GUDEADS-EPC1202-MIB DEFINITIONS ::= BEGIN
IMPORTS
enterprises,
MODULE-IDENTITY,
OBJECT-TYPE,
NOTIFICATION-TYPE,
Gauge32,
Integer32,
Unsigned32
FROM SNMPv2-SMI
OBJECT-GROUP,
NOTIFICATION-GROUP
FROM SNMPv2-CONF;
gudeads MODULE-IDENTITY
LAST-UPDATED "200703051356Z" -- Mar 5, 2007 1:56:00 PM
ORGANIZATION "Gude Analog- und Digitalsysteme GmbH"
CONTACT-INFO
"http://www.gudeads.com/"
DESCRIPTION
""
REVISION "200703051356Z" -- Mar 5, 2007 1:56:00 PM
DESCRIPTION
"$Id:$"
-- 1.3.6.1.4.1.28507
::= { enterprises 28507 }
gadsEPC1202 OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.43
::= { gudeads 43 }
-- Notification Types
--
events OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.43.3
::= { gadsEPC1202 3 }
-- Scalars and Tables
--
epc1202Objects OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.43.1
::= { gadsEPC1202 1 }
epc1202CommonConfig OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.43.1.1
::= { epc1202Objects 1 }
epc1202SNMPaccess OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.43.1.1.1
::= { epc1202CommonConfig 1 }
epc1202TrapCtrl OBJECT-TYPE
SYNTAX Integer32 (0..3)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"0 = off
1 = Ver. 1
2 = Ver. 2c
3 = Ver. 3"
-- 1.3.6.1.4.1.28507.43.1.1.1.1
::= { epc1202SNMPaccess 1 }
epc1202TrapIPTable OBJECT-TYPE
SYNTAX SEQUENCE OF Epc1202TrapIPEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"list of all Trap receiver"
-- 1.3.6.1.4.1.28507.43.1.1.1.2
::= { epc1202SNMPaccess 2 }
epc1202TrapIPEntry OBJECT-TYPE
SYNTAX Epc1202TrapIPEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"an entry containing management
informations regarding the list of trap
receivers"
INDEX {
epc1202TrapIPIndex }
-- 1.3.6.1.4.1.28507.43.1.1.1.2.1
::= { epc1202TrapIPTable 1 }
Epc1202TrapIPEntry ::= SEQUENCE {
epc1202TrapIPIndex Integer32,
epc1202TrapAddr OCTET STRING }
epc1202TrapIPIndex OBJECT-TYPE
SYNTAX Integer32 (1..8)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A unique value, greater than zero, for each receiver slot."
-- 1.3.6.1.4.1.28507.43.1.1.1.2.1.1
::= { epc1202TrapIPEntry 1 }
epc1202TrapAddr OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..99))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"DNS name or IP address specifying one Trap receiver slot.
A port can optionally be specified: 'name:port' An empty
string disables this slot."
-- 1.3.6.1.4.1.28507.43.1.1.1.2.1.2
::= { epc1202TrapIPEntry 2 }
epc1202DeviceConfig OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.43.1.2
::= { epc1202Objects 2 }
epc1202IntActors OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.43.1.3
::= { epc1202Objects 3 }
epc1202relayports OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.43.1.3.1
::= { epc1202IntActors 1 }
epc1202portNumber OBJECT-TYPE
SYNTAX Integer32 (1..4)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of Relay Ports"
-- 1.3.6.1.4.1.28507.43.1.3.1.1
::= { epc1202relayports 1 }
-- the Interfaces table
-- The Interfaces table contains information on the entity's
-- interfaces. Each sub-layer below the internetwork-layer
-- of a network interface is considered to be an interface.
epc1202portTable OBJECT-TYPE
SYNTAX SEQUENCE OF Epc1202portEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"list of all EPC Relay Ports"
-- 1.3.6.1.4.1.28507.43.1.3.1.2
::= { epc1202relayports 2 }
epc1202portEntry OBJECT-TYPE
SYNTAX Epc1202portEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing management information applicable to a
particular relay port."
