Observium_CE/mibs/ciena/WWP-ENVIRON-MIB

969 lines
30 KiB
Plaintext

--
-- WWP-ENVIRON-MIB.my
--
--
WWP-ENVIRON-MIB DEFINITIONS ::= BEGIN
IMPORTS
TEXTUAL-CONVENTION FROM SNMPv2-TC
NOTIFICATION-TYPE, Counter32, Integer32, OBJECT-TYPE, MODULE-IDENTITY
FROM SNMPv2-SMI
TruthValue, DisplayString
FROM SNMPv2-TC
wwpModules
FROM WWP-SMI;
wwpEnvironMIB MODULE-IDENTITY
LAST-UPDATED "200104031700Z"
ORGANIZATION "World Wide Packets, Inc"
CONTACT-INFO
" Mib Meister
Postal: World Wide Packets
P.O. Box 950
Veradale, WA 99037
USA
Phone: +1 509 242 9000
Email: mib.meister@worldwidepackets.com"
DESCRIPTION
"The MIB module for the WWP Specifc environment. It contains the
environment variables for the WWP System."
REVISION "200304280000Z" -- 28th April. 2003
DESCRIPTION
"Updated the battery status. Added the four notifications
for the battery state change. The new added notification
wwpEnvPortalPowerSourceNotification replaces the
wwpEnvPowerSwitchNotification."
REVISION "200303110000Z" -- 11th March. 2003
DESCRIPTION
"Changed the temperature thresholds to be read-write.
Added Battery States and updated the notification for the
battery states. Added dry contact, door and RF notifications."
REVISION "200104031700Z"
DESCRIPTION
"Initial creation."
::= { wwpModules 13 }
--
-- Textual conventions
--
PortList ::= TEXTUAL-CONVENTION
STATUS current
DESCRIPTION
"Each octet within this value specifies a set of eight
ports, with the first octet specifying ports 1 through
8, the second octet specifying ports 9 through 16, etc.
Within each octet, the most significant bit represents
the lowest numbered port, and the least significant bit
represents the highest numbered port. Thus, each port
of the bridge is represented by a single bit within the
value of this object. If that bit has a value of '1'
then that port is included in the set of ports; the port
is not included if its bit has a value of '0'."
SYNTAX OCTET STRING (SIZE (0..255))
--
-- Node definitions
--
wwpEnvironMIBObjects OBJECT IDENTIFIER ::= { wwpEnvironMIB 1 }
wwpEnviron OBJECT IDENTIFIER ::= { wwpEnvironMIBObjects 1 }
-- the Battery Module
wwpEnvBatteryModule OBJECT IDENTIFIER ::= { wwpEnviron 1 }
-- the Power Supply module group.
wwpEnvPowerSupplyModule OBJECT IDENTIFIER ::= { wwpEnviron 2 }
-- the Fan module group.
wwpEnvFanModule OBJECT IDENTIFIER ::= { wwpEnviron 3 }
-- the Temp Module
wwpEnvTempSensor OBJECT IDENTIFIER ::= { wwpEnviron 4 }
-- The Port Power Management Module
wwpEnvPortPowerMgmt OBJECT IDENTIFIER ::= { wwpEnviron 5 }
-- The Environ Notif Objects
wwpEnvNotif OBJECT IDENTIFIER ::= { wwpEnviron 6 }
-- The Portal Battery Module
wwpEnvPortalBatteryModule OBJECT IDENTIFIER ::= { wwpEnviron 7 }
-- The Door Module
wwpEnvDoorModule OBJECT IDENTIFIER ::= { wwpEnviron 8 }
-- The Dry Contact Module
wwpEnvDryContactModule OBJECT IDENTIFIER ::= { wwpEnviron 9 }
-- The RF module
wwpEnvRFModule OBJECT IDENTIFIER ::= { wwpEnviron 10 }
-- Notifications
wwpEnvironMIBNotificationPrefix OBJECT IDENTIFIER ::= { wwpEnvironMIB 2 }
wwpEnvironMIBNotifications OBJECT IDENTIFIER ::=
{ wwpEnvironMIBNotificationPrefix 0 }
-- Conformance information
wwpEnvironMIBConformance OBJECT IDENTIFIER ::= { wwpEnvironMIB 3 }
wwpEnvironMIBCompliances OBJECT IDENTIFIER ::= { wwpEnvironMIBConformance 1 }
wwpEnvironMIBGroups OBJECT IDENTIFIER ::= { wwpEnvironMIBConformance 2 }
wwpEnvBattStatus OBJECT-TYPE
SYNTAX INTEGER {
presentAndWorking(1),
presentButNotWorking(2),
notPresent(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Describes the battery hardware the device is configured
with. For Portals, the Management station should use the
new added object wwpEnvPortalCurrentBattStatus
for the batery status."
