Observium_CE/mibs/ge/GESINGLEUPS-MIB

2690 lines
94 KiB
Plaintext

-- GE Management Information Base VERSION 2.00
--
-- Date: 11/10/2004
-- Changes: remove of "_" in snmp identifiers, remove of duplicate comment characters
-- Author : MHCL
--
-- Date 02/14/2005
-- Changes: remove additional size definition for DisplayString
-- Changes: remove additional range definition of PositiveInteger32
-- Changes: change of range definition for Integer32 entries
-- Changes: change names of managed UPSs so that tablenames end with 'table'
-- without changes of other structures
-- Changes: change some Capital-/Lowercase issues
-- Author : MHCL
-- Date: 15/11/2006
-- Changes: added BatterRipple
-- Changes: added OutputPowerFactor; OutputPeakCurrent; OutputShareCurrent
-- Changes: added alarm HighpeedBusfailure; HighpeedBusCRCfailure; ConnectivityBusfailure
-- Changes: added traps HighpeedBusfailure; HighpeedBusCRCfailure; ConnectivityBusfailure
-- Changes: added traps HighpeedBusrestore; HighpeedBusCRCrestore; ConnectivityBusrestore
-- Changes: added group Diagnostic
-- Changes: added BatteryLifetime; FansLifetime; DCcapacitorsLifetime; ACcapacitorsLifetime
-- GlobalServiceCheck
-- Changes: added Status ServiceCheck
-- Deleted: geEnvironmental tree
-- Deleted: geModem tree
-- Deleted: geDevices tree
-- Deleted: geSoftware tree
--
-- Author: GE, Stefan Kuhn
-- Date: 25/11/2006
-- Changes: upsDiagnosticGlobalServiceChecke Syntax from DisplayString to Integer32
-- Changes: upsDiagnosticGlobalServiceChecke into upsDiagnosticGlobalServiceCheck
--
-- Author: GE, Stefan Kuhn
-- Date: 27/11/2006
-- added: upsDiagnosticBusJACommunicationStatus
-- added: upsDiagnosticBusJBCommunicationStatus
-- Moved: BatteryLifetime; FansLifetime; DCcapacitorsLifetime; ACcapacitorsLifetime
-- GlobalServiceCheck
-- Author: GE, Stefan Kuhn
--
-- Date: 10/12/2006
-- modified: upsSecondsOnBattery from NonNegativeInteger32 back to Integer32
-- for the backard compatibility
-- added: upsAlarmHighSpeedBusJACRCFailure,upsAlarmHighSpeedBusJBCRCFailure,upsAlarmShareCurrent,
-- upsAlarmDCRipple and there relative traps
-- Author: GE, Stefan Kuhn
--
-- Date: 22/Oct/2007
-- added: geDevices group
-- Author: GE, L. Giuntini
--
-- Date: Jan 8th, 2008
-- Author: GE, L. Giuntini
-- Created version 2.00 for SMIv2 compliance
-- Changes include the following:
-- * MODULE-IDENTITY clause introduced right after the IMPORT statement
-- * Compliance to RFC2578, section 7.1.1, second paragraph
-- in case of enumerations, use INTEGER rather than Integer32
-- * Replace MAX-ACCESS read-only with MAX-ACCESS read-write
-- (access `write-only' is no longer allowed in SMIv2)
-- * Use NOTIFICATION-TYPE instead of TRAP-TYPE for Traps
-- Remove ENTERPRISE clause
-- Rename VARIABLES clause as OBJECTS clause
-- Add STATUS current clause
-- Incorporate traps in the Object tree
-- * Finally, corrected some errors (undefined/re-defined identifiers)
-- Added 'Trap' to the trap name in order to prevent redefinition errors
--
-- Date: Jul 5th, 2010
-- Author: GE, L. Giuntini
-- Created version 2.40 for IEMi / eBoost introduction
-- Modified:
-- * Description (Properties) for the upsStatus, upsUPSMode OIDs
-- * Various changes to ensure full SNMP v2 compliance
--
-- GE-MIB
-- { iso org(3) dod(6) internet(1) private(4) enterprises(1) imv(818) }
--
-- Title: GE-MIB
-- By: Theo Versteeg & Fontana Gianluca
--
-- 11-5-00 Theo Versteeg
-- Removed the complete Victron-MIB to create a new IMV-mib to cover Comprot4,
-- IM and IMV1 protocol.
-- incl. external devices and object for the agents and protection software.
--
-- Entries marked with (*) are part of the RFC1628 definition
-- Although we integrated the RFC1628 in our own OID range,
-- all RCF1628 OIDs should also be accessable on their own OID defined in RFC1628.
GESINGLEUPS-MIB DEFINITIONS ::= BEGIN
IMPORTS
MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE,
OBJECT-IDENTITY, Counter32, Gauge32, Integer32, Unsigned32, enterprises
FROM SNMPv2-SMI
DisplayString, TimeStamp, TimeInterval, TestAndIncr,
AutonomousType, TEXTUAL-CONVENTION
FROM SNMPv2-TC;
imv MODULE-IDENTITY
LAST-UPDATED "201007050000Z"
ORGANIZATION "GE Digital Energy"
CONTACT-INFO
"GE Digital Energy
Via Cantonale, 50
CH-6595 Riazzino
Switzerland"
DESCRIPTION
"The MIB module to describe GE Digital Energy
Uninterruptible Power Supplies."
REVISION "201007050000Z"
DESCRIPTION
"Updated following IEMi & eBoost introduction."
REVISION "200801080000Z"
DESCRIPTION
"SNMPv2 compliant MIB released."
::= { enterprises 818 }
PositiveInteger32 ::= TEXTUAL-CONVENTION
DISPLAY-HINT "d"
STATUS current
DESCRIPTION
"This data type is a non-zero and non-negative value."
SYNTAX Integer32 (1..2147483647)
NonNegativeInteger32 ::= TEXTUAL-CONVENTION
DISPLAY-HINT "d"
STATUS current
DESCRIPTION
"This data type is a non-negative value."
SYNTAX Integer32 (0..2147483647)
geHardware OBJECT IDENTIFIER ::= { imv 1 }
geUPS OBJECT IDENTIFIER ::= { geHardware 1 }
-- The following list is not really a table, but can be implemented as one in the software.
-- The complete UPS section is simply too large to fit in a pre-defined table.
-- The solution:
-- * All objects are defined for geGenericUPS
-- * All individual UPSs of parallel systems can be reached by their respective sequence
-- number as reflected in below list in stead of the geGenericUPS objects.
geGenericUPS OBJECT IDENTIFIER ::= { geUPS 10 }
-- Generic UPS
upsIdentgen OBJECT IDENTIFIER ::= { geGenericUPS 1 }
upsBatterygen OBJECT IDENTIFIER ::= { geGenericUPS 2 }
upsInputgen OBJECT IDENTIFIER ::= { geGenericUPS 3 }
upsOutputgen OBJECT IDENTIFIER ::= { geGenericUPS 4 }
upsBypassgen OBJECT IDENTIFIER ::= { geGenericUPS 5 }
upsAlarmgen OBJECT IDENTIFIER ::= { geGenericUPS 6 }
upsWellKnownAlarmsgen OBJECT IDENTIFIER ::= { upsAlarmgen 3 }
upsTestgen OBJECT IDENTIFIER ::= { geGenericUPS 7 }
upsWellKnownTestsgen OBJECT IDENTIFIER ::= { upsTestgen 7 }
upsControlgen OBJECT IDENTIFIER ::= { geGenericUPS 8 }
upsConfiggen OBJECT IDENTIFIER ::= { geGenericUPS 9 }
upsGetSetgen OBJECT IDENTIFIER ::= { geGenericUPS 10 }
geUPSTrapsgen OBJECT IDENTIFIER ::= { geGenericUPS 11 }
upsDiagnosticgen OBJECT IDENTIFIER ::= { geGenericUPS 12 }
-- Device
geDevices OBJECT IDENTIFIER ::= { geHardware 100 }
geDevicesDescriptions OBJECT IDENTIFIER ::= { geDevices 1 }
advSNMPWebIntCard OBJECT IDENTIFIER ::= { geDevicesDescriptions 1 }
snmpWebIntCard OBJECT IDENTIFIER ::= { geDevicesDescriptions 2 }
snmpWebIntBox OBJECT IDENTIFIER ::= { geDevicesDescriptions 3 }
--
-- The GE UPS group
--
geDiscoveredUPSsMask OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Reading this variable returns bit mask indicating which
UPSs in a parallel system are alive. Management
software should poll only these UPSs on their snmp
branches 11-18 as follows:
1 FirstUPS alive
2 SecondUPS alive
4 ThirdUPS alive
8 FourthUPS alive
16 FifthUPS alive
32 SixthUPS alive
64 SeventhUPS alive
128 EigthUPS alive
Since the management software should always monitor
the GenericUPS branch (10), this value has no meaning
for single upses (which provide values on that snmp
branch), and should be set to zero in that case."
