-- Tripplite MIB
|
|
|
|
-- { iso org(3) dod(6) internet(1) private(4) enterprises(1) tripplite(850) trippUPS1(1) ups(1) }
|
|
|
|
TRIPPUPS1-MIB DEFINITIONS ::= BEGIN
|
|
|
|
-- Title : UPS MIB for Tripp Lite Uninterruptible Power Supplies
|
|
-- Date : Dec 9, 1993
|
|
-- By : Sean T McCartney
|
|
-- Note : Subagent #1, specific watchdog for Netmon port #1
|
|
-- Update : Apr 24, 1995
|
|
-- By : Dave Cole - Systems Enhancement Corporation
|
|
|
|
IMPORTS
|
|
enterprises, OBJECT-TYPE, NetworkAddress, IpAddress, Counter, Gauge, TimeTicks
|
|
FROM RFC1155-SMI
|
|
DisplayString
|
|
FROM RFC1213-MIB
|
|
TRAP-TYPE
|
|
FROM RFC-1215;
|
|
|
|
tripplite OBJECT IDENTIFIER ::= { enterprises 850 }
|
|
trippUPS1 OBJECT IDENTIFIER ::= { tripplite 1 }
|
|
ups OBJECT IDENTIFIER ::= { trippUPS1 1 }
|
|
|
|
upsIdent OBJECT IDENTIFIER ::= { ups 1 }
|
|
upsBattery OBJECT IDENTIFIER ::= { ups 2 }
|
|
upsInput OBJECT IDENTIFIER ::= { ups 3 }
|
|
upsOutput OBJECT IDENTIFIER ::= { ups 4 }
|
|
upsAlarm OBJECT IDENTIFIER ::= { ups 6 }
|
|
upsWellKnownAlarms OBJECT IDENTIFIER ::= { ups 7 }
|
|
upsTest OBJECT IDENTIFIER ::= { ups 8 }
|
|
upsControl OBJECT IDENTIFIER ::= { ups 9 }
|
|
upsConfig OBJECT IDENTIFIER ::= { ups 10 }
|
|
|
|
-- The Device Identification group.
|
|
-- All objects in this group are set at device initialization and remain static.
|
|
|
|
upsIdentManufacturer OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..31))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The name of the UPS manufacturer."
|
|
::= { upsIdent 1 }
|
|
|
|
upsIdentModel OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..63))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS Model designation."
|
|
::= { upsIdent 2 }
|
|
|
|
upsIdentUPSSoftwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..63))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS Firmware software version(s). This variable
|
|
may or may not have the same value as
|
|
upsIdentAgentSoftwareVersion in some implementations."
|
|
::= { upsIdent 3 }
|
|
|
|
upsIdentAgentSoftwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..63))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS agent software version. This variable may or
|
|
may not have the same value as
|
|
upsIdentUPSSoftwareVersion in some implementations."
|
|
::= { upsIdent 4 }
|
|
|
|
upsIdentName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..63))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A string identifying the UPS. This object should be
|
|
set by the administrator."
|
|
::= { upsIdent 5 }
|
|
|
|
upsIdentAttachedDevices OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..63))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A string identifying the devices attached to the
|
|
output(s) of the UPS. This object should be set by
|
|
the administrator."
|
|
::= { upsIdent 6 }
|
|
|
|
|
|
-- The Battery group.
|
|
-- Implementation of this group is mandatory for all systems.
|
|
|
|
upsBatteryStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown(1),
|
|
batteryNormal(2),
|
|
batteryLow(3),
|
|
batteryDepleted(4)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The indication of the capacity remaining in the UPS
|
|
system's batteries. A value of batteryNormal
|
|
indicates that the batteries are fully charged. A
|
|
value of batteryLow indicates that the remaining battery
|
|
run-time is less than or equal to
|
|
upsConfigMinutesRemaining. A value of batteryDepleted
|
|
indicates that the UPS will be unable to sustain the
|
|
present load when and if the utility power is lost."
