2697 lines
98 KiB
Plaintext
2697 lines
98 KiB
Plaintext
VALERE-DC-POWER-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE,
|
|
OBJECT-IDENTITY, Counter32, Gauge32, Integer32,
|
|
enterprises
|
|
FROM SNMPv2-SMI
|
|
DisplayString, TimeStamp, TimeInterval, TestAndIncr,
|
|
AutonomousType, TEXTUAL-CONVENTION
|
|
FROM SNMPv2-TC
|
|
MODULE-COMPLIANCE, OBJECT-GROUP
|
|
FROM SNMPv2-CONF
|
|
sysUpTime FROM RFC1213-MIB;
|
|
--
|
|
-- date and time in UTC format YYMMDDHHmmZ
|
|
--
|
|
vpwrDcPowerMgt MODULE-IDENTITY
|
|
LAST-UPDATED "0512020000Z"
|
|
ORGANIZATION "Valere Power Inc."
|
|
CONTACT-INFO
|
|
"Contact: Valere Customer Support
|
|
Postal: 661 N. Plano Road, Suite 300
|
|
Richardson, TX-75081
|
|
Web: http://www.valerepower.com
|
|
email: support@valerepower.com
|
|
Phone 866-240-6614
|
|
"
|
|
DESCRIPTION
|
|
|
|
" MIB Version 0.8
|
|
Need description here.
|
|
History
|
|
Add table to retrieve module inventory info
|
|
MIB Version 0.7
|
|
Dec 1, 05
|
|
Fixed HP Openview error
|
|
Fixed warnings generated by MG-SOFT
|
|
Add table to retrieve rectifier inventory info
|
|
MIB Version 0.6
|
|
Feb 10, 2004 Added additional traps.
|
|
Defined Ringers and other modules.
|
|
Feb 08, 2003 Changed vpwrTrapDestinationTable to vpwrTrapTable
|
|
Corrected entry for vpwrTrapTable to be VpwrTrapTableEntry
|
|
This fixes errors generated by MG-SOFT mib compiler.
|
|
Oct 30, 2002 initial release - version 0.4
|
|
"
|
|
|
|
::= {enterprises 13858}
|
|
|
|
PositiveInteger ::= TEXTUAL-CONVENTION
|
|
DISPLAY-HINT "d"
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This data type is a non-zero and non-negative value."
|
|
SYNTAX INTEGER (1..2147483647)
|
|
|
|
NonNegativeInteger ::= TEXTUAL-CONVENTION
|
|
DISPLAY-HINT "d"
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This data type is a non-negative value."
|
|
SYNTAX INTEGER (0..2147483647)
|
|
|
|
|
|
|
|
vpwrDcPowerProducts OBJECT IDENTIFIER ::= { vpwrDcPowerMgt 1 }
|
|
vpwrDcPowerSystem OBJECT IDENTIFIER ::= { vpwrDcPowerMgt 2 }
|
|
vpwrDcPowerRectifier OBJECT IDENTIFIER ::= { vpwrDcPowerMgt 3 }
|
|
vpwrDcPowerLvd OBJECT IDENTIFIER ::= { vpwrDcPowerMgt 4 }
|
|
vpwrDcPowerTest OBJECT IDENTIFIER ::= { vpwrDcPowerMgt 5 }
|
|
vpwrDcPowerModuleIdent OBJECT IDENTIFIER ::= { vpwrDcPowerMgt 6 }
|
|
vpwrDcPowerBatteryGroup OBJECT IDENTIFIER ::= { vpwrDcPowerMgt 7 }
|
|
vpwrDcPowerAlarmGroup OBJECT IDENTIFIER ::= { vpwrDcPowerMgt 8 }
|
|
vpwrDcPowerSnmpConfig OBJECT IDENTIFIER ::= { vpwrDcPowerMgt 9 }
|
|
vpwrDcPowerTraps OBJECT IDENTIFIER ::= { vpwrDcPowerMgt 10 }
|
|
vpwrDcPowerTrapsMsgString OBJECT IDENTIFIER ::= { vpwrDcPowerMgt 11 }
|
|
|
|
vpwrDcPowerRinger OBJECT IDENTIFIER ::= { vpwrDcPowerMgt 12 }
|
|
vpwrDcPowerDcDcConverter OBJECT IDENTIFIER ::= { vpwrDcPowerMgt 13 }
