeviceReadingU32Value
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The value of a single sensor reading, or one half of a 64-bit reading,
in integer format, not translated to human-readable form. See
EGW4SensorDeviceReadingU32Value for further explanation."
::= {EGW4SensorInfoBySensorRegisOrderEntry 10 }
EGW4SensorInfoBySensorRegisOrderSensDevReadingVl2 OBJECT-TYPE
SYNTAX EGW4SensorDeviceReadingU32Value
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The value of a single sensor reading, or one half of a 64-bit reading,
in integer format, not translated to human-readable form. See
EGW4SensorDeviceReadingU32Value for further explanation."
::= {EGW4SensorInfoBySensorRegisOrderEntry 11 }
EGW4SensorInfoBySensorRegisOrderSensDevReadingVl3 OBJECT-TYPE
SYNTAX EGW4SensorDeviceReadingU32Value
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The value of a single sensor reading, or one half of a 64-bit reading,
in integer format, not translated to human-readable form. See
EGW4SensorDeviceReadingU32Value for further explanation."
::= {EGW4SensorInfoBySensorRegisOrderEntry 12 }
EGW4SensorInfoBySensorRegisOrderSensDevReadingVl4 OBJECT-TYPE
SYNTAX EGW4SensorDeviceReadingU32Value
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The value of a single sensor reading, or one half of a 64-bit reading,
in integer format, not translated to human-readable form. See
EGW4SensorDeviceReadingU32Value for further explanation."
::= {EGW4SensorInfoBySensorRegisOrderEntry 13 }
EGW4SensorInfoBySensorRegisOrderSensDevReadingVl5 OBJECT-TYPE
SYNTAX EGW4SensorDeviceReadingU32Value
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The value of a single sensor reading, or one half of a 64-bit reading,
in integer format, not translated to human-readable form. See
EGW4SensorDeviceReadingU32Value for further explanation."
::= {EGW4SensorInfoBySensorRegisOrderEntry 14 }
EGW4SensorInfoBySensorRegisOrderSensDevReadingVl6 OBJECT-TYPE
SYNTAX EGW4SensorDeviceReadingU32Value
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The value of a single sensor reading, or one half of a 64-bit reading,
in integer format, not translated to human-readable form. See
EGW4SensorDeviceReadingU32Value for further explanation."
::= {EGW4SensorInfoBySensorRegisOrderEntry 15 }
EGW4SensorInfoBySensorRegisOrderSensDevReadingVl7 OBJECT-TYPE
SYNTAX EGW4SensorDeviceReadingU32Value
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The value of a single sensor reading, or one half of a 64-bit reading,
in integer format, not translated to human-readable form. See
EGW4SensorDeviceReadingU32Value for further explanation."
::= {EGW4SensorInfoBySensorRegisOrderEntry 16 }
EGW4SensorInfoBySensorRegisOrderSensDevReadingVl8 OBJECT-TYPE
SYNTAX EGW4SensorDeviceReadingU32Value
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The value of a single sensor reading, or one half of a 64-bit reading,
in integer format, not translated to human-readable form. See
EGW4SensorDeviceReadingU32Value for further explanation."
::= {EGW4SensorInfoBySensorRegisOrderEntry 17 }
--
-- Traps
--
--Map of types used in traps to those used in requests
-- EGW4-Trap-DevIDReported ::= EGW4-GatewayID
-- EGW4-Trap-AllValuesReported ::=
-- CHOICE {
-- EGW4-trap-values-translatable EGW4-SensorDeviceReadingValuesAll,
-- EGW4-trap-values-unknown EGW4-SensorDeviceReadingUntranslated
-- }
-- EGW4-Trap-AllUnitsReported ::= EGW4-SensorDeviceReadingUnitsAll
-- EGW4-Trap-AgeReported ::= EGW4-SensorDeviceReadingUnitsAll
-- EGW4-Trap-AlarmingReported ::= EGW4-SensorDeviceReadingUnitsAll
EGW4TrapDevIDReported ::= TEXTUAL-CONVENTION
STATUS mandatory
DESCRIPTION
"The serial number identifier of the sensor device assigned and
programmed by the manufacturer. This will ordinarily be printed
on a label on the housing of the device. EGW4TrapDevIDReported
is the same as EGW4SensorID."
