-- GE Management Information Base VERSION 2.00
|
|
--
|
|
-- Date: 11/10/2004
|
|
-- Changes: remove of "_" in snmp identifiers, remove of duplicate comment characters
|
|
-- Author : MHCL
|
|
--
|
|
-- Date 02/14/2005
|
|
-- Changes: remove additional size definition for DisplayString
|
|
-- Changes: remove additional range definition of PositiveInteger32
|
|
-- Changes: change of range definition for Integer32 entries
|
|
-- Changes: change names of managed UPSs so that tablenames end with 'table'
|
|
-- without changes of other structures
|
|
-- Changes: change some Capital-/Lowercase issues
|
|
|
|
-- Author : MHCL
|
|
-- Date: 15/11/2006
|
|
-- Changes: added BatterRipple
|
|
-- Changes: added OutputPowerFactor; OutputPeakCurrent; OutputShareCurrent
|
|
-- Changes: added alarm HighpeedBusfailure; HighpeedBusCRCfailure; ConnectivityBusfailure
|
|
-- Changes: added traps HighpeedBusfailure; HighpeedBusCRCfailure; ConnectivityBusfailure
|
|
-- Changes: added traps HighpeedBusrestore; HighpeedBusCRCrestore; ConnectivityBusrestore
|
|
-- Changes: added group Diagnostic
|
|
-- Changes: added BatteryLifetime; FansLifetime; DCcapacitorsLifetime; ACcapacitorsLifetime
|
|
-- GlobalServiceCheck
|
|
-- Changes: added Status ServiceCheck
|
|
-- Deleted: geEnvironmental tree
|
|
-- Deleted: geModem tree
|
|
-- Deleted: geDevices tree
|
|
-- Deleted: geSoftware tree
|
|
--
|
|
-- Author: GE, Stefan Kuhn
|
|
-- Date: 25/11/2006
|
|
-- Changes: upsDiagnosticGlobalServiceChecke Syntax from DisplayString to Integer32
|
|
-- Changes: upsDiagnosticGlobalServiceChecke into upsDiagnosticGlobalServiceCheck
|
|
--
|
|
-- Author: GE, Stefan Kuhn
|
|
-- Date: 27/11/2006
|
|
-- added: upsDiagnosticBusJACommunicationStatus
|
|
-- added: upsDiagnosticBusJBCommunicationStatus
|
|
-- Moved: BatteryLifetime; FansLifetime; DCcapacitorsLifetime; ACcapacitorsLifetime
|
|
-- GlobalServiceCheck
|
|
-- Author: GE, Stefan Kuhn
|
|
--
|
|
-- Date: 10/12/2006
|
|
-- modified: upsSecondsOnBattery from NonNegativeInteger32 back to Integer32
|
|
-- for the backard compatibility
|
|
-- added: upsAlarmHighSpeedBusJACRCFailure,upsAlarmHighSpeedBusJBCRCFailure,upsAlarmShareCurrent,
|
|
-- upsAlarmDCRipple and there relative traps
|
|
-- Author: GE, Stefan Kuhn
|
|
--
|
|
-- Date: 22/Oct/2007
|
|
-- added: geDevices group
|
|
-- Author: GE, L. Giuntini
|
|
--
|
|
-- Date: Jan 8th, 2008
|
|
-- Author: GE, L. Giuntini
|
|
-- Created version 2.00 for SMIv2 compliance
|
|
-- Changes include the following:
|
|
-- * MODULE-IDENTITY clause introduced right after the IMPORT statement
|
|
-- * Compliance to RFC2578, section 7.1.1, second paragraph
|
|
-- in case of enumerations, use INTEGER rather than Integer32
|
|
-- * Replace MAX-ACCESS read-only with MAX-ACCESS read-write
|
|
-- (access `write-only' is no longer allowed in SMIv2)
|
|
-- * Use NOTIFICATION-TYPE instead of TRAP-TYPE for Traps
|
|
-- Remove ENTERPRISE clause
|
|
-- Rename VARIABLES clause as OBJECTS clause
|
|
-- Add STATUS current clause
|
|
-- Incorporate traps in the Object tree
|
|
-- * Finally, corrected some errors (undefined/re-defined identifiers)
|
|
-- Added 'Trap' to the trap name in order to prevent redefinition errors
|
|
--
|
|
-- Date: Jul 5th, 2010
|
|
-- Author: GE, L. Giuntini
|
|
-- Created version 2.40 for IEMi / eBoost introduction
|
|
-- Modified:
|
|
-- * Description (Properties) for the upsStatus, upsUPSMode OIDs
|
|
-- * Various changes to ensure full SNMP v2 compliance
|
|
--
|
|
-- GE-MIB
|
|
-- { iso org(3) dod(6) internet(1) private(4) enterprises(1) imv(818) }
|
|
--
|
|
-- Title: GE-MIB
|
|
-- By: Theo Versteeg & Fontana Gianluca
|
|
--
|
|
-- 11-5-00 Theo Versteeg
|
|
-- Removed the complete Victron-MIB to create a new IMV-mib to cover Comprot4,
|
|
-- IM and IMV1 protocol.
|
|
-- incl. external devices and object for the agents and protection software.
|
|
--
|
|
-- Entries marked with (*) are part of the RFC1628 definition
|
|
-- Although we integrated the RFC1628 in our own OID range,
|
|
-- all RCF1628 OIDs should also be accessable on their own OID defined in RFC1628.
|
|
|
|
|
|
GESINGLEUPS-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
|
|
MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE,
|
|
OBJECT-IDENTITY, Counter32, Gauge32, Integer32, Unsigned32, enterprises
|
|
FROM SNMPv2-SMI
|
|
DisplayString, TimeStamp, TimeInterval, TestAndIncr,
|
|
AutonomousType, TEXTUAL-CONVENTION
|
|
FROM SNMPv2-TC;
|
|
|
|
imv MODULE-IDENTITY
|
|
LAST-UPDATED "201007050000Z"
|
|
ORGANIZATION "GE Digital Energy"
|
|
CONTACT-INFO
|
|
"GE Digital Energy
|
|
Via Cantonale, 50
|
|
CH-6595 Riazzino
|
|
Switzerland"
|
|
DESCRIPTION
|
|
"The MIB module to describe GE Digital Energy
|
|
Uninterruptible Power Supplies."
|
|
REVISION "201007050000Z"
|
|
DESCRIPTION
|
|
"Updated following IEMi & eBoost introduction."
|
|
REVISION "200801080000Z"
|
|
DESCRIPTION
|
|
"SNMPv2 compliant MIB released."
|
|
::= { enterprises 818 }
|
|
|
|
PositiveInteger32 ::= TEXTUAL-CONVENTION
|
|
DISPLAY-HINT "d"
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This data type is a non-zero and non-negative value."
|
|
SYNTAX Integer32 (1..2147483647)
|
|
|
|
|
|
NonNegativeInteger32 ::= TEXTUAL-CONVENTION
|
|
DISPLAY-HINT "d"
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This data type is a non-negative value."
|
|
SYNTAX Integer32 (0..2147483647)
|
|
|
|
geHardware OBJECT IDENTIFIER ::= { imv 1 }
|
|
|
|
geUPS OBJECT IDENTIFIER ::= { geHardware 1 }
|
|
|
|
|
|
-- The following list is not really a table, but can be implemented as one in the software.
|
|
-- The complete UPS section is simply too large to fit in a pre-defined table.
|
|
-- The solution:
|
|
-- * All objects are defined for geGenericUPS
|
|
-- * All individual UPSs of parallel systems can be reached by their respective sequence
|
|
-- number as reflected in below list in stead of the geGenericUPS objects.
|
|
|
|
geGenericUPS OBJECT IDENTIFIER ::= { geUPS 10 }
|
|
|
|
-- Generic UPS
|
|
|
|
upsIdentgen OBJECT IDENTIFIER ::= { geGenericUPS 1 }
|
|
upsBatterygen OBJECT IDENTIFIER ::= { geGenericUPS 2 }
|
|
upsInputgen OBJECT IDENTIFIER ::= { geGenericUPS 3 }
|
|
upsOutputgen OBJECT IDENTIFIER ::= { geGenericUPS 4 }
|
|
upsBypassgen OBJECT IDENTIFIER ::= { geGenericUPS 5 }
|
|
upsAlarmgen OBJECT IDENTIFIER ::= { geGenericUPS 6 }
|
|
upsWellKnownAlarmsgen OBJECT IDENTIFIER ::= { upsAlarmgen 3 }
|
|
upsTestgen OBJECT IDENTIFIER ::= { geGenericUPS 7 }
|
|
upsWellKnownTestsgen OBJECT IDENTIFIER ::= { upsTestgen 7 }
|
|
upsControlgen OBJECT IDENTIFIER ::= { geGenericUPS 8 }
|
|
upsConfiggen OBJECT IDENTIFIER ::= { geGenericUPS 9 }
|
|
upsGetSetgen OBJECT IDENTIFIER ::= { geGenericUPS 10 }
|
|
geUPSTrapsgen OBJECT IDENTIFIER ::= { geGenericUPS 11 }
|
|
upsDiagnosticgen OBJECT IDENTIFIER ::= { geGenericUPS 12 }
|
|
|
|
-- Device
|
|
|
|
geDevices OBJECT IDENTIFIER ::= { geHardware 100 }
|
|
geDevicesDescriptions OBJECT IDENTIFIER ::= { geDevices 1 }
|
|
|
|
advSNMPWebIntCard OBJECT IDENTIFIER ::= { geDevicesDescriptions 1 }
|
|
snmpWebIntCard OBJECT IDENTIFIER ::= { geDevicesDescriptions 2 }
|
|
snmpWebIntBox OBJECT IDENTIFIER ::= { geDevicesDescriptions 3 }
|
|
|
|
--
|
|
-- The GE UPS group
|
|
--
|
|
|
|
geDiscoveredUPSsMask OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reading this variable returns bit mask indicating which
|
|
UPSs in a parallel system are alive. Management
|
|
software should poll only these UPSs on their snmp
|
|
branches 11-18 as follows:
|
|
|
|
1 FirstUPS alive
|
|
2 SecondUPS alive
|
|
4 ThirdUPS alive
|
|
8 FourthUPS alive
|
|
16 FifthUPS alive
|
|
32 SixthUPS alive
|
|
64 SeventhUPS alive
|
|
128 EigthUPS alive
|
|
|
|
Since the management software should always monitor
|
|
the GenericUPS branch (10), this value has no meaning
|
|
for single upses (which provide values on that snmp
|
|
branch), and should be set to zero in that case."
