-- EATON Environmental Rack Monitor MIB
-- MIB for Rack Monitor Environmental Monitoring System
--
-- { iso org(3) dod(6) internet(1) private(4) enterprises(1) powerware(534)
-- product(6) dataCenter(7) environmentalMonitor(1)
-- ==============================================================================================
---
--- Revision History
---
--- v1.00a1 05-Oct-2006 Kevin Lee
--- Created
--- v1.00a2 17-Oct-2006 Kenneth Liu
--- 1. Renew the item, rmConfigDateFormat, to support 4 formats
--- v1.00a3 20-Oct-2006 Kenneth Liu
--- 1. "enterprises 536" -> "enterprises 534"
--- v1.00a4 27-Nov-2006 Kenneth Liu
--- 1. Updated file based on the MIB form EATON.
--- v1.00a5 05-Jan-2007 Kenneth Liu
--- 1. Fixed some wording errors, it can pass the verification (Level:4)
--- on the http://wwwsnmp.cs.utwente.nl/ietf/mibs/validate/
--- v1.00a6 19-Jan-2007 Kenneth Liu
--- 1. Replace "sensorConfig" with "sc".
--- 2. Replace "SensorConfig" with "Sc".
--- 3. Replace "rackMonitor" with "rm".
--- 4. Replace "RackMonitor" with "Rm".
--- 5. Replace "sensorMonitor" with "sm".
--- 6. Replace "SensorMonitor" with "Sm".
--- v1.00b6 05-Feb-2007 Kenneth Liu
--- 1. Version Change.
--- v2.00 10-May-2007 Kenneth Liu
--- 1. Version Change.
---
RackMonitor-MIB DEFINITIONS ::= BEGIN
IMPORTS
enterprises
FROM RFC1155-SMI
OBJECT-TYPE
FROM RFC-1212
DisplayString
FROM RFC1213-MIB
TRAP-TYPE
FROM RFC-1215;
powerware OBJECT IDENTIFIER ::= { enterprises 534 }
product OBJECT IDENTIFIER ::= { powerware 6 }
dataCenter OBJECT IDENTIFIER ::= { product 7 }
environmentalMonitor OBJECT IDENTIFIER ::= { dataCenter 1 }
insObjects OBJECT IDENTIFIER ::= { environmentalMonitor 1 }
rmTraps OBJECT IDENTIFIER ::= { environmentalMonitor 2 }
rmIdent OBJECT IDENTIFIER ::= { insObjects 1 }
rmConfig OBJECT IDENTIFIER ::= { insObjects 2 }
sensorMonitor OBJECT IDENTIFIER ::= { insObjects 3 }
sensorConfig OBJECT IDENTIFIER ::= { insObjects 4 }
-- ===========================================================================
--
-- insIdentification
--
-- All objects in this group except for upsIdentName and
-- upsIdentAttachedDevices are set at device initialization
-- and remain static.
--
-- ===========================================================================
insIdentManufacturer OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..31))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The name of the RackMonitor manufacturer."
::= { rmIdent 1 }
insIdentModel OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The RackMonitor Model designation."
::= { rmIdent 2 }
insIdentAgentSoftwareVersion OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The RackMonitor software/firmware version. This variable may or
may not have the same value as
upsIdentUPSSoftwareVersion in some implementations."
::= { rmIdent 3 }
insIdentName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A string identifying the RackMonitor. This object should be
set by the administrator."
::= { rmIdent 4 }
-- ===========================================================================
--
-- rmConfig
--
-- ===========================================================================
rmConfigMibVersion OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The version of MIB spec."