::= { geUPS 1 }
geRequestPacket OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Put the string, formatted as a IMV/CP4 packet, directly to internally RS485 bus.
This OID could be used for accede directly to the internally RS485 bus from a remote place."
::= { geUPS 2 }
geReplyPacket OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Contain the reply of the IMV/CP4 request packet sent using the OID geRequestPacket.
Every time that a write command has be made at the OID ge RequestPacket, the value of this OID is erased."
::= { geUPS 3 }
--
-- The Device Identification group. Generic
-- All objects in this group except for upsIdentName and
-- upsIdentAttachedDevices are set at device initialization
-- and remain static.
--
upsIdentManufacturergen OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The name of the UPS manufacturer.(*)"
::= { upsIdentgen 1 }
upsIdentModelgen OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The UPS Model designation.(*)"
::= { upsIdentgen 2 }
upsIdentUPSSoftwareVersiongen OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The UPS firmware/software version(s). This variable
may or may not have the same value as
upsIdentAgentSoftwareVersion in some implementations.(*)"
::= { upsIdentgen 3 }
upsIdentAgentSoftwareVersiongen OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The UPS agent software version. This variable may or
may not have the same value as
upsIdentUPSSoftwareVersion in some implementations.(*)"
::= { upsIdentgen 4 }
upsIdentNamegen OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A string identifying the UPS. This object should be
set by the administrator.(*)"
::= { upsIdentgen 5 }
upsIdentAttachedDevicesgen OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A string identifying the devices attached to the
output(s) of the UPS. This object should be set by
the administrator.(*)"
::= { upsIdentgen 6 }
upsIdentUPSSerialNumbergen OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The UPS serial number"
::= { upsIdentgen 7 }
upsIdentComProtVersiongen OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The IMV communication protocol version"
::= { upsIdentgen 8 }
upsIdentOperatingTimegen OBJECT-TYPE
SYNTAX NonNegativeInteger32
UNITS "seconds"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present value of the operating time.
total 'on' time since UPS manufactured"
::= { upsIdentgen 9 }
--
-- Battery Group Generic
--
upsBatteryStatusgen OBJECT-TYPE
SYNTAX INTEGER {
unknown(1),
batteryNormal(2),
batteryLow(3),
batteryDepleted(4)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The indication of the capacity remaining in the UPS
system's batteries. A value of batteryNormal
indicates that the remaining run-time is greater than
upsConfigLowBattTime. A value of batteryLow indicates
that the remaining battery run-time is less than or
equal to upsConfigLowBattTime. A value of
batteryDepleted indicates that the UPS will be unable
to sustain the present load when and if the utility
power is lost (including the possibility that the
utility power is currently absent and the UPS is
unable to sustain the output).(*)"
::= { upsBatterygen 1 }
upsSecondsOnBatterygen OBJECT-TYPE
SYNTAX Integer32
UNITS "seconds"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"If the unit is on battery power, the elapsed time
since the UPS last switched to battery power, or the
time since the network management subsystem was last
restarted, whichever is less. Zero shall be returned
if the unit is not on battery power.(*)"
::= { upsBatterygen 2 }
upsEstimatedMinutesRemaininggen OBJECT-TYPE
SYNTAX PositiveInteger32
UNITS "minutes"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"An estimate of the time to battery charge depletion
under the present load conditions if the utility power
is off and remains off, or if it were to be lost and
remain off.(*)"
::= { upsBatterygen 3 }
upsEstimatedChargeRemaininggen OBJECT-TYPE
SYNTAX Integer32 (0..100)
UNITS "percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"An estimate of the battery charge remaining expressed
as a percent of full charge.(*)"
::= { upsBatterygen 4 }
upsBatteryVoltagegen OBJECT-TYPE
SYNTAX NonNegativeInteger32
UNITS "0.1 Volt DC"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The magnitude of the present battery voltage.(*)"
::= { upsBatterygen 5 }
upsBatteryCurrentgen OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 Amp DC"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present battery current.(*)"
::= { upsBatterygen 6 }
upsBatteryTemperaturegen OBJECT-TYPE
SYNTAX Integer32
UNITS "degrees Centigrade"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The ambient temperature at or near the UPS Battery
casing.(*)"
::= { upsBatterygen 7 }
upsBatteryRipplegen OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 Volt RMS"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present DC link RMS voltage ripple.(*)"
::= { upsBatterygen 8 }
--
-- Input Group
--
upsInputLineBadsgen OBJECT-TYPE
SYNTAX Counter32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A count of the number of times the input entered an
out-of-tolerance condition as defined by the
manufacturer. This count is incremented by one each
time the input transitions from zero out-of-tolerance
lines to one or more input lines out-of-tolerance.(*)"
::= { upsInputgen 1 }
upsInputNumLinesgen OBJECT-TYPE
SYNTAX NonNegativeInteger32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of input lines utilized in this device.
This variable indicates the number of rows in the
input table.(*)"
::= { upsInputgen 2 }
upsInputGenTable OBJECT-TYPE
SYNTAX SEQUENCE OF UpsInputGenEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of input table entries. The number of entries
is given by the value of upsInputNumLines.(*)"
::= { upsInputgen 3 }
upsInputGenEntry OBJECT-TYPE
SYNTAX UpsInputGenEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a
particular input line.(*)"
INDEX { upsInputLineIndexgen }
::= { upsInputGenTable 1 }
UpsInputGenEntry ::= SEQUENCE {
upsInputLineIndexgen PositiveInteger32,
upsInputFrequencygen NonNegativeInteger32,
upsInputVoltagegen NonNegativeInteger32,
upsInputCurrentgen NonNegativeInteger32,
upsInputTruePowergen NonNegativeInteger32,
upsInputVoltageMingen NonNegativeInteger32,
upsInputVoltageMaxgen NonNegativeInteger32
}
upsInputLineIndexgen OBJECT-TYPE
SYNTAX PositiveInteger32
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The input line identifier.(*)"
::= { upsInputGenEntry 1 }
upsInputFrequencygen OBJECT-TYPE
SYNTAX NonNegativeInteger32
UNITS "0.1 Hertz"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present input frequency.(*)"
::= { upsInputGenEntry 2 }
upsInputVoltagegen OBJECT-TYPE
SYNTAX NonNegativeInteger32
UNITS "RMS Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The magnitude of the present input voltage.(*)"
::= { upsInputGenEntry 3 }
upsInputCurrentgen OBJECT-TYPE
SYNTAX NonNegativeInteger32
UNITS "0.1 RMS Amp"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The magnitude of the present input current.(*)"
::= { upsInputGenEntry 4 }
upsInputTruePowergen OBJECT-TYPE
SYNTAX NonNegativeInteger32
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The magnitude of the present input true power.(*)"
::= { upsInputGenEntry 5 }
upsInputVoltageMingen OBJECT-TYPE
SYNTAX NonNegativeInteger32
UNITS "RMS Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The lowest magnitude of the input voltage since last read out."
::= { upsInputGenEntry 6 }
upsInputVoltageMaxgen OBJECT-TYPE
SYNTAX NonNegativeInteger32
UNITS "RMS Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The highest magnitude of the input voltage since last read out."
::= { upsInputGenEntry 7 }
--
-- The Output group.
--
upsOutputSourcegen OBJECT-TYPE
SYNTAX INTEGER {
other(1),
none(2),
normal(3),
bypass(4),
battery(5),
booster(6),
reducer(7)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present source of output power. The enumeration
none(2) indicates that there is no source of output
power (and therefore no output power), for example,
the system has opened the output breaker.(*)"
::= { upsOutputgen 1 }
upsOutputFrequencygen OBJECT-TYPE
SYNTAX NonNegativeInteger32
UNITS "0.1 Hertz"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present output frequency.(*)"
::= { upsOutputgen 2 }
upsOutputNumLinesgen OBJECT-TYPE
SYNTAX NonNegativeInteger32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of output lines utilized in this device.
