EATON-EPDU-PU-SW-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
NOTIFICATION-TYPE, OBJECT-TYPE, MODULE-IDENTITY,
|
|
enterprises, IpAddress, Integer32
|
|
FROM SNMPv2-SMI
|
|
NOTIFICATION-GROUP, OBJECT-GROUP, MODULE-COMPLIANCE
|
|
FROM SNMPv2-CONF;
|
|
|
|
pulizzi MODULE-IDENTITY
|
|
LAST-UPDATED "200910161200Z"
|
|
ORGANIZATION
|
|
"Eaton Corporation"
|
|
CONTACT-INFO
|
|
"Eaton Corporation
|
|
Technical Resource Center phone numbers
|
|
United States: 1.800.843.9433 or 919.870.3028
|
|
Canada: 1.800.461.9166 ext. 260
|
|
All other countries: Call your local service representative."
|
|
DESCRIPTION
|
|
"The MIB module for Eaton Switched ePDUs (Enclosed Power Distribution Units.)"
|
|
|
|
REVISION "200910161200Z"
|
|
DESCRIPTION
|
|
"
|
|
Updated to add objects for units with up to 36 outlets and up to six measurement sections:
|
|
- Added outlet25 through outlet36 branches under outletConfig
|
|
- Added variables for outlets 25 through 36 under outletControl and outletStatus
|
|
- Added outletSection4Config, outletSection5Config, and outletSection6Config
|
|
- Added outletSection4, outletSection5, and outletSection6
|
|
- Added the events branch and defined the appropriate notifications
|
|
- Added the eventInfo branch to define objects used in notifications
|
|
- Deprecated totalVoltage as it is no longer useful
|
|
- Updated the conformance groups
|
|
"
|
|
|
|
REVISION "200812221200Z"
|
|
DESCRIPTION
|
|
"
|
|
Updated to fix syntax errors:
|
|
- Added conformance groups
|
|
- Filled in descriptions for all variables
|
|
- Renamed the following variables: outletSection1Log to outletSection1Alert,
|
|
outletSection2Log to outletSection2Alert, outletSection3Log to outletSection3Alert,
|
|
tempSensor1Log to tempSensor1Alert, tempSensor2Log to tempSensor2Alert,
|
|
humSensor1Log to humSensor1Alert, contactClosure1Log to contactClosure1Alert,
|
|
contactClosure2Log to contactClosure2Alert, contactClosure3Log to contactClosure3Alert,
|
|
keyBoardTime to loginTimeout; changed 'allert' to 'alert' wherever it appeared
|
|
- Renamed MIB file to EATON-EPDU-PU-SW-MIB
|
|
"
|
|
|
|
REVISION "200802131200Z"
|
|
DESCRIPTION
|
|
"
|
|
- CHANGED DISPLAYSTRING DATA TYPE TO OCTET STRING
|
|
- CHANGED GLOBAL COMMAND, PING ENABLED, AND PING INTERVAL
|
|
- CHANGED IP ADDRESS, SUBNET MASK, DEFAULT GATEWAY TO READ-ONLY
|
|
"
|
|
|
|
REVISION "200605011200Z"
|
|
DESCRIPTION
|
|
"
|
|
INITIAL RELEASE.
|
|
"
|
|
::= { enterprises 20677 }
|
|
|
|
ipv3600 OBJECT IDENTIFIER ::= { pulizzi 2 }
|
|
unitConfig OBJECT IDENTIFIER ::= { ipv3600 1 }
|
|
networkSettings OBJECT IDENTIFIER ::= { ipv3600 2 }
|
|
logManagerConfig OBJECT IDENTIFIER ::= { ipv3600 3 }
|
|
serialSettings OBJECT IDENTIFIER ::= { ipv3600 4 }
|
|
telnetSettings OBJECT IDENTIFIER ::= { ipv3600 5 }
|
|
outletMngt OBJECT IDENTIFIER ::= { ipv3600 6 }
|
|
outletConfig OBJECT IDENTIFIER ::= { outletMngt 1 }
|
|
outlet1 OBJECT IDENTIFIER ::= { outletConfig 1 }
|
|
outlet2 OBJECT IDENTIFIER ::= { outletConfig 2 }
|
|
outlet3 OBJECT IDENTIFIER ::= { outletConfig 3 }
|
|
outlet4 OBJECT IDENTIFIER ::= { outletConfig 4 }
|
|
outlet5 OBJECT IDENTIFIER ::= { outletConfig 5 }
|
|
outlet6 OBJECT IDENTIFIER ::= { outletConfig 6 }
|
|
outlet7 OBJECT IDENTIFIER ::= { outletConfig 7 }
|
|
outlet8 OBJECT IDENTIFIER ::= { outletConfig 8 }
|
|
outlet9 OBJECT IDENTIFIER ::= { outletConfig 9 }
|
|
outlet10 OBJECT IDENTIFIER ::= { outletConfig 10 }
|
|
outlet11 OBJECT IDENTIFIER ::= { outletConfig 11 }
|
|
outlet12 OBJECT IDENTIFIER ::= { outletConfig 12 }
|
|
outlet13 OBJECT IDENTIFIER ::= { outletConfig 13 }
|
|
outlet14 OBJECT IDENTIFIER ::= { outletConfig 14 }
|
|
outlet15 OBJECT IDENTIFIER ::= { outletConfig 15 }
|
|
outlet16 OBJECT IDENTIFIER ::= { outletConfig 16 }
|
|
outlet17 OBJECT IDENTIFIER ::= { outletConfig 17 }
|
|
outlet18 OBJECT IDENTIFIER ::= { outletConfig 18 }
|
|
outlet19 OBJECT IDENTIFIER ::= { outletConfig 19 }
|
|
outlet20 OBJECT IDENTIFIER ::= { outletConfig 20 }
|
|
outlet21 OBJECT IDENTIFIER ::= { outletConfig 21 }
|
|
outlet22 OBJECT IDENTIFIER ::= { outletConfig 22 }
|
|
outlet23 OBJECT IDENTIFIER ::= { outletConfig 23 }
|
|
outlet24 OBJECT IDENTIFIER ::= { outletConfig 24 }
|
|
outlet25 OBJECT IDENTIFIER ::= { outletConfig 25 }
|
|
outlet26 OBJECT IDENTIFIER ::= { outletConfig 26 }
|
|
outlet27 OBJECT IDENTIFIER ::= { outletConfig 27 }
|
|
outlet28 OBJECT IDENTIFIER ::= { outletConfig 28 }
|
|
outlet29 OBJECT IDENTIFIER ::= { outletConfig 29 }
|
|
outlet30 OBJECT IDENTIFIER ::= { outletConfig 30 }
|
|
outlet31 OBJECT IDENTIFIER ::= { outletConfig 31 }
|
|
outlet32 OBJECT IDENTIFIER ::= { outletConfig 32 }
|
|
outlet33 OBJECT IDENTIFIER ::= { outletConfig 33 }
|
|
outlet34 OBJECT IDENTIFIER ::= { outletConfig 34 }
|
|
outlet35 OBJECT IDENTIFIER ::= { outletConfig 35 }
|
|
outlet36 OBJECT IDENTIFIER ::= { outletConfig 36 }
|
|
outletControl OBJECT IDENTIFIER ::= { outletMngt 2 }
|
|
outletStatus OBJECT IDENTIFIER ::= { outletMngt 3 }
|
|
snmpSettings OBJECT IDENTIFIER ::= { ipv3600 7 }
|
|
snmpTraps OBJECT IDENTIFIER ::= { snmpSettings 8 }
|
|
environmentalSettings OBJECT IDENTIFIER ::= { ipv3600 8 }
|
|
temperatureSensorConfig OBJECT IDENTIFIER ::= { environmentalSettings 1 }
|
|
tempSensor1 OBJECT IDENTIFIER ::= { temperatureSensorConfig 1 }
|
|
tempSensor2 OBJECT IDENTIFIER ::= { temperatureSensorConfig 2 }
|
|
humiditySensorConfig OBJECT IDENTIFIER ::= { environmentalSettings 2 }
|
|
humSensor1 OBJECT IDENTIFIER ::= { humiditySensorConfig 1 }
|
|
contactClosureConfig OBJECT IDENTIFIER ::= { environmentalSettings 3 }
|
|
contactClosure1 OBJECT IDENTIFIER ::= { contactClosureConfig 1 }
|
|
contactClosure2 OBJECT IDENTIFIER ::= { contactClosureConfig 2 }
|
|
contactClosure3 OBJECT IDENTIFIER ::= { contactClosureConfig 3 }
|
|
outletSectionConfig OBJECT IDENTIFIER ::= { environmentalSettings 4 }
|
|
outletSection1Config OBJECT IDENTIFIER ::= { outletSectionConfig 1 }
|
|
outletSection2Config OBJECT IDENTIFIER ::= { outletSectionConfig 2 }
|
|
outletSection3Config OBJECT IDENTIFIER ::= { outletSectionConfig 3 }
|
|
outletSection4Config OBJECT IDENTIFIER ::= { outletSectionConfig 4 }
|
|
outletSection5Config OBJECT IDENTIFIER ::= { outletSectionConfig 5 }
|
|
outletSection6Config OBJECT IDENTIFIER ::= { outletSectionConfig 6 }
|
|
currentSensorValues OBJECT IDENTIFIER ::= { environmentalSettings 5 }
|
|
currentOutletSectionValues OBJECT IDENTIFIER ::= { environmentalSettings 6 }
|
|
outletSection1 OBJECT IDENTIFIER ::= { currentOutletSectionValues 1 }
|
|
outletSection2 OBJECT IDENTIFIER ::= { currentOutletSectionValues 2 }
|
|
outletSection3 OBJECT IDENTIFIER ::= { currentOutletSectionValues 3 }
|
|
total OBJECT IDENTIFIER ::= { currentOutletSectionValues 4 }
|
|
outletSection4 OBJECT IDENTIFIER ::= { currentOutletSectionValues 5 }
|
|
outletSection5 OBJECT IDENTIFIER ::= { currentOutletSectionValues 6 }
|
|
outletSection6 OBJECT IDENTIFIER ::= { currentOutletSectionValues 7 }
|
|
events OBJECT IDENTIFIER ::= { ipv3600 9 }
|
|
eventInfo OBJECT IDENTIFIER ::= { ipv3600 10 }
|
|
conformance OBJECT IDENTIFIER ::= { ipv3600 25 }
|
|
groups OBJECT IDENTIFIER ::= { conformance 5 }
|
|
|
|
unitName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive name of unit."
|
|
::= { unitConfig 1 }
|
|
|
|
strappingId OBJECT-TYPE
|
|
SYNTAX Integer32 (0..23)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"ID of unit when connected in a strapping configuration."
|
|
::= { unitConfig 2 }
|
|
|
|
unitTime OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..5))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time hh:mm"
|
|
::= { unitConfig 3 }
|
|
|
|
unitDate OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..10))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Today's date mm/dd/yyyy"
|
|
::= { unitConfig 4 }
|
|
|
|
unitDayOfWeek OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
sunday (1),
|
|
monday (2),
|
|
tuesday (3),
|
|
wednesday (4),
|
|
thursday (5),
|
|
friday (6),
|
|
saturday (7)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Today's day of week. This is important when scheduling logs to be sent on a particular week day."
|
|
::= { unitConfig 5 }
|
|
|
|
vaLoggingInterval OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
fiveminutes (1),
|
|
fifteenminutes (2),
|
|
hourly (3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Interval for updating the VA log."
|
|
::= { unitConfig 6 }
|
|
|
|
loginTimeout OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Timeout (in seconds) for serial, telnet, and web interfaces."