|
|
vpwrDcPowerDcAcInverter OBJECT IDENTIFIER ::= { vpwrDcPowerMgt 14 }
|
|
vpwrDcPowerBayController OBJECT IDENTIFIER ::= { vpwrDcPowerMgt 15 }
|
|
vpwrDcPowerIoModule OBJECT IDENTIFIER ::= { vpwrDcPowerMgt 16 }
|
|
vpwrDcPowerDist OBJECT IDENTIFIER ::= { vpwrDcPowerMgt 17 }
|
|
vpwrDcPowerTrio OBJECT IDENTIFIER ::= { vpwrDcPowerMgt 18 }
|
|
|
|
-- vpwrDcPowerTraps OBJECT IDENTIFIER ::= { vpwrDcPowerTrapsRoot 0 }
|
|
|
|
vpwrSystemIdentGroup OBJECT IDENTIFIER ::= { vpwrDcPowerSystem 1 }
|
|
vpwrSystemConfigGroup OBJECT IDENTIFIER ::= { vpwrDcPowerSystem 2 }
|
|
vpwrSystemParameterGroup OBJECT IDENTIFIER ::= { vpwrDcPowerSystem 3 }
|
|
vpwrSystemPanelIdentGroup OBJECT IDENTIFIER ::= { vpwrDcPowerSystem 4 }
|
|
vpwrSystemBayctrlIdentGroup OBJECT IDENTIFIER ::= { vpwrDcPowerSystem 5 }
|
|
|
|
vpwrLvdConfigGroup OBJECT IDENTIFIER ::= { vpwrDcPowerLvd 1 }
|
|
vpwrLvdAlarmGroup OBJECT IDENTIFIER ::= { vpwrDcPowerLvd 2 }
|
|
vpwrLvdTestGroup OBJECT IDENTIFIER ::= { vpwrDcPowerLvd 3 }
|
|
|
|
vpwrRectifierConfigGroup OBJECT IDENTIFIER ::= { vpwrDcPowerRectifier 1 }
|
|
vpwrRectifierAlarmGroup OBJECT IDENTIFIER ::= { vpwrDcPowerRectifier 2 }
|
|
vpwrRectifierTestGroup OBJECT IDENTIFIER ::= { vpwrDcPowerRectifier 3 }
|
|
|
|
vpwrBatteryTempGroup OBJECT IDENTIFIER ::= { vpwrDcPowerBatteryGroup 1 }
|
|
vpwrBatteryCurrentGroup OBJECT IDENTIFIER ::= { vpwrDcPowerBatteryGroup 2 }
|
|
vpwrBatteryBoostGroup OBJECT IDENTIFIER ::= { vpwrDcPowerBatteryGroup 3 }
|
|
vpwrBatteryDischargeTestGroup OBJECT IDENTIFIER ::= { vpwrDcPowerBatteryGroup 4 }
|
|
|
|
|
|
vpwrRingerConfigGroup OBJECT IDENTIFIER ::= { vpwrDcPowerRinger 1 }
|
|
vpwrRingerAlarmGroup OBJECT IDENTIFIER ::= { vpwrDcPowerRinger 2 }
|
|
vpwrRingerTestGroup OBJECT IDENTIFIER ::= { vpwrDcPowerRinger 3 }
|
|
|
|
vpwrDcDcConverterConfigGroup OBJECT IDENTIFIER ::= { vpwrDcPowerDcDcConverter 1 }
|
|
vpwrDcDcConverterAlarmGroup OBJECT IDENTIFIER ::= { vpwrDcPowerDcDcConverter 2 }
|
|
vpwrDcDcConverterTestGroup OBJECT IDENTIFIER ::= { vpwrDcPowerDcDcConverter 3 }
|
|
|
|
|
|
vpwrDcAcInverterConfigGroup OBJECT IDENTIFIER ::= { vpwrDcPowerDcAcInverter 1 }
|
|
vpwrDcAcInverterAlarmGroup OBJECT IDENTIFIER ::= { vpwrDcPowerDcAcInverter 2 }
|
|
vpwrDcAcInverterTestGroup OBJECT IDENTIFIER ::= { vpwrDcPowerDcAcInverter 3 }
|
|
|
|
-- vpwrAcLineModuleConfigGroup OBJECT IDENTIFIER ::= { vpwrDcPowerAcLineModule 1 }
|
|
-- vpwrAcLineModuleAlarmGroup OBJECT IDENTIFIER ::= { vpwrDcPowerAcLineModule 2 }
|
|
-- vpwrAcLineModuleTestGroup OBJECT IDENTIFIER ::= { vpwrDcPowerAcLineModule 3 }
|
|
|
|
vpwrIoModuleConfigGroup OBJECT IDENTIFIER ::= { vpwrDcPowerIoModule 1 }
|
|
vpwrIoModuleAlarmGroup OBJECT IDENTIFIER ::= { vpwrDcPowerIoModule 2 }
|
|
vpwrIoModuleTestGroup OBJECT IDENTIFIER ::= { vpwrDcPowerIoModule 3 }
