Observium_CE/mibs/gude/GUDEADS-PDU8311-MIB

734 lines
16 KiB
Plaintext

GUDEADS-PDU8311-MIB DEFINITIONS ::= BEGIN
IMPORTS
enterprises,
MODULE-IDENTITY,
OBJECT-TYPE,
NOTIFICATION-TYPE,
Integer32,
Unsigned32
FROM SNMPv2-SMI
OBJECT-GROUP,
NOTIFICATION-GROUP
FROM SNMPv2-CONF;
gudeads MODULE-IDENTITY
LAST-UPDATED "200703051356Z" -- Mar 5, 2007 1:56:00 PM
ORGANIZATION "Gude Analog- und Digitalsysteme GmbH"
CONTACT-INFO
"http://www.gudeads.com/"
DESCRIPTION
""
REVISION "200703051356Z" -- Mar 5, 2007 1:56:00 PM
DESCRIPTION
"$Id:$"
-- 1.3.6.1.4.1.28507
::= { enterprises 28507 }
pdu8311AirPressureEvtSen NOTIFICATION-TYPE
OBJECTS {
pdu8311SensorIndex,
pdu8311AirPressure}
STATUS current
DESCRIPTION
"Air Pressure limits exceeded
"
-- 1.3.6.1.4.1.28507.62.3.4
::= { events 4 }
pdu8311DewPtDiffEvtSen NOTIFICATION-TYPE
OBJECTS {
pdu8311SensorIndex,
pdu8311DewPointDiff}
STATUS current
DESCRIPTION
"Dew Point Difference limits exceeded"
-- 1.3.6.1.4.1.28507.62.3.5
::= { events 5 }
gadsPDU8311 OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.62
::= { gudeads 62 }
-- Notification Types
--
events OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.62.3
::= { gadsPDU8311 3 }
-- Scalars and Tables
--
pdu8311Objects OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.62.1
::= { gadsPDU8311 1 }
pdu8311CommonConfig OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.62.1.1
::= { pdu8311Objects 1 }
pdu8311SNMPaccess OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.62.1.1.1
::= { pdu8311CommonConfig 1 }
pdu8311TrapCtrl OBJECT-TYPE
SYNTAX Integer32 (0..3)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"0 = off
1 = Ver. 1
2 = Ver. 2c
3 = Ver. 3"
-- 1.3.6.1.4.1.28507.62.1.1.1.1
::= { pdu8311SNMPaccess 1 }
pdu8311TrapIPTable OBJECT-TYPE
SYNTAX SEQUENCE OF Pdu8311TrapIPEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"list of all Trap receiver"
-- 1.3.6.1.4.1.28507.62.1.1.1.2
::= { pdu8311SNMPaccess 2 }
pdu8311TrapIPEntry OBJECT-TYPE
SYNTAX Pdu8311TrapIPEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"an entry containing management
informations regarding the list of trap
receivers"
INDEX {
pdu8311TrapIPIndex }
-- 1.3.6.1.4.1.28507.62.1.1.1.2.1
::= { pdu8311TrapIPTable 1 }
Pdu8311TrapIPEntry ::= SEQUENCE {
pdu8311TrapIPIndex Integer32,
pdu8311TrapAddr OCTET STRING }
pdu8311TrapIPIndex OBJECT-TYPE
SYNTAX Integer32 (1..8)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A unique value, greater than zero, for each receiver slot."
-- 1.3.6.1.4.1.28507.62.1.1.1.2.1.1
::= { pdu8311TrapIPEntry 1 }
pdu8311TrapAddr OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..99))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"DNS name or IP address specifying one Trap receiver slot.
A port can optionally be specified: 'name:port' An empty
string disables this slot."
-- 1.3.6.1.4.1.28507.62.1.1.1.2.1.2
::= { pdu8311TrapIPEntry 2 }
pdu8311DeviceConfig OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.62.1.2
::= { pdu8311Objects 2 }
pdu8311IntActors OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.62.1.3
::= { pdu8311Objects 3 }
pdu8311ExtActors OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.62.1.4
::= { pdu8311Objects 4 }
pdu8311IntSensors OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.62.1.5
::= { pdu8311Objects 5 }
pdu8311PowerChan OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.62.1.5.1
::= { pdu8311IntSensors 1 }
pdu8311ActivePowerChan OBJECT-TYPE
SYNTAX Unsigned32 (1..3)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of suppported Power Channels."
-- 1.3.6.1.4.1.28507.62.1.5.1.1
::= { pdu8311PowerChan 1 }
pdu8311PowerTable OBJECT-TYPE
SYNTAX SEQUENCE OF Pdu8311PowerEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"All available Channel Interfaces."