|
|
::= { unitConfig 7 }
|
|
|
|
invertDisplay OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal (0),
|
|
inverted (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Select the orientation of the local 7-segment display."
|
|
::= { unitConfig 8 }
|
|
|
|
fahrenheitOrCelsius OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
fahrenheit (0),
|
|
celsius (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Units for temperature readings."
|
|
::= { unitConfig 9 }
|
|
|
|
unitIPAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Network IP address"
|
|
::= { networkSettings 1 }
|
|
|
|
subnetMask OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Network subnet mask"
|
|
::= { networkSettings 2 }
|
|
|
|
defaultGateway OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Network default gateway"
|
|
::= { networkSettings 3 }
|
|
|
|
webPort OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Port number for non-secure (http) web interface."
|
|
::= { networkSettings 4 }
|
|
|
|
webEnabled OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enabled (1),
|
|
disabled (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enables or disables the web interface (both secure and non-secure)."
|
|
::= { networkSettings 5 }
|
|
|
|
macAddress OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..17))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Hardware network address"
|
|
::= { networkSettings 6 }
|
|
|
|
enablePing OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enables ping watchdog feature. If enabled, the IP address for each outlet (if non-zero) will be pinged
|
|
periodically; the outlet will be rebooted if there is no ping response."
|
|
::= { networkSettings 7 }
|
|
|
|
pingInterval OBJECT-TYPE
|
|
SYNTAX Integer32 (1..999)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Interval (in minutes) beween attempts to ping the IP address corresponding to an outlet."
|
|
::= { networkSettings 8 }
|
|
|
|
mailServerIPAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"IP address of mail server for sending logs and alerts."
|
|
::= { logManagerConfig 1 }
|
|
|
|
sendLogFrom OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Email address (x@y.z format) to be used as the from address for logs and alerts."
|
|
::= { logManagerConfig 2 }
|
|
|
|
sendLogToUser1Address OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Email address to which to send unit logs."
|
|
::= { logManagerConfig 3 }
|
|
|
|
sendLogToUser2Address OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Second email address to which to send unit logs."
|
|
::= { logManagerConfig 4 }
|
|
|
|
sendAlertsToUser1Address OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Email address to which to send unit alerts."
|
|
::= { logManagerConfig 5 }
|
|
|
|
sendAlertsToUser2Address OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Second email address to which to send unit alerts."
|
|
::= { logManagerConfig 6 }
|
|
|
|
sendLogFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
weeklyOnSunday (1),
|
|
weeklyOnMonday (2),
|
|
weeklyOnTuesday (3),
|
|
weeklyOnWednesday (4),
|
|
weeklyOnThursday (5),
|
|
weeklyOnFriday (6),
|
|
weeklyOnSaturday (7),
|
|
daily (8),
|
|
whenFull (9),
|
|
never (10)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Frequency with which to send logs via email."
|
|
::= { logManagerConfig 7 }
|
|
|
|
sendLogTime OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time of day to send logs via email. Not applicable if sendLogFrequency is set to whenFull or never."
|
|
::= { logManagerConfig 8 }
|
|
|
|
userLogInLogOut OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (1),
|
|
sendToLog (2),
|
|
sendAlert (3),
|
|
sendtoLogAndAlert (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enabled setting to log or send an alert when a user logs in or logs out of the serial, telnet, or web interfaces."
|
|
::= { logManagerConfig 9 }
|
|
|
|
userLogInLogOutFailed OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (1),
|
|
sendToLog (2),
|
|
sendAlert (3),
|
|
sendtoLogAndAlert (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enabled setting to log or send an alert when a user attempts to log in but fails because of a username or password mismatch."
|
|
::= { logManagerConfig 10 }
|
|
|
|
outletActivity OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (1),
|
|
sendToLog (2),
|
|
sendAlert (3),
|
|
sendtoLogAndAlert (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enabled setting to log or send an alert each time an outlet changes state."
|
|
::= { logManagerConfig 11 }
|
|
|
|
systemOnOff OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (1),
|
|
sendToLog (2),
|
|
sendAlert (3),
|
|
sendtoLogAndAlert (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enabled setting to log or send an alert each time the unit powers up."
|
|
::= { logManagerConfig 12 }
|
|
|
|
outletSection1Alert OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
sendAlert (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enabled setting to send an email alert when section 1 thresholds are breached."
|
|
::= { logManagerConfig 13 }
|
|
|
|
outletSection2Alert OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
sendAlert (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enabled setting to send an email alert when section 2 thresholds are brached."
|
|
::= { logManagerConfig 14 }
|
|
|
|
outletSection3Alert OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
sendAlert (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enabled setting to send an email alert when section 3 thresholds are breached."
|
|
::= { logManagerConfig 15 }
|
|
|
|
tempSensor1Alert OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
sendAlert (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enabled setting to send an email alert when temperature sensor 1 thresholds are breached."
|
|
::= { logManagerConfig 16 }
|
|
|
|
tempSensor2Alert OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
sendAlert (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enabled setting to send an email alert when temperature sensor 2 thresholds are breached."
|
|
::= { logManagerConfig 17 }
|
|
|
|
humSensor1Alert OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
sendAlert (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enabled setting to send an email alert when humidity sensor thresholds are breached."
|
|
::= { logManagerConfig 18 }
|
|
|
|
contactClosure1Alert OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
sendAlert (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enabled setting to send an email alert when contact sensor 1 changes state."
|
|
::= { logManagerConfig 19 }
|
|
|
|
contactClosure2Alert OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
sendAlert (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enabled setting to send an email alert when contact sensor 2 changes state."
|
|
::= { logManagerConfig 20 }
|
|
|
|
contactClosure3Alert OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
sendAlert (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enabled setting to send an email alert when contact sensor 3 changes state."
|
|
::= { logManagerConfig 21 }
|
|
|
|
baudRate OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
baud9600 (0),
|
|
baud19200 (1),
|
|
baud38400 (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Serial baud rate, does not take effect unless unit is soft-rebooted."
|
|
::= { serialSettings 1 }
|
|
|
|
telnetPort OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Telnet interface port, default is 23."
|
|
::= { telnetSettings 1 }
|
|
|
|
telnetEnabled OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enabled (1),
|
|
disabled (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enabled setting for the telnet interface. This can be disabled for security."
|
|
::= { telnetSettings 2 }
|
|
|
|
outlet1Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive outlet name"
|
|
::= { outlet1 1 }
|
|
|
|
outlet1PingIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ping watchdog IP address"
|
|
::= { outlet1 2 }
|
|
|
|
outlet1Link OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"URL of web configuration interface for the device connected to this outlet."
|
|
::= { outlet1 3 }
|
|
|
|
outlet1SequenceTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to delay turning on after a Sequence On command is issued."
|
|
::= { outlet1 4 }
|
|
|
|
outlet1RebootTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to remain off when a Reboot command is issued."
|
|
::= { outlet1 5 }
|
|
|
|
outlet2Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive outlet name"
|
|
::= { outlet2 1 }
|
|
|
|
outlet2PingIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ping watchdog IP address"
|
|
::= { outlet2 2 }
|
|
|
|
outlet2Link OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"URL of web configuration interface for the device connected to this outlet."
|
|
::= { outlet2 3 }
|
|
|
|
outlet2SequenceTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to delay turning on after a Sequence On command is issued."
|
|
::= { outlet2 4 }
|
|
|
|
outlet2RebootTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to remain off when a Reboot command is issued."
|
|
::= { outlet2 5 }
|
|
|
|
outlet3Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive outlet name"
|
|
::= { outlet3 1 }
|
|
|
|
outlet3PingIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ping watchdog IP address"
|
|
::= { outlet3 2 }
|
|
|
|
outlet3Link OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"URL of web configuration interface for the device connected to this outlet."
|
|
::= { outlet3 3 }
|
|
|
|
outlet3SequenceTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to delay turning on after a Sequence On command is issued."
|
|
::= { outlet3 4 }
|
|
|
|
outlet3RebootTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to remain off when a Reboot command is issued."
|
|
::= { outlet3 5 }
|
|
|
|
outlet4Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive outlet name"
|
|
::= { outlet4 1 }
|
|
|
|
outlet4PingIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ping watchdog IP address"
|
|
::= { outlet4 2 }
|
|
|
|
outlet4Link OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"URL of web configuration interface for the device connected to this outlet."
|
|
::= { outlet4 3 }
|
|
|
|
outlet4SequenceTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to delay turning on after a Sequence On command is issued."
|
|
::= { outlet4 4 }
|
|
|
|
outlet4RebootTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to remain off when a Reboot command is issued."
|
|
::= { outlet4 5 }
|
|
|
|
outlet5Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive outlet name"
|
|
::= { outlet5 1 }
|
|
|
|
outlet5PingIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ping watchdog IP address"
|
|
::= { outlet5 2 }
|
|
|
|
outlet5Link OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"URL of web configuration interface for the device connected to this outlet."
|
|
::= { outlet5 3 }
|
|
|
|
outlet5SequenceTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to delay turning on after a Sequence On command is issued."
|
|
::= { outlet5 4 }
|
|
|
|
outlet5RebootTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to remain off when a Reboot command is issued."
|
|
::= { outlet5 5 }
|
|
|
|
outlet6Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive outlet name"
|
|
::= { outlet6 1 }
|
|
|
|
outlet6PingIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ping watchdog IP address"
|
|
::= { outlet6 2 }
|
|
|
|
outlet6Link OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"URL of web configuration interface for the device connected to this outlet."
|
|
::= { outlet6 3 }
|
|
|
|
outlet6SequenceTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to delay turning on after a Sequence On command is issued."
|
|
::= { outlet6 4 }
|
|
|
|
outlet6RebootTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to remain off when a Reboot command is issued."
|
|
::= { outlet6 5 }
|
|
|
|
outlet7Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive outlet name"
|
|
::= { outlet7 1 }
|
|
|
|
outlet7PingIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ping watchdog IP address"
|
|
::= { outlet7 2 }
|
|
|
|
outlet7Link OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"URL of web configuration interface for the device connected to this outlet."
|
|
::= { outlet7 3 }
|
|
|
|
outlet7SequenceTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to delay turning on after a Sequence On command is issued."
|
|
::= { outlet7 4 }
|
|
|
|
outlet7RebootTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to remain off when a Reboot command is issued."
|
|
::= { outlet7 5 }
|
|
|
|
outlet8Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive outlet name"
|
|
::= { outlet8 1 }
|
|
|
|
outlet8PingIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ping watchdog IP address"
|
|
::= { outlet8 2 }
|
|
|
|
outlet8Link OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"URL of web configuration interface for the device connected to this outlet."
|
|
::= { outlet8 3 }
|
|
|
|
outlet8SequenceTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to delay turning on after a Sequence On command is issued."
|
|
::= { outlet8 4 }
|
|
|
|
outlet8RebootTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to remain off when a Reboot command is issued."
|
|
::= { outlet8 5 }
|
|
|
|
outlet9Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive outlet name"
|
|
::= { outlet9 1 }
|
|
|
|
outlet9PingIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ping watchdog IP address"
|
|
::= { outlet9 2 }
|
|
|
|
outlet9Link OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"URL of web configuration interface for the device connected to this outlet."
|
|
::= { outlet9 3 }
|
|
|
|
outlet9SequenceTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to delay turning on after a Sequence On command is issued."
|
|
::= { outlet9 4 }
|
|
|
|
outlet9RebootTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to remain off when a Reboot command is issued."
