2257 lines
67 KiB
Plaintext
2257 lines
67 KiB
Plaintext
--BESTPOWER-MIB { iso(1) org(3) dod(6) internet(1) private(4)
|
|
-- enterprises(1) bestpower(2947) }
|
|
|
|
--Last Modification 03/23/00 by Steve Van Duser
|
|
|
|
--Contributing Authors: Steve Van Duser BEST POWER
|
|
-- Jamie Krueger BEST POWER
|
|
-- Brian Young BEST POWER
|
|
-- RFC1628 model for a UPS MIB
|
|
|
|
BESTPOWER-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
enterprises, IpAddress, Gauge
|
|
FROM RFC1155-SMI
|
|
DisplayString
|
|
FROM RFC1213-MIB
|
|
OBJECT-TYPE
|
|
FROM RFC-1212
|
|
TRAP-TYPE
|
|
FROM RFC-1215;
|
|
--textual conventions
|
|
NonNegativeInteger ::= INTEGER
|
|
PositiveInteger ::= INTEGER
|
|
-- TimeStamp ::= TimeTicks
|
|
|
|
bestPower OBJECT IDENTIFIER ::= { enterprises 2947 }
|
|
bestLink OBJECT IDENTIFIER ::= { bestPower 1 }
|
|
|
|
upsIdent OBJECT IDENTIFIER ::= { bestLink 1 }
|
|
upsBattery OBJECT IDENTIFIER ::= { bestLink 2 }
|
|
upsInput OBJECT IDENTIFIER ::= { bestLink 3 }
|
|
upsOutput OBJECT IDENTIFIER ::= { bestLink 4 }
|
|
upsConfig OBJECT IDENTIFIER ::= { bestLink 5 }
|
|
upsControl OBJECT IDENTIFIER ::= { bestLink 6 }
|
|
upsTest OBJECT IDENTIFIER ::= { bestLink 7 }
|
|
upsAlarm OBJECT IDENTIFIER ::= { bestLink 8 }
|
|
upsBypass OBJECT IDENTIFIER ::= { bestLink 9 }
|
|
|
|
|
|
|
|
-- Ident Group
|
|
|
|
upsIdentUpsName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..19))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An ID string identifying the Family of UPS."
|
|
::= { upsIdent 1 }
|
|
|
|
upsIdentModel OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..29))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS model name (example: 'FE500VA')."
|
|
::= { upsIdent 2 }
|
|
|
|
upsIdentVARating OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The capacity rating of the UPS expressed in VoltAmperes(VA)."
|
|
::= { upsIdent 3 }
|
|
|
|
upsIdentUpsType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
standby(1),
|
|
online(2),
|
|
offline(3),
|
|
lineInterative(4),
|
|
3PhaseDC(5),
|
|
3PhaseLI(6),
|
|
hybrid(7)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Type of UPS."
|
|
::= { upsIdent 4 }
|
|
|
|
upsIdentUpsSerialNumber OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A unique identification number provided by the factory."
|
|
::= { upsIdent 5 }
|
|
|
|
|
|
upsIdentFirmwareRevision OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..19))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The firmware revision of the UPS."
|
|
::= { upsIdent 7 }
|
|
|
|
upsIdentInstallationDate OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(6..10))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The date when the UPS was installed in mm/dd/yyyy format."
|
|
::= { upsIdent 8 }
|
|
|
|
-- the upsBattery group
|
|
|
|
upsBatteryStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(1),
|
|
upsOnBattery(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The status of the inverter ."
|
|
::= { upsBattery 1 }
|
|
|
|
upsBatteryTimeOnBattery OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The elapsed time in seconds since the UPS has switched to battery power."
|
|
::= { upsBattery 2 }
|
|
|
|
upsBatteryRuntimeRemaining OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The remaining time in minutes that the UPS will be able to run on battery power."
|
|
::= { upsBattery 3 }
|
|
|
|
upsBatteryVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS battery voltage expressed in 1/10 VDC."
|
|
::= { upsBattery 4 }
|
|
|
|
upsBatteryCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The battery current expressed in 1/10 ADC."
|
|
::= { upsBattery 5 }
|
|
|
|
upsBatteryTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The internal UPS temperature expressed in 1/10 degree C."
|
|
::= { upsBattery 6 }
|
|
|
|
upsBatteryLastReplaceDate OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(6..10))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The date when the UPS system's batteries were last replaced
|
|
in mm/dd/yyyy format. When the UPS batteries are replaced,
|
|
this value should be reset by the administrator."
|
|
::= { upsBattery 7 }
|
|
|
|
|
|
|
|
upsBatteryCellVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS battery cell voltage expressed in 1/100 VDC."
|
|
::= { upsBattery 8 }
|
|
|
|
upsBatteryPositiveVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS battery voltage measured from the most postive point in the battery
|
|
string to the common reference point. The value is expressed in 1/10 VDC."
|
|
::= { upsBattery 9 }
|
|
|
|
|
|
upsBatteryNegativeVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS battery voltage measured from the most negative point in the battery
|
|
string to the common reference point. The value is expressed in 1/10 VDC."
|
|
::= { upsBattery 10 }
|
|
|
|
-- the upsInput group
|
|
|
|
|
|
--upsInputPhase OBJECT-TYPE
|
|
-- SYNTAX INTEGER
|
|
-- ACCESS read-only
|
|
-- STATUS mandatory
|
|
-- DESCRIPTION
|
|
-- "The AC input phase."
|
|
-- ::= { upsInput 1 }
|
|
|
|
|
|
|
|
upsInputFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The utility line frequency in 1/10 Hz."
|
|
::= { upsInput 2 }
|
|
|
|
upsInputVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The utility line voltage in 1/10 VAC."
|
|
::= { upsInput 3 }
|
|
|
|
upsInputCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The utility line current in 1/10 Ampere AC."
|
|
::= { upsInput 4 }
|
|
|
|
|
|
|
|
upsInput3PhaseCurrent OBJECT IDENTIFIER ::= { upsInput 6 }
|
|
|
|
|
|
upsInputCurrentL1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present input current on L1."
|
|
::= { upsInput3PhaseCurrent 1 }
|
|
|
|
upsInputCurrentL2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present input current on L2."
|
|
::= { upsInput3PhaseCurrent 2 }
|
|
|
|
upsInputCurrentL3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present input current on L3."
|
|
::= { upsInput3PhaseCurrent 3 }
|
|
|
|
|
|
upsInput3PhaseVoltageLtoN OBJECT IDENTIFIER ::= { upsInput 7 }
|
|
|
|
|
|
upsInputVoltageL1toN OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present input voltage from L1 to Neutral."
|
|
::= { upsInput3PhaseVoltageLtoN 1 }
|
|
|
|
upsInputVoltageL2toN OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present input voltage from L2 to Neutral."