This variable indicates the number of rows in the
output table.(*)"
::= { upsOutputgen 3 }
upsOutputGenTable OBJECT-TYPE
SYNTAX SEQUENCE OF UpsOutputGenEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of output table entries. The number of
entries is given by the value of upsOutputNumLines.(*)"
::= { upsOutputgen 4 }
upsOutputGenEntry OBJECT-TYPE
SYNTAX UpsOutputGenEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a
particular output line.(*)"
INDEX { upsOutputLineIndexgen }
::= { upsOutputGenTable 1 }
UpsOutputGenEntry ::= SEQUENCE {
upsOutputLineIndexgen PositiveInteger32,
upsOutputVoltagegen NonNegativeInteger32,
upsOutputCurrentgen NonNegativeInteger32,
upsOutputPowergen NonNegativeInteger32,
upsOutputPercentLoadgen Integer32,
upsOutputPowerFactorgen Integer32,
upsOutputPeakCurrentgen Integer32,
upsOutputShareCurrentgen Integer32
}
upsOutputLineIndexgen OBJECT-TYPE
SYNTAX PositiveInteger32
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The output line identifier.(*)"
::= { upsOutputGenEntry 1 }
upsOutputVoltagegen OBJECT-TYPE
SYNTAX NonNegativeInteger32
UNITS "RMS Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present output voltage.(*)"
::= { upsOutputGenEntry 2 }
upsOutputCurrentgen OBJECT-TYPE
SYNTAX NonNegativeInteger32
UNITS "0.1 RMS Amp"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present output current.(*)"
::= { upsOutputGenEntry 3 }
upsOutputPowergen OBJECT-TYPE
SYNTAX NonNegativeInteger32
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present output true power.(*)"
::= { upsOutputGenEntry 4 }
upsOutputPercentLoadgen OBJECT-TYPE
SYNTAX Integer32 (0..200)
UNITS "percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The percentage of the UPS power capacity presently
being used on this output line, i.e., the greater of
the percent load of true power capacity and the
percent load of VA.(*)"
::= { upsOutputGenEntry 5 }
upsOutputPowerFactorgen OBJECT-TYPE
SYNTAX Integer32 (-99..100)
UNITS "0.01 cos phi"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present output power factor.
The returned value correspond to the cosf of the load.
A positive value indicate an inductive load;
a negative value indicate a capacitive load;
value 1 indicate a resistive load.
If the measure is not available due to a small load for
a consistent calculation, the NA value is then returned.(*)"
::= { upsOutputGenEntry 6 }
upsOutputPeakCurrentgen OBJECT-TYPE
SYNTAX Integer32
UNITS "Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present output peak current.(*)"
::= { upsOutputGenEntry 7 }
upsOutputShareCurrentgen OBJECT-TYPE
SYNTAX Integer32
UNITS "Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"In a parallel system ideally all the UPS are requested to
contribute to the load with the same amount of current,
i.e. with no current share. The current share occurs when an
UPS exchanges some current with another UPS, so that this
current component doesn't feed the load.
The share part of the UPS current represents an undesired UPS
loading, and therefore it should be minimized. If the share
current is too high, the UPS results overloaded and in some
conditions (i.e. very high load) the system could turn on
bypass reducing dramatically the global system reliability.
PMAD detects the amount of share currents in a parallel system,
generating an alarm if this value is above a parameter-based threshold.
Single UPS systems don't have this feature, NA will be provided.(*)"
::= { upsOutputGenEntry 8 }
--
-- The Bypass group generic.
--
upsBypassFrequencygen OBJECT-TYPE
SYNTAX NonNegativeInteger32
UNITS "0.1 Hertz"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present bypass frequency.(*)"
::= { upsBypassgen 1 }
upsBypassNumLinesgen OBJECT-TYPE
SYNTAX NonNegativeInteger32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of bypass lines utilized in this device.
This entry indicates the number of rows in the bypass
table.(*)"
::= { upsBypassgen 2 }
upsBypassGenTable OBJECT-TYPE
SYNTAX SEQUENCE OF UpsBypassGenEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of bypass table entries. The number of
entries is given by the value of upsBypassNumLines.(*)"
::= { upsBypassgen 3 }
upsBypassGenEntry OBJECT-TYPE
SYNTAX UpsBypassGenEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a
particular bypass input.(*)"
INDEX { upsBypassLineIndexgen }
::= { upsBypassGenTable 1 }
UpsBypassGenEntry ::= SEQUENCE {
upsBypassLineIndexgen PositiveInteger32,
upsBypassVoltagegen NonNegativeInteger32,
upsBypassCurrentgen NonNegativeInteger32,
upsBypassPowergen NonNegativeInteger32
}
upsBypassLineIndexgen OBJECT-TYPE
SYNTAX PositiveInteger32
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The bypass line identifier.(*)"
::= { upsBypassGenEntry 1 }
upsBypassVoltagegen OBJECT-TYPE
SYNTAX NonNegativeInteger32
UNITS "RMS Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present bypass voltage.(*)"
::= { upsBypassGenEntry 2 }
upsBypassCurrentgen OBJECT-TYPE
SYNTAX NonNegativeInteger32
UNITS "0.1 RMS Amp"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present bypass current.(*)"
::= { upsBypassGenEntry 3 }
upsBypassPowergen OBJECT-TYPE
SYNTAX NonNegativeInteger32
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present true power conveyed by the bypass.(*)"
::= { upsBypassGenEntry 4 }
--
-- The Alarm group generic.
--
upsAlarmsPresentgen OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present number of active alarm conditions.(*)"
::= { upsAlarmgen 1 }
upsAlarmGenTable OBJECT-TYPE
SYNTAX SEQUENCE OF UpsAlarmGenEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of alarm table entries. The table contains
zero, one, or many rows at any moment, depending upon
the number of alarm conditions in effect. The table
is initially empty at agent startup. The agent
creates a row in the table each time a condition is
detected and deletes that row when that condition no
longer pertains. The agent creates the first row with
upsAlarmId equal to 1, and increments the value of
upsAlarmId each time a new row is created, wrapping to
the first free value greater than or equal to 1 when
the maximum value of upsAlarmId would otherwise be
exceeded. Consequently, after multiple operations,
the table may become sparse, e.g., containing entries
for rows 95, 100, 101, and 203 and the entries should
not be assumed to be in chronological order because
upsAlarmId might have wrapped.
Alarms are named by an AutonomousType (OBJECT
IDENTIFIER), upsAlarmDescr, to allow a single table to
reflect well known alarms plus alarms defined by a
particular implementation, i.e., as documented in the
private enterprise MIB definition for the device. No
two rows will have the same value of upsAlarmDescr,
since alarms define conditions. In order to meet this
requirement, care should be taken in the definition of
alarm conditions to insure that a system cannot enter
the same condition multiple times simultaneously.
The number of rows in the table at any given time is
reflected by the value of upsAlarmsPresent.(*)"
::= { upsAlarmgen 2 }
upsAlarmGenEntry OBJECT-TYPE
SYNTAX UpsAlarmGenEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a
particular alarm.(*)"
INDEX { upsAlarmIdgen }
::= { upsAlarmGenTable 1 }
UpsAlarmGenEntry ::= SEQUENCE {
upsAlarmIdgen PositiveInteger32,
upsAlarmDescrgen AutonomousType,
upsAlarmTimegen TimeStamp
}
upsAlarmIdgen OBJECT-TYPE
SYNTAX PositiveInteger32
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A unique identifier for an alarm condition. This
value must remain constant.(*)"
::= { upsAlarmGenEntry 1 }
upsAlarmDescrgen OBJECT-TYPE
SYNTAX AutonomousType
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A reference to an alarm description object. The
object referenced should not be accessible, but rather
be used to provide a unique description of the alarm
condition.(*)"
::= { upsAlarmGenEntry 2 }
upsAlarmTimegen OBJECT-TYPE
SYNTAX TimeStamp
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The value of sysUpTime when the alarm condition was
detected. If the alarm condition was detected at the
time of agent startup and presumably existed before
agent startup, the value of upsAlarmTime shall equal
0.(*)"
::= { upsAlarmGenEntry 3 }
--
-- Well known alarm conditions generic.
