Observium_CE/mibs/huawei/HUAWEI-POWER-MIB

4905 lines
146 KiB
Plaintext

-- ============================================================================
-- Copyright (C) 2019 by HUAWEI TECHNOLOGIES. All rights reserved.
-- Description: This MIB is used for defining Power Monitor management
-- MIB objects.
-- Reference:
-- Version: V3.62
-- ============================================================================
HUAWEI-POWER-MIB DEFINITIONS ::= BEGIN
IMPORTS
hwEnvEmuIndex,hwEnvEmuType,hwDigChannelIndex
FROM HUAWEI-ENVIRONMENT-MIB
huaweiUtility
FROM HUAWEI-MIB
Integer32, OBJECT-TYPE, MODULE-IDENTITY, NOTIFICATION-TYPE
FROM SNMPv2-SMI
DisplayString, RowStatus, TruthValue, DateAndTime, TEXTUAL-CONVENTION
FROM SNMPv2-TC
hwFrameIndex
FROM HUAWEI-DEVICE-MIB;
hwPower MODULE-IDENTITY
LAST-UPDATED "201903270000Z"
ORGANIZATION "Huawei Technologies Co.,Ltd."
CONTACT-INFO
"Huawei Industrial Base
Bantian, Longgang
Shenzhen 518129
People's Republic of China
Website: http://www.huawei.com
Email: support@huawei.com
"
DESCRIPTION
"
This MIB is used for defining Power Monitor management MIB objects.
"
-- Revision history
REVISION "201903270000Z"
DESCRIPTION "V3.62, added enumerate etp4860(131) in hwPowerType leaf for smu EMU."
REVISION "201903061000Z"
DESCRIPTION "V3.61, added description of enumerate etp48200(130) and modified the description of enumerate unknown in hwPowerType leaf for smu EMU."
REVISION "201903060000Z"
DESCRIPTION "V3.60, added enumerate etp48200(130) in hwPowerType leaf for smu EMU."
REVISION "201812210000Z"
DESCRIPTION "V3.59,
add enumerate supplyRecoverAutotestTerminated(7) in hwBatteryLogTestFinish leaf.
modified the Description of hwBatteryLogTestFinish."
REVISION "201809120000Z"
DESCRIPTION "V3.58,
add the leaf of hwEmmPowerBatteryBoardFaultTrap and hwEmmPowerBatteryBoardRecoverTrap.
modified the Description of hwPowerCellChargeHighTemperatureProtectionFaultTrap."
REVISION "201806190000Z"
DESCRIPTION "V3.57, modify description the leaf of hwPowerBluetoothSwitch."
REVISION "201805290000Z"
DESCRIPTION "V3.56,
add the node of hwPowerWiringCheckSwitch for setting and getting the wiring check switch of SMU.
add the node of hwPowerLatitude and hwPowerLongitude for getting the location of battery.
add the leaf of hwPowerBatteryContactorFaultTrap and hwPowerBatteryContactorRestoreTrap.
add the leaf of hwPowerLowTemperatureProtectionFaultTrap and hwPowerLowTemperatureProtectionRestoreTrap.
add the leaf of hwPowerCellChargeHighTemperatureProtectionFaultTrap and hwPowerCellChargeHighTemperatureProtectionRestoreTrap.
add the leaf of hwPowerOvervoltageProtectionFaultTrap and hwPowerOvervoltageProtectionRestoreTrap.
add the leaf of hwPowerOvercurrentProtectionFaultTrap and hwPowerOvercurrentProtectionRestoreTrap.
add the leaf of hwPowerBattCellPackFaultTrap and hwPowerBattCellPackRestoreTrap.
add the leaf of hwPowerBattManualDisconnectionFaultTrap and hwPowerBattManualDisconnectionRestoreTrap.
add the node of hwPowerBluetoothSwitch for getting the power bluetooth switch state of SMU"
REVISION "201801160000Z"
DESCRIPTION "V3.55, added enumerate etp4850(129) in hwPowerType leaf for smu EMU."
REVISION "201711270000Z"
DESCRIPTION "V3.54,
add the node hwBatteryHeaterState for getting the heater state of battery.
add the node hwBatteryHealthState for getting the health state of battery.
add the leaf of hwPowerBatteryHeaterFaultTrap and hwPowerBatteryHeaterFaultRestoreTrap.
add the leaf of hwPowerBatteryPortReverseConnectTrap and hwPowerBatteryPortReverseConnectRestoreTrap.
add the table hwBatteryCellTable fot getting the temperature and voltage of battery cell."
REVISION "201709250000Z"
DESCRIPTION "V3.53,
add invalid value(-1) in hwBatteryAntiTheftSwitch.
add invalid value(-1) in hwBatteryAntiTheftTimeout.
add invalid value(-1) in hwLiBatteryGroupChargeLimit."
REVISION "201709120000Z"
DESCRIPTION "V3.52,
add the node hwBatteryAntiTheftSwitch for setting and getting the anti-theft switch of battery.
add the node hwBatteryAntiTheftTimeout for setting and getting the anti-theft timeout time of battery.
add the node hwLiBatteryGroupChargeLimit for setting and getting the LiBattery charge limit quotiety.
add the node hwBatterySequence and hwBatteryAddress for getting the LiBattery sequence and address.
add the leaf of hwPowerBatteryEleCoreFaultTrap and hwPowerBatteryEleCoreRestoreTrap."
REVISION "201709060000Z"
DESCRIPTION "V3.51, add the node hwBatteryGroupType for getting
the type of the lead-acid battery."
REVISION "201704070000Z"
DESCRIPTION "V3.50, add the node hwRemoteUnitSlotDCOutputVol and hwRemoteUnitSlotDCOutputCur for getting
the Remote Power module DC output info."
REVISION "201703310000Z"
DESCRIPTION "V3.49,
modified the Description of hwACCurrentA.
modified the Description of hwACVoltB.
modified the Description of hwACCurrentB.
modified the Description of hwACVoltC.
modified the Description of hwACCurrentC.
modified the Description of hwACVoltageHigh.
modified the Description of hwACVoltageLow.
add enumerate invalid(-1) in hwACVoltageAState leaf.
modified the Description of hwACVoltageAState.
add enumerate invalid(-1) in hwACVoltageBState leaf.
modified the Description of hwACVoltageBState.
add enumerate invalid(-1) in hwACVoltageCState leaf.
modified the Description of hwACVoltageCState."
REVISION "201702170000Z"
DESCRIPTION "V3.48, add the leaf of hwRemoteUnitRestoreTrap and hwRemoteUnitFaultTrap,
hwRemoteUnitCircuitRestoreTrap and hwRemoteUnitCircuitFailTrap."
REVISION "201606220000Z"
DESCRIPTION "V3.47, add the leaf of hwBatteryLowTemperature."
REVISION "201605260000Z"
DESCRIPTION "V3.46, modified the Description of hwBatteryLogTestBatteryTemperature."
REVISION "201511240000Z"
DESCRIPTION "V3.45, modified the objects of hwEmmDigMainsupplyFaultTrap and hwEmmDigMainsupplyRecoverTrap."
REVISION "201511040000Z"
DESCRIPTION "V3.44, modified the Description of hwBatteryTemperature."
REVISION "201509070000Z"
DESCRIPTION "V3.43,
modified the Description of hwPowerName.
modified the Description of hwRectifierVoltage.
modified the Description of hwRectifierCurrent.
modified the default value of hwRectifierCurrentLimit.
modified the Description of hwBatteryGroupBomCode.
modified the Description of hwBatteryCapacity.
modified the Description of hwRemoteUnitDCOutputVol.
modified the Description of hwRemoteUnitDCOutputCur.
modified the Description of hwRemoteUnitSlotCircuitNum.
modified the Description of hwRemoteUnitSlotHardVersion.
modified the Description of hwRemoteUnitSlotSoftVersion.
modified the Description of hwRemoteUnitSlotNum.
modified the Description of hwRemoteUnitCircuitInputVol.
modified the Description of hwRemoteUnitCircuitInputCur.
"
REVISION "201508131200Z"
DESCRIPTION "V3.42,
modified the Description of hwACVoltA.
modified the Description of hwDCVoltageOut
modified the Description of hwDCOutLoadCurrent.
modified the Description of hwBatteryVoltage.
modified the Description of hwBatteryCurrent.
modified the Description of hwLoadVoltageHigh.
modified the Description of hwBatteryRemainCapacity.
"
REVISION "201504170000Z"
DESCRIPTION "V3.41, add the leaf of hwPowerBatteryTempLowTrap and hwPowerBatteryTempLowRestoreTrap,
hwPowerBatteryTempHighTrap and hwPowerBatteryTempHighRestoreTrap,hwPowerBatteryChargeOverVolTrap and
hwPowerBatteryChargeOverVolRestoreTrap,hwPowerBatteryDischargeLackVolTrap and hwPowerBatteryDischargeLackVolRestoreTrap,
hwPowerBatteryChargeOverCurTrap and hwPowerBatteryChargeOverCurRestoreTrap,hwPowerBatteryDischargeOverCurTrap and
hwPowerBatteryDischargeOverCurRestoreTrap for LiBattery alarm."
REVISION "201412160000Z"
DESCRIPTION "V3.39, Correct the node hwPowerRowStatus,hwACRowStatus, hwDCOutRowStatus,
hwLoadInfoRowStatus, hwRectifierRowStatus, hwBatteryGroupRowStatus, hwChargeControlRowStatus,
hwBatteryRowStatus, hwACInfoRowStatus from read-write to read-create."
REVISION "201410250000Z"
DESCRIPTION "V3.38, Modify the node name from hwBatteryState to hwBatteryOperStatus"
REVISION "201406230000Z"
DESCRIPTION "V3.37, Modify the following not normative nodes to satisfy for the new OMSYS tool.
hwPowerType
hwACVoltageAState
hwACVoltageBState
hwACVoltageCState
hwBatteryTestDuration
hwACInfoMCBTrigger"
REVISION "201402270000Z"
DESCRIPTION "V3.36, correct the description of hwPowerType's value list."
REVISION "201401090000Z"
DESCRIPTION "V3.40, add OBJECT IDENTIFIER hwRemotePowerMonObjs and table hwRemoteUnitSysInfoTable,
hwRemoteUnitSlotTable, hwRemoteUnitCircuitTable for Remote Power System RemoteUnit."
REVISION "201312280000Z"
DESCRIPTION "V3.35, modify the leaf of hwRectifierOperState."
REVISION "201311160000Z"
DESCRIPTION "V3.34, modify the leaf of hwRectifierOperState."
REVISION "201212280000Z"
DESCRIPTION "V3.33, added enumerate etp48150(128) in hwPowerType leaf for smu EMU,
added enumerate h801pmu(127) in hwPowerType leaf for H801PMU."
REVISION "201212140000Z"
DESCRIPTION "V3.32, add the leaf of hwBatteryLogTestBatteryTemperature, hwBatteryLogTestBatteryCurrent
and hwBatteryGroupBomCode for battery smart manage.
add enumerate sleep(6) in hwChargeOperStatus leaf.
add enumerate supplyRecoverAutotestTerminated(7) in hwBatteryTestResult leaf."
REVISION "201207240000Z"
DESCRIPTION "V3.31, add the leaf of hwPowerModuleRestoreTrap and hwPowerModuleMismatchTrap for SMU digital alarm."
REVISION "201206250000Z"
DESCRIPTION "V3.30, add enumerate smu(124) in hwPowerType leaf for smu EMU,
modified the name of hwBatteryTestPrealarmThreshold to hwBatteryTestAlarmThreshold,
modified description of hwBatteryTestDuration,hwBatteryTestTerminateVoltage and hwBatteryTestAlarmThreshold,
delete enumerate smu(124),
add enumerate etp4830(125) and enumerate etp4890(126) in hwPowerType leaf for smu EMU"
REVISION "201201090000Z"
DESCRIPTION "V3.29, add the leafs of hwEmmBatt1TempFaultTrap, hwEmmBatt1TempRestoreTrap, hwEmmEnviHumFaultTrap,
hwEmmEnviHumRestoreTrap, hwEmmEnvi1TempFaultTrap, hwEmmEnvi1TempRestoreTrap, hwEmmBattTemFaultTrap,
hwEmmBattTemRecoverTrap and hwEmmPowerBatteryOffRecoverTrap"
REVISION "201112170000Z"
DESCRIPTION "V3.28, added hwBatteryLogTestEfficiency the objects of hwEmmPowerBattaryTestStopTrap.
add the leaf of hwEmmPowerBatteryUnDetectTrap and ch_hwEmmPowerBatteryDetectRecoverTrap for SMU digital alarm."
REVISION "201112080000Z"
DESCRIPTION "V3.27, added hwBatteryTestPrealarmThreshold leaf node for getting and setting battery test prealarm threshold.
added hwBatteryLogTestEfficiency leaf node for inquiry efficiency setting. "
REVISION "201108170000Z"
DESCRIPTION "V3.25, add the leaf of hwEmmPowerBatteryOffTrap for battary power-off."
REVISION "201103160000Z"
DESCRIPTION "V3.25, added enumerate discharge(5) in hwChargeOperStatus leaf for discharge.
add enumerate LiFeBattery(123) in hwPowerType leaf for LiFeBattery EMU"
REVISION "201012170000Z"
DESCRIPTION "V3.24, added Objects hwBatteryLogTestBatteryStatus of hwEmmPowerBattaryTestStopTrap node."
REVISION "201011100000Z"
DESCRIPTION "V3.23, added enumerate power3000(122) in hwPowerType leaf for Power3000 EMU.
