952 lines
24 KiB
Plaintext

-----------------------------------------------------------------------
-- MIB table for H7531
--
-- v1.0 for firmware 9-5-0-0, 2017-04-19
-----------------------------------------------------------------------
H7531-MIB DEFINITIONS ::= BEGIN
IMPORTS
enterprises
FROM RFC1155-SMI
OBJECT-TYPE
FROM RFC-1212
TRAP-TYPE
FROM RFC-1215;
DisplayString ::= OCTET STRING
comet OBJECT IDENTIFIER ::= { enterprises 22626 }
products OBJECT IDENTIFIER ::= { comet 1 }
h7531 OBJECT IDENTIFIER ::= { products 2 }
values OBJECT IDENTIFIER ::= { h7531 1 }
global OBJECT IDENTIFIER ::= { h7531 2 }
valuesInt OBJECT IDENTIFIER ::= { h7531 3 }
settings OBJECT IDENTIFIER ::= { h7531 4 }
traps OBJECT IDENTIFIER ::= { h7531 5 }
tables OBJECT IDENTIFIER ::= { h7531 6 }
-----------------------------------------------------------------------
-- Measured values - String
-----------------------------------------------------------------------
temp OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Temperature"
::= { values 1 }
hum OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Relative humidity"
::= { values 2 }
compVal OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Computed value"
::= { values 3 }
press OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Atmospheric pressure"
::= { values 4 }
bin1 OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "BIN Input 1 state; 0 state description, 1 state description"
::= { values 5 }
bin2 OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "BIN Input 2 state; 0 state description, 1 state description"
::= { values 6 }
bin3 OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "BIN Input 3 state; 0 state description, 1 state description"
::= { values 7 }
re1 OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Relay 1 state; open, closed"
::= { values 8 }
re2 OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Relay 2 state; open, closed"
::= { values 9 }
tempAlarm1 OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm1 on Temperature; none, active"
::= { values 10 }
humAlarm1 OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm1 on Relative humidity; none, active"
::= { values 11 }
compValAlarm1 OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm1 on Computed value; none, active"
::= { values 12 }
pressAlarm1 OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm1 on Atmospheric pressure; none, active"
::= { values 13 }
tempAlarm2 OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm2 on Temperature; none, active"
::= { values 14 }
humAlarm2 OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm2 on Relative humidity; none, active"
::= { values 15 }
compValAlarm2 OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm2 on Computed value; none, active"
::= { values 16 }
pressAlarm2 OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm2 on Atmospheric pressure; none, active"
::= { values 17 }
bin1Alarm OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm on BIN Input 1; none, active"
::= { values 18 }
bin2Alarm OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm on BIN Input 2; none, active"
::= { values 19 }
bin3Alarm OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm on BIN Input 3; none, active"
::= { values 20 }
tempUnit OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Temperature Unit"
::= { values 21 }
humUnit OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Relative humidity Unit"
::= { values 22 }
compValUnit OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Computed value Unit"
::= { values 23 }
pressUnit OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Atmospheric pressure Unit"
::= { values 24 }
-----------------------------------------------------------------------
-- Device informations
-----------------------------------------------------------------------
sensorName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..68))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Device name"
::= { global 1 }
serialNumber OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..16))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Serial number"
::= { global 2 }
deviceType OBJECT-TYPE
SYNTAX INTEGER (0..65534)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Device type"
::= { global 3 }
-----------------------------------------------------------------------
-- Measured values - Integer
-----------------------------------------------------------------------
tempInt OBJECT-TYPE
SYNTAX INTEGER (-5000..20000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Temperature (value*10)"
::= { valuesInt 1 }
humInt OBJECT-TYPE
SYNTAX INTEGER (-5000..20000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Relative humidity (value*10)"
::= { valuesInt 2 }
compValInt OBJECT-TYPE
SYNTAX INTEGER (-5000..20000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Computed value (value*10)"
::= { valuesInt 3 }
pressInt OBJECT-TYPE
SYNTAX INTEGER (-5000..20000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Atmospheric pressure (value*X)"
::= { valuesInt 4 }
bin1Int OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "BIN Input 1 state"
::= { valuesInt 5 }