::= { rmConfig 1}
rmConfigNetwork OBJECT IDENTIFIER ::= { rmConfig 2 }
rmConfigIpAddress OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
" The ip address that NMS can identify the managed
device"
::= { rmConfigNetwork 1 }
rmConfigGateway OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
" The default gateway that allow device managed
through routers "
::= { rmConfigNetwork 2 }
rmConfigSubnetMask OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
" Internet address subnet mask"
::= { rmConfigNetwork 3 }
rmConfigDateTime OBJECT IDENTIFIER ::= { rmConfig 3 }
rmConfigDate OBJECT-TYPE
SYNTAX DisplayString (SIZE (10..10))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The date in Environmental Rack Monitor, format is (dd/mm/yyyy)"
::= { rmConfigDateTime 1}
rmConfigTime OBJECT-TYPE
SYNTAX DisplayString (SIZE (8..8))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The time in Environmental Rack Monitor, format is (hh:mm:ss)"
::= { rmConfigDateTime 2}
rmConfigTimeFromNtp OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable update of the date and time from the NTP server."
::= { rmConfigDateTime 3}
rmConfigNtpIpAddress OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
"NTP IP address."
::= { rmConfigDateTime 4}
rmConfigNtpTimeZone OBJECT-TYPE
SYNTAX INTEGER {
gMT-1200(1),
gMT-1100(2),
gMT-1000(3),
gMT-0900(4),
gMT-0800(5),
gMT-0700(6),
gMT-0600(7),
gMT-0500(8),
gMT-0400(9),
gMT-0330(10),
gMT-0300(11),
gMT-0200(12),
gMT-0100(13),
gMT-0000(14),
gMT0100(15),
gMT0200(16),
gMT0300(17),
gMT0330(18),
gMT0400(19),
gMT0500(20),
gMT0530(21),
gMT0600(22),
gMT0700(23),
gMT0800(24),
gMT0900(25),
gMT1000(26),
gMT1100(27),
gMT1200(28)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
" Enable/disable update of the date and time from the NTP server."
::= { rmConfigDateTime 5}
rmConfigDayLightSaving OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable daylight saving for NTP time, if enabled, the time
obtained from the NTP will be set one hour in advance to reflect daylight saving status."
::= { rmConfigDateTime 6}
rmConfigLog OBJECT IDENTIFIER ::= { rmConfig 4 }
rmConfigHistoryLogFrequency OBJECT-TYPE
SYNTAX INTEGER (5..3600) -- in seconds
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The frequency of the history log update. The value
is in seconds"
::= { rmConfigLog 1}
rmConfigExtHistoryLogFrequency OBJECT-TYPE
SYNTAX INTEGER (1..1440) -- in minutes
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The frequency of the extended history log update.
The value is in seconds"
::= { rmConfigLog 2}
rmConfigConfigurationLog OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
" Enable/Disable Environmental Rack Monitor parameters change logging."
::= { rmConfigLog 3}
rmConfigDhcpStatue OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable or Disable DHCP/BootP capability"
::= { rmConfig 5}
rmConfigPingStatue OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable or Disable Ping Echo capability"
::= { rmConfig 6}
rmConfigTftpStatue OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable or Disable TFTP network upgrade capability"
::= { rmConfig 7}
rmConfigTelnet OBJECT IDENTIFIER ::= { rmConfig 8 }
rmConfigTelnetStatue OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable or Disable telnet access"
::= { rmConfigTelnet 1}
rmConfigTelnetPortNumber OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setting the server port for telnet."
::= { rmConfigTelnet 2}
rmConfigHttp OBJECT IDENTIFIER ::= { rmConfig 9 }
rmConfigHttpStatue OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable or Disable HTTP access"
::= { rmConfigHttp 1}
rmConfigHttpPortNumber OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setting the server port of HTTP."
::= { rmConfigHttp 2}
rmConfigHttpSecurity OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/Disable HTTP access for read-only users"
::= { rmConfigHttp 3}
rmConfigSnmp OBJECT IDENTIFIER ::= { rmConfig 10 }
rmConfigSnmpStatue OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable or Disable SNMP access"
::= { rmConfigSnmp 1}
rmConfigSnmpPortNumber OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setting the server port for SNMP."