Modified the objects of hwEmmPowerBattloopFaultTrap and hwEmmPowerBattloopRecoverTrap.
Added hwEmmDigMainsupplyFaultTrap and hwEmmDigMainsupplyRecoverTrap."
REVISION "201007180900Z"
DESCRIPTION "V3.22, added enumerate power3000(122) in hwPowerType leaf for Power3000 EMU.
Modified the objects of hwEmmPowerBattloopFaultTrap and hwEmmPowerBattloopRecoverTrap.
Added hwEmmDigMainsupplyFaultTrap and hwEmmDigMainsupplyRecoverTrap."
REVISION "201006120900Z"
DESCRIPTION "V3.21, modified description of hwBatteryGroupOperStatus node."
REVISION "201004210900Z"
DESCRIPTION "V3.20, modified node name to avoid conflict."
REVISION "201004080900Z"
DESCRIPTION "V3.19, modified this MIB for clearing simple tester errors and warnings."
REVISION "201003090900Z"
DESCRIPTION "V3.18, added hwBatteryInstallTime leaf node for getting the battery installation time"
REVISION "201002060900Z"
DESCRIPTION "V3.17,Modified the description."
REVISION "201001290900Z"
DESCRIPTION "V3.16,Deleted simple tester MIB compile errors and warnings."
REVISION "200611100900Z"
DESCRIPTION "V3.09,Added hwBatteryHardwareState."
REVISION "200610250900Z"
DESCRIPTION "V3.08,Added hwBatteryVoltageState."
::= { huaweiUtility 2 }
MeasuresRange ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Basic unit of measure:
1.pressure:indicated by mV, 1V = 1000 mV
2.current:indicated by mA, 1A = 1000 mA
3.temperature: indicated by 1% degree centigrade
"
SYNTAX Integer32
hwPowerMonObjects OBJECT IDENTIFIER ::= { hwPower 1 }
hwPowerSysInfoTable OBJECT-TYPE
SYNTAX SEQUENCE OF HwPowerSysInfoEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Power basic information table. The indexes of this table are hwEnvEmuIndex
and hwPowerIndex. hwEnvEmuIndex comes from hwEnvironmentInfoTable and is
the index of the monitoring unit. hwPowerIndex is the index of the power
supply monitored by the monitoring unit.
"
::= { hwPowerMonObjects 1 }
hwPowerSysInfoEntry OBJECT-TYPE
SYNTAX HwPowerSysInfoEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Power basic information table. The indexes of this entry are hwEnvEmuIndex
and hwPowerIndex. hwEnvEmuIndex comes from hwEnvironmentInfoTable and is
the index of the monitoring unit. hwPowerIndex is the index of the power
supply monitored by the monitoring unit.
"
INDEX { hwEnvEmuIndex, hwPowerIndex }
::= { hwPowerSysInfoTable 1 }
HwPowerSysInfoEntry ::=
SEQUENCE {
hwPowerIndex
Integer32,
hwPowerType
INTEGER,
hwPowerName
DisplayString,
hwPowerState
INTEGER,
hwPowerRowStatus
RowStatus,
hwPowerControlMode
INTEGER,
hwPowerRemoteFrameID
Integer32,
hwPowerProtect
INTEGER,
hwPowerVersion
DisplayString,
hwPowerSupplyState
INTEGER,
hwPowerWiringCheckSwitch
INTEGER,
hwPowerLatitude
DisplayString,
hwPowerLongitude
DisplayString,
hwPowerBluetoothSwitch
INTEGER
}
hwPowerIndex OBJECT-TYPE
SYNTAX Integer32 (0..255)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Index of the power supply monitored by the monitoring unit"
::= { hwPowerSysInfoEntry 1 }
hwPowerType OBJECT-TYPE
SYNTAX INTEGER
{
power4875(1),
power4810(2),
power48100(3),
power4850(4),
power48240(5),
power48120(6),
power48300(7),
power48240SinglePhase(8),
universalPower(9),
power4845(10),
rpower(11),
power4805(15),
power4820(16),
onps(17),
power4875l(18),
psma(100),
permAl175nt(101),
mcs1800(102),
mcs1800A(103),
mcs3000(104),
sm40sm60(105),
scu(106),
eltek(107),
dk04(108),
dk04C(109),
dpc(110),
power4830(120),
h831pmua(121),
power3000(122),
liFeBattery(123),
etp4830(125),
etp4890(126),
h801pmu(127),
etp48150(128),
etp4850(129),
etp48200(130),
etp4860(131),
other(255)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Type of the Power emu device.
Options:
1.power4875(1) - Type of the Power emu device is power4875
2.power4810(2) - Type of the Power emu device is power4810
3.power48100(3) - Type of the Power emu device is power48100
4.power4850(4) - Type of the Power emu device is power4850
5.power48240(5) - Type of the Power emu device is power48240
6.power48120(6) - Type of the Power emu device is power48120
7.power48300(7) - Type of the Power emu device is power48300
8.power48240SinglePhase(8) - Type of the Power emu device is power48240SinglePhase
9.universalPower(9) - Type of the Power emu device is universalPower
10.power4845(10) - Pwr4845
11.rpower(11) - Type of the Power emu device is rpower
12.power4805(15) - Type of the Power emu device is power4805
13.power4820(16) - Type of the Power emu device is power4820
14.onps(17) - Type of the Power emu device is onps
15.power4875l(18) - Pwr4875L
16.psma(100) - Type of the Power emu device is psma
17.perm-al175nt(101) - Type of the Power emu device is perm-al175nt
18.mcs1800(102) - Type of the Power emu device is mcs1800
19.mcs1800A(103) - Type of the Power emu device is mcs1800A
20.mcs3000(104) - Type of the Power emu device is mcs3000
21.sm40sm60(105) - Type of the Power emu device is sm40sm60
22.scu(106) - Type of the Power emu device is scu
23.eltek(107) - Type of the Power emu device is eltek
24.dk04(108) - Type of the Power emu device is dk04
25.dk04C(109) - Type of the Power emu device is dk04C
26.dpc(110) - Type of the Power emu device is dpc
27.power4830(120) - Pwr4830L
28.h831pmua(121) - Type of the Power emu device is h831pmua
29.power3000(122) - Pwr3000
30.liFeBattery(123) - Type of the Power emu device is LiFeBattery
31.etp4830(125), - ETP4830
32.etp4890(126), - ETP4890
33.h801pmu(127), - H801PMU
34.etp48150(128), - ETP48150
35.etp4850(129), - ETP4850
36.etp48200(130), - ETP48200
37.etp4860(131), - ETP4860
38.other(255) - Unkown
"
::= { hwPowerSysInfoEntry 2 }
hwPowerName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"
Power name.
Invalid: null string.
"
::= { hwPowerSysInfoEntry 3 }
hwPowerState OBJECT-TYPE
SYNTAX INTEGER
{
normal(1),
fault(2),
protecting(3),
switched(4),
invalid(-1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Power board status:
Refers to the status of communication between the internal monitor board
of the power device and the external upper board.
Options:
1.normal(1) - indicates the normal state
2.fault(2) - indicates the faulty state
3.protecting(3)- indicates that the backup power supply works in the protection state
4.switched(4) - indicates that the main power supply is faulty, and is protected by backup power supply
5.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
"
::= { hwPowerSysInfoEntry 4 }
hwPowerRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-create
STATUS current
DESCRIPTION
"RowStatus standard operation. The values 1 and 2 are supported currently.
1 indicates the activation status, and 2 indicates the non-activation status."
::= { hwPowerSysInfoEntry 5 }
hwPowerControlMode OBJECT-TYPE
SYNTAX INTEGER
{
manualControl(1),
autoControl(2),
invalid(-1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Control mode of the power monitor module.
Options:
1.manualControl(1) - control by manual, the remote mode
2.autoControl(2) - auto control mode, the default is auto control mode
3.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
"
DEFVAL { manualControl }
::= { hwPowerSysInfoEntry 6 }
hwPowerRemoteFrameID OBJECT-TYPE
SYNTAX Integer32 (0..255)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Apply for remote power system.
It is the frame ID that the remote unit exists in"
::= { hwPowerSysInfoEntry 7 }
hwPowerProtect OBJECT-TYPE
SYNTAX INTEGER
{
protect(1),
undoProtect(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Apply for remote power system.
It is used to enable or disable N+1 protection function.
Options:
1.protect(1) - enables the N+1 protection function
2.undoProtect(2) - disables the N+1 protection function"
::= { hwPowerSysInfoEntry 8 }
hwPowerVersion OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Version of power"
::= { hwPowerSysInfoEntry 9 }
hwPowerSupplyState OBJECT-TYPE
SYNTAX INTEGER
{
ac(1),
battery(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"
Power supply modes.
Options:
1.ac(1) - indicates the AC power supply
2.battery(2) - indicates power supply by the batteries
"
::= { hwPowerSysInfoEntry 10 }
hwPowerWiringCheckSwitch OBJECT-TYPE
SYNTAX INTEGER
{
disable(1),
enable(2),
invalid(-1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Power wiring check switch of SMU.
Options:
1. disable(1) - indicates that the power wiring check state of SMU is disabled
2. enable(2) - indicates that the power wiring check state is enabled
3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation
"
DEFVAL { disable }
::= { hwPowerSysInfoEntry 11 }
hwPowerLatitude OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..32))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The power latitude value.
Invalid: -.
"
::= { hwPowerSysInfoEntry 12 }
hwPowerLongitude OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..32))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The power longitude value.
Invalid: -.
"
::= { hwPowerSysInfoEntry 13 }
hwPowerBluetoothSwitch OBJECT-TYPE
SYNTAX INTEGER
{
enable(0),
disable(1),
invalid(-1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Power bluetooth state of SMU.
Options:
1. enable(0) - indicates that the power bluetooth state of SMU is enabled.
2. disable(1) - indicates that the power bluetooth state of SMU is disabled.
3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation
"
DEFVAL { disable }
::= { hwPowerSysInfoEntry 14 }
hwACInputTable OBJECT-TYPE
SYNTAX SEQUENCE OF HwACInputEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"AC input table. Through this table,
AC input monitoring parameters of 4875 power supply, 4845 power supply,
4810 power supply, 48100 power supply, and 48240 power supply can
be set and queried.
The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwACLoopIndex.
hwEnvEmuIndex is the index of the monitoring unit.
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwACLoopIndex is the index of the AC input power supply monitored by the monitoring unit.
"
::= { hwPowerMonObjects 2 }
hwACInputEntry OBJECT-TYPE
SYNTAX HwACInputEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"AC input table. Through this table,
AC input monitoring parameters of 4875 power supply, 4845 power supply,
4810 power supply, 48100 power supply, and 48240 power supply can
be set and queried.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwACLoopIndex.
hwEnvEmuIndex is the index of the monitoring unit.
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwACLoopIndex is the index of the AC input power supply monitored by the monitoring unit."
INDEX { hwEnvEmuIndex, hwPowerIndex, hwACLoopIndex }
::= { hwACInputTable 1 }
HwACInputEntry ::=
SEQUENCE {
hwACLoopIndex
Integer32,
hwACPowerState
INTEGER,
hwACVoltA
MeasuresRange,
hwACCurrentA
MeasuresRange,
hwACVoltB
MeasuresRange,
hwACCurrentB
MeasuresRange,
hwACVoltC
MeasuresRange,
hwACCurrentC
MeasuresRange,
hwACVoltageHigh
MeasuresRange,
hwACVoltageLow
MeasuresRange,
hwACRowStatus
RowStatus,
hwACVoltageAState
INTEGER,
hwACVoltageBState
INTEGER,
hwACVoltageCState
INTEGER
}
hwACLoopIndex OBJECT-TYPE
SYNTAX Integer32 (0..255)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Input loop index. There are two channels of AC current input,
which are the backup for each other."
::= { hwACInputEntry 1 }
hwACPowerState OBJECT-TYPE
SYNTAX INTEGER
{
normal(1),
offline(2),
exceedVoltage(3),
belowVoltage(4),
backup(5),
invalid(-1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status of power supply.
Options:
1.normal(1) - indicates that the power supply is normal
2.offline(2) - indicates that the power supply is offline
3.exceedVoltage(3) - indicates that the power supply is overvoltage
4.belowVoltage(4) - indicates that the power supply is undervoltage
5.backup(5) - indicates that the power supply is not supported currently
6.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
"
::= { hwACInputEntry 2 }
hwACVoltA OBJECT-TYPE
SYNTAX MeasuresRange
UNITS "mV"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"AC Inuput voltage A.
Unit: mV
invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
"
::= { hwACInputEntry 3 }
hwACCurrentA OBJECT-TYPE
SYNTAX MeasuresRange
UNITS "mA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"AC input Current A.
Unit: mA
invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
"
::= { hwACInputEntry 4 }
hwACVoltB OBJECT-TYPE
SYNTAX MeasuresRange
UNITS "mV"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"AC input voltage B.
Unit: mv
invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
"
::= { hwACInputEntry 5 }
hwACCurrentB OBJECT-TYPE
SYNTAX MeasuresRange
UNITS "mA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"AC input current B.
Unit: mA
invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
"
::= { hwACInputEntry 6 }
hwACVoltC OBJECT-TYPE
SYNTAX MeasuresRange
UNITS "mV"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"AC input voltage C.
Unit: mV
invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
"
::= { hwACInputEntry 7 }
hwACCurrentC OBJECT-TYPE
SYNTAX MeasuresRange
UNITS "mA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"AC input current C.