|
|
::= { upsBattery 1 }
|
|
|
|
upsSecondsOnBattery OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"If the unit is on battery power, the elapsed time
|
|
since the UPS last switched to battery power, or the
|
|
time since the network management subsystem was last
|
|
restarted, whichever is less. Zero shall be returned
|
|
if the unit is not on battery power. UNITS - seconds"
|
|
::= { upsBattery 2 }
|
|
|
|
upsEstimatedMinutesRemaining OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An estimate of the time to battery charge depletion
|
|
under the present load conditions if the utility power
|
|
were to be lost and remain off. UNITS - minutes"
|
|
::= { upsBattery 3 }
|
|
|
|
upsBatteryChargeRemaining OBJECT-TYPE
|
|
SYNTAX INTEGER (0..100)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The estimate of the battery charge remaining expressed
|
|
as a percent of full charge."
|
|
::= { upsBattery 4 }
|
|
|
|
upsBatteryVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present battery voltage. UNITS 0.1 Volt DC."
|
|
::= { upsBattery 5 }
|
|
|
|
-------------------------------------------------------------------------------
|
|
-- Note : upsBatteryCurrent MIB variable removed by Dave Cole (SEC) on 4/24/95
|
|
-- To conform with older versions of this MIB, {upsBattery 6 } is reserved.
|
|
-------------------------------------------------------------------------------
|
|
|
|
upsBatteryTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The ambient temperature at or near the UPS Battery.
|
|
UNITS degrees Centigrade"
|
|
::= { upsBattery 7 }
|
|
|
|
-- the table group has one attribute of its own - the number of rows in the
|
|
-- contained table. It also contains the table of names.
|
|
|
|
-- The Input group.
|
|
-- Implementation of this group is mandatory for all systems.
|
|
|
|
upsInputFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present input frequency. UNITS 0.1 Hertz"
|
|
::= { upsInput 1 }
|
|
|
|
upsInputLineBads OBJECT-TYPE
|
|
SYNTAX Counter
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A count of the number of times the input entered an
|
|
out-of-tolerance condition as defined by the manufacturer."
|
|
::= { upsInput 2 }
|
|
|
|
upsInputNumLines OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of input lines utilized in this device.
|
|
This variable indicates the number of rows in the input table."
|
|
::= { upsInput 3 }
|
|
|
|
upsInputVolt OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present input voltage.
|
|
UNITS RMS Volts"
|
|
::= { upsInput 4 }
|
|
|
|
upsInputTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsInputEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of input table entries. The number of entries
|
|
is given by the value of upsInputNumLines."
|
|
::= { upsInput 5 }
|
|
|
|
upsInputEntry OBJECT-TYPE
|
|
SYNTAX UpsInputEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular input line."
|
|
INDEX { upsInputLineIndex }
|
|
::= { upsInputTable 1 }
|
|
|
|
UpsInputEntry ::=
|
|
SEQUENCE {
|
|
upsInputLineIndex INTEGER,
|
|
upsInputVoltage INTEGER
|
|
}
|
|
|
|
upsInputLineIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The input line identifier."
|
|
::= { upsInputEntry 1 }
|
|
|
|
upsInputVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present input voltage.
|
|
UNITS RMS Volts"
|
|
::= { upsInputEntry 2 }
|
|
|
|
-- The Output group.
|
|
-- Implementation of this group is mandatory for all systems.
|
|
|
|
upsOutputSource OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
other(1),
|
|
none(2),
|
|
normal(3),
|
|
bypass(4),
|
|
battery(5),
|
|
booster(6),
|
|
reducer(7)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present source of output power."
|
|
::= { upsOutput 1 }
|
|
|
|
upsOutputFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present output frequency.
|
|
UNITS 0.1 Hertz"
|
|
::= { upsOutput 2 }
|
|
|
|
upsOutputNumLines OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of output lines utilized in this device.
|
|
This variable indicates the number of rows in the output table."
|
|
::= { upsOutput 3 }
|
|
|
|
upsOutputPercLoad OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The percentage of true power capacity presently being used.
|
|
UNITS percent"
|
|
::= { upsOutput 4 }
|
|
|
|
upsOutputTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsOutputEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of output table entries. The number of
|
|
entries is given by the value of upsOutputNumLines."