|
|
::= { upsInput3PhaseVoltageLtoN 2 }
|
|
|
|
upsInputVoltageL3toN OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present input voltage from L3 to Neutral."
|
|
::= { upsInput3PhaseVoltageLtoN 3 }
|
|
|
|
|
|
|
|
upsInput3PhaseVoltageLtoL OBJECT IDENTIFIER ::= { upsInput 8 }
|
|
|
|
|
|
upsInputVoltageL1toL2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present input voltage from L1 to L2."
|
|
::= { upsInput3PhaseVoltageLtoL 1 }
|
|
|
|
upsInputVoltageL2toL3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present input voltage from L2 to L3."
|
|
::= { upsInput3PhaseVoltageLtoL 2 }
|
|
|
|
upsInputVoltageL3toL1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present input voltage from L3 to L1."
|
|
::= { upsInput3PhaseVoltageLtoL 3 }
|
|
|
|
|
|
|
|
-- the upsOutput group
|
|
|
|
|
|
|
|
--upsOutputStatus OBJECT-TYPE
|
|
-- SYNTAX INTEGER {
|
|
-- unknown(1),
|
|
-- onLine(2),
|
|
-- onBattery(3),
|
|
-- onBypass(4)
|
|
-- }
|
|
-- ACCESS read-only
|
|
-- STATUS mandatory
|
|
-- DESCRIPTION
|
|
-- "The current state of the UPS. If the UPS is unable
|
|
-- to determine its state, this variable is set
|
|
-- to unknown(1)."
|
|
-- ::= { upsOutput 1 }
|
|
|
|
--upsOutputPhase OBJECT-TYPE
|
|
-- SYNTAX INTEGER
|
|
-- ACCESS read-only
|
|
-- STATUS mandatory
|
|
-- DESCRIPTION
|
|
-- "The output phase."
|
|
-- ::= { upsOutput 2 }
|
|
|
|
|
|
upsOutputFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The output frequency of the UPS expressed in 1/10 Hz."
|
|
::= { upsOutput 3 }
|
|
|
|
upsOutputVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The output voltage of the UPS expressed in 1/10 VAC."
|
|
::= { upsOutput 4 }
|
|
|
|
upsOutputCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The output current of the UPS expressed in 1/10 AC Amperes."
|
|
::= { upsOutput 5 }
|
|
|
|
upsOutputTruePower OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The true output power of the UPS expressed in 1/100 Watts."
|
|
::= { upsOutput 6 }
|
|
|
|
upsOutputApparentPower OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The apparent output power of the UPS expressed in 1/100 VoltAmperes(VA)."
|
|
::= { upsOutput 7 }
|
|
|
|
upsOutputPowerFactor OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The output powerfactor of the UPS expressed in +/- 1/100 units deviating
|
|
from 1."
|
|
::= { upsOutput 8 }
|
|
|
|
upsOutputPercentFullLoad OBJECT-TYPE
|
|
SYNTAX INTEGER -- UNITS percent
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The percentage of the total UPS power capacity being used expressed
|
|
in % of 100."
|
|
::= { upsOutput 9 }
|
|
|
|
|
|
|
|
upsOutput3PhaseVoltageLtoN OBJECT IDENTIFIER ::= { upsOutput 10 }
|
|
|
|
|
|
upsOutputVoltageL1toN OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present Output voltage from L1 to Neutral."
|
|
::= { upsOutput3PhaseVoltageLtoN 1 }
|
|
|
|
upsOutputVoltageL2toN OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present Output voltage from L2 to Neutral."
|
|
::= { upsOutput3PhaseVoltageLtoN 2 }
|
|
|
|
upsOutputVoltageL3toN OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present Output voltage from L3 to Neutral."
|
|
::= { upsOutput3PhaseVoltageLtoN 3 }
|
|
|
|
|
|
|
|
upsOutput3PhaseVoltageLtoL OBJECT IDENTIFIER ::= { upsOutput 11 }
|
|
|
|
|
|
upsOutputVoltageL1toL2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present Output voltage from L1 to L2."
|
|
::= { upsOutput3PhaseVoltageLtoL 1 }
|
|
|
|
upsOutputVoltageL2toL3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present Output voltage from L2 to L3."
|
|
::= { upsOutput3PhaseVoltageLtoL 2 }
|
|
|
|
upsOutputVoltageL3toL1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present Output voltage from L3 to L1."
|
|
::= { upsOutput3PhaseVoltageLtoL 3 }
|
|
|
|
|
|
upsOutput3PhaseCurrent OBJECT IDENTIFIER ::= { upsOutput 12 }
|
|
|
|
|
|
upsOutputCurrentL1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present Output current on L1."
|
|
::= { upsOutput3PhaseCurrent 1 }
|
|
|
|
upsOutputCurrentL2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present Output current on L2."
|
|
::= { upsOutput3PhaseCurrent 2 }
|
|
|
|
upsOutputCurrentL3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present Output current on L3."
|
|
::= { upsOutput3PhaseCurrent 3 }
|
|
|
|
|
|
upsOutput3PhaseApparentPower OBJECT IDENTIFIER ::= { upsOutput 13 }
|
|
|
|
|
|
upsOutputApparentPowerL1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present Output ApparentPower on L1."
|
|
::= { upsOutput3PhaseApparentPower 1 }
|
|
|
|
upsOutputApparentPowerL2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present Output ApparentPower on L2."
|
|
::= { upsOutput3PhaseApparentPower 2 }
|
|
|
|
upsOutputApparentPowerL3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present Output ApparentPower on L3."
|
|
::= { upsOutput3PhaseApparentPower 3 }
|
|
|
|
|
|
upsOutput3PhaseTruePower OBJECT IDENTIFIER ::= { upsOutput 14 }
|
|
|
|
|
|
upsOutputTruePowerL1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present Output TruePower on L1."
|
|
::= { upsOutput3PhaseTruePower 1 }
|
|
|
|
upsOutputTruePowerL2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present Output TruePower on L2."
|
|
::= { upsOutput3PhaseTruePower 2 }
|
|
|
|
upsOutputTruePowerL3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present Output TruePower on L3."
|
|
::= { upsOutput3PhaseTruePower 3 }
|
|
|
|
|
|
upsOutput3PhasePowerFactor OBJECT IDENTIFIER ::= { upsOutput 15 }
|
|
|
|
|
|
upsOutputPowerFactorL1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present Output PowerFactor on L1."
|
|
::= { upsOutput3PhasePowerFactor 1 }
|
|
|
|
upsOutputPowerFactorL2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present Output PowerFactor on L2."
|
|
::= { upsOutput3PhasePowerFactor 2 }
|
|
|
|
upsOutputPowerFactorL3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present Output PowerFactor on L3."