|
|
|
|
--
|
|
-- The Identification group.
|
|
--
|
|
|
|
|
|
vpwrIdentManufacturer OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..31))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The name of the DC Power manufacturer."
|
|
::= { vpwrSystemIdentGroup 1 }
|
|
|
|
vpwrIdentModel OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..15))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The DC Power Model designation."
|
|
::= { vpwrSystemIdentGroup 2 }
|
|
|
|
vpwrIdentControllerVersion OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..15))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The hardware/firmware version(s). This variable
|
|
may or may not have the same value as
|
|
vpwrIdentAgentSoftwareVersion."
|
|
::= { vpwrSystemIdentGroup 3 }
|
|
|
|
vpwrIdentAgentSoftwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..15))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The SNMP agent software version. This variable may or
|
|
may not have the same value as
|
|
vpwrIdentControllerFirmwareVersion."
|
|
::= { vpwrSystemIdentGroup 4 }
|
|
|
|
vpwrIdentName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..31))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A string identifying the system. This object should be
|
|
set by the administrator."
|
|
::= { vpwrSystemIdentGroup 5 }
|
|
|
|
--
|
|
-- The System Identifier group.
|
|
-- All objects in this group are read-only. It describes
|
|
-- various modules (rectifiers, converters, ringers, LVDs, etc.) that make up
|
|
-- the power system and are inserted into a shelf(.1) or panel(.2)
|
|
--
|
|
vpwrSystemIdentTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VpwrSystemIdentEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This table describes shelves and modules
|
|
that make up the sysetm.
|
|
"
|
|
::= { vpwrSystemIdentGroup 6 }
|
|
|
|
--
|
|
-- The System Identifier Entry. Defines the sequence for module tables.
|
|
--
|
|
vpwrSystemIdentEntry OBJECT-TYPE
|
|
SYNTAX VpwrSystemIdentEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular alarm."
|
|
INDEX { vpwrBayIndex, vpwrModuleIndex }
|
|
::= { vpwrSystemIdentTable 1 }
|
|
|
|
|
|
VpwrSystemIdentEntry ::= SEQUENCE {
|
|
vpwrBayIndex PositiveInteger,
|
|
vpwrModuleIndex PositiveInteger,
|
|
vpwrModuleOID OBJECT IDENTIFIER ,
|
|
vpwrModuleCurrent INTEGER ,
|
|
vpwrModuleOperStatus INTEGER ,
|
|
vpwrModuleCapacity INTEGER
|
|
}
|
|
|
|
--
|
|
-- The System Shelf Identifier group.
|
|
--
|
|
-- vpwrShelfIdentEntry OBJECT-TYPE
|
|
-- SYNTAX VpwrSystemIdentEntry
|
|
-- MAX-ACCESS not-accessible
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "An entry containing information applicable to a
|
|
-- particular module making up the system."