|
|
::= { upsOutput 5 }
|
|
|
|
upsOutputEntry OBJECT-TYPE
|
|
SYNTAX UpsOutputEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular output line."
|
|
INDEX { upsOutputLineIndex }
|
|
::= { upsOutputTable 1 }
|
|
|
|
UpsOutputEntry ::= SEQUENCE {
|
|
upsOutputLineIndex INTEGER,
|
|
upsOutputVoltage INTEGER,
|
|
upsOutputCurrent INTEGER,
|
|
upsOutputPower INTEGER,
|
|
upsOutputPercentLoad INTEGER
|
|
}
|
|
|
|
upsOutputLineIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The output line identifier."
|
|
::= { upsOutputEntry 1 }
|
|
|
|
upsOutputVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present output voltage.
|
|
UNITS RMS Volts"
|
|
::= { upsOutputEntry 2 }
|
|
|
|
upsOutputCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present output mandatory.
|
|
UNITS 0.1 Amp"
|
|
::= { upsOutputEntry 3 }
|
|
|
|
upsOutputPower OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present output true power.
|
|
UNITS Watts"
|
|
::= { upsOutputEntry 4 }
|
|
|
|
upsOutputPercentLoad OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The percentage of true power capacity presently being used.
|
|
UNITS percent"
|
|
::= { upsOutputEntry 5 }
|
|
|
|
-- Alarm Group
|
|
|
|
upsAlarmsPresent OBJECT-TYPE
|
|
SYNTAX Gauge
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present number of active alarm conditions."
|
|
::= { upsAlarm 1 }
|
|
|
|
upsAlarmID OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
upsAlarmBatteryBad(1),
|
|
upsAlarmOnBattery(2),
|
|
upsAlarmLowBattery(3),
|
|
upsAlarmDepletedBattery(4),
|
|
upsAlarmTempBad(5),
|
|
upsAlarmOutputOverload(6),
|
|
upsAlarmOutputOffAsRequested(7),
|
|
upsAlarmOutputOff(8),
|
|
upsAlarmDiagnosticTestFailed(9),
|
|
upsAlarmCommunicationsLost(10),
|
|
upsAlarmShutdownPending(11),
|
|
upsAlarmShutdownImminent(12),
|
|
upsAlarmTestInProgress(13)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A unique identifier for an alarm condition. This
|
|
value must remain constant."
|
|
::= { upsAlarm 2 }
|
|
|
|
upsAlarmDESCR OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..31))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A reference to an alarm description object. The
|
|
object references should not be accessible, but rather
|
|
be used to provide a unique description of the alarm
|
|
condition."
|
|
::= { upsAlarm 3 }
|
|
|
|
upsAlarmTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsAlarmEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of alarm table entries. The table consists of
|
|
zero, one, or may rows at any moment, depending upon
|
|
the number of alarm conditions in effect. The table
|
|
is initially empty at agent startup. The agent
|
|
creates a row in the table each time a condition is
|
|
detected and deletes that row when that condition no
|
|
longer pertains. The agent creates the first row with
|
|
upsAlarmId equal to 1, and increments the value fo
|
|
upsAlarmId each time a new row is created, wrapping to
|
|
the first free value greater than or equal to 1 when
|
|
the maximum value of upsAlarmId would otherwise be
|
|
exceeded. Consequently, after multiple operations,
|
|
the table may become sparse, e.g., containing entries
|
|
for rows 95, 100, 101, and 203 and the entries are in
|
|
chronological order until upsAlarmId wraps.
|
|
|
|
Alarms are named by and OBJECT IDENTIFIER,
|
|
upsAlarmDescr, to allow a single table to reflect well
|
|
known alarms plus alarms defined by a particular
|
|
implementation, i.e., as documented in the private
|
|
enterprise MIB definition for the device. No two rows
|
|
will have the same value of upsAlarmDescr, since
|
|
alarms define conditions. In order to meet this
|
|
requirement, care should be take in the definition of
|
|
the number of active rows in the table at any given
|
|
time is reflected by the value fo upsAlarms."