INDEX {
epc1202PortIndex }
-- 1.3.6.1.4.1.28507.43.1.3.1.2.1
::= { epc1202portTable 1 }
Epc1202portEntry ::= SEQUENCE {
epc1202PortIndex Integer32,
epc1202PortName OCTET STRING,
epc1202PortState INTEGER,
epc1202PortSwitchCount Integer32,
epc1202PortStartupMode INTEGER,
epc1202PortStartupDelay Integer32,
epc1202PortRepowerTime Integer32 }
epc1202PortIndex OBJECT-TYPE
SYNTAX Integer32 (1..4)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A unique value, greater than zero, for each Relay Port."
-- 1.3.6.1.4.1.28507.43.1.3.1.2.1.1
::= { epc1202portEntry 1 }
epc1202PortName OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (0..15))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A textual string containing name of a Relay Port."
-- 1.3.6.1.4.1.28507.43.1.3.1.2.1.2
::= { epc1202portEntry 2 }
epc1202PortState OBJECT-TYPE
SYNTAX INTEGER {
off(0),
on(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"current state of a Relay Port"
-- 1.3.6.1.4.1.28507.43.1.3.1.2.1.3
::= { epc1202portEntry 3 }
epc1202PortSwitchCount OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total number of switch actions ocurred on a Relay Port.
Does not count switch commands which will not switch
the ralay state, so just real relay switches are displayed here."
-- 1.3.6.1.4.1.28507.43.1.3.1.2.1.4
::= { epc1202portEntry 4 }
epc1202PortStartupMode OBJECT-TYPE
SYNTAX INTEGER {
off(0),
on(1),
laststate(2) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"set Mode of startup sequence (off, on , remember last state)"
DEFVAL { off }
-- 1.3.6.1.4.1.28507.43.1.3.1.2.1.5
::= { epc1202portEntry 5 }
epc1202PortStartupDelay OBJECT-TYPE
SYNTAX Integer32
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Delay in sec for startup action"
DEFVAL { 0 }
-- 1.3.6.1.4.1.28507.43.1.3.1.2.1.6
::= { epc1202portEntry 6 }
epc1202PortRepowerTime OBJECT-TYPE
SYNTAX Integer32 (0..65535)
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Delay in sec for repower port after switching off"
DEFVAL { 0 }
-- 1.3.6.1.4.1.28507.43.1.3.1.2.1.7
::= { epc1202portEntry 7 }
epc1202ExtActors OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.43.1.4
::= { epc1202Objects 4 }
epc1202IntSensors OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.43.1.5
::= { epc1202Objects 5 }
epc1202PowerChan OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.43.1.5.1
::= { epc1202IntSensors 1 }
epc1202ActivePowerChan OBJECT-TYPE
SYNTAX Unsigned32 (1)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of suppported Power Channels."
-- 1.3.6.1.4.1.28507.43.1.5.1.1
::= { epc1202PowerChan 1 }
epc1202PowerTable OBJECT-TYPE
SYNTAX SEQUENCE OF Epc1202PowerEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"All available Channel Interfaces."
-- 1.3.6.1.4.1.28507.43.1.5.1.2
::= { epc1202PowerChan 2 }
epc1202PowerEntry OBJECT-TYPE
SYNTAX Epc1202PowerEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing management information
applicable to a particular Power Channel."
