IBM-PDU-MIB DEFINITIONS ::= BEGIN
|
|
|
|
|
|
IMPORTS
|
|
MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE FROM SNMPv2-SMI
|
|
enterprises, Integer32, Unsigned32 FROM SNMPv2-SMI
|
|
MODULE-COMPLIANCE, OBJECT-GROUP, NOTIFICATION-GROUP FROM SNMPv2-CONF
|
|
TEXTUAL-CONVENTION, DisplayString FROM SNMPv2-TC;
|
|
|
|
|
|
ibmPowerDistributionUnitMIB MODULE-IDENTITY
|
|
LAST-UPDATED "201205310000Z"
|
|
ORGANIZATION "International Business Machines"
|
|
CONTACT-INFO "International Business Machines
|
|
1 New Orchard Road
|
|
Armonk, New York 10504-1722
|
|
United States
|
|
E-mail: ews@us.ibm.com"
|
|
DESCRIPTION "The MIB module representing a power disribution
|
|
unit supported by a single SNMP agent"
|
|
REVISION "201205310000Z"
|
|
DESCRIPTION "1. Additions of fields ibmPduReboot, ibmPduOutletGlobalDelayTimer,
|
|
and ibmPduOutletIndividualDelayTimer for IBM/Netezza.
|
|
|
|
Licensed Materials - Property of IBM
|
|
Copyright IBM Corp. 2012"
|
|
|
|
REVISION "201201180000Z"
|
|
DESCRIPTION "The IBM Power Distribution Unit MIB definitions for
|
|
enabling power monitoring and management of an IBM
|
|
Power Unit.
|
|
|
|
Licensed Materials - Property of IBM
|
|
Copyright IBM Corp. 2009"
|
|
::= { ibmProd 223 }
|
|
|
|
ibm OBJECT IDENTIFIER ::= { enterprises 2 }
|
|
ibmProd OBJECT IDENTIFIER ::= { ibm 6 }
|
|
|
|
ibmPduMetadata OBJECT IDENTIFIER ::= { ibmPowerDistributionUnitMIB 7 }
|
|
ibmPduDevice OBJECT IDENTIFIER ::= { ibmPowerDistributionUnitMIB 8 }
|
|
ibmPduOutlets OBJECT IDENTIFIER ::= { ibmPduDevice 2 }
|
|
ibmPduPower OBJECT IDENTIFIER ::= { ibmPduDevice 3 }
|
|
ibmPduEnvironment OBJECT IDENTIFIER ::= { ibmPduDevice 4 }
|
|
ibmPduExternalMonitors OBJECT IDENTIFIER ::= { ibmPowerDistributionUnitMIB 9 }
|
|
ibmPduTraps OBJECT IDENTIFIER ::= { ibmPowerDistributionUnitMIB 0 }
|
|
ibmPduTrapData OBJECT IDENTIFIER ::= { ibmPduTraps 1 }
|
|
ibmPduTrapDataObjects OBJECT IDENTIFIER ::= { ibmPduTrapData 1 }
|
|
ibmPduConformance OBJECT IDENTIFIER ::= { ibmPowerDistributionUnitMIB 2 }
|
|
ibmPduCompliances OBJECT IDENTIFIER ::= { ibmPduConformance 1 }
|
|
ibmPduGroups OBJECT IDENTIFIER ::= { ibmPduConformance 2 }
|
|
ibmPduLocation OBJECT IDENTIFIER ::= { ibmPduMetadata 1 }
|
|
ibmPduImage OBJECT IDENTIFIER ::= { ibmPduMetadata 2 }
|
|
|
|
|
|
-- ////////////////////////////////////////////////////////
|
|
-- //////////////// TEXTUAL-CONVENTIONs ///////////////////
|
|
-- ////////////////////////////////////////////////////////
|
|
|
|
IbmPduPowerBuf ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION "Buffer that contains the power records. This buffer
|
|
contains ibmPduBufferEntries (default 120) average
|
|
power samples, in Watts, at 4 bytes each sample, in
|
|
little-endian format."
|
|
SYNTAX OCTET STRING(SIZE(480))
|
|
|
|
|
|
IbmPduEnvBuf ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION "Buffer that contains temperature or humidity records.
|
|
This buffer contains ibmPduBufferEntries (default 120)
|
|
average point-in-time samples at 2 bytes each in
|
|
little-endian format."
|
|
SYNTAX OCTET STRING(SIZE(240))
|
|
|
|
|
|
IbmPduMilliAmps ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION "Used for floating point amperage values since SNMP
|
|
does not support floating point numbers."