--
upsAlarmBatteryBadgen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more batteries have been determined to require
replacement.(*)"
::= { upsWellKnownAlarmsgen 1 }
upsAlarmOnBatterygen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The UPS is drawing power from the batteries.(*)"
::= { upsWellKnownAlarmsgen 2 }
upsAlarmLowBatterygen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The remaining battery run-time is less than or equal
to upsConfigLowBattTime.(*)"
::= { upsWellKnownAlarmsgen 3 }
upsAlarmDepletedBatterygen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The UPS will be unable to sustain the present load
when and if the utility power is lost.(*)"
::= { upsWellKnownAlarmsgen 4 }
upsAlarmTempBadgen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A temperature is out of tolerance.(*)"
::= { upsWellKnownAlarmsgen 5 }
upsAlarmInputBadgen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"An input condition is out of tolerance.(*)"
::= { upsWellKnownAlarmsgen 6 }
upsAlarmOutputBadgen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"An output condition (other than OutputOverload) is
out of tolerance.(*)"
::= { upsWellKnownAlarmsgen 7 }
upsAlarmOutputOverloadgen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output load exceeds the UPS output capacity.(*)"
::= { upsWellKnownAlarmsgen 8 }
upsAlarmOnBypassgen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The Bypass is presently engaged on the UPS.(*)"
::= { upsWellKnownAlarmsgen 9 }
upsAlarmBypassBadgen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The Bypass is out of tolerance.(*)"
::= { upsWellKnownAlarmsgen 10 }
upsAlarmOutputOffAsRequestedgen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The UPS has shutdown as requested, i.e., the output
is off.(*)"
::= { upsWellKnownAlarmsgen 11 }
upsAlarmUpsOffAsRequestedgen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The entire UPS has shutdown as commanded.(*)"
::= { upsWellKnownAlarmsgen 12 }
upsAlarmChargerFailedgen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"An uncorrected problem has been detected within the
UPS charger subsystem.(*)"
::= { upsWellKnownAlarmsgen 13 }
upsAlarmUpsOutputOffgen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output of the UPS is in the off state.(*)"
::= { upsWellKnownAlarmsgen 14 }
upsAlarmUpsSystemOffgen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The UPS system is in the off state.(*)"
::= { upsWellKnownAlarmsgen 15 }
upsAlarmFanFailuregen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The failure of one or more fans in the UPS has been
detected.(*)"
::= { upsWellKnownAlarmsgen 16 }
upsAlarmFuseFailuregen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The failure of one or more fuses has been detected.(*)"
::= { upsWellKnownAlarmsgen 17 }
upsAlarmGeneralFaultgen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A general fault in the UPS has been detected.(*)"
::= { upsWellKnownAlarmsgen 18 }
upsAlarmDiagnosticTestFailedgen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The result of the last diagnostic test indicates a
failure.(*)"
::= { upsWellKnownAlarmsgen 19 }
upsAlarmCommunicationsLostgen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A problem has been encountered in the communications
between the agent and the UPS.(*)"
::= { upsWellKnownAlarmsgen 20 }
upsAlarmAwaitingPowergen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The UPS output is off and the UPS is awaiting the
return of input power.(*)"
::= { upsWellKnownAlarmsgen 21 }
upsAlarmShutdownPendinggen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A upsShutdownAfterDelay countdown is underway.(*)"
::= { upsWellKnownAlarmsgen 22 }
upsAlarmShutdownImminentgen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The UPS will turn off power to the load in less than
5 seconds; this may be either a timed shutdown or a
low battery shutdown.(*)"
::= { upsWellKnownAlarmsgen 23 }
upsAlarmTestInProgressgen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A test is in progress, as initiated and indicated by
the Test Group. Tests initiated via other
implementation-specific mechanisms can indicate the
presence of the testing in the alarm table, if
desired, via a OBJECT-IDENTITY macro in the MIB
document specific to that implementation and are
outside the scope of this OBJECT-IDENTITY.(*)"
::= { upsWellKnownAlarmsgen 24 }
upsAlarmReceptacleOffgen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The receptacle are switch off "
::= { upsWellKnownAlarmsgen 25 }
upsAlarmHighSpeedBusFailuregen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A problem on the High Speed Bus communication is detected"
::= { upsWellKnownAlarmsgen 26 }
upsAlarmHighSpeedBusJACRCFailuregen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A High Speed Bus CRC failure on Bus JA is detected"
::= { upsWellKnownAlarmsgen 27 }
upsAlarmConnectivityBusFailuregen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A problem on the Connectivity Bus communication is detected"
::= { upsWellKnownAlarmsgen 28 }
upsAlarmHighSpeedBusJBCRCFailuregen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A High Speed Bus CRC failure on Bus JB is detected"
::= { upsWellKnownAlarmsgen 29 }
upsAlarmCurrentSharinggen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The UPS detects an high current sharing on the parallel system"
::= { upsWellKnownAlarmsgen 30 }
upsAlarmDCRipplegen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The UPS detects an high ripple voltage on his DC link"
::= { upsWellKnownAlarmsgen 31 }
upsAlarmMaskAgen OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Specifies which alarm can be handled by the UPS.
The 'Mask' parameter is a Long Integer32. The meaning
of every bit is the same as for the 'upsAlarmGroupA'
command. A bit having value=1 indicates that the
corresponding alarm is handled by the UPS."
::= { upsAlarmgen 4 }
--
-- The Test Group generic
--
upsTestIdgen OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The test is named by an OBJECT IDENTIFIER which
allows a standard mechanism for the initiation of
tests, including the well known tests identified in
this document as well as those introduced by a
particular implementation, i.e., as documented in the
private enterprise MIB definition for the device.
Setting this variable initiates the named test. Sets
to this variable require the presence of
upsTestSpinLock in the same SNMP message.
The set request will be rejected with an appropriate
error message if the requested test cannot be
performed, including attempts to start a test when
another test is already in progress. The status of
the current or last test is maintained in
upsTestResultsSummary. Tests in progress may be
aborted by setting the upsTestId variable to
upsTestAbortTestInProgress.
Read operations return the value of the name of the
test in progress if a test is in progress or the name
of the last test performed if no test is in progress,
unless no test has been run, in which case the well
known value upsTestNoTestsInitiated is returned.(*)"
::= { upsTestgen 1 }
-- see [6] for more information on the semantics of objects with
-- syntax of TestAndIncr
upsTestSpinLockgen OBJECT-TYPE
SYNTAX TestAndIncr
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A spin lock on the test subsystem. The spinlock is
used as follows.
Before starting a test, a manager-station should make
sure that a test is not in progress as follows:
tryagain:
get (upsTestSpinLock)
while (upsTestResultsSummary == inProgress) {
/* loop while a test is running for another
manager */
short delay
get (upsTestSpinLock)
}
lockvalue = upsTestSpinLock
/* no test in progress, start the test */
set (upsTestSpinLock = lockvalue, upsTestId =
requestedtest)
if (errorindex == 1) { /* (upsTestSpinLock
failed) */
/* if problem is not access control, then
some other manager slipped in ahead of us
*/
goto tryagain
}
if (errorindex == 2) { /* (upsTestId) */
/* cannot perform the test */
give up
}
/* test started ok */
/* wait for test completion by polling
upsTestResultsSummary */
get (upsTestSpinLock, upsTestResultsSummary,
upsTestResultsDetail)
while (upsTestResultsSummary == inProgress) {
short delay
get (upsTestSpinLock, upsTestResultsSummary,
upsTestResultsDetail)
}
/* when test completes, retrieve any additional
test results */
/* if upsTestSpinLock == lockvalue + 1, then
these are our test */
/* results (as opposed to another manager's */
The initial value of upsTestSpinLock at agent
initialization shall
be 1.(*)"
::= { upsTestgen 2 }
upsTestResultsSummarygen OBJECT-TYPE
SYNTAX INTEGER {
donePass(1),
doneWarning(2),
doneError(3),
aborted(4),
inProgress(5),
noTestsInitiated(6)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The results of the current or last UPS diagnostics
test performed. The values for donePass(1),
doneWarning(2), and doneError(3) indicate that the
test completed either successfully, with a warning, or
with an error, respectively. The value aborted(4) is
returned for tests which are aborted by setting the
value of upsTestId to upsTestAbortTestInProgress.
Tests which have not yet concluded are indicated by
inProgress(5). The value noTestsInitiated(6)
indicates that no previous test results are available,
such as is the case when no tests have been run since
the last reinitialization of the network management
subsystem and the system has no provision for non-
volatile storage of test results.(*)"
::= { upsTestgen 3 }
upsTestResultsDetailgen OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Additional information about upsTestResultsSummary.
If no additional information available, a zero length
string is returned.(*)"
::= { upsTestgen 4 }
upsTestStartTimegen OBJECT-TYPE
SYNTAX TimeStamp
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The value of sysUpTime at the time the test in
progress was initiated, or, if no test is in progress,
the time the previous test was initiated. If the
value of upsTestResultsSummary is noTestsInitiated(6),
upsTestStartTime has the value 0.(*)"
::= { upsTestgen 5 }
upsTestElapsedTimegen OBJECT-TYPE
SYNTAX TimeInterval
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The amount of time, in TimeTicks, since the test in
progress was initiated, or, if no test is in progress,
the previous test took to complete. If the value of
upsTestResultsSummary is noTestsInitiated(6),
upsTestElapsedTime has the value 0.(*)"
::= { upsTestgen 6 }
--
-- Well known tests generic.
--
upsTestNoTestsInitiatedgen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"No tests have been initiated and no test is in
progress.(*)"
::= { upsWellKnownTestsgen 1 }
upsTestAbortTestInProgressgen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The test in progress is to be aborted / the test in
progress was aborted.(*)"
::= { upsWellKnownTestsgen 2 }
upsTestGeneralSystemsTestgen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The manufacturer's standard test of UPS device
systems.(*)"
::= { upsWellKnownTestsgen 3 }
upsTestQuickBatteryTestgen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A test that is sufficient to determine if the battery
needs replacement.(*)"
::= { upsWellKnownTestsgen 4 }
upsTestDeepBatteryCalibrationgen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system is placed on battery to a discharge level,
set by the manufacturer, sufficient to determine
battery replacement and battery run-time with a high
degree of confidence. WARNING: this test will leave
the battery in a low charge state and will require
time for recharging to a level sufficient to provide
normal battery duration for the protected load.(*)"
::= { upsWellKnownTestsgen 5 }
--
-- The Control group generic.
--
upsShutdownTypegen OBJECT-TYPE
SYNTAX INTEGER {
output(1),
system(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This object determines the nature of the action to be
taken at the time when the countdown of the
upsShutdownAfterDelay and upsRebootWithDuration
objects reaches zero.