|
|
::= { upsOutput3PhasePowerFactor 3 }
|
|
|
|
|
|
|
|
upsOutput3PhasePercentLoad OBJECT IDENTIFIER ::= { upsOutput 16 }
|
|
|
|
|
|
upsOutputPercentLoadL1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present Output PercentLoad on L1."
|
|
::= { upsOutput3PhasePercentLoad 1 }
|
|
|
|
upsOutputPercentLoadL2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present Output PercentLoad on L2."
|
|
::= { upsOutput3PhasePercentLoad 2 }
|
|
|
|
upsOutputPercentLoadL3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present Output PercentLoad on L3."
|
|
::= { upsOutput3PhasePercentLoad 3 }
|
|
|
|
|
|
|
|
-- the upsBypass group
|
|
|
|
upsBypassStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(1),
|
|
upsOnBypass(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The status of the bypass mode."
|
|
::= { upsBypass 1 }
|
|
|
|
|
|
upsBypass3PhaseVoltageLtoN OBJECT IDENTIFIER ::= { upsBypass 2 }
|
|
|
|
|
|
upsBypassVoltageL1toN OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present Bypass voltage from L1 to Neutral."
|
|
::= { upsBypass3PhaseVoltageLtoN 1 }
|
|
|
|
upsBypassVoltageL2toN OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present Bypass voltage from L2 to Neutral."
|
|
::= { upsBypass3PhaseVoltageLtoN 2 }
|
|
|
|
upsBypassVoltageL3toN OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present Bypass voltage from L3 to Neutral."
|
|
::= { upsBypass3PhaseVoltageLtoN 3 }
|
|
|
|
|
|
|
|
upsBypass3PhaseVoltageLtoL OBJECT IDENTIFIER ::= { upsBypass 3 }
|
|
|
|
|
|
upsBypassVoltageL1toL2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present Bypass voltage from L1 to L2."
|
|
::= { upsBypass3PhaseVoltageLtoL 1 }
|
|
|
|
upsBypassVoltageL2toL3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present Bypass voltage from L2 to L3."
|
|
::= { upsBypass3PhaseVoltageLtoL 2 }
|
|
|
|
upsBypassVoltageL3toL1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present Bypass voltage from L3 to L1."
|
|
::= { upsBypass3PhaseVoltageLtoL 3 }
|
|
|
|
|
|
|
|
|
|
|
|
|
|
-- the upsConfig group
|
|
|
|
|
|
|
|
--upsConfigLowRuntimeSetpoint OBJECT-TYPE
|
|
-- SYNTAX INTEGER
|
|
-- ACCESS read-write
|
|
-- STATUS mandatory
|
|
-- DESCRIPTION
|
|
-- "This setpoint controls when the UPS will initiate a Low Runtime
|
|
-- Alarm."
|
|
-- ::= { upsConfig 1 }
|
|
|
|
-- upsConfigDelayBeforeRestart OBJECT-TYPE
|
|
-- SYNTAX INTEGER
|
|
-- ACCESS read-write
|
|
-- STATUS mandatory
|
|
-- DESCRIPTION
|
|
-- "The delay in seconds after utility line power returns
|
|
-- before the UPS will turn on. This value is used in
|
|
-- conjunction with TurnUPSOff, RebootUPS, and
|
|
-- the Scheduled Shutdown objects."
|
|
-- ::= { upsConfig 2 }
|
|
|
|
|
|
|
|
upsConfigDelayBeforeShutdown OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The delay in seconds that the UPS waits before executing an off
|
|
command upon request of an external device."
|
|
::= { upsConfig 3 }
|
|
|
|
|
|
upsConfigAutoRestart OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
yes(1),
|
|
no(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The status of the Auto Restart mode."
|
|
::= { upsConfig 11 }
|
|
|
|
|
|
upsConfigShutdownUPSAfterOSShdn OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
yes(1),
|
|
no(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this value to 1, enables the UPS to be shutdown after the
|
|
registered clients operating systems have shutdown."
|
|
::= { upsConfig 14 }
|
|
|
|
|
|
upsConfigACFailEventActions OBJECT IDENTIFIER ::= { upsConfig 12 }
|
|
|
|
upsConfigDelayBeforeFirstWarningMessage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The amount of time to delay in seconds before sending the first AC Fail message."
|
|
::= { upsConfigACFailEventActions 1 }
|
|
|
|
|
|
upsConfigWarningInterval OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The amount of time to delay in seconds between sending the additional AC Fail messages."
|
|
::= { upsConfigACFailEventActions 2 }
|
|
|
|
|
|
upsConfigClientOperatingSystemShutdown OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Determines whether or not to initiate a shutdown of all registered clients based on the
|
|
AC Fail event with duration."
|
|
::= { upsConfigACFailEventActions 3 }
|
|
|
|
|
|
upsConfigDelayBeforeClientShutdown OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
" The time allowed in seconds during an AC Fail condition before shutting
|
|
down of all registered clients."
|
|
::= { upsConfigACFailEventActions 4 }
|
|
|
|
|
|
upsConfigLowBatteryEventActions OBJECT IDENTIFIER ::= { upsConfig 13 }
|
|
|
|
upsConfigClientOsShutdown OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Determines whether or not to initiate a shutdown of all registered clients based on the
|
|
Low Battery condition."
|
|
::= { upsConfigLowBatteryEventActions 1 }
|
|
|
|
|
|
|
|
|
|
|
|
|
|
upsConfigTestScheduleTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsConfigTestScheduleEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The table to schedule ups battery tests."
|
|
::= { upsConfig 4 }
|
|
|
|
upsConfigTestScheduleEntry OBJECT-TYPE
|
|
SYNTAX UpsConfigTestScheduleEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The entries for each day."
|
|
INDEX { upsConfigTestScheduleIndex }
|
|
::= { upsConfigTestScheduleTable 1 }
|
|
|
|
UpsConfigTestScheduleEntry ::= SEQUENCE {
|
|
upsConfigTestScheduleIndex
|
|
INTEGER,
|
|
upsConfigTestScheduleDay
|
|
INTEGER,
|
|
upsConfigTestScheduleTime
|
|
DisplayString
|
|
}
|
|
|
|
upsConfigTestScheduleIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index of scheduled events."
|
|
::= { upsConfigTestScheduleEntry 1 }
|
|
|
|
upsConfigTestScheduleDay OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
sunday(1),
|
|
monday(2),
|
|
tuesday(3),
|
|
wednesday(4),
|
|
thursday(5),
|
|
friday(6),
|
|
saturday(7),
|
|
none(8)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The weekday on which the UPS should shut down."