|
|
SYNTAX Unsigned32
|
|
|
|
IbmPduMilliVolt ::= TEXTUAL-CONVENTION
|
|
STATUS voltage
|
|
DESCRIPTION "Used for floating point voltage values since SNMP
|
|
does not support floating point numbers."
|
|
SYNTAX Unsigned32
|
|
|
|
|
|
-- ////////////////////////////////////////////////////////
|
|
-- ///////////////////// ibmDevice ATTRs /////////////////////
|
|
-- ////////////////////////////////////////////////////////
|
|
|
|
ibmPduBufferTagValue OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Used for the update interval of power and environmental
|
|
registers. The buffer tag is incremented every sample
|
|
of data that is captured in the buffer."
|
|
::= { ibmPowerDistributionUnitMIB 3 }
|
|
|
|
|
|
ibmPduSampleRate OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Sample rate in seconds for each entry in the sampled buffer.
|
|
The default is 30."
|
|
::= { ibmPowerDistributionUnitMIB 4 }
|
|
|
|
|
|
ibmPduBufferVersion OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..7))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Version of the snapshot buffer."
|
|
::= { ibmPowerDistributionUnitMIB 5 }
|
|
|
|
|
|
ibmPduBufferEntries OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Number of entries contained in each data buffer.
|
|
The default is 120."
|
|
::= { ibmPowerDistributionUnitMIB 6 }
|
|
|
|
|
|
ibmPduSoftwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE (0..63))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Version of the software loaded on the PDU."
|
|
::= { ibmPduMetadata 3 }
|
|
|
|
|
|
ibmPduMachineType OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE (0..4))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Machine type of the PDU."
|
|
::= { ibmPduMetadata 4 }
|
|
|
|
|
|
ibmPduModelNumber OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE (0..15))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Model number of the PDU."
|
|
::= { ibmPduMetadata 5 }
|
|
|
|
ibmPduPartNumber OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE (0..10))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Part number of the PDU."
|
|
::= { ibmPduMetadata 6 }
|
|
|
|
|
|
ibmPduName OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE (0..63))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Name of the device."
|
|
::= { ibmPduMetadata 7 }
|
|
|
|
|
|
ibmPduManufacturer OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..63))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The name of manufacturer."
|
|
::= { ibmPduMetadata 8 }
|
|
|
|
|
|
ibmPduSerialNumber OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..6))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Serial number of the device."
|
|
::= { ibmPduMetadata 9 }
|
|
|
|
|
|
ibmPduDescription OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..255))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Description of the device."
|
|
::= { ibmPduMetadata 10 }
|
|
|
|
|
|
ibmPduUrl OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..127))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "URL of the web interface to the ibmDevice if available."
|
|
::= { ibmPduMetadata 11 }
|
|
|
|
ibmPduReboot OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Set 1 to reboot PDU."
|
|
::= { ibmPduMetadata 12 }
|
|
|
|
ibmPduDateTime OBJECT-TYPE
|
|
SYNTAX DateAndTime
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Set or get PDU Date and Time."
|
|
::= { ibmPduMetadata 13 }
|
|
|
|
-- ////////////////////////////////////////////////////////
|
|
-- ////////////////////// ibmLocation ////////////////////////
|
|
-- ////////////////////////////////////////////////////////
|
|
ibmPduTelephoneNumber OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..31))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Telephone number of building and site
|
|
where the device is located."
|
|
::= { ibmPduLocation 1 }
|
|
|
|
|
|
ibmPduCountryRegion OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..31))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Country or region where the device
|
|
is located."
|
|
::= { ibmPduLocation 2 }
|
|
|
|
|
|
ibmPduStreetAddress OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..31))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Street address of building where the
|
|
device is located."
|
|
::= { ibmPduLocation 3 }
|
|
|
|
|
|
ibmPduCity OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..31))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "City where the device is located."
|
|
::= { ibmPduLocation 4 }
|
|
|
|
|
|
ibmPduStateProvince OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..15))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "State or province where the device
|
|
is located."
|
|
::= { ibmPduLocation 5 }
|
|
|
|
|
|
ibmPduPostalCode OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..15))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Postal code where the device is
|
|
located."
|
|
::= { ibmPduLocation 6 }
|
|
|
|
|
|
ibmPduBuilding OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..15))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Building name where the device is
|
|
located."
|
|
::= { ibmPduLocation 7 }
|
|
|
|
|
|
ibmPduFloor OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..7))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Floor number or designation where
|
|
the device is located."
|
|
::= { ibmPduLocation 8 }
|
|
|
|
|
|
ibmPduRoomNumber OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..7))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Room number where the device is
|
|
located."