|
|
-- INDEX { vpwrBayIndex vpwrModuleIndex }
|
|
-- ::= { vpwrSystemIdentTable 1 }
|
|
--
|
|
vpwrBayIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Identifies Bay number that this module belongs to.
|
|
The possible values are 1 through 16 limited by vpwrSystemShelfCapacity."
|
|
::= { vpwrSystemIdentEntry 1 }
|
|
|
|
vpwrModuleIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This object identifies the module by its position in the shelf.
|
|
Module numbering is left to right starting with module 1. So, the
|
|
module in the first slot has an index of 1, the next module is 2 and
|
|
so on."
|
|
::= { vpwrSystemIdentEntry 2 }
|
|
|
|
vpwrModuleOID OBJECT-TYPE
|
|
SYNTAX OBJECT IDENTIFIER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"It indicates the type of the module by specifiying its OID"
|
|
::= { vpwrSystemIdentEntry 3}
|
|
|
|
vpwrModuleCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The meaning of this object depends upon the module type
|
|
which is indicated by vpwrModuleOID as follows
|
|
- Current for Rectifier module.
|
|
- Not Applicable for LVD module
|
|
"
|
|
::= { vpwrSystemIdentEntry 4}
|
|
|
|
vpwrModuleOperStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
moduleStatusOK(0),
|
|
moduleStatusAlarm(1),
|
|
moduleStatusDisabled(2),
|
|
moduleStatusRingerAOn(3),
|
|
moduleStatusRingerBOn(4),
|
|
moduleStatusUnknown(5)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This object indicates current over all status of the module."
|
|
::= { vpwrSystemIdentEntry 5}
|
|
|
|
vpwrModuleCapacity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The meaning of this object depends upon the module type
|
|
which is indicated by vpwrModuleOID as follows
|
|
- Capacity for Rectifier module.
|
|
- Not Applicable for LVD module
|
|
"
|
|
::= { vpwrSystemIdentEntry 6}
|
|
|
|
--
|
|
-- The System Panel Identifier group.
|
|
--
|
|
vpwrPanelIdentTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VpwrPanelIdentEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This table describes shelves and modules
|
|
that make up the panels.
|
|
"
|
|
::= { vpwrSystemPanelIdentGroup 1 }
|
|
|
|
|
|
vpwrPanelIdentEntry OBJECT-TYPE
|
|
SYNTAX VpwrPanelIdentEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular panel making up the system."
|
|
INDEX { vpwrPanelBayIndex, vpwrPanelModuleIndex }
|
|
::= { vpwrPanelIdentTable 1 }
|
|
|
|
VpwrPanelIdentEntry ::= SEQUENCE {
|
|
vpwrPanelBayIndex PositiveInteger,
|
|
vpwrPanelModuleIndex PositiveInteger,
|
|
vpwrPanelModuleOID OBJECT IDENTIFIER ,
|
|
vpwrPanelModuleCurrent INTEGER ,
|
|
vpwrPanelModuleOperStatus INTEGER ,
|
|
vpwrPanelModuleCapacity INTEGER
|
|
}
|
|
|
|
vpwrPanelBayIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Identifies bay number that this module belongs to.
|
|
The possible values are 1 through 16, starting from the top."
|
|
::= { vpwrPanelIdentEntry 1 }
|
|
|
|
vpwrPanelModuleIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This object identifies the module within the panel.
|
|
The orentation of modules within the panel is mappable."
|
|
::= { vpwrPanelIdentEntry 2 }
|
|
|
|
vpwrPanelModuleOID OBJECT-TYPE
|
|
SYNTAX OBJECT IDENTIFIER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"It indicates the type of the module by specifiying its OID"
|
|
::= { vpwrPanelIdentEntry 3}
|
|
|
|
vpwrPanelModuleCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is the Current of the first shunt of the module."