Unit: mA
invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
"
::= { hwACInputEntry 8 }
hwACVoltageHigh OBJECT-TYPE
SYNTAX MeasuresRange
UNITS "mV"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"AC input over-voltage alarm threshold.
Unit: mV
invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
"
DEFVAL { 280000 }
::= { hwACInputEntry 9 }
hwACVoltageLow OBJECT-TYPE
SYNTAX MeasuresRange
UNITS "mV"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"AC input under-voltage alarm threshold.
Unit: mV
invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
"
DEFVAL { 180000 }
::= { hwACInputEntry 10 }
hwACRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-create
STATUS current
DESCRIPTION
"Only the add operation, delete operation, and status query operation are supported."
::= { hwACInputEntry 11 }
hwACVoltageAState OBJECT-TYPE
SYNTAX INTEGER
{
normal(0),
belowVoltage(1) ,
exceedVoltage(2),
missingPhase(3),
invalid(-1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase AB/A of AC input state.
Options:
1. normal(0) - indicates that the Phase AB/A of AC input state is normal
2. belowVoltage(1) - indicates that the Phase AB/A of AC input state is belowVoltage
3. exceedVoltage(2) - indicates that the Phase AB/A of AC input state is exceedVoltage
4. missingPhase(3) - indicates that the Phase AB/A of AC input state is missing-phase
5. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
"
::= { hwACInputEntry 12 }
hwACVoltageBState OBJECT-TYPE
SYNTAX INTEGER
{
normal(0),
belowVoltage(1) ,
exceedVoltage(2),
missingPhase(3),
invalid(-1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase BC/B of AC input state.
Options:
1. normal(0) - indicates that the Phase BC/B of AC input state is normal
2. belowVoltage(1) - indicates that the Phase BC/B of AC input state is belowVoltage
3. exceedVoltage(2) - indicates that the Phase BC/B of AC input state is exceedVoltage
4. missingPhase(3) - indicates that the Phase BC/B of AC input state is missing-phase
5. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
"
::= { hwACInputEntry 13 }
hwACVoltageCState OBJECT-TYPE
SYNTAX INTEGER
{
normal(0),
belowVoltage(1) ,
exceedVoltage(2),
missingPhase(3),
invalid(-1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase CA/C of AC input state.
Options:
1. normal(0) - indicates that the Phase CA/C of AC input state is normal
2. belowVoltage(1) - indicates that the Phase CA/C of AC input state is belowVoltage
3. exceedVoltage(2) - indicates that the Phase CA/C of AC input state is exceedVoltage
4. missingPhase(3) - indicates that the Phase CA/C of AC input state is missing-phase
5. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
"
::= { hwACInputEntry 14 }
hwDCOutTable OBJECT-TYPE
SYNTAX SEQUENCE OF HwDCOutEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"DC output table. Through this table,
DC output monitoring parameters of 4875 power supply, 4845 power supply,
4810 power supply, 482400 power supply, and 48100 power supply can
be set and queried.
The indexes of this table are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex, which comes from hwEnvironmentInfoTable,
is the index of the monitored unit.
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
"
::= { hwPowerMonObjects 3 }
hwDCOutEntry OBJECT-TYPE
SYNTAX HwDCOutEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"DC output table. Through this table,
DC output monitoring parameters of 4875 power supply, 4845 power supply,
4810 power supply, 482400 power supply, and 48100 power supply can
be set and queried.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex, which comes from hwEnvironmentInfoTable,
is the index of the monitored unit.
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
"
INDEX { hwEnvEmuIndex, hwPowerIndex }
::= { hwDCOutTable 1 }
HwDCOutEntry ::=
SEQUENCE {
hwDCVoltageOut
MeasuresRange,
hwDCCurrentOut
MeasuresRange,
hwDCVoltageOutHigh
MeasuresRange,
hwDCVoltageOutLow
MeasuresRange,
hwDCVoltageOutState
INTEGER,
hwDCCurrentOutHigh
MeasuresRange,
hwDCCurrentOutLow
MeasuresRange,
hwDCCurrentOutState
INTEGER,
hwDCOutRowStatus
RowStatus,
hwDCOutLoadCurrent
MeasuresRange,
hwDCOutLoadTmpHigh
MeasuresRange,
hwDCOutRunState
BITS ,
hwDCCommunicationState
INTEGER
}
hwDCVoltageOut OBJECT-TYPE
SYNTAX MeasuresRange
UNITS "mV"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"DC voltage output.
Unit: mV.
invalid: -1"
::= { hwDCOutEntry 1 }
hwDCCurrentOut OBJECT-TYPE
SYNTAX MeasuresRange
UNITS "mA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"DC current output.
Unit: mA"
::= { hwDCOutEntry 2 }
hwDCVoltageOutHigh OBJECT-TYPE
SYNTAX MeasuresRange
UNITS "mV"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Output DC exceed-voltage alarm point.
Default: 58000
Unit: mV"
DEFVAL { 58000 }
::= { hwDCOutEntry 3 }
hwDCVoltageOutLow OBJECT-TYPE
SYNTAX MeasuresRange
UNITS "mV"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Output DC below-voltage alarm point . Default value is 45V.
Unit: mV"
DEFVAL { 45000 }
::= { hwDCOutEntry 4 }
hwDCVoltageOutState OBJECT-TYPE
SYNTAX INTEGER
{
normal(1),
exceedVoltage(2),
belowVoltage(3),
invalid(-1)
}
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"DC output voltage status.
Options:
1. normal(1) - indicates that the DC output voltage state is normal
2. exceedVoltage(2) - indicates that the DC output voltage state is exceedVoltage
3. belowVoltage(3) - indicates that the DC output voltage state is belowVoltage
4.invalid(-1) - indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
"
::= { hwDCOutEntry 5 }
hwDCCurrentOutHigh OBJECT-TYPE
SYNTAX MeasuresRange
UNITS "mA"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Output DC exceed-current alarm point .
Unit: mA"
::= { hwDCOutEntry 6 }
hwDCCurrentOutLow OBJECT-TYPE
SYNTAX MeasuresRange
UNITS "mA"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Output below-current alarm point .
Unit: mA"
::= { hwDCOutEntry 7 }
hwDCCurrentOutState OBJECT-TYPE
SYNTAX INTEGER
{
normal(1),
exceedVoltage(2),
belowVoltage(3),
invalid(-1)
}
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"DC output current status.
Options:
1.normal(1) - indicates that the DC output current state is normal
2.exceedVoltage(2) - indicates that the DC output current state is exceedVoltage
3.belowVoltage(3) - indicates that the DC output current state is belowVoltage
4.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
"
::= { hwDCOutEntry 8 }
hwDCOutRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-create
STATUS current
DESCRIPTION
"RowStatus standard operation"
::= { hwDCOutEntry 9 }
hwDCOutLoadCurrent OBJECT-TYPE
SYNTAX MeasuresRange
UNITS "mA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Total load current of DC output .
Unit: mA.
invalid: -1"
::= { hwDCOutEntry 10 }
hwDCOutLoadTmpHigh OBJECT-TYPE
SYNTAX MeasuresRange
UNITS "0.01 degree"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The off protection point under the load temperature, by default,
it is 65 degrees centigrade.
Unit: 0.01 degree"
DEFVAL { 6500 }
::= { hwDCOutEntry 11 }
hwDCOutRunState OBJECT-TYPE
SYNTAX BITS
{
battery1ChargeCurOver(0),
battery2ChargeCurOver(1),
batteryVoltageOver(2),
batteryVoltageLack(3),
loadOff(4),
batteryOff(5),
communicationFailure(6),
dcOutManual(7)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"DC output running status.
Options:
1.battery1ChargeCurOver(0) - indicates battery 1 charge over-current
2.battery2ChargeCurOver(1) - indicates battery 2 charge over-current
3.batteryVoltageOver(2) - indicates output over-voltage
4.batteryVoltageLack(3) - indicates battery lack-voltage
5.loadOff(4) - indicates load off twice
6.batteryOff(5) - indictes battery protection (off once)
7.communicationFailure(6) - indicates that the communication fails
8.dcOutManual(7) - indicates DC by manual"
::= { hwDCOutEntry 12 }
hwDCCommunicationState OBJECT-TYPE
SYNTAX INTEGER
{
normal(0),
fault(1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"DC communication status.
Options:
1.normal(0) - indicates that the DC communication state is normal
2.fault(1) - indicates that the DC communication state is fault
"
::= { hwDCOutEntry 13 }
hwLoadinfoTable OBJECT-TYPE
SYNTAX SEQUENCE OF HwLoadinfoEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Load information table. Through this table, the load parameter can be set and queried.
The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwLoadIndex.
hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit.
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwLoadIndex is the index of the monitored load.
"
::= { hwPowerMonObjects 4 }
hwLoadinfoEntry OBJECT-TYPE
SYNTAX HwLoadinfoEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Load information table. Through this table, the load parameter can be set and queried.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwLoadIndex.
hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit.
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwLoadIndex is the index of the monitored load.
"
INDEX { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
::= { hwLoadinfoTable 1 }
HwLoadinfoEntry ::=
SEQUENCE {
hwLoadIndex
Integer32,
hwLoadInfoAdminState
INTEGER,
hwLoadInfoOperStatus
INTEGER,
hwLoadCurrent
MeasuresRange,
hwLoadVoltage
MeasuresRange,
hwLoadVoltageHigh
MeasuresRange,
hwLoadLoadName
DisplayString,
hwLoadInfoRowStatus
RowStatus,
hwLoadFuseState
INTEGER,
hwLoadHoreIndex
Integer32
}
hwLoadIndex OBJECT-TYPE
SYNTAX Integer32 (0..255)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Loop index: usually each DC output loop corresponds to a load."
::= { hwLoadinfoEntry 1 }
hwLoadInfoAdminState OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2),
invalid(-1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Load operation.
Options:
1. on(1) - indicates that the Load is enabled
2. off(2) - indicates that the Load is disabled
3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
"
DEFVAL { on }
::= { hwLoadinfoEntry 2 }
hwLoadInfoOperStatus OBJECT-TYPE
SYNTAX INTEGER
{
normal(1),
abnormal(2),
stop(3),
invalid(-1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status of power supply.
Options:
1. normal(1) - indicates that the state of power supply is normal
2. abnormal(2) - indicates that the state of power supply is abnormal
3. stop(3) - indicates that the state of power supply is stopping power supply
4. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
"
::= { hwLoadinfoEntry 3 }
hwLoadCurrent OBJECT-TYPE
SYNTAX MeasuresRange
UNITS "mA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Present current .
Unit: mA"
::= { hwLoadinfoEntry 4 }
hwLoadVoltage OBJECT-TYPE
SYNTAX MeasuresRange
UNITS "mV"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Present voltage .
Unit: mV"
::= { hwLoadinfoEntry 5 }
hwLoadVoltageHigh OBJECT-TYPE
SYNTAX MeasuresRange
UNITS "mV"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Off voltage (Stop external voltage), in unit of mV,
When DC output voltage exceeds the value, the load will be automatically cut off.
Unit: mV
"
::= { hwLoadinfoEntry 6 }
hwLoadLoadName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Load name: usually each DC output loop corresponds to a load."
::= { hwLoadinfoEntry 7 }
hwLoadInfoRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-create
STATUS current
DESCRIPTION
"RowStatus standard operation"
::= { hwLoadinfoEntry 8 }
hwLoadFuseState OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2),
invalid(-1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Load fuse state, including the auxiliary load fuse.
Options:
1. on(1) - indicates that the fuse is connected
2. off(2) - indicates that the fuse is disconnected
3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
"
::= { hwLoadinfoEntry 9 }
hwLoadHoreIndex OBJECT-TYPE
SYNTAX Integer32 (0..255)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"
load hore index
"
::= { hwLoadinfoEntry 10 }
hwRectifierTable OBJECT-TYPE
SYNTAX SEQUENCE OF HwRectifierEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Rectifier module table.
Through this table, the status information of the rectifier module
can be set and queried.
The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwRectifierIndex.
hwEnvEmuIndex, which comes from hwEnvironmentInfoTable,
is the index of the monitored unit.
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwRectifierIndex is the index of the monitored rectifier module under the power supply.
"
::= { hwPowerMonObjects 5 }
hwRectifierEntry OBJECT-TYPE
SYNTAX HwRectifierEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Rectifier module table.
Through this table, the status information of the rectifier module
can be set and queried.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwRectifierIndex.
hwEnvEmuIndex, which comes from hwEnvironmentInfoTable,
is the index of the monitored unit.
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwRectifierIndex is the index of the monitored rectifier module under the power supply.
"
INDEX { hwEnvEmuIndex, hwPowerIndex, hwRectifierIndex }
::= { hwRectifierTable 1 }
HwRectifierEntry ::=
SEQUENCE {
hwRectifierIndex
Integer32,
hwRectifierAdminState
INTEGER,
hwRectifierOperState
INTEGER,
hwRectifierVoltage
MeasuresRange,
hwRectifierCurrent
MeasuresRange,
hwRectifierRowStatus
RowStatus,
hwRectifierCurrentLimit
TruthValue,
hwRectifierRunState
BITS,
hwRectifierChargeState
INTEGER
}
hwRectifierIndex OBJECT-TYPE
SYNTAX Integer32 (0..255)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rectifier Module index. There are multiple rectifier
modules to a power source.
"
::= { hwRectifierEntry 1 }
hwRectifierAdminState OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2),
invalid(-1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Switch operation of rectifier module.