INDEX {
epc1202PowerIndex }
-- 1.3.6.1.4.1.28507.43.1.5.1.2.1
::= { epc1202PowerTable 1 }
Epc1202PowerEntry ::= SEQUENCE {
epc1202PowerIndex Integer32,
epc1202ChanStatus Integer32,
epc1202AbsEnergyActive Gauge32,
epc1202PowerActive Integer32,
epc1202Current Gauge32,
epc1202Voltage Gauge32,
epc1202Frequency Gauge32,
epc1202PowerFactor Integer32,
epc1202Pangle Integer32,
epc1202PowerApparent Integer32,
epc1202PowerReactive Integer32,
epc1202AbsEnergyReactive Gauge32,
epc1202AbsEnergyActiveResettable Gauge32,
epc1202AbsEnergyReactiveResettable Gauge32,
epc1202ResetTime Gauge32,
epc1202ForwEnergyActive Gauge32,
epc1202ForwEnergyReactive Gauge32,
epc1202ForwEnergyActiveResettable Gauge32,
epc1202ForwEnergyReactiveResettable Gauge32,
epc1202RevEnergyActive Gauge32,
epc1202RevEnergyReactive Gauge32,
epc1202RevEnergyActiveResettable Gauge32,
epc1202RevEnergyReactiveResettable Gauge32 }
epc1202PowerIndex OBJECT-TYPE
SYNTAX Integer32 (1)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Index of Power Channel entries"
-- 1.3.6.1.4.1.28507.43.1.5.1.2.1.1
::= { epc1202PowerEntry 1 }
epc1202ChanStatus OBJECT-TYPE
SYNTAX Integer32 (0..1)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"0 = data not active, 1 = data valid"
-- 1.3.6.1.4.1.28507.43.1.5.1.2.1.2
::= { epc1202PowerEntry 2 }
epc1202PowerActive OBJECT-TYPE
SYNTAX Integer32
UNITS "W"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Active Power"
-- 1.3.6.1.4.1.28507.43.1.5.1.2.1.4
::= { epc1202PowerEntry 4 }
epc1202PowerFactor OBJECT-TYPE
SYNTAX Integer32
UNITS "0.001"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Power Factor of Channel between
-1.0 and 1.00"
-- 1.3.6.1.4.1.28507.43.1.5.1.2.1.8
::= { epc1202PowerEntry 8 }
epc1202Pangle OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degree"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase Angle between Voltage
and L Line Current between
-180.0 and 180.0"
-- 1.3.6.1.4.1.28507.43.1.5.1.2.1.9
::= { epc1202PowerEntry 9 }
epc1202PowerApparent OBJECT-TYPE
SYNTAX Integer32
UNITS "VA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"L Line Mean Apparent Power"
-- 1.3.6.1.4.1.28507.43.1.5.1.2.1.10
::= { epc1202PowerEntry 10 }
epc1202PowerReactive OBJECT-TYPE
SYNTAX Integer32
UNITS "VAR"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"L Line Mean Reactive Power"
-- 1.3.6.1.4.1.28507.43.1.5.1.2.1.11
::= { epc1202PowerEntry 11 }
epc1202OVPTable OBJECT-TYPE
SYNTAX SEQUENCE OF Epc1202OVPEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Overvoltage Protection Table"
-- 1.3.6.1.4.1.28507.43.1.5.2
::= { epc1202IntSensors 2 }
epc1202OVPEntry OBJECT-TYPE
SYNTAX Epc1202OVPEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION ""
INDEX {
epc1202OVPIndex }
-- 1.3.6.1.4.1.28507.43.1.5.2.1
::= { epc1202OVPTable 1 }
Epc1202OVPEntry ::= SEQUENCE {
epc1202OVPIndex Integer32,
epc1202OVPStatus INTEGER }
epc1202OVPIndex OBJECT-TYPE
SYNTAX Integer32 (1)
MAX-ACCESS read-only
STATUS current
DESCRIPTION ""
-- 1.3.6.1.4.1.28507.43.1.5.2.1.1
::= { epc1202OVPEntry 1 }
epc1202OVPStatus OBJECT-TYPE
SYNTAX INTEGER {
unknown(2),
ok(1),
failure(0) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"shows the status of the
built-in Overvoltage Protection"
-- 1.3.6.1.4.1.28507.43.1.5.2.1.2
::= { epc1202OVPEntry 2 }
epc1202ExtSensors OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.43.1.6
::= { epc1202Objects 6 }
epc1202SensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF Epc1202SensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION ""