|
|
::= { vpwrPanelIdentEntry 4}
|
|
|
|
vpwrPanelModuleOperStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
moduleStatusOK(0),
|
|
moduleStatusAlarm(1),
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This object indicates over all status of the module."
|
|
::= { vpwrPanelIdentEntry 5}
|
|
|
|
vpwrPanelModuleCapacity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is the overall Capacity of the module and is for reference only."
|
|
::= { vpwrPanelIdentEntry 6}
|
|
|
|
--
|
|
-- The System Bayctrl Identifier group.
|
|
--
|
|
vpwrBayctrlIdentTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VpwrBayctrlIdentEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This table describes bay controllers
|
|
that make up the system.
|
|
"
|
|
::= { vpwrSystemBayctrlIdentGroup 1 }
|
|
|
|
|
|
vpwrBayctrlIdentEntry OBJECT-TYPE
|
|
SYNTAX VpwrBayctrlIdentEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular bay controller making up the system."
|
|
INDEX { vpwrBayctrlIndex}
|
|
::= { vpwrBayctrlIdentTable 1 }
|
|
|
|
VpwrBayctrlIdentEntry ::= SEQUENCE {
|
|
vpwrBayctrlIndex PositiveInteger,
|
|
vpwrBayctrlOID OBJECT IDENTIFIER ,
|
|
vpwrBayctrlCurrent INTEGER ,
|
|
vpwrBayctrlOperStatus INTEGER ,
|
|
vpwrBayctrlCapacity INTEGER
|
|
}
|
|
|
|
vpwrBayctrlIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Identifies bay number that this module belongs to.
|
|
The possible values are 0 through 15, starting from the top."
|
|
::= { vpwrBayctrlIdentEntry 1 }
|
|
|
|
vpwrBayctrlOID OBJECT-TYPE
|
|
SYNTAX OBJECT IDENTIFIER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"It indicates the type of the module by specifiying its OID"
|
|
::= { vpwrBayctrlIdentEntry 2}
|
|
|
|
vpwrBayctrlCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is the total output Current of the bay"
|
|
::= { vpwrBayctrlIdentEntry 3}
|
|
|
|
vpwrBayctrlOperStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
moduleStatusOK(0),
|
|
moduleStatusAlarm(1),
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This object indicates over all status of the bay"
|
|
::= { vpwrBayctrlIdentEntry 4}
|
|
|
|
vpwrBayctrlCapacity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is the overall Capacity of the bay and is for reference only."
|
|
::= { vpwrBayctrlIdentEntry 5}
|
|
|
|
|
|
-- --
|
|
--The System Configuration Parameters group.
|
|
-- --
|
|
|
|
vpwrSystemTempCompensation OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
tempCompDisabled(0),
|
|
tempCompEnabled(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter enables/disables temperature compensation.
|
|
"
|
|
REFERENCE " "
|
|
|
|
::= {vpwrSystemConfigGroup 1}
|
|
|
|
vpwrSystemTempCompStartTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER (25 .. 60)
|
|
UNITS "degrees Centigrade"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" The temperature at which temperature compensation becomes
|
|
active.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrSystemConfigGroup 2}
|
|
|
|
vpwrSystemTempCompStopVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" When temperature compensation is active, vpwrSystemTempCompStopVoltage is the
|
|
limit to which float voltage will be reduced.
|
|
For example, to set this voltage to 51.75 volts enter a value of 5175.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrSystemConfigGroup 3}
|
|
|
|
vpwrSystemTempCompensationSlope OBJECT-TYPE
|
|
SYNTAX INTEGER (0 .. 250)
|
|
UNITS " milli-Volts per degrees Centigrade"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" The rate at which float voltage is changed, within the specified limits,
|
|
when temperature compensation is active.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrSystemConfigGroup 4}
|
|
|
|
vpwrSystemThermalSenseType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
external(0),
|
|
internal(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter selects the temperature sensing point for temperature
|
|
compensation (in)activation.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrSystemConfigGroup 5}
|
|
|
|
vpwrSystemHVAlarmSetpoint OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System High voltage alarm voltage setting.