|
|
::= { upsConfigTestScheduleEntry 2 }
|
|
|
|
upsConfigTestScheduleTime OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The time that the process of shutting down the UPS will be initiated"
|
|
::= { upsConfigTestScheduleEntry 3 }
|
|
|
|
|
|
|
|
|
|
upsConfigShutdownScheduleTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsConfigShutdownScheduleEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The table to schedule shutting down the ups."
|
|
::= { upsConfig 5 }
|
|
|
|
upsConfigShutdownScheduleEntry OBJECT-TYPE
|
|
SYNTAX UpsConfigShutdownScheduleEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The entries for each day."
|
|
INDEX { upsConfigShutdownScheduleIndex }
|
|
::= { upsConfigShutdownScheduleTable 1 }
|
|
|
|
UpsConfigShutdownScheduleEntry ::= SEQUENCE {
|
|
upsConfigShutdownScheduleIndex
|
|
INTEGER,
|
|
upsConfigScheduleShutdownDay
|
|
INTEGER,
|
|
upsConfigScheduleShutdownTime
|
|
DisplayString,
|
|
upsConfigScheduleRestartDay
|
|
INTEGER,
|
|
upsConfigScheduleRestartTime
|
|
DisplayString
|
|
}
|
|
|
|
upsConfigShutdownScheduleIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index of scheduled events."
|
|
::= { upsConfigShutdownScheduleEntry 1 }
|
|
|
|
upsConfigScheduleShutdownDay OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
sunday(1),
|
|
monday(2),
|
|
tuesday(3),
|
|
wednesday(4),
|
|
thursday(5),
|
|
friday(6),
|
|
saturday(7),
|
|
none(8)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The weekday on which the UPS should shut down."
|
|
::= { upsConfigShutdownScheduleEntry 2 }
|
|
|
|
upsConfigScheduleShutdownTime OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The time that the process of shutting down the UPS will be initiated"
|
|
::= { upsConfigShutdownScheduleEntry 3 }
|
|
|
|
upsConfigScheduleRestartDay OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
sunday(1),
|
|
monday(2),
|
|
tuesday(3),
|
|
wednesday(4),
|
|
thursday(5),
|
|
friday(6),
|
|
saturday(7),
|
|
none(8)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The weekday on which the UPS should restart"
|
|
|
|
::= { upsConfigShutdownScheduleEntry 4 }
|
|
|
|
upsConfigScheduleRestartTime OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The time the UPS will restart in hh:mm:ss format."
|
|
::= { upsConfigShutdownScheduleEntry 5 }
|
|
|
|
|
|
|
|
upsConfigbestLink OBJECT IDENTIFIER ::= { upsConfig 8 }
|
|
|
|
bestLinkHistoryLogFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The frequency of updating the history log in minutes."
|
|
::= { upsConfigbestLink 1 }
|
|
|
|
bestLinkRefreshFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The frequency of saving configuration,history and event log data
|
|
in non-volatile memory. If the value is set to 0, then saving data
|
|
is disabled."
|
|
::= { upsConfigbestLink 2 }
|
|
|
|
bestLinkNetId OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The IP address of the device. Setting this parameter causes BestLink to reboot."
|
|
::= { upsConfigbestLink 3 }
|
|
|
|
bestLinkGateway OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The gateway address for the network BestLink is connected to."
|
|
::= { upsConfigbestLink 4 }
|
|
|
|
bestLinkNetMask OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The net mask of the device."
|
|
::= { upsConfigbestLink 5 }
|
|
|
|
bestLinkSysDate OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(6..10))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The system date of the device. The date is in mm/dd/yyyy format.
|
|
The range of system date is from 1/1/1980 to 12/31/2037."
|
|
::= { upsConfigbestLink 6 }
|
|
|
|
bestLinkSysTime OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(5..8))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The system time of the device. The time is in hh:mm:ss format."
|
|
::= { upsConfigbestLink 7 }
|
|
|
|
bestLinkTftpFileName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..59))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The tftp file name that contains the software upgrade image."
|
|
::= { upsConfigbestLink 8 }
|
|
|
|
bestLinkTftpHost OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The tftp host IP address from where to get the image."
|
|
::= { upsConfigbestLink 9 }
|
|
|
|
bestLinkFlashEEPROM OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
no(1),
|
|
yes(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Saves the history log, eventlog, and configuration data to non-volatile
|
|
memory."
|
|
::= { upsConfigbestLink 10 }
|
|
|
|
bestLinkPrimaryTimeServer OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The primary time server is responsible for sending the
|
|
correct time to the UPS."
|
|
::= { upsConfigbestLink 11 }
|
|
|
|
bestLinkSecondaryTimeServer OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The secondary time server responsible for sending the
|
|
correct time to the UPS."
|
|
::= { upsConfigbestLink 12 }
|
|
|
|
bestLinkSoftwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The version of BestLink software."
|
|
::= { upsConfigbestLink 13 }
|
|
|
|
bestLinkMIBVersion OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The version of MIB implemented in SNMP/WEB Card software."
|
|
::= { upsConfigbestLink 14 }
|
|
|
|
bestLinkDHCPControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enabled(1),
|
|
disabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable/Disable DHCP function of SNMP/WEB Card."
|
|
::= { upsConfigbestLink 15 }
|
|
|
|
bestLinkTelnetControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enabled(1),
|
|
disabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable/Disable Telnet function of SNMP/WEB Card."
|
|
::= { upsConfigbestLink 16 }
|
|
|
|
bestLinkTftpControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enabled(1),
|
|
disabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable/Disable TFTP function of SNMP/WEB Card."
|
|
::= { upsConfigbestLink 17 }
|
|
|
|
bestLinkResetToDefault OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
reset(1),
|
|
nothing(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Reset all parameters of SNMP/WEB Card to default setting."
|
|
::= { upsConfigbestLink 18 }
|
|
|
|
bestLinkRestartAgent OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
restart(1),
|
|
nothing(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Restart of SNMP/WEB Card."
|
|
::= { upsConfigbestLink 19 }
|
|
|
|
upsConfigTrapsReceivers OBJECT IDENTIFIER ::= { upsConfig 9 }
|
|
|
|
upsConfigTrapsReceiversTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsConfigTrapsReceiversEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of managers to send traps to."
|
|
::= { upsConfigTrapsReceivers 1 }
|
|
|
|
upsConfigTrapsReceiversEntry OBJECT-TYPE
|
|
SYNTAX UpsConfigTrapsReceiversEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The managers to send traps to."
|
|
INDEX { trapsIndex}
|
|
::= { upsConfigTrapsReceiversTable 1 }
|
|
|
|
UpsConfigTrapsReceiversEntry ::= SEQUENCE {
|
|
trapsIndex INTEGER,
|
|
trapsReceiverAddr IpAddress,
|
|
receiverCommunityString DisplayString,
|
|
severityLevel INTEGER,
|
|
receiverAccept INTEGER
|
|
}
|
|
|
|
trapsIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index to a trap receiver entry."