|
|
::= { geUPS 1 }
|
|
|
|
geRequestPacket OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Put the string, formatted as a IMV/CP4 packet, directly to internally RS485 bus.
|
|
This OID could be used for accede directly to the internally RS485 bus from a remote place."
|
|
::= { geUPS 2 }
|
|
|
|
geReplyPacket OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Contain the reply of the IMV/CP4 request packet sent using the OID geRequestPacket.
|
|
Every time that a write command has be made at the OID ge RequestPacket, the value of this OID is erased."
|
|
::= { geUPS 3 }
|
|
|
|
|
|
|
|
--
|
|
-- The Device Identification group. Generic
|
|
-- All objects in this group except for upsIdentName and
|
|
-- upsIdentAttachedDevices are set at device initialization
|
|
-- and remain static.
|
|
--
|
|
|
|
upsIdentManufacturergen OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The name of the UPS manufacturer.(*)"
|
|
::= { upsIdentgen 1 }
|
|
|
|
upsIdentModelgen OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS Model designation.(*)"
|
|
::= { upsIdentgen 2 }
|
|
|
|
upsIdentUPSSoftwareVersiongen OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS firmware/software version(s). This variable
|
|
may or may not have the same value as
|
|
upsIdentAgentSoftwareVersion in some implementations.(*)"
|
|
::= { upsIdentgen 3 }
|
|
|
|
upsIdentAgentSoftwareVersiongen OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS agent software version. This variable may or
|
|
may not have the same value as
|
|
upsIdentUPSSoftwareVersion in some implementations.(*)"
|
|
::= { upsIdentgen 4 }
|
|
|
|
upsIdentNamegen OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A string identifying the UPS. This object should be
|
|
set by the administrator.(*)"
|
|
::= { upsIdentgen 5 }
|
|
|
|
upsIdentAttachedDevicesgen OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A string identifying the devices attached to the
|
|
output(s) of the UPS. This object should be set by
|
|
the administrator.(*)"
|
|
::= { upsIdentgen 6 }
|
|
|
|
upsIdentUPSSerialNumbergen OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS serial number"
|
|
::= { upsIdentgen 7 }
|
|
|
|
upsIdentComProtVersiongen OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The IMV communication protocol version"
|
|
::= { upsIdentgen 8 }
|
|
|
|
upsIdentOperatingTimegen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present value of the operating time.
|
|
total 'on' time since UPS manufactured"
|
|
::= { upsIdentgen 9 }
|
|
|
|
--
|
|
-- Battery Group Generic
|
|
--
|
|
|
|
upsBatteryStatusgen OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown(1),
|
|
batteryNormal(2),
|
|
batteryLow(3),
|
|
batteryDepleted(4)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The indication of the capacity remaining in the UPS
|
|
system's batteries. A value of batteryNormal
|
|
indicates that the remaining run-time is greater than
|
|
upsConfigLowBattTime. A value of batteryLow indicates
|
|
that the remaining battery run-time is less than or
|
|
equal to upsConfigLowBattTime. A value of
|
|
batteryDepleted indicates that the UPS will be unable
|
|
to sustain the present load when and if the utility
|
|
power is lost (including the possibility that the
|
|
utility power is currently absent and the UPS is
|
|
unable to sustain the output).(*)"
|
|
::= { upsBatterygen 1 }
|
|
|
|
upsSecondsOnBatterygen OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"If the unit is on battery power, the elapsed time
|
|
since the UPS last switched to battery power, or the
|
|
time since the network management subsystem was last
|
|
restarted, whichever is less. Zero shall be returned
|
|
if the unit is not on battery power.(*)"
|
|
::= { upsBatterygen 2 }
|
|
|
|
upsEstimatedMinutesRemaininggen OBJECT-TYPE
|
|
SYNTAX PositiveInteger32
|
|
UNITS "minutes"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An estimate of the time to battery charge depletion
|
|
under the present load conditions if the utility power
|
|
is off and remains off, or if it were to be lost and
|
|
remain off.(*)"
|
|
::= { upsBatterygen 3 }
|
|
|
|
upsEstimatedChargeRemaininggen OBJECT-TYPE
|
|
SYNTAX Integer32 (0..100)
|
|
UNITS "percent"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An estimate of the battery charge remaining expressed
|
|
as a percent of full charge.(*)"
|
|
::= { upsBatterygen 4 }
|
|
|
|
upsBatteryVoltagegen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
UNITS "0.1 Volt DC"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The magnitude of the present battery voltage.(*)"
|
|
::= { upsBatterygen 5 }
|
|
|
|
upsBatteryCurrentgen OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.1 Amp DC"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present battery current.(*)"
|
|
::= { upsBatterygen 6 }
|
|
|
|
upsBatteryTemperaturegen OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "degrees Centigrade"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The ambient temperature at or near the UPS Battery
|
|
casing.(*)"
|
|
::= { upsBatterygen 7 }
|
|
|
|
upsBatteryRipplegen OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.1 Volt RMS"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present DC link RMS voltage ripple.(*)"
|
|
::= { upsBatterygen 8 }
|
|
|
|
|
|
--
|
|
-- Input Group
|
|
--
|
|
|
|
upsInputLineBadsgen OBJECT-TYPE
|
|
SYNTAX Counter32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A count of the number of times the input entered an
|
|
out-of-tolerance condition as defined by the
|
|
manufacturer. This count is incremented by one each
|
|
time the input transitions from zero out-of-tolerance
|
|
lines to one or more input lines out-of-tolerance.(*)"
|
|
::= { upsInputgen 1 }
|
|
|
|
upsInputNumLinesgen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of input lines utilized in this device.
|
|
This variable indicates the number of rows in the
|
|
input table.(*)"
|
|
::= { upsInputgen 2 }
|
|
|
|
upsInputGenTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsInputGenEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of input table entries. The number of entries
|
|
is given by the value of upsInputNumLines.(*)"
|
|
::= { upsInputgen 3 }
|
|
|
|
upsInputGenEntry OBJECT-TYPE
|
|
SYNTAX UpsInputGenEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular input line.(*)"
|
|
INDEX { upsInputLineIndexgen }
|
|
::= { upsInputGenTable 1 }
|
|
|
|
UpsInputGenEntry ::= SEQUENCE {
|
|
upsInputLineIndexgen PositiveInteger32,
|
|
upsInputFrequencygen NonNegativeInteger32,
|
|
upsInputVoltagegen NonNegativeInteger32,
|
|
upsInputCurrentgen NonNegativeInteger32,
|
|
upsInputTruePowergen NonNegativeInteger32,
|
|
upsInputVoltageMingen NonNegativeInteger32,
|
|
upsInputVoltageMaxgen NonNegativeInteger32
|
|
}
|
|
|
|
upsInputLineIndexgen OBJECT-TYPE
|
|
SYNTAX PositiveInteger32
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The input line identifier.(*)"
|
|
::= { upsInputGenEntry 1 }
|
|
|
|
upsInputFrequencygen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
UNITS "0.1 Hertz"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present input frequency.(*)"
|
|
::= { upsInputGenEntry 2 }
|
|
|
|
upsInputVoltagegen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
UNITS "RMS Volts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The magnitude of the present input voltage.(*)"
|
|
::= { upsInputGenEntry 3 }
|
|
|
|
upsInputCurrentgen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
UNITS "0.1 RMS Amp"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The magnitude of the present input current.(*)"
|
|
::= { upsInputGenEntry 4 }
|
|
|
|
upsInputTruePowergen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
UNITS "Watts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The magnitude of the present input true power.(*)"
|
|
::= { upsInputGenEntry 5 }
|
|
|
|
upsInputVoltageMingen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
UNITS "RMS Volts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The lowest magnitude of the input voltage since last read out."
|
|
::= { upsInputGenEntry 6 }
|
|
|
|
upsInputVoltageMaxgen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
UNITS "RMS Volts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The highest magnitude of the input voltage since last read out."
|
|
::= { upsInputGenEntry 7 }
|
|
|
|
--
|
|
-- The Output group.
|
|
--
|
|
|
|
upsOutputSourcegen OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
other(1),
|
|
none(2),
|
|
normal(3),
|
|
bypass(4),
|
|
battery(5),
|
|
booster(6),
|
|
reducer(7)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present source of output power. The enumeration
|
|
none(2) indicates that there is no source of output
|
|
power (and therefore no output power), for example,
|
|
the system has opened the output breaker.(*)"
|
|
::= { upsOutputgen 1 }
|
|
|
|
upsOutputFrequencygen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
UNITS "0.1 Hertz"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present output frequency.(*)"
|
|
::= { upsOutputgen 2 }
|
|
|
|
upsOutputNumLinesgen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of output lines utilized in this device.
|
|
This variable indicates the number of rows in the
|
|
output table.(*)"
|
|
::= { upsOutputgen 3 }
|
|
|
|
upsOutputGenTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsOutputGenEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of output table entries. The number of
|
|
entries is given by the value of upsOutputNumLines.(*)"
|
|
::= { upsOutputgen 4 }
|
|
|
|
upsOutputGenEntry OBJECT-TYPE
|
|
SYNTAX UpsOutputGenEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular output line.(*)"
|
|
INDEX { upsOutputLineIndexgen }
|
|
::= { upsOutputGenTable 1 }
|
|
|
|
UpsOutputGenEntry ::= SEQUENCE {
|
|
upsOutputLineIndexgen PositiveInteger32,
|
|
upsOutputVoltagegen NonNegativeInteger32,
|
|
upsOutputCurrentgen NonNegativeInteger32,
|
|
upsOutputPowergen NonNegativeInteger32,
|
|
upsOutputPercentLoadgen Integer32,
|
|
upsOutputPowerFactorgen Integer32,
|
|
upsOutputPeakCurrentgen Integer32,
|
|
upsOutputShareCurrentgen Integer32
|
|
}
|
|
|
|
upsOutputLineIndexgen OBJECT-TYPE
|
|
SYNTAX PositiveInteger32
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The output line identifier.(*)"
|
|
::= { upsOutputGenEntry 1 }
|
|
|
|
upsOutputVoltagegen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
UNITS "RMS Volts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present output voltage.(*)"
|
|
::= { upsOutputGenEntry 2 }
|
|
|
|
upsOutputCurrentgen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
UNITS "0.1 RMS Amp"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present output current.(*)"
|
|
::= { upsOutputGenEntry 3 }
|
|
|
|
upsOutputPowergen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
UNITS "Watts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present output true power.(*)"
|
|
::= { upsOutputGenEntry 4 }
|
|
|
|
upsOutputPercentLoadgen OBJECT-TYPE
|
|
SYNTAX Integer32 (0..200)
|
|
UNITS "percent"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The percentage of the UPS power capacity presently
|
|
being used on this output line, i.e., the greater of
|
|
the percent load of true power capacity and the
|
|
percent load of VA.(*)"
|
|
::= { upsOutputGenEntry 5 }
|
|
|
|
upsOutputPowerFactorgen OBJECT-TYPE
|
|
SYNTAX Integer32 (-99..100)
|
|
UNITS "0.01 cos phi"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present output power factor.