|
|
::= { ibmPduLocation 9 }
|
|
|
|
|
|
ibmPduRow OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..7))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Row number where the device is
|
|
located."
|
|
::= { ibmPduLocation 10 }
|
|
|
|
|
|
ibmPduAisle OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..7))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Aisle number where the device is
|
|
located."
|
|
::= { ibmPduLocation 11 }
|
|
|
|
|
|
ibmPduDisplaceHeight OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Displaced height in Centimeters."
|
|
::= { ibmPduLocation 12 }
|
|
|
|
|
|
ibmPduAltitude OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Altitude in Meters."
|
|
::= { ibmPduLocation 13 }
|
|
|
|
|
|
ibmPduOtherInfo OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..63))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Additional ibmLocation information."
|
|
::= { ibmPduLocation 14 }
|
|
|
|
|
|
-- ////////////////////////////////////////////////////////
|
|
-- ///////////////////// IMAGE ATTRS //////////////////////
|
|
-- ////////////////////////////////////////////////////////
|
|
ibmPduLogo OBJECT-TYPE
|
|
SYNTAX OCTET STRING(SIZE(65535))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Device logo or image."
|
|
::= { ibmPduImage 1 }
|
|
|
|
|
|
ibmPduDeviceFront OBJECT-TYPE
|
|
SYNTAX OCTET STRING(SIZE(65535))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Image of the front of the device."
|
|
::= { ibmPduImage 2 }
|
|
|
|
|
|
ibmPduDeviceRear OBJECT-TYPE
|
|
SYNTAX OCTET STRING(SIZE(65535))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Image of the back of the device."
|
|
::= { ibmPduImage 3 }
|
|
|
|
|
|
-- ////////////////////////////////////////////////////////
|
|
-- ///////////////////// ibmDevice POWER /////////////////////
|
|
-- ////////////////////////////////////////////////////////
|
|
|
|
ibmPduPhaseCount OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
single(1),
|
|
three(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The number of input power phases for the PDU."
|
|
::= { ibmPduPower 1 }
|
|
|
|
|
|
ibmPduPhaseTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF IbmPduPowerPhaseStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "A list of power phase entries. The number of
|
|
entries is given by phaseNumber."
|
|
::= { ibmPduPower 2 }
|
|
|
|
|
|
ibmPduPhaseTableEntry OBJECT-TYPE
|
|
SYNTAX IbmPduPowerPhaseStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "A value contained within the PowerPhaseStruct."
|
|
INDEX { ibmPduPhaseNumber }
|
|
::= { ibmPduPhaseTable 1 }
|
|
|
|
|
|
|
|
IbmPduPowerPhaseStruct ::= SEQUENCE { ibmPduPhaseNumber Unsigned32,
|
|
ibmPduPhaseAvgPower IbmPduPowerBuf,
|
|
ibmPduPhaseMaxPower IbmPduPowerBuf,
|
|
ibmPduPhaseLastPowerReading Unsigned32 }
|
|
|
|
|
|
ibmPduPhaseNumber OBJECT-TYPE
|
|
SYNTAX Unsigned32(1..3)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "The power phase number."
|
|
::= { ibmPduPhaseTableEntry 1 }
|
|
|
|
|
|
ibmPduPhaseAvgPower OBJECT-TYPE
|
|
SYNTAX IbmPduPowerBuf
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Buffer containing average power values. Refer to
|
|
description of IbmPduPowerBuf for information about
|
|
buffer format."
|
|
::= { ibmPduPhaseTableEntry 2 }
|
|
|
|
|
|
ibmPduPhaseMaxPower OBJECT-TYPE
|
|
SYNTAX IbmPduPowerBuf
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Buffer containing max power values. Refer to
|
|
description of IbmPduPowerBuf for information about
|
|
buffer format."
|
|
::= { ibmPduPhaseTableEntry 3 }
|
|
|
|
|
|
ibmPduPhaseLastPowerReading OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The value of the most recent power reading for this
|
|
phase, in Watts."
|
|
::= { ibmPduPhaseTableEntry 4 }
|
|
|
|
|
|
-- ////////////////////////////////////////////////////////
|
|
-- ///////////////////// ENVIRONMENT //////////////////////
|
|
-- ////////////////////////////////////////////////////////
|
|
ibmPduThermalBuffer OBJECT-TYPE
|
|
SYNTAX IbmPduEnvBuf
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Buffer that contains the thermal records. Refer to
|
|
description of IbmPduEnvBuf for information about
|
|
buffer format."