|
|
"
|
|
::= { vpwrSystemConfigGroup 6}
|
|
vpwrSystemBDAlarmSetpoint OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System Battery Discharge voltage setting."
|
|
::= { vpwrSystemConfigGroup 7}
|
|
|
|
--
|
|
-- Threshold for Internal Temperature Trap
|
|
--
|
|
vpwrSystemInternalTempLThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "degrees Centigrade"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature value at which temperature compensation inactive (clear)
|
|
trap would be sent if temperature compensation was active when this
|
|
value is reached.
|
|
"
|
|
::= { vpwrSystemConfigGroup 8}
|
|
|
|
vpwrSystemInternalTempUThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "degrees Centigrade"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature value at which temperature compensation active (set) trap
|
|
would be sent.
|
|
"
|
|
::= { vpwrSystemConfigGroup 9}
|
|
|
|
--
|
|
-- The System Current Operating Parameters group.
|
|
--
|
|
|
|
|
|
vpwrSystemShelfCapacity OBJECT-TYPE
|
|
SYNTAX INTEGER (1 .. 16)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" It describes the maximum number of shelves that can/are controlled
|
|
by the controller. Each shelf is uniquely numbered in the range
|
|
from 1 to vpwrShelfCapacity.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrSystemParameterGroup 1}
|
|
|
|
vpwrSystemVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" The current system voltage.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrSystemParameterGroup 2}
|
|
|
|
vpwrSystemCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS " Amperes"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" The current system current.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrSystemParameterGroup 3}
|
|
|
|
vpwrSystemControllerState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
systemControllerStateUnknown(0),
|
|
systemControllerStateNormal(1),
|
|
systemControllerStateChange(2) ,
|
|
systemControllerStateAlarm(3),
|
|
systemControllerStateMenu(4 ),
|
|
systemControllerStateIrActive(5)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" Current System state as shown on the enhanced display.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrSystemParameterGroup 4}
|
|
|
|
|
|
vpwrSystemInternalTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "degrees Centigrade"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" The current controller internal temperature.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrSystemParameterGroup 5}
|
|
|
|
vpwrSystemTempCompensationState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
systemTempCompInactive(0),
|
|
systemTempCompActive(1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" Active or Inactive. Applicable only if temperature compensation is enabled.
|
|
This means that the controller is temperature compensating the float voltage.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrSystemParameterGroup 6}
|
|
|
|
vpwrSystemType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
sysTypeUnknow (0),
|
|
sysType48V (1),
|
|
sysType24V(2) ,
|
|
sysType12V(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This parameter describes the type of the system being managed.
|
|
This object is set by Valere Power Inc.
|
|
"
|
|
::= { vpwrSystemParameterGroup 7 }
|
|
|
|
--
|
|
-- The System LVD Operating Setpoints group.
|
|
--
|
|
|
|
vpwrLvdWarningSetpoint OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS " * .01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"LVD Warning voltage setpoint."
|
|
::= { vpwrLvdConfigGroup 1}
|
|
|
|
vpwrLvdDisconnectSetpoint OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"LVD disconnect voltage setpoint."
|
|
::= { vpwrLvdConfigGroup 2}
|
|
vpwrLvdReconnectSetpoint OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"LVD Reconnect voltage setpoint."
|
|
::= { vpwrLvdConfigGroup 3}
|
|
vpwrLvdReconnectDelayTimer OBJECT-TYPE
|
|
SYNTAX INTEGER (20..240)
|
|
UNITS " Seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The delay time, in seconds, before LVD is reconnected"
|
|
::= { vpwrLvdConfigGroup 4}
|
|
|
|
vpwrLvdContactorConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VpwrLvdContactorConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This table describes shelves and modules
|
|
that make up the sysetm.
|
|
"
|
|
::= { vpwrLvdConfigGroup 5 }
|
|
|
|
vpwrLvdContactorConfigEntry OBJECT-TYPE
|
|
SYNTAX VpwrLvdContactorConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular module making up the system."