-- 1.3.6.1.4.1.28507.62.1.5.1.2
::= { pdu8311PowerChan 2 }
pdu8311PowerEntry OBJECT-TYPE
SYNTAX Pdu8311PowerEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing management information
applicable to a particular Power Channel."
INDEX {
pdu8311PowerIndex }
-- 1.3.6.1.4.1.28507.62.1.5.1.2.1
::= { pdu8311PowerTable 1 }
Pdu8311PowerEntry ::= SEQUENCE {
pdu8311PowerIndex Integer32,
pdu8311ChanStatus Integer32,
pdu8311AbsEnergyActive Unsigned32,
pdu8311PowerActive Integer32,
pdu8311Current Unsigned32,
pdu8311Voltage Unsigned32,
pdu8311Frequency Unsigned32,
pdu8311PowerFactor Integer32,
pdu8311Pangle Integer32,
pdu8311PowerApparent Integer32,
pdu8311PowerReactive Integer32,
pdu8311AbsEnergyReactive Unsigned32,
pdu8311AbsEnergyActiveResettable Unsigned32,
pdu8311AbsEnergyReactiveResettable Unsigned32,
pdu8311ResetTime Unsigned32,
pdu8311ForwEnergyActive Unsigned32,
pdu8311ForwEnergyReactive Unsigned32,
pdu8311ForwEnergyActiveResettable Unsigned32,
pdu8311ForwEnergyReactiveResettable Unsigned32,
pdu8311RevEnergyActive Unsigned32,
pdu8311RevEnergyReactive Unsigned32,
pdu8311RevEnergyActiveResettable Unsigned32,
pdu8311RevEnergyReactiveResettable Unsigned32,
pdu8311ResidualCurrent Unsigned32 }
pdu8311PowerIndex OBJECT-TYPE
SYNTAX Integer32 (1)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Index of Power Channel entries"
-- 1.3.6.1.4.1.28507.62.1.5.1.2.1.1
::= { pdu8311PowerEntry 1 }
pdu8311ChanStatus OBJECT-TYPE
SYNTAX Integer32 (0..1)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"0 = data not active, 1 = data valid"
-- 1.3.6.1.4.1.28507.62.1.5.1.2.1.2
::= { pdu8311PowerEntry 2 }
pdu8311AbsEnergyActive OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Wh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Absolute Active Energy counter."
-- 1.3.6.1.4.1.28507.62.1.5.1.2.1.3
::= { pdu8311PowerEntry 3 }
pdu8311PowerActive OBJECT-TYPE
SYNTAX Integer32
UNITS "W"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Active Power"
-- 1.3.6.1.4.1.28507.62.1.5.1.2.1.4
::= { pdu8311PowerEntry 4 }
pdu8311Current OBJECT-TYPE
SYNTAX Unsigned32
UNITS "mA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual Current on Power Channel."
-- 1.3.6.1.4.1.28507.62.1.5.1.2.1.5
::= { pdu8311PowerEntry 5 }
pdu8311ResidualCurrent OBJECT-TYPE
SYNTAX Unsigned32
UNITS "mA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual Residual Current on Power Channel.
According Typ A IEC 60755. Only visible on
models that support this feature."
-- 1.3.6.1.4.1.28507.62.1.5.1.2.1.24
::= { pdu8311PowerEntry 24 }
pdu8311Voltage OBJECT-TYPE
SYNTAX Unsigned32
UNITS "V"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual Voltage on Power Channel"
-- 1.3.6.1.4.1.28507.62.1.5.1.2.1.6
::= { pdu8311PowerEntry 6 }
pdu8311Frequency OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 hz"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Frequency of Power Channel"
-- 1.3.6.1.4.1.28507.62.1.5.1.2.1.7
::= { pdu8311PowerEntry 7 }
pdu8311PowerFactor OBJECT-TYPE
SYNTAX Integer32
UNITS "0.001"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Power Factor of Channel between
-1.0 and 1.00"
-- 1.3.6.1.4.1.28507.62.1.5.1.2.1.8
::= { pdu8311PowerEntry 8 }
pdu8311Pangle OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degree"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase Angle between Voltage
and L Line Current between
-180.0 and 180.0"
-- 1.3.6.1.4.1.28507.62.1.5.1.2.1.9
::= { pdu8311PowerEntry 9 }
pdu8311PowerApparent OBJECT-TYPE
SYNTAX Integer32
UNITS "VA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"L Line Mean Apparent Power"
-- 1.3.6.1.4.1.28507.62.1.5.1.2.1.10
::= { pdu8311PowerEntry 10 }
pdu8311PowerReactive OBJECT-TYPE
SYNTAX Integer32
UNITS "VAR"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"L Line Mean Reactive Power"
-- 1.3.6.1.4.1.28507.62.1.5.1.2.1.11
::= { pdu8311PowerEntry 11 }
pdu8311AbsEnergyReactive OBJECT-TYPE
SYNTAX Unsigned32
UNITS "VARh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Absolute Reactive Energy counter."