|
|
::= { ibmPduEnvironment 1 }
|
|
|
|
|
|
ibmPduHumidityBuffer OBJECT-TYPE
|
|
SYNTAX IbmPduEnvBuf
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Buffer that contains the humdity records. Refer to
|
|
description of IbmPduEnvBuf for information about
|
|
buffer format."
|
|
::= { ibmPduEnvironment 2 }
|
|
|
|
|
|
ibmPduThermalThresholdWarning OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The value of the warning threshold for
|
|
the given temperature returned in Celsius."
|
|
::= { ibmPduEnvironment 3 }
|
|
|
|
|
|
ibmPduThermalThresholdCritical OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The value of the critical threshold for
|
|
the given temperature returned in Celsius."
|
|
::= { ibmPduEnvironment 4 }
|
|
|
|
|
|
ibmPduHumidityThresholdWarning OBJECT-TYPE
|
|
SYNTAX Unsigned32(0..100)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The value of the warning threshold for
|
|
the given humidity returned as a percent."
|
|
::= { ibmPduEnvironment 5 }
|
|
|
|
|
|
ibmPduHumidityThresholdCritical OBJECT-TYPE
|
|
SYNTAX Unsigned32(0..100)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The value of the critical threshold for
|
|
the given humidity returned as a percent."
|
|
::= { ibmPduEnvironment 6 }
|
|
|
|
|
|
ibmPduThermalLastReading OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The value of the most recent temperature reading for
|
|
the internal temperature sensor, in degrees Celsius."
|
|
::= { ibmPduEnvironment 7 }
|
|
|
|
ibmPduHumidityLastReading OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The value of the most recent humidity reading for
|
|
the internal humidity sensor, as a percentage."
|
|
::= { ibmPduEnvironment 8 }
|
|
|
|
-- ////////////////////////////////////////////////////////
|
|
-- //////////////////////// OUTLETS ///////////////////////
|
|
-- ////////////////////////////////////////////////////////
|
|
|
|
ibmPduOutletCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The number of outlets (regardless of their current state) present on this PDU."
|
|
::= { ibmPduOutlets 1 }
|
|
|
|
|
|
ibmPduOutletTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF IbmPduOutletStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "A list of outlet entries. The number of entries is given by the value of
|
|
outletCount."
|
|
::= { ibmPduOutlets 2 }
|
|
|
|
ibmPduOutletGlobalDelayTimer OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Global delay timer for all outlets. Range: 0 sec ~ 3600 sec. Default value:0 sec. To combine with Individual Delay timer to control outlet state/behavior as rack power on/restore"
|
|
::= { ibmPduOutlets 3 }
|
|
|
|
|
|
|
|
ibmPduOutletEntry OBJECT-TYPE
|
|
SYNTAX IbmPduOutletStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "A value contained within the OutletStruct."
|
|
INDEX { ibmPduOutletNumber }
|
|
::= { ibmPduOutletTable 1 }
|
|
|
|
|
|
IbmPduOutletStruct ::= SEQUENCE { ibmPduOutletNumber Integer32,
|
|
ibmPduOutletName DisplayString,
|
|
ibmPduOutletType INTEGER,
|
|
ibmPduOutletDescription DisplayString,
|
|
ibmPduOutletAvgPower IbmPduPowerBuf,
|
|
ibmPduOutletMaxPower IbmPduPowerBuf,
|
|
ibmPduOutletPowerFactor Unsigned32,
|
|
ibmPduOutletVoltage IbmPduMilliVolt,
|
|
ibmPduOutletCurrent IbmPduMilliAmps,
|
|
ibmPduOutletMaxCapacity IbmPduMilliAmps,
|
|
ibmPduOutletCurrentThresholdWarning IbmPduMilliAmps,
|
|
ibmPduOutletCurrentThresholdCritical IbmPduMilliAmps,
|
|
ibmPduOutletState INTEGER,
|
|
ibmPduOutletGroupIndex Unsigned32,
|
|
ibmPduOutletLastPowerReading Unsigned32,
|
|
ibmPduOutletIndividualDelayTimer Unsigned32}
|
|
|
|
|
|
ibmPduOutletNumber OBJECT-TYPE
|
|
SYNTAX Integer32(0..255)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "The unique index of the given outlet."
|
|
::= { ibmPduOutletEntry 1 }
|
|
|
|
|
|
ibmPduOutletName OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE (0..64))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Text describing the name or designation of the given outlet."
|
|
::= { ibmPduOutletEntry 2 }
|
|
|
|
|
|
ibmPduOutletType OBJECT-TYPE
|
|
SYNTAX INTEGER { c13(0),
|
|
c19(1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Type of the outlet."