|
|
::= { upsAlarm 4 }
|
|
|
|
upsAlarmEntry OBJECT-TYPE
|
|
SYNTAX UpsAlarmEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular alarm."
|
|
INDEX { upsAlarmId }
|
|
::= { upsAlarmTable 1 }
|
|
|
|
UpsAlarmEntry ::= SEQUENCE {
|
|
upsAlarmId INTEGER,
|
|
upsAlarmDescr DisplayString,
|
|
upsAlarmTime TimeTicks
|
|
}
|
|
|
|
upsAlarmId OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A unique identifier for an alarm condition. This
|
|
value must remain constant."
|
|
::= { upsAlarmEntry 1 }
|
|
|
|
upsAlarmDescr OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..31))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A reference to an alarm description object. The
|
|
object references should not be accessible, but rather
|
|
be used to provide a unique description of the alarm
|
|
condition."
|
|
::= { upsAlarmEntry 2 }
|
|
|
|
upsAlarmTime OBJECT-TYPE
|
|
SYNTAX TimeTicks
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The value of sysUpTime when the alarm condition was
|
|
detected. If the alarm condition was detected at the
|
|
time of agent startup and presumable existed before
|
|
agent startup, the value of upsAlarmTime shall equal
|
|
0."
|
|
::= { upsAlarmEntry 3 }
|
|
|
|
upsAlarmBatteryBad OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"One or more batteries have been determined to require
|
|
replacement."
|
|
::= { upsWellKnownAlarms 1 }
|
|
|
|
upsAlarmOnBattery OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS is drawing power from the batteries."
|
|
::= { upsWellKnownAlarms 2 }
|
|
|
|
upsAlarmLowBattery OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The remaining battery run-time is less than or equal
|
|
to upsConfigMinutesRemaining."
|
|
::= { upsWellKnownAlarms 3 }
|
|
|
|
upsAlarmDepletedBattery OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS will be unable to sustain the present load
|
|
when and if the utility power is lost."
|
|
::= { upsWellKnownAlarms 4 }
|
|
|
|
upsAlarmTempBad OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A temperature is out of tolerance."
|
|
::= { upsWellKnownAlarms 5 }
|
|
|
|
upsAlarmOutputOverload OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The output load exceeds the UPS output capacity."
|
|
::= { upsWellKnownAlarms 6 }
|
|
|
|
upsAlarmOutputOffAsRequested OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS has shutdown as commanded, i.e., the output is off."
|
|
::= { upsWellKnownAlarms 7 }
|
|
|
|
upsAlarmUpsOutputOff OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS is in the off state."
|
|
::= { upsWellKnownAlarms 8 }
|
|
|
|
upsAlarmDiagnosticTestFailed OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The result of the last diagnostic test indicates a
|
|
failure."
|
|
::= { upsWellKnownAlarms 9 }
|
|
|
|
upsAlarmCommunicationsLost OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A problem has been encountered in the
|
|
communications between the agent and the UPS."
|
|
::= { upsWellKnownAlarms 10 }
|
|
|
|
upsAlarmShutdownPending OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A upsShutdownAfterDelay countdown is underway."
|
|
::= { upsWellKnownAlarms 11 }
|
|
|
|
upsAlarmShutdownImminent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A upsShutdownAfterDelay countdown is underway."
|
|
::= { upsWellKnownAlarms 12 }
|
|
|
|
upsAlarmTestInProgress OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A upsShutdownAfterDelay countdown is underway."
|
|
::= { upsWellKnownAlarms 13 }
|
|
|
|
-- Test Group
|
|
|
|
upsTestId OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noTestsInitiated(1),
|
|
abortTestInProgress(2),
|
|
generalSystemsTest(3),
|
|
checkBatteryTest(4),
|
|
deepBatteryCalibration(5)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The test named by an OBJECT IDENTIFIER which
|
|
allows a standard mechanism for the initiation of
|
|
test, including the well known tests identified in
|
|
this document as well as those introduced by a
|
|
particular implementation, i.e., as
|
|
documented in the private enterprise MIB definition
|
|
for the device.