::= { wwpEnvBatteryModule 1 }
--
-- Power Module
--
wwpEnvPowerTable OBJECT-TYPE
SYNTAX SEQUENCE OF WwpEnvPowerEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of power supply entries."
::= { wwpEnvPowerSupplyModule 1 }
wwpEnvPowerEntry OBJECT-TYPE
SYNTAX WwpEnvPowerEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry in the powerTable providing objects for a
power supply."
INDEX { wwpEnvPowerSupplyNum }
::= { wwpEnvPowerTable 1 }
WwpEnvPowerEntry ::= SEQUENCE {
wwpEnvPowerSupplyNum Integer32,
wwpEnvPowerSupplyState INTEGER,
wwpEnvPowerSupplyType INTEGER,
wwpEnvPowerSupplyRedundancy INTEGER
}
wwpEnvPowerSupplyNum OBJECT-TYPE
SYNTAX Integer32(1..2147483647)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Denotes the power supply."
::= { wwpEnvPowerEntry 1 }
wwpEnvPowerSupplyState OBJECT-TYPE
SYNTAX INTEGER {
infoNotAvailable(1),
notInstalled(2),
installedAndOperating(3),
installedAndNotOperating(4)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Denotes the power supply's state."
::= { wwpEnvPowerEntry 2 }
wwpEnvPowerSupplyType OBJECT-TYPE
SYNTAX INTEGER {
ac-dc(1),
dc-dc(2),
notSupported(3), -- Object is not supported
highOutput(4),
external(5)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Denotes the power supply type."
::= { wwpEnvPowerEntry 3 }
wwpEnvPowerSupplyRedundancy OBJECT-TYPE
SYNTAX INTEGER {
redundant(1),
notRedundant(2),
notSupported(3) -- Object is not supported
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Denotes whether or not the power supply is redundant."
::= { wwpEnvPowerEntry 4 }
wwpEnvRedPowerSupplyNotifEnabled OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"This variable indicates whether the system
generates the wwpEnvRedPowerSupplyNotification.
A false value prevents this notifications
from being generated by this system."
DEFVAL { true }
::= { wwpEnvPowerSupplyModule 2 }
--
-- The Fan module group
--
wwpEnvFanModuleTable OBJECT-TYPE
SYNTAX SEQUENCE OF WwpEnvFanModuleEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of fan module entries."
::= { wwpEnvFanModule 1 }
wwpEnvFanModuleEntry OBJECT-TYPE
SYNTAX WwpEnvFanModuleEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry in the fan module Table providing objects for a
fan module."
INDEX { wwpEnvFanModuleNum }
::= { wwpEnvFanModuleTable 1 }
WwpEnvFanModuleEntry ::= SEQUENCE {
wwpEnvFanModuleNum Integer32,
wwpEnvFanModuleState INTEGER,
wwpEnvFanAvgSpeed Integer32,
wwpEnvFanCurrentSpeed Integer32,
wwpEnvFanMinSpeed Integer32
}
wwpEnvFanModuleNum OBJECT-TYPE
SYNTAX Integer32 (1..2147483647)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Denotes the Fan module."
::= { wwpEnvFanModuleEntry 1 }
wwpEnvFanModuleState OBJECT-TYPE
SYNTAX INTEGER {
infoNotAvailable(1),
notInstalled(2),
installedAndOperating(3),
installedAndNotOperating(4)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Denotes the fan modules state."
::= { wwpEnvFanModuleEntry 2 }
wwpEnvFanAvgSpeed OBJECT-TYPE
SYNTAX Integer32 (0..2147483647)
UNITS "rpm"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The fans average speed in RPM. The average is calculated
on a continuous basis from system startup."