::= { rmConfigSnmp 2}
rmConfigControl OBJECT IDENTIFIER ::= { rmConfig 11 }
rmConfigResetToDefault OBJECT-TYPE
SYNTAX INTEGER {
reset(1),
nothing(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Reset all parameters of Environmental Rack Monitor to default values"
::= { rmConfigControl 1}
rmConfigRestart OBJECT-TYPE
SYNTAX INTEGER {
restart(1),
nothing(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Restart rm"
::= { rmConfigControl 2}
rmConfigTrap OBJECT IDENTIFIER ::= { rmConfig 12 }
rmConfigTrapRetryCount OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The count of repeat traps to send to NMS before trap
acknowledge received."
::= { rmConfigTrap 1}
rmConfigTrapRetryTime OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The time between retry traps sent to NMS."
::= { rmConfigTrap 2}
rmConfigTrapAckSignature OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The signature of trap acknowledge."
::= { rmConfigTrap 3}
rmConfigPollRate OBJECT-TYPE
SYNTAX INTEGER (3..60)
ACCESS read-write
STATUS mandatory
DESCRIPTION
" The frequency that the Rack Monitor will read from sensors
(unit : second)."
::= { rmConfig 13}
rmConfigTrapsReceiversTable OBJECT-TYPE
SYNTAX SEQUENCE OF RmConfigTrapsReceiversEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of managers to send traps to. The number of
entries is given by the value of rmConfigNumTrapReceivers"
::= { rmConfig 14}
rmConfigTrapsReceiversEntry OBJECT-TYPE
SYNTAX RmConfigTrapsReceiversEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The managers to send traps to."
INDEX { trapsIndex}
::= { rmConfigTrapsReceiversTable 1 }
RmConfigTrapsReceiversEntry ::=
SEQUENCE {
trapsIndex
INTEGER,
trapsReceiverAddr
IpAddress,
receiverCommunityString
DisplayString,
receiverSeverityLevel
INTEGER,
receiverDescription
DisplayString
}
trapsIndex OBJECT-TYPE
SYNTAX INTEGER (1..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a trap receiver entry."
::= { rmConfigTrapsReceiversEntry 1 }
trapsReceiverAddr OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The IP address of the manager to send a trap to."
::= { rmConfigTrapsReceiversEntry 2 }
receiverCommunityString OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..19))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The community name to use in the trap when
sent to the manager."
::= { rmConfigTrapsReceiversEntry 3 }
receiverSeverityLevel OBJECT-TYPE
SYNTAX INTEGER {
informational(1),
warning(2),
severe(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The severity level of traps to be received by this manager."
::= { rmConfigTrapsReceiversEntry 4 }
receiverDescription OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Description of trap receivers"
::= { rmConfigTrapsReceiversEntry 5 }
rmConfigAccessControlTable OBJECT-TYPE
SYNTAX SEQUENCE OF RmConfigAccessControlEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of managers which can access rm with private
community string."
::= { rmConfig 15}
rmConfigAccessControlEntry OBJECT-TYPE
SYNTAX RmConfigAccessControlEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The managers."
INDEX { accessIndex}
::= { rmConfigAccessControlTable 1 }
RmConfigAccessControlEntry ::=
SEQUENCE {
accessIndex
INTEGER,
accessControlAddr
IpAddress,
accessCommunityString
DisplayString,
accessControlMode
INTEGER
}
accessIndex OBJECT-TYPE
SYNTAX INTEGER (1..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a access control entry."