|
|
The returned value correspond to the cosf of the load.
|
|
A positive value indicate an inductive load;
|
|
a negative value indicate a capacitive load;
|
|
value 1 indicate a resistive load.
|
|
If the measure is not available due to a small load for
|
|
a consistent calculation, the NA value is then returned.(*)"
|
|
::= { upsOutputGenEntry 6 }
|
|
|
|
upsOutputPeakCurrentgen OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Amps"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present output peak current.(*)"
|
|
::= { upsOutputGenEntry 7 }
|
|
|
|
upsOutputShareCurrentgen OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Amps"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"In a parallel system ideally all the UPS are requested to
|
|
contribute to the load with the same amount of current,
|
|
i.e. with no current share. The current share occurs when an
|
|
UPS exchanges some current with another UPS, so that this
|
|
current component doesn't feed the load.
|
|
The share part of the UPS current represents an undesired UPS
|
|
loading, and therefore it should be minimized. If the share
|
|
current is too high, the UPS results overloaded and in some
|
|
conditions (i.e. very high load) the system could turn on
|
|
bypass reducing dramatically the global system reliability.
|
|
PMAD detects the amount of share currents in a parallel system,
|
|
generating an alarm if this value is above a parameter-based threshold.
|
|
Single UPS systems don't have this feature, NA will be provided.(*)"
|
|
::= { upsOutputGenEntry 8 }
|
|
|
|
--
|
|
-- The Bypass group generic.
|
|
--
|
|
|
|
upsBypassFrequencygen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
UNITS "0.1 Hertz"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present bypass frequency.(*)"
|
|
::= { upsBypassgen 1 }
|
|
|
|
upsBypassNumLinesgen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of bypass lines utilized in this device.
|
|
This entry indicates the number of rows in the bypass
|
|
table.(*)"
|
|
::= { upsBypassgen 2 }
|
|
|
|
upsBypassGenTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsBypassGenEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of bypass table entries. The number of
|
|
entries is given by the value of upsBypassNumLines.(*)"
|
|
::= { upsBypassgen 3 }
|
|
|
|
upsBypassGenEntry OBJECT-TYPE
|
|
SYNTAX UpsBypassGenEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular bypass input.(*)"
|
|
INDEX { upsBypassLineIndexgen }
|
|
::= { upsBypassGenTable 1 }
|
|
|
|
UpsBypassGenEntry ::= SEQUENCE {
|
|
upsBypassLineIndexgen PositiveInteger32,
|
|
upsBypassVoltagegen NonNegativeInteger32,
|
|
upsBypassCurrentgen NonNegativeInteger32,
|
|
upsBypassPowergen NonNegativeInteger32
|
|
}
|
|
|
|
upsBypassLineIndexgen OBJECT-TYPE
|
|
SYNTAX PositiveInteger32
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The bypass line identifier.(*)"
|
|
::= { upsBypassGenEntry 1 }
|
|
|
|
upsBypassVoltagegen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
UNITS "RMS Volts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present bypass voltage.(*)"
|
|
::= { upsBypassGenEntry 2 }
|
|
|
|
upsBypassCurrentgen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
UNITS "0.1 RMS Amp"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present bypass current.(*)"
|
|
::= { upsBypassGenEntry 3 }
|
|
|
|
upsBypassPowergen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
UNITS "Watts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present true power conveyed by the bypass.(*)"
|
|
::= { upsBypassGenEntry 4 }
|
|
|
|
--
|
|
-- The Alarm group generic.
|
|
--
|
|
|
|
upsAlarmsPresentgen OBJECT-TYPE
|
|
SYNTAX Gauge32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present number of active alarm conditions.(*)"
|
|
::= { upsAlarmgen 1 }
|
|
|
|
upsAlarmGenTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsAlarmGenEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of alarm table entries. The table contains
|
|
zero, one, or many rows at any moment, depending upon
|
|
the number of alarm conditions in effect. The table
|
|
is initially empty at agent startup. The agent
|
|
creates a row in the table each time a condition is
|
|
detected and deletes that row when that condition no
|
|
longer pertains. The agent creates the first row with
|
|
upsAlarmId equal to 1, and increments the value of
|
|
upsAlarmId each time a new row is created, wrapping to
|
|
the first free value greater than or equal to 1 when
|
|
the maximum value of upsAlarmId would otherwise be
|
|
exceeded. Consequently, after multiple operations,
|
|
the table may become sparse, e.g., containing entries
|
|
for rows 95, 100, 101, and 203 and the entries should
|
|
not be assumed to be in chronological order because
|
|
upsAlarmId might have wrapped.
|
|
|
|
Alarms are named by an AutonomousType (OBJECT
|
|
IDENTIFIER), upsAlarmDescr, to allow a single table to
|
|
reflect well known alarms plus alarms defined by a
|
|
particular implementation, i.e., as documented in the
|
|
private enterprise MIB definition for the device. No
|
|
two rows will have the same value of upsAlarmDescr,
|
|
since alarms define conditions. In order to meet this
|
|
requirement, care should be taken in the definition of
|
|
alarm conditions to insure that a system cannot enter
|
|
the same condition multiple times simultaneously.
|
|
|
|
The number of rows in the table at any given time is
|
|
reflected by the value of upsAlarmsPresent.(*)"
|
|
::= { upsAlarmgen 2 }
|
|
|
|
upsAlarmGenEntry OBJECT-TYPE
|
|
SYNTAX UpsAlarmGenEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular alarm.(*)"
|
|
INDEX { upsAlarmIdgen }
|
|
::= { upsAlarmGenTable 1 }
|
|
|
|
UpsAlarmGenEntry ::= SEQUENCE {
|
|
upsAlarmIdgen PositiveInteger32,
|
|
upsAlarmDescrgen AutonomousType,
|
|
upsAlarmTimegen TimeStamp
|
|
}
|
|
|
|
upsAlarmIdgen OBJECT-TYPE
|
|
SYNTAX PositiveInteger32
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique identifier for an alarm condition. This
|
|
value must remain constant.(*)"
|
|
::= { upsAlarmGenEntry 1 }
|
|
|
|
upsAlarmDescrgen OBJECT-TYPE
|
|
SYNTAX AutonomousType
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A reference to an alarm description object. The
|
|
object referenced should not be accessible, but rather
|
|
be used to provide a unique description of the alarm
|
|
condition.(*)"
|
|
::= { upsAlarmGenEntry 2 }
|
|
|
|
upsAlarmTimegen OBJECT-TYPE
|
|
SYNTAX TimeStamp
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of sysUpTime when the alarm condition was
|
|
detected. If the alarm condition was detected at the
|
|
time of agent startup and presumably existed before
|
|
agent startup, the value of upsAlarmTime shall equal
|
|
0.(*)"
|
|
::= { upsAlarmGenEntry 3 }
|
|
|
|
--
|
|
-- Well known alarm conditions generic.