::= { wwpEnvFanModuleEntry 3 }
wwpEnvFanCurrentSpeed OBJECT-TYPE
SYNTAX Integer32 (0..2147483647)
UNITS "rpm"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current speed of the fan in RPM."
::= { wwpEnvFanModuleEntry 4 }
wwpEnvFanMinSpeed OBJECT-TYPE
SYNTAX Integer32 (0..2147483647)
UNITS "rpm"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The minimum speed of the fan in RPM."
::= { wwpEnvFanModuleEntry 5 }
wwpEnvFanModuleNotifEnabled OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This variable indicates whether the system
generates the wwpEnvFanModuleNotification.
A false value prevents this notifications
from being generated by this system."
DEFVAL { true }
::= { wwpEnvFanModule 2 }
--
-- The Temp module group
--
wwpEnvTempSensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF WwpEnvTempSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of Temp Sensors entries."
::= { wwpEnvTempSensor 1 }
wwpEnvTempSensorEntry OBJECT-TYPE
SYNTAX WwpEnvTempSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry in the Temp Sensor Table providing objects for a
Temp Sensor."
INDEX { wwpEnvTempSensorNum }
::= { wwpEnvTempSensorTable 1 }
WwpEnvTempSensorEntry ::= SEQUENCE {
wwpEnvTempSensorNum Integer32,
wwpEnvTempSensorValue Integer32,
wwpEnvTempSensorHighThreshold Integer32,
wwpEnvTempSensorLowThreshold Integer32,
wwpEnvTempSensorState INTEGER
}
wwpEnvTempSensorNum OBJECT-TYPE
SYNTAX Integer32 (1..2147483647)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Denotes the Temp sensor module."
::= { wwpEnvTempSensorEntry 1 }
wwpEnvTempSensorValue OBJECT-TYPE
SYNTAX Integer32
UNITS "degrees Celsius"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The value of temperature measured by the sensor
inside the device in degrees C."
::= { wwpEnvTempSensorEntry 2 }
wwpEnvTempSensorHighThreshold OBJECT-TYPE
SYNTAX Integer32
UNITS "degrees Celsius"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The highest value that the object wwpEnvTempSensorValue
may obtain at which a wwpEnvMIBTempNotification is sent."
::= { wwpEnvTempSensorEntry 3 }
wwpEnvTempSensorLowThreshold OBJECT-TYPE
SYNTAX Integer32
UNITS "degrees Celsius"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The Lowest value that the object wwpEnvTempSensorValue
may obtain at which a wwpEnvMIBTempNotification is sent."
::= { wwpEnvTempSensorEntry 4 }
wwpEnvTempSensorState OBJECT-TYPE
SYNTAX INTEGER {
higherThanThreshold(0),
normal(1),
lowerThanThreshold(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The state indicates whether the current temp is greater than,
equal to or less than the threshold state."
::= { wwpEnvTempSensorEntry 5 }
wwpEnvTempNotifEnabled OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This variable indicates whether the system
generates the wwpEnvTempNotification.
A false value prevents this notifications
from being generated by this system."
DEFVAL { true }
::= { wwpEnvTempSensor 2 }
--
-- The Port Power Management group
--
wwpPortPowerMgmtTable OBJECT-TYPE
SYNTAX SEQUENCE OF WwpPortPowerMgmtEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of Port Power Management entries. This table affects
the port power only when the input power supply is Battery."
::= { wwpEnvPortPowerMgmt 1 }
wwpPortPowerMgmtEntry OBJECT-TYPE
SYNTAX WwpPortPowerMgmtEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry in the Port Power Mgmt Table providing objects for
Port Power Management."
INDEX { wwpEnvPortBankId }
::= { wwpPortPowerMgmtTable 1 }
WwpPortPowerMgmtEntry ::= SEQUENCE {
wwpEnvPortBankId Integer32,
wwpEnvPortMap PortList,
wwpEnvPortBankOn INTEGER
}
wwpEnvPortBankId OBJECT-TYPE
SYNTAX Integer32 (1..2147483647)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Denotes the Port Bank module. A Bank is a set of ports
for the power management when the source of the input
power is switched to battery."
::= { wwpPortPowerMgmtEntry 1 }
wwpEnvPortMap OBJECT-TYPE
SYNTAX PortList
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The port map associated with this BankId."