|
|
|
|
Setting this variable initiates the named test. Sets
|
|
to this variable require the presence of
|
|
upsTestSpinLock in the same SNMP message.
|
|
|
|
The set request will be rejected with an appropriate
|
|
error message if the requested test cannot be
|
|
performed, including attempts to start a test when
|
|
another test is already in progress. Tests in
|
|
progress may be aborted by setting this variable to
|
|
upsTestAbortTestInProgress.
|
|
|
|
Read operations return the value of the name of the
|
|
test in progress if a test is in progress or the name
|
|
of the last test performed if no test is in progress,
|
|
unless no test has bee run, in which case the well
|
|
known value upsTestNoTestsInitiated is returned."
|
|
::= { upsTest 1 }
|
|
|
|
|
|
upsTestResultsSummary OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
donePass(1),
|
|
doneWarning(2),
|
|
doneError(3),
|
|
aborted(4),
|
|
inProgress(5),
|
|
noTestsInitiated(6)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The results of the mandatory or last UPS diagnostics
|
|
test performed. The values for donePass(1),
|
|
doneWarning(2), and doneError(3) are self-documenting.
|
|
The value aborted(4) is returned for tests which are
|
|
aborted by setting the value of upsTestId to
|
|
upsTestAbortTestInProgress. Tests which have not yet
|
|
concluded are indicated by inProgress(5). The value
|
|
noTestsInitiated(4) indicates that no previous test
|
|
results are available, such as in the case when no
|
|
tests have been run since the last reinitialization of
|
|
the network management subsystem and the system has no
|
|
provision for non-volatile storage of test results."
|
|
::= { upsTest 2 }
|
|
|
|
--------------------------------------------------------------------------------------------------------------------------
|
|
-- Note : upsTestResultsDetail MIB variable removed by Dave Cole (SEC) on 4/24/95
|
|
-- To conform with older versions of this MIB, {upsTest 3 } is reserved.
|
|
--------------------------------------------------------------------------------------------------------------------------
|
|
|
|
--------------------------------------------------------------------------------------------------------------------------
|
|
-- Note : upsTestStartTime MIB variable removed by Dave Cole (SEC) on 4/24/95
|
|
-- To conform with older versions of this MIB, {upsTest 4 } is reserved.
|
|
--------------------------------------------------------------------------------------------------------------------------
|
|
|
|
-- Control Group
|
|
|
|
upsShutdownType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
output(1),
|
|
system(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this object will start the output after the
|
|
indicated number of seconds. Setting this object to 0
|
|
will cause the UPS to start the output immediately.
|
|
If the output is already on at the time the delay has
|
|
counted down, nothing will happen."
|
|
::= { upsControl 1 }
|
|
|
|
upsShutdownAfterDelay OBJECT-TYPE
|
|
SYNTAX INTEGER (-1..32767)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this object will shutdown (i.e., turn off)
|
|
either the UPS output or the UPS system (as determined
|
|
by the value of upsShhutdownType at the time of
|
|
shutdown) after the indicated number of seconds, or
|
|
less if the UPS batteries become depleted. Setting
|
|
this object to 0 will cause the shutdown to occur
|
|
immediately. Setting this object to -1 will abort the
|
|
countdown. If the system is already in the desired
|
|
state at the time the countdown reaches 0, then
|
|
nothing will happen. That is, there is no additional
|
|
action at that time if upsShutdownType = system and
|
|
the system is already off. Similarly, there is no
|
|
additional action at that time if upsShutdownType =
|
|
output and the output is already off. When read,
|
|
upsShutdownAfterDelay will return the number of
|
|
seconds remaining until shutdown, or -1 if no shutdown
|
|
countdown is in effect. On some systems, if the agent
|
|
is restarted while a shutdown countdown is in effect,
|
|
the countdown may be aborted. Sets to this object
|
|
override any upsShutdownAfterDelay already in effect.