|
|
::= { outlet9 5 }
|
|
|
|
outlet10Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive outlet name"
|
|
::= { outlet10 1 }
|
|
|
|
outlet10PingIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ping watchdog IP address"
|
|
::= { outlet10 2 }
|
|
|
|
outlet10Link OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"URL of web configuration interface for the device connected to this outlet."
|
|
::= { outlet10 3 }
|
|
|
|
outlet10SequenceTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to delay turning on after a Sequence On command is issued."
|
|
::= { outlet10 4 }
|
|
|
|
outlet10RebootTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to remain off when a Reboot command is issued."
|
|
::= { outlet10 5 }
|
|
|
|
outlet11Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive outlet name"
|
|
::= { outlet11 1 }
|
|
|
|
outlet11PingIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ping watchdog IP address"
|
|
::= { outlet11 2 }
|
|
|
|
outlet11Link OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"URL of web configuration interface for the device connected to this outlet."
|
|
::= { outlet11 3 }
|
|
|
|
outlet11SequenceTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to delay turning on after a Sequence On command is issued."
|
|
::= { outlet11 4 }
|
|
|
|
outlet11RebootTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to remain off when a Reboot command is issued."
|
|
::= { outlet11 5 }
|
|
|
|
outlet12Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive outlet name"
|
|
::= { outlet12 1 }
|
|
|
|
outlet12PingIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ping watchdog IP address"
|
|
::= { outlet12 2 }
|
|
|
|
outlet12Link OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"URL of web configuration interface for the device connected to this outlet."
|
|
::= { outlet12 3 }
|
|
|
|
outlet12SequenceTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to delay turning on after a Sequence On command is issued."
|
|
::= { outlet12 4 }
|
|
|
|
outlet12RebootTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to remain off when a Reboot command is issued."
|
|
::= { outlet12 5 }
|
|
|
|
outlet13Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive outlet name"
|
|
::= { outlet13 1 }
|
|
|
|
outlet13PingIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ping watchdog IP address"
|
|
::= { outlet13 2 }
|
|
|
|
outlet13Link OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"URL of web configuration interface for the device connected to this outlet."
|
|
::= { outlet13 3 }
|
|
|
|
outlet13SequenceTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to delay turning on after a Sequence On command is issued."
|
|
::= { outlet13 4 }
|
|
|
|
outlet13RebootTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to remain off when a Reboot command is issued."
|
|
::= { outlet13 5 }
|
|
|
|
outlet14Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive outlet name"
|
|
::= { outlet14 1 }
|
|
|
|
outlet14PingIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ping watchdog IP address"
|
|
::= { outlet14 2 }
|
|
|
|
outlet14Link OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"URL of web configuration interface for the device connected to this outlet."
|
|
::= { outlet14 3 }
|
|
|
|
outlet14SequenceTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to delay turning on after a Sequence On command is issued."
|
|
::= { outlet14 4 }
|
|
|
|
outlet14RebootTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to remain off when a Reboot command is issued."
|
|
::= { outlet14 5 }
|
|
|
|
outlet15Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive outlet name"
|
|
::= { outlet15 1 }
|
|
|
|
outlet15PingIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ping watchdog IP address"
|
|
::= { outlet15 2 }
|
|
|
|
outlet15Link OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"URL of web configuration interface for the device connected to this outlet."
|
|
::= { outlet15 3 }
|
|
|
|
outlet15SequenceTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to delay turning on after a Sequence On command is issued."
|
|
::= { outlet15 4 }
|
|
|
|
outlet15RebootTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to remain off when a Reboot command is issued."
|
|
::= { outlet15 5 }
|
|
|
|
outlet16Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive outlet name"
|
|
::= { outlet16 1 }
|
|
|
|
outlet16PingIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ping watchdog IP address"
|
|
::= { outlet16 2 }
|
|
|
|
outlet16Link OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"URL of web configuration interface for the device connected to this outlet."
|
|
::= { outlet16 3 }
|
|
|
|
outlet16SequenceTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to delay turning on after a Sequence On command is issued."
|
|
::= { outlet16 4 }
|
|
|
|
outlet16RebootTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to remain off when a Reboot command is issued."
|
|
::= { outlet16 5 }
|
|
|
|
outlet17Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive outlet name"
|
|
::= { outlet17 1 }
|
|
|
|
outlet17PingIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ping watchdog IP address"
|
|
::= { outlet17 2 }
|
|
|
|
outlet17Link OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"URL of web configuration interface for the device connected to this outlet."
|
|
::= { outlet17 3 }
|
|
|
|
outlet17SequenceTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to delay turning on after a Sequence On command is issued."
|
|
::= { outlet17 4 }
|
|
|
|
outlet17RebootTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to remain off when a Reboot command is issued."
|
|
::= { outlet17 5 }
|
|
|
|
outlet18Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive outlet name"
|
|
::= { outlet18 1 }
|
|
|
|
outlet18PingIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ping watchdog IP address"
|
|
::= { outlet18 2 }
|
|
|
|
outlet18Link OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"URL of web configuration interface for the device connected to this outlet."
|
|
::= { outlet18 3 }
|
|
|
|
outlet18SequenceTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to delay turning on after a Sequence On command is issued."
|
|
::= { outlet18 4 }
|
|
|
|
outlet18RebootTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to remain off when a Reboot command is issued."
|
|
::= { outlet18 5 }
|
|
|
|
outlet19Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive outlet name"
|
|
::= { outlet19 1 }
|
|
|
|
outlet19PingIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ping watchdog IP address"
|
|
::= { outlet19 2 }
|
|
|
|
outlet19Link OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"URL of web configuration interface for the device connected to this outlet."
|
|
::= { outlet19 3 }
|
|
|
|
outlet19SequenceTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to delay turning on after a Sequence On command is issued."
|
|
::= { outlet19 4 }
|
|
|
|
outlet19RebootTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to remain off when a Reboot command is issued."
|
|
::= { outlet19 5 }
|
|
|
|
outlet20Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive outlet name"
|
|
::= { outlet20 1 }
|
|
|
|
outlet20PingIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ping watchdog IP address"
|
|
::= { outlet20 2 }
|
|
|
|
outlet20Link OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"URL of web configuration interface for the device connected to this outlet."
|
|
::= { outlet20 3 }
|
|
|
|
outlet20SequenceTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to delay turning on after a Sequence On command is issued."
|
|
::= { outlet20 4 }
|
|
|
|
outlet20RebootTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to remain off when a Reboot command is issued."
|
|
::= { outlet20 5 }
|
|
|
|
outlet21Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive outlet name"
|
|
::= { outlet21 1 }
|
|
|
|
outlet21PingIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ping watchdog IP address"
|
|
::= { outlet21 2 }
|
|
|
|
outlet21Link OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"URL of web configuration interface for the device connected to this outlet."
|
|
::= { outlet21 3 }
|
|
|
|
outlet21SequenceTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to delay turning on after a Sequence On command is issued."
|
|
::= { outlet21 4 }
|
|
|
|
outlet21RebootTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to remain off when a Reboot command is issued."
|
|
::= { outlet21 5 }
|
|
|
|
outlet22Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive outlet name"
|
|
::= { outlet22 1 }
|
|
|
|
outlet22PingIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ping watchdog IP address"
|
|
::= { outlet22 2 }
|
|
|
|
outlet22Link OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"URL of web configuration interface for the device connected to this outlet."
|
|
::= { outlet22 3 }
|
|
|
|
outlet22SequenceTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to delay turning on after a Sequence On command is issued."
|
|
::= { outlet22 4 }
|
|
|
|
outlet22RebootTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to remain off when a Reboot command is issued."
|
|
::= { outlet22 5 }
|
|
|
|
outlet23Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive outlet name"
|
|
::= { outlet23 1 }
|
|
|
|
outlet23PingIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ping watchdog IP address"
|
|
::= { outlet23 2 }
|
|
|
|
outlet23Link OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"URL of web configuration interface for the device connected to this outlet."
|
|
::= { outlet23 3 }
|
|
|
|
outlet23SequenceTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to delay turning on after a Sequence On command is issued."
|
|
::= { outlet23 4 }
|
|
|
|
outlet23RebootTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to remain off when a Reboot command is issued."
|
|
::= { outlet23 5 }
|
|
|
|
outlet24Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive outlet name"
|
|
::= { outlet24 1 }
|
|
|
|
outlet24PingIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ping watchdog IP address"
|
|
::= { outlet24 2 }
|
|
|
|
outlet24Link OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"URL of web configuration interface for the device connected to this outlet."
|
|
::= { outlet24 3 }
|
|
|
|
outlet24SequenceTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to delay turning on after a Sequence On command is issued."
|
|
::= { outlet24 4 }
|
|
|
|
outlet24RebootTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to remain off when a Reboot command is issued."
|
|
::= { outlet24 5 }
|
|
|
|
outlet25Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive outlet name"
|
|
::= { outlet25 1 }
|
|
|
|
outlet25PingIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ping watchdog IP address"
|
|
::= { outlet25 2 }
|
|
|
|
outlet25Link OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"URL of web configuration interface for the device connected to this outlet."
|
|
::= { outlet25 3 }
|
|
|
|
outlet25SequenceTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to delay turning on after a Sequence On command is issued."
|
|
::= { outlet25 4 }
|
|
|
|
outlet25RebootTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to remain off when a Reboot command is issued."
|
|
::= { outlet25 5 }
|
|
|
|
outlet26Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive outlet name"
|
|
::= { outlet26 1 }
|
|
|
|
outlet26PingIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ping watchdog IP address"
|
|
::= { outlet26 2 }
|
|
|
|
outlet26Link OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"URL of web configuration interface for the device connected to this outlet."
|
|
::= { outlet26 3 }
|
|
|
|
outlet26SequenceTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to delay turning on after a Sequence On command is issued."
|
|
::= { outlet26 4 }
|
|
|
|
outlet26RebootTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to remain off when a Reboot command is issued."
|
|
::= { outlet26 5 }
|
|
|
|
outlet27Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive outlet name"
|
|
::= { outlet27 1 }
|
|
|
|
outlet27PingIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ping watchdog IP address"
|
|
::= { outlet27 2 }
|
|
|
|
outlet27Link OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"URL of web configuration interface for the device connected to this outlet."
|
|
::= { outlet27 3 }
|
|
|
|
outlet27SequenceTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to delay turning on after a Sequence On command is issued."
|
|
::= { outlet27 4 }
|
|
|
|
outlet27RebootTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to remain off when a Reboot command is issued."
|
|
::= { outlet27 5 }
|
|
|
|
outlet28Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive outlet name"
|
|
::= { outlet28 1 }
|
|
|
|
outlet28PingIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ping watchdog IP address"
|
|
::= { outlet28 2 }
|
|
|
|
outlet28Link OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"URL of web configuration interface for the device connected to this outlet."
|
|
::= { outlet28 3 }
|
|
|
|
outlet28SequenceTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to delay turning on after a Sequence On command is issued."
|
|
::= { outlet28 4 }
|
|
|
|
outlet28RebootTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to remain off when a Reboot command is issued."
|
|
::= { outlet28 5 }
|
|
|
|
outlet29Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive outlet name"
|
|
::= { outlet29 1 }
|
|
|
|
outlet29PingIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ping watchdog IP address"
|
|
::= { outlet29 2 }
|
|
|
|
outlet29Link OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"URL of web configuration interface for the device connected to this outlet."
|
|
::= { outlet29 3 }
|
|
|
|
outlet29SequenceTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to delay turning on after a Sequence On command is issued."
|
|
::= { outlet29 4 }
|
|
|
|
outlet29RebootTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to remain off when a Reboot command is issued."