::= { rmConfigAccessControlEntry 1 }
accessControlAddr OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The IP address of the manager to access RackMonitor"
::= { rmConfigAccessControlEntry 2 }
accessCommunityString OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..19))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The community name to use in the manager when
access RackMonitor"
::= { rmConfigAccessControlEntry 3 }
accessControlMode OBJECT-TYPE
SYNTAX INTEGER {
readOnly (1),
read-write (2),
notAccess (3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Access type, only read/Write access type can change parameter
of RackMonitor"
::= { rmConfigAccessControlEntry 4 }
rmConfigTemperatureUnit OBJECT-TYPE
SYNTAX INTEGER {
celsius(1),
fahrenheit(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The temperature unit of the system, can be Celsius or Fahrenheit"
::= { rmConfig 16}
rmConfigDateFormat OBJECT-TYPE
SYNTAX INTEGER {
mm-dd-yyyy(1),
dd-mm-yyyy(2),
yyyy-mm-dd(3),
dd-mmm-yyyy(4)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The date format of the system, can be dd/mm/yyyy or mm/dd/yyyy"
::= { rmConfig 17}
-- Sensor Monitoring
smSensorNumber OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The number of sensors that can be monitored."
::= { sensorMonitor 1}
smSensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF SmSensorEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of sensor devices to be monitored."
::= { sensorMonitor 2}
smSensorEntry OBJECT-TYPE
SYNTAX SmSensorEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The sensor device."
INDEX { smDeviceIndex}
::= { smSensorTable 1 }
SmSensorEntry ::=
SEQUENCE {
smDeviceIndex
INTEGER,
smDeviceStatus
INTEGER,
smDeviceTemperature
INTEGER,
smDeviceTemperatureAlarm
INTEGER,
smDeviceHumidity
INTEGER,
smDeviceHumidityAlarm
INTEGER,
smAlarm1
INTEGER,
smAlarm2
INTEGER
}
smDeviceIndex OBJECT-TYPE
SYNTAX INTEGER (1..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a sensor device entry."
::= { smSensorEntry 1 }
smDeviceStatus OBJECT-TYPE
SYNTAX INTEGER {
unknow(1),
disabled(2),
eMD-HT(3),
eMD-T(4)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The device type plugged into RackMonitor."
::= { smSensorEntry 2 }
smDeviceTemperature OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The temperature of sensor on device RackMonitor, the unit is 0.1 degree."
::= { smSensorEntry 3 }
smDeviceTemperatureAlarm OBJECT-TYPE
SYNTAX INTEGER {
unknow(1),
disabled(2),
normal(3),
lowWarning(4),
lowCritical(5),
highWarning(6),
highCritical(7)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The status of temperature sensor on device RackMonitor."
::= { smSensorEntry 4 }
smDeviceHumidity OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The humidity of sensor on device RackMonitor, the unit is 0.1%."
::= { smSensorEntry 5 }
smDeviceHumidityAlarm OBJECT-TYPE
SYNTAX INTEGER {
unknow(1),
disabled(2),
normal(3),
lowWarning(4),
lowCritical(5),
highWarning(6),
highCritical(7)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The device type plugged into RackMonitor."
::= { smSensorEntry 6 }
smAlarm1 OBJECT-TYPE
SYNTAX INTEGER {
unknow(1),
disabled(2),
active(3),
inactive(4)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The device type plugged into RackMonitor."
::= { smSensorEntry 7 }
smAlarm2 OBJECT-TYPE
SYNTAX INTEGER {
unknow(1),
disabled(2),
active(3),
inactive(4)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The device type plugged into RackMonitor."
::= { smSensorEntry 8 }
-- Sensor Configuration
scSensorNumber OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The number of sensors that can be plugged into RackMonitor."
::= { sensorConfig 1}
scSensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF ScSensorEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of sensor devices to be configured."
::= { sensorConfig 2}
scSensorEntry OBJECT-TYPE
SYNTAX ScSensorEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The sensor device."
INDEX { scDeviceIndex}
::= { scSensorTable 1 }
ScSensorEntry ::=
SEQUENCE {
scDeviceIndex
INTEGER,
scDeviceName
DisplayString,
scDeviceState
INTEGER
}
scDeviceIndex OBJECT-TYPE
SYNTAX INTEGER (1..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a sensor device entry."
::= { scSensorEntry 1 }
scDeviceName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..15))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The name of the sensor device for identification."