Options:
1.on(1) - indicates that the Rectifier module is enabled
2.off(2) - indicates that the Rectifier module is disabled
3.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
"
DEFVAL { on }
::= { hwRectifierEntry 2 }
hwRectifierOperState OBJECT-TYPE
SYNTAX INTEGER
{
normal(1),
fault(2),
protect(3),
communicationFailure(4),
on(5),
noConfig(6),
offline(7),
close(8),
invalid(-1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Present state, 5 and 6 respectively indicates the on/off state of the 48100 power device.
Options:
1. normal(1) - indicates that the Rectifier operation state is normal
2. fault(2) - indicates that the Rectifier operation state is fault
3. protect(3) - indicates that the Rectifier operation state is protect
4. communicationFailure(4) - indicates that the Rectifier operation state is communicationFailure
5. on(5) - indicates that the Rectifier operation state is on
6. noConfig(6) - indicates that the Rectifier operation state is not Configured
7. offline(7) - indicates that the Rectifier operation state is offline
8. close(8) - indicates that the Rectifier operation state is closed
9. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
"
::= { hwRectifierEntry 3 }
hwRectifierVoltage OBJECT-TYPE
SYNTAX MeasuresRange
UNITS "mV"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Output voltage .
Unit: mV
Invalid(-1) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
"
::= { hwRectifierEntry 4 }
hwRectifierCurrent OBJECT-TYPE
SYNTAX MeasuresRange
UNITS "mA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Output current .
Unit: mA
Invalid(-1) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
"
::= { hwRectifierEntry 5 }
hwRectifierRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-create
STATUS current
DESCRIPTION
"RowStatus standard operation"
::= { hwRectifierEntry 6 }
hwRectifierCurrentLimit OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"current limit switch"
DEFVAL { 2 }
::= { hwRectifierEntry 7 }
hwRectifierRunState OBJECT-TYPE
SYNTAX BITS
{
rectifierOn(0),
averageCharge(1),
output(2),
isLimit(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Running state of rectifier module.
Options:
1.rectifierOn(0) - indicates that the module is on
2.averageCharge(1) - indicates that the module is being averagely charged.
3.output(2) - indicates that the module has output
4. isLimit(3) - indicates the current limit switch
"
::= { hwRectifierEntry 8 }
hwRectifierChargeState OBJECT-TYPE
SYNTAX INTEGER
{
float(0),
average(1),
test(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Charging state of rectifier.
Options:
1. float(0) - indicates that the Charge state of Rectifier is float
2. average(1) - indicates that the Charge state of Rectifier is average
3. test(2) - indicates that the Charge state of Rectifier is test
"
::= { hwRectifierEntry 9 }
hwBatteryGroup OBJECT IDENTIFIER ::= { hwPowerMonObjects 6 }
hwBatteryGroupTable OBJECT-TYPE
SYNTAX SEQUENCE OF HwBatteryGroupEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Basic information table of battery group.
The indexes of this table are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit,
and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
"
::= { hwBatteryGroup 1 }
hwBatteryGroupEntry OBJECT-TYPE
SYNTAX HwBatteryGroupEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Basic information table of battery group.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit,
and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
"
INDEX { hwEnvEmuIndex, hwPowerIndex }
::= { hwBatteryGroupTable 1 }
HwBatteryGroupEntry ::=
SEQUENCE {
hwBatteryGroupCapacity
Integer32,
hwBatteryGroupCapcaityRemain
Integer32,
hwBatteryGroups
Integer32,
hwBatteryGroupVoltageLow
MeasuresRange,
hwBatteryGroupChargeLimit
MeasuresRange,
hwBatteryGroupRowStatus
RowStatus,
hwBatteryGroupOperStatus
INTEGER,
hwBatteryGroupVoltageHigh
MeasuresRange,
hwBatteryGroupTwiceOffVoltage
MeasuresRange,
hwBatteryGroupProtectVoltage
MeasuresRange,
hwBatteryGroupTmpOffHigh
MeasuresRange,
hwBatteryInstallTime
DisplayString,
hwBatteryGroupBomCode
DisplayString,
hwBatteryGroupType
INTEGER,
hwLiBatteryGroupChargeLimit
Integer32
}
hwBatteryGroupCapacity OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Total capacity of the present battery group.
Unit: Ah"
::= { hwBatteryGroupEntry 1 }
hwBatteryGroupCapcaityRemain OBJECT-TYPE
SYNTAX Integer32 (-1..100)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Total remain capacity of the present battery group .
invalid(-1) indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
Unit: Ah"
::= { hwBatteryGroupEntry 2 }
hwBatteryGroups OBJECT-TYPE
SYNTAX Integer32 (0..255)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Number of battery group"
DEFVAL { 2 }
::= { hwBatteryGroupEntry 3 }
hwBatteryGroupVoltageLow OBJECT-TYPE
SYNTAX MeasuresRange
UNITS "mV"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"When the voltage of the battery group is lower than the value set,
the battery group will no longer supply power. Its unit is mV.
Default: 43000
Unit: mV
"
DEFVAL { 43000 }
::= { hwBatteryGroupEntry 4 }
hwBatteryGroupChargeLimit OBJECT-TYPE
SYNTAX MeasuresRange
UNITS "percent"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Charge limit point quotient, the product of which and the max capacity
of the battery group is the max charge current allowed.
Default: 15
Unit: percent
"
DEFVAL { 15 }
::= { hwBatteryGroupEntry 5 }
hwBatteryGroupRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-create
STATUS current
DESCRIPTION
"RowStatus standard operation"
::= { hwBatteryGroupEntry 6 }
hwBatteryGroupOperStatus OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2),
invalid(-1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The State of the battery supply which was connected with Power EMU.
To use this function,please confirm that the battery group was connected with Power EMU and the Power EMU state is Normal.
When the mains supply is abnormal, the battery group usually supplies power in an emergency.
Options:
1.on(1) - indicates that the state of the battery power supply is on
2.off(2) - indicates that the state of the battery power supply is off
3.invalid(-1) - indicates that the device can not get the value,e.g. the EMU does not support this operation, or the EMU state is abnormal"
::= { hwBatteryGroupEntry 7 }
hwBatteryGroupVoltageHigh OBJECT-TYPE
SYNTAX MeasuresRange
UNITS "mV"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"When the voltage of the battery group is higher than the value set, the battery group
will no longer supply power. Its unit is mV.
Default: 43000
Unit: mV
"
DEFVAL { 43000 }
::= { hwBatteryGroupEntry 8 }
hwBatteryGroupTwiceOffVoltage OBJECT-TYPE
SYNTAX MeasuresRange
UNITS "mV"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The twice off protection voltage of the battery group. Its unit is mV.
Default: 44000
Unit: mV
"
DEFVAL { 44000 }
::= { hwBatteryGroupEntry 9 }
hwBatteryGroupProtectVoltage OBJECT-TYPE
SYNTAX MeasuresRange
UNITS "mV"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The first off protection voltage of the battery,
whose default is 43V.
Default: 43000
Unit: mV
"
DEFVAL { 43000 }
::= { hwBatteryGroupEntry 10 }
hwBatteryGroupTmpOffHigh OBJECT-TYPE
SYNTAX MeasuresRange
UNITS "0.01 degree"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The high temperature off protection point of the battery group,
whose default is 50 degrees centigrade.
Unit: 0.01 degree
"
DEFVAL { 5000 }
::= { hwBatteryGroupEntry 11 }
hwBatteryInstallTime OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"
The installing date of battery group.
"
::= { hwBatteryGroupEntry 12 }
hwBatteryGroupBomCode OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"
The BOM code of battery.
Invalid: null string.
"
::= { hwBatteryGroupEntry 13 }
hwBatteryGroupType OBJECT-TYPE
SYNTAX INTEGER
{
general(1),
tcbc(2),
tcbb(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"
The type of lead-acid battery.
1: general.
2: tcbc.
3: tcbb.
"
DEFVAL { general }
::= { hwBatteryGroupEntry 14 }
hwLiBatteryGroupChargeLimit OBJECT-TYPE
SYNTAX Integer32 (-1 | 50..1050)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The charge limit quotiety of the LiBattery.
SNMP uses it which has been enlarged 1000 by host.
user uses it which has been lessened 1000 by SNMP.
Default: 1050.
The invalid value -1 indicates that the device can not get the value, e.g. the EMU does not support this operation.
"
DEFVAL { 1050 }
::= { hwBatteryGroupEntry 15 }
hwChargeTable OBJECT-TYPE
SYNTAX SEQUENCE OF HwChargeEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Charge management table.
Through this table, the charging parameter of the battery can be set and queried.
The indexes of this table are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit,
and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
"
::= { hwBatteryGroup 2 }
hwChargeEntry OBJECT-TYPE
SYNTAX HwChargeEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Charge management table.
Through this table, the charging parameter of the battery can be set and queried.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit,
and hwPowerIndex is the index of the power supply monitored by the monitoring unit."
INDEX { hwEnvEmuIndex, hwPowerIndex }
::= { hwChargeTable 1 }
HwChargeEntry ::=
SEQUENCE {
hwChargeAdminStatus
INTEGER,
hwChargeOperStatus
INTEGER,
hwAverageChargeVoltage
MeasuresRange,
hwFloatChargeVoltage
MeasuresRange,
hwChargeControlRowStatus
RowStatus,
hwAverageChargeTime
Integer32,
hwBatteryTmpRedeemingQuotiety
Integer32
}
hwChargeAdminStatus OBJECT-TYPE
SYNTAX INTEGER
{
average(1),
float(2),
auto(3),
invalid(-1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Charge management mode.
Options:
1. average(1) - indicates that the charge management mode is average charge
2. float(2) - indicates that the charge management mode is float charge
3. auto(3) - indicates that the charge management mode is auto-control charge
4. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
"
DEFVAL { float }
::= { hwChargeEntry 1 }
hwChargeOperStatus OBJECT-TYPE
SYNTAX INTEGER
{
average(1),
float(2),
full(3),
noCharge(4),
discharge(5),
sleep(6),
invalid(-1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Charge operation status.
Options:
1. average(1) - indicates that the charge operation state is average charge
2. float(2) - indicates that the charge operation state is float charge
3. full(3) - indicates that the charge operation state is full
4. noCharge(4) - indicates that there is no charge in operation
5. discharge(5) - indicates that there is discharge in operation
6. sleep(6) - indicates that the charge operation state is sleep
7. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
"
::= { hwChargeEntry 2 }
hwAverageChargeVoltage OBJECT-TYPE
SYNTAX MeasuresRange
UNITS "mV"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Voltage value of average charge, in unit of mV.
Default: 56500
Unit: mV
"
DEFVAL { 56500 }
::= { hwChargeEntry 3 }
hwFloatChargeVoltage OBJECT-TYPE
SYNTAX MeasuresRange
UNITS "mV"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Voltage value of float charge .
Default: 53500
Unit: mV
"
DEFVAL { 53500 }
::= { hwChargeEntry 4 }
hwChargeControlRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-create
STATUS current
DESCRIPTION
"RowStatus standard operation"
::= { hwChargeEntry 5 }
hwAverageChargeTime OBJECT-TYPE
SYNTAX Integer32
UNITS "day"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Timing average charge time interval, effective range is 190 days.
Default :value is 60 days
Unit: day"
DEFVAL { 60 }
::= { hwChargeEntry 6 }
hwBatteryTmpRedeemingQuotiety OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Temperature redeeming quotient, used to set the co-relation
between the float charge voltage and the battery temperature.
It means How much will the float charge voltage decrease
with the increasing of every degree centigrade of the battery
temperature. The unit is mV.
Specific value is determined by the redeem feature curve of
floating charge for the battery group used.
Default value is 100mV
"
DEFVAL { 100 }
::= { hwChargeEntry 7 }
hwBatteryTable OBJECT-TYPE
SYNTAX SEQUENCE OF HwBatteryEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Battery group state table.
Through this table, the status parameter of a battery group can be set and queried.
The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwBatteryIndex.
hwEnvEmuIndex is the index of the monitored unit.
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwBatteryIndex is the index of the monitored battery group.
"
::= { hwBatteryGroup 3 }
hwBatteryEntry OBJECT-TYPE
SYNTAX HwBatteryEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Battery group state table.
Through this table, the status parameter of a battery group can be set and queried.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryIndex.
hwEnvEmuIndex is the index of the monitored unit.
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwBatteryIndex is the index of the monitored battery group.
"
INDEX { hwEnvEmuIndex, hwPowerIndex, hwBatteryIndex }
::= { hwBatteryTable 1 }
HwBatteryEntry ::=
SEQUENCE {
hwBatteryIndex
Integer32,
hwBatteryCapacity
Integer32,
hwBatteryLoopState
INTEGER,
hwBatteryVoltage
MeasuresRange,
hwBatteryOperStatus
INTEGER,
hwBatteryCurrent
MeasuresRange,
hwBatteryTemperature
Integer32,
hwBatteryRowStatus
RowStatus,
hwBatteryCurrentHigh
MeasuresRange,
hwBatteryFuseState
INTEGER,
hwBatteryContactState
INTEGER,
hwBatteryRemainCapacity
Integer32,
hwBatteryProtectState
INTEGER,
hwBatteryVoltageState
INTEGER,
hwBatteryHardwareState
INTEGER,
hwBatteryLowTemperature
Integer32,
hwBatteryAntiTheftSwitch
INTEGER,
hwBatteryAntiTheftTimeout
Integer32,
hwBatterySequence
Integer32,
hwBatteryAddress
Integer32,
hwBatteryHeaterState
INTEGER,
hwBatteryHealthState
Integer32
}
hwBatteryIndex OBJECT-TYPE
SYNTAX Integer32 (0..255)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Battery group loop index"
::= { hwBatteryEntry 1 }
hwBatteryCapacity OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The permitted max battery capacity of the battery group loop charge.