|
|
::= { outlet29 5 }
|
|
|
|
outlet30Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive outlet name"
|
|
::= { outlet30 1 }
|
|
|
|
outlet30PingIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ping watchdog IP address"
|
|
::= { outlet30 2 }
|
|
|
|
outlet30Link OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"URL of web configuration interface for the device connected to this outlet."
|
|
::= { outlet30 3 }
|
|
|
|
outlet30SequenceTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to delay turning on after a Sequence On command is issued."
|
|
::= { outlet30 4 }
|
|
|
|
outlet30RebootTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to remain off when a Reboot command is issued."
|
|
::= { outlet30 5 }
|
|
|
|
outlet31Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive outlet name"
|
|
::= { outlet31 1 }
|
|
|
|
outlet31PingIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ping watchdog IP address"
|
|
::= { outlet31 2 }
|
|
|
|
outlet31Link OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"URL of web configuration interface for the device connected to this outlet."
|
|
::= { outlet31 3 }
|
|
|
|
outlet31SequenceTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to delay turning on after a Sequence On command is issued."
|
|
::= { outlet31 4 }
|
|
|
|
outlet31RebootTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to remain off when a Reboot command is issued."
|
|
::= { outlet31 5 }
|
|
|
|
outlet32Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive outlet name"
|
|
::= { outlet32 1 }
|
|
|
|
outlet32PingIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ping watchdog IP address"
|
|
::= { outlet32 2 }
|
|
|
|
outlet32Link OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"URL of web configuration interface for the device connected to this outlet."
|
|
::= { outlet32 3 }
|
|
|
|
outlet32SequenceTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to delay turning on after a Sequence On command is issued."
|
|
::= { outlet32 4 }
|
|
|
|
outlet32RebootTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to remain off when a Reboot command is issued."
|
|
::= { outlet32 5 }
|
|
|
|
outlet33Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive outlet name"
|
|
::= { outlet33 1 }
|
|
|
|
outlet33PingIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ping watchdog IP address"
|
|
::= { outlet33 2 }
|
|
|
|
outlet33Link OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"URL of web configuration interface for the device connected to this outlet."
|
|
::= { outlet33 3 }
|
|
|
|
outlet33SequenceTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to delay turning on after a Sequence On command is issued."
|
|
::= { outlet33 4 }
|
|
|
|
outlet33RebootTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to remain off when a Reboot command is issued."
|
|
::= { outlet33 5 }
|
|
|
|
outlet34Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive outlet name"
|
|
::= { outlet34 1 }
|
|
|
|
outlet34PingIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ping watchdog IP address"
|
|
::= { outlet34 2 }
|
|
|
|
outlet34Link OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"URL of web configuration interface for the device connected to this outlet."
|
|
::= { outlet34 3 }
|
|
|
|
outlet34SequenceTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to delay turning on after a Sequence On command is issued."
|
|
::= { outlet34 4 }
|
|
|
|
outlet34RebootTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to remain off when a Reboot command is issued."
|
|
::= { outlet34 5 }
|
|
|
|
outlet35Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive outlet name"
|
|
::= { outlet35 1 }
|
|
|
|
outlet35PingIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ping watchdog IP address"
|
|
::= { outlet35 2 }
|
|
|
|
outlet35Link OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"URL of web configuration interface for the device connected to this outlet."
|
|
::= { outlet35 3 }
|
|
|
|
outlet35SequenceTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to delay turning on after a Sequence On command is issued."
|
|
::= { outlet35 4 }
|
|
|
|
outlet35RebootTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to remain off when a Reboot command is issued."
|
|
::= { outlet35 5 }
|
|
|
|
outlet36Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive outlet name"
|
|
::= { outlet36 1 }
|
|
|
|
outlet36PingIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ping watchdog IP address"
|
|
::= { outlet36 2 }
|
|
|
|
outlet36Link OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"URL of web configuration interface for the device connected to this outlet."
|
|
::= { outlet36 3 }
|
|
|
|
outlet36SequenceTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to delay turning on after a Sequence On command is issued."
|
|
::= { outlet36 4 }
|
|
|
|
outlet36RebootTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds for the outlet to remain off when a Reboot command is issued."
|
|
::= { outlet36 5 }
|
|
|
|
globalCommand OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
nochange (0),
|
|
globalOn (1),
|
|
globalOff (2),
|
|
sequenceOn (3),
|
|
sequenceOff (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Issue a command to all outlets on this unit."
|
|
::= { outletControl 1 }
|
|
|
|
outlet1Command OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOn (1),
|
|
immediateOff (2),
|
|
reboot (3),
|
|
nochange (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Issue an outlet command"
|
|
::= { outletControl 2 }
|
|
|
|
outlet2Command OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOn (1),
|
|
immediateOff (2),
|
|
reboot (3),
|
|
nochange (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Issue an outlet command"
|
|
::= { outletControl 3 }
|
|
|
|
outlet3Command OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOn (1),
|
|
immediateOff (2),
|
|
reboot (3),
|
|
nochange (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Issue an outlet command"
|
|
::= { outletControl 4 }
|
|
|
|
outlet4Command OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOn (1),
|
|
immediateOff (2),
|
|
reboot (3),
|
|
nochange (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Issue an outlet command"
|
|
::= { outletControl 5 }
|
|
|
|
outlet5Command OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOn (1),
|
|
immediateOff (2),
|
|
reboot (3),
|
|
nochange (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Issue an outlet command"
|
|
::= { outletControl 6 }
|
|
|
|
outlet6Command OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOn (1),
|
|
immediateOff (2),
|
|
reboot (3),
|
|
nochange (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Issue an outlet command"
|
|
::= { outletControl 7 }
|
|
|
|
outlet7Command OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOn (1),
|
|
immediateOff (2),
|
|
reboot (3),
|
|
nochange (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Issue an outlet command"
|
|
::= { outletControl 8 }
|
|
|
|
outlet8Command OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOn (1),
|
|
immediateOff (2),
|
|
reboot (3),
|
|
nochange (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Issue an outlet command"
|
|
::= { outletControl 9 }
|
|
|
|
outlet9Command OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOn (1),
|
|
immediateOff (2),
|
|
reboot (3),
|
|
nochange (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Issue an outlet command"
|
|
::= { outletControl 10 }
|
|
|
|
outlet10Command OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOn (1),
|
|
immediateOff (2),
|
|
reboot (3),
|
|
nochange (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Issue an outlet command"
|
|
::= { outletControl 11 }
|
|
|
|
outlet11Command OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOn (1),
|
|
immediateOff (2),
|
|
reboot (3),
|
|
nochange (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Issue an outlet command"
|
|
::= { outletControl 12 }
|
|
|
|
outlet12Command OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOn (1),
|
|
immediateOff (2),
|
|
reboot (3),
|
|
noChange (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Issue an outlet command"
|
|
::= { outletControl 13 }
|
|
|
|
outlet13Command OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOn (1),
|
|
immediateOff (2),
|
|
reboot (3),
|
|
nochange (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Issue an outlet command"
|
|
::= { outletControl 14 }
|
|
|
|
outlet14Command OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOn (1),
|
|
immediateOff (2),
|
|
reboot (3),
|
|
nochange (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Issue an outlet command"
|
|
::= { outletControl 15 }
|
|
|
|
outlet15Command OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOn (1),
|
|
immediateOff (2),
|
|
reboot (3),
|
|
nochange (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Issue an outlet command"
|
|
::= { outletControl 16 }
|
|
|
|
outlet16Command OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOn (1),
|
|
immediateOff (2),
|
|
reboot (3),
|
|
nochange (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Issue an outlet command"
|
|
::= { outletControl 17 }
|
|
|
|
outlet17Command OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOn (1),
|
|
immediateOff (2),
|
|
reboot (3),
|
|
nochange (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Issue an outlet command"
|
|
::= { outletControl 18 }
|
|
|
|
outlet18Command OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOn (1),
|
|
immediateOff (2),
|
|
reboot (3),
|
|
nochange (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Issue an outlet command"
|
|
::= { outletControl 19 }
|
|
|
|
outlet19Command OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOn (1),
|
|
immediateOff (2),
|
|
reboot (3),
|
|
nochange (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Issue an outlet command"
|
|
::= { outletControl 20 }
|
|
|
|
outlet20Command OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOn (1),
|
|
immediateOff (2),
|
|
reboot (3),
|
|
nochange (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Issue an outlet command"
|
|
::= { outletControl 21 }
|
|
|
|
outlet21Command OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOn (1),
|
|
immediateOff (2),
|
|
reboot (3),
|
|
nochange (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Issue an outlet command"
|
|
::= { outletControl 22 }
|
|
|
|
outlet22Command OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOn (1),
|
|
immediateOff (2),
|
|
reboot (3),
|
|
nochange (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Issue an outlet command"
|
|
::= { outletControl 23 }
|
|
|
|
outlet23Command OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOn (1),
|
|
immediateOff (2),
|
|
reboot (3),
|
|
nochange (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Issue an outlet command"
|
|
::= { outletControl 24 }
|
|
|
|
outlet24Command OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOn (1),
|
|
immediateOff (2),
|
|
reboot (3),
|
|
nochange (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Issue an outlet command"
|
|
::= { outletControl 25 }
|
|
|
|
outlet25Command OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOn (1),
|
|
immediateOff (2),
|
|
reboot (3),
|
|
nochange (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Issue an outlet command"
|
|
::= { outletControl 26 }
|
|
|
|
outlet26Command OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOn (1),
|
|
immediateOff (2),
|
|
reboot (3),
|
|
nochange (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Issue an outlet command"
|
|
::= { outletControl 27 }
|
|
|
|
outlet27Command OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOn (1),
|
|
immediateOff (2),
|
|
reboot (3),
|
|
nochange (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Issue an outlet command"
|
|
::= { outletControl 28 }
|
|
|
|
outlet28Command OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOn (1),
|
|
immediateOff (2),
|
|
reboot (3),
|
|
nochange (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Issue an outlet command"
|
|
::= { outletControl 29 }
|
|
|
|
outlet29Command OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOn (1),
|
|
immediateOff (2),
|
|
reboot (3),
|
|
nochange (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Issue an outlet command"
|
|
::= { outletControl 30 }
|
|
|
|
outlet30Command OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOn (1),
|
|
immediateOff (2),
|
|
reboot (3),
|
|
nochange (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Issue an outlet command"
|
|
::= { outletControl 31 }
|
|
|
|
outlet31Command OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOn (1),
|
|
immediateOff (2),
|
|
reboot (3),
|
|
nochange (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Issue an outlet command"
|
|
::= { outletControl 32 }
|
|
|
|
outlet32Command OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOn (1),
|
|
immediateOff (2),
|
|
reboot (3),
|
|
nochange (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Issue an outlet command"
|
|
::= { outletControl 33 }
|
|
|
|
outlet33Command OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOn (1),
|
|
immediateOff (2),
|
|
reboot (3),
|
|
nochange (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Issue an outlet command"
|
|
::= { outletControl 34 }
|
|
|
|
outlet34Command OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOn (1),
|
|
immediateOff (2),
|
|
reboot (3),
|
|
nochange (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Issue an outlet command"
|
|
::= { outletControl 35 }
|
|
|
|
outlet35Command OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOn (1),
|
|
immediateOff (2),
|
|
reboot (3),
|
|
nochange (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Issue an outlet command"
|
|
::= { outletControl 36 }
|
|
|
|
outlet36Command OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOn (1),
|
|
immediateOff (2),
|
|
reboot (3),
|
|
nochange (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Issue an outlet command"
|
|
::= { outletControl 37 }
|
|
|
|
outlet1Status OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on (1),
|
|
off (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get the outlet status"
|
|
::= { outletStatus 1 }
|
|
|
|
outlet2Status OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on (1),
|
|
off (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get the outlet status"
|
|
::= { outletStatus 2 }
|
|
|
|
outlet3Status OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on (1),
|
|
off (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get the outlet status"
|
|
::= { outletStatus 3 }
|
|
|
|
outlet4Status OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on (1),
|
|
off (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get the outlet status"