-- 1.3.6.1.4.1.28507.43.1.6.1
::= { epc1202ExtSensors 1 }
epc1202SensorEntry OBJECT-TYPE
SYNTAX Epc1202SensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION ""
INDEX {
epc1202SensorIndex }
-- 1.3.6.1.4.1.28507.43.1.6.1.1
::= { epc1202SensorTable 1 }
Epc1202SensorEntry ::= SEQUENCE {
epc1202SensorIndex Integer32,
epc1202TempSensor Integer32,
epc1202HygroSensor Integer32,
epc1202InputSensor INTEGER,
epc1202AirPressure Integer32,
epc1202DewPoint Integer32,
epc1202DewPointDiff Integer32 }
epc1202SensorIndex OBJECT-TYPE
SYNTAX Integer32 (1)
MAX-ACCESS read-only
STATUS current
DESCRIPTION ""
-- 1.3.6.1.4.1.28507.43.1.6.1.1.1
::= { epc1202SensorEntry 1 }
epc1202TempSensor OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degree Celsius"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"actual temperature"
-- 1.3.6.1.4.1.28507.43.1.6.1.1.2
::= { epc1202SensorEntry 2 }
epc1202HygroSensor OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 percent humidity"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"actual humidity"
-- 1.3.6.1.4.1.28507.43.1.6.1.1.3
::= { epc1202SensorEntry 3 }
epc1202InputSensor OBJECT-TYPE
SYNTAX INTEGER {
off(0),
on(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"logical state of input sensor"
-- 1.3.6.1.4.1.28507.43.1.6.1.1.4
::= { epc1202SensorEntry 4 }
-- Conformance
--
epc1202Conf OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.43.2
::= { gadsEPC1202 2 }
-- Groups
--
epc1202Groups OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.43.2.1
::= { epc1202Conf 1 }
-- Compliance
--
epc1202Compls OBJECT IDENTIFIER
-- 1.3.6.1.4.1.28507.43.2.2
::= { epc1202Conf 2 }
epc1202SwitchEvtPort NOTIFICATION-TYPE
OBJECTS {
epc1202PortIndex,
epc1202PortName,
epc1202PortState,
epc1202PortSwitchCount}
STATUS current
DESCRIPTION
"Event is triggered when a port is switched"
-- 1.3.6.1.4.1.28507.43.3.1
::= { events 1 }
epc1202BasicGroup OBJECT-GROUP
OBJECTS {
epc1202TrapCtrl,
epc1202TrapIPIndex,
epc1202TrapAddr,
epc1202portNumber,
epc1202PortIndex,
epc1202PortName,
epc1202PortState,
epc1202PortSwitchCount,
epc1202PortStartupMode,
epc1202PortStartupDelay,
epc1202PortRepowerTime,
epc1202ActivePowerChan,
epc1202PowerIndex,
epc1202ChanStatus,
epc1202AbsEnergyActive,
epc1202PowerActive,
epc1202Current,
epc1202Voltage,
epc1202Frequency,
epc1202PowerFactor,
epc1202Pangle,
epc1202PowerApparent,
epc1202PowerReactive,
epc1202AbsEnergyReactive,
epc1202AbsEnergyActiveResettable,
epc1202AbsEnergyReactiveResettable,
epc1202ResetTime,
epc1202ForwEnergyActive,
epc1202ForwEnergyReactive,
epc1202ForwEnergyActiveResettable,
epc1202ForwEnergyReactiveResettable,
epc1202RevEnergyActive,
epc1202RevEnergyReactive,
epc1202RevEnergyActiveResettable,
epc1202RevEnergyReactiveResettable,
epc1202OVPIndex,
epc1202OVPStatus,
epc1202SensorIndex,
epc1202TempSensor,
epc1202HygroSensor,
epc1202InputSensor,
epc1202AirPressure,
epc1202DewPoint,
epc1202DewPointDiff }
STATUS current
DESCRIPTION
"Basic objects."
-- 1.3.6.1.4.1.28507.43.2.1.1
::= { epc1202Groups 1 }
epc1202NotificationGroup NOTIFICATION-GROUP
NOTIFICATIONS {
epc1202SwitchEvtPort,
epc1202TempEvtSen,
epc1202InputEvtSen,
epc1202AirPressureEvtSen,
epc1202DewPtDiffEvtSen,
epc1202OVPEvt,
epc1202LineAmperageEvt,
epc1202HygroEvtSen }
STATUS current
DESCRIPTION
""
-- 1.3.6.1.4.1.28507.43.2.1.2
::= { epc1202Groups 2 }
epc1202AbsEnergyActive OBJECT-TYPE
SYNTAX Gauge32
UNITS "Wh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Absolute Active Energy counter."