|
|
::= { ibmPduOutletEntry 3 }
|
|
|
|
|
|
ibmPduOutletDescription OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE (0..63))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Description of the outlet."
|
|
::= { ibmPduOutletEntry 4 }
|
|
|
|
|
|
ibmPduOutletAvgPower OBJECT-TYPE
|
|
SYNTAX IbmPduPowerBuf
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Buffer containing average power values. Refer to
|
|
description of IbmPduPowerBuf for information about
|
|
buffer format."
|
|
::= { ibmPduOutletEntry 5 }
|
|
|
|
|
|
ibmPduOutletMaxPower OBJECT-TYPE
|
|
SYNTAX IbmPduPowerBuf
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Buffer containing max power values. Refer to
|
|
description of IbmPduPowerBuf for information about
|
|
buffer format."
|
|
::= { ibmPduOutletEntry 6 }
|
|
|
|
ibmPduOutletPowerFactor OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The value of the Power Factor of the given outlet."
|
|
::= { ibmPduOutletEntry 7 }
|
|
|
|
|
|
ibmPduOutletVoltage OBJECT-TYPE
|
|
SYNTAX IbmPduMilliVolt
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The value of the Voltage of the given outlet
|
|
returned in MilliVolt."
|
|
::= { ibmPduOutletEntry 8 }
|
|
|
|
|
|
ibmPduOutletCurrent OBJECT-TYPE
|
|
SYNTAX IbmPduMilliAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The value of the Current of the given outlet
|
|
returned in Milliamps."
|
|
::= { ibmPduOutletEntry 9 }
|
|
|
|
|
|
ibmPduOutletMaxCapacity OBJECT-TYPE
|
|
SYNTAX IbmPduMilliAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The maximum capacity of the current
|
|
outlet in Milliamps."
|
|
::= { ibmPduOutletEntry 10 }
|
|
|
|
|
|
ibmPduOutletCurrentThresholdWarning OBJECT-TYPE
|
|
SYNTAX IbmPduMilliAmps
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The value of the warning threshold
|
|
for the given outlet returned in Milliamps."
|
|
::= { ibmPduOutletEntry 11 }
|
|
|
|
|
|
ibmPduOutletCurrentThresholdCritical OBJECT-TYPE
|
|
SYNTAX IbmPduMilliAmps
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The value of the critical threshold
|
|
for the given outlet returned in Milliamps."
|
|
::= { ibmPduOutletEntry 12 }
|
|
|
|
|
|
ibmPduOutletState OBJECT-TYPE
|
|
SYNTAX INTEGER { error(-1),
|
|
off(0),
|
|
on(1),
|
|
cycling(2),
|
|
delaySwitch10(3),
|
|
delaySwitch30(4),
|
|
delaySwitch60(5)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The value of the operational state for the given outlet.
|
|
This can also be used to set (change) the outlet state."
|
|
::= { ibmPduOutletEntry 13 }
|
|
|
|
|
|
ibmPduOutletGroupIndex OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The index of the outlet group in which the outlet resides.
|
|
If there are no outlet groups present, the default is 0."
|
|
::= { ibmPduOutletEntry 14 }
|
|
|
|
ibmPduOutletLastPowerReading OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The value of the most recent power reading for this
|
|
outlet, in Watts."
|
|
::= { ibmPduOutletEntry 15 }
|
|
|
|
ibmPduOutletIndividualDelayTimer OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The delay timer for each outlet as AC power restored. Range: 0 sec ~ 3600 sec. Default Value: 0 sec. To combine with Global Delay timer to control outlet state/behavior as rack power or or restore"
|
|
::= { ibmPduOutletEntry 16 }
|
|
|
|
-- ////////////////////////////////////////////////////////
|
|
-- ////////////////// EXTERNAL MONITORS ///////////////////
|
|
-- ////////////////////////////////////////////////////////
|
|
|
|
ibmPduExtMonitorCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The number of external monitors (regardless of
|
|
their current state) present on this PDU."
|
|
::= { ibmPduExternalMonitors 1 }
|
|
|
|
|
|
ibmPduExtMonitorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF IbmPduExternalMonitorStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "A list of external monitors. The number of
|
|
entries is given by the value of externalMonitorCount."
|
|
::= { ibmPduExternalMonitors 2 }
|
|
|
|
|
|
ibmPduExtMonitorEntry OBJECT-TYPE
|
|
SYNTAX IbmPduExternalMonitorStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "A value contained within the ExternalMonitorStruct."