Setting this object to output(1) indicates that
shutdown requests should cause only the output of the
UPS to turn off. Setting this object to system(2)
indicates that shutdown requests will cause the entire
UPS system to turn off.(*)"
::= { upsControlgen 1 }
upsShutdownAfterDelaygen OBJECT-TYPE
SYNTAX Integer32 (-1..2147483647)
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Setting this object will shutdown (i.e., turn off)
either the UPS output or the UPS system (as determined
by the value of upsShutdownType at the time of
shutdown) after the indicated number of seconds, or
less if the UPS batteries become depleted. Setting
this object to 0 will cause the shutdown to occur
immediately. Setting this object to -1 will abort the
countdown. If the system is already in the desired
state at the time the countdown reaches 0, then
nothing will happen. That is, there is no additional
action at that time if upsShutdownType = system and
the system is already off. Similarly, there is no
additional action at that time if upsShutdownType =
output and the output is already off. When read,
upsShutdownAfterDelay will return the number of
seconds remaining until shutdown, or -1 if no shutdown
countdown is in effect. On some systems, if the agent
is restarted while a shutdown countdown is in effect,
the countdown may be aborted. Sets to this object
override any upsShutdownAfterDelay already in effect.(*)"
::= { upsControlgen 2 }
upsStartupAfterDelaygen OBJECT-TYPE
SYNTAX Integer32 (-1..2147483647)
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Setting this object will start the output after the
indicated number of seconds, including starting the
UPS, if necessary. Setting this object to 0 will
cause the startup to occur immediately. Setting this
object to -1 will abort the countdown. If the output
is already on at the time the countdown reaches 0,
then nothing will happen. Sets to this object
override the effect of any upsStartupAfterDelay
countdown or upsRebootWithDuration countdown in
progress. When read, upsStartupAfterDelay will return
the number of seconds until startup, or -1 if no
startup countdown is in effect. If the countdown
expires during a utility failure, the startup shall
not occur until the utility power is restored. On
some systems, if the agent is restarted while a
startup countdown is in effect, the countdown is
aborted.(*)"
::= { upsControlgen 3 }
upsRebootWithDurationgen OBJECT-TYPE
SYNTAX Integer32 (-1..300)
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Setting this object will immediately shutdown (i.e.,
turn off) either the UPS output or the UPS system (as
determined by the value of upsShutdownType at the time
of shutdown) for a period equal to the indicated
number of seconds, after which time the output will be
started, including starting the UPS, if necessary. If
the number of seconds required to perform the request
is greater than the requested duration, then the
requested shutdown and startup cycle shall be
performed in the minimum time possible, but in no case
shall this require more than the requested duration
plus 60 seconds. When read, upsRebootWithDuration
shall return the number of seconds remaining in the
countdown, or -1 if no countdown is in progress. If
the startup should occur during a utility failure, the
startup shall not occur until the utility power is
restored.(*)"
::= { upsControlgen 4 }
upsAutoRestartgen OBJECT-TYPE
SYNTAX INTEGER {
on(1),
off(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Setting this object to 'on' will cause the UPS system
to restart after a shutdown if the shutdown occurred
during a power loss as a result of either a
upsShutdownAfterDelay or an internal battery depleted
condition. Setting this object to 'off' will prevent
the UPS system from restarting after a shutdown until
an operator manually or remotely explicitly restarts
it. If the UPS is in a startup or reboot countdown,
then the UPS will not restart until that delay has
been satisfied.(*)"
::= { upsControlgen 5 }
upsReceptaclesNumgen OBJECT-TYPE
SYNTAX NonNegativeInteger32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of receptacles utilized in this device.
This entry indicates the number of rows in the receptacle
table."
::= { upsControlgen 6 }
upsReceptacleGenTable OBJECT-TYPE
SYNTAX SEQUENCE OF UpsReceptacleGenEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of receptacle table entries. The number of
entries is given by the value of upsReceptacleNum."
::= { upsControlgen 7 }
upsReceptacleGenEntry OBJECT-TYPE
SYNTAX UpsReceptacleGenEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a
particular receptacle."
INDEX { upsReceptacleLineIndexgen }
::= { upsReceptacleGenTable 1 }
UpsReceptacleGenEntry ::= SEQUENCE {
upsReceptacleLineIndexgen PositiveInteger32,
upsReceptacleOnOffgen INTEGER
}
upsReceptacleLineIndexgen OBJECT-TYPE
SYNTAX PositiveInteger32
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The receptacle line identifier."
::= { upsReceptacleGenEntry 1 }
upsReceptacleOnOffgen OBJECT-TYPE
SYNTAX INTEGER {
on(1),
off(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The present state of the receptacle. Setting this
object to 'on' will cause the receptacle to be turned
on. Setting this object to 'off' will turn the
receptacle off. If the receptacle is already in the
desired state nothing will happen. After an
autorestart (see upsAutoRestart) the receptacle will
be on."
::= { upsReceptacleGenEntry 2 }
upsUPSModegen OBJECT-TYPE
SYNTAX INTEGER {
offLine(1),
onLine(2),
ecomode(3),
iem(4)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The operation mode off the UPS. Off-line indicates a
mode in which the input power is transferred to the
output directly or via a step-up or step-down
transformer. On-line mode indicates a mode in which
the output power is regenerated through some convertor.
the operating mode of the UPS may be fixed, or may be
selectable (e.g. an on-line UPS with ecomode)"
::= { upsControlgen 8 }
upsRectifierOnOffgen OBJECT-TYPE
SYNTAX INTEGER {
on(1),
off(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The present state of the rectifier. Setting this
object to 'on' will cause the rectifier to be turned
on. Setting this object to 'off' will turn the
rectifier off. If the rectifier is already in the
desired state nothing will happen. "
::= { upsControlgen 9 }
upsBatteryChargeMethodgen OBJECT-TYPE
SYNTAX INTEGER {
normalcharge(1),
boostcharge(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The present state of the charge method. Setting this
object to 'Normal charge' will cause the battery to be
charged using the normal method. Setting this object to
'Boost charge' will charge the battery in boost mode.
If the charge method is already in the desired state
nothing will happen. "
::= { upsControlgen 10 }
upsInverterOnOffgen OBJECT-TYPE
SYNTAX INTEGER {
on(1),
off(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The present state of the inverter. Setting this
object to 'on' will cause the inverter to be turned
on. Setting this object to 'off' will turn the
inverter off. If the inverter is already in the
desired state nothing will happen. "
::= { upsControlgen 11 }
upsBypassOnOffgen OBJECT-TYPE
SYNTAX INTEGER {
on(1),
off(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The present state of the bypass. Setting this
object to 'on' will cause the bypass to be activated.
Setting this object to 'off' will deactivate the
bypass. If the UPS is already in the
desired state nothing will happen. "
::= { upsControlgen 12 }
upsLoadSourcegen OBJECT-TYPE
SYNTAX INTEGER {
onbypass(1),
onInverter(2),
onDetour(3),
loadOff(4),
other (5)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The present source of the load. Setting this
object to 'On bypass' will cause the load to be
supplied by the bypass.
Setting this object to 'On inverter' will cause the
load to be supplied by the inverter.
If the load is already supplied by the desired
source nothing will happen. "
::= { upsControlgen 13 }
--
-- The Configuration group generic.