-- 1.3.6.1.4.1.28507.43.1.5.1.2.1.3
::= { epc1202PowerEntry 3 }
epc1202Current OBJECT-TYPE
SYNTAX Gauge32
UNITS "mA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual Curent on Power Channel."
-- 1.3.6.1.4.1.28507.43.1.5.1.2.1.5
::= { epc1202PowerEntry 5 }
epc1202Voltage OBJECT-TYPE
SYNTAX Gauge32
UNITS "V"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual Voltage on Power Channel"
-- 1.3.6.1.4.1.28507.43.1.5.1.2.1.6
::= { epc1202PowerEntry 6 }
epc1202Frequency OBJECT-TYPE
SYNTAX Gauge32
UNITS "0.01 hz"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Frequency of Power Channel"
-- 1.3.6.1.4.1.28507.43.1.5.1.2.1.7
::= { epc1202PowerEntry 7 }
epc1202AbsEnergyReactive OBJECT-TYPE
SYNTAX Gauge32
UNITS "VARh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Absolute Reactive Energy counter."
-- 1.3.6.1.4.1.28507.43.1.5.1.2.1.12
::= { epc1202PowerEntry 12 }
epc1202AbsEnergyActiveResettable OBJECT-TYPE
SYNTAX Gauge32
UNITS "Wh"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Resettable Absolute Active Energy counter.
Writing '0' resets all resettable counter."
-- 1.3.6.1.4.1.28507.43.1.5.1.2.1.13
::= { epc1202PowerEntry 13 }
epc1202AbsEnergyReactiveResettable OBJECT-TYPE
SYNTAX Gauge32
UNITS "VARh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Resettable Absolute Reactive Energy counter."
-- 1.3.6.1.4.1.28507.43.1.5.1.2.1.14
::= { epc1202PowerEntry 14 }
epc1202ResetTime OBJECT-TYPE
SYNTAX Gauge32
UNITS "s"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Time in seconds since last Energy
Counter reset."
-- 1.3.6.1.4.1.28507.43.1.5.1.2.1.15
::= { epc1202PowerEntry 15 }
epc1202ForwEnergyActive OBJECT-TYPE
SYNTAX Gauge32
UNITS "Wh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Forward Active Energy counter."
-- 1.3.6.1.4.1.28507.43.1.5.1.2.1.16
::= { epc1202PowerEntry 16 }
epc1202ForwEnergyReactive OBJECT-TYPE
SYNTAX Gauge32
UNITS "VARh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Forward Reactive Energy counter."
-- 1.3.6.1.4.1.28507.43.1.5.1.2.1.17
::= { epc1202PowerEntry 17 }
epc1202ForwEnergyActiveResettable OBJECT-TYPE
SYNTAX Gauge32
UNITS "Wh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Resettable Forward Active Energy counter."
-- 1.3.6.1.4.1.28507.43.1.5.1.2.1.18
::= { epc1202PowerEntry 18 }
epc1202ForwEnergyReactiveResettable OBJECT-TYPE
SYNTAX Gauge32
UNITS "VARh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Resettable Forward Reactive Energy counter."
-- 1.3.6.1.4.1.28507.43.1.5.1.2.1.19
::= { epc1202PowerEntry 19 }
epc1202RevEnergyActive OBJECT-TYPE
SYNTAX Gauge32
UNITS "Wh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Reverse Active Energy counter."
-- 1.3.6.1.4.1.28507.43.1.5.1.2.1.20
::= { epc1202PowerEntry 20 }
epc1202RevEnergyReactive OBJECT-TYPE
SYNTAX Gauge32
UNITS "VARh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Reverse Reactive Energy counter."