|
|
INDEX { ibmPduExtMonitorNumber }
|
|
::= { ibmPduExtMonitorTable 1 }
|
|
|
|
|
|
IbmPduExternalMonitorStruct ::= SEQUENCE { ibmPduExtMonitorNumber Integer32,
|
|
ibmPduExtThermalBuffer IbmPduEnvBuf,
|
|
ibmPduExtHumidityBuffer IbmPduEnvBuf,
|
|
ibmPduExtThermalThresholdWarning Unsigned32,
|
|
ibmPduExtThermalThresholdCritical Unsigned32,
|
|
ibmPduExtHumidityThresholdWarning Unsigned32,
|
|
ibmPduExtHumidityThresholdCritical Unsigned32,
|
|
ibmPduExtThermalLastReading Unsigned32,
|
|
ibmPduExtHumidityLastReading Unsigned32
|
|
}
|
|
|
|
|
|
ibmPduExtMonitorNumber OBJECT-TYPE
|
|
SYNTAX Integer32(0..255)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "The unique index of the given external monitor."
|
|
::= { ibmPduExtMonitorEntry 1 }
|
|
|
|
|
|
ibmPduExtThermalBuffer OBJECT-TYPE
|
|
SYNTAX IbmPduEnvBuf
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Buffer that contains the thermal records. Refer to
|
|
description of IbmPduEnvBuf for information about
|
|
buffer format."
|
|
::= { ibmPduExtMonitorEntry 2 }
|
|
|
|
|
|
ibmPduExtHumidityBuffer OBJECT-TYPE
|
|
SYNTAX IbmPduEnvBuf
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Buffer that contains the humdity records. Refer to
|
|
description of IbmPduEnvBuf for information about
|
|
buffer format."
|
|
::= { ibmPduExtMonitorEntry 3 }
|
|
|
|
|
|
ibmPduExtThermalThresholdWarning OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The value of the warning threshold for
|
|
the given temperature returned in Celsius."
|
|
::= { ibmPduExtMonitorEntry 4 }
|
|
|
|
|
|
ibmPduExtThermalThresholdCritical OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The value of the critical threshold for
|
|
the given temperature returned in Celsius."
|
|
::= { ibmPduExtMonitorEntry 5 }
|
|
|
|
|
|
ibmPduExtHumidityThresholdWarning OBJECT-TYPE
|
|
SYNTAX Unsigned32(0..100)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The value of the warning threshold for
|
|
the given humidity returned as a percent."
|
|
::= { ibmPduExtMonitorEntry 6 }
|
|
|
|
|
|
ibmPduExtHumidityThresholdCritical OBJECT-TYPE
|
|
SYNTAX Unsigned32(0..100)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The value of the critical threshold for
|
|
the given humidity returned as a percent."
|
|
::= { ibmPduExtMonitorEntry 7 }
|
|
|
|
|
|
ibmPduExtThermalLastReading OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The value of the most recent temperature reading for
|
|
the external temperature sensor, in degrees Celsius.
|
|
If no external temperature sensor is connected, a
|
|
value of -1 should be returned."
|
|
::= { ibmPduExtMonitorEntry 8 }
|
|
|
|
ibmPduExtHumidityLastReading OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The value of the most recent humidity reading for
|
|
the external humidity sensor, as a percentage. If no
|
|
external humidity sensor is connected, a value of -1
|
|
should be returned."
|
|
::= { ibmPduExtMonitorEntry 9 }
|
|
|
|
-- ////////////////////////////////////////////////////////
|
|
-- ////////////////////// Traps ///////////////////////////
|
|
-- ////////////////////////////////////////////////////////
|
|
ibmPduObjectIndex OBJECT-TYPE
|
|
SYNTAX Unsigned32(0..255)
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION "Index in the table of an outlet or external meter"
|
|
::= { ibmPduTrapDataObjects 1 }
|
|
|
|
|
|
ibmPduObjectType OBJECT-TYPE
|
|
SYNTAX INTEGER { pdu(0),
|
|
outlet(1),
|
|
extMeter(2)
|
|
}
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION "The type of object represented in the trap."
|
|
::= { ibmPduTrapDataObjects 2 }
|
|
|
|
|
|
ibmPduObjectID OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION "Unique ID or name of the object represented in the trap."
|
|
::= { ibmPduTrapDataObjects 3 }
|
|
|
|
|
|
ibmPduSeverity OBJECT-TYPE
|
|
SYNTAX INTEGER { informational(0),
|
|
warning(1),
|
|
critical(2)
|
|
}
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION "Severity of the trap."
|
|
::= { ibmPduTrapDataObjects 4 }
|
|
|
|
|
|
ibmPduTrapDescription OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION "Textual description of the trap."