--
upsConfigInputVoltagegen OBJECT-TYPE
SYNTAX NonNegativeInteger32
UNITS "RMS Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The magnitude of the nominal input voltage. On those
systems which support read-write access to this
object, if there is an attempt to set this variable to
a value that is not supported, the request must be
rejected and the agent shall respond with an
appropriate error message, i.e., badValue for SNMPv1,
or inconsistentValue for SNMPv2.(*)"
::= { upsConfiggen 1 }
upsConfigInputFreqgen OBJECT-TYPE
SYNTAX NonNegativeInteger32
UNITS "0.1 Hertz"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The nominal input frequency. On those systems which
support read-write access to this object, if there is
an attempt to set this variable to a value that is not
supported, the request must be rejected and the agent
shall respond with an appropriate error message, i.e.,
badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)"
::= { upsConfiggen 2 }
upsConfigOutputVoltagegen OBJECT-TYPE
SYNTAX NonNegativeInteger32
UNITS "RMS Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The magnitude of the nominal output voltage. On
those systems which support read-write access to this
object, if there is an attempt to set this variable to
a value that is not supported, the request must be
rejected and the agent shall respond with an
appropriate error message, i.e., badValue for SNMPv1,
or inconsistentValue for SNMPv2.(*)"
::= { upsConfiggen 3 }
upsConfigOutputFreqgen OBJECT-TYPE
SYNTAX NonNegativeInteger32
UNITS "0.1 Hertz"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The nominal output frequency. On those systems which
support read-write access to this object, if there is
an attempt to set this variable to a value that is not
supported, the request must be rejected and the agent
shall respond with an appropriate error message, i.e.,
badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)"
::= { upsConfiggen 4 }
upsConfigOutputVAgen OBJECT-TYPE
SYNTAX NonNegativeInteger32
UNITS "Volt-Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The magnitude of the nominal Volt-Amp rating.(*)"
::= { upsConfiggen 5 }
upsConfigOutputPowergen OBJECT-TYPE
SYNTAX NonNegativeInteger32
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The magnitude of the nominal true power rating.(*)"
::= { upsConfiggen 6 }
upsConfigLowBattTimegen OBJECT-TYPE
SYNTAX NonNegativeInteger32
UNITS "minutes"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value of upsEstimatedMinutesRemaining at which a
lowBattery condition is declared. For agents which
support only discrete (discontinuous) values, then the
agent shall round up to the next supported value. If
the requested value is larger than the largest
supported value, then the largest supported value
shall be selected.(*)"
::= { upsConfiggen 7 }
upsConfigAudibleStatusgen OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
enabled(2),
muted(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The requested state of the audible alarm. When in
the disabled state, the audible alarm should never
sound. The enabled state is self-describing. Setting
this object to muted(3) when the audible alarm is
sounding shall temporarily silence the alarm. It will
remain muted until it would normally stop sounding and
the value returned for read operations during this
period shall equal muted(3). At the end of this
period, the value shall revert to enabled(2). Writes
of the value muted(3) when the audible alarm is not
sounding shall be accepted but otherwise shall have no
effect.(*)"
::= { upsConfiggen 8 }
upsConfigLowVoltageTransferPointgen OBJECT-TYPE
SYNTAX NonNegativeInteger32
UNITS "RMS Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The minimum input line voltage allowed before the UPS
system transfers to battery backup.(*)"
::= { upsConfiggen 9 }
upsConfigHighVoltageTransferPointgen OBJECT-TYPE
SYNTAX NonNegativeInteger32
UNITS "RMS Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The maximum line voltage allowed before the UPS
system transfers to battery backup.(*)"
::= { upsConfiggen 10 }
upsConfigBatteryCapacitygen OBJECT-TYPE
SYNTAX NonNegativeInteger32
UNITS "Amps Hours"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The installed battery capacity. This value is the 'factory'-value,
not the value after calibration."
::= { upsConfiggen 11 }
upsConfigBatteryChargeCurrentgen OBJECT-TYPE
SYNTAX NonNegativeInteger32
UNITS "0.1 Amp DC"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The maximum battery charge current, including external chargers."
::= { upsConfiggen 12 }
upsConfigNoLoadShutdowngen OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
enabled(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Dis- or enable 'no load' shutdown from the contact interface."
::= { upsConfiggen 13 }
upsConfigStartDelaygen OBJECT-TYPE
SYNTAX PositiveInteger32
UNITS "minutes"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Minimum required autonomy time before the UPS may perform an
autorestart."
::= { upsConfiggen 14 }
--
-- The GetSet group generic.
--
upsEventGetNextgen OBJECT-TYPE
SYNTAX PositiveInteger32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The number of events to retreive from the UPS event buffer.
When this object is set the EventTable will be filled with the
requested number of entries. The value upsEventSetStartingTimeStamp
will be used as the start value of the table with the lowest index number."
::= { upsGetSetgen 1 }
upsEventGetPreviousgen OBJECT-TYPE
SYNTAX PositiveInteger32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The number of events to retreive from the UPS event buffer.
When this object is set the EventTable will be filled with the
requested number of entries. The value upsEventLastTime will
be used as the last value of the table with the highest index number.
Returns SNMPNOSUCHNAME for UPSs that don't support this command."
::= { upsGetSetgen 2 }
upsEventSetStartingTimeStampgen OBJECT-TYPE
SYNTAX NonNegativeInteger32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The timestamp which is used as starting point for downloading
events from the UPS event buffer"
::= { upsGetSetgen 3 }
upsEventRetreiveCurrentTimeStampgen OBJECT-TYPE
SYNTAX NonNegativeInteger32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current timestamp is retreived from the UPS"
::= { upsGetSetgen 4 }
upsEventTableSizegen OBJECT-TYPE
SYNTAX NonNegativeInteger32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of entries in the event table.
This object indicates the number of rows in the event table."
::= { upsGetSetgen 5 }
upsEventGenTable OBJECT-TYPE
SYNTAX SEQUENCE OF UpsEventGenEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of event table entries. The number of entries is always
10, and the value of upsEventTableSize gives the number of valid
entries from the begging of the table. Invalid entries return 0.
To prevent problems with simultaneous queries from several agents,
these values MUST be accessed using several PDUs in the
same SNMP message (<number> is (1..10)):
PDU-SET upsSetStartingTimeStamp <time>
PDU-SET upsEventGetNext <number>
PDU-GET upsEventTableSize
PDU-GET upsEventCode,upsEventStatus,upsEventTime 1
PDU-GET upsEventCode,upsEventStatus,upsEventTime 2
..
PDU-GET upsEventCode,upsEventStatus,upsEventTime <number>
The table is read up to requested number of events and the
management software afterwards decides which entries are
valid, as indicated by the upsEventTableSize.
"
::= { upsGetSetgen 6 }
upsEventGenEntry OBJECT-TYPE
SYNTAX UpsEventGenEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a
particular event."
INDEX { upsEventLineIndexgen }
::= { upsEventGenTable 1 }
UpsEventGenEntry ::= SEQUENCE {
upsEventLineIndexgen PositiveInteger32,
upsEventCodegen Integer32,
upsEventStatusgen NonNegativeInteger32,
upsEventTimegen NonNegativeInteger32
}
upsEventLineIndexgen OBJECT-TYPE
SYNTAX PositiveInteger32
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The event line identifier."
::= { upsEventGenEntry 1 }
upsEventCodegen OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The event code in numerical format."
::= { upsEventGenEntry 2 }
upsEventStatusgen OBJECT-TYPE
SYNTAX NonNegativeInteger32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The status of the UPS at the moment that the event was generated.
The format is specified at the 'upsStatus' command.
If the UPS is not able to deliver status information, then
SNMPNOSUCHNAME is returned."
::= { upsEventGenEntry 3 }
upsEventTimegen OBJECT-TYPE
SYNTAX NonNegativeInteger32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The timestamp of the moment the event was generated."
::= { upsEventGenEntry 4 }
upsParametersReadgen OBJECT-TYPE
SYNTAX PositiveInteger32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The number of parameters to retreive from the UPS.
When this object is set the ParameterTable will be filled with the
requested number of entries. The value upsParametersStartAddress
will be used as the start value of the table with the lowest index
number."
::= { upsGetSetgen 7 }
upsParametersWritegen OBJECT-TYPE
SYNTAX PositiveInteger32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The number of parameters to write to the UPS.
When this object is set the ParameterTable will be send to the ups.
The value upsParametersStartAddress will be used for the first value
of the table with the lowest index number."
::= { upsGetSetgen 8 }
upsParametersStartAddressgen OBJECT-TYPE
SYNTAX NonNegativeInteger32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The address which is used as starting point for downloading
parameters from the UPS"
::= { upsGetSetgen 9 }
upsParameterTableSizegen OBJECT-TYPE
SYNTAX NonNegativeInteger32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of entries in the parameter table.
This object indicates the number of rows in the parameter table."
::= { upsGetSetgen 10 }
upsParameterGenTable OBJECT-TYPE
SYNTAX SEQUENCE OF UpsParameterGenEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of parameter entries. The number of entries is always
16, and the value of upsParameterTableSize gives the number of valid
entries from the begging of the table. Invalid entries return 0.
To prevent problems with simultaneous queries from several agents,
these values MUST be accessed using several PDUs in the
same SNMP message (<number> is (1..16)):
Read sequence:
PDU-SET upsSetStartingAddress <addr>
PDU-SET upsParametersRead <number>
PDU-GET upsParameterTableSize
PDU-GET upsParameterValue 1
PDU-GET upsParameterValue 2
..
PDU-GET upsParameterValue <number>
The table is read up to requested number of events and the
management software afterwards decides which entries are
valid, as indicated by the upsParameterTableSize.
Write sequence:
PDU-SET upsSetStartingAddress <addr>
PDU-SET upsParameterValue 1
PDU-SET upsParameterValue 2
..
PDU-SET upsParameterValue <number>
PDU-SET upsParametersWrite <number>
"
::= { upsGetSetgen 11 }
upsParameterGenEntry OBJECT-TYPE
SYNTAX UpsParameterGenEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a
particular parameter."
INDEX { upsParameterLineIndexgen }
::= { upsParameterGenTable 1 }
UpsParameterGenEntry ::= SEQUENCE {
upsParameterLineIndexgen PositiveInteger32,
upsParameterValuegen Integer32
}
upsParameterLineIndexgen OBJECT-TYPE
SYNTAX PositiveInteger32
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The parameter line identifier."
::= { upsParameterGenEntry 1 }
upsParameterValuegen OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The parameter value in numerical format."