Unit: Ah
Invalid(-1) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
"
DEFVAL { 100 }
::= { hwBatteryEntry 2 }
hwBatteryLoopState OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2),
invalid(-1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The battery group present status.
Options:
1. on(1) - indicates that the present state of battery group is on
2. off(2) - indicates that the present state of battery group is off
3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
"
::= { hwBatteryEntry 3 }
hwBatteryVoltage OBJECT-TYPE
SYNTAX MeasuresRange
UNITS "mV"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The loop voltage of the battery group.
Unit: mV
invalid: -1"
::= { hwBatteryEntry 4 }
hwBatteryOperStatus OBJECT-TYPE
SYNTAX INTEGER
{
charge(1),
discharge(2),
invalid(-1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present state of the battery group loop.
Options:
1. charge(1) - indicates that the present state of the battery group loop is charge
2. discharge(2) - indicates that the present state of the battery group loop is discharge
3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
"
::= { hwBatteryEntry 5 }
hwBatteryCurrent OBJECT-TYPE
SYNTAX MeasuresRange
UNITS "mA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Present current .
Unit: mA
invalid: -1"
::= { hwBatteryEntry 6 }
hwBatteryTemperature OBJECT-TYPE
SYNTAX Integer32
UNITS "degree"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The loop temperature of the battery group.
Unit: degree
Invaild:2147483647(0X7FFFFFFF)
"
::= { hwBatteryEntry 7 }
hwBatteryRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-create
STATUS current
DESCRIPTION
"RowStatus standard operation"
::= { hwBatteryEntry 8 }
hwBatteryCurrentHigh OBJECT-TYPE
SYNTAX MeasuresRange
UNITS "mA"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The over-current alarm point of the battery group.
Unit: mA"
::= { hwBatteryEntry 9 }
hwBatteryFuseState OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2),
invalid(-1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Battery fuse state.
Options:
1. on(1) - indicates that the fuse is connected
2. off(2) - indicates that the fuse is disconnected
3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
"
::= { hwBatteryEntry 10 }
hwBatteryContactState OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2),
invalid(-1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The state of the battery contactor.
Options:
1. on(1) - indicates that the contactor is connected
2. off(2) - indicates that the contactor is disconnected
3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal"
::= { hwBatteryEntry 11 }
hwBatteryRemainCapacity OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Remain capacity of the battery,
invalid(-1)
"
::= { hwBatteryEntry 12 }
hwBatteryProtectState OBJECT-TYPE
SYNTAX INTEGER
{
normal(1),
overtemperature(2),
overCurrent(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Protection status of the battery.
Options:
1. normal(1) - indicates that the Protection status of the battery is normal
2. overtemperature(2) - indicates that the Protection status of the battery is overtemperature
3. overCurrent(3) - indicates that the Protection status of the battery is overCurrent
"
::= { hwBatteryEntry 13 }
hwBatteryVoltageState OBJECT-TYPE
SYNTAX INTEGER
{
normal(1),
exceedVoltage(2),
belowVoltage(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Voltage state of Battery.
Options:
1. normal(1) - indicates that Voltage state of Battery is normal
2. exceedVoltage(2) - indicates that Voltage state of Battery is exceedVoltage
3. belowVoltage(3) - indicates that Voltage state of Battery is belowVoltage
"
::= { hwBatteryEntry 14 }
hwBatteryHardwareState OBJECT-TYPE
SYNTAX INTEGER
{
normal(1),
fault(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Hardware State of Battery.
Options:
1. normal(1) - indicates that the hardware state of Battery is normal
2. fault(2) - indicates that the hardware state of Battery is fault
"
::= { hwBatteryEntry 15 }
hwBatteryLowTemperature OBJECT-TYPE
SYNTAX Integer32
UNITS "degree"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The lowest loop temperature of the battery group.
Unit: degree
Invaild:2147483647(0X7FFFFFFF)
"
::= { hwBatteryEntry 16 }
hwBatteryAntiTheftSwitch OBJECT-TYPE
SYNTAX INTEGER
{
disable(1),
enable(2),
invalid(-1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Anti-theft switch of Battery.
Options:
1. disable(1) - indicates that the anti-theft state of Battery is disabled
2. enable(2) - indicates that the anti-theft state of Battery is enabled
3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation"
DEFVAL { disable }
::= { hwBatteryEntry 17 }
hwBatteryAntiTheftTimeout OBJECT-TYPE
SYNTAX Integer32 (-1 | 8..720)
UNITS "hour"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The anti-theft timeout time of battery.
The invalid value -1 indicates that the device can not get the value, e.g. the EMU does not support this operation."
DEFVAL { 72 }
::= { hwBatteryEntry 18 }
hwBatterySequence OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The sequence of LiBattery."
::= { hwBatteryEntry 19 }
hwBatteryAddress OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The address of LiBattery which corresponds to the subnode of LiBattery."
::= { hwBatteryEntry 20 }
hwBatteryHeaterState OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2),
noconfig(3),
invalid(-1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The state of battery heater."
::= { hwBatteryEntry 21 }
hwBatteryHealthState OBJECT-TYPE
SYNTAX Integer32 (-1..100)
UNITS "%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The health state of battery.
Unit:%
invalid:-1"
::= { hwBatteryEntry 22 }
hwBatteryTestTable OBJECT-TYPE
SYNTAX SEQUENCE OF HwBatteryTestEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Battery test table.
The indexes of this table are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit,
and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
"
::= { hwBatteryGroup 4 }
hwBatteryTestEntry OBJECT-TYPE
SYNTAX HwBatteryTestEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Battery test table.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit,
and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
"
INDEX { hwEnvEmuIndex, hwPowerIndex }
::= { hwBatteryTestTable 1 }
HwBatteryTestEntry ::=
SEQUENCE {
hwBatteryTestAdminStatus
INTEGER,
hwBatteryTestAutoDischargePeriod
Integer32,
hwBatteryTestResult
INTEGER,
hwBatteryTestStartTime
DateAndTime,
hwBatteryTestDuration
Integer32,
hwBatteryTestTerminateVoltage
Integer32,
hwBatteryTestTotalDischargeAH
Integer32,
hwBatteryTestOperStatus
INTEGER,
hwBatteryTestPhase
INTEGER,
hwBatteryTestStartHour
Integer32,
hwBatteryTestAlarmThreshold
Integer32
}
hwBatteryTestAdminStatus OBJECT-TYPE
SYNTAX INTEGER
{
start(1),
terminate(2),
enableAutoTest(3),
disableAutoTest(4),
timeautoTest(5),
offautoTest(6),
timeoffautoTest(7)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Battery test admin status.
Options:
1. start(1) - indicates that the Battery starts testing
2. terminate(2) - indicates that the Battery terminates testing
3. enableAutoTest(3) - indicates that the Battery enables auto test function
4. disableAutoTest(4) - indicates that the Battery disables auto test function
5. timeautoTest(5) - indicates that the Battery enable timing auto test function
6. offautoTest(6) - indicates that the Battery enable off auto test function
7. timeoffautoTest(7) - indicates that the Battery enable timing+off auto test
"
::= { hwBatteryTestEntry 1 }
hwBatteryTestAutoDischargePeriod OBJECT-TYPE
SYNTAX Integer32
UNITS "day"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Auto discharge test period.
Effective range is 30 -240 days.
Default: 120
Unit: day
"
DEFVAL { 120 }
::= { hwBatteryTestEntry 2 }
hwBatteryTestResult OBJECT-TYPE
SYNTAX INTEGER
{
testing(1),
complete(2),
alarmTerminated(3),
hostTerminated(4),
overtimeTerminated(5),
normal(6),
supplyRecoverAutotestTerminated(7)
}
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Test result:
Options:
1. testing(1) - indicates that the Battery test is in operation
2. complete(2) - indicates that the Battery test is completed normally
3. alarmTerminated(3) - indicates that the Battery test is stopped by alarms
4. hostTerminated(4) - indicates that the Battery test is stopped by the host
5. overtimeTerminated(5) - indicates that the Battery test is stopped because of over time
6. normal(6) - indicates that the Battery test is not started
7. supplyRecoverAutotestTerminated(7) - indicates that the Battery test is stopped because of supply recover
"
::= { hwBatteryTestEntry 3 }
hwBatteryTestStartTime OBJECT-TYPE
SYNTAX DateAndTime
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Time of starting test"
::= { hwBatteryTestEntry 4 }
hwBatteryTestDuration OBJECT-TYPE
SYNTAX Integer32
UNITS "hour"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Battery discharge test duration.
Effective range is 1-100 hours.
Default :value is 10 hours
Unit: hour
"
::= { hwBatteryTestEntry 5 }
hwBatteryTestTerminateVoltage OBJECT-TYPE
SYNTAX Integer32
UNITS "mV"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Battery discharge test end voltage.
Effective range (DC lack alarm voltage+0.5V-voltage of floating charge).
Default: 45600
Unit: mV
"
::= { hwBatteryTestEntry 6 }
hwBatteryTestTotalDischargeAH OBJECT-TYPE
SYNTAX Integer32
UNITS "mAH"
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"
Total discharge AH.
Unit: mAH
"
::= { hwBatteryTestEntry 7 }
hwBatteryTestOperStatus OBJECT-TYPE
SYNTAX INTEGER
{
autoTestPermit(1),
autoTestForbid(2),
timeautoTestPermit(3),
offautoTestPermit(4),
timeoffautoTestPermit(5)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"
Battery discharge test operate status.
Options:
1. autoTestPermit(1) - indicates that auto discharge test is enabled
2. autoTestForbid(2) - indicates that auto discharge test is disabled
3. timeautoTestPermit(3) - indicates that timing auto discharge test is enabled
4. offautoTestPermit(4) - indicates that off auto discharge test is enabled
5. timeoffautoTestPermit(5) - indicates that timing-off auto discharge test is enabled"
::= { hwBatteryTestEntry 8 }
hwBatteryTestPhase OBJECT-TYPE
SYNTAX INTEGER
{
charge(1),
discharge(2),
record(3),
finish(4),
waitingfordischarge(5)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Battery test phase.
Options:
1. charge(1) - indicates the batter test phase is charge
2. discharge(2) - indicates the batter test phase is discharge
3. record(3) - indicates the power equipment recording test result
4. finish(4) - indicates that the discharge is complete
5.waitingfordischarge(5) - indicates that preparation is ready for discharge command
"
::= { hwBatteryTestEntry 9 }
hwBatteryTestStartHour OBJECT-TYPE
SYNTAX Integer32
UNITS "hour"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Discharge start time.
Effective range is 0 23
Default: 0
Unit: hour
"
DEFVAL { '0'b }
::= { hwBatteryTestEntry 10 }
hwBatteryTestAlarmThreshold OBJECT-TYPE
SYNTAX Integer32
UNITS "percent"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The battery discharge test alarm threshold in ratio of the range:1~79."
DEFVAL { 70 }
::= { hwBatteryTestEntry 11 }
hwBatteryLogTestTable OBJECT-TYPE
SYNTAX SEQUENCE OF HwBatteryLogTestEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Battery test result table,
Through this table, the discharging test result of the battery group can be saved and queried.
The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwBatteryLogTestIndex.
hwEnvEmuIndex is the index of the monitored unit.
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwBatteryLogTestIndex is the index of the monitored battery.
"
::= { hwBatteryGroup 5 }
hwBatteryLogTestEntry OBJECT-TYPE
SYNTAX HwBatteryLogTestEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Battery test result table,
Through this table, the discharging test result of the battery group can be saved and queried.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryLogTestIndex.
hwEnvEmuIndex is the index of the monitored unit.
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwBatteryLogTestIndex is the index of the monitored battery.
"
INDEX { hwEnvEmuIndex, hwPowerIndex, hwBatteryLogTestIndex }
::= { hwBatteryLogTestTable 1 }
HwBatteryLogTestEntry ::=
SEQUENCE {
hwBatteryLogTestIndex
Integer32,
hwBatteryLogTestStartTime
DateAndTime,
hwBatteryLogTestDischargeDuration
Integer32,
hwBatteryLogTestTerminateVoltage
Integer32,
hwBatteryLogTestBatteryStatus
INTEGER,
hwBatteryLogTestTotalDischargeAH
Integer32,
hwBatteryLogTestFinish
INTEGER,
hwBatteryLogTestEfficiency
Integer32,
hwBatteryLogTestBatteryTemperature
Integer32,
hwBatteryLogTestBatteryCurrent
Integer32
}
hwBatteryLogTestIndex OBJECT-TYPE
SYNTAX Integer32 (0..255)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Battery discharge test result index"
::= { hwBatteryLogTestEntry 1 }
hwBatteryLogTestStartTime OBJECT-TYPE
SYNTAX DateAndTime
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Battery discharge test start time"
::= { hwBatteryLogTestEntry 2 }
hwBatteryLogTestDischargeDuration OBJECT-TYPE
SYNTAX Integer32
UNITS "minute"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Duration of discharge.
Unit: minute"
::= { hwBatteryLogTestEntry 3 }
hwBatteryLogTestTerminateVoltage OBJECT-TYPE
SYNTAX Integer32
UNITS "mV"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"End voltage of battery discharge test .
Unit: mV"
::= { hwBatteryLogTestEntry 4 }
hwBatteryLogTestBatteryStatus OBJECT-TYPE
SYNTAX INTEGER
{
expectant(1),
unexpected(2),
unknown(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Battery status.