::= { wwpPortPowerMgmtEntry 2 }
wwpEnvPortBankOn OBJECT-TYPE
SYNTAX INTEGER {
off(0),
on(1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The object to decide whether the port related to this Bank
should be on or not if the input power supply is switched
to Battery."
::= { wwpPortPowerMgmtEntry 3 }
--
-- notif group
--
wwpPowerSwitchingOp OBJECT-TYPE
SYNTAX INTEGER {
none(0),
acToBattery(1),
bateryToAC(2)
}
--MAX-ACCESS accessible-for-notify
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The object to notify whether the input power supply is switching
from ac to Battery or vice versa."
::= { wwpEnvNotif 1 }
--
-- portal battery group
--
wwpEnvPortalBatteryStatus OBJECT-TYPE
SYNTAX INTEGER {
present(1),
missing(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Describes the current status of the
battery. If battery is connected then the
status is indicated as 'present'."
::= { wwpEnvPortalBatteryModule 1 }
wwpEnvPortalBatteryVoltageLevel OBJECT-TYPE
SYNTAX INTEGER {
normal(1),
low(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Describes the current voltage level of the
battery."
::= { wwpEnvPortalBatteryModule 2 }
wwpEnvPortalBatteryCondition OBJECT-TYPE
SYNTAX INTEGER {
good(1),
bad(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Describes the current condition of the battery."
::= { wwpEnvPortalBatteryModule 3 }
wwpEnvPortalPowerSource OBJECT-TYPE
SYNTAX INTEGER {
primaryPower(1),
battery(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Describes the current power source for the device."
::= { wwpEnvPortalBatteryModule 4 }
wwpEnvBatteryNormalStateName OBJECT-TYPE
SYNTAX DisplayString (SIZE(1..128))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The state name associated with the low state
of the battery."
::= { wwpEnvPortalBatteryModule 5 }
wwpEnvBatteryLowStateName OBJECT-TYPE
SYNTAX DisplayString (SIZE(1..128))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The state name associated with the normal state
of the battery."
::= { wwpEnvPortalBatteryModule 6 }
wwpEnvBatteryGoodStateName OBJECT-TYPE
SYNTAX DisplayString (SIZE(1..128))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The state name associated with the good state
of the battery."
::= { wwpEnvPortalBatteryModule 7 }
wwpEnvBatteryBadStateName OBJECT-TYPE
SYNTAX DisplayString (SIZE(1..128))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The state name associated with the bad state
of the battery."
::= { wwpEnvPortalBatteryModule 8 }
wwpEnvBatteryPresentStateName OBJECT-TYPE
SYNTAX DisplayString (SIZE(1..128))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The state name associated with the battery state
'present'."
::= { wwpEnvPortalBatteryModule 9 }
wwpEnvBatteryMissingStateName OBJECT-TYPE
SYNTAX DisplayString (SIZE(1..128))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The state name associated with the battery state
'missing'."
::= { wwpEnvPortalBatteryModule 10 }
wwpEnvBatteryPowerPrimaryStateName OBJECT-TYPE
SYNTAX DisplayString (SIZE(1..128))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The state name associated with the state when the
device is on primary power."
::= { wwpEnvPortalBatteryModule 11 }
wwpEnvBatteryPowerBatteryStateName OBJECT-TYPE
SYNTAX DisplayString (SIZE(1..128))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The state name associated with the state when the
device is on battery power."
::= { wwpEnvPortalBatteryModule 12 }
wwpEnvBatteryLowStateNotifEnabled OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This variable indicates whether the system
will generate the wwpEnvPortalBatteryStatusNotification
in case of battery state changing from normal to low
or vice versa.
A false value prevents this notifications
from being generated by this system."
DEFVAL { true }
::= { wwpEnvPortalBatteryModule 13 }
wwpEnvBatteryBadStateNotifEnabled OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This variable indicates whether the system
will generate the wwpEnvPortalBatteryStatusNotification
in case of battery state changing from good to bad
or vice versa.
A false value prevents this notifications
from being generated by this system."
DEFVAL { true }
::= { wwpEnvPortalBatteryModule 14 }
wwpEnvBatteryMissingStateNotifEnabled OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This variable indicates whether the system
will generate the wwpEnvPortalBatteryStatusNotification
in case of battery state changing from present to missing
or vice versa.