|
|
::= { upsConfigTrapsReceiversEntry 1 }
|
|
|
|
trapsReceiverAddr OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The IP address of the manager to send a trap to."
|
|
::= { upsConfigTrapsReceiversEntry 2 }
|
|
|
|
receiverCommunityString OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..19))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The community name to use in the trap when
|
|
sent to the manager."
|
|
::= { upsConfigTrapsReceiversEntry 3 }
|
|
|
|
severityLevel OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
information(1),
|
|
warning(2),
|
|
severe(3)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The severity threshold of traps to send to the manager.
|
|
Traps are labeled by severity as informational(1), warning(2),
|
|
severe(3). Only traps of equal or greater severity than
|
|
this value are sent to the manager."
|
|
::= { upsConfigTrapsReceiversEntry 4 }
|
|
|
|
receiverAccept OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
yes (1),
|
|
no (2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry will become active if yes, otherwise it will be
|
|
disabled."
|
|
::= { upsConfigTrapsReceiversEntry 5 }
|
|
|
|
upsConfigRegisteredShutdownClients OBJECT IDENTIFIER ::= { upsConfig 10 }
|
|
|
|
upsRegisteredShutdownClientsTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsRegisteredShutdownClientsEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of registered shutdown client table entries.
|
|
The table contains zero, one, or many rows at any moment,
|
|
depending upon the number of Netwatch clients registered
|
|
with BestLink"
|
|
::= { upsConfigRegisteredShutdownClients 1 }
|
|
|
|
upsRegisteredShutdownClientsEntry OBJECT-TYPE
|
|
SYNTAX UpsRegisteredShutdownClientsEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular registered shutdown client."
|
|
INDEX { upsRegisteredShutdownClientsIndex }
|
|
::= { upsRegisteredShutdownClientsTable 1 }
|
|
|
|
UpsRegisteredShutdownClientsEntry ::= SEQUENCE {
|
|
upsRegisteredShutdownClientsIndex PositiveInteger,
|
|
upsRegisteredShutdownClientsIPAddress IpAddress
|
|
}
|
|
|
|
upsRegisteredShutdownClientsIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An index of alarm entries in the RegisteredShutdownClientsTable."
|
|
::= { upsRegisteredShutdownClientsEntry 1 }
|
|
|
|
upsRegisteredShutdownClientsIPAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The IP Address of the registered shutdown client"
|
|
::= { upsRegisteredShutdownClientsEntry 2 }
|
|
|
|
upsRegisteredShutdownClientsTotalNumberOf OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The total number of registered shutdown clients."
|
|
::= { upsConfigRegisteredShutdownClients 2 }
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
-- the upsControl group
|
|
|
|
upsControlTurnOffUPS OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
cancelUpsOff(1),
|
|
upsOff(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this variable to UpsOff(2) causes the UPS to shut off.
|
|
When the UPS is in the off state, the UPS will remain off until
|
|
the ON/OFF switch is manually toggled.
|
|
|
|
Setting this variable to cancelUpsOff(1) allows for a method to cancel
|
|
the upsOff(2) command to the UPS that is still pending, or will make
|
|
an attempt to restart a UPS that has been shutdown, provided that
|
|
BestLink is powered by some other means.
|
|
|
|
Setting this variable to rebootUps(3) causes the UPS to shut off
|
|
and turn back on.
|
|
|
|
Setting this variable to cancelrebootUps(4) allows for a method to
|
|
cancel the rebootUps(3) command to the UPS that is still pending,
|
|
or will make an attempt to restart a UPS that has been shutdown,
|
|
provided that BestLink is powered by some other means."
|
|
::= { upsControl 1 }
|
|
|
|
--upsControlModeOfOperation OBJECT-TYPE
|
|
-- SYNTAX INTEGER {
|
|
-- off(1),
|
|
-- auto(2),
|
|
-- lineCondition(3),
|
|
-- inverter(4),
|
|
-- bypass(5)
|
|
-- }
|
|
-- ACCESS read-write
|
|
-- STATUS mandatory
|
|
-- DESCRIPTION
|
|
-- "Setting this variable forces the UPS into a new operating mode."
|
|
-- ::= { upsControl 2 }
|
|
|
|
upsControlActivateUpsScheduling OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off(1),
|
|
on(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this variable to On(2) causes the
|
|
UPS to activate the scheduling parameters that have been previously
|
|
configured within the upsConfigDailyShutdownScheduleTable and the
|
|
upsConfigWeeklyShutdownScheduleTable. Setting this variable to Off(1)
|
|
suspends all currently configured schedules."
|
|
::= { upsControl 4 }
|
|
|
|
|
|
upsControlEnableGeneratorSensitivity OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
auto(1),
|
|
g1(2),
|
|
g2(3),
|
|
g3(4),
|
|
g4(5),
|
|
disable(6)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this value to a value other than (disable) begins to increase the UPS ability
|
|
to reject poor line sources for example from a poorly regulated AC generator.
|
|
The greater the value the greater the tolerance to allow poor line to be used to power the UPS.
|
|
This control is used to prevent the UPS from using its batteries to create output power and
|
|
allow an AC generator to supply power to the UPS."
|
|
::= { upsControl 5 }
|
|
|
|
|
|
|
|
-- the upsTest group
|
|
|
|
upsManualTests OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noTestInitiated(1),
|
|
initiateBatteryTest(5),
|
|
abortBatteryTest(9)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this variable to any value other than (1) causes the UPS
|
|
to perform a manual test or abort a particular test in progress."
|
|
::= { upsTest 1 }
|
|
|
|
-- the upsAlarm group
|
|
|
|
upsAlarmsPresent OBJECT-TYPE
|
|
SYNTAX Gauge
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present number of active alarm conditions."
|
|
::= { upsAlarm 1 }
|
|
|
|
upsLastKnownAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
onBattery(1),
|
|
lowRuntime(2),
|
|
nearLowBattery(3),
|
|
lowBattery(4),
|
|
highBattery(5),
|
|
checkBattery(6),
|
|
replaceBattery(7),
|
|
checkInverter(8),
|
|
batteriesDisconnected(9),
|
|
outputOverload(10),
|
|
lowAcOut(11),
|
|
circuitBreakerWarning(12),
|
|
circuitBreakerShdn(13),
|
|
bypassOn(14),
|
|
autoBypass(15),
|
|
siteWiringFault(16),
|
|
checkFan(17),
|
|
highAmbTemp(18),
|
|
highHSTemp(19),
|
|
highXFMRTemp(20),
|
|
highPFMTemp(21),
|
|
probeMissing(22),
|
|
checkPowerSupply(23),
|
|
tapRegulator(24),
|
|
relayFailure(25),
|
|
checkFuse(26),
|
|
checkMOV(27),
|
|
memoryError(28),
|
|
callService(29),
|
|
upsFailed(30),
|
|
userTest(31),
|
|
testInProgress(32),
|
|
diagnosticTestFailed(33),
|
|
ePO(34),
|
|
upsOff(35),
|
|
communicationsLost(36),
|
|
noAlarm(37)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A unique identifier for an alarm condition. This
|
|
value must remain constant. Value 'noAlarm(37)'
|
|
will be returned if no Alarm has occured till the
|
|
point of GET operation."