|
|
--
|
|
|
|
upsAlarmBatteryBadgen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more batteries have been determined to require
|
|
replacement.(*)"
|
|
::= { upsWellKnownAlarmsgen 1 }
|
|
|
|
upsAlarmOnBatterygen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS is drawing power from the batteries.(*)"
|
|
::= { upsWellKnownAlarmsgen 2 }
|
|
|
|
upsAlarmLowBatterygen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The remaining battery run-time is less than or equal
|
|
to upsConfigLowBattTime.(*)"
|
|
::= { upsWellKnownAlarmsgen 3 }
|
|
|
|
upsAlarmDepletedBatterygen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS will be unable to sustain the present load
|
|
when and if the utility power is lost.(*)"
|
|
::= { upsWellKnownAlarmsgen 4 }
|
|
|
|
upsAlarmTempBadgen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A temperature is out of tolerance.(*)"
|
|
::= { upsWellKnownAlarmsgen 5 }
|
|
|
|
upsAlarmInputBadgen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An input condition is out of tolerance.(*)"
|
|
::= { upsWellKnownAlarmsgen 6 }
|
|
|
|
upsAlarmOutputBadgen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An output condition (other than OutputOverload) is
|
|
out of tolerance.(*)"
|
|
::= { upsWellKnownAlarmsgen 7 }
|
|
|
|
upsAlarmOutputOverloadgen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The output load exceeds the UPS output capacity.(*)"
|
|
::= { upsWellKnownAlarmsgen 8 }
|
|
|
|
upsAlarmOnBypassgen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Bypass is presently engaged on the UPS.(*)"
|
|
::= { upsWellKnownAlarmsgen 9 }
|
|
|
|
upsAlarmBypassBadgen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Bypass is out of tolerance.(*)"
|
|
::= { upsWellKnownAlarmsgen 10 }
|
|
|
|
upsAlarmOutputOffAsRequestedgen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS has shutdown as requested, i.e., the output
|
|
is off.(*)"
|
|
::= { upsWellKnownAlarmsgen 11 }
|
|
|
|
upsAlarmUpsOffAsRequestedgen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The entire UPS has shutdown as commanded.(*)"
|
|
::= { upsWellKnownAlarmsgen 12 }
|
|
|
|
upsAlarmChargerFailedgen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An uncorrected problem has been detected within the
|
|
UPS charger subsystem.(*)"
|
|
::= { upsWellKnownAlarmsgen 13 }
|
|
|
|
upsAlarmUpsOutputOffgen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The output of the UPS is in the off state.(*)"
|
|
::= { upsWellKnownAlarmsgen 14 }
|
|
|
|
upsAlarmUpsSystemOffgen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS system is in the off state.(*)"
|
|
::= { upsWellKnownAlarmsgen 15 }
|
|
|
|
upsAlarmFanFailuregen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The failure of one or more fans in the UPS has been
|
|
detected.(*)"
|
|
::= { upsWellKnownAlarmsgen 16 }
|
|
|
|
upsAlarmFuseFailuregen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The failure of one or more fuses has been detected.(*)"
|
|
::= { upsWellKnownAlarmsgen 17 }
|
|
|
|
upsAlarmGeneralFaultgen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A general fault in the UPS has been detected.(*)"
|
|
::= { upsWellKnownAlarmsgen 18 }
|
|
|
|
upsAlarmDiagnosticTestFailedgen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The result of the last diagnostic test indicates a
|
|
failure.(*)"
|
|
::= { upsWellKnownAlarmsgen 19 }
|
|
|
|
upsAlarmCommunicationsLostgen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A problem has been encountered in the communications
|
|
between the agent and the UPS.(*)"
|
|
::= { upsWellKnownAlarmsgen 20 }
|
|
|
|
upsAlarmAwaitingPowergen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS output is off and the UPS is awaiting the
|
|
return of input power.(*)"
|
|
::= { upsWellKnownAlarmsgen 21 }
|
|
|
|
upsAlarmShutdownPendinggen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A upsShutdownAfterDelay countdown is underway.(*)"
|
|
::= { upsWellKnownAlarmsgen 22 }
|
|
|
|
upsAlarmShutdownImminentgen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS will turn off power to the load in less than
|
|
5 seconds; this may be either a timed shutdown or a
|
|
low battery shutdown.(*)"
|
|
::= { upsWellKnownAlarmsgen 23 }
|
|
|
|
upsAlarmTestInProgressgen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A test is in progress, as initiated and indicated by
|
|
the Test Group. Tests initiated via other
|
|
implementation-specific mechanisms can indicate the
|
|
presence of the testing in the alarm table, if
|
|
desired, via a OBJECT-IDENTITY macro in the MIB
|
|
document specific to that implementation and are
|
|
outside the scope of this OBJECT-IDENTITY.(*)"
|
|
::= { upsWellKnownAlarmsgen 24 }
|
|
|
|
upsAlarmReceptacleOffgen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The receptacle are switch off "
|
|
::= { upsWellKnownAlarmsgen 25 }
|
|
|
|
upsAlarmHighSpeedBusFailuregen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A problem on the High Speed Bus communication is detected"
|
|
::= { upsWellKnownAlarmsgen 26 }
|
|
|
|
upsAlarmHighSpeedBusJACRCFailuregen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A High Speed Bus CRC failure on Bus JA is detected"
|
|
::= { upsWellKnownAlarmsgen 27 }
|
|
|
|
upsAlarmConnectivityBusFailuregen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A problem on the Connectivity Bus communication is detected"
|
|
::= { upsWellKnownAlarmsgen 28 }
|
|
|
|
upsAlarmHighSpeedBusJBCRCFailuregen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A High Speed Bus CRC failure on Bus JB is detected"
|
|
::= { upsWellKnownAlarmsgen 29 }
|
|
|
|
upsAlarmCurrentSharinggen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS detects an high current sharing on the parallel system"
|
|
::= { upsWellKnownAlarmsgen 30 }
|
|
|
|
upsAlarmDCRipplegen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS detects an high ripple voltage on his DC link"
|
|
::= { upsWellKnownAlarmsgen 31 }
|
|
|
|
upsAlarmMaskAgen OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Specifies which alarm can be handled by the UPS.
|
|
The 'Mask' parameter is a Long Integer32. The meaning
|
|
of every bit is the same as for the 'upsAlarmGroupA'
|
|
command. A bit having value=1 indicates that the
|
|
corresponding alarm is handled by the UPS."
|
|
::= { upsAlarmgen 4 }
|
|
|
|
--
|
|
-- The Test Group generic
|
|
--
|
|
|
|
upsTestIdgen OBJECT-TYPE
|
|
SYNTAX OBJECT IDENTIFIER
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The test is named by an OBJECT IDENTIFIER which
|
|
allows a standard mechanism for the initiation of
|
|
tests, including the well known tests identified in
|
|
this document as well as those introduced by a
|
|
particular implementation, i.e., as documented in the
|
|
private enterprise MIB definition for the device.
|
|
|
|
Setting this variable initiates the named test. Sets
|
|
to this variable require the presence of
|
|
upsTestSpinLock in the same SNMP message.
|
|
|
|
The set request will be rejected with an appropriate
|
|
error message if the requested test cannot be
|
|
performed, including attempts to start a test when
|
|
another test is already in progress. The status of
|
|
the current or last test is maintained in
|
|
upsTestResultsSummary. Tests in progress may be
|
|
aborted by setting the upsTestId variable to
|
|
upsTestAbortTestInProgress.
|
|
|
|
Read operations return the value of the name of the
|
|
test in progress if a test is in progress or the name
|
|
of the last test performed if no test is in progress,
|
|
unless no test has been run, in which case the well
|
|
known value upsTestNoTestsInitiated is returned.(*)"
|
|
::= { upsTestgen 1 }
|
|
|
|
-- see [6] for more information on the semantics of objects with
|
|
-- syntax of TestAndIncr
|
|
|
|
upsTestSpinLockgen OBJECT-TYPE
|
|
SYNTAX TestAndIncr
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A spin lock on the test subsystem. The spinlock is
|
|
used as follows.
|
|
|
|
Before starting a test, a manager-station should make
|
|
sure that a test is not in progress as follows:
|
|
|
|
tryagain:
|
|
get (upsTestSpinLock)
|
|
while (upsTestResultsSummary == inProgress) {
|
|
/* loop while a test is running for another
|
|
manager */
|
|
short delay
|
|
get (upsTestSpinLock)
|
|
}
|
|
lockvalue = upsTestSpinLock
|
|
/* no test in progress, start the test */
|
|
set (upsTestSpinLock = lockvalue, upsTestId =
|
|
requestedtest)
|
|
if (errorindex == 1) { /* (upsTestSpinLock
|
|
failed) */
|
|
/* if problem is not access control, then
|
|
some other manager slipped in ahead of us
|
|
*/
|
|
goto tryagain
|
|
}
|
|
if (errorindex == 2) { /* (upsTestId) */
|
|
/* cannot perform the test */
|
|
give up
|
|
}
|
|
/* test started ok */
|
|
/* wait for test completion by polling
|
|
upsTestResultsSummary */
|
|
get (upsTestSpinLock, upsTestResultsSummary,
|
|
upsTestResultsDetail)
|
|
while (upsTestResultsSummary == inProgress) {
|
|
short delay
|
|
get (upsTestSpinLock, upsTestResultsSummary,
|
|
upsTestResultsDetail)
|
|
}
|
|
/* when test completes, retrieve any additional
|
|
test results */
|
|
/* if upsTestSpinLock == lockvalue + 1, then
|
|
these are our test */
|
|
/* results (as opposed to another manager's */
|
|
The initial value of upsTestSpinLock at agent
|
|
initialization shall
|
|
be 1.(*)"
|
|
::= { upsTestgen 2 }
|
|
|
|
upsTestResultsSummarygen OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
donePass(1),
|
|
doneWarning(2),
|
|
doneError(3),
|
|
aborted(4),
|
|
inProgress(5),
|
|
noTestsInitiated(6)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The results of the current or last UPS diagnostics
|
|
test performed. The values for donePass(1),
|
|
doneWarning(2), and doneError(3) indicate that the
|
|
test completed either successfully, with a warning, or
|
|
with an error, respectively. The value aborted(4) is
|
|
returned for tests which are aborted by setting the
|
|
value of upsTestId to upsTestAbortTestInProgress.
|
|
Tests which have not yet concluded are indicated by
|
|
inProgress(5). The value noTestsInitiated(6)
|
|
indicates that no previous test results are available,
|
|
such as is the case when no tests have been run since
|
|
the last reinitialization of the network management
|
|
subsystem and the system has no provision for non-
|
|
volatile storage of test results.(*)"
|
|
::= { upsTestgen 3 }
|
|
|
|
upsTestResultsDetailgen OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Additional information about upsTestResultsSummary.
|
|
If no additional information available, a zero length
|
|
string is returned.(*)"
|
|
::= { upsTestgen 4 }
|
|
|
|
upsTestStartTimegen OBJECT-TYPE
|
|
SYNTAX TimeStamp
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of sysUpTime at the time the test in
|
|
progress was initiated, or, if no test is in progress,
|
|
the time the previous test was initiated. If the
|
|
value of upsTestResultsSummary is noTestsInitiated(6),
|
|
upsTestStartTime has the value 0.(*)"
|
|
::= { upsTestgen 5 }
|
|
|
|
upsTestElapsedTimegen OBJECT-TYPE
|
|
SYNTAX TimeInterval
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The amount of time, in TimeTicks, since the test in
|
|
progress was initiated, or, if no test is in progress,
|
|
the previous test took to complete. If the value of
|
|
upsTestResultsSummary is noTestsInitiated(6),
|
|
upsTestElapsedTime has the value 0.(*)"
|
|
::= { upsTestgen 6 }
|
|
|
|
--
|
|
-- Well known tests generic.
|
|
--
|
|
|
|
upsTestNoTestsInitiatedgen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"No tests have been initiated and no test is in
|
|
progress.(*)"
|
|
::= { upsWellKnownTestsgen 1 }
|
|
|
|
upsTestAbortTestInProgressgen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The test in progress is to be aborted / the test in
|
|
progress was aborted.(*)"
|
|
::= { upsWellKnownTestsgen 2 }
|
|
|
|
upsTestGeneralSystemsTestgen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The manufacturer's standard test of UPS device
|
|
systems.(*)"
|
|
::= { upsWellKnownTestsgen 3 }
|
|
|
|
upsTestQuickBatteryTestgen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A test that is sufficient to determine if the battery
|
|
needs replacement.(*)"
|
|
::= { upsWellKnownTestsgen 4 }
|
|
|
|
upsTestDeepBatteryCalibrationgen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system is placed on battery to a discharge level,
|
|
set by the manufacturer, sufficient to determine
|
|
battery replacement and battery run-time with a high
|
|
degree of confidence. WARNING: this test will leave
|
|
the battery in a low charge state and will require
|
|
time for recharging to a level sufficient to provide
|
|
normal battery duration for the protected load.(*)"
|
|
::= { upsWellKnownTestsgen 5 }
|
|
|
|
--
|
|
-- The Control group generic.