bin2Int OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "BIN Input 2 state"
::= { valuesInt 6 }
bin3Int OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "BIN Input 3 state"
::= { valuesInt 7 }
re1Int OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Relay 1 state"
::= { valuesInt 8 }
re2Int OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Relay 2 state"
::= { valuesInt 9 }
tempAlarm1Int OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm1 on Temperature"
::= { valuesInt 10 }
humAlarm1Int OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm1 on Relative humidity"
::= { valuesInt 11 }
compValAlarm1Int OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm1 on Computed value"
::= { valuesInt 12 }
pressAlarm1Int OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm1 on Atmospheric pressure"
::= { valuesInt 13 }
tempAlarm2Int OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm2 on Temperature"
::= { valuesInt 14 }
humAlarm2Int OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm2 on Relative humidity"
::= { valuesInt 15 }
compValAlarm2Int OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm2 on Computed value"
::= { valuesInt 16 }
pressAlarm2Int OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm2 on Atmospheric pressure"
::= { valuesInt 17 }
bin1AlarmInt OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm on BIN Input 1"
::= { valuesInt 18 }
bin2AlarmInt OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm on BIN Input 2"
::= { valuesInt 19 }
bin3AlarmInt OBJECT-TYPE
SYNTAX INTEGER (0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm on BIN Input 3"
::= { valuesInt 20 }
-----------------------------------------------------------------------
-- Alarm settings
-----------------------------------------------------------------------
tempLim1Int OBJECT-TYPE
SYNTAX INTEGER (-5000..20000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Temperature Alarm1 Limit (value*10)"
::= { settings 1 }
humLim1Int OBJECT-TYPE
SYNTAX INTEGER (-5000..20000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Humidity Alarm1 Limit (value*10)"
::= { settings 2 }
compValLim1Int OBJECT-TYPE
SYNTAX INTEGER (-5000..20000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Computed Alarm1 Limit (value*10)"
::= { settings 3 }
pressLim1Int OBJECT-TYPE
SYNTAX INTEGER (-5000..20000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Atmospheric pressure Alarm1 Limit (value*X)"
::= { settings 4 }
tempLim2Int OBJECT-TYPE
SYNTAX INTEGER (-5000..20000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Temperature Alarm2 Limit (value*10)"
::= { settings 5 }
humLim2Int OBJECT-TYPE
SYNTAX INTEGER (-5000..20000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Humidity Alarm2 Limit (value*10)"
::= { settings 6 }
compValLim2Int OBJECT-TYPE
SYNTAX INTEGER (-5000..20000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Computed value Alarm2 Limit (value*10)"
::= { settings 7 }
pressLim2Int OBJECT-TYPE
SYNTAX INTEGER (-5000..20000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Atmospheric pressure Alarm2 Limit (value*X)"
::= { settings 8 }
tempHyst1Int OBJECT-TYPE
SYNTAX INTEGER (0..10000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Temperature Alarm1 Hysteresis (value*10)"
::= { settings 9 }
humHyst1Int OBJECT-TYPE
SYNTAX INTEGER (0..10000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Humidity Alarm1 Hysteresis (value*10)"
::= { settings 10 }
compValHyst1Int OBJECT-TYPE
SYNTAX INTEGER (0..10000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Computed value Alarm1 Hysteresis (value*10)"
::= { settings 11 }
pressHyst1Int OBJECT-TYPE
SYNTAX INTEGER (0..10000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Atmospheric pressure Alarm1 Hysteresis (value*X)"
::= { settings 12 }
tempHyst2Int OBJECT-TYPE
SYNTAX INTEGER (0..10000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Temperature Alarm2 Hysteresis (value*10)"
::= { settings 13 }
humHyst2Int OBJECT-TYPE
SYNTAX INTEGER (0..10000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Humidity Alarm2 Hysteresis (value*10)"
::= { settings 14 }
compValHyst2Int OBJECT-TYPE
SYNTAX INTEGER (0..10000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Computed value Alarm2 Hysteresis (value*10)"
::= { settings 15 }
pressHyst2Int OBJECT-TYPE
SYNTAX INTEGER (0..10000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Atmospheric pressure Alarm2 Hysteresis (value*X)"
::= { settings 16 }
tempDelay1Int OBJECT-TYPE
SYNTAX INTEGER (0..30000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Temperature Alarm1 Delay [sec]"
::= { settings 17 }
humDelay1Int OBJECT-TYPE
SYNTAX INTEGER (0..30000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Humidity Alarm1 Delay [sec]"
::= { settings 18 }
compValDelay1Int OBJECT-TYPE
SYNTAX INTEGER (0..30000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Computed value Alarm1 Delay [sec]"
::= { settings 19 }
pressDelay1Int OBJECT-TYPE
SYNTAX INTEGER (0..30000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Atmospheric pressure Alarm1 Delay [sec]"
::= { settings 20 }
tempDelay2Int OBJECT-TYPE