Options:
1. expectant(1) - indicates the batter test state is expectant
2. unexpected(2) - indicates the batter test state is unexpected
3. unknown(3) - indicates the batter test state is unknown
"
::= { hwBatteryLogTestEntry 5 }
hwBatteryLogTestTotalDischargeAH OBJECT-TYPE
SYNTAX Integer32
UNITS "mAH"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"
Discharge cumulate AH.
Unit: mAH
"
::= { hwBatteryLogTestEntry 6 }
hwBatteryLogTestFinish OBJECT-TYPE
SYNTAX INTEGER
{
testing(1),
completed(2),
alarmTerminated (3),
hostTerminated(4),
overtimeTerminated(5),
notTest(6),
supplyRecoverAutotestTerminated(7)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Battery Test result.
Options:
1. testing(1) - indicates that it is during testing
2. completed(2) - indicates that the test is completed normally
3. alarmTerminated(3) - indicates that the test is stopped by alarms
4. hostTerminated(4) - indicates that the test is stopped by the host
5. overtimeTerminated(5) - indicates that the test is stopped because of over 100 hours
6. notTest(6) - indicates that the test is not started
7. supplyRecoverAutotestTerminated(7) - indicates that the test is stopped because of supply recover
"
::= { hwBatteryLogTestEntry 7 }
hwBatteryLogTestEfficiency OBJECT-TYPE
SYNTAX Integer32
UNITS "percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"
The information of battery test efficiency.
"
::= { hwBatteryLogTestEntry 8 }
hwBatteryLogTestBatteryTemperature OBJECT-TYPE
SYNTAX Integer32
UNITS "0.01 Degree"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Battery discharge test end Temperature.
Unit: 0.01 Degree
Invaild: 0X7FFFFFFF
"
::= { hwBatteryLogTestEntry 9 }
hwBatteryLogTestBatteryCurrent OBJECT-TYPE
SYNTAX Integer32
UNITS "mA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Battery discharge test average Current.
Unit: mA
"
::= { hwBatteryLogTestEntry 10 }
hwBatteryCellTable OBJECT-TYPE
SYNTAX SEQUENCE OF HwBatteryCellEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The state of battery cell.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryCellIndex.
hwEnvEmuIndex is the index of the monitored unit.
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwBatteryCellIndex is the index of the battery cell.
"
::= { hwBatteryGroup 6 }
hwBatteryCellEntry OBJECT-TYPE
SYNTAX HwBatteryCellEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The state of battery cell.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryCellIndex.
hwEnvEmuIndex is the index of the monitored unit.
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwBatteryCellIndex is the index of battery cell.
"
INDEX { hwEnvEmuIndex, hwPowerIndex, hwBatteryCellIndex }
::= { hwBatteryCellTable 1 }
HwBatteryCellEntry ::=
SEQUENCE {
hwBatteryCellIndex
Integer32,
hwBatteryCellTemperature
Integer32,
hwBatteryCellVoltage
Integer32
}
hwBatteryCellIndex OBJECT-TYPE
SYNTAX Integer32 (0..15)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The index of battery cell."
::= { hwBatteryCellEntry 1 }
hwBatteryCellTemperature OBJECT-TYPE
SYNTAX Integer32
UNITS "C"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The temperature of battery cell.
Unit: C
Non-value: 0x7FFFFFFF"
::= { hwBatteryCellEntry 2 }
hwBatteryCellVoltage OBJECT-TYPE
SYNTAX Integer32
UNITS "mV"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The voltage of battery cell.
Unit: mV
Non-value: -1"
::= { hwBatteryCellEntry 3 }
hwRemoteProvidePowerInfoTable OBJECT-TYPE
SYNTAX SEQUENCE OF HwRemoteProvidePowerInfoEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Remote provide power basic information table.
The indexes of this table are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit,
and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
"
::= { hwPowerMonObjects 7 }
hwRemoteProvidePowerInfoEntry OBJECT-TYPE
SYNTAX HwRemoteProvidePowerInfoEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Remote provide power basic information table.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit,
and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
"
INDEX { hwEnvEmuIndex,hwPowerIndex }
::= { hwRemoteProvidePowerInfoTable 1 }
HwRemoteProvidePowerInfoEntry ::=
SEQUENCE {
hwPowerCentralState
INTEGER,
hwPowerCentralDCInPutState
INTEGER,
hwPowerCentralDCOutputState
INTEGER,
hwPowerCentralDCOutputMode
INTEGER,
hwPowerRemoteCommState
INTEGER,
hwPowerRemoteDCInputState
INTEGER,
hwPowerRemoteLineCurState
INTEGER,
hwPowerRemotePowerState
INTEGER,
hwPowerRemoteLineState
BITS,
hwPowerCentralLoadState
INTEGER
}
hwPowerCentralState OBJECT-TYPE
SYNTAX INTEGER
{
normal(1),
temOver(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"State of the central module.
Options:
1. normal(1) - indicates the normal state
2. temOver(2) - indicates the over-temperature
"
::= { hwRemoteProvidePowerInfoEntry 1 }
hwPowerCentralDCInPutState OBJECT-TYPE
SYNTAX INTEGER
{
normal(1),
lack(2),
over(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"State of central module DC input:
Options:
1.normal(1) - indicates the normal state
2.lack(2) - indicates the voltage underflow
3.over(3) - indicates the voltage overflow
"
::= { hwRemoteProvidePowerInfoEntry 2}
hwPowerCentralDCOutputState OBJECT-TYPE
SYNTAX INTEGER
{
normal(1),
volLack(2),
volOver(3),
loadOver(4),
shortCircuit(5),
noLoad(6)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"State of central module DC output.
Options:
1. normal(1) - indicates the normal state
2. volLack(2) - indicates the voltage underflow
3. volOver(3) - indicates the voltage overflow
4. loadOver(4) - indicates the over-loading
5. shortCircuit(5) - indicates the short circuit
6. noLoad(6) - indicates no load
"
::= { hwRemoteProvidePowerInfoEntry 3 }
hwPowerCentralDCOutputMode OBJECT-TYPE
SYNTAX INTEGER
{
highVolMode(1),
lowVolMode(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Mode of central module DC output.
Options:
1. highVolMode(1) - indicates the high voltage output mode
2. lowVolMode(2) - indicates the low voltage output mode
"
::= { hwRemoteProvidePowerInfoEntry 4 }
hwPowerRemoteCommState OBJECT-TYPE
SYNTAX INTEGER
{
normal(1),
revfault(2),
sendfault(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Remote power module communications state.
Options:
1. normal(1) - indicates the normal state
2. revfault(2) - indicates the receiving of fault
3. sendfault(3) - indicates the sending of fault"
::= { hwRemoteProvidePowerInfoEntry 5 }
hwPowerRemoteDCInputState OBJECT-TYPE
SYNTAX INTEGER
{
normal(1),
lack(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"State of remote module DC input.
Options:
1. normal(1) - indicates the normal state
2. lack(2) - indicates that the voltage is underflow
"
::= { hwRemoteProvidePowerInfoEntry 6 }
hwPowerRemoteLineCurState OBJECT-TYPE
SYNTAX INTEGER
{
normal(1),
cablejoining(2),
curLeakage(3),
curOver(4)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"state of line between central and remote module.
Options:
1.normal(1) - indicates the normal state
2.cablejoining(2) - indicates the cable joining
3.curLeakage(3) - indicates the cur Leakage
4.curOver(4) - indicates the cur Over
"
::= { hwRemoteProvidePowerInfoEntry 7 }
hwPowerRemotePowerState OBJECT-TYPE
SYNTAX INTEGER
{
normal(1),
fault(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"state of remote UA60 power.
Options:
1. normal(1) - indicates the normal state
2. fault(2) - indicates the faulty state
"
::= { hwRemoteProvidePowerInfoEntry 8 }
hwPowerRemoteLineState OBJECT-TYPE
SYNTAX BITS
{
u1state(0),
u2state(1),
u3state(2),
u4state(3),
a1state(4),
a2state(5),
a3state(6),
a4state(7)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"State of line U1.
Options:
1. u1state(0) - indicates the power remote line state is u1 state
2. u2state(1) - indicates the power remote line state is u2 state
3. u3state(2) - indicates the power remote line state is u3 state
4. u4state(3) - indicates the power remote line state is u4 state
5. a1state(4) - indicates the power remote line state is a1 state
6. a2state(5) - indicates the power remote line state is a2 state
7. a3state(6) - indicates the power remote line state is a3 state
8. a4state(7) - indicates the power remote line state is a4 state
"
::= { hwRemoteProvidePowerInfoEntry 9 }
hwPowerCentralLoadState OBJECT-TYPE
SYNTAX INTEGER
{
normal(1),
overload(2),
nonload(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"state of central load.
Options:
1. normal(1) - indicates the normal state
2. overload(2) - indicates overload
3. nonload(3) - indicates non-load
"
::= { hwRemoteProvidePowerInfoEntry 10 }
hwPowerMibTrap OBJECT IDENTIFIER ::= { hwPower 2 }
hwPowerTrapOid OBJECT IDENTIFIER ::= { hwPowerMibTrap 1 }
hwPowerTrapsDefine OBJECT IDENTIFIER ::= { hwPowerMibTrap 2 }
hwPowerTraps OBJECT IDENTIFIER ::= { hwPowerTrapsDefine 0 }
powerConnFaultAlarm NOTIFICATION-TYPE
OBJECTS {hwEnvEmuIndex, hwPowerIndex }
STATUS current
DESCRIPTION
" This trap message is reported when the communication between
the power module and the monitoring board is fault."
::= { hwPowerTraps 1 }
powerConnFaultAlarmResume NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the communication between
the power module and the monitoring board resumes."
::= { hwPowerTraps 2 }
acInputVoltageAlarm NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwACLoopIndex }
STATUS current
DESCRIPTION
"This trap message is reported when there is a exception of AC input voltage."
::= { hwPowerTraps 3 }
acInputVoltageAlarmResume NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwACLoopIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the state of AC input voltage resumes."
::= { hwPowerTraps 4 }
acInputVoltageHighAlarm NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwACLoopIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the input voltage is too high."
::= { hwPowerTraps 5 }
acInputVoltageHighAlarmResume NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwACLoopIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the input voltage
resumes to the normal range from a high value."
::= { hwPowerTraps 6 }
acInputVoltageLowAlarm NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwACLoopIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the input voltage is too low."
::= { hwPowerTraps 7 }
acInputVoltageLowAlarmResume NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwACLoopIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the input voltage
resumes to the normal range from a low value."
::= { hwPowerTraps 8 }
dcOutputVoltageHighAlarm NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the output voltage is too high."
::= { hwPowerTraps 9 }
dcOutputVoltageHighAlarmResume NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the output voltage
resumes to the normal range from a high value."
::= { hwPowerTraps 10 }
dcOutputCurrentHighAlarm NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the output current is too high."
::= { hwPowerTraps 11 }
dcOutputCurrentHighAlarmResume NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the output current
resumes to the normal range from a high value."
::= { hwPowerTraps 12 }
dcOutputVoltageLowAlarm NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the output voltage is too low."
::= { hwPowerTraps 13 }
dcOutputVoltageLowAlarmResume NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the output voltage
resumes to the normal range from a low value."
::= { hwPowerTraps 14 }
dcOutputCurrentLowAlarm NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the output current is too low."
::= { hwPowerTraps 15 }
dcOutputCurrentLowAlarmResume NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the output current
resumes to the normal range from a low value."
::= { hwPowerTraps 16 }
overLoadPowerAbnormalAlarm NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the state of load power is abnormal."
::= { hwPowerTraps 17 }
overLoadPowerAbnormalAlarmResume NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the state of load power recovers to normal."
::= { hwPowerTraps 18 }
overBattPowerOffAlarm NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the battery is powered off."
::= { hwPowerTraps 19 }
overBattPowerOffAlarmResume NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the battery is powered on."
::= { hwPowerTraps 20 }
overLoadPowerOffAlarm NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the loadpower is powered off."
::= { hwPowerTraps 21 }
overLoadPowerOffAlarmResume NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the loadpower is powered on."
::= { hwPowerTraps 22 }
acMainsSupplyAlarm NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwACLoopIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the AC mains supply is abnormal."
::= { hwPowerTraps 23 }
acMainsSupplyAlarmResume NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwACLoopIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the AC mains supply recovers to normal."
::= { hwPowerTraps 24 }
batteryLoopAlarm NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwBatteryIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the loop of battery group disconnects."
::= { hwPowerTraps 25 }
batteryLoopAlarmResume NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwBatteryIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the loop of battery group connects."
::= { hwPowerTraps 26 }
batteryFuseAlarm NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwBatteryIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the fuse of battery group disconnects."
::= { hwPowerTraps 27 }
batteryFuseAlarmResume NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwBatteryIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the fuse of battery group connects. "
::= { hwPowerTraps 28 }
batteryContachAlarm NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwBatteryIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the contactor of battery group disconnects."
::= { hwPowerTraps 29 }
batteryContachAlarmResume NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwBatteryIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the contactor of battery group connects."
::= { hwPowerTraps 30 }
userModuleOffAlarm NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the user module is powered off."
::= { hwPowerTraps 31 }
userModuleOffAlarmResume NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the user module is powered on."
::= { hwPowerTraps 32 }
transferModuleOffAlarm NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the transfer module is powered off."
::= { hwPowerTraps 33 }
transferModuleOffAlarmResume NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the transfer module is powered on."
::= { hwPowerTraps 34 }
userModuleSwitchAlarm NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the user module is switched off."
::= { hwPowerTraps 35 }
transferModuleSwitchAlarm NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the transfer module is switched off."
::= { hwPowerTraps 37 }
loadFuseAlarm NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the load fuse is abnormal."