SYNTAX Unsigned32(1..2147483631)
EGW4TrapAllValuesReported ::= TEXTUAL-CONVENTION
STATUS mandatory
DESCRIPTION
"This will make one of two reports. For the case the sensor type is
known to the gateway, this will be all of the datums for the most
recent reading of the sensor device, separated by commas, in textual
format, using the EGW4SensorDeviceReadingValuesAll format.
Where the sensor type is not known to the gateway, this will be
the untranslated data block received from a sensor, in hexadecimal
format. This EGW4TrapAllValuesReported is the same as either
EGW4SensorDeviceReadingValuesAll or
EGW4SensorDeviceReadingUntranslated."
SYNTAX OCTET STRING
EGW4TrapAllUnitsReported ::= TEXTUAL-CONVENTION
STATUS mandatory
DESCRIPTION
"All of the units corresponding to the datums for the most recent
reading of the sensor device, separated by commas, in textual
format. For example, for a sensor reporting temperature and
humidity this might read 'degrees C, %RH'.
EGW4TrapAllUnitsReported is the same as
EGW4SensorDeviceReadingUnitsAll."
SYNTAX OCTET STRING
EGW4TrapAgeReported ::= TEXTUAL-CONVENTION
STATUS mandatory
DESCRIPTION
"The age of the sensor report received most recently from a sensor.
That time is reported as the number of seconds between the time of
the sensor report and the time this information is requested.
EGW4TrapAgeReported is the same as
EGW4SensorDeviceReadingAge."
SYNTAX OCTET STRING
EGW4TrapAlarmingReported ::= TEXTUAL-CONVENTION
STATUS mandatory
DESCRIPTION
"Either 'Alarming' or 'Not alarming'. A device will report an alarm
if it is programmed with a threshold found to be exceeded. Examples:
a temperature sensor for a refrigeration unit can be programmed to
alarm if the measured temperature rises above a threshold, and
a door sensor might alarm if a security door is opened.
EGW4TrapAlarmingReported is the same as
EGW4SensorDeviceReadingAlarming."
SYNTAX OCTET STRING
EGW4NewSensorTraffic TRAP-TYPE
ENTERPRISE EGW4
VARIABLES {
EGW4SensorInfoTranslatedFormatSensorDeviceID, EGW4TrapDevIDReported,
EGW4SensorInfoTranslatedFormatSensorDeviceReadingValuesAll, EGW4TrapAllValuesReported,
EGW4SensorInfoTranslatedFormatSensorDeviceReadingUnitsAll, EGW4TrapAllUnitsReported,
EGW4SensorInfoTranslatedFormatSensorDeviceReadingAge, EGW4TrapAgeReported,
EGW4SensorInfoTranslatedFormatSensorDeviceAlarming, EGW4TrapAlarmingReported
}
DESCRIPTION
"This trap, when enabled, will generate a report corresponding to new
data from any registered sensor as it is received. Included with the
trap message are the sensor ID, all values the sensor reports, units for
all those values, the age, and whether the sensor is alarming."
::= 1
EGW4DeviceAlarming TRAP-TYPE
ENTERPRISE EGW4
VARIABLES {
EGW4SensorInfoTranslatedFormatSensorDeviceID, EGW4TrapDevIDReported,
EGW4SensorInfoTranslatedFormatSensorDeviceReadingValuesAll, EGW4TrapAllValuesReported,
EGW4SensorInfoTranslatedFormatSensorDeviceReadingUnitsAll, EGW4TrapAllUnitsReported,
EGW4SensorInfoTranslatedFormatSensorDeviceReadingAge, EGW4TrapAgeReported,
EGW4SensorInfoTranslatedFormatSensorDeviceAlarming, EGW4TrapAlarmingReported
}
DESCRIPTION
"This trap, when enabled, will generate a report corresponding to new
data from any registered sensor as it is received, but only if that
sensor is alarming and the EGW4NewSensorTraffic trap is disabled.
(That trap will generate the same message, rendering this trap redundant.)
Included with the trap message are the sensor ID, all values the sensor
reports, units for all those values, the age, and whether the sensor
is alarming."
::= 2
END