|
|
--
|
|
|
|
upsShutdownTypegen OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
output(1),
|
|
system(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This object determines the nature of the action to be
|
|
taken at the time when the countdown of the
|
|
upsShutdownAfterDelay and upsRebootWithDuration
|
|
objects reaches zero.
|
|
|
|
Setting this object to output(1) indicates that
|
|
shutdown requests should cause only the output of the
|
|
UPS to turn off. Setting this object to system(2)
|
|
indicates that shutdown requests will cause the entire
|
|
UPS system to turn off.(*)"
|
|
::= { upsControlgen 1 }
|
|
|
|
upsShutdownAfterDelaygen OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..2147483647)
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this object will shutdown (i.e., turn off)
|
|
either the UPS output or the UPS system (as determined
|
|
by the value of upsShutdownType at the time of
|
|
shutdown) after the indicated number of seconds, or
|
|
less if the UPS batteries become depleted. Setting
|
|
this object to 0 will cause the shutdown to occur
|
|
immediately. Setting this object to -1 will abort the
|
|
countdown. If the system is already in the desired
|
|
state at the time the countdown reaches 0, then
|
|
nothing will happen. That is, there is no additional
|
|
action at that time if upsShutdownType = system and
|
|
the system is already off. Similarly, there is no
|
|
additional action at that time if upsShutdownType =
|
|
output and the output is already off. When read,
|
|
upsShutdownAfterDelay will return the number of
|
|
seconds remaining until shutdown, or -1 if no shutdown
|
|
countdown is in effect. On some systems, if the agent
|
|
is restarted while a shutdown countdown is in effect,
|
|
the countdown may be aborted. Sets to this object
|
|
override any upsShutdownAfterDelay already in effect.(*)"
|
|
::= { upsControlgen 2 }
|
|
|
|
upsStartupAfterDelaygen OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..2147483647)
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this object will start the output after the
|
|
indicated number of seconds, including starting the
|
|
UPS, if necessary. Setting this object to 0 will
|
|
cause the startup to occur immediately. Setting this
|
|
object to -1 will abort the countdown. If the output
|
|
is already on at the time the countdown reaches 0,
|
|
then nothing will happen. Sets to this object
|
|
override the effect of any upsStartupAfterDelay
|
|
countdown or upsRebootWithDuration countdown in
|
|
progress. When read, upsStartupAfterDelay will return
|
|
the number of seconds until startup, or -1 if no
|
|
startup countdown is in effect. If the countdown
|
|
expires during a utility failure, the startup shall
|
|
not occur until the utility power is restored. On
|
|
some systems, if the agent is restarted while a
|
|
startup countdown is in effect, the countdown is
|
|
aborted.(*)"
|
|
::= { upsControlgen 3 }
|
|
|
|
upsRebootWithDurationgen OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..300)
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this object will immediately shutdown (i.e.,
|
|
turn off) either the UPS output or the UPS system (as
|
|
determined by the value of upsShutdownType at the time
|
|
of shutdown) for a period equal to the indicated
|
|
number of seconds, after which time the output will be
|
|
started, including starting the UPS, if necessary. If
|
|
the number of seconds required to perform the request
|
|
is greater than the requested duration, then the
|
|
requested shutdown and startup cycle shall be
|
|
performed in the minimum time possible, but in no case
|
|
shall this require more than the requested duration
|
|
plus 60 seconds. When read, upsRebootWithDuration
|
|
shall return the number of seconds remaining in the
|
|
countdown, or -1 if no countdown is in progress. If
|
|
the startup should occur during a utility failure, the
|
|
startup shall not occur until the utility power is
|
|
restored.(*)"
|
|
::= { upsControlgen 4 }
|
|
|
|
upsAutoRestartgen OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on(1),
|
|
off(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this object to 'on' will cause the UPS system
|
|
to restart after a shutdown if the shutdown occurred
|
|
during a power loss as a result of either a
|
|
upsShutdownAfterDelay or an internal battery depleted
|
|
condition. Setting this object to 'off' will prevent
|
|
the UPS system from restarting after a shutdown until
|
|
an operator manually or remotely explicitly restarts
|
|
it. If the UPS is in a startup or reboot countdown,
|
|
then the UPS will not restart until that delay has
|
|
been satisfied.(*)"
|
|
::= { upsControlgen 5 }
|
|
|
|
upsReceptaclesNumgen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of receptacles utilized in this device.
|
|
This entry indicates the number of rows in the receptacle
|
|
table."
|
|
::= { upsControlgen 6 }
|
|
|
|
upsReceptacleGenTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsReceptacleGenEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of receptacle table entries. The number of
|
|
entries is given by the value of upsReceptacleNum."
|
|
::= { upsControlgen 7 }
|
|
|
|
upsReceptacleGenEntry OBJECT-TYPE
|
|
SYNTAX UpsReceptacleGenEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular receptacle."
|
|
INDEX { upsReceptacleLineIndexgen }
|
|
::= { upsReceptacleGenTable 1 }
|
|
|
|
UpsReceptacleGenEntry ::= SEQUENCE {
|
|
upsReceptacleLineIndexgen PositiveInteger32,
|
|
upsReceptacleOnOffgen INTEGER
|
|
}
|
|
|
|
upsReceptacleLineIndexgen OBJECT-TYPE
|
|
SYNTAX PositiveInteger32
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The receptacle line identifier."
|
|
::= { upsReceptacleGenEntry 1 }
|
|
|
|
upsReceptacleOnOffgen OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on(1),
|
|
off(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present state of the receptacle. Setting this
|
|
object to 'on' will cause the receptacle to be turned
|
|
on. Setting this object to 'off' will turn the
|
|
receptacle off. If the receptacle is already in the
|
|
desired state nothing will happen. After an
|
|
autorestart (see upsAutoRestart) the receptacle will
|
|
be on."
|
|
::= { upsReceptacleGenEntry 2 }
|
|
|
|
upsUPSModegen OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
offLine(1),
|
|
onLine(2),
|
|
ecomode(3),
|
|
iem(4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The operation mode off the UPS. Off-line indicates a
|
|
mode in which the input power is transferred to the
|
|
output directly or via a step-up or step-down
|
|
transformer. On-line mode indicates a mode in which
|
|
the output power is regenerated through some convertor.
|
|
the operating mode of the UPS may be fixed, or may be
|
|
selectable (e.g. an on-line UPS with ecomode)"
|
|
::= { upsControlgen 8 }
|
|
|
|
upsRectifierOnOffgen OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on(1),
|
|
off(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present state of the rectifier. Setting this
|
|
object to 'on' will cause the rectifier to be turned
|
|
on. Setting this object to 'off' will turn the
|
|
rectifier off. If the rectifier is already in the
|
|
desired state nothing will happen. "
|
|
::= { upsControlgen 9 }
|
|
|
|
upsBatteryChargeMethodgen OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normalcharge(1),
|
|
boostcharge(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present state of the charge method. Setting this
|
|
object to 'Normal charge' will cause the battery to be
|
|
charged using the normal method. Setting this object to
|
|
'Boost charge' will charge the battery in boost mode.
|
|
If the charge method is already in the desired state
|
|
nothing will happen. "
|
|
::= { upsControlgen 10 }
|
|
|
|
upsInverterOnOffgen OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on(1),
|
|
off(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present state of the inverter. Setting this
|
|
object to 'on' will cause the inverter to be turned
|
|
on. Setting this object to 'off' will turn the
|
|
inverter off. If the inverter is already in the
|
|
desired state nothing will happen. "
|
|
::= { upsControlgen 11 }
|
|
|
|
upsBypassOnOffgen OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on(1),
|
|
off(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present state of the bypass. Setting this
|
|
object to 'on' will cause the bypass to be activated.
|
|
Setting this object to 'off' will deactivate the
|
|
bypass. If the UPS is already in the
|
|
desired state nothing will happen. "
|
|
::= { upsControlgen 12 }
|
|
|
|
upsLoadSourcegen OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
onbypass(1),
|
|
onInverter(2),
|
|
onDetour(3),
|
|
loadOff(4),
|
|
other (5)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present source of the load. Setting this
|
|
object to 'On bypass' will cause the load to be
|
|
supplied by the bypass.
|
|
Setting this object to 'On inverter' will cause the
|
|
load to be supplied by the inverter.
|
|
If the load is already supplied by the desired
|
|
source nothing will happen. "
|
|
::= { upsControlgen 13 }
|
|
|
|
--
|
|
-- The Configuration group generic.