SYNTAX INTEGER (0..30000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Temperature Alarm2 Delay [sec]"
::= { settings 21 }
humDelay2Int OBJECT-TYPE
SYNTAX INTEGER (0..30000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Humidity Alarm2 Delay [sec]"
::= { settings 22 }
compValDelay2Int OBJECT-TYPE
SYNTAX INTEGER (0..30000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Computed value Alarm2 Delay [sec]"
::= { settings 23 }
pressDelay2Int OBJECT-TYPE
SYNTAX INTEGER (0..30000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Atmospheric pressure Alarm2 Delay [sec]"
::= { settings 24 }
tempType1Int OBJECT-TYPE
SYNTAX INTEGER (0..2)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Temperature Alarm1 Type; 0-disbaled, 1-low, 2-high"
::= { settings 25 }
humType1Int OBJECT-TYPE
SYNTAX INTEGER (0..2)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Humidity Alarm1 Type; 0-disbaled, 1-low, 2-high"
::= { settings 26 }
compValType1Int OBJECT-TYPE
SYNTAX INTEGER (0..2)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Computed value Alarm1 Type; 0-disbaled, 1-low, 2-high"
::= { settings 27 }
pressType1Int OBJECT-TYPE
SYNTAX INTEGER (0..2)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Atmospheric pressure Alarm1 Type; 0-disbaled, 1-low, 2-high"
::= { settings 28 }
tempType2Int OBJECT-TYPE
SYNTAX INTEGER (0..2)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Temperature Alarm2 Type; 0-disbaled, 1-low, 2-high"
::= { settings 29 }
humType2Int OBJECT-TYPE
SYNTAX INTEGER (0..2)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Humidity Alarm2 Type; 0-disbaled, 1-low, 2-high"
::= { settings 30 }
compValType2Int OBJECT-TYPE
SYNTAX INTEGER (0..2)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Computed value Alarm2 Type; 0-disbaled, 1-low, 2-high"
::= { settings 31 }
pressType2Int OBJECT-TYPE
SYNTAX INTEGER (0..2)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Atmospheric pressure Alarm2 Type; 0-disbaled, 1-low, 2-high"
::= { settings 32 }
bin1DelayInt OBJECT-TYPE
SYNTAX INTEGER (0..30000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "BIN Input 1 Delay [sec]"
::= { settings 33 }
bin2DelayInt OBJECT-TYPE
SYNTAX INTEGER (0..30000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "BIN Input 2 Delay [sec]"
::= { settings 34 }
bin3DelayInt OBJECT-TYPE
SYNTAX INTEGER (0..30000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "BIN Input 3 Delay [sec]"
::= { settings 35 }
bin1TypeInt OBJECT-TYPE
SYNTAX INTEGER (0..2)
ACCESS read-only
STATUS mandatory
DESCRIPTION "BIN Input 1 Type; 0-disbaled, 1-low state, 2-high state"
::= { settings 36 }
bin2TypeInt OBJECT-TYPE
SYNTAX INTEGER (0..2)
ACCESS read-only
STATUS mandatory
DESCRIPTION "BIN Input 2 Type; 0-disbaled, 1-low state, 2-high state"
::= { settings 37 }
bin3TypeInt OBJECT-TYPE
SYNTAX INTEGER (0..2)
ACCESS read-only
STATUS mandatory
DESCRIPTION "BIN Input 3 Type; 0-disbaled, 1-low state, 2-high state"
::= { settings 38 }
-----------------------------------------------------------------------
-- Trap message
-----------------------------------------------------------------------
messageString OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Message giving more detailed information on trap"
::= { traps 1 }
-----------------------------------------------------------------------
-- Tables
-----------------------------------------------------------------------
historyTable OBJECT-TYPE
SYNTAX SEQUENCE OF HistoryEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "Table of the history values"
::= { tables 1 }
historyEntry OBJECT-TYPE
SYNTAX HistoryEntry
ACCESS not-accessible
STATUS optional
DESCRIPTION "History values entries"
INDEX { histTemp }
::= { historyTable 1 }
HistoryEntry ::=
SEQUENCE {
histTemp
INTEGER,
histHum
INTEGER,
histCompVal
INTEGER,
histPress
INTEGER
}
histTemp OBJECT-TYPE
SYNTAX INTEGER(-5000..20000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Temperature reading"
::= { historyEntry 1 }
histHum OBJECT-TYPE
SYNTAX INTEGER(-5000..20000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Humidity reading"
::= { historyEntry 2 }
histCompVal OBJECT-TYPE
SYNTAX INTEGER (-5000..20000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Computed value reading"
::= { historyEntry 3 }
histPress OBJECT-TYPE
SYNTAX INTEGER(-5000..20000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Atmospheric pressure reading"
::= { historyEntry 4 }
-----------------------------------------------------------------------
-- Traps definition
-----------------------------------------------------------------------
trapTest TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString }
DESCRIPTION "Testing trap, testing trap by TSensor software"
::= 0
trapNTPError TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString }
DESCRIPTION "Error on time synchronisation via NTP"
::= 1
trapEmailErrLogin TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString }
DESCRIPTION "SMTP error - unknown server"
::= 2
trapEmailErrAuth TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString }
DESCRIPTION "SMTP error - authentication error"
::= 3
trapEmailErrSome TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString }
