<?php
|
|
/**
|
|
* Observium
|
|
*
|
|
* This file is part of Observium.
|
|
*
|
|
* @package observium
|
|
* @subpackage discovery
|
|
* @copyright (C) Adam Armstrong
|
|
*
|
|
*/
|
|
|
|
// NOTE. This is old version of WebGraph-Thermo-Hygrometer-US-MIB
|
|
$mib = 'WebGraph-OLD-Thermo-Hygrometer-US-MIB';
|
|
|
|
//WebGraph-OLD-Thermo-Hygrometer-US-MIB::wtWebGraphThermHygroBinaryTempValue.1 = INTEGER: 266
|
|
//WebGraph-OLD-Thermo-Hygrometer-US-MIB::wtWebGraphThermHygroBinaryTempValue.2 = INTEGER: 587
|
|
//WebGraph-OLD-Thermo-Hygrometer-US-MIB::wtWebGraphThermHygroPortName.1 = STRING: "Temperatur"
|
|
//WebGraph-OLD-Thermo-Hygrometer-US-MIB::wtWebGraphThermHygroPortName.2 = STRING: "rel. Feuchte"
|
|
//WebGraph-OLD-Thermo-Hygrometer-US-MIB::wtWebGraphThermHygroPortText.1 = STRING: "Sensorbeschreibung 1"
|
|
//WebGraph-OLD-Thermo-Hygrometer-US-MIB::wtWebGraphThermHygroPortText.2 = STRING: "Sensorbeschreibung 2"
|
|
//WebGraph-OLD-Thermo-Hygrometer-US-MIB::wtWebGraphThermHygroPortSensorSelect.1 = Hex-STRING: 00 00 00 02
|
|
//WebGraph-OLD-Thermo-Hygrometer-US-MIB::wtWebGraphThermHygroPortSensorSelect.2 = Hex-STRING: 00 00 00 01
|
|
|
|
//WebGraph-OLD-Thermo-Hygrometer-US-MIB::wtWebGraphThermHygroAlarmMin.1 = STRING: "10"
|
|
//WebGraph-OLD-Thermo-Hygrometer-US-MIB::wtWebGraphThermHygroAlarmMax.1 = STRING: "25"
|
|
//WebGraph-OLD-Thermo-Hygrometer-US-MIB::wtWebGraphThermHygroAlarmRHMin.1 = STRING: "10"
|
|
//WebGraph-OLD-Thermo-Hygrometer-US-MIB::wtWebGraphThermHygroAlarmRHMax.1 = STRING: "85"
|
|
//WebGraph-OLD-Thermo-Hygrometer-US-MIB::wtWebGraphThermHygroAlarmAHMin.1 = STRING: "1"
|
|
//WebGraph-OLD-Thermo-Hygrometer-US-MIB::wtWebGraphThermHygroAlarmAHMax.1 = STRING: "25"
|
|
|
|
$oids = snmpwalk_cache_oid($device, "wtWebGraphThermHygroBinaryTempValueTable", [], $mib);
|
|
if ($GLOBALS['snmp_status']) {
|
|
$oids = snmpwalk_cache_oid($device, "wtWebGraphThermHygroPortTable", $oids, $mib);
|
|
|
|
// Temperature
|
|
if (is_numeric($oids[1]['wtWebGraphThermHygroBinaryTempValue'])) {
|
|
$index = 1;
|
|
$scale = 0.1;
|
|
$descr = $oids[1]['wtWebGraphThermHygroPortName'];
|
|
$oid = '.1.3.6.1.4.1.5040.1.2.9.1.4.1.1.1';
|
|
$oid_name = 'wtWebGraphThermHygroBinaryTempValue';
|
|
$value = $oids[1]['wtWebGraphThermHygroBinaryTempValue'];
|
|
|
|
$limits = snmp_get_multi_oid($device, 'wtWebGraphThermHygroAlarmMin.1 wtWebGraphThermHygroAlarmMax.1', [], $mib);
|
|
$limits['limit_high'] = trim($limits[1]['wtWebGraphThermHygroAlarmMax'], ' "');
|
|
$limits['limit_low'] = trim($limits[1]['wtWebGraphThermHygroAlarmMin'], ' "');
|
|
$options = ['limit_high' => (is_numeric($limits['limit_high']) ? $limits['limit_high'] : NULL),
|
|
'limit_low' => (is_numeric($limits['limit_low']) ? $limits['limit_low'] : NULL)];
|
|
|
|
$options['rename_rrd'] = "wut-wtWebGraphThermHygroBinaryTempValue.1";
|
|
discover_sensor_ng($device, 'temperature', $mib, $oid_name, $oid, $index, $descr, $scale, $value, $options);
|
|
}
|
|
|
|
// Humidity/Volts
|
|
if (is_numeric($oids[2]['wtWebGraphThermHygroBinaryTempValue'])) {
|
|
// Binary coded options for sensor 2:
|
|
// Octet 1: unused
|
|
// Octet 2: unused
|
|
// Octet 3: unused
|
|
// Octet 4:
|
|
// Bit 0 : W&T Sensor rel. humidity (default)
|
|
// Bit 1 : Skalar 0-2.5V
|
|
// Bit 2 : Disconnect
|
|
// Bit 3-7: unused"
|
|
[, , , $octet] = explode(' ', $oids[2]['wtWebGraphThermHygroPortSensorSelect']);
|
|
|
|
$index = 2;
|
|
$scale = 0.1;
|
|
$descr = $oids[2]['wtWebGraphThermHygroPortName'];
|
|
$oid = '.1.3.6.1.4.1.5040.1.2.9.1.4.1.1.2';
|
|
$oid_name = 'wtWebGraphThermHygroBinaryTempValue';
|
|
$value = $oids[2]['wtWebGraphThermHygroBinaryTempValue'];
|
|
|
|
if ($octet == "01") {
|
|
// Humidity
|
|
$limits = snmp_get_multi_oid($device, 'wtWebGraphThermHygroAlarmRHMin.1 wtWebGraphThermHygroAlarmRHMax.1', [], $mib);
|
|
$limits['limit_high'] = trim($limits[1]['wtWebGraphThermHygroAlarmRHMax'], ' "');
|
|
$limits['limit_low'] = trim($limits[1]['wtWebGraphThermHygroAlarmRHMin'], ' "');
|
|
$options = ['limit_high' => (is_numeric($limits['limit_high']) ? $limits['limit_high'] : NULL),
|
|
'limit_low' => (is_numeric($limits['limit_low']) ? $limits['limit_low'] : NULL)];
|
|
|
|
$options['rename_rrd'] = "wut-wtWebGraphThermHygroBinaryTempValue.2";
|
|
discover_sensor_ng($device, 'humidity', $mib, $oid_name, $oid, $index, $descr, $scale, $value, $options);
|
|
} elseif ($octet == "02") {
|
|
// Voltage? Not tested
|
|
$options = [];
|
|
$options['rename_rrd'] = "wtWebGraphThermHygroBinaryTempValue.2";
|
|
discover_sensor_ng($device, 'voltage', $mib, $oid_name, $oid, $index, $descr, $scale, $value, $options);
|
|
}
|
|
}
|
|
}
|
|
|
|
unset($oids, $oid, $descr, $options, $limits, $value);
|
|
|
|
// EOF
|