|
|
--
|
|
|
|
upsConfigInputVoltagegen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
UNITS "RMS Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The magnitude of the nominal input voltage. On those
|
|
systems which support read-write access to this
|
|
object, if there is an attempt to set this variable to
|
|
a value that is not supported, the request must be
|
|
rejected and the agent shall respond with an
|
|
appropriate error message, i.e., badValue for SNMPv1,
|
|
or inconsistentValue for SNMPv2.(*)"
|
|
::= { upsConfiggen 1 }
|
|
|
|
upsConfigInputFreqgen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
UNITS "0.1 Hertz"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The nominal input frequency. On those systems which
|
|
support read-write access to this object, if there is
|
|
an attempt to set this variable to a value that is not
|
|
supported, the request must be rejected and the agent
|
|
shall respond with an appropriate error message, i.e.,
|
|
badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)"
|
|
::= { upsConfiggen 2 }
|
|
|
|
upsConfigOutputVoltagegen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
UNITS "RMS Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The magnitude of the nominal output voltage. On
|
|
those systems which support read-write access to this
|
|
object, if there is an attempt to set this variable to
|
|
a value that is not supported, the request must be
|
|
rejected and the agent shall respond with an
|
|
appropriate error message, i.e., badValue for SNMPv1,
|
|
or inconsistentValue for SNMPv2.(*)"
|
|
::= { upsConfiggen 3 }
|
|
|
|
upsConfigOutputFreqgen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
UNITS "0.1 Hertz"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The nominal output frequency. On those systems which
|
|
support read-write access to this object, if there is
|
|
an attempt to set this variable to a value that is not
|
|
supported, the request must be rejected and the agent
|
|
shall respond with an appropriate error message, i.e.,
|
|
badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)"
|
|
::= { upsConfiggen 4 }
|
|
|
|
upsConfigOutputVAgen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
UNITS "Volt-Amps"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The magnitude of the nominal Volt-Amp rating.(*)"
|
|
::= { upsConfiggen 5 }
|
|
|
|
upsConfigOutputPowergen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
UNITS "Watts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The magnitude of the nominal true power rating.(*)"
|
|
::= { upsConfiggen 6 }
|
|
|
|
upsConfigLowBattTimegen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
UNITS "minutes"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of upsEstimatedMinutesRemaining at which a
|
|
lowBattery condition is declared. For agents which
|
|
support only discrete (discontinuous) values, then the
|
|
agent shall round up to the next supported value. If
|
|
the requested value is larger than the largest
|
|
supported value, then the largest supported value
|
|
shall be selected.(*)"
|
|
::= { upsConfiggen 7 }
|
|
|
|
upsConfigAudibleStatusgen OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(1),
|
|
enabled(2),
|
|
muted(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The requested state of the audible alarm. When in
|
|
the disabled state, the audible alarm should never
|
|
sound. The enabled state is self-describing. Setting
|
|
this object to muted(3) when the audible alarm is
|
|
sounding shall temporarily silence the alarm. It will
|
|
remain muted until it would normally stop sounding and
|
|
the value returned for read operations during this
|
|
period shall equal muted(3). At the end of this
|
|
period, the value shall revert to enabled(2). Writes
|
|
of the value muted(3) when the audible alarm is not
|
|
sounding shall be accepted but otherwise shall have no
|
|
effect.(*)"
|
|
::= { upsConfiggen 8 }
|
|
|
|
upsConfigLowVoltageTransferPointgen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
UNITS "RMS Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The minimum input line voltage allowed before the UPS
|
|
system transfers to battery backup.(*)"
|
|
::= { upsConfiggen 9 }
|
|
|
|
upsConfigHighVoltageTransferPointgen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
UNITS "RMS Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The maximum line voltage allowed before the UPS
|
|
system transfers to battery backup.(*)"
|
|
::= { upsConfiggen 10 }
|
|
|
|
upsConfigBatteryCapacitygen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
UNITS "Amps Hours"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The installed battery capacity. This value is the 'factory'-value,
|
|
not the value after calibration."
|
|
::= { upsConfiggen 11 }
|
|
|
|
upsConfigBatteryChargeCurrentgen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
UNITS "0.1 Amp DC"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The maximum battery charge current, including external chargers."
|
|
::= { upsConfiggen 12 }
|
|
|
|
upsConfigNoLoadShutdowngen OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(1),
|
|
enabled(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Dis- or enable 'no load' shutdown from the contact interface."
|
|
::= { upsConfiggen 13 }
|
|
|
|
upsConfigStartDelaygen OBJECT-TYPE
|
|
SYNTAX PositiveInteger32
|
|
UNITS "minutes"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Minimum required autonomy time before the UPS may perform an
|
|
autorestart."
|
|
::= { upsConfiggen 14 }
|
|
|
|
--
|
|
-- The GetSet group generic.
|
|
--
|
|
|
|
upsEventGetNextgen OBJECT-TYPE
|
|
SYNTAX PositiveInteger32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of events to retreive from the UPS event buffer.
|
|
When this object is set the EventTable will be filled with the
|
|
requested number of entries. The value upsEventSetStartingTimeStamp
|
|
will be used as the start value of the table with the lowest index number."
|
|
::= { upsGetSetgen 1 }
|
|
|
|
upsEventGetPreviousgen OBJECT-TYPE
|
|
SYNTAX PositiveInteger32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of events to retreive from the UPS event buffer.
|
|
When this object is set the EventTable will be filled with the
|
|
requested number of entries. The value upsEventLastTime will
|
|
be used as the last value of the table with the highest index number.
|
|
|
|
Returns SNMPNOSUCHNAME for UPSs that don't support this command."
|
|
::= { upsGetSetgen 2 }
|
|
|
|
upsEventSetStartingTimeStampgen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The timestamp which is used as starting point for downloading
|
|
events from the UPS event buffer"
|
|
::= { upsGetSetgen 3 }
|
|
|
|
upsEventRetreiveCurrentTimeStampgen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current timestamp is retreived from the UPS"
|
|
::= { upsGetSetgen 4 }
|
|
|
|
upsEventTableSizegen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of entries in the event table.
|
|
This object indicates the number of rows in the event table."
|
|
::= { upsGetSetgen 5 }
|
|
|
|
upsEventGenTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsEventGenEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of event table entries. The number of entries is always
|
|
10, and the value of upsEventTableSize gives the number of valid
|
|
entries from the begging of the table. Invalid entries return 0.
|
|
|
|
To prevent problems with simultaneous queries from several agents,
|
|
these values MUST be accessed using several PDUs in the
|
|
same SNMP message (<number> is (1..10)):
|
|
|
|
PDU-SET upsSetStartingTimeStamp <time>
|
|
PDU-SET upsEventGetNext <number>
|
|
PDU-GET upsEventTableSize
|
|
PDU-GET upsEventCode,upsEventStatus,upsEventTime 1
|
|
PDU-GET upsEventCode,upsEventStatus,upsEventTime 2
|
|
..
|
|
PDU-GET upsEventCode,upsEventStatus,upsEventTime <number>
|
|
|
|
The table is read up to requested number of events and the
|
|
management software afterwards decides which entries are
|
|
valid, as indicated by the upsEventTableSize.
|
|
"
|
|
::= { upsGetSetgen 6 }
|
|
|
|
upsEventGenEntry OBJECT-TYPE
|
|
SYNTAX UpsEventGenEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular event."
|
|
INDEX { upsEventLineIndexgen }
|
|
::= { upsEventGenTable 1 }
|
|
|
|
UpsEventGenEntry ::= SEQUENCE {
|
|
upsEventLineIndexgen PositiveInteger32,
|
|
upsEventCodegen Integer32,
|
|
upsEventStatusgen NonNegativeInteger32,
|
|
upsEventTimegen NonNegativeInteger32
|
|
}
|
|
|
|
upsEventLineIndexgen OBJECT-TYPE
|
|
SYNTAX PositiveInteger32
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The event line identifier."
|
|
::= { upsEventGenEntry 1 }
|
|
|
|
upsEventCodegen OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The event code in numerical format."
|
|
::= { upsEventGenEntry 2 }
|
|
|
|
upsEventStatusgen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The status of the UPS at the moment that the event was generated.
|
|
The format is specified at the 'upsStatus' command.
|
|
If the UPS is not able to deliver status information, then
|
|
SNMPNOSUCHNAME is returned."
|
|
::= { upsEventGenEntry 3 }
|
|
|
|
upsEventTimegen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The timestamp of the moment the event was generated."
|
|
::= { upsEventGenEntry 4 }
|
|
|
|
upsParametersReadgen OBJECT-TYPE
|
|
SYNTAX PositiveInteger32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of parameters to retreive from the UPS.
|
|
When this object is set the ParameterTable will be filled with the
|
|
requested number of entries. The value upsParametersStartAddress
|
|
will be used as the start value of the table with the lowest index
|
|
number."
|
|
::= { upsGetSetgen 7 }
|
|
|
|
upsParametersWritegen OBJECT-TYPE
|
|
SYNTAX PositiveInteger32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of parameters to write to the UPS.
|
|
When this object is set the ParameterTable will be send to the ups.
|
|
The value upsParametersStartAddress will be used for the first value
|
|
of the table with the lowest index number."
|
|
::= { upsGetSetgen 8 }
|
|
|
|
upsParametersStartAddressgen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The address which is used as starting point for downloading
|
|
parameters from the UPS"
|
|
::= { upsGetSetgen 9 }
|
|
|
|
upsParameterTableSizegen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of entries in the parameter table.
|
|
This object indicates the number of rows in the parameter table."
|
|
::= { upsGetSetgen 10 }
|
|
|
|
upsParameterGenTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsParameterGenEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of parameter entries. The number of entries is always
|
|
16, and the value of upsParameterTableSize gives the number of valid
|
|
entries from the begging of the table. Invalid entries return 0.
|
|
|
|
To prevent problems with simultaneous queries from several agents,
|
|
these values MUST be accessed using several PDUs in the
|
|
same SNMP message (<number> is (1..16)):
|
|
|
|
Read sequence:
|
|
|
|
PDU-SET upsSetStartingAddress <addr>
|
|
PDU-SET upsParametersRead <number>
|
|
PDU-GET upsParameterTableSize
|
|
PDU-GET upsParameterValue 1
|
|
PDU-GET upsParameterValue 2
|
|
..
|
|
PDU-GET upsParameterValue <number>
|
|
|
|
The table is read up to requested number of events and the
|
|
management software afterwards decides which entries are
|
|
valid, as indicated by the upsParameterTableSize.
|
|
|
|
Write sequence:
|
|
|
|
PDU-SET upsSetStartingAddress <addr>
|
|
PDU-SET upsParameterValue 1
|
|
PDU-SET upsParameterValue 2
|
|
..
|
|
PDU-SET upsParameterValue <number>
|
|
PDU-SET upsParametersWrite <number>
|
|
"
|
|
::= { upsGetSetgen 11 }
|
|
|
|
upsParameterGenEntry OBJECT-TYPE
|
|
SYNTAX UpsParameterGenEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular parameter."
|
|
INDEX { upsParameterLineIndexgen }
|
|
::= { upsParameterGenTable 1 }
|
|
|
|
UpsParameterGenEntry ::= SEQUENCE {
|
|
upsParameterLineIndexgen PositiveInteger32,
|
|
upsParameterValuegen Integer32
|
|
}
|
|
|
|
upsParameterLineIndexgen OBJECT-TYPE
|
|
SYNTAX PositiveInteger32
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The parameter line identifier."
|
|
::= { upsParameterGenEntry 1 }
|
|
|
|
upsParameterValuegen OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The parameter value in numerical format."