|
|
UNITS seconds"
|
|
::= { upsControl 2 }
|
|
|
|
upsStartupAfterDelay OBJECT-TYPE
|
|
SYNTAX INTEGER (-1..32767)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this object will start the output after the
|
|
indicated number of seconds, includeing starting the
|
|
UPS, if necessary. Setting this object to 0 will
|
|
cause the start to occur immediately. Setting this
|
|
object to -1 will abort the countdown. If the output
|
|
is already on at the time the countdown reaches 0,
|
|
nothing will happen. Sets to this object
|
|
override the effect of any upsStartupAfterDelay
|
|
countdown or upsRebootDuration countdown in progress.
|
|
When read, upsStartupAfterDelay will return the number
|
|
of seconds until start, or -1 if no startup
|
|
countdown is in effect. If the countdown expires
|
|
during a utility failure, the startup shall depend
|
|
upon the value of upsAutoRestart at that time. On
|
|
some systems, if the agent is restarted while a
|
|
startup countdown is in effect, the countdown is
|
|
aborted.
|
|
UNITS seconds"
|
|
::= { upsControl 3 }
|
|
|
|
upsRebootDuration OBJECT-TYPE
|
|
SYNTAX INTEGER (-1..100)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this object will immediately shutdown (i.e.,
|
|
turn off) either the UPS output or the UPS system (as
|
|
determined by the value of the upsShutdownType at the time
|
|
of shutdown) for a period equal to the indicated
|
|
number of seconds, after which time the output will be
|
|
started, including starting the UPS, if necessary. If
|
|
the number of seconds required to perform the request
|
|
is greater than the requested duration, then the
|
|
requested shutdown and startup cycle shall be
|
|
performed in the minimum time possible, but in no case
|
|
shall this require more than the requested duration
|
|
plus 60 seconds. When read, upsRebootDuration shall
|
|
return the number of seconds remaining in the
|
|
countdown, or -1 if no countdown is in progress. If
|
|
the startup should occur during a utility failure, the
|
|
startup shall depend on the value of upsAutoRestart
|
|
at that time.
|
|
UNITS seconds"
|
|
::= { upsControl 4 }
|
|
|
|
upsAutoRestart OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this object to 'on' will cause the UPS system
|
|
to restart after a shutdown if/when utility power is present."
|
|
::= { upsControl 5 }
|
|
|
|
-- upsConfig group
|
|
|
|
--------------------------------------------------------------------------------------------------------------------------------
|
|
-- Note : upsConfigInputVoltage MIB variable removed by Dave Cole (SEC) on 4/24/95
|
|
-- To conform with older versions of this MIB, {upsConfig 1 } is reserved.
|
|
--------------------------------------------------------------------------------------------------------------------------------
|
|
|
|
--------------------------------------------------------------------------------------------------------------------------------
|
|
-- Note : upsInputFreq MIB variable removed by Dave Cole (SEC) on 4/24/95
|
|
-- To conform with older versions of this MIB, {upsConfig 2 } is reserved.
|
|
--------------------------------------------------------------------------------------------------------------------------------
|
|
|
|
--------------------------------------------------------------------------------------------------------------------------------
|
|
-- Note : upsConfigOutputVoltage MIB variable removed by Dave Cole (SEC) on 4/24/95
|
|
-- To conform with older versions of this MIB, {upsConfig 3 } is reserved.
|
|
--------------------------------------------------------------------------------------------------------------------------------
|
|
|
|
--------------------------------------------------------------------------------------------------------------------------------
|
|
-- Note : upsConfigOutputFreq MIB variable removed by Dave Cole (SEC) on 4/24/95
|
|
-- To conform with older versions of this MIB, {upsConfig 4 } is reserved.
|
|
--------------------------------------------------------------------------------------------------------------------------------
|
|
|
|
--------------------------------------------------------------------------------------------------------------------------------
|
|
-- Note : upsConfigOutputVA MIB variable removed by Dave Cole (SEC) on 4/24/95
|
|
-- To conform with older versions of this MIB, {upsConfig 5 } is reserved.
|
|
--------------------------------------------------------------------------------------------------------------------------------
|
|
|
|
--------------------------------------------------------------------------------------------------------------------------------
|
|
-- Note : upsConfigOutputPower MIB variable removed by Dave Cole (SEC) on 4/24/95
|
|
-- To conform with older versions of this MIB, {upsConfig 6 } is reserved.