::= { scSensorEntry 2 }
scDeviceState OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
auto(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The setup of sensor device type."
::= { scSensorEntry 3 }
scSensor1 OBJECT IDENTIFIER ::= { sensorConfig 3 }
scSensor1DeviceName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..15))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The name of sensor device."
::= { scSensor1 1}
scSensor1DeviceState OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
auto(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The setup of sensor device type."
::= { scSensor1 2 }
scSensor1Temperature OBJECT IDENTIFIER ::= { scSensor1 3 }
scSensor1TemperatureName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..15))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The temperature sensor name."
::= { scSensor1Temperature 1 }
scSensor1TemperatureLowWarning OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The set point to trigger low warning alarm."
::= { scSensor1Temperature 2 }
scSensor1TemperatureLowCritical OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The threshold to trigger low critical alarm."
::= { scSensor1Temperature 3 }
scSensor1TemperatureHighWarning OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The threshold to trigger high warning alarm."
::= { scSensor1Temperature 4 }
scSensor1TemperatureHighCritical OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The threshold to trigger high critical alarm."
::= { scSensor1Temperature 5 }
scSensor1TemperatureHysteresis OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The set value to prevent too many alarms when temperature is hovering around the
set threshold."
::= { scSensor1Temperature 6 }
scSensor1TemperatureCalibration OBJECT-TYPE
SYNTAX INTEGER {
temperatureIncrease0Point0(1),
temperatureIncrease0Point5(2),
temperatureIncrease1Point0(3),
temperatureIncrease1Point5(4),
temperatureIncrease2Point0(5),
temperatureIncrease2Point5(6),
temperatureIncrease3Point0(7),
temperatureMinus0Point5(8),
temperatureMinus1Point0(9),
temperatureMinus1Point5(10),
temperatureMinus2Point0(11),
temperatureMinus2Point5(12),
temperatureMinusPoint0(13)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The set value to get the correct temperature according to the reference temperature."
::= { scSensor1Temperature 7 }
scSensor1TemperatureLowWarningStatus OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/Disable the set point to trigger low warning alarm."
::= { scSensor1Temperature 8 }
scSensor1TemperatureLowCriticalStatus OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/Disable the set point to trigger low critical alarm."
::= { scSensor1Temperature 9 }
scSensor1TemperatureHighWarningStatus OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/Disable the set point to trigger high warning alarm."
::= { scSensor1Temperature 10 }
scSensor1TemperatureHighCriticalStatus OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable the set point to trigger high critical alarm."
::= { scSensor1Temperature 11 }
scSensor1Humidity OBJECT IDENTIFIER ::= { scSensor1 4 }
scSensor1HumdityName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..15))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The humidity sensor name."
::= { scSensor1Humidity 1 }
scSensor1HumidityLowWarning OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The set point to trigger low warning alarm."
::= { scSensor1Humidity 2 }
scSensor1HumidityLowCritical OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The threshold to trigger low critical alarm."
::= { scSensor1Humidity 3 }
scSensor1HumidityHighWarning OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The threshold to trigger high warning alarm."
::= { scSensor1Humidity 4 }
scSensor1HumidityHighCritical OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The threshold to trigger high critical alarm."
::= { scSensor1Humidity 5 }
scSensor1HumidityHysteresis OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The set value to prevent too many alarms when Humidity is hovering around the
set threshold."
::= { scSensor1Humidity 6 }
scSensor1HumidityCalibration OBJECT-TYPE
SYNTAX INTEGER {
humidityIncrease0Point0(1),
humidityIncrease1Point0(2),
humidityIncrease2Point0(3),
humidityIncrease3Point0(4),
humidityIncrease4Point0(5),
humidityIncrease5Point0(6),
humidityIncrease6Point0(7),
humidityMinus1Point0(8),
humidityMinus2Point0(9),
humidityMinus3Point0(10),
humidityMinus4Point0(11),
humidityMinus5Point0(12),
humidityMinus6Point0(13)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The set value to get the correct temperature according to your reference temperature."