|
|
|
|
INDEX { vpwrBayIndex, vpwrModuleIndex,vpwrLvdContactorIndex }
|
|
|
|
::= { vpwrLvdContactorConfigTable 1 }
|
|
|
|
VpwrLvdContactorConfigEntry ::= SEQUENCE {
|
|
vpwrLvdContactorIndex PositiveInteger,
|
|
vpwrLvdContactorWarningSetpoint PositiveInteger ,
|
|
vpwrLvdContactorDisconnectSetpoint PositiveInteger ,
|
|
vpwrLvdContactorReconnectSetpoint PositiveInteger ,
|
|
vpwrLvdContactorReconnectDelayTimer PositiveInteger ,
|
|
vpwrLvdContactorState PositiveInteger
|
|
}
|
|
vpwrLvdContactorIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
UNITS " None"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"contactor index"
|
|
::= { vpwrLvdContactorConfigEntry 1}
|
|
|
|
vpwrLvdContactorWarningSetpoint OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
UNITS " * .01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"LVD Warning voltage setpoint."
|
|
::= { vpwrLvdContactorConfigEntry 2}
|
|
|
|
vpwrLvdContactorDisconnectSetpoint OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"LVD disconnect voltage setpoint."
|
|
::= { vpwrLvdContactorConfigEntry 3}
|
|
vpwrLvdContactorReconnectSetpoint OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"LVD Reconnect voltage setpoint."
|
|
::= { vpwrLvdContactorConfigEntry 4}
|
|
vpwrLvdContactorReconnectDelayTimer OBJECT-TYPE
|
|
SYNTAX PositiveInteger (0..240)
|
|
UNITS " Seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The delay time, in seconds, before LVD is reconnected"
|
|
::= { vpwrLvdContactorConfigEntry 5}
|
|
vpwrLvdContactorState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
contactorOpen (0),
|
|
contactorClose(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The delay time, in seconds, before LVD is reconnected"
|
|
::= { vpwrLvdContactorConfigEntry 6}
|
|
|
|
|
|
--
|
|
-- The Rectifier Operating Parameters group.
|
|
--
|
|
|
|
vpwrRectifierFVSetpoint OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System Float Voltage setting"
|
|
::= { vpwrRectifierConfigGroup 1}
|
|
vpwrRectifierHVSDSetpoint OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System High Voltage Shutdown voltage setting"
|
|
::= { vpwrRectifierConfigGroup 2}
|
|
|
|
vpwrRectifierCurrentLimitAdminState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
rectCurrentLimitDisabled(0),
|
|
rectCurrentLimitEnabled(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter allows enabling or disabling boost.
|
|
"
|
|
REFERENCE " "
|
|
|
|
::= {vpwrRectifierConfigGroup 3}
|
|
|
|
vpwrRectifierCurrentLimit OBJECT-TYPE
|
|
SYNTAX INTEGER (5 .. 200)
|
|
UNITS "Amperes"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Rectifier current limit setpoint"
|
|
::= { vpwrRectifierConfigGroup 4}
|
|
|
|
--
|
|
-- The Alarm group.
|
|
--
|
|
|
|
|
|
vpwrAlarmsPresent OBJECT-TYPE
|
|
SYNTAX Gauge32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present number of active alarm conditions."
|
|
::= { vpwrDcPowerAlarmGroup 1 }
|
|
|
|
vpwrAlarmTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VpwrAlarmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of alarm table entries. The table contains
|
|
zero, one, or many rows at any moment, depending upon
|
|
the number of alarm conditions in effect. The table
|
|
is initially empty at agent startup. The agent
|
|
creates a row in the table each time a condition is
|
|
detected and deletes that row when that condition no
|
|
longer pertains.
|
|
The vpwrAlarmIndex, for each type of module starts at 1
|
|
and is limited by the total number of alarams that can be
|
|
generated by the module.
|
|
|
|
Alarms are named by an AutonomousType (OBJECT
|
|
IDENTIFIER), vpwrAlarmDescr, to allow a single table to
|
|
reflect alarms for different type of modules.