::= { hwPowerTraps 39 }
loadFuseAlarmResume NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the load fuse resumes."
::= { hwPowerTraps 40 }
chargeCtrlStateAlarm NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the control state of average or floating charge converts."
::= { hwPowerTraps 41 }
chargeModeAlarm NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the charge state converts."
::= { hwPowerTraps 42 }
acCommFailAlarm NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the AC panel communication fails."
::= { hwPowerTraps 43 }
acCommFailAlarmResume NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the AC panel communication resumes."
::= { hwPowerTraps 44 }
batteryChargeOverAlarm NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwBatteryIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the Over-current of battery group happens."
::= { hwPowerTraps 45 }
batteryChargeOverAlarmResume NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwBatteryIndex }
STATUS current
DESCRIPTION
"OThis trap message is reported when the Over-current of battery group resumes."
::= { hwPowerTraps 46 }
batteryVoltageLackAlarm NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwBatteryIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the voltage of battery group lacks."
::= { hwPowerTraps 47 }
batteryVoltageLackAlarmResume NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwBatteryIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the voltage of battery group recovers from lack."
::= { hwPowerTraps 48 }
loadTwiceOffAlarm NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the load is powered off twice."
::= { hwPowerTraps 49 }
loadTwiceOffAlarmResume NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the load recovers from powering off twice."
::= { hwPowerTraps 50 }
loadOnceOffAlarm NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwBatteryIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the load is powered off once."
::= { hwPowerTraps 51 }
loadOnceOffAlarmResume NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwBatteryIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the load recovers from powering off once."
::= { hwPowerTraps 52 }
acInputPowerOffAlarm NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the AC input is powered off."
::= { hwPowerTraps 53 }
acInputPowerOffAlarmResume NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the AC input power is powered off."
::= { hwPowerTraps 54 }
acInputLoopSwtichAlarm NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex, hwLoadIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the AC input loop switches to another one."
::= { hwPowerTraps 55 }
batteryDischargeTestStartAlarm NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the battery discharge test starts."
::= { hwPowerTraps 56 }
batteryDischargeTestStopAlarm NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the battery discharge test stops."
::= { hwPowerTraps 57 }
powerProtectAlarm NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the power protection function is enbaled."
::= { hwPowerTraps 58 }
powerUndoProtectAlarm NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the power protection function is disabled."
::= { hwPowerTraps 59 }
powerCentralOutputModeSwtichAlarm NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the central output mode swtiches to another one."
::= { hwPowerTraps 60 }
powerCentralTempretaureAlarm NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the central tempretaure is abnormal."
::= { hwPowerTraps 61 }
powerCentralInputAlarm NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the central input voltage is abnormal."
::= { hwPowerTraps 62 }
powerCentralOutputAlarm NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the central output voltage is abnormal."
::= { hwPowerTraps 63 }
powerRemoteCommFaultAlarm NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the communiction between the remote and central fails."
::= { hwPowerTraps 64 }
powerRemoteVoltageAlarm NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the remote voltage is abnormal."
::= { hwPowerTraps 65}
powerLineAlarm NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the power line is abnormal."
::= { hwPowerTraps 66 }
powerRemotePowerAlarm1 NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the remote power is abnormal."
::= { hwPowerTraps 67 }
powerRemotePowerAlarm2 NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the Line UA is abnormal."
::= { hwPowerTraps 68 }
powerRemotePowerAlarm3 NOTIFICATION-TYPE
OBJECTS { hwEnvEmuIndex, hwPowerIndex }
STATUS current
DESCRIPTION
"This trap message is reported when the Central load is abnormal."
::= { hwPowerTraps 69 }
hwACInfomationTable OBJECT-TYPE
SYNTAX SEQUENCE OF HwACInfomationEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"AC infomation table. The table is not supported.
The indexes of this table are hwEnvEmuIndex and hwPowerIndex."
::= { hwPowerMonObjects 8 }
hwACInfomationEntry OBJECT-TYPE
SYNTAX HwACInfomationEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"AC infomation table. The table is not supported.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex."
INDEX { hwEnvEmuIndex, hwPowerIndex }
::= { hwACInfomationTable 1 }
HwACInfomationEntry ::=
SEQUENCE {
hwACInfoCommState
INTEGER,
hwACInfoThunderState
INTEGER,
hwACInfoCurrentLoop
Integer32,
hwACInfoMCBTrigger
INTEGER,
hwACInfoFrequency
Integer32,
hwACInfoRowStatus
RowStatus
}
hwACInfoCommState OBJECT-TYPE
SYNTAX INTEGER
{
normal(0),
fault(1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"communication state of AC input module.
The node is not supported.
Options:
1. normal(0) - indicates the communication state of AC is normal
2. fault(1) - indicates the communication state of AC is fault
"
::= { hwACInfomationEntry 1 }
hwACInfoThunderState OBJECT-TYPE
SYNTAX INTEGER
{
normal(0),
fault(1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Thunder's state.
The node is not supported.
Options:
1. normal(0) - indicates the state of Thunder is normal
2. fault(1) - indicates the state of Thunder is fault
"
::= { hwACInfomationEntry 2 }
hwACInfoCurrentLoop OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Current AC input working loop.
The leaf is not supported.
"
::= { hwACInfomationEntry 3 }
hwACInfoMCBTrigger OBJECT-TYPE
SYNTAX INTEGER
{
normal(0),
breakDown(1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"AC input MCB trigger state.
The leaf is not supported.
Options:
1. normal(0) - indicates the AC input MCB trigger state is normal
2. breakDown(1)- indicates the AC input MCB trigger state is break-down
"
::= { hwACInfomationEntry 4 }
hwACInfoFrequency OBJECT-TYPE
SYNTAX Integer32
UNITS "HZ"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The infomation of AC input frequency.
This leaf is not supported.
Unit: HZ
"
::= { hwACInfomationEntry 5 }
hwACInfoRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-create
STATUS current
DESCRIPTION
"RowStatus standard operation
The leaf is not supported.
"
::= { hwACInfomationEntry 6 }
powerConformance OBJECT IDENTIFIER ::= { hwPower 3 }
powerCompliances OBJECT IDENTIFIER ::= { powerConformance 1 }
powerGroups OBJECT IDENTIFIER ::= { powerConformance 2 }
hwEnvironPowerTraps OBJECT IDENTIFIER ::= { hwPower 4 }
hwEnvironPowerCommonTraps OBJECT IDENTIFIER ::= { hwEnvironPowerTraps 1 }
hwEnvironPowerAlarmTraps OBJECT IDENTIFIER ::= { hwEnvironPowerTraps 2 }
hwEnvironPowerAlarmTrapsPrefix OBJECT IDENTIFIER ::= { hwEnvironPowerAlarmTraps 0 }
hwEmmPowerBattaryTestStartTrap NOTIFICATION-TYPE
OBJECTS {
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the power
device battary discharge test starts.
"
::= { hwEnvironPowerAlarmTrapsPrefix 1 }
hwEmmPowerBattaryTestStopTrap NOTIFICATION-TYPE
OBJECTS {
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwEnvEmuType,
hwPowerType,
hwBatteryLogTestBatteryStatus,
hwBatteryLogTestEfficiency
}
STATUS current
DESCRIPTION
"The agent generates this trap when the power
device battary discharge test ends.
"
::= { hwEnvironPowerAlarmTrapsPrefix 2 }
hwEmmPowerAcvolFaultTrap NOTIFICATION-TYPE
OBJECTS {
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwACLoopIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the power
device AC input voltage is abnormal.
"
::= { hwEnvironPowerAlarmTrapsPrefix 3 }
hwEmmPowerAcvolRecoverTrap NOTIFICATION-TYPE
OBJECTS {
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwACLoopIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the power
device AC input voltage recovers.
"
::= { hwEnvironPowerAlarmTrapsPrefix 4 }
hwEmmPowerDcvolFaultTrap NOTIFICATION-TYPE
OBJECTS {
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the power
device DC output voltage is abnormal.
"
::= { hwEnvironPowerAlarmTrapsPrefix 5 }
hwEmmPowerDcvolRecoverTrap NOTIFICATION-TYPE
OBJECTS {
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the power
device DC output voltage recovers.
"
::= { hwEnvironPowerAlarmTrapsPrefix 6 }
hwEmmPowerBattloopFaultTrap NOTIFICATION-TYPE
OBJECTS {
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwBatteryIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the power
device the battery loop is broken.
In this case, the function of he backup power is lost.
"
::= { hwEnvironPowerAlarmTrapsPrefix 7 }
hwEmmPowerBattloopRecoverTrap NOTIFICATION-TYPE
OBJECTS {
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwBatteryIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the power
device battery loop recovers.
"
::= { hwEnvironPowerAlarmTrapsPrefix 8 }
hwEmmPowerLoadfuseFaultTrap NOTIFICATION-TYPE
OBJECTS {
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwLoadIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the fuse of the power device
is broken. In this case, the device is powered off.
"
::= { hwEnvironPowerAlarmTrapsPrefix 9 }
hwEmmPowerLoadfuseRecoverTrap NOTIFICATION-TYPE
OBJECTS {
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwLoadIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the fuse of the power
device recovers.
"
::= { hwEnvironPowerAlarmTrapsPrefix 10 }
hwEmmPowerRectifierFaultTrap NOTIFICATION-TYPE
OBJECTS {
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwRectifierIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the rectifier
module of the power device is abnormal and the spully power may decrease.
"
::= { hwEnvironPowerAlarmTrapsPrefix 11 }
hwEmmPowerRectifierRecoverTrap NOTIFICATION-TYPE
OBJECTS {
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwRectifierIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the rectifier module of the
power device recovers.
"
::= { hwEnvironPowerAlarmTrapsPrefix 12 }
hwEmmDigMainsupplyFaultTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
main supply digital is faulty.
"
::= { hwEnvironPowerAlarmTrapsPrefix 13 }
hwEmmDigMainsupplyRecoverTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
main supply digital recovers.
"
::= { hwEnvironPowerAlarmTrapsPrefix 14 }
hwEmmPowerBatteryOffTrap NOTIFICATION-TYPE
OBJECTS {
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the power
of battary is off.
"
::= { hwEnvironPowerAlarmTrapsPrefix 15 }
hwEmmBatt1TempFaultTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
battery group 1 temperature sensor fault
occurs.
"
::= { hwEnvironPowerAlarmTrapsPrefix 16 }
hwEmmBatt1TempRestoreTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
battery group 1 temperature sensor fault
recovers.
"
::= { hwEnvironPowerAlarmTrapsPrefix 17 }
hwEmmEnviHumFaultTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
environment humidity sensor fault occurs.
"
::= { hwEnvironPowerAlarmTrapsPrefix 18 }
hwEmmEnviHumRestoreTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
environment humidity sensor fault recovers.
"
::= { hwEnvironPowerAlarmTrapsPrefix 19 }
hwEmmEnvi1TempFaultTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
environment 1 temperature sensor fault
occurs.
"
::= { hwEnvironPowerAlarmTrapsPrefix 20 }
hwEmmEnvi1TempRestoreTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
environment 1 temperature sensor fault
recovers.
"
::= { hwEnvironPowerAlarmTrapsPrefix 21 }
hwEmmBattTemFaultTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the battery
temperature out of normal range.
"
::= { hwEnvironPowerAlarmTrapsPrefix 22 }
hwEmmBattTemRecoverTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the battery
temperature recovers to normal range.
"
::= { hwEnvironPowerAlarmTrapsPrefix 23 }
hwEmmPowerBatteryOffRecoverTrap NOTIFICATION-TYPE
OBJECTS {
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the power
of battary recovers to on state.
"
::= { hwEnvironPowerAlarmTrapsPrefix 24 }
hwEmmPowerBatteryUnDetectTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
one or more batteries are not detected.
"
::= { hwEnvironPowerAlarmTrapsPrefix 25 }
hwEmmPowerBatteryDetectRecoverTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
batteries recover.
"
::= { hwEnvironPowerAlarmTrapsPrefix 26 }
hwPowerModuleMismatchTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
the power supply system detects mismatched power module .
"
::= { hwEnvironPowerAlarmTrapsPrefix 27 }
hwPowerModuleRestoreTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the power module recovers.
"
::= { hwEnvironPowerAlarmTrapsPrefix 28 }
hwPowerBatteryTempLowTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
battery temperature is low.
"
::= { hwEnvironPowerAlarmTrapsPrefix 29 }
hwPowerBatteryTempLowRestoreTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
battery recovers from low temperature.
"
::= { hwEnvironPowerAlarmTrapsPrefix 30 }
hwPowerBatteryTempHighTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
battery temperature is High.
"
::= { hwEnvironPowerAlarmTrapsPrefix 31 }
hwPowerBatteryTempHighRestoreTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
battery recovers from High temperature.
"
::= { hwEnvironPowerAlarmTrapsPrefix 32 }
hwPowerBatteryChargeOverVolTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
battery is charged over voltage.
"
::= { hwEnvironPowerAlarmTrapsPrefix 33 }
hwPowerBatteryChargeOverVolRestoreTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
battery recovers from charged over voltage.
"
::= { hwEnvironPowerAlarmTrapsPrefix 34 }
hwPowerBatteryDischargeLackVolTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
discharging battery is lack voltage.
"
::= { hwEnvironPowerAlarmTrapsPrefix 35 }
hwPowerBatteryDischargeLackVolRestoreTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
battery recovers from discharging lack voltage.
"
::= { hwEnvironPowerAlarmTrapsPrefix 36 }
hwPowerBatteryChargeOverCurTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
battery is charged over current.