::= { scSensor1Humidity 7 }
scSensor1HumidityLowWarningStatus OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/Disable the set point to trigger low warning alarm."
::= { scSensor1Humidity 8 }
scSensor1HumidityLowCriticalStatus OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/Disable the set point to trigger low critical alarm."
::= { scSensor1Humidity 9 }
scSensor1HumidityHighWarningStatus OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/Disable the set point to trigger high warning alarm."
::= { scSensor1Humidity 10 }
scSensor1HumidityHighCriticalStatus OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/Disable the set point to trigger high critical alarm."
::= { scSensor1Humidity 11 }
scSensor1Alarm1 OBJECT IDENTIFIER ::= { scSensor1 5 }
scSensor1Alarm1Name OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..15))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The name of alarm-1."
::= { scSensor1Alarm1 1 }
scSensor1Alarm1State OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
normalOpen(2),
normalClose(3),
highActive(4),
lowActive(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setup the signal type to trigger alarm."
::= { scSensor1Alarm1 2 }
scSensor1Alarm1Hysteresis OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The set value to delay the alarm triggered when event occurs."
::= { scSensor1Alarm1 3 }
scSensor1Alarm2 OBJECT IDENTIFIER ::= { scSensor1 6 }
scSensor1Alarm2Name OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..15))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The name of alarm-1."
::= { scSensor1Alarm2 1 }
scSensor1Alarm2State OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
normalOpen(2),
normalClose(3),
highActive(4),
lowActive(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setup the signal type to trigger alarm."
::= { scSensor1Alarm2 2 }
scSensor1Alarm2Hysteresis OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The set value to delay the alarm triggered when event occurs."
::= { scSensor1Alarm2 3 }
scSensor2 OBJECT IDENTIFIER ::= { sensorConfig 4 }
scSensor2DeviceName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..15))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The name of sensor device."
::= { scSensor2 1}
scSensor2DeviceState OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
auto(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The setup of sensor device type."
::= { scSensor2 2 }
scSensor2Temperature OBJECT IDENTIFIER ::= { scSensor2 3 }
scSensor2TemperatureName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..15))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The temperature sensor name."
::= { scSensor2Temperature 1 }
scSensor2TemperatureLowWarning OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The set point to trigger low warning alarm."
::= { scSensor2Temperature 2 }
scSensor2TemperatureLowCritical OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The threshold to trigger low critical alarm."
::= { scSensor2Temperature 3 }
scSensor2TemperatureHighWarning OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The threshold to trigger high warning alarm."
::= { scSensor2Temperature 4 }
scSensor2TemperatureHighCritical OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The threshold to trigger high critical alarm."
::= { scSensor2Temperature 5 }
scSensor2TemperatureHysteresis OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The set value to prevent too many alarms when temperature is hovering around the
set threshold."
::= { scSensor2Temperature 6 }
scSensor2TemperatureCalibration OBJECT-TYPE
SYNTAX INTEGER {
temperatureIncrease0Point0(1),
temperatureIncrease0Point5(2),
temperatureIncrease1Point0(3),
temperatureIncrease1Point5(4),
temperatureIncrease2Point0(5),
temperatureIncrease2Point5(6),
temperatureIncrease3Point0(7),
temperatureMinus0Point5(8),
temperatureMinus1Point0(9),
temperatureMinus1Point5(10),
temperatureMinus2Point0(11),
temperatureMinus2Point5(12),
temperatureMinusPoint0(13)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The set value to get the correct temperature according to your reference temperature."
::= { scSensor2Temperature 7 }
scSensor2TemperatureLowWarningStatus OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/Disable the set point to trigger low warning alarm."
::= { scSensor2Temperature 8 }
scSensor2TemperatureLowCriticalStatus OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/Disable the set point to trigger low critical alarm."
::= { scSensor2Temperature 9 }
scSensor2TemperatureHighWarningStatus OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/Disable the set point to trigger high warning alarm."