|
|
::= { upsParameterGenEntry 2 }
|
|
|
|
upsStatusgen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The global UPS status is returned. Every bit reflects a specific
|
|
status condition. Unused bits returns as 0. The status value can
|
|
also be found on other commands. The value SNMPNOSUCHNAME means
|
|
'invalid status' or 'status value non available'.
|
|
|
|
Status
|
|
1 0000 0001h upsStatusEcomodeIsOn
|
|
2 0000 0002h upsStatusBatteryIsCharging
|
|
4 0000 0004h upsStatusBatteryIsDischarging
|
|
8 0000 0008h upsStatusAlarmIsActive
|
|
16 0000 0010h upsStatusRectifierIsOn
|
|
32 0000 0020h upsStatusLowBattery
|
|
64 0000 0040h upsStatusOnBypass
|
|
128 0000 0080h upsStatusMainsBypassOK
|
|
256 0000 0100h upsStatusMainsRectifierOK
|
|
512 0000 0200h upsStatusDetourIsOn
|
|
1024 0000 0400h upsStatusAcousticAlarmIsOn
|
|
2048 0000 0800h upsStatusGlobalServiceCheck
|
|
4096 0000 1000h upsStatusInverterIsOn
|
|
8192 0000 2000h upsStatusNotInParallel (Q1 open)
|
|
16384 0000 4000h upsStatusResetLoadOff
|
|
32768 0000 8000h upsStatusLoadOff
|
|
65536 0001 0000h upsStatusBoostMode
|
|
131072 0002 0000h upsStatusBuckMode
|
|
262144 0004 0000h upsStatusIemModeIsOn
|
|
524288 0008 0000h upsStatus5thFilterIsOn
|
|
1048576 0010 0000h upsStatus11thFilterIsOn
|
|
2097152 0020 0000h upsStatus2ndRectifierBridgeIsOn
|
|
4194304 0040 0000h - reserved -
|
|
8388608 0080 0000h - reserved -
|
|
16777216 0100 0000h - reserved -
|
|
33554432 0200 0000h - reserved -
|
|
67108864 0400 0000h - reserved -
|
|
134217728 0800 0000h - reserved -
|
|
268435456 1000 0000h upsGlobalParallelValues "
|
|
::= { upsGetSetgen 12 }
|
|
|
|
upsMainsStatisticsMBfailgen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Count of main bypass failures (>200 ms), since UPS installation."
|
|
::= { upsGetSetgen 13 }
|
|
|
|
upsMainsStatisticsMRfailgen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Count of mains rectifier failures (>200 ms), since UPS installation."
|
|
::= { upsGetSetgen 14 }
|
|
|
|
upsMainsStatisticsB2gen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Count of transients on the mains bypass (0..2 ms), during the last 7 days."
|
|
::= { upsGetSetgen 15 }
|
|
|
|
upsMainsStatisticsB5gen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Count of transients on the mains bypass (2..5 ms), during the last 7 days."
|
|
::= { upsGetSetgen 16 }
|
|
|
|
upsMainsStatisticsB10gen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Count of transients on the mains bypass (5..10 ms), during the last 7 days."
|
|
::= { upsGetSetgen 17 }
|
|
|
|
upsMainsStatisticsB200gen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Count of transients on the mains bypass (10..200 ms), during the last 7 days."
|
|
::= { upsGetSetgen 18 }
|
|
|
|
upsMainsStatisticsBypRelgen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Bypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'."
|
|
::= { upsGetSetgen 19 }
|
|
|
|
upsTimegen OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current timestamp (or real-time) of the UPS. For the format,
|
|
see 'Timestamp' specifications. The write-command has to comply with the
|
|
correct timestamp format expected by the UPS (counter value or real-time-clock
|
|
value). Missing to doing so will result in a SNMPgenERROR,
|
|
meaning 'command not supported'. It is possible to know which is the timestamp
|
|
format supported by the UPS, by issuing a read-command or by reading events,
|
|
which includes timestamps."
|
|
::= { upsGetSetgen 20 }
|
|
|
|
upsRequestPermissiongen OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An encrypted code is send to enable use of restricted write objects during
|
|
a limited period of time."
|
|
::= { upsGetSetgen 21 }
|
|
|
|
upsEventGetCodegen OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The code which is used as starting point to downloading the events from the
|
|
UPS event buffer."
|
|
::= { upsGetSetgen 22 }
|
|
|
|
upsEventSpinLockgen OBJECT-TYPE
|
|
SYNTAX TestAndIncr
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A spin lock on the event subsystem. "
|
|
|
|
::= { upsGetSetgen 23 }
|
|
|
|
upsParameterSpinLockgen OBJECT-TYPE
|
|
SYNTAX TestAndIncr
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A spin lock on the parameters subsystem. "
|
|
|
|
::= { upsGetSetgen 24 }
|
|
|
|
|
|
---
|
|
--- GE Trap group generic
|
|
---
|
|
|
|
upsTrapAlarmBatteryBadgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more batteries have been determined to require
|
|
replacement."
|
|
::= { geUPSTrapsgen 1 }
|
|
|
|
upsTrapAlarmOnBatterygen NOTIFICATION-TYPE
|
|
OBJECTS { upsSecondsOnBatterygen }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS is drawing power from the batteries."
|
|
::= { geUPSTrapsgen 2 }
|
|
|
|
upsTrapAlarmLowBatterygen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The remaining battery run-time is less than or equal
|
|
to upsConfigLowBattTime."
|
|
::= { geUPSTrapsgen 3 }
|
|
|
|
upsTrapAlarmDepletedBatterygen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS will be unable to sustain the present load
|
|
when and if the utility power is lost)"
|
|
::= { geUPSTrapsgen 4 }
|
|
|
|
upsTrapAlarmTempBadgen NOTIFICATION-TYPE
|
|
OBJECTS { upsBatteryTemperaturegen }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A temperature is out of tolerance."
|
|
::= { geUPSTrapsgen 5 }
|
|
|
|
upsTrapAlarmInputBadgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An input condition is out of tolerance."
|
|
::= { geUPSTrapsgen 6 }
|
|
|
|
upsTrapAlarmOutputBadgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An output condition (other than OutputOverload) is
|
|
out of tolerance."
|
|
::= { geUPSTrapsgen 7 }
|
|
|
|
upsTrapAlarmOutputOverloadgen NOTIFICATION-TYPE
|
|
OBJECTS { upsOutputNumLinesgen, upsOutputPercentLoadgen }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The output load exceeds the UPS output capacity."
|
|
::= { geUPSTrapsgen 8 }
|
|
|
|
upsTrapAlarmOnBypassgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Bypass is presently engaged on the UPS."
|
|
::= { geUPSTrapsgen 9 }
|
|
|
|
upsTrapAlarmBypassBadgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Bypass is out of tolerance."
|
|
::= { geUPSTrapsgen 10 }
|
|
|
|
upsTrapAlarmOutputOffAsRequestedgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS has shutdown as requested, i.e., the output
|
|
is off."
|
|
::= { geUPSTrapsgen 11 }
|
|
|
|
upsTrapAlarmUpsOffAsRequestedgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The entire UPS has shutdown as commanded."
|
|
::= { geUPSTrapsgen 12 }
|
|
|
|
upsTrapAlarmChargerFailedgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An uncorrected problem has been detected within the
|
|
UPS charger subsystem."
|
|
::= { geUPSTrapsgen 13 }
|
|
|
|
upsTrapAlarmUpsOutputOffgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The output of the UPS is in the off state."
|
|
::= { geUPSTrapsgen 14 }
|
|
|
|
upsTrapAlarmUpsSystemOffgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS system is in the off state."
|
|
::= { geUPSTrapsgen 15 }
|
|
|
|
upsTrapAlarmFanFailuregen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The failure of one or more fans in the UPS has been
|
|
detected."
|
|
::= { geUPSTrapsgen 16 }
|
|
|
|
upsTrapAlarmFuseFailuregen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The failure of one or more fuses has been detected."
|
|
::= { geUPSTrapsgen 17 }
|
|
|
|
upsTrapAlarmGeneralFaultgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A general fault in the UPS has been detected."
|
|
::= { geUPSTrapsgen 18 }
|
|
|
|
upsTrapAlarmDiagnosticTestFailedgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The result of the last diagnostic test indicates a
|
|
failure."
|
|
::= { geUPSTrapsgen 19 }
|
|
|
|
upsTrapAlarmCommunicationsLostgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A problem has been encountered in the communication
|
|
between the agent and the UPS."
|
|
::= { geUPSTrapsgen 20 }
|
|
|
|
upsTrapAlarmAwaitingPowergen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS output is off and the UPS is awaiting the
|
|
return of the input power (*)."
|
|
::= { geUPSTrapsgen 21 }
|
|
|
|
upsTrapAlarmShutdownPendinggen NOTIFICATION-TYPE
|
|
OBJECTS { upsShutdownAfterDelaygen }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A upsShutdownAfterDelay countdown is underway."
|
|
::= { geUPSTrapsgen 22 }
|
|
|
|
upsTrapAlarmShutdownImminentgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS will turn off power to the load in less than
|
|
5 seconds; this may be either a timed shutdown or a
|
|
low battery shutdown."
|
|
::= { geUPSTrapsgen 23 }
|
|
|
|
upsTrapAlarmTestInProgressgen NOTIFICATION-TYPE
|
|
OBJECTS { upsTestIdgen }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A test is in progress, as initiated and indicated by
|
|
the Test Group. Tests initiated via other
|
|
implementation-specific mechanisms can indicate the
|
|
presence of the testing in the alarm table, if
|
|
desired, via a OBJECT-IDENTITY macro in the MIB
|
|
document specific to that implementation and are
|
|
outside the scope of this OBJECT-IDENTITY."
|
|
::= { geUPSTrapsgen 24 }
|
|
|
|
upsTrapAlarmReceptacleOffgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A receptacle has been switched off."
|
|
::= { geUPSTrapsgen 25 }
|
|
|
|
upsTrapAlarmHighspeedBusFailuregen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A problem on the Highspeed Bus communication is detected."
|
|
::= { geUPSTrapsgen 26 }
|
|
|
|
upsTrapAlarmHighspeedBusJACRCFailuregen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A CRC failure on the Highspeed Bus JA is detected."