|
|
--------------------------------------------------------------------------------------------------------------------------------
|
|
|
|
--------------------------------------------------------------------------------------------------------------------------------
|
|
-- Note : upsConfigLowBattTime MIB variable removed by Dave Cole (SEC) on 4/24/95
|
|
-- To conform with older versions of this MIB, {upsConfig 7 } is reserved.
|
|
--------------------------------------------------------------------------------------------------------------------------------
|
|
|
|
--------------------------------------------------------------------------------------------------------------------------------
|
|
-- Note : upsConfigAudibleStatus MIB variable removed by Dave Cole (SEC) on 4/24/95
|
|
-- To conform with older versions of this MIB, {upsConfig 8 } is reserved.
|
|
--------------------------------------------------------------------------------------------------------------------------------
|
|
|
|
--------------------------------------------------------------------------------------------------------------------------------
|
|
-- Note : upsConfigLowVoltageTransferPoint MIB variable removed by Dave Cole (SEC) on
|
|
-- 4/24/95. To conform with older versions of this MIB, {upsConfig 9 } is reserved.
|
|
--------------------------------------------------------------------------------------------------------------------------------
|
|
|
|
--------------------------------------------------------------------------------------------------------------------------------
|
|
-- Note : upsConfigHighVoltageTransferPoint MIB variable removed by Dave Cole (SEC) on
|
|
-- 4/24/95. To conform with older versions of this MIB, {upsConfig 10 } is reserved.
|
|
--------------------------------------------------------------------------------------------------------------------------------
|
|
|
|
upsConfigInputVoltageHigh OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"If the value of the input voltage (in Volts) exceeds this value, a
|
|
utilityVoltageHigh trap will be triggered."
|
|
::= { upsConfig 11 }
|
|
|
|
upsConfigInputVoltageLow OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"If the value of the input voltage (in Volts) falls below this value, a
|
|
utilityVoltageLow trap will be triggered."
|
|
::= { upsConfig 12 }
|
|
|
|
upsConfigOutputPercLoadHigh OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"If the value of the output percent load exceeds this value, a upsOverload trap
|
|
will be triggered."
|
|
::= { upsConfig 13 }
|
|
|
|
upsConfigBatteryPercLow OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"If the value of the battery percent capacity falls below this value, a lowBattery
|
|
trap will be triggered."
|
|
::= { upsConfig 14 }
|
|
|
|
upsConfigBatteryTemperatureHigh OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"If the value of the battery temperature exceeds this value, a
|
|
batteryTemperatureHigh trap will be triggered."
|
|
::= { upsConfig 15 }
|
|
|
|
-- Traps
|
|
|
|
---------------------------------------------------------------------------------------------------------------------------
|
|
-- Note : upsOnBattery trap modified by Dave Cole (SEC) on 4/24/95
|
|
-- To conform with older versions of this MIB, trap 1 is reserved.
|
|
---------------------------------------------------------------------------------------------------------------------------
|
|
|
|
---------------------------------------------------------------------------------------------------------------------------
|
|
-- Note : upsTestCompleted trap removed by Dave Cole (SEC) on 4/24/95
|
|
-- To conform with older versions of this MIB, trap 2 is reserved.
|
|
---------------------------------------------------------------------------------------------------------------------------
|
|
|
|
---------------------------------------------------------------------------------------------------------------------------
|
|
-- Note : upsAlarmEntryAdded trap removed by Dave Cole (SEC) on 4/24/95
|
|
-- To conform with older versions of this MIB, trap 3 is reserved.
|
|
---------------------------------------------------------------------------------------------------------------------------
|
|
|
|
---------------------------------------------------------------------------------------------------------------------------
|
|
-- Note : upsAlarmEntryDeleted trap removed by Dave Cole (SEC) on 4/24/95
|
|
-- To conform with older versions of this MIB, trap 4 is reserved.