::= { scSensor2Temperature 10 }
scSensor2TemperatureHighCriticalStatus OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/Disable the set point to trigger high critical alarm."
::= { scSensor2Temperature 11 }
scSensor2Humidity OBJECT IDENTIFIER ::= { scSensor2 4 }
scSensor2HumdityName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..15))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The humidity sensor name."
::= { scSensor2Humidity 1 }
scSensor2HumidityLowWarning OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The set point to trigger low warning alarm."
::= { scSensor2Humidity 2 }
scSensor2HumidityLowCritical OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The threshold to trigger low critical alarm."
::= { scSensor2Humidity 3 }
scSensor2HumidityHighWarning OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The threshold to trigger high warning alarm."
::= { scSensor2Humidity 4 }
scSensor2HumidityHighCritical OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The threshold to trigger high critical alarm."
::= { scSensor2Humidity 5 }
scSensor2HumidityHysteresis OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The set value to prevent too many alarms when Humidity is hovering around the
set threshold."
::= { scSensor2Humidity 6 }
scSensor2HumidityCalibration OBJECT-TYPE
SYNTAX INTEGER {
humidityIncrease0Point0(1),
humidityIncrease1Point0(2),
humidityIncrease2Point0(3),
humidityIncrease3Point0(4),
humidityIncrease4Point0(5),
humidityIncrease5Point0(6),
humidityIncrease6Point0(7),
humidityMinus1Point0(8),
humidityMinus2Point0(9),
humidityMinus3Point0(10),
humidityMinus4Point0(11),
humidityMinus5Point0(12),
humidityMinus6Point0(13)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The set value to get the correct temperature according to the reference temperature."
::= { scSensor2Humidity 7 }
scSensor2HumidityLowWarningStatus OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/Disable the set point to trigger low warning alarm."
::= { scSensor2Humidity 8 }
scSensor2HumidityLowCriticalStatus OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/Disable the set point to trigger low critical alarm."
::= { scSensor2Humidity 9 }
scSensor2HumidityHighWarningStatus OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/Disable the set point to trigger high warning alarm."
::= { scSensor2Humidity 10 }
scSensor2HumidityHighCriticalStatus OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/Disable the set point to trigger high critical alarm."
::= { scSensor2Humidity 11 }
scSensor2Alarm1 OBJECT IDENTIFIER ::= { scSensor2 5 }
scSensor2Alarm1Name OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..15))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The name of alarm-1."
::= { scSensor2Alarm1 1 }
scSensor2Alarm1State OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
normalOpen(2),
normalClose(3),
highActive(4),
lowActive(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setup the signal type to trigger alarm."
::= { scSensor2Alarm1 2 }
scSensor2Alarm1Hysteresis OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The set value to delay the alarm triggered when event occurs."
::= { scSensor2Alarm1 3 }
scSensor2Alarm2 OBJECT IDENTIFIER ::= { scSensor2 6 }
scSensor2Alarm2Name OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..15))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The name of alarm-1."
::= { scSensor2Alarm2 1 }
scSensor2Alarm2State OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
normalOpen(2),
normalClose(3),
highActive(4),
lowActive(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setup the signal type to trigger alarm."
::= { scSensor2Alarm2 2 }
scSensor2Alarm2Hysteresis OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The set value to delay the alarm triggered when event occurs."
::= { scSensor2Alarm2 3 }
-- ===========================================================================
-- upsTraps
--
-- Traps group
-- ===========================================================================
-- This section defines the well-known notifications sent by
-- Environmental Rack Monitor agents.
-- Care must be taken to insure that no particular notification
-- is sent to a single receiving entity more often than once
-- every five seconds.
rmCommunicationRestored TRAP-TYPE
ENTERPRISE rmTraps
DESCRIPTION
"INFORMATION: Communication between RackMonitor and sensor had
established."