A false value prevents this notifications
from being generated by this system."
DEFVAL { true }
::= { wwpEnvPortalBatteryModule 15 }
wwpEnvBatteryPowerNotifEnabled OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This variable indicates whether the system
will generate the wwpEnvPortalBatteryStatusNotification
in case of input power changing from primary to battery
or vice versa.
A false value prevents this notifications
from being generated by this system."
DEFVAL { true }
::= { wwpEnvPortalBatteryModule 16 }
wwpEnvBatteryPeriodicTrapsTimer OBJECT-TYPE
SYNTAX INTEGER(0..8760)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Adjusts the amount of time, in hours, when the current
state of the battery is evaluated and status traps are
automatically issued. When set to zero (0) no periodic
evaluation of the battery is performed."
DEFVAL { 0 }
::= { wwpEnvPortalBatteryModule 17 }
wwpEnvBatteryPowerUpTrapsEnable OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"When set to true, upon portal power-up the state of
the battery is evaluated and status traps are issued.
When set to false, no portal power-up battery state
traps will be issued."
DEFVAL { false }
::= { wwpEnvPortalBatteryModule 18 }
--
-- door group
--
wwpEnvDoorState OBJECT-TYPE
SYNTAX INTEGER {
open(1),
close(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The state of the door."
::= { wwpEnvDoorModule 1 }
wwpEnvDoorNotifEnabled OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This variable indicates whether the system
generates the wwpEnvDoorStateChgNotification.
A false value prevents this notifications
from being generated by this system."
DEFVAL { true }
::= { wwpEnvDoorModule 2 }
--
-- dry contact group
--
wwpEnvDryContactOpenStateName OBJECT-TYPE
SYNTAX DisplayString ( SIZE(1..128))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The state name associated with the open state
of the dry contact."
::= { wwpEnvDryContactModule 1 }
wwpEnvDryContactOpenStateChgAccumulate OBJECT-TYPE
SYNTAX INTEGER {
enable(1),
disable(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Setting this object to 'enable' will cause the
system to accumulate open state changes."
::= { wwpEnvDryContactModule 2 }
wwpEnvDryContactOpenStateCount OBJECT-TYPE
SYNTAX Counter32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of times the dry contact has
entered the open state."
::= { wwpEnvDryContactModule 3 }
wwpEnvDryContactOpenStateNotifEnabled OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This variable indicates whether the system
generates the wwpEnvDryContactOpenStateNotification.
A false value prevents this notifications
from being generated by this system."
DEFVAL { true }
::= { wwpEnvDryContactModule 4 }
wwpEnvDryContactCloseStateName OBJECT-TYPE
SYNTAX DisplayString ( SIZE(1..128))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The state name associated with the close state
of the dry contact."
::= { wwpEnvDryContactModule 5 }
wwpEnvDryContactCloseStateChgAccumulate OBJECT-TYPE
SYNTAX INTEGER {
enable(1),
disable(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Setting this object to 'enable' will cause the
system to accumulate close state changes."
::= { wwpEnvDryContactModule 6 }
wwpEnvDryContactCloseStateCount OBJECT-TYPE
SYNTAX Counter32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of times the dry contact has
entered the close state."
::= { wwpEnvDryContactModule 7 }
wwpEnvDryContactCloseStateNotifEnabled OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This variable indicates whether the system
generates the wwpEnvDryContactCloseStateNotification.
A false value prevents this notifications
from being generated by this system."
DEFVAL { true }
::= { wwpEnvDryContactModule 8 }
--
-- RF module
--
wwpEnvRFModuleState OBJECT-TYPE
SYNTAX INTEGER {
enable(1),
disable(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Setting this object to 'enable' will set the
the RF state to 'enable'."
::= { wwpEnvRFModule 1 }
wwpEnvRFModuleSignalDetect OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The status of signal detect by the RF Module."
::= { wwpEnvRFModule 2 }
wwpEnvPowerSupplyStatusNotification NOTIFICATION-TYPE
OBJECTS {
wwpEnvPowerSupplyNum,
wwpEnvPowerSupplyState,
wwpEnvPowerSupplyType
}
STATUS current
DESCRIPTION
"A wwpEnvPowerSupplyStatusNotification is sent if a
power supply state is changed."