|
|
---------------------------------------------------------------------------------------------------------------------------
|
|
|
|
upsOnBattery TRAP-TYPE
|
|
ENTERPRISE tripplite
|
|
VARIABLES { upsIdentAttachedDevices, upsEstimatedMinutesRemaining }
|
|
DESCRIPTION
|
|
"The UPS is on battery."
|
|
::= 5
|
|
|
|
powerRestored TRAP-TYPE
|
|
ENTERPRISE tripplite
|
|
DESCRIPTION
|
|
"Utility power has been restored."
|
|
::= 6
|
|
|
|
lowBattery TRAP-TYPE
|
|
ENTERPRISE tripplite
|
|
DESCRIPTION
|
|
"The UPS batteries are low and will soon be exhausted."
|
|
::= 7
|
|
|
|
returnFromLowBattery TRAP-TYPE
|
|
ENTERPRISE tripplite
|
|
DESCRIPTION
|
|
"The UPS has returned from a low battery condition."
|
|
::= 8
|
|
|
|
communicationEstablished TRAP-TYPE
|
|
ENTERPRISE tripplite
|
|
DESCRIPTION
|
|
"Communication with the UPS has been established. This trap will be sent
|
|
each time there is a transition from a power off condition to a power on condition."
|
|
::= 9
|
|
|
|
communicationLost TRAP-TYPE
|
|
ENTERPRISE tripplite
|
|
DESCRIPTION
|
|
"Communication with the UPS has been lost."
|
|
::= 10
|
|
|
|
upsOverload TRAP-TYPE
|
|
ENTERPRISE tripplite
|
|
DESCRIPTION
|
|
"The UPS has sensed a load greater than the value of the
|
|
upsConfigOutputPercLoadHigh MIB variable."
|
|
::= 11
|
|
|
|
upsDiagnosticsFailed TRAP-TYPE
|
|
ENTERPRISE tripplite
|
|
DESCRIPTION
|
|
"The UPS failed its self-test."
|
|
::= 12
|
|
|
|
upsDiagnosticsPassed TRAP-TYPE
|
|
ENTERPRISE tripplite
|
|
DESCRIPTION
|
|
"The UPS passed its internal self-test."
|
|
::= 13
|
|
|
|
utilityVoltageHigh TRAP-TYPE
|
|
ENTERPRISE tripplite
|
|
DESCRIPTION
|
|
"The UPS input voltage greater than or equal to the value of
|
|
the upsConfigInputVoltageHigh MIB variable."
|
|
::= 14
|
|
|
|
utilityVoltageLow TRAP-TYPE
|
|
ENTERPRISE tripplite
|
|
DESCRIPTION
|
|
"The UPS input voltage is less than or equal to the value of
|
|
the upsConfigInputVoltageLow MIB variable."
|
|
::= 15
|
|
|
|
utilityVoltageReturnToNormal TRAP-TYPE
|
|
ENTERPRISE tripplite
|
|
DESCRIPTION
|
|
"The UPS has returned from a utility voltage high or low condition."
|
|
::= 16
|
|
|
|
batteryTemperatureHigh TRAP-TYPE
|
|
ENTERPRISE tripplite
|
|
DESCRIPTION
|
|
"The UPS battery temperature has exceeded the value of the
|
|
upsConfigBatteryTemperatureHigh MIB variable."
|
|
::= 17
|
|
|
|
shutdownPending TRAP-TYPE
|
|
ENTERPRISE tripplite
|
|
DESCRIPTION
|
|
"A UPS shutdown countdown is underway."
|
|
::= 18
|
|
|
|
upsSleeping TRAP-TYPE
|
|
ENTERPRISE tripplite
|
|
DESCRIPTION
|
|
"The output of the UPS has been turned off."
|
|
::= 19
|
|
|
|
upsWokeup TRAP-TYPE
|
|
ENTERPRISE tripplite
|
|
DESCRIPTION
|
|
"The output of the UPS has been turned on."
|
|
::= 20
|
|
|
|
upsBatteryNeedsReplacement TRAP-TYPE
|
|
ENTERPRISE tripplite
|
|
DESCRIPTION
|
|
"The UPS battery needs to be replaced."
|
|
::= 21
|
|
END
|