DESCRIPTION "SMTP error - error during communication with server, unexpected return code"
::= 4
trapEmailErrSocket TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString }
DESCRIPTION "SMTP error - socket error, server is not available"
::= 5
trapEmailErrDNS TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString }
DESCRIPTION "SMTP error - DNS error"
::= 6
trapSOAPErrFile TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString }
DESCRIPTION "SOAP error - file SOAP not found"
::= 7
trapSOAPErrDNS TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString }
DESCRIPTION "SOAP error - DNS error"
::= 8
trapSOAPErrSocket TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString }
DESCRIPTION "SOAP error - socket error, server is not available"
::= 9
trapSOAPErrDelivery TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString }
DESCRIPTION "SOAP error - delivery error, wrong return code from server"
::= 10
trapTempAlarm1 TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, temp, tempAlarm1Int }
DESCRIPTION "Trap for alarm1 on Temperature"
::= 11
trapHumAlarm1 TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, hum, humAlarm1Int }
DESCRIPTION "Trap for alarm1 on Relative humidity"
::= 12
trapCompValAlarm1 TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, compVal, compValAlarm1Int }
DESCRIPTION "Trap for alarm1 on Computed value"
::= 13
trapPressAlarm1 TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, press, pressAlarm1Int }
DESCRIPTION "Trap for alarm1 on Atmospheric pressure"
::= 14
trapTempAlarm2 TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, temp, tempAlarm2Int }
DESCRIPTION "Trap for alarm2 on Temperature"
::= 21
trapHumAlarm2 TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, hum, humAlarm2Int }
DESCRIPTION "Trap for alarm2 on Relative humidity"
::= 22
trapCompValAlarm2 TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, compVal, compValAlarm2Int }
DESCRIPTION "Trap for alarm2 on Computed value"
::= 23
trapPressAlarm2 TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, press, pressAlarm2Int }
DESCRIPTION "Trap for alarm2 on Atmospheric pressure"
::= 24
trapTempClrAlarm1 TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, temp, tempAlarm1Int }
DESCRIPTION "Trap for clearing alarm 1 on Temperature"
::= 31
trapHumClrAlarm1 TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, hum, humAlarm1Int }
DESCRIPTION "Trap for clearing alarm 1 on Relative humidity"
::= 32
trapCompValClrAlarm1 TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, compVal, compValAlarm1Int }
DESCRIPTION "Trap for clearing alarm 1 on Computed value"
::= 33
trapPressClrAlarm1 TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, press, pressAlarm1Int }
DESCRIPTION "Trap for clearing alarm 1 on Atmospheric pressure"
::= 34
trapTempClrAlarm2 TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, temp, tempAlarm2Int }
DESCRIPTION "Trap for clearing alarm 2 on Temperature"
::= 41
trapHumClrAlarm2 TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, hum, humAlarm2Int }
DESCRIPTION "Trap for clearing alarm 2 on Relative humidity"
::= 42
trapCompValClrAlarm2 TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, compVal, compValAlarm2Int }
DESCRIPTION "Trap for clearing alarm 2 on Computed value"
::= 43
trapPressClrAlarm2 TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, press, pressAlarm2Int }
DESCRIPTION "Trap for clearing alarm 2 on Atmospheric pressure"
::= 44
trapBin1Alarm TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, bin1Int, bin1AlarmInt }
DESCRIPTION "Trap for alarm on BIN Input 1"
::= 51
trapBin2Alarm TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, bin2Int, bin2AlarmInt }
DESCRIPTION "Trap for alarm on BIN Input 2"
::= 52
trapBin3Alarm TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, bin3Int, bin3AlarmInt }
DESCRIPTION "Trap for alarm on BIN Input 3"
::= 53
trapBin1ClrAlarm TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, bin1Int, bin1AlarmInt }
DESCRIPTION "Trap for clearing alarm on BIN Input 1"
::= 61
trapBin2ClrAlarm TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, bin2Int, bin2AlarmInt }
DESCRIPTION "Trap for clearing alarm on BIN Input 2"
::= 62
trapBin3ClrAlarm TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, bin3Int, bin3AlarmInt }
DESCRIPTION "Trap for clearing alarm on BIN Input 3"
::= 63
trapRelay1Closed TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, re1Int }
DESCRIPTION "Trap for closed Relay 1"
::= 70
trapRelay2Closed TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, re2Int }
DESCRIPTION "Trap for closed Relay 2"
::= 71
trapRelay1Open TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, re1Int }
DESCRIPTION "Trap for open Relay 1"
::= 72
trapRelay2Open TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, re2Int }
DESCRIPTION "Trap for open Relay 2"
::= 73
trapAcousticActivated TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString }
DESCRIPTION "Trap for activated acoustic"
::= 74
trapAcousticDeactivated TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString }
DESCRIPTION "Trap for deactivated acoustic"
::= 75
END