|
|
::= { upsAlarm 2 }
|
|
|
|
upsAlarmTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsAlarmEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of alarm table entries. The table contains
|
|
zero, one, or many rows at any moment, depending upon
|
|
the number of alarm conditions in effect. The table
|
|
is initially empty at agent startup. The agent
|
|
creates a row in the table each time a condition is
|
|
detected and deletes that row when that condition no
|
|
longer pertains. The agent creates the first row with
|
|
upsAlarmIndex equal to 1, and increments the value of
|
|
upsAlarmIndex each time a new row is created."
|
|
::= { upsAlarm 3 }
|
|
|
|
upsAlarmEntry OBJECT-TYPE
|
|
SYNTAX UpsAlarmEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular alarm."
|
|
INDEX { upsAlarmIndex }
|
|
::= { upsAlarmTable 1 }
|
|
|
|
UpsAlarmEntry ::= SEQUENCE {
|
|
upsAlarmIndex PositiveInteger,
|
|
upsAlarmName INTEGER,
|
|
upsAlarmTime DisplayString
|
|
}
|
|
|
|
upsAlarmIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An index of alarm entries in the alarm log."
|
|
::= { upsAlarmEntry 1 }
|
|
|
|
upsAlarmName OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
onBattery(1),
|
|
lowRuntime(2),
|
|
nearLowBattery(3),
|
|
lowBattery(4),
|
|
highBattery(5),
|
|
checkBattery(6),
|
|
replaceBattery(7),
|
|
checkInverter(8),
|
|
batteriesDisconnected(9),
|
|
outputOverload(10),
|
|
lowAcOut(11),
|
|
circuitBreakerWarning(12),
|
|
circuitBreakerShdn(13),
|
|
bypassOn(14),
|
|
autoBypass(15),
|
|
siteWiringFault(16),
|
|
checkFan(17),
|
|
highAmbTemp(18),
|
|
highHSTemp(19),
|
|
highXFMRTemp(20),
|
|
highPFMTemp(21),
|
|
probeMissing(22),
|
|
checkPowerSupply(23),
|
|
tapRegulator(24),
|
|
relayFailure(25),
|
|
checkFuse(26),
|
|
checkMOV(27),
|
|
memoryError(28),
|
|
callService(29),
|
|
upsFailed(30),
|
|
userTest(31),
|
|
testInProgress(32),
|
|
diagnosticTestFailed(33),
|
|
ePO(34),
|
|
upsOff(35),
|
|
communicationsLost(36)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A unique identifier for an alarm condition. This
|
|
value must remain constant."
|
|
::= { upsAlarmEntry 2 }
|
|
|
|
upsAlarmTime OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The time that the alarm occurred in hh:mm:ss format."
|
|
::= { upsAlarmEntry 3 }
|
|
|
|
upsWellKnownAlarms OBJECT IDENTIFIER ::= { upsAlarm 4 }
|
|
|
|
upsAlarmOnBattery OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS is drawing power from the batteries."
|
|
::= { upsWellKnownAlarms 1 }
|
|
|
|
upsAlarmLowRuntime OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The remaining battery runtime is less than or equal
|
|
to the upsConfigLowRuntimeSetpoint."
|
|
::= { upsWellKnownAlarms 2 }
|
|
|
|
upsAlarmNearLowBattery OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The battery voltage on the UPS has reached a value where the inverter will
|
|
not be able to function very much longer."
|
|
::= { upsWellKnownAlarms 3 }
|
|
|
|
upsAlarmLowBattery OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The battery voltage on the UPS has reached a value where the inverter
|
|
has stopped providing output power to the connected load equipment.
|
|
The UPS has shutdown to protect the batteries from complete discharge."
|
|
::= {upsWellKnownAlarms 4 }
|
|
|
|
upsAlarmHighBattery OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The battery charger voltage on the UPS has reached a value that
|
|
is too high for safe battery maintenance."
|
|
::= { upsWellKnownAlarms 5 }
|
|
|
|
upsAlarmCheckBattery OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The periodic battery test has failed. A manual test of the batteries
|
|
needs to be performed to determine which battery\batteries need
|
|
replaced."
|
|
::= { upsWellKnownAlarms 6 }
|
|
|
|
-- All FERRUPS models
|
|
|
|
upsAlarmReplaceBattery OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"One or more batteries have been determined to require
|
|
replacement. Compatibility: Fortress II"
|
|
::= { upsWellKnownAlarms 7 }
|
|
|
|
upsAlarmCheckInverter OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The inverter has failed the automatic system test."
|
|
::= { upsWellKnownAlarms 8 }
|
|
|
|
upsAlarmBatteriesDisconnected OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS has detected that the DC voltage needed to start up is too
|
|
low or missing."
|
|
::= { upsWellKnownAlarms 9 }
|
|
|
|
upsAlarmOutputOverload OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The output load exceeds the UPS output capacity."
|
|
::= { upsWellKnownAlarms 10 }
|
|
|
|
upsAlarmLowAcOut OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The output load has exceeded the UPS output capacity, and the UPS has shut down."
|
|
::= { upsWellKnownAlarms 11 }
|
|
|
|
upsAlarmCircuitBreakerWarning OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"To much load equipment has been connected to the UPS and has has caused excess
|
|
current draw from the output."
|
|
|
|
-- Unity/1 single phase UPS only
|
|
|
|
::= { upsWellKnownAlarms 12 }
|
|
|
|
upsAlarmCircuitBreakerShdn OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS has shut down due to an extended excess of current draw
|
|
from the output."
|
|
|
|
-- Unity/1 single phase UPS only
|
|
|
|
::= { upsWellKnownAlarms 13 }
|
|
|
|
upsAlarmBypassOn OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Bypass is presently engaged on the UPS."
|
|
|
|
-- SOLA/BEST UPS only
|
|
|
|
::= { upsWellKnownAlarms 14 }
|
|
|
|
upsAlarmAutoBypass OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS has gone into the Auto Bypass mode to redirect power around
|
|
the UPS circuitry."
|
|
|
|
-- Unity/1 single phase UPS only
|
|
|
|
::= { upsWellKnownAlarms 15 }
|
|
|
|
upsAlarmSiteWiringFault OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS has found a problem in your wall outlet."