|
|
::= { outletStatus 4 }
|
|
|
|
outlet5Status OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on (1),
|
|
off (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get the outlet status"
|
|
::= { outletStatus 5 }
|
|
|
|
outlet6Status OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on (1),
|
|
off (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get the outlet status"
|
|
::= { outletStatus 6 }
|
|
|
|
outlet7Status OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on (1),
|
|
off (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get the outlet status"
|
|
::= { outletStatus 7 }
|
|
|
|
outlet8Status OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on (1),
|
|
off (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get the outlet status"
|
|
::= { outletStatus 8 }
|
|
|
|
outlet9Status OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on (1),
|
|
off (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get the outlet status"
|
|
::= { outletStatus 9 }
|
|
|
|
outlet10Status OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on (1),
|
|
off (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get the outlet status"
|
|
::= { outletStatus 10 }
|
|
|
|
outlet11Status OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on (1),
|
|
off (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get the outlet status"
|
|
::= { outletStatus 11 }
|
|
|
|
outlet12Status OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on (1),
|
|
off (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get the outlet status"
|
|
::= { outletStatus 12 }
|
|
|
|
outlet13Status OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on (1),
|
|
off (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get the outlet status"
|
|
::= { outletStatus 13 }
|
|
|
|
outlet14Status OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on (1),
|
|
off (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get the outlet status"
|
|
::= { outletStatus 14 }
|
|
|
|
outlet15Status OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on (1),
|
|
off (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get the outlet status"
|
|
::= { outletStatus 15 }
|
|
|
|
outlet16Status OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on (1),
|
|
off (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get the outlet status"
|
|
::= { outletStatus 16 }
|
|
|
|
outlet17Status OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on (1),
|
|
off (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get the outlet status"
|
|
::= { outletStatus 17 }
|
|
|
|
outlet18Status OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on (1),
|
|
off (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get the outlet status"
|
|
::= { outletStatus 18 }
|
|
|
|
outlet19Status OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on (1),
|
|
off (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get the outlet status"
|
|
::= { outletStatus 19 }
|
|
|
|
outlet20Status OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on (1),
|
|
off (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get the outlet status"
|
|
::= { outletStatus 20 }
|
|
|
|
outlet21Status OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on (1),
|
|
off (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get the outlet status"
|
|
::= { outletStatus 21 }
|
|
|
|
outlet22Status OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on (1),
|
|
off (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get the outlet status"
|
|
::= { outletStatus 22 }
|
|
|
|
outlet23Status OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on (1),
|
|
off (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get the outlet status"
|
|
::= { outletStatus 23 }
|
|
|
|
outlet24Status OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on (1),
|
|
off (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get the outlet status"
|
|
::= { outletStatus 24 }
|
|
|
|
outlet25Status OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on (1),
|
|
off (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get the outlet status"
|
|
::= { outletStatus 25 }
|
|
|
|
outlet26Status OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on (1),
|
|
off (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get the outlet status"
|
|
::= { outletStatus 26 }
|
|
|
|
outlet27Status OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on (1),
|
|
off (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get the outlet status"
|
|
::= { outletStatus 27 }
|
|
|
|
outlet28Status OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on (1),
|
|
off (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get the outlet status"
|
|
::= { outletStatus 28 }
|
|
|
|
outlet29Status OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on (1),
|
|
off (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get the outlet status"
|
|
::= { outletStatus 29 }
|
|
|
|
outlet30Status OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on (1),
|
|
off (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get the outlet status"
|
|
::= { outletStatus 30 }
|
|
|
|
outlet31Status OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on (1),
|
|
off (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get the outlet status"
|
|
::= { outletStatus 31 }
|
|
|
|
outlet32Status OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on (1),
|
|
off (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get the outlet status"
|
|
::= { outletStatus 32 }
|
|
|
|
outlet33Status OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on (1),
|
|
off (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get the outlet status"
|
|
::= { outletStatus 33 }
|
|
|
|
outlet34Status OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on (1),
|
|
off (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get the outlet status"
|
|
::= { outletStatus 34 }
|
|
|
|
outlet35Status OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on (1),
|
|
off (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get the outlet status"
|
|
::= { outletStatus 35 }
|
|
|
|
outlet36Status OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on (1),
|
|
off (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get the outlet status"
|
|
::= { outletStatus 36 }
|
|
|
|
publicCommunityName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS not-accessible
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Enter the read-only community name. Default public"
|
|
::= { snmpSettings 1 }
|
|
|
|
privateCommunityName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS not-accessible
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Enter the read-write community name. Default private"
|
|
::= { snmpSettings 2 }
|
|
|
|
trapCommunityName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS not-accessible
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Enter the Trap community name. Default public"
|
|
::= { snmpSettings 3 }
|
|
|
|
publicCommunityPassword OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS not-accessible
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Enter the read-only community password. Default public"
|
|
::= { snmpSettings 4 }
|
|
|
|
privateCommunityPassword OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS not-accessible
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Enter the read-write community password. Default private"
|
|
::= { snmpSettings 5 }
|
|
|
|
trapIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enter the IP address to which to send SNMP traps."
|
|
::= { snmpSettings 6 }
|
|
|
|
snmpEnabled OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
MAX-ACCESS not-accessible
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Enabled setting for SNMP interface"
|
|
::= { snmpSettings 7 }
|
|
|
|
trapUserLoginLogout OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enabled setting to send an SNMP trap when a user logs in/out of the serial, telnet, or web interfaces."
|
|
::= { snmpTraps 1 }
|
|
|
|
trapFailedLogin OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enabled setting to send an SNMP trap when a user fails to log into the serial, telnet, or web interfaces because of a username or password mismatch."
|
|
::= { snmpTraps 2 }
|
|
|
|
trapOutletActivity OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enabled setting to send an SNMP trap whenever an outlet changes state."
|
|
::= { snmpTraps 3 }
|
|
|
|
trapSystemOnOff OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enabled setting to send an SNMP trap when the PDU powers up."
|
|
::= { snmpTraps 4 }
|
|
|
|
trapOutletSection1Threshold OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enabled setting to send an SNMP trap when the section 1 thresholds are breached."
|
|
::= { snmpTraps 5 }
|
|
|
|
trapOutletSection2Threshold OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enabled setting to send an SNMP trap when the section 2 thresholds are breached."
|
|
::= { snmpTraps 6 }
|
|
|
|
trapOutletSection3Threshold OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enabled setting to send an SNMP trap when the section 3 thresholds are breached."
|
|
::= { snmpTraps 7 }
|
|
|
|
trapTemperatureSensor1Threshold OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enabled setting to send an SNMP trap when the temperature 1 sensor thresholds are breached."
|
|
::= { snmpTraps 8 }
|
|
|
|
trapTemperatureSensor2Threshold OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enabled setting to send an SNMP trap when the temperature 2 sensor thresholds are breached."
|
|
::= { snmpTraps 9 }
|
|
|
|
trapHumiditySensorThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enabled setting to send an SNMP trap when the humidity sensor thresholds are breached."
|
|
::= { snmpTraps 10 }
|
|
|
|
trapContactClosure1Threshold OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enabled setting to send an SNMP trap when the contact sensor 1 state changes."
|
|
::= { snmpTraps 11 }
|
|
|
|
trapContactClosure2Threshold OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enabled setting to send an SNMP trap when the contact sensor 2 state changes."
|
|
::= { snmpTraps 12 }
|
|
|
|
trapContactClosure3Threshold OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enabled setting to send an SNMP trap when the contact sensor 3 state changes."
|
|
::= { snmpTraps 13 }
|
|
|
|
tempSensor1Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive sensor name"
|
|
::= { tempSensor1 1 }
|
|
|
|
tempSensor1Enable OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When disabled, the sensor measurement is not displayed and the thresholds are ignored."
|
|
::= { tempSensor1 2 }
|
|
|
|
tempSensor1HighThresh OBJECT-TYPE
|
|
SYNTAX Integer32 (-100..300)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sensor high threshold"
|
|
::= { tempSensor1 3 }
|
|
|
|
tempSensor1LowThresh OBJECT-TYPE
|
|
SYNTAX Integer32 (-100..300)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sensor low threshold"
|
|
::= { tempSensor1 4 }
|
|
|
|
tempSensor1ControlOutlet OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enabled setting to control an outlet or group based on the sensor thresholds."
|
|
::= { tempSensor1 5 }
|
|
|
|
tempSensor1OutletName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet or group name to control based on the sensor measurement."
|
|
::= { tempSensor1 6 }
|
|
|
|
tempSensor1OutletState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
turnOutletOn (0),
|
|
turnOutletOff (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"turnOutletOn setting will turn the outlet/group on when the thresholds are breached and off when between the thresholds.
|
|
turnOutletOff setting will turn the outlet/group off when the thresholds are breached and on when between the thresholds."
|
|
::= { tempSensor1 7 }
|
|
|
|
tempSensor2Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive sensor name"
|
|
::= { tempSensor2 1 }
|
|
|
|
tempSensor2Enable OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When disabled, the sensor measurement is not displayed and the thresholds are ignored."
|
|
::= { tempSensor2 2 }
|
|
|
|
tempSensor2HighThresh OBJECT-TYPE
|
|
SYNTAX Integer32 (-100..300)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sensor high threshold"
|
|
::= { tempSensor2 3 }
|
|
|
|
tempSensor2LowThresh OBJECT-TYPE
|
|
SYNTAX Integer32 (-100..300)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sensor low threshold"
|
|
::= { tempSensor2 4 }
|
|
|
|
tempSensor2ControlOutlet OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enabled setting to control an outlet or group based on the sensor thresholds."
|
|
::= { tempSensor2 5 }
|
|
|
|
tempSensor2OutletName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet or group name to control based on the sensor measurement."
|
|
::= { tempSensor2 6 }
|
|
|
|
tempSensor2OutletState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
turnOutletOn (0),
|
|
turnOutletOff (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"turnOutletOn setting will turn the outlet/group on when the thresholds are breached and off when between the thresholds.
|
|
turnOutletOff setting will turn the outlet/group off when the thresholds are breached and on when between the thresholds."
|
|
::= { tempSensor2 7 }
|
|
|
|
humSensor1Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive sensor name"
|
|
::= { humSensor1 1 }
|
|
|
|
humSensor1Enable OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When disabled, the sensor measurement is not displayed and the thresholds are ignored."
|
|
::= { humSensor1 2 }
|
|
|
|
humSensor1HighThresh OBJECT-TYPE
|
|
SYNTAX Integer32 (0..100)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sensor high threshold"
|
|
::= { humSensor1 3 }
|
|
|
|
humSensor1LowThresh OBJECT-TYPE
|
|
SYNTAX Integer32 (0..100)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sensor low threshold"
|
|
::= { humSensor1 4 }
|
|
|
|
humSensor1ControlOutlet OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enabled setting to control an outlet or group based on the sensor thresholds."
|
|
::= { humSensor1 5 }
|
|
|
|
humSensor1OutletName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet or group name to control based on the sensor measurement."
|
|
::= { humSensor1 6 }
|
|
|
|
humSensor1OutletState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
turnOutletOn (0),
|
|
turnOutletOff (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"turnOutletOn setting will turn the outlet/group on when the thresholds are breached and off when between the thresholds.
|
|
turnOutletOff setting will turn the outlet/group off when the thresholds are breached and on when between the thresholds."