-- 1.3.6.1.4.1.28507.62.1.5.1.2.1.12
::= { pdu8311PowerEntry 12 }
pdu8311AbsEnergyActiveResettable OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Wh"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Resettable Absolute Active Energy counter.
Writing '0' resets all resettable counter."
-- 1.3.6.1.4.1.28507.62.1.5.1.2.1.13
::= { pdu8311PowerEntry 13 }
pdu8311AbsEnergyReactiveResettable OBJECT-TYPE
SYNTAX Unsigned32
UNITS "VARh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Resettable Absolute Reactive Energy counter."
-- 1.3.6.1.4.1.28507.62.1.5.1.2.1.14
::= { pdu8311PowerEntry 14 }
pdu8311ResetTime OBJECT-TYPE
SYNTAX Unsigned32
UNITS "s"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Time in seconds since last Energy
Counter reset."
-- 1.3.6.1.4.1.28507.62.1.5.1.2.1.15
::= { pdu8311PowerEntry 15 }
pdu8311ForwEnergyActive OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Wh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Forward Active Energy counter."
-- 1.3.6.1.4.1.28507.62.1.5.1.2.1.16
::= { pdu8311PowerEntry 16 }
pdu8311ForwEnergyReactive OBJECT-TYPE
SYNTAX Unsigned32
UNITS "VARh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Forward Reactive Energy counter."
-- 1.3.6.1.4.1.28507.62.1.5.1.2.1.17
::= { pdu8311PowerEntry 17 }
pdu8311ForwEnergyActiveResettable OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Wh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Resettable Forward Active Energy counter."
-- 1.3.6.1.4.1.28507.62.1.5.1.2.1.18
::= { pdu8311PowerEntry 18 }
pdu8311ForwEnergyReactiveResettable OBJECT-TYPE
SYNTAX Unsigned32
UNITS "VARh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Resettable Forward Reactive Energy counter."
-- 1.3.6.1.4.1.28507.62.1.5.1.2.1.19
::= { pdu8311PowerEntry 19 }
pdu8311RevEnergyActive OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Wh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Reverse Active Energy counter."
-- 1.3.6.1.4.1.28507.62.1.5.1.2.1.20
::= { pdu8311PowerEntry 20 }
pdu8311RevEnergyReactive OBJECT-TYPE
SYNTAX Unsigned32
UNITS "VARh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Reverse Reactive Energy counter."
-- 1.3.6.1.4.1.28507.62.1.5.1.2.1.21
::= { pdu8311PowerEntry 21 }
pdu8311RevEnergyActiveResettable OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Wh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Resettable Reverse Active Energy counter."
-- 1.3.6.1.4.1.28507.62.1.5.1.2.1.22
::= { pdu8311PowerEntry 22 }
pdu8311RevEnergyReactiveResettable OBJECT-TYPE
SYNTAX Unsigned32
UNITS "VARh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Resettable Reverse Reactive Energy counter."
-- 1.3.6.1.4.1.28507.62.1.5.1.2.1.23
::= { pdu8311PowerEntry 23 }
pdu8311ExtSensors OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.62.1.6
::= { pdu8311Objects 6 }
pdu8311SensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF Pdu8311SensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION ""
-- 1.3.6.1.4.1.28507.62.1.6.1
::= { pdu8311ExtSensors 1 }
pdu8311SensorEntry OBJECT-TYPE
SYNTAX Pdu8311SensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION ""
INDEX {
pdu8311SensorIndex }
-- 1.3.6.1.4.1.28507.62.1.6.1.1
::= { pdu8311SensorTable 1 }
Pdu8311SensorEntry ::= SEQUENCE {
pdu8311SensorIndex Integer32,
pdu8311TempSensor Integer32,
pdu8311HygroSensor Integer32,
pdu8311InputSensor INTEGER,
pdu8311AirPressure Integer32,
pdu8311DewPoint Integer32,
pdu8311DewPointDiff Integer32 }
pdu8311SensorIndex OBJECT-TYPE
SYNTAX Integer32 (1..2)
MAX-ACCESS read-only
STATUS current
DESCRIPTION ""
-- 1.3.6.1.4.1.28507.62.1.6.1.1.1
::= { pdu8311SensorEntry 1 }
pdu8311TempSensor OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degree Celsius"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"actual temperature"