::= { upsParameterGenEntry 2 }
upsStatusgen OBJECT-TYPE
SYNTAX NonNegativeInteger32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The global UPS status is returned. Every bit reflects a specific
status condition. Unused bits returns as 0. The status value can
also be found on other commands. The value SNMPNOSUCHNAME means
'invalid status' or 'status value non available'.
Status
1 0000 0001h upsStatusEcomodeIsOn
2 0000 0002h upsStatusBatteryIsCharging
4 0000 0004h upsStatusBatteryIsDischarging
8 0000 0008h upsStatusAlarmIsActive
16 0000 0010h upsStatusRectifierIsOn
32 0000 0020h upsStatusLowBattery
64 0000 0040h upsStatusOnBypass
128 0000 0080h upsStatusMainsBypassOK
256 0000 0100h upsStatusMainsRectifierOK
512 0000 0200h upsStatusDetourIsOn
1024 0000 0400h upsStatusAcousticAlarmIsOn
2048 0000 0800h upsStatusGlobalServiceCheck
4096 0000 1000h upsStatusInverterIsOn
8192 0000 2000h upsStatusNotInParallel (Q1 open)
16384 0000 4000h upsStatusResetLoadOff
32768 0000 8000h upsStatusLoadOff
65536 0001 0000h upsStatusBoostMode
131072 0002 0000h upsStatusBuckMode
262144 0004 0000h upsStatusIemModeIsOn
524288 0008 0000h upsStatus5thFilterIsOn
1048576 0010 0000h upsStatus11thFilterIsOn
2097152 0020 0000h upsStatus2ndRectifierBridgeIsOn
4194304 0040 0000h - reserved -
8388608 0080 0000h - reserved -
16777216 0100 0000h - reserved -
33554432 0200 0000h - reserved -
67108864 0400 0000h - reserved -
134217728 0800 0000h - reserved -
268435456 1000 0000h upsGlobalParallelValues "
::= { upsGetSetgen 12 }
upsMainsStatisticsMBfailgen OBJECT-TYPE
SYNTAX NonNegativeInteger32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Count of main bypass failures (>200 ms), since UPS installation."
::= { upsGetSetgen 13 }
upsMainsStatisticsMRfailgen OBJECT-TYPE
SYNTAX NonNegativeInteger32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Count of mains rectifier failures (>200 ms), since UPS installation."
::= { upsGetSetgen 14 }
upsMainsStatisticsB2gen OBJECT-TYPE
SYNTAX NonNegativeInteger32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Count of transients on the mains bypass (0..2 ms), during the last 7 days."
::= { upsGetSetgen 15 }
upsMainsStatisticsB5gen OBJECT-TYPE
SYNTAX NonNegativeInteger32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Count of transients on the mains bypass (2..5 ms), during the last 7 days."
::= { upsGetSetgen 16 }
upsMainsStatisticsB10gen OBJECT-TYPE
SYNTAX NonNegativeInteger32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Count of transients on the mains bypass (5..10 ms), during the last 7 days."
::= { upsGetSetgen 17 }
upsMainsStatisticsB200gen OBJECT-TYPE
SYNTAX NonNegativeInteger32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Count of transients on the mains bypass (10..200 ms), during the last 7 days."
::= { upsGetSetgen 18 }
upsMainsStatisticsBypRelgen OBJECT-TYPE
SYNTAX NonNegativeInteger32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Bypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'."
::= { upsGetSetgen 19 }
upsTimegen OBJECT-TYPE
SYNTAX NonNegativeInteger32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The current timestamp (or real-time) of the UPS. For the format,
see 'Timestamp' specifications. The write-command has to comply with the
correct timestamp format expected by the UPS (counter value or real-time-clock
value). Missing to doing so will result in a SNMPgenERROR,
meaning 'command not supported'. It is possible to know which is the timestamp
format supported by the UPS, by issuing a read-command or by reading events,
which includes timestamps."
::= { upsGetSetgen 20 }
upsRequestPermissiongen OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"An encrypted code is send to enable use of restricted write objects during
a limited period of time."
::= { upsGetSetgen 21 }
upsEventGetCodegen OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The code which is used as starting point to downloading the events from the
UPS event buffer."
::= { upsGetSetgen 22 }
upsEventSpinLockgen OBJECT-TYPE
SYNTAX TestAndIncr
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A spin lock on the event subsystem. "
::= { upsGetSetgen 23 }
upsParameterSpinLockgen OBJECT-TYPE
SYNTAX TestAndIncr
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A spin lock on the parameters subsystem. "
::= { upsGetSetgen 24 }
---
--- GE Trap group generic
---
upsTrapAlarmBatteryBadgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"One or more batteries have been determined to require
replacement."
::= { geUPSTrapsgen 1 }
upsTrapAlarmOnBatterygen NOTIFICATION-TYPE
OBJECTS { upsSecondsOnBatterygen }
STATUS current
DESCRIPTION
"The UPS is drawing power from the batteries."
::= { geUPSTrapsgen 2 }
upsTrapAlarmLowBatterygen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"The remaining battery run-time is less than or equal
to upsConfigLowBattTime."
::= { geUPSTrapsgen 3 }
upsTrapAlarmDepletedBatterygen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"The UPS will be unable to sustain the present load
when and if the utility power is lost)"
::= { geUPSTrapsgen 4 }
upsTrapAlarmTempBadgen NOTIFICATION-TYPE
OBJECTS { upsBatteryTemperaturegen }
STATUS current
DESCRIPTION
"A temperature is out of tolerance."
::= { geUPSTrapsgen 5 }
upsTrapAlarmInputBadgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"An input condition is out of tolerance."
::= { geUPSTrapsgen 6 }
upsTrapAlarmOutputBadgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"An output condition (other than OutputOverload) is
out of tolerance."
::= { geUPSTrapsgen 7 }
upsTrapAlarmOutputOverloadgen NOTIFICATION-TYPE
OBJECTS { upsOutputNumLinesgen, upsOutputPercentLoadgen }
STATUS current
DESCRIPTION
"The output load exceeds the UPS output capacity."
::= { geUPSTrapsgen 8 }
upsTrapAlarmOnBypassgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"The Bypass is presently engaged on the UPS."
::= { geUPSTrapsgen 9 }
upsTrapAlarmBypassBadgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"The Bypass is out of tolerance."
::= { geUPSTrapsgen 10 }
upsTrapAlarmOutputOffAsRequestedgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"The UPS has shutdown as requested, i.e., the output
is off."
::= { geUPSTrapsgen 11 }
upsTrapAlarmUpsOffAsRequestedgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"The entire UPS has shutdown as commanded."
::= { geUPSTrapsgen 12 }
upsTrapAlarmChargerFailedgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"An uncorrected problem has been detected within the
UPS charger subsystem."
::= { geUPSTrapsgen 13 }
upsTrapAlarmUpsOutputOffgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"The output of the UPS is in the off state."
::= { geUPSTrapsgen 14 }
upsTrapAlarmUpsSystemOffgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"The UPS system is in the off state."
::= { geUPSTrapsgen 15 }
upsTrapAlarmFanFailuregen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"The failure of one or more fans in the UPS has been
detected."
::= { geUPSTrapsgen 16 }
upsTrapAlarmFuseFailuregen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"The failure of one or more fuses has been detected."
::= { geUPSTrapsgen 17 }
upsTrapAlarmGeneralFaultgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"A general fault in the UPS has been detected."
::= { geUPSTrapsgen 18 }
upsTrapAlarmDiagnosticTestFailedgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"The result of the last diagnostic test indicates a
failure."
::= { geUPSTrapsgen 19 }
upsTrapAlarmCommunicationsLostgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"A problem has been encountered in the communication
between the agent and the UPS."
::= { geUPSTrapsgen 20 }
upsTrapAlarmAwaitingPowergen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"The UPS output is off and the UPS is awaiting the
return of the input power (*)."
::= { geUPSTrapsgen 21 }
upsTrapAlarmShutdownPendinggen NOTIFICATION-TYPE
OBJECTS { upsShutdownAfterDelaygen }
STATUS current
DESCRIPTION
"A upsShutdownAfterDelay countdown is underway."
::= { geUPSTrapsgen 22 }
upsTrapAlarmShutdownImminentgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"The UPS will turn off power to the load in less than
5 seconds; this may be either a timed shutdown or a
low battery shutdown."
::= { geUPSTrapsgen 23 }
upsTrapAlarmTestInProgressgen NOTIFICATION-TYPE
OBJECTS { upsTestIdgen }
STATUS current
DESCRIPTION
"A test is in progress, as initiated and indicated by
the Test Group. Tests initiated via other
implementation-specific mechanisms can indicate the
presence of the testing in the alarm table, if
desired, via a OBJECT-IDENTITY macro in the MIB
document specific to that implementation and are
outside the scope of this OBJECT-IDENTITY."
::= { geUPSTrapsgen 24 }
upsTrapAlarmReceptacleOffgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"A receptacle has been switched off."