|
|
|
|
::= { upsWellKnownAlarms 16 }
|
|
|
|
upsAlarmCheckFan OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The fan on the UPS has stopped "
|
|
|
|
--Unity/1 single phase, Fortress, Fortress II (Fan Malfunction),
|
|
--and FERRUPS (Check Cooling)
|
|
|
|
::= { upsWellKnownAlarms 17 }
|
|
|
|
upsAlarmHighAmbTemp OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The internal temperature inside the UPS is too hot."
|
|
|
|
-- All FERRUPS models
|
|
|
|
::= { upsWellKnownAlarms 18 }
|
|
|
|
upsAlarmHighHSTemp OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Inverter heatsink assembly inside the UPS is to hot ."
|
|
|
|
-- All FERRUPS models
|
|
|
|
::= { upsWellKnownAlarms 19 }
|
|
|
|
upsAlarmHighXFMRTemp OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The temperature of the main transformer inside the UPS is too hot ."
|
|
|
|
-- All FERRUPS models
|
|
|
|
::= { upsWellKnownAlarms 20 }
|
|
|
|
upsAlarmHighPFMTemp OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The temperature of the PFM module inside the UPS is too hot ."
|
|
|
|
-- FERRUPS FE with PFM module installed
|
|
|
|
::= { upsWellKnownAlarms 21 }
|
|
|
|
upsAlarmProbeMissing OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"One or all of the sense probes has been disconnected on the UPS."
|
|
::= { upsWellKnownAlarms 22 }
|
|
|
|
upsAlarmCheckPowerSupply OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The internal DC supply voltages are attenuated or missing."
|
|
|
|
::= { upsWellKnownAlarms 23 }
|
|
|
|
upsAlarmTapRegulator OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS detected a possible failure in the tap changer (open or
|
|
welded relay, etc.)"
|
|
|
|
::= { upsWellKnownAlarms 24 }
|
|
|
|
upsAlarmRelayFailure OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"There is a hardware problem inside the UPS."
|
|
|
|
::= { upsWellKnownAlarms 25 }
|
|
|
|
upsAlarmCheckFuse OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The failure of one or more fuses has been detected."
|
|
::= { upsWellKnownAlarms 26 }
|
|
|
|
upsAlarmCheckMOV OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"One or more MOVs have failed due to a voltage surge."
|
|
::= { upsWellKnownAlarms 27 }
|
|
|
|
upsAlarmMemoryError OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS has lost the programmed settings in the memory of the logic
|
|
board."
|
|
::= { upsWellKnownAlarms 28 }
|
|
|
|
upsAlarmCallService OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A hardware malfunction has occurred inside the UPS. Please consult a
|
|
factory authorized service representative for assistance."
|
|
::= { upsWellKnownAlarms 29 }
|
|
|
|
upsAlarmupsFailed OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A general fault in the UPS has been detected."
|
|
|
|
-- BEST/SOLA UPS
|
|
|
|
::= { upsWellKnownAlarms 30 }
|
|
|
|
upsAlarmUserTest OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A user test of the alarm beeper is in progress."
|
|
|
|
-- All FERRUPS models
|
|
|
|
::= { upsWellKnownAlarms 31 }
|
|
|
|
upsAlarmTestInProgress OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A test is in progress."
|
|
::= { upsWellKnownAlarms 32 }
|
|
|
|
upsAlarmDiagnosticTestFailed OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The result of the last diagnostic test indicates a failure."
|
|
::= { upsWellKnownAlarms 33 }
|
|
|
|
upsAlarmEPO OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Emergency Power OFF feature has been activiated at the RS-232
|
|
port on the UPS."
|
|
::= { upsWellKnownAlarms 34 }
|
|
|
|
upsAlarmUpsOff OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The output of the UPS is in the off state."
|
|
::= { upsWellKnownAlarms 35 }
|
|
|
|
upsAlarmCommunicationsLost OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A problem has been encountered in the
|
|
communications between the agent and the UPS."
|
|
::= { upsWellKnownAlarms 36 }
|
|
|
|
-- Traps
|
|
|
|
upsTrapPowerFail TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"WARNING: Utility power not available."
|
|
::= 1
|
|
|
|
upsTrapPowerRestored TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"INFORMATION: Utility power has been restored."
|
|
::= 2
|
|
|
|
upsTrapUPSOnBattery TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
VARIABLES {
|
|
upsBatteryTimeOnBattery,
|
|
upsBatteryRuntimeRemaining,
|
|
upsBatteryVoltage
|
|
}
|
|
DESCRIPTION
|
|
"WARNING: The UPS has switched to battery backup power."
|
|
::= 3
|
|
|
|
upsTrapUPSNotOnBattery TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS is not on battery power."
|
|
::= 4
|
|
|
|
upsTrapLowRuntime TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"SEVERE: The runtime remaining on battery power is very short,
|
|
and the UPS will soon shut down."
|
|
::= 5
|
|
|
|
upsTrapUPSCanRunOnBattery TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS has returned from a low runtime
|
|
condition."
|
|
::= 6
|
|
|
|
upsTrapNearLowBattery TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
VARIABLES {upsBatteryVoltage }
|
|
DESCRIPTION
|
|
"SEVERE: The UPS batteries are low and will soon be exhausted.
|
|
If utility power is not restored the UPS will put itself
|
|
to 'sleep' and immediately cut power to the load."
|
|
::= 7
|
|
|
|
upsTrapHighBattery TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
VARIABLES {upsBatteryVoltage }
|
|
DESCRIPTION
|
|
"WARNING: The battery charger voltage on the UPS has reached a
|
|
value that is too high for safe battery maintenance."
|
|
|
|
-- Fortress, Fortress II, Unity/1 Single-Phase, and FERRUPS.
|
|
-- Also include (Check Charger)
|
|
-- for FERRUPS FE series.
|
|
|
|
::= 8
|
|
|
|
upsTrapBatteryOK TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS has returned from a near low or high battery
|
|
condition."
|
|
::= 9
|
|
|
|
upsTrapLowBattery TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
VARIABLES { upsBatteryVoltage }
|
|
DESCRIPTION
|
|
"SEVERE: The UPS will run for approximately 2 minutes more and then
|
|
put itself to sleep to prevent a complete discharge of the batteries."
|
|
::= 10
|
|
|
|
upsTrapCheckBattery TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"SEVERE: The UPS has failed a scheduled or manual battery test."
|
|
|
|
::= 11
|
|
|
|
upsTrapReplaceBattery TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"SEVERE: One or more UPS batteries need to be replaced."
|
|
::= 12
|
|
|
|
upsTrapCheckInverter TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"SEVERE: The UPS has failed a scheduled or manual inverter test."
|
|
::= 13
|
|
|
|
upsTrapBatteriesDisconnected TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"WARNING: The UPS battery voltage is either too low or missing to start up."