-- 1.3.6.1.4.1.28507.62.1.6.1.1.2
::= { pdu8311SensorEntry 2 }
pdu8311HygroSensor OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 percent humidity"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"actual humidity"
-- 1.3.6.1.4.1.28507.62.1.6.1.1.3
::= { pdu8311SensorEntry 3 }
pdu8311InputSensor OBJECT-TYPE
SYNTAX INTEGER {
off(0),
on(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"logical state of input sensor"
-- 1.3.6.1.4.1.28507.62.1.6.1.1.4
::= { pdu8311SensorEntry 4 }
-- Conformance
--
pdu8311Conf OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.62.2
::= { gadsPDU8311 2 }
-- Groups
--
pdu8311Groups OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.62.2.1
::= { pdu8311Conf 1 }
-- Compliance
--
pdu8311Compls OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.62.2.2
::= { pdu8311Conf 2 }
pdu8311TempEvtSen NOTIFICATION-TYPE
OBJECTS {
pdu8311SensorIndex,
pdu8311TempSensor}
STATUS current
DESCRIPTION
"temperature limits exceeded"
-- 1.3.6.1.4.1.28507.62.3.1
::= { events 1 }
pdu8311HygroEvtSen NOTIFICATION-TYPE
OBJECTS {
pdu8311SensorIndex,
pdu8311HygroSensor}
STATUS current
DESCRIPTION
"hygro limits exceeded"
-- 1.3.6.1.4.1.28507.62.3.2
::= { events 2 }
pdu8311InputEvtSen NOTIFICATION-TYPE
OBJECTS {
pdu8311SensorIndex,
pdu8311InputSensor}
STATUS current
DESCRIPTION
"change of logical input sensor state"
-- 1.3.6.1.4.1.28507.62.3.3
::= { events 3 }
pdu8311LineAmperageEvt NOTIFICATION-TYPE
OBJECTS {
pdu8311PowerIndex,
pdu8311PowerActive,
pdu8311Current,
pdu8311Voltage,
pdu8311Frequency,
pdu8311PowerApparent,
pdu8311PowerReactive}
STATUS current
DESCRIPTION
"Event is triggered when a measured
current is crossing the entered limits"
-- 1.3.6.1.4.1.28507.62.3.6
::= { events 6 }
pdu8311BasicGroup OBJECT-GROUP
OBJECTS {
pdu8311TrapCtrl,
pdu8311TrapIPIndex,
pdu8311TrapAddr,
pdu8311ActivePowerChan,
pdu8311PowerIndex,
pdu8311ChanStatus,
pdu8311AbsEnergyActive,
pdu8311PowerActive,
pdu8311Current,
pdu8311Voltage,
pdu8311Frequency,
pdu8311PowerFactor,
pdu8311Pangle,
pdu8311PowerApparent,
pdu8311PowerReactive,
pdu8311AbsEnergyReactive,
pdu8311AbsEnergyActiveResettable,
pdu8311AbsEnergyReactiveResettable,
pdu8311ResetTime,
pdu8311ForwEnergyActive,
pdu8311ForwEnergyReactive,
pdu8311ForwEnergyActiveResettable,
pdu8311ForwEnergyReactiveResettable,
pdu8311RevEnergyActive,
pdu8311RevEnergyReactive,
pdu8311RevEnergyActiveResettable,
pdu8311RevEnergyReactiveResettable,
pdu8311ResidualCurrent,
pdu8311SensorIndex,
pdu8311TempSensor,
pdu8311HygroSensor,
pdu8311InputSensor,
pdu8311AirPressure,
pdu8311DewPoint,
pdu8311DewPointDiff }
STATUS current
DESCRIPTION
"Basic objects."
-- 1.3.6.1.4.1.28507.62.2.1.1
::= { pdu8311Groups 1 }
pdu8311NotificationGroup NOTIFICATION-GROUP
NOTIFICATIONS {
pdu8311TempEvtSen,
pdu8311HygroEvtSen,
pdu8311InputEvtSen,
pdu8311LineAmperageEvt,
pdu8311AirPressureEvtSen,
pdu8311DewPtDiffEvtSen }
STATUS current
DESCRIPTION ""
-- 1.3.6.1.4.1.28507.62.2.1.2
::= { pdu8311Groups 2 }
pdu8311AirPressure OBJECT-TYPE
SYNTAX Integer32
UNITS "1 hPA (hectopascal) ~ 1 milibar"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"actual air pressure"
-- 1.3.6.1.4.1.28507.62.1.6.1.1.5
::= { pdu8311SensorEntry 5 }
pdu8311DewPoint OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degree Celsius"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"dew point for actual temperature and humidity"
-- 1.3.6.1.4.1.28507.62.1.6.1.1.6
::= { pdu8311SensorEntry 6 }
pdu8311DewPointDiff OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degree Celsius"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"difference between dew point and actual
temperature (Temp - DewPoint)"
-- 1.3.6.1.4.1.28507.62.1.6.1.1.7
::= { pdu8311SensorEntry 7 }
END