::= { geUPSTrapsgen 25 }
upsTrapAlarmHighspeedBusFailuregen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"A problem on the Highspeed Bus communication is detected."
::= { geUPSTrapsgen 26 }
upsTrapAlarmHighspeedBusJACRCFailuregen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"A CRC failure on the Highspeed Bus JA is detected."
::= { geUPSTrapsgen 27 }
upsTrapAlarmConnectivityBusFailuregen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"A Connectivity Bus failure is detected"
::= { geUPSTrapsgen 28 }
upsTrapAlarmHighspeedBusJBCRCFailuregen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"A CRC failure on the Highspeed Bus JB is detected."
::= { geUPSTrapsgen 29 }
upsTrapAlarmCurrentSharingFailuregen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"An high current sharing on the parallel system is detected."
::= { geUPSTrapsgen 30 }
upsTrapAlarmDCRippleFailuregen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"An high ripple voltage on his DC link is detected."
::= { geUPSTrapsgen 31 }
upsTrapAlarmBatteryBadRestoredgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"A Battery bad condition is restored."
::= { geUPSTrapsgen 33 }
upsTrapAlarmOnBatteryRestoredgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"The UPS is drawing power from mains again."
::= { geUPSTrapsgen 34 }
upsTrapAlarmLowBatteryRestoredgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"A Low Battery condition is restored."
::= { geUPSTrapsgen 35 }
upsTrapAlarmDepletedBatteryRestoredgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"A Depleted Battery condition is restored."
::= { geUPSTrapsgen 36 }
upsTrapAlarmTempBadRestoredgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"A bad temperature condition is restored."
::= { geUPSTrapsgen 37 }
upsTrapAlarmInputBadRestoredgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"An input bad condition is restored."
::= { geUPSTrapsgen 38 }
upsTrapAlarmOutputBadRestoredgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"An output bad condition is restored."
::= { geUPSTrapsgen 39 }
upsTrapAlarmOutputOverloadRestoredgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"An output overload condition is restored."
::= { geUPSTrapsgen 40 }
upsTrapAlarmOnBypassRestoredgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"An On Bypass condition is restored."
::= { geUPSTrapsgen 41 }
upsTrapAlarmBypassBadRestoredgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"A Bypass bad condition is restored."
::= { geUPSTrapsgen 42 }
upsTrapAlarmOutputOffAsRequestedRestoredgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"A request shutdown has been restored."
::= { geUPSTrapsgen 43 }
upsTrapAlarmUpsOffAsRequestedRestoredgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"A entire UPS command has been restored."
::= { geUPSTrapsgen 44 }
upsTrapAlarmChargerFailedRestoredgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"A Charger Failer condition is restored."
::= { geUPSTrapsgen 45 }
upsTrapAlarmUpsOutputOngen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"The output of the UPS switched in the on state."
::= { geUPSTrapsgen 46 }
upsTrapAlarmUpsSystemOngen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"The UPS system is switched in the on state."
::= { geUPSTrapsgen 47 }
upsTrapAlarmFanFailureRestoredgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"A Fan failure condition is restored."
::= { geUPSTrapsgen 48 }
upsTrapAlarmFuseFailureRestoredgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"A Fuse failure condition is restored."
::= { geUPSTrapsgen 49 }
upsTrapAlarmGeneralFaultRestoredgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"A general fault is restored."
::= { geUPSTrapsgen 50 }
upsTrapAlarmDiagnosticTestFailedRestoredgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"A last diagnostic test indicates a failure is
restored."
::= { geUPSTrapsgen 51 }
upsTrapAlarmCommunicationsLostRestoredgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"A problem in the communication between the agent
and the UPS is restored."
::= { geUPSTrapsgen 52 }
upsTrapAlarmAwaitingPowerRestoredgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"A awaiting power condition is restored (*)."
::= { geUPSTrapsgen 53 }
upsTrapAlarmShutdownPendingRestoredgen NOTIFICATION-TYPE
OBJECTS { upsShutdownAfterDelaygen }
STATUS current
DESCRIPTION
"A upsShutdownAfterDelay countdown is restored."
::= { geUPSTrapsgen 54 }
upsTrapAlarmShutdownImminentRestoredgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"A shutdown imminent condition is restored."
::= { geUPSTrapsgen 55 }
upsTrapAlarmTestInProgressRestoredgen NOTIFICATION-TYPE
OBJECTS { upsTestIdgen }
STATUS current
DESCRIPTION
"The test is in progress is terminated."
::= { geUPSTrapsgen 56 }
upsTrapAlarmReceptacleOn NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"A receptacle has been switched on."
::= { geUPSTrapsgen 57 }
upsTrapAlarmHighspeedBusRestoredgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"A problem on the Highspeed Bus communication is restored."
::= { geUPSTrapsgen 58 }
upsTrapAlarmHighspeedBusJACRCRestoredAgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"A CRC failure on the Highspeed Bus JA is restored."
::= { geUPSTrapsgen 59 }
upsTrapAlarmConnectivityBusRestoredgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"A problem on the Connectivity Bus communication is restored."
::= { geUPSTrapsgen 60 }
upsTrapAlarmHighspeedBusJBCRCRestoredBgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"A CRC failure on the Highspeed Bus JB is restored."
::= { geUPSTrapsgen 61 }
upsTrapAlarmCurrentSharingRestoredgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"An high current sharing on the parallel system is restored."
::= { geUPSTrapsgen 62 }
upsTrapAlarmDCRippleRestoredgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"An high ripple voltage on his DC link is restored."
::= { geUPSTrapsgen 63 }
upsTrapAlarmValueLowgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"A measurement value reached a value below its low-level threshold."
::= { geUPSTrapsgen 129 }
upsTrapAlarmValueHighgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"A measurement value reached a value higher than its high-level threshold."
::= { geUPSTrapsgen 130 }
upsTrapAlarmValueLowRestoredgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"A ValueLow alarm condition is restored."
::= { geUPSTrapsgen 133 }
upsTrapAlarmValueHighRestoredgen NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"A ValueHigh alarm condition is restored."
::= { geUPSTrapsgen 134 }
--
-- Diagnostic Group Generic
--
upsDiagnosticBusJACommunicationStatusgen OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Bit oriented values associated to the ID of the UPS
(bit0 = UPS1 ... bit7 = UPS8).
The correspondent UPS is not present on the high speed
bus communication JA if bit=0.(*)"
::= { upsDiagnosticgen 1 }
upsDiagnosticBusJBCommunicationStatusgen OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Bit oriented values associated to the ID of the UPS
(bit0 = UPS1 ... bit7 = UPS8).
The correspondent UPS is not present on the high speed
bus communication JA if bit=0.(*)"
::= { upsDiagnosticgen 2 }
upsDiagnosticBatteryLifetimegen OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The critical components are associated to Service
parameters indicating the remaining lifetime.
They are initially set to default values depending
to the data given by the component supplier.
The parameter values decrease over time and when one
of them reaches zero (lifetime expiration) a service
check warning is generated, indicating that a check or
a replacement is suggested for that component.
The service technician is then required to re-set the
default value after the replacing of the component.(*)"
::= { upsDiagnosticgen 3 }
upsDiagnosticFansLifetimegen OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The critical components are associated to Service
parameters indicating the remaining lifetime.
They are initially set to default values depending
to the data given by the component supplier.
The parameter values decrease over time and when one
of them reaches zero (lifetime expiration) a service
check warning is generated, indicating that a check or
a replacement is suggested for that component.
The service technician is then required to re-set the
default value after the replacing of the component.(*)"
::= { upsDiagnosticgen 4 }
upsDiagnosticDCcapacitorsLifetimegen OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The critical components are associated to Service
parameters indicating the remaining lifetime.
They are initially set to default values depending
to the data given by the component supplier.
The parameter values decrease over time and when one
of them reaches zero (lifetime expiration) a service
check warning is generated, indicating that a check or
a replacement is suggested for that component.
The service technician is then required to re-set the
default value after the replacing of the component.(*)"
::= { upsDiagnosticgen 5 }
upsDiagnosticACcapacitorsLifetimegen OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The critical components are associated to Service
parameters indicating the remaining lifetime.
They are initially set to default values depending
to the data given by the component supplier.
The parameter values decrease over time and when one
of them reaches zero (lifetime expiration) a service
check warning is generated, indicating that a check or
a replacement is suggested for that component.
The service technician is then required to re-set the
default value after the replacing of the component.(*)"
::= { upsDiagnosticgen 6 }
upsDiagnosticGlobalServiceCheckgen OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The critical components are associated to Service
parameters indicating the remaining lifetime.
They are initially set to default values depending
to the data given by the component supplier.
The parameter values decrease over time and when one
of them reaches zero (lifetime expiration) a service
check warning is generated, indicating that a check or
a replacement is suggested for that component.
The service technician is then required to re-set the
default value after the replacing of the component.(*)"
::= { upsDiagnosticgen 7 }
END