299 lines
7.2 KiB
Plaintext

-----------------------------------------------------------------------
-- MIB table for T5541
--
-- v3.0 for firmware 1-5-7-2, 2016-04-11
-----------------------------------------------------------------------
T5541-MIB DEFINITIONS ::= BEGIN
IMPORTS
enterprises
FROM RFC1155-SMI
OBJECT-TYPE
FROM RFC-1212
TRAP-TYPE
FROM RFC-1215;
DisplayString ::= OCTET STRING
comet OBJECT IDENTIFIER ::= { enterprises 22626 }
products OBJECT IDENTIFIER ::= { comet 1 }
t5541 OBJECT IDENTIFIER ::= { products 2 }
values OBJECT IDENTIFIER ::= { t5541 1 }
global OBJECT IDENTIFIER ::= { t5541 2 }
valuesInt OBJECT IDENTIFIER ::= { t5541 3 }
settings OBJECT IDENTIFIER ::= { t5541 4 }
traps OBJECT IDENTIFIER ::= { t5541 5 }
tables OBJECT IDENTIFIER ::= { t5541 6 }
-----------------------------------------------------------------------
-- Measured values - String
-----------------------------------------------------------------------
co2 OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "CO2 level"
::= { values 4 }
co2Alarm OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm on CO2; none, high, low"
::= { values 8 }
co2Unit OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "CO2 Unit"
::= { values 12 }
co2Min OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Minimal CO2 level"
::= { values 16 }
co2Max OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Maximal CO2 level"
::= { values 20 }
-----------------------------------------------------------------------
-- Device informations
-----------------------------------------------------------------------
sensorName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..68))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Device name"
::= { global 1 }
serialNumber OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..16))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Serial number"
::= { global 2 }
deviceType OBJECT-TYPE
SYNTAX INTEGER (0..65534)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Device type"
::= { global 3 }
-----------------------------------------------------------------------
-- Measured values - Integer
-----------------------------------------------------------------------
co2Int OBJECT-TYPE
SYNTAX INTEGER (-5000..20000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "CO2 level"
::= { valuesInt 4 }
co2AlarmInt OBJECT-TYPE
SYNTAX INTEGER (0..2)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm on CO2; 0 - No, 1 - High, 2 - Low"
::= { valuesInt 8 }
-----------------------------------------------------------------------
-- Alarm settings
-----------------------------------------------------------------------
co2LowInt OBJECT-TYPE
SYNTAX INTEGER (-5000..20000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "CO2 Limit Low"
::= { settings 13 }
co2HighInt OBJECT-TYPE
SYNTAX INTEGER (-5000..20000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "CO2 Limit High"
::= { settings 14 }
co2DelayInt OBJECT-TYPE
SYNTAX INTEGER (0..4500)
ACCESS read-only
STATUS mandatory
DESCRIPTION "CO2 alaram delay [sec]"
::= { settings 15 }
co2HystInt OBJECT-TYPE
SYNTAX INTEGER (0..10000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "CO2 hysteresis"
::= { settings 16 }
-----------------------------------------------------------------------
-- Trap message
-----------------------------------------------------------------------
messageString OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Message giving more detailed information on alarms"
::= { traps 1 }
-----------------------------------------------------------------------
-- Tables
-----------------------------------------------------------------------
historyTable OBJECT-TYPE
SYNTAX SEQUENCE OF HistoryEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "Table of the history values"
::= { tables 1 }
historyEntry OBJECT-TYPE
SYNTAX HistoryEntry
ACCESS not-accessible
STATUS optional
DESCRIPTION "History values entries"
INDEX { histCO2 }
::= { historyTable 1 }
HistoryEntry ::=
SEQUENCE {
histCO2
INTEGER
}
histCO2 OBJECT-TYPE
SYNTAX INTEGER(-5000..20000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "CO2 level reading"
::= { historyEntry 4 }
-----------------------------------------------------------------------
-- Traps definition
-----------------------------------------------------------------------
trapTest TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString }
DESCRIPTION
"Testing trap, testing trap by TSensor software"
::= 0
trapNTPError TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString }
DESCRIPTION
"Error on time synchronisation via NTP"
::= 1
trapEmailErrLogin TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString }
DESCRIPTION
"SMTP error - unknown server"
::= 2
trapEmailErrAuth TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString }
DESCRIPTION
"SMTP error - authentication error"
::= 3
trapEmailErrSome TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString }
DESCRIPTION
"SMTP error - error during communication with server, unexpected return code"
::= 4
trapEmailErrSocket TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString }
DESCRIPTION
"SMTP error - socket error, server is not available"
::= 5
trapEmailErrDNS TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString }
DESCRIPTION
"SMTP error - DNS error"
::= 6
trapSOAPErrFile TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString }
DESCRIPTION
"SOAP error - file SOAP not found"
::= 7
trapSOAPErrDNS TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString }
DESCRIPTION
"SOAP error - DNS error"
::= 8
trapSOAPErrSocket TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString }
DESCRIPTION
"SOAP error - socket error, server is not available"
::= 9
trapSOAPErrDelivery TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString }
DESCRIPTION
"SOAP error - delivery error, wrong return code from server"
::= 10
trapCo2HighAlarm TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, co2, co2AlarmInt }
DESCRIPTION
"Trap for high alarm on CO2 level"
::= 14
trapCo2LowAlarm TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, co2, co2AlarmInt }
DESCRIPTION
"Trap for low alarm on CO2 level"
::= 24
trapCo2ClrAlarm TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, co2, co2AlarmInt }
DESCRIPTION
"Trap for clearing alarm on CO2 level"
::= 34
trapCo2Error TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, co2, co2AlarmInt }
DESCRIPTION
"Trap for error on CO2 level"
::= 44
END