|
|
|
|
The number of rows in the table at any given time is
|
|
reflected by the value of vpwrAlarmsPresent."
|
|
|
|
::= { vpwrDcPowerAlarmGroup 2 }
|
|
|
|
vpwrAlarmEntry OBJECT-TYPE
|
|
SYNTAX VpwrAlarmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular alarm."
|
|
INDEX { vpwrAlarmIndex }
|
|
::= { vpwrAlarmTable 1 }
|
|
|
|
VpwrAlarmEntry ::= SEQUENCE {
|
|
vpwrAlarmIndex PositiveInteger,
|
|
vpwrAlarmDescr AutonomousType,
|
|
vpwrAlarmTime TimeStamp
|
|
}
|
|
|
|
vpwrAlarmIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Identifies the alarm associated with the module.
|
|
It is unique on per module type basis. For example,
|
|
multiple rectifiers can have the same alarm and therefore same
|
|
vpwrAlarmIndex active at any one time.
|
|
"
|
|
::= { vpwrAlarmEntry 1 }
|
|
|
|
|
|
vpwrAlarmDescr OBJECT-TYPE
|
|
SYNTAX AutonomousType
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A reference to an alarm description object. The
|
|
object referenced should not be accessible, but rather
|
|
be used to provide a unique description of the alarm
|
|
condition."
|
|
::= { vpwrAlarmEntry 2 }
|
|
|
|
vpwrAlarmTime OBJECT-TYPE
|
|
SYNTAX TimeStamp
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of sysUpTime when the alarm condition was
|
|
detected."
|
|
|
|
::= { vpwrAlarmEntry 3 }
|
|
|
|
|
|
|
|
--
|
|
-- The Battery Group
|
|
--
|
|
|
|
|
|
|
|
vpwrBatteryTempTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VpwrBatteryTempEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table describes battery temperature probes.
|
|
"
|
|
::= { vpwrBatteryTempGroup 1 }
|
|
|
|
vpwrBatteryTempEntry OBJECT-TYPE
|
|
SYNTAX VpwrBatteryTempEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular temperature probe."
|
|
INDEX { vpwrBatteryTempIndex }
|
|
::= { vpwrBatteryTempTable 1 }
|
|
|
|
VpwrBatteryTempEntry ::= SEQUENCE {
|
|
vpwrBatteryTempIndex INTEGER,
|
|
vpwrBatteryTempName DisplayString,
|
|
vpwrBatteryTemp INTEGER
|
|
}
|
|
|
|
vpwrBatteryTempIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Index into temperature table"
|
|
::= { vpwrBatteryTempEntry 1}
|
|
|
|
vpwrBatteryTempName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (1 .. 8))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A string identifying probe location."
|
|
::= { vpwrBatteryTempEntry 2}
|
|
|
|
vpwrBatteryTemp OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "degrees Centigrade"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Current temperature as recorded by the probe."
|
|
::= { vpwrBatteryTempEntry 3}
|
|
|
|
|
|
-- Threshold for Battery Temperature Trap
|
|
|
|
vpwrBatteryTempLThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "degrees Centigrade"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature value at which a clear trap would be sent.
|
|
All three battery temperature must be at or below this value
|
|
to trigger this trap.
|
|
"
|
|
::= { vpwrBatteryTempGroup 2}
|
|
|
|
vpwrBatteryTempUThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "degrees Centigrade"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature value at which a set trap would be sent.
|
|
Any one of the three battery temperatures at or exceeding this limit
|
|
would trigger the trap.
|
|
"
|
|
::= { vpwrBatteryTempGroup 3}
|
|
|
|
batteryTempCompensation OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
tempCompDisabled(0),
|
|
tempCompEnabled(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter enables/disables temperature compensation.
|
|
"
|
|
REFERENCE " "
|
|
|
|
::= {vpwrBatteryTempGroup 4}
|
|
|
|
batteryTempCompHighStartTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER (25 .. 60)
|
|
UNITS "degrees Centigrade"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" The temperature at which temperature compensation becomes
|
|
active.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBatteryTempGroup 5}
|
|