::= 1
rmCommunicationLost TRAP-TYPE
ENTERPRISE rmTraps
DESCRIPTION
"WARNING: Communication between RackMonitor and sensor had
lost."
::= 2
rmAlarm1Inactive TRAP-TYPE
ENTERPRISE rmTraps
DESCRIPTION
"INFORMATION: Alarm1 of sensor had return from active state."
::= 3
rmAlarm1Active TRAP-TYPE
ENTERPRISE rmTraps
DESCRIPTION
"WARNING: Alarm1 has become active."
::= 4
rmAlarm2Inactive TRAP-TYPE
ENTERPRISE rmTraps
DESCRIPTION
"INFORMATION: Alarm2 of sensor has returned to normal state."
::= 5
rmAlarm2Active TRAP-TYPE
ENTERPRISE rmTraps
DESCRIPTION
"WARNING: Alarm2 had became active."
::= 6
rmTemperatureNotHighWarning TRAP-TYPE
ENTERPRISE rmTraps
DESCRIPTION
"INFORMATION: The temperature of sensor had return from High warning to normal."
::= 7
rmTemperatureHighWarning TRAP-TYPE
ENTERPRISE rmTraps
DESCRIPTION
"WARNING: The temperature of sensor was higher than High warning set point."
::= 8
rmTemperatureNotLowWarning TRAP-TYPE
ENTERPRISE rmTraps
DESCRIPTION
"INFORMATION: The temperature of sensor had return from low warning to normal."
::= 9
rmTemperatureLowWarning TRAP-TYPE
ENTERPRISE rmTraps
DESCRIPTION
"WARNING: The temperature of sensor was lower than low warning set point."
::= 10
rmTemperatureNotHighCritical TRAP-TYPE
ENTERPRISE rmTraps
DESCRIPTION
"INFORMATION: The temperature of sensor lower than high critical set point."
::= 11
rmTemperatureHighCritical TRAP-TYPE
ENTERPRISE rmTraps
DESCRIPTION
"CRITICAL: The temperature of sensor was higher than high critical set point."
::= 12
rmTemperatureNotLowCritical TRAP-TYPE
ENTERPRISE rmTraps
DESCRIPTION
"INFORMATION: The temperature of sensor was higher than low critical set point."
::= 13
rmTemperatureLowCritical TRAP-TYPE
ENTERPRISE rmTraps
DESCRIPTION
"CRITICAL: The temperature of sensor was lower than low critical set point."
::= 14
rmHumidityNotHighWarning TRAP-TYPE
ENTERPRISE rmTraps
DESCRIPTION
"INFORMATION: The humidity of sensor had return from High warning to normal."
::= 15
rmHumidityHighWarning TRAP-TYPE
ENTERPRISE rmTraps
DESCRIPTION
"WARNING: The humidity of sensor was higher than High warning set point."
::= 16
rmHumidityNotLowWarning TRAP-TYPE
ENTERPRISE rmTraps
DESCRIPTION
"INFORMATION: The humidity of sensor had return from low warning to normal."
::= 17
rmHumidityLowWarning TRAP-TYPE
ENTERPRISE rmTraps
DESCRIPTION
"WARNING: The humidity of sensor was lower than low warning set point."
::= 18
rmHumidityNotHighCritical TRAP-TYPE
ENTERPRISE rmTraps
DESCRIPTION
"INFORMATION: The humidity of sensor lower than high critical set point."
::= 19
rmHumidityHighCritical TRAP-TYPE
ENTERPRISE rmTraps
DESCRIPTION
"CRITICAL: The humidity of sensor was higher than high critical set point."
::= 20
rmHumidityNotLowCritical TRAP-TYPE
ENTERPRISE rmTraps
DESCRIPTION
"INFORMATION: The humidity of sensor was higher than low critical set point."
::= 21
rmHumidityLowCritical TRAP-TYPE
ENTERPRISE rmTraps
DESCRIPTION
"CRITICAL: The humidity of sensor was lower than low critical set point."
::= 22
END