::= { wwpEnvironMIBNotifications 1 }
wwpEnvFanModuleNotification NOTIFICATION-TYPE
OBJECTS {
wwpEnvFanModuleNum,
wwpEnvFanModuleState
}
STATUS current
DESCRIPTION
"A wwpEnvFanModuleNotification is sent if the
fan state changes."
::= { wwpEnvironMIBNotifications 2 }
wwpEnvTempNotification NOTIFICATION-TYPE
OBJECTS {
wwpEnvTempSensorState,
wwpEnvTempSensorValue,
wwpEnvTempSensorHighThreshold,
wwpEnvTempSensorLowThreshold
}
STATUS current
DESCRIPTION
"A wwpEnvTempNotification is sent if the
wwpEnvTempSensorState is changed."
::= { wwpEnvironMIBNotifications 3 }
wwpEnvPowerSwitchNotification NOTIFICATION-TYPE
OBJECTS {
wwpPowerSwitchingOp
}
STATUS current
DESCRIPTION
"A wwpEnvPowerSwitchNotification is sent if the
input power supply is switched to Battery from the
AC power or switched from the Battery to the AC Power."
::= { wwpEnvironMIBNotifications 4 }
wwpEnvPortalBatteryStatusNotification NOTIFICATION-TYPE
OBJECTS {
wwpEnvPortalBatteryStatus
}
STATUS current
DESCRIPTION
"A wwpEnvPortalBatteryStatusNotification is sent if the
Battery status changes. If the device supports the
configurable battery state names, then the corresponding
battery state name should also be sent with this notification."
::= { wwpEnvironMIBNotifications 5 }
wwpEnvPortalBatteryVoltageLevelNotification NOTIFICATION-TYPE
OBJECTS {
wwpEnvPortalBatteryVoltageLevel
}
STATUS current
DESCRIPTION
"A wwpEnvPortalBatteryVoltageLevelNotification is sent if the
Battery voltage level changes from normal to low or vice versa.
If the device supports the configurable battery state names, then
the corresponding battery state name should also be sent with
this notification."
::= { wwpEnvironMIBNotifications 6 }
wwpEnvPortalBatteryConditionNotification NOTIFICATION-TYPE
OBJECTS {
wwpEnvPortalBatteryCondition
}
STATUS current
DESCRIPTION
"A wwpEnvPortalBatteryConditionNotification is sent if the
Battery condition changes from good to bad or vice versa.
If the device supports the configurable battery state names, then
the corresponding battery state name should also be sent with
this notification."
::= { wwpEnvironMIBNotifications 7 }
wwpEnvPortalPowerSourceNotification NOTIFICATION-TYPE
OBJECTS {
wwpEnvPortalPowerSource
}
STATUS current
DESCRIPTION
"A wwpEnvPortalPowerSourceNotification is sent if the
Battery input power source changes from battery to primary
power or vice versa. A device which supports
wwpEnvPowerSwitchNotification should not support this
notification. If the device supports the configurable
battery state names, then the corresponding battery state
name should also be sent with this notification."
::= { wwpEnvironMIBNotifications 8 }
wwpEnvDoorStateChgNotification NOTIFICATION-TYPE
OBJECTS {
wwpEnvDoorState
}
STATUS current
DESCRIPTION
"A wwpEnvDoorStateChgNotification is sent if the
door state changes."
::= { wwpEnvironMIBNotifications 9 }
wwpEnvDryContactOpenStateNotification NOTIFICATION-TYPE
OBJECTS {
wwpEnvDryContactOpenStateName,
wwpEnvDryContactOpenStateCount
}
STATUS current
DESCRIPTION
"A wwpEnvDryContactOpenStateNotification is sent when the
dry contact enters in the open state."
::= { wwpEnvironMIBNotifications 10 }
wwpEnvDryContactCloseStateNotification NOTIFICATION-TYPE
OBJECTS {
wwpEnvDryContactCloseStateName,
wwpEnvDryContactCloseStateCount
}
STATUS current
DESCRIPTION
"A wwpEnvDryContactCloseStateNotification is sent when the
dry contact enters in the close state."
::= { wwpEnvironMIBNotifications 11 }
END
--
-- WWP-ENVIRON-MIB
--