|
|
::= 14
|
|
|
|
upsTrapOutputOverload TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"WARNING: The output load exceeds the UPS output capacity."
|
|
::= 15
|
|
|
|
upsTrapUPSNoLongerOverloaded TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS has returned from an output overload
|
|
condition."
|
|
::= 16
|
|
|
|
upsTrapLowAcOut TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"SEVERE: The output load has exceeded the UPS output capacity, and the UPS has shut down."
|
|
|
|
-- All FERRUPS Models
|
|
|
|
::= 17
|
|
|
|
upsTrapCircuitBreakerWarning TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"SEVERE: To much load equipment has been connected to the UPS and
|
|
has has caused excess current draw from the output."
|
|
|
|
-- Unity/1 single phase UPS only
|
|
|
|
::= 18
|
|
|
|
upsTrapCircuitBreakerOK TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS has returned from a circuit breaker warning
|
|
condition."
|
|
::= 19
|
|
|
|
upsTrapCircuitBreakerShdn TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"SEVERE: The UPS has shut down due to an extended excess of current
|
|
draw from the output."
|
|
|
|
-- Unity/1 single phase UPS only
|
|
|
|
::= 20
|
|
|
|
upsTrapBypassOn TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"SEVERE: The Bypass is presently engaged on the UPS."
|
|
::= 21
|
|
|
|
upsTrapUPSOnline TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS has returned from an on bypass condition."
|
|
::= 22
|
|
|
|
upsTrapSiteWiringFault TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"SEVERE: The UPS has found a problem in your wall outlet."
|
|
::= 23
|
|
|
|
upsTrapCheckFan TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"SEVERE: The fan on the UPS has stopped ."
|
|
|
|
-- Unity/1 single phase, Fortress, Fortress II (Fan Malfunction)
|
|
-- and FERRUPS (Check Cooling)
|
|
|
|
::= 24
|
|
|
|
upsTrapHighUPSTemp TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"SEVERE: The internal temperature inside the UPS is too hot."
|
|
|
|
-- All FERRUPS models
|
|
|
|
::= 25
|
|
|
|
upsTrapTempOK TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS has returned from a high ambient temp
|
|
condition."
|
|
::= 26
|
|
|
|
upsTrapHighHSTemp TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"SEVERE: The Inverter heatsink assembly inside the UPS is too hot ."
|
|
|
|
-- All FERRUPS models
|
|
|
|
::= 27
|
|
|
|
upsTrapHSTempOK TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS has returned from a high heatsink temp condition."
|
|
::= 28
|
|
|
|
upsTrapHighXFMRTemp TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"SEVERE: The temperature of the main transformer inside the UPS is too hot ."
|
|
|
|
-- All FERRUPS models
|
|
|
|
::= 29
|
|
|
|
upsTrapHighPFMTemp TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"SEVERE: The temperature of the PFM module inside the UPS is too hot."
|
|
|
|
-- FERRUPS FE with PFM module installed
|
|
|
|
::= 30
|
|
|
|
upsTrapProbeMissing TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"SEVERE: One or all of the temperature probes has been disconnected on the UPS."
|
|
|
|
-- FERRUPS FE only
|
|
::= 31
|
|
|
|
upsTrapProbeReconnected TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS has returned from a probe missing condition."
|
|
::= 32
|
|
|
|
upsTrapCheckPowerSupply TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"SEVERE: The internal DC supply voltages are attenuated or missing."
|
|
::= 33
|
|
|
|
upsTrapTapRegulatorFault TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"SEVERE: The UPS detected a possible failure in the tap changer (open or welded relay, etc.)"
|
|
::= 34
|
|
|
|
upsTrapRelayFailure TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"SEVERE: There is a hardware problem inside the UPS."
|
|
::= 35
|
|
|
|
upsTrapCheckFuse TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"SEVERE: The failure of one or more fuses has been detected."
|
|
::= 36
|
|
|
|
upsTrapCheckMOV TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"SEVERE: One or more MOVs have failed due to a voltage surge."
|
|
::= 37
|
|
|
|
upsTrapMemoryError TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"SEVERE: The UPS has lost the programmed settings in the memory of the logic board."
|
|
::= 38
|
|
|
|
upsTrapCallService TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"SEVERE: A hardware malfunction has occurred inside the UPS.
|
|
Please consult a factory authorized service representative for assistance."
|
|
::= 39
|
|
|
|
upsTrapManualAlarmBeeperTestInitiated TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"INFORMATION: A manual test of the alarm beeper is being performed
|
|
on the UPS."
|
|
::= 40
|
|
|
|
upsTrapManualAlarmBeeperTestAborted TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"INFORMATION: The test of UPS has completed."
|
|
::= 41
|
|
|
|
upsTrapScheduledTestInProgress TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"INFORMATION: A test is in progress."
|
|
::= 42
|
|
|
|
upsTrapScheduledTestFailed TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"SEVERE: The last test performed failed."
|
|
::= 43
|
|
|
|
upsTrapCommunicationLost TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"SEVERE: Communication to the UPS has been lost. Steps
|
|
to reestablish communication are in progress."
|
|
::= 44
|
|
|
|
upsTrapCommunicationRestored TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"INFORMATION: Communication with the UPS has been
|
|
restored."
|
|
::= 45
|
|
|
|
upsTrapUPSGoingDown TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"WARNING: The ups has been given shutdown command
|
|
by the management station."
|
|
::= 46
|
|
|
|
upsTrapUPSTurnedOff TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"INFORMATION: The ups has been turned off
|
|
by the management station."
|
|
::= 47
|
|
|
|
upsTrapUPSSleeping TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS has entered in 'sleep' mode. Power to the
|
|
load has been cut off."
|
|
::= 48
|
|
|
|
upsTrapUPSWokeUp TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS woke up from 'sleep' mode. Power to the load has been restored."
|
|
::= 49
|
|
|
|
upsTrapUPSRebooted TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS is rebooted."
|
|
::= 50
|
|
|
|
upsTrapEmergencyPowerOFF TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"SEVERE: The Emergency Power OFF feature has been activiated at
|
|
the RS-232 port on the UPS."
|
|
::= 51
|
|
|
|
upsTrapHistLogWarn TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"WARNING: The ups history log buffer is almost full."
|
|
::= 52
|
|
|
|
upsTrapEventLogWarn TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"WARNING: The ups event log buffer is almost full."
|
|
::= 53
|
|
|
|
upsTrapUPSFail TRAP-TYPE
|
|
ENTERPRISE bestLink
|
|
DESCRIPTION
|
|
"SEVERE: A critical fault has been detected inside the UPS.
|
|
Power to the load has been shut off."
|
|
::= 54
|
|
|
|
END
|
|
|