|
|
::= { humSensor1 7 }
|
|
|
|
contactClosure1Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive sensor name"
|
|
::= { contactClosure1 1 }
|
|
|
|
contactClosure1Enable OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When disabled, the sensor measurement is not displayed and the contact state is ignored."
|
|
::= { contactClosure1 2 }
|
|
|
|
contactClosure1ControlOutlet OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enabled setting to control an outlet or group based on the contact state."
|
|
::= { contactClosure1 3 }
|
|
|
|
contactClosure1OutletName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet or group name to control based on the contact state."
|
|
::= { contactClosure1 4 }
|
|
|
|
contactClosure1OutletState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
turnOutletOn (0),
|
|
turnOutletOff (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"turnOutletOn setting will turn the outlet/group on when the contact is closed and off when the contact is open.
|
|
turnOutletOff setting will turn the outlet/group off when the contact is open and on when the contact is closed."
|
|
::= { contactClosure1 5 }
|
|
|
|
contactClosure2Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive sensor name"
|
|
::= { contactClosure2 1 }
|
|
|
|
contactClosure2Enable OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When disabled, the sensor measurement is not displayed and the contact state is ignored."
|
|
::= { contactClosure2 2 }
|
|
|
|
contactClosure2ControlOutlet OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enabled setting to control an outlet or group based on the contact state."
|
|
::= { contactClosure2 3 }
|
|
|
|
contactClosure2OutletName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet or group name to control based on the contact state."
|
|
::= { contactClosure2 4 }
|
|
|
|
contactClosure2OutletState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
turnOutletOn (0),
|
|
turnOutletOff (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"turnOutletOn setting will turn the outlet/group on when the contact is closed and off when the contact is open.
|
|
turnOutletOff setting will turn the outlet/group off when the contact is open and on when the contact is closed."
|
|
::= { contactClosure2 5 }
|
|
|
|
contactClosure3Name OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive sensor name"
|
|
::= { contactClosure3 1 }
|
|
|
|
contactClosure3Enable OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When disabled, the sensor measurement is not displayed and the contact state is ignored."
|
|
::= { contactClosure3 2 }
|
|
|
|
contactClosure3ControlOutlet OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enabled setting to control an outlet or group based on the contact state."
|
|
::= { contactClosure3 3 }
|
|
|
|
contactClosure3OutletName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet or group name to control based on the contact state."
|
|
::= { contactClosure3 4 }
|
|
|
|
contactClosure3OutletState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
turnOutletOn (0),
|
|
turnOutletOff (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"turnOutletOn setting will turn the outlet/group on when the contact is closed and off when the contact is open.
|
|
turnOutletOff setting will turn the outlet/group off when the contact is open and on when the contact is closed."
|
|
::= { contactClosure3 5 }
|
|
|
|
outletSection1VoltageHighThreshold OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Upper threshold for section voltage measurement"
|
|
::= { outletSection1Config 1 }
|
|
|
|
outletSection1VoltageLowThreshold OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Lower threshold for section voltage measurement"
|
|
::= { outletSection1Config 2 }
|
|
|
|
outletSection1CurrentHighThreshold OBJECT-TYPE
|
|
SYNTAX Integer32 (0..20)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Upper threshold for section current measurement"
|
|
::= { outletSection1Config 3 }
|
|
|
|
outletSection1CurrentLowThreshold OBJECT-TYPE
|
|
SYNTAX Integer32 (0..20)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Lower threshold for section current measurement"
|
|
::= { outletSection1Config 4 }
|
|
|
|
outletSection1ControlOutlet OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enabled setting to control an outlet or group based on the section voltage and current thresholds."
|
|
::= { outletSection1Config 5 }
|
|
|
|
outletSection1OutletName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet or group name to control based on the section voltage and current measurement."
|
|
::= { outletSection1Config 6 }
|
|
|
|
outletSection2VoltageHighThreshold OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Upper threshold for section voltage measurement"
|
|
::= { outletSection2Config 1 }
|
|
|
|
outletSection2VoltageLowThreshold OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Lower threshold for section voltage measurement"
|
|
::= { outletSection2Config 2 }
|
|
|
|
outletSection2CurrentHighThreshold OBJECT-TYPE
|
|
SYNTAX Integer32 (0..20)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Upper threshold for section current measurement"
|
|
::= { outletSection2Config 3 }
|
|
|
|
outletSection2CurrentLowThreshold OBJECT-TYPE
|
|
SYNTAX Integer32 (0..20)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Lower threshold for section current measurement"
|
|
::= { outletSection2Config 4 }
|
|
|
|
outletSection2ControlOutlet OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enabled setting to control an outlet or group based on the section voltage and current thresholds."
|
|
::= { outletSection2Config 5 }
|
|
|
|
outletSection2OutletName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet or group name to control based on the section voltage and current measurement."
|
|
::= { outletSection2Config 6 }
|
|
|
|
outletSection3VoltageHighThreshold OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Upper threshold for section voltage measurement"
|
|
::= { outletSection3Config 1 }
|
|
|
|
outletSection3VoltageLowThreshold OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Lower threshold for section voltage measurement"
|
|
::= { outletSection3Config 2 }
|
|
|
|
outletSection3CurrentHighThreshold OBJECT-TYPE
|
|
SYNTAX Integer32 (0..20)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Upper threshold for section current measurement"
|
|
::= { outletSection3Config 3 }
|
|
|
|
outletSection3CurrentLowThreshold OBJECT-TYPE
|
|
SYNTAX Integer32 (0..20)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Lower threshold for section current measurement"
|
|
::= { outletSection3Config 4 }
|
|
|
|
outletSection3ControlOutlet OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enabled setting to control an outlet or group based on the section voltage and current thresholds."
|
|
::= { outletSection3Config 5 }
|
|
|
|
outletSection3OutletName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet or group name to control based on the section voltage and current measurement."
|
|
::= { outletSection3Config 6 }
|
|
|
|
outletSection4VoltageHighThreshold OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Upper threshold for section voltage measurement"
|
|
::= { outletSection4Config 1 }
|
|
|
|
outletSection4VoltageLowThreshold OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Lower threshold for section voltage measurement"
|
|
::= { outletSection4Config 2 }
|
|
|
|
outletSection4CurrentHighThreshold OBJECT-TYPE
|
|
SYNTAX Integer32 (0..20)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Upper threshold for section current measurement"
|
|
::= { outletSection4Config 3 }
|
|
|
|
outletSection4CurrentLowThreshold OBJECT-TYPE
|
|
SYNTAX Integer32 (0..20)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Lower threshold for section current measurement"
|
|
::= { outletSection4Config 4 }
|
|
|
|
outletSection4ControlOutlet OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enabled setting to control an outlet or group based on the section voltage and current thresholds."
|
|
::= { outletSection4Config 5 }
|
|
|
|
outletSection4OutletName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet or group name to control based on the section voltage and current measurement."
|
|
::= { outletSection4Config 6 }
|
|
|
|
outletSection5VoltageHighThreshold OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Upper threshold for section voltage measurement"
|
|
::= { outletSection5Config 1 }
|
|
|
|
outletSection5VoltageLowThreshold OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Lower threshold for section voltage measurement"
|
|
::= { outletSection5Config 2 }
|
|
|
|
outletSection5CurrentHighThreshold OBJECT-TYPE
|
|
SYNTAX Integer32 (0..20)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Upper threshold for section current measurement"
|
|
::= { outletSection5Config 3 }
|
|
|
|
outletSection5CurrentLowThreshold OBJECT-TYPE
|
|
SYNTAX Integer32 (0..20)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Lower threshold for section current measurement"
|
|
::= { outletSection5Config 4 }
|
|
|
|
outletSection5ControlOutlet OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enabled setting to control an outlet or group based on the section voltage and current thresholds."
|
|
::= { outletSection5Config 5 }
|
|
|
|
outletSection5OutletName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet or group name to control based on the section voltage and current measurement."
|
|
::= { outletSection5Config 6 }
|
|
|
|
outletSection6VoltageHighThreshold OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Upper threshold for section voltage measurement"
|
|
::= { outletSection6Config 1 }
|
|
|
|
outletSection6VoltageLowThreshold OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Lower threshold for section voltage measurement"
|
|
::= { outletSection6Config 2 }
|
|
|
|
outletSection6CurrentHighThreshold OBJECT-TYPE
|
|
SYNTAX Integer32 (0..20)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Upper threshold for section current measurement"
|
|
::= { outletSection6Config 3 }
|
|
|
|
outletSection6CurrentLowThreshold OBJECT-TYPE
|
|
SYNTAX Integer32 (0..20)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Lower threshold for section current measurement"
|
|
::= { outletSection6Config 4 }
|
|
|
|
outletSection6ControlOutlet OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled (0),
|
|
enabled (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enabled setting to control an outlet or group based on the section voltage and current thresholds."
|
|
::= { outletSection6Config 5 }
|
|
|
|
outletSection6OutletName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet or group name to control based on the section voltage and current measurement."
|
|
::= { outletSection6Config 6 }
|
|
|
|
tempSensor1Temp OBJECT-TYPE
|
|
SYNTAX Integer32 (-100..300)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature sensor measurement (units are indicated by the fahrenheitOrCelsius leaf under the unitConfig branch)"
|
|
::= { currentSensorValues 1 }
|
|
|
|
tempSensor2Temp OBJECT-TYPE
|
|
SYNTAX Integer32 (-100..300)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature sensor measurement (units are indicated by the fahrenheitOrCelsius leaf under the unitConfig branch)"
|
|
::= { currentSensorValues 2 }
|
|
|
|
humSensor1Humidity OBJECT-TYPE
|
|
SYNTAX Integer32 (0..100)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Humidity sensor measurement (percent relative humidity)"
|
|
::= { currentSensorValues 3 }
|
|
|
|
contactClosure1State OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
contactOpen (0),
|
|
contactClosed (1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Contact sensor state"
|
|
::= { currentSensorValues 4 }
|
|
|
|
contactClosure2State OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
contactOpen (0),
|
|
contactClosed (1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Contact sensor state"
|
|
::= { currentSensorValues 5 }
|
|
|
|
contactClosure3State OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
contactOpen (0),
|
|
contactClosed (1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Contact sensor state"
|
|
::= { currentSensorValues 6 }
|
|
|
|
outletSection1Voltage OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Voltage measurement 1. This is either the section 1 voltage, the Line X-Y voltage, or the Phase X-N voltage, depending on the PDU hardware."
|
|
::= { outletSection1 1 }
|
|
|
|
outletSection1Current OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Current measurement 1. This is either the section 1 current or the Phase X current, depending on the PDU hardware."
|
|
::= { outletSection1 2 }
|
|
|
|
outletSection1Va OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Section 1 VA (or phase X VA, depending on the PDU hardware)."
|
|
::= { outletSection1 3 }
|
|
|
|
outletSection2Voltage OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Voltage measurement 2. This is either the section 2 voltage, the Line Y-Z voltage, or the Phase Y-N voltage, depending on the PDU hardware."
|
|
::= { outletSection2 1 }
|
|
|
|
outletSection2Current OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Current measurement 2. This is either the section 2 current or the Phase Y current, depending on the PDU hardware."
|
|
::= { outletSection2 2 }
|
|
|
|
outletSection2Va OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Section 2 VA (or phase Y VA, depending on the PDU hardware)."
|
|
::= { outletSection2 3 }
|
|
|
|
outletSection3Voltage OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Voltage measurement 3. This is either the section 3 voltage, the Line Z-X voltage, or the Phase Z-N voltage, depending on the PDU hardware."