|
|
::= { ibmPduTrapDataObjects 5 }
|
|
|
|
|
|
ibmPduState OBJECT-TYPE
|
|
SYNTAX INTEGER { powerOff(0),
|
|
powerOn(1),
|
|
reboot(2),
|
|
delayedOn(3),
|
|
delayedOff(4)
|
|
}
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION "State change for management of an outlet."
|
|
::= { ibmPduTrapDataObjects 6 }
|
|
|
|
ibmPduVoltageWarning OBJECT-TYPE
|
|
SYNTAX INTEGER { voltageNormal(0),
|
|
voltageOutOfRange(1)
|
|
}
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION "Voltage Warning."
|
|
::= { ibmPduTrapDataObjects 7 }
|
|
|
|
|
|
ibmPduCurrentThreshold NOTIFICATION-TYPE
|
|
OBJECTS { ibmPduObjectIndex,
|
|
ibmPduObjectType,
|
|
ibmPduObjectID,
|
|
ibmPduSeverity,
|
|
ibmPduTrapDescription
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "Threshold for Current events set by the user."
|
|
::= { ibmPduTraps 1 }
|
|
|
|
|
|
ibmPduThermalThreshold NOTIFICATION-TYPE
|
|
OBJECTS { ibmPduObjectIndex,
|
|
ibmPduObjectType,
|
|
ibmPduObjectID,
|
|
ibmPduSeverity,
|
|
ibmPduTrapDescription
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "Threshold for thermal events set by the user."
|
|
::= { ibmPduTraps 2 }
|
|
|
|
|
|
ibmPduHumidityThreshold NOTIFICATION-TYPE
|
|
OBJECTS { ibmPduObjectIndex,
|
|
ibmPduObjectType,
|
|
ibmPduObjectID,
|
|
ibmPduSeverity,
|
|
ibmPduTrapDescription
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "Threshold for humidity events set by the user."
|
|
::= { ibmPduTraps 3 }
|
|
|
|
|
|
ibmPduOutletStateChange NOTIFICATION-TYPE
|
|
OBJECTS { ibmPduObjectIndex,
|
|
ibmPduObjectID,
|
|
ibmPduState,
|
|
ibmPduTrapDescription
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "Outlet state has changed."
|
|
::= { ibmPduTraps 4 }
|
|
|
|
|
|
ibmPduFirmwareChanged NOTIFICATION-TYPE
|
|
OBJECTS { ibmPduObjectID,
|
|
ibmPduTrapDescription
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU firmware has been updated."
|
|
::= { ibmPduTraps 5 }
|
|
|
|
|
|
ibmPduDeviceStateChange NOTIFICATION-TYPE
|
|
OBJECTS { ibmPduObjectID,
|
|
ibmPduState,
|
|
ibmPduTrapDescription
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "Device state has changed."
|
|
::= { ibmPduTraps 6 }
|
|
|
|
ibmPduACVoltageWarning NOTIFICATION-TYPE
|
|
OBJECTS { ibmPduObjectID,
|
|
ibmPduVoltageWarning
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "AC Voltage +/- 15% Normal."
|
|
::= { ibmPduTraps 7 }
|
|
|
|
-- ////////////////////////////////////////////////////////
|
|
-- /////////////////// Compliances ////////////////////////
|
|
-- ////////////////////////////////////////////////////////
|
|
|
|
ibmPduDeviceGroup OBJECT-GROUP
|
|
OBJECTS { ibmPduBufferTagValue,
|
|
ibmPduSampleRate,
|
|
ibmPduBufferVersion,
|
|
ibmPduBufferEntries,
|
|
ibmPduSoftwareVersion,
|
|
ibmPduMachineType,
|
|
ibmPduModelNumber,
|
|
ibmPduPartNumber,
|
|
ibmPduName,
|
|
ibmPduManufacturer,
|
|
ibmPduSerialNumber,
|
|
ibmPduDescription,
|
|
ibmPduUrl,
|
|
ibmPduReboot,
|
|
ibmPduPhaseCount,
|
|
ibmPduPhaseAvgPower,
|
|
ibmPduPhaseMaxPower,
|
|
ibmPduPhaseLastPowerReading,
|
|
ibmPduThermalBuffer,
|
|
ibmPduHumidityBuffer,
|
|
ibmPduThermalThresholdWarning,
|
|
ibmPduThermalThresholdCritical,
|
|
ibmPduHumidityThresholdWarning,
|
|
ibmPduHumidityThresholdCritical,
|
|
ibmPduThermalLastReading,
|
|
ibmPduHumidityLastReading
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "A group of objects containing base information about
|
|
the overall PDU."