"
::= { hwEnvironPowerAlarmTrapsPrefix 37 }
hwPowerBatteryChargeOverCurRestoreTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
battery recovers from charged over current.
"
::= { hwEnvironPowerAlarmTrapsPrefix 38 }
hwPowerBatteryDischargeOverCurTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
discharging battery is over current.
"
::= { hwEnvironPowerAlarmTrapsPrefix 39 }
hwPowerBatteryDischargeOverCurRestoreTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
battery recovers from discharging over current.
"
::= { hwEnvironPowerAlarmTrapsPrefix 40 }
hwRemoteUnitCircuitFailTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex,
hwRemoteUnitSlotIndex,
hwRemoteUnitCircuitIndex,
hwEnvEmuType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
circuit of the power module is fault.
"
::= { hwEnvironPowerAlarmTrapsPrefix 41 }
hwRemoteUnitCircuitRestoreTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex,
hwRemoteUnitSlotIndex,
hwRemoteUnitCircuitIndex,
hwEnvEmuType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
circuit of the power module is recovers from fault.
"
::= { hwEnvironPowerAlarmTrapsPrefix 42 }
hwRemoteUnitFaultTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex,
hwRemoteUnitSlotIndex,
hwEnvEmuType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
power module is fault.
"
::= { hwEnvironPowerAlarmTrapsPrefix 43 }
hwRemoteUnitRestoreTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex,
hwRemoteUnitSlotIndex,
hwEnvEmuType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
power module is recovers from fault.
"
::= { hwEnvironPowerAlarmTrapsPrefix 44 }
hwPowerBatteryEleCoreFaultTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex,
hwEnvEmuType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
LiBattery cell is fault.
"
::= { hwEnvironPowerAlarmTrapsPrefix 45 }
hwPowerBatteryEleCoreRestoreTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex,
hwEnvEmuType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
LiBattery cell is recovers from fault.
"
::= { hwEnvironPowerAlarmTrapsPrefix 46 }
hwPowerBatteryHeaterFaultTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
battery heater fault occurs.
"
::= { hwEnvironPowerAlarmTrapsPrefix 47 }
hwPowerBatteryHeaterFaultRestoreTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
battery heater fault recovers.
"
::= { hwEnvironPowerAlarmTrapsPrefix 48 }
hwPowerBatteryPortReverseConnectTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
battery port is connected reversely.
"
::= { hwEnvironPowerAlarmTrapsPrefix 49 }
hwPowerBatteryPortReverseConnectRestoreTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
battery port is connected correctly .
"
::= { hwEnvironPowerAlarmTrapsPrefix 50 }
hwPowerBatteryContactorFaultTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
battery contactor is fault.
"
::= { hwEnvironPowerAlarmTrapsPrefix 51 }
hwPowerBatteryContactorRestoreTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
battery contactor fault recovers.
"
::= { hwEnvironPowerAlarmTrapsPrefix 52 }
hwPowerLowTemperatureProtectionFaultTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex
}
STATUS current
DESCRIPTION
"The agent generates this trap when the battery cell temperature is lower
than the protection point.
"
::= { hwEnvironPowerAlarmTrapsPrefix 53 }
hwPowerLowTemperatureProtectionRestoreTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
battery cell low temperature protection fault recovers.
"
::= { hwEnvironPowerAlarmTrapsPrefix 54 }
hwPowerCellChargeHighTemperatureProtectionFaultTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex
}
STATUS current
DESCRIPTION
"The agent generates this trap when the battery cell temperature is higher
than the protection point when the battery is charging or discharging.
"
::= { hwEnvironPowerAlarmTrapsPrefix 55 }
hwPowerCellChargeHighTemperatureProtectionRestoreTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
battery cell high temperature protection fault recovers.
"
::= { hwEnvironPowerAlarmTrapsPrefix 56 }
hwPowerOvervoltageProtectionFaultTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex
}
STATUS current
DESCRIPTION
"The agent generates this trap when the battery charging voltage is higher
than the protection point.
"
::= { hwEnvironPowerAlarmTrapsPrefix 57 }
hwPowerOvervoltageProtectionRestoreTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
battery over voltage protection fault recovers.
"
::= { hwEnvironPowerAlarmTrapsPrefix 58 }
hwPowerOvercurrentProtectionFaultTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex
}
STATUS current
DESCRIPTION
"The agent generates this trap when the battery charging electric current is bigger
than the protection point.
"
::= { hwEnvironPowerAlarmTrapsPrefix 59 }
hwPowerOvercurrentProtectionRestoreTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
battery over electric current protection fault recovers.
"
::= { hwEnvironPowerAlarmTrapsPrefix 60 }
hwPowerBattCellPackFaultTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex
}
STATUS current
DESCRIPTION
"The agent generates this trap when the battery cell pack fault.
"
::= { hwEnvironPowerAlarmTrapsPrefix 61 }
hwPowerBattCellPackRestoreTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex
}
STATUS current
DESCRIPTION
"The agent generates this trap when the battery cell pack fault recovers.
"
::= { hwEnvironPowerAlarmTrapsPrefix 62 }
hwPowerBattManualDisconnectionFaultTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex
}
STATUS current
DESCRIPTION
"The agent generates this trap when the battery is disconnected manually.
"
::= { hwEnvironPowerAlarmTrapsPrefix 63 }
hwPowerBattManualDisconnectionRestoreTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex
}
STATUS current
DESCRIPTION
"The agent generates this trap when the battery manual disconnection fault recovers.
"
::= { hwEnvironPowerAlarmTrapsPrefix 64 }
hwEmmPowerBatteryBoardFaultTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
one or more batteries are not detected.
"
::= { hwEnvironPowerAlarmTrapsPrefix 65 }
hwEmmPowerBatteryBoardRecoverTrap NOTIFICATION-TYPE
OBJECTS
{
hwFrameIndex,
hwEnvEmuIndex,
hwPowerIndex,
hwEnvEmuType,
hwPowerType
}
STATUS current
DESCRIPTION
"The agent generates this trap when the
batteries recover.
"
::= { hwEnvironPowerAlarmTrapsPrefix 66 }
hwRemotePowerMonObjs OBJECT IDENTIFIER ::= { hwPower 5 }
hwRemoteUnitSysInfoTable OBJECT-TYPE
SYNTAX SEQUENCE OF HwRemoteUnitSysInfoEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Remote power system, remote unit basic information table. The indexes of
this entry is hwEnvEmuIndex.
"
::= { hwRemotePowerMonObjs 1 }
hwRemoteUnitSysInfoEntry OBJECT-TYPE
SYNTAX HwRemoteUnitSysInfoEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Remote power system, remote unit basic information table. The indexes of
this entry is hwEnvEmuIndex.
"
INDEX { hwEnvEmuIndex }
::= { hwRemoteUnitSysInfoTable 1 }
HwRemoteUnitSysInfoEntry ::=
SEQUENCE {
hwRemoteUnitPowerSystype
INTEGER,
hwRemoteUnitDCOutputVol
Integer32,
hwRemoteUnitDCOutputCur
Integer32,
hwRemoteUnitSlotNum
Integer32
}
hwRemoteUnitPowerSystype OBJECT-TYPE
SYNTAX INTEGER
{
rftv(1),
rftc(2),
invalid(255)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Type of the remote unit power system.
Options:
1.rftv(1) - Type of the remote unit power system is RFT-V
2.rftc(2) - Type of the remote unit power system is RFT-C
3.invalid(255) - Unknown
"
::= { hwRemoteUnitSysInfoEntry 1 }
hwRemoteUnitDCOutputVol OBJECT-TYPE
SYNTAX Integer32
UNITS "mV"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The remote unit DC output voltage.
Invalid(0x7FFFFFFF) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
"
::= { hwRemoteUnitSysInfoEntry 2 }
hwRemoteUnitDCOutputCur OBJECT-TYPE
SYNTAX Integer32
UNITS "mA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The remote unit DC output current.
Invalid(0x7FFFFFFF) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
"
::= { hwRemoteUnitSysInfoEntry 3 }
hwRemoteUnitSlotNum OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The remote unit slot number.
Invalid(-1) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
"
::= { hwRemoteUnitSysInfoEntry 4 }
hwRemoteUnitSlotTable OBJECT-TYPE
SYNTAX SEQUENCE OF HwRemoteUnitSlotEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Remote power system, remote unit slot information table. The indexes of
this entry are hwEnvEmuIndex, hwRemoteUnitSlotIndex.
"
::= { hwRemotePowerMonObjs 2 }
hwRemoteUnitSlotEntry OBJECT-TYPE
SYNTAX HwRemoteUnitSlotEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Remote power system, remote unit slot information table. The indexes of
this entry are hwEnvEmuIndex, hwRemoteUnitSlotIndex.
"
INDEX { hwEnvEmuIndex, hwRemoteUnitSlotIndex }
::= { hwRemoteUnitSlotTable 1 }
HwRemoteUnitSlotEntry ::=
SEQUENCE {
hwRemoteUnitSlotIndex
Integer32,
hwRemoteUnitSlotCircuitNum
Integer32,
hwRemoteUnitSlotHardVersion
OCTET STRING,
hwRemoteUnitSlotSoftVersion
OCTET STRING,
hwRemoteUnitSlotStatus
INTEGER,
hwRemoteUnitSlotAdminStatus
INTEGER,
hwRemoteUnitSlotDCOutputVol
Integer32,
hwRemoteUnitSlotDCOutputCur
Integer32
}
hwRemoteUnitSlotIndex OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The remote unit slot index."
::= { hwRemoteUnitSlotEntry 1 }
hwRemoteUnitSlotCircuitNum OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The remote unit slot circuit number.
Invalid:-1.
"
::= { hwRemoteUnitSlotEntry 2 }
hwRemoteUnitSlotHardVersion OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(1..128))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The remote unit slot hard version.
Invalid: null string.
"
::= { hwRemoteUnitSlotEntry 3 }
hwRemoteUnitSlotSoftVersion OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(1..128))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The remote unit slot soft version.
Invalid: null string.
"
::= { hwRemoteUnitSlotEntry 4 }
hwRemoteUnitSlotStatus OBJECT-TYPE
SYNTAX INTEGER
{
normal(1),
fault(2),
null(3),
invalid(255)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The state of the remote unit slot.
Options:
1.normal(1) - The state of the remote unit slot is normal
2.fault(2) - The state of the remote unit slot is fault
3.null(3) - The state of the remote unit slot is null
4.invalid(255) - Unknown
"
::= { hwRemoteUnitSlotEntry 5 }
hwRemoteUnitSlotAdminStatus OBJECT-TYPE
SYNTAX INTEGER
{
delete(1),
invalid(255)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Delete the remote unit slot.
Options:
1.delete(1) - Delete the remote unit slot
2.invalid(255) - Unknown
"
::= { hwRemoteUnitSlotEntry 6 }
hwRemoteUnitSlotDCOutputVol OBJECT-TYPE
SYNTAX Integer32
UNITS "mV"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The remote unit slot DC output voltage.
Invalid:-1.
"
::= { hwRemoteUnitSlotEntry 7 }
hwRemoteUnitSlotDCOutputCur OBJECT-TYPE
SYNTAX Integer32
UNITS "mA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The remote unit slot DC output current.
Invalid:-1.
"
::= { hwRemoteUnitSlotEntry 8 }
hwRemoteUnitCircuitTable OBJECT-TYPE
SYNTAX SEQUENCE OF HwRemoteUnitCircuitEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Remote power system, remote unit circuit information table. The indexes of
this entry are hwEnvEmuIndex, hwRemoteUnitSlotIndex, hwRemoteUnitCircuitIndex.
"
::= { hwRemotePowerMonObjs 3 }
hwRemoteUnitCircuitEntry OBJECT-TYPE
SYNTAX HwRemoteUnitCircuitEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Remote power system, remote unit circuit information table. The indexes of
this entry are hwEnvEmuIndex, hwRemoteUnitSlotIndex, hwRemoteUnitCircuitIndex.
"
INDEX { hwEnvEmuIndex, hwRemoteUnitSlotIndex, hwRemoteUnitCircuitIndex }
::= { hwRemoteUnitCircuitTable 1 }
HwRemoteUnitCircuitEntry ::=
SEQUENCE {
hwRemoteUnitCircuitIndex
Integer32,
hwRemoteUnitCircuitInputVol
Integer32,
hwRemoteUnitCircuitInputCur
Integer32,
hwRemoteUnitCircuitState
INTEGER
}
hwRemoteUnitCircuitIndex OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The remote unit circuit index."
::= { hwRemoteUnitCircuitEntry 1 }
hwRemoteUnitCircuitInputVol OBJECT-TYPE
SYNTAX Integer32
UNITS "mV"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The remote unit circuit input voltage.
Invalid(0x7FFFFFFF) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
"
::= { hwRemoteUnitCircuitEntry 2 }
hwRemoteUnitCircuitInputCur OBJECT-TYPE
SYNTAX Integer32
UNITS "mA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The remote unit circuit input current.
Invalid(0x7FFFFFFF) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
"
::= { hwRemoteUnitCircuitEntry 3 }
hwRemoteUnitCircuitState OBJECT-TYPE
SYNTAX INTEGER
{
normal(1),
fault(2),
null(3),
invalid(255)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The state of the remote unit circuit.
Options:
1.normal(1) - The state of the remote unit circuit is normal
2.fault(2) - The state of the remote unit circuit is fault
3.null(3) - The state of the remote unit circuit is null
4.invalid(255) - Unknown
"
::= { hwRemoteUnitCircuitEntry 4 }
END