|
|
::= { outletSection3 1 }
|
|
|
|
outletSection3Current OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Current measurement 3. This is either the section 3 current or the Phase Z current, depending on the PDU hardware."
|
|
::= { outletSection3 2 }
|
|
|
|
outletSection3Va OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Section 3 VA (or phase Z VA, depending on the PDU hardware)."
|
|
::= { outletSection3 3 }
|
|
|
|
totalVoltage OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"None"
|
|
::= { total 1 }
|
|
|
|
totalCurrent OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sum of current for all outlet sections (or phases)"
|
|
::= { total 2 }
|
|
|
|
totalVa OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total PDU VA"
|
|
::= { total 3 }
|
|
|
|
outletSection4Voltage OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Voltage measurement 4 (section 4 voltage). This object will not be present if the PDU hardware measures Line-to-Line voltage or Phase voltage."
|
|
::= { outletSection4 1 }
|
|
|
|
outletSection4Current OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Current measurement 4. This is the section 4 current."
|
|
::= { outletSection4 2 }
|
|
|
|
outletSection4Va OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Section 4 VA"
|
|
::= { outletSection4 3 }
|
|
|
|
outletSection5Voltage OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Voltage measurement 5 (section 5 voltage). This object will not be present if the PDU hardware measures Line-to-Line voltage or Phase voltage."
|
|
::= { outletSection5 1 }
|
|
|
|
outletSection5Current OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Current measurement 5. This is the section 5 current."
|
|
::= { outletSection5 2 }
|
|
|
|
outletSection5Va OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Section 5 VA"
|
|
::= { outletSection5 3 }
|
|
|
|
outletSection6Voltage OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Voltage measurement 6 (section 6 voltage). This object will not be present if the PDU hardware measures Line-to-Line voltage or Phase voltage."
|
|
::= { outletSection6 1 }
|
|
|
|
outletSection6Current OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Current measurement 6. This is the section 6 current."
|
|
::= { outletSection6 2 }
|
|
|
|
outletSection6Va OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Section 6 VA"
|
|
::= { outletSection6 3 }
|
|
|
|
notifyOutletState NOTIFICATION-TYPE
|
|
OBJECTS { infoItemIdx,
|
|
infoItemName,
|
|
infoOutletState }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet state has changed."
|
|
::= { events 1 }
|
|
|
|
notifyCurrentThreshold NOTIFICATION-TYPE
|
|
OBJECTS { infoItemIdx,
|
|
infoItemName,
|
|
infoThresholdState,
|
|
infoThresholdValue,
|
|
infoMeasuredValue }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Current measurement has exceeded a threshold or returned from crossing a threshold."
|
|
::= { events 2 }
|
|
|
|
notifyVoltageThreshold NOTIFICATION-TYPE
|
|
OBJECTS { infoItemIdx,
|
|
infoItemName,
|
|
infoThresholdState,
|
|
infoThresholdValue,
|
|
infoMeasuredValue }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Voltage measurement has exceeded a threshold or returned from crossing a threshold."
|
|
::= { events 3 }
|
|
|
|
notifyTempSensorThreshold NOTIFICATION-TYPE
|
|
OBJECTS { infoItemIdx,
|
|
infoItemName,
|
|
infoThresholdState,
|
|
infoThresholdValue,
|
|
infoMeasuredValue,
|
|
fahrenheitOrCelsius }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature measurement has exceeded a threshold or returned from crossing a threshold."
|
|
::= { events 4 }
|
|
|
|
notifyHumidSensorThreshold NOTIFICATION-TYPE
|
|
OBJECTS { infoItemIdx,
|
|
infoItemName,
|
|
infoThresholdState,
|
|
infoThresholdValue,
|
|
infoMeasuredValue }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Humidity measurement has exceeded a threshold or returned from crossing a threshold."
|
|
::= { events 5 }
|
|
|
|
notifyContactSensorThreshold NOTIFICATION-TYPE
|
|
OBJECTS { infoItemIdx,
|
|
infoItemName,
|
|
infoContactState }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Contact sensor has changed state."
|
|
::= { events 6 }
|
|
|
|
notifyUserLogin NOTIFICATION-TYPE
|
|
OBJECTS { infoUserName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A user has logged in."
|
|
::= { events 7 }
|
|
|
|
notifyUserLogout NOTIFICATION-TYPE
|
|
OBJECTS { infoUserName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A user has logged out."
|
|
::= { events 8 }
|
|
|
|
notifyFailedLogin NOTIFICATION-TYPE
|
|
OBJECTS { infoUserName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A login failure occurred."
|
|
::= { events 9 }
|
|
|
|
notifyOutletWatchdogFailed NOTIFICATION-TYPE
|
|
OBJECTS { infoItemIdx,
|
|
infoItemName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An outlet watchdog has failed and the corresponding outlet is being rebooted."
|
|
::= { events 10 }
|
|
|
|
infoItemIdx OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Numerical index of the item that caused the notification. For example, if the notification
|
|
was related to the state of outlet 5, this value will be 5 no matter what the customized
|
|
outlet name is. Similarly, if the notification was related to a voltage threshold being
|
|
exceeded for voltage measurement 2, this value will be 2."
|
|
::= { eventInfo 1 }
|
|
|
|
infoItemName OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Textual name of the item that caused the notification. For example, if an outlet
|
|
state change caused the notification, this will be the customized name of the outlet.
|
|
If a voltage threshold caused the notification, this will be the fixed name of the voltage
|
|
measurement (e.g., Line X-Y)."
|
|
::= { eventInfo 2 }
|
|
|
|
infoOutletState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on (1),
|
|
off (2)
|
|
}
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The new state of an outlet."
|
|
::= { eventInfo 3 }
|
|
|
|
infoThresholdState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
good (0),
|
|
lowWarning (1),
|
|
highWarning (3)
|
|
}
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The new state of a measurement that has upper and lower thresholds."
|
|
::= { eventInfo 4 }
|
|
|
|
infoThresholdValue OBJECT-TYPE
|
|
SYNTAX Integer32 (-100..300)
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The threshold which has been crossed."
|
|
::= { eventInfo 5 }
|
|
|
|
infoMeasuredValue OBJECT-TYPE
|
|
SYNTAX Integer32 (-100..300)
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The actual measured value."
|
|
::= { eventInfo 6 }
|
|
|
|
infoContactState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
contactOpen (0),
|
|
contactClosed (1)
|
|
}
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The new state of a contact switch sensor."
|
|
::= { eventInfo 7 }
|
|
|
|
infoUserName OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Login name of a user."
|
|
::= { eventInfo 8 }
|
|
|
|
compliances MODULE-COMPLIANCE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The requirements for conforming to the Switched ePDU MIB."
|
|
MODULE
|
|
GROUP allObjects
|
|
DESCRIPTION
|
|
"All objects group."
|
|
GROUP allNotifications
|
|
DESCRIPTION
|
|
"All notifications group."
|
|
::= { conformance 1 }
|
|
|
|
oldCompliances MODULE-COMPLIANCE
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"Deprecated requirements for conforming to the Switched ePDU MIB."
|
|
MODULE
|
|
GROUP oldObjects
|
|
DESCRIPTION
|
|
"Deprecated objects"
|
|
::= { conformance 2 }
|
|
|
|
obsoleteCompliances MODULE-COMPLIANCE
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Obsoleted requirements for conforming to the Switched ePDU MIB."
|
|
MODULE
|
|
GROUP obsoleteObjects
|
|
DESCRIPTION
|
|
"Obsolete objects"
|
|
::= { conformance 3 }
|
|
|
|
allObjects OBJECT-GROUP
|
|
OBJECTS { baudRate,
|
|
contactClosure1Alert,
|
|
contactClosure1ControlOutlet,
|
|
contactClosure1Enable,
|
|
contactClosure1Name,
|
|
contactClosure1OutletName,
|
|
contactClosure1OutletState,
|
|
contactClosure1State,
|
|
contactClosure2Alert,
|
|
contactClosure2ControlOutlet,
|
|
contactClosure2Enable,
|
|
contactClosure2Name,
|
|
contactClosure2OutletName,
|
|
contactClosure2OutletState,
|
|
contactClosure2State,
|
|
contactClosure3Alert,
|
|
contactClosure3ControlOutlet,
|
|
contactClosure3Enable,
|
|
contactClosure3Name,
|
|
contactClosure3OutletName,
|
|
contactClosure3OutletState,
|
|
contactClosure3State,
|
|
defaultGateway,
|
|
enablePing,
|
|
fahrenheitOrCelsius,
|
|
globalCommand,
|
|
humSensor1Alert,
|
|
humSensor1ControlOutlet,
|
|
humSensor1Enable,
|
|
humSensor1HighThresh,
|
|
humSensor1Humidity,
|
|
humSensor1LowThresh,
|
|
humSensor1Name,
|
|
humSensor1OutletName,
|
|
humSensor1OutletState,
|
|
infoContactState,
|
|
infoItemIdx,
|
|
infoItemName,
|
|
infoMeasuredValue,
|
|
infoOutletState,
|
|
infoThresholdState,
|
|
infoThresholdValue,
|
|
infoUserName,
|
|
invertDisplay,
|
|
loginTimeout,
|
|
macAddress,
|
|
mailServerIPAddress,
|
|
outlet10Command,
|
|
outlet10Link,
|
|
outlet10Name,
|
|
outlet10PingIpAddress,
|
|
outlet10RebootTime,
|
|
outlet10SequenceTime,
|
|
outlet10Status,
|
|
outlet11Command,
|
|
outlet11Link,
|
|
outlet11Name,
|
|
outlet11PingIpAddress,
|
|
outlet11RebootTime,