|
|
::= { ibmPduGroups 1 }
|
|
|
|
|
|
ibmPduImageGroup OBJECT-GROUP
|
|
OBJECTS { ibmPduLogo,
|
|
ibmPduDeviceFront,
|
|
ibmPduDeviceRear
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "A group of objects containing image information
|
|
of the PDU."
|
|
::= { ibmPduGroups 2 }
|
|
|
|
|
|
ibmPduLocationGroup OBJECT-GROUP
|
|
OBJECTS { ibmPduTelephoneNumber,
|
|
ibmPduCountryRegion,
|
|
ibmPduStreetAddress,
|
|
ibmPduCity,
|
|
ibmPduStateProvince,
|
|
ibmPduPostalCode,
|
|
ibmPduBuilding,
|
|
ibmPduFloor,
|
|
ibmPduRoomNumber,
|
|
ibmPduRow,
|
|
ibmPduAisle,
|
|
ibmPduDisplaceHeight,
|
|
ibmPduAltitude,
|
|
ibmPduOtherInfo
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "A group of objects containing ibmLocation information
|
|
of the PDU."
|
|
::= { ibmPduGroups 3 }
|
|
|
|
|
|
ibmPduOutletGroup OBJECT-GROUP
|
|
OBJECTS { ibmPduOutletCount,
|
|
ibmPduOutletName,
|
|
ibmPduOutletType,
|
|
ibmPduOutletDescription,
|
|
ibmPduOutletAvgPower,
|
|
ibmPduOutletMaxPower,
|
|
ibmPduOutletCurrent,
|
|
ibmPduOutletMaxCapacity,
|
|
ibmPduOutletCurrentThresholdWarning,
|
|
ibmPduOutletCurrentThresholdCritical,
|
|
ibmPduOutletState,
|
|
ibmPduOutletGroupIndex,
|
|
ibmPduOutletLastPowerReading,
|
|
ibmPduOutletIndividualDelayTimer,
|
|
ibmPduOutletGlobalDelayTimer
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "A group of objects containing information about
|
|
the outlets in a PDU."
|
|
::= { ibmPduGroups 4 }
|
|
|
|
|
|
ibmPduExtMonitorGroup OBJECT-GROUP
|
|
OBJECTS { ibmPduExtMonitorCount,
|
|
ibmPduExtThermalBuffer,
|
|
ibmPduExtHumidityBuffer,
|
|
ibmPduExtThermalThresholdWarning,
|
|
ibmPduExtThermalThresholdCritical,
|
|
ibmPduExtHumidityThresholdWarning,
|
|
ibmPduOutletCurrentThresholdCritical,
|
|
ibmPduExtHumidityThresholdCritical,
|
|
ibmPduExtThermalLastReading,
|
|
ibmPduExtHumidityLastReading
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "A group of objects containing information about
|
|
external thermal and humidity monitors connected
|
|
to the PDU."
|
|
::= { ibmPduGroups 5 }
|
|
|
|
|
|
ibmPduTrapDataGroup OBJECT-GROUP
|
|
OBJECTS { ibmPduObjectIndex,
|
|
ibmPduObjectType,
|
|
ibmPduObjectID,
|
|
ibmPduSeverity,
|
|
ibmPduState,
|
|
ibmPduTrapDescription,
|
|
ibmPduVoltageWarning
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "A group of object containing data for traps."
|
|
::= { ibmPduGroups 6 }
|
|
|
|
|
|
ibmPduTrapGroup NOTIFICATION-GROUP
|
|
NOTIFICATIONS { ibmPduCurrentThreshold,
|
|
ibmPduThermalThreshold,
|
|
ibmPduHumidityThreshold,
|
|
ibmPduOutletStateChange,
|
|
ibmPduFirmwareChanged,
|
|
ibmPduDeviceStateChange,
|
|
ibmPduACVoltageWarning
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "A group of objects containing information about
|
|
traps of the PDU, its outlets, and external meters."
|
|
::= { ibmPduGroups 7 }
|
|
|
|
|
|
ibmPduCompliance MODULE-COMPLIANCE
|
|
STATUS current
|
|
DESCRIPTION "The requirements for conformance to the PDU-MIB."
|
|
MODULE -- this module
|
|
|
|
MANDATORY-GROUPS {
|
|
ibmPduDeviceGroup,
|
|
ibmPduLocationGroup,
|
|
ibmPduImageGroup,
|
|
ibmPduOutletGroup,
|
|
ibmPduExtMonitorGroup,
|
|
ibmPduTrapDataGroup,
|
|
ibmPduTrapGroup
|
|
}
|
|
::= { ibmPduCompliances 8 }
|
|
|
|
END |