-- 1.3.6.1.4.1.28507.43.1.5.1.2.1.21
::= { epc1202PowerEntry 21 }
epc1202RevEnergyActiveResettable OBJECT-TYPE
SYNTAX Gauge32
UNITS "Wh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Resettable Reverse Active Energy counter."
-- 1.3.6.1.4.1.28507.43.1.5.1.2.1.22
::= { epc1202PowerEntry 22 }
epc1202RevEnergyReactiveResettable OBJECT-TYPE
SYNTAX Gauge32
UNITS "VARh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Resettable Reverse Reactive Energy counter."
-- 1.3.6.1.4.1.28507.43.1.5.1.2.1.23
::= { epc1202PowerEntry 23 }
epc1202AirPressure OBJECT-TYPE
SYNTAX Integer32
UNITS "1 hPA (hectopascal) ~ 1 milibar"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"actual air pressure"
-- 1.3.6.1.4.1.28507.43.1.6.1.1.5
::= { epc1202SensorEntry 5 }
epc1202DewPoint OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degree Celsius"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"dew point for actual temperature and humidity"
-- 1.3.6.1.4.1.28507.43.1.6.1.1.6
::= { epc1202SensorEntry 6 }
epc1202DewPointDiff OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degree Celsius"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"difference between dew point and actual
temperature (Temp - DewPoint)"
-- 1.3.6.1.4.1.28507.43.1.6.1.1.7
::= { epc1202SensorEntry 7 }
epc1202TempEvtSen NOTIFICATION-TYPE
OBJECTS {
epc1202SensorIndex,
epc1202TempSensor}
STATUS current
DESCRIPTION
"temperature limits exceeded"
-- 1.3.6.1.4.1.28507.43.3.3
-- 1.3.6.1.4.1.28507.43.3.2
::= { events 2 }
epc1202HygroEvtSen NOTIFICATION-TYPE
OBJECTS {
epc1202SensorIndex,
epc1202HygroSensor}
STATUS current
DESCRIPTION
"hygro limits exceeded"
-- 1.3.6.1.4.1.28507.43.3.4
-- 1.3.6.1.4.1.28507.43.3.3
::= { events 3 }
epc1202InputEvtSen NOTIFICATION-TYPE
OBJECTS {
epc1202SensorIndex,
epc1202InputSensor}
STATUS current
DESCRIPTION
"change of logical input sensor state"
-- 1.3.6.1.4.1.28507.43.3.5
-- 1.3.6.1.4.1.28507.43.3.4
::= { events 4 }
epc1202AirPressureEvtSen NOTIFICATION-TYPE
OBJECTS {
epc1202SensorIndex,
epc1202AirPressure}
STATUS current
DESCRIPTION
"Air Pressure limits exceeded"
-- 1.3.6.1.4.1.28507.43.3.6
-- 1.3.6.1.4.1.28507.43.3.5
::= { events 5 }
epc1202DewPtDiffEvtSen NOTIFICATION-TYPE
OBJECTS {
epc1202SensorIndex,
epc1202DewPointDiff}
STATUS current
DESCRIPTION
"Dew Point Difference limits exceeded"
-- 1.3.6.1.4.1.28507.43.3.7
-- 1.3.6.1.4.1.28507.43.3.6
::= { events 6 }
epc1202OVPEvt NOTIFICATION-TYPE
OBJECTS {
epc1202OVPStatus}
STATUS current
DESCRIPTION
"Event is triggered when the OVP status changes"
-- 1.3.6.1.4.1.28507.43.3.8
-- 1.3.6.1.4.1.28507.43.3.7
::= { events 7 }
epc1202LineAmperageEvt NOTIFICATION-TYPE
OBJECTS {
epc1202PowerIndex,
epc1202PowerActive,
epc1202Current,
epc1202Voltage,
epc1202Frequency,
epc1202PowerApparent,
epc1202PowerReactive}
STATUS current
DESCRIPTION
"Event is triggered when a measured
current is crossing the entered limits"
-- 1.3.6.1.4.1.28507.43.3.9
-- 1.3.6.1.4.1.28507.43.3.8
::= { events 8 }
END