|
|
::= { geUPSTrapsgen 27 }
|
|
|
|
upsTrapAlarmConnectivityBusFailuregen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A Connectivity Bus failure is detected"
|
|
::= { geUPSTrapsgen 28 }
|
|
|
|
upsTrapAlarmHighspeedBusJBCRCFailuregen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A CRC failure on the Highspeed Bus JB is detected."
|
|
::= { geUPSTrapsgen 29 }
|
|
|
|
upsTrapAlarmCurrentSharingFailuregen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An high current sharing on the parallel system is detected."
|
|
::= { geUPSTrapsgen 30 }
|
|
|
|
upsTrapAlarmDCRippleFailuregen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An high ripple voltage on his DC link is detected."
|
|
::= { geUPSTrapsgen 31 }
|
|
|
|
upsTrapAlarmBatteryBadRestoredgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A Battery bad condition is restored."
|
|
::= { geUPSTrapsgen 33 }
|
|
|
|
upsTrapAlarmOnBatteryRestoredgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS is drawing power from mains again."
|
|
::= { geUPSTrapsgen 34 }
|
|
|
|
upsTrapAlarmLowBatteryRestoredgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A Low Battery condition is restored."
|
|
::= { geUPSTrapsgen 35 }
|
|
|
|
upsTrapAlarmDepletedBatteryRestoredgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A Depleted Battery condition is restored."
|
|
::= { geUPSTrapsgen 36 }
|
|
|
|
upsTrapAlarmTempBadRestoredgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A bad temperature condition is restored."
|
|
::= { geUPSTrapsgen 37 }
|
|
|
|
upsTrapAlarmInputBadRestoredgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An input bad condition is restored."
|
|
::= { geUPSTrapsgen 38 }
|
|
|
|
upsTrapAlarmOutputBadRestoredgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An output bad condition is restored."
|
|
::= { geUPSTrapsgen 39 }
|
|
|
|
upsTrapAlarmOutputOverloadRestoredgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An output overload condition is restored."
|
|
::= { geUPSTrapsgen 40 }
|
|
|
|
upsTrapAlarmOnBypassRestoredgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An On Bypass condition is restored."
|
|
::= { geUPSTrapsgen 41 }
|
|
|
|
upsTrapAlarmBypassBadRestoredgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A Bypass bad condition is restored."
|
|
::= { geUPSTrapsgen 42 }
|
|
|
|
upsTrapAlarmOutputOffAsRequestedRestoredgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A request shutdown has been restored."
|
|
::= { geUPSTrapsgen 43 }
|
|
|
|
upsTrapAlarmUpsOffAsRequestedRestoredgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A entire UPS command has been restored."
|
|
::= { geUPSTrapsgen 44 }
|
|
|
|
upsTrapAlarmChargerFailedRestoredgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A Charger Failer condition is restored."
|
|
::= { geUPSTrapsgen 45 }
|
|
|
|
upsTrapAlarmUpsOutputOngen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The output of the UPS switched in the on state."
|
|
::= { geUPSTrapsgen 46 }
|
|
|
|
upsTrapAlarmUpsSystemOngen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS system is switched in the on state."
|
|
::= { geUPSTrapsgen 47 }
|
|
|
|
upsTrapAlarmFanFailureRestoredgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A Fan failure condition is restored."
|
|
::= { geUPSTrapsgen 48 }
|
|
|
|
upsTrapAlarmFuseFailureRestoredgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A Fuse failure condition is restored."
|
|
::= { geUPSTrapsgen 49 }
|
|
|
|
upsTrapAlarmGeneralFaultRestoredgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A general fault is restored."
|
|
::= { geUPSTrapsgen 50 }
|
|
|
|
upsTrapAlarmDiagnosticTestFailedRestoredgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A last diagnostic test indicates a failure is
|
|
restored."
|
|
::= { geUPSTrapsgen 51 }
|
|
|
|
upsTrapAlarmCommunicationsLostRestoredgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A problem in the communication between the agent
|
|
and the UPS is restored."
|
|
::= { geUPSTrapsgen 52 }
|
|
|
|
upsTrapAlarmAwaitingPowerRestoredgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A awaiting power condition is restored (*)."
|
|
::= { geUPSTrapsgen 53 }
|
|
|
|
upsTrapAlarmShutdownPendingRestoredgen NOTIFICATION-TYPE
|
|
OBJECTS { upsShutdownAfterDelaygen }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A upsShutdownAfterDelay countdown is restored."
|
|
::= { geUPSTrapsgen 54 }
|
|
|
|
upsTrapAlarmShutdownImminentRestoredgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A shutdown imminent condition is restored."
|
|
::= { geUPSTrapsgen 55 }
|
|
|
|
upsTrapAlarmTestInProgressRestoredgen NOTIFICATION-TYPE
|
|
OBJECTS { upsTestIdgen }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The test is in progress is terminated."
|
|
::= { geUPSTrapsgen 56 }
|
|
|
|
upsTrapAlarmReceptacleOn NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A receptacle has been switched on."
|
|
::= { geUPSTrapsgen 57 }
|
|
|
|
upsTrapAlarmHighspeedBusRestoredgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A problem on the Highspeed Bus communication is restored."
|
|
::= { geUPSTrapsgen 58 }
|
|
|
|
upsTrapAlarmHighspeedBusJACRCRestoredAgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A CRC failure on the Highspeed Bus JA is restored."
|
|
::= { geUPSTrapsgen 59 }
|
|
|
|
upsTrapAlarmConnectivityBusRestoredgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A problem on the Connectivity Bus communication is restored."
|
|
::= { geUPSTrapsgen 60 }
|
|
|
|
upsTrapAlarmHighspeedBusJBCRCRestoredBgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A CRC failure on the Highspeed Bus JB is restored."
|
|
::= { geUPSTrapsgen 61 }
|
|
|
|
upsTrapAlarmCurrentSharingRestoredgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An high current sharing on the parallel system is restored."
|
|
::= { geUPSTrapsgen 62 }
|
|
|
|
upsTrapAlarmDCRippleRestoredgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An high ripple voltage on his DC link is restored."
|
|
::= { geUPSTrapsgen 63 }
|
|
|
|
upsTrapAlarmValueLowgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A measurement value reached a value below its low-level threshold."
|
|
::= { geUPSTrapsgen 129 }
|
|
|
|
upsTrapAlarmValueHighgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A measurement value reached a value higher than its high-level threshold."
|
|
::= { geUPSTrapsgen 130 }
|
|
|
|
upsTrapAlarmValueLowRestoredgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A ValueLow alarm condition is restored."
|
|
::= { geUPSTrapsgen 133 }
|
|
|
|
upsTrapAlarmValueHighRestoredgen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A ValueHigh alarm condition is restored."
|
|
::= { geUPSTrapsgen 134 }
|
|
|
|
--
|
|
-- Diagnostic Group Generic
|
|
--
|
|
|
|
upsDiagnosticBusJACommunicationStatusgen OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Bit oriented values associated to the ID of the UPS
|
|
(bit0 = UPS1 ... bit7 = UPS8).
|
|
The correspondent UPS is not present on the high speed
|
|
bus communication JA if bit=0.(*)"
|
|
::= { upsDiagnosticgen 1 }
|
|
|
|
upsDiagnosticBusJBCommunicationStatusgen OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Bit oriented values associated to the ID of the UPS
|
|
(bit0 = UPS1 ... bit7 = UPS8).
|
|
The correspondent UPS is not present on the high speed
|
|
bus communication JA if bit=0.(*)"
|
|
::= { upsDiagnosticgen 2 }
|
|
|
|
upsDiagnosticBatteryLifetimegen OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The critical components are associated to Service
|
|
parameters indicating the remaining lifetime.
|
|
They are initially set to default values depending
|
|
to the data given by the component supplier.
|
|
The parameter values decrease over time and when one
|
|
of them reaches zero (lifetime expiration) a service
|
|
check warning is generated, indicating that a check or
|
|
a replacement is suggested for that component.
|
|
The service technician is then required to re-set the
|
|
default value after the replacing of the component.(*)"
|
|
::= { upsDiagnosticgen 3 }
|
|
|
|
upsDiagnosticFansLifetimegen OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The critical components are associated to Service
|
|
parameters indicating the remaining lifetime.
|
|
They are initially set to default values depending
|
|
to the data given by the component supplier.
|
|
The parameter values decrease over time and when one
|
|
of them reaches zero (lifetime expiration) a service
|
|
check warning is generated, indicating that a check or
|
|
a replacement is suggested for that component.
|
|
The service technician is then required to re-set the
|
|
default value after the replacing of the component.(*)"
|
|
::= { upsDiagnosticgen 4 }
|
|
|
|
upsDiagnosticDCcapacitorsLifetimegen OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The critical components are associated to Service
|
|
parameters indicating the remaining lifetime.
|
|
They are initially set to default values depending
|
|
to the data given by the component supplier.
|
|
The parameter values decrease over time and when one
|
|
of them reaches zero (lifetime expiration) a service
|
|
check warning is generated, indicating that a check or
|
|
a replacement is suggested for that component.
|
|
The service technician is then required to re-set the
|
|
default value after the replacing of the component.(*)"
|
|
::= { upsDiagnosticgen 5 }
|
|
|
|
upsDiagnosticACcapacitorsLifetimegen OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The critical components are associated to Service
|
|
parameters indicating the remaining lifetime.
|
|
They are initially set to default values depending
|
|
to the data given by the component supplier.
|
|
The parameter values decrease over time and when one
|
|
of them reaches zero (lifetime expiration) a service
|
|
check warning is generated, indicating that a check or
|
|
a replacement is suggested for that component.
|
|
The service technician is then required to re-set the
|
|
default value after the replacing of the component.(*)"
|
|
::= { upsDiagnosticgen 6 }
|
|
|
|
upsDiagnosticGlobalServiceCheckgen OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The critical components are associated to Service
|
|
parameters indicating the remaining lifetime.
|
|
They are initially set to default values depending
|
|
to the data given by the component supplier.
|
|
The parameter values decrease over time and when one
|
|
of them reaches zero (lifetime expiration) a service
|
|
check warning is generated, indicating that a check or
|
|
a replacement is suggested for that component.
|
|
The service technician is then required to re-set the
|
|
default value after the replacing of the component.(*)"
|
|
::= { upsDiagnosticgen 7 }
|
|
|
|
END
|
|
|
|
|