|
|
outlet11SequenceTime,
|
|
outlet11Status,
|
|
outlet12Command,
|
|
outlet12Link,
|
|
outlet12Name,
|
|
outlet12PingIpAddress,
|
|
outlet12RebootTime,
|
|
outlet12SequenceTime,
|
|
outlet12Status,
|
|
outlet13Command,
|
|
outlet13Link,
|
|
outlet13Name,
|
|
outlet13PingIpAddress,
|
|
outlet13RebootTime,
|
|
outlet13SequenceTime,
|
|
outlet13Status,
|
|
outlet14Command,
|
|
outlet14Link,
|
|
outlet14Name,
|
|
outlet14PingIpAddress,
|
|
outlet14RebootTime,
|
|
outlet14SequenceTime,
|
|
outlet14Status,
|
|
outlet15Command,
|
|
outlet15Link,
|
|
outlet15Name,
|
|
outlet15PingIpAddress,
|
|
outlet15RebootTime,
|
|
outlet15SequenceTime,
|
|
outlet15Status,
|
|
outlet16Command,
|
|
outlet16Link,
|
|
outlet16Name,
|
|
outlet16PingIpAddress,
|
|
outlet16RebootTime,
|
|
outlet16SequenceTime,
|
|
outlet16Status,
|
|
outlet17Command,
|
|
outlet17Link,
|
|
outlet17Name,
|
|
outlet17PingIpAddress,
|
|
outlet17RebootTime,
|
|
outlet17SequenceTime,
|
|
outlet17Status,
|
|
outlet18Command,
|
|
outlet18Link,
|
|
outlet18Name,
|
|
outlet18PingIpAddress,
|
|
outlet18RebootTime,
|
|
outlet18SequenceTime,
|
|
outlet18Status,
|
|
outlet19Command,
|
|
outlet19Link,
|
|
outlet19Name,
|
|
outlet19PingIpAddress,
|
|
outlet19RebootTime,
|
|
outlet19SequenceTime,
|
|
outlet19Status,
|
|
outlet1Command,
|
|
outlet1Link,
|
|
outlet1Name,
|
|
outlet1PingIpAddress,
|
|
outlet1RebootTime,
|
|
outlet1SequenceTime,
|
|
outlet1Status,
|
|
outlet20Command,
|
|
outlet20Link,
|
|
outlet20Name,
|
|
outlet20PingIpAddress,
|
|
outlet20RebootTime,
|
|
outlet20SequenceTime,
|
|
outlet20Status,
|
|
outlet21Command,
|
|
outlet21Link,
|
|
outlet21Name,
|
|
outlet21PingIpAddress,
|
|
outlet21RebootTime,
|
|
outlet21SequenceTime,
|
|
outlet21Status,
|
|
outlet22Command,
|
|
outlet22Link,
|
|
outlet22Name,
|
|
outlet22PingIpAddress,
|
|
outlet22RebootTime,
|
|
outlet22SequenceTime,
|
|
outlet22Status,
|
|
outlet23Command,
|
|
outlet23Link,
|
|
outlet23Name,
|
|
outlet23PingIpAddress,
|
|
outlet23RebootTime,
|
|
outlet23SequenceTime,
|
|
outlet23Status,
|
|
outlet24Command,
|
|
outlet24Link,
|
|
outlet24Name,
|
|
outlet24PingIpAddress,
|
|
outlet24RebootTime,
|
|
outlet24SequenceTime,
|
|
outlet24Status,
|
|
outlet25Command,
|
|
outlet25Link,
|
|
outlet25Name,
|
|
outlet25PingIpAddress,
|
|
outlet25RebootTime,
|
|
outlet25SequenceTime,
|
|
outlet25Status,
|
|
outlet26Command,
|
|
outlet26Link,
|
|
outlet26Name,
|
|
outlet26PingIpAddress,
|
|
outlet26RebootTime,
|
|
outlet26SequenceTime,
|
|
outlet26Status,
|
|
outlet27Command,
|
|
outlet27Link,
|
|
outlet27Name,
|
|
outlet27PingIpAddress,
|
|
outlet27RebootTime,
|
|
outlet27SequenceTime,
|
|
outlet27Status,
|
|
outlet28Command,
|
|
outlet28Link,
|
|
outlet28Name,
|
|
outlet28PingIpAddress,
|
|
outlet28RebootTime,
|
|
outlet28SequenceTime,
|
|
outlet28Status,
|
|
outlet29Command,
|
|
outlet29Link,
|
|
outlet29Name,
|
|
outlet29PingIpAddress,
|
|
outlet29RebootTime,
|
|
outlet29SequenceTime,
|
|
outlet29Status,
|
|
outlet2Command,
|
|
outlet2Link,
|
|
outlet2Name,
|
|
outlet2PingIpAddress,
|
|
outlet2RebootTime,
|
|
outlet2SequenceTime,
|
|
outlet2Status,
|
|
outlet30Command,
|
|
outlet30Link,
|
|
outlet30Name,
|
|
outlet30PingIpAddress,
|
|
outlet30RebootTime,
|
|
outlet30SequenceTime,
|
|
outlet30Status,
|
|
outlet31Command,
|
|
outlet31Link,
|
|
outlet31Name,
|
|
outlet31PingIpAddress,
|
|
outlet31RebootTime,
|
|
outlet31SequenceTime,
|
|
outlet31Status,
|
|
outlet32Command,
|
|
outlet32Link,
|
|
outlet32Name,
|
|
outlet32PingIpAddress,
|
|
outlet32RebootTime,
|
|
outlet32SequenceTime,
|
|
outlet32Status,
|
|
outlet33Command,
|
|
outlet33Link,
|
|
outlet33Name,
|
|
outlet33PingIpAddress,
|
|
outlet33RebootTime,
|
|
outlet33SequenceTime,
|
|
outlet33Status,
|
|
outlet34Command,
|
|
outlet34Link,
|
|
outlet34Name,
|
|
outlet34PingIpAddress,
|
|
outlet34RebootTime,
|
|
outlet34SequenceTime,
|
|
outlet34Status,
|
|
outlet35Command,
|
|
outlet35Link,
|
|
outlet35Name,
|
|
outlet35PingIpAddress,
|
|
outlet35RebootTime,
|
|
outlet35SequenceTime,
|
|
outlet35Status,
|
|
outlet36Command,
|
|
outlet36Link,
|
|
outlet36Name,
|
|
outlet36PingIpAddress,
|
|
outlet36RebootTime,
|
|
outlet36SequenceTime,
|
|
outlet36Status,
|
|
outlet3Command,
|
|
outlet3Link,
|
|
outlet3Name,
|
|
outlet3PingIpAddress,
|
|
outlet3RebootTime,
|
|
outlet3SequenceTime,
|
|
outlet3Status,
|
|
outlet4Command,
|
|
outlet4Link,
|
|
outlet4Name,
|
|
outlet4PingIpAddress,
|
|
outlet4RebootTime,
|
|
outlet4SequenceTime,
|
|
outlet4Status,
|
|
outlet5Command,
|
|
outlet5Link,
|
|
outlet5Name,
|
|
outlet5PingIpAddress,
|
|
outlet5RebootTime,
|
|
outlet5SequenceTime,
|
|
outlet5Status,
|
|
outlet6Command,
|
|
outlet6Link,
|
|
outlet6Name,
|
|
outlet6PingIpAddress,
|
|
outlet6RebootTime,
|
|
outlet6SequenceTime,
|
|
outlet6Status,
|
|
outlet7Command,
|
|
outlet7Link,
|
|
outlet7Name,
|
|
outlet7PingIpAddress,
|
|
outlet7RebootTime,
|
|
outlet7SequenceTime,
|
|
outlet7Status,
|
|
outlet8Command,
|
|
outlet8Link,
|
|
outlet8Name,
|
|
outlet8PingIpAddress,
|
|
outlet8RebootTime,
|
|
outlet8SequenceTime,
|
|
outlet8Status,
|
|
outlet9Command,
|
|
outlet9Link,
|
|
outlet9Name,
|
|
outlet9PingIpAddress,
|
|
outlet9RebootTime,
|
|
outlet9SequenceTime,
|
|
outlet9Status,
|
|
outletActivity,
|
|
outletSection1Alert,
|
|
outletSection1Current,
|
|
outletSection1CurrentHighThreshold,
|
|
outletSection1CurrentLowThreshold,
|
|
outletSection1Va,
|
|
outletSection1Voltage,
|
|
outletSection1VoltageHighThreshold,
|
|
outletSection1VoltageLowThreshold,
|
|
outletSection2Alert,
|
|
outletSection2Current,
|
|
outletSection2CurrentHighThreshold,
|
|
outletSection2CurrentLowThreshold,
|
|
outletSection2Va,
|
|
outletSection2Voltage,
|
|
outletSection2VoltageHighThreshold,
|
|
outletSection2VoltageLowThreshold,
|
|
outletSection3Alert,
|
|
outletSection3Current,
|
|
outletSection3CurrentHighThreshold,
|
|
outletSection3CurrentLowThreshold,
|
|
outletSection3Va,
|
|
outletSection3Voltage,
|
|
outletSection3VoltageHighThreshold,
|
|
outletSection3VoltageLowThreshold,
|
|
outletSection4Current,
|
|
outletSection4CurrentHighThreshold,
|
|
outletSection4CurrentLowThreshold,
|
|
outletSection4Va,
|
|
outletSection4Voltage,
|
|
outletSection4VoltageHighThreshold,
|
|
outletSection4VoltageLowThreshold,
|
|
outletSection5Current,
|
|
outletSection5CurrentHighThreshold,
|
|
outletSection5CurrentLowThreshold,
|
|
outletSection5Va,
|
|
outletSection5Voltage,
|
|
outletSection5VoltageHighThreshold,
|
|
outletSection5VoltageLowThreshold,
|
|
outletSection6Current,
|
|
outletSection6CurrentHighThreshold,
|
|
outletSection6CurrentLowThreshold,
|
|
outletSection6Va,
|
|
outletSection6Voltage,
|
|
outletSection6VoltageHighThreshold,
|
|
outletSection6VoltageLowThreshold,
|
|
pingInterval,
|
|
sendAlertsToUser1Address,
|
|
sendAlertsToUser2Address,
|
|
sendLogFrequency,
|
|
sendLogFrom,
|
|
sendLogTime,
|
|
sendLogToUser1Address,
|
|
sendLogToUser2Address,
|
|
strappingId,
|
|
subnetMask,
|
|
systemOnOff,
|
|
telnetEnabled,
|
|
telnetPort,
|
|
tempSensor1Alert,
|
|
tempSensor1ControlOutlet,
|
|
tempSensor1Enable,
|
|
tempSensor1HighThresh,
|
|
tempSensor1LowThresh,
|
|
tempSensor1Name,
|
|
tempSensor1OutletName,
|
|
tempSensor1OutletState,
|
|
tempSensor1Temp,
|
|
tempSensor2Alert,
|
|
tempSensor2ControlOutlet,
|
|
tempSensor2Enable,
|
|
tempSensor2HighThresh,
|
|
tempSensor2LowThresh,
|
|
tempSensor2Name,
|
|
tempSensor2OutletName,
|
|
tempSensor2OutletState,
|
|
tempSensor2Temp,
|
|
totalCurrent,
|
|
totalVa,
|
|
trapContactClosure1Threshold,
|
|
trapContactClosure2Threshold,
|
|
trapContactClosure3Threshold,
|
|
trapFailedLogin,
|
|
trapHumiditySensorThreshold,
|
|
trapIpAddress,
|
|
trapOutletActivity,
|
|
trapOutletSection1Threshold,
|
|
trapOutletSection2Threshold,
|
|
trapOutletSection3Threshold,
|
|
trapSystemOnOff,
|
|
trapTemperatureSensor1Threshold,
|
|
trapTemperatureSensor2Threshold,
|
|
trapUserLoginLogout,
|
|
unitDate,
|
|
unitDayOfWeek,
|
|
unitIPAddress,
|
|
unitName,
|
|
unitTime,
|
|
userLogInLogOut,
|
|
userLogInLogOutFailed,
|
|
vaLoggingInterval,
|
|
webEnabled,
|
|
webPort }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The object group."
|
|
::= { groups 1 }
|
|
|
|
oldObjects OBJECT-GROUP
|
|
OBJECTS { outletSection1ControlOutlet,
|
|
outletSection1OutletName,
|
|
outletSection2ControlOutlet,
|
|
outletSection2OutletName,
|
|
outletSection3ControlOutlet,
|
|
outletSection3OutletName,
|
|
outletSection4ControlOutlet,
|
|
outletSection4OutletName,
|
|
outletSection5ControlOutlet,
|
|
outletSection5OutletName,
|
|
outletSection6ControlOutlet,
|
|
outletSection6OutletName }
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The deprecated objects group."
|
|
::= { groups 2 }
|
|
|
|
obsoleteObjects OBJECT-GROUP
|
|
OBJECTS { totalVoltage }
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"The obsoleted objects group."
|
|
::= { groups 3 }
|
|
|
|
allNotifications NOTIFICATION-GROUP
|
|
NOTIFICATIONS { notifyContactSensorThreshold,
|
|
notifyCurrentThreshold,
|
|
notifyFailedLogin,
|
|
notifyHumidSensorThreshold,
|
|
notifyOutletState,
|
|
notifyOutletWatchdogFailed,
|
|
notifyTempSensorThreshold,
|
|
notifyUserLogin,
|
|
notifyUserLogout,
|
|
notifyVoltageThreshold }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The notifications group."
|
|
::= { groups 4 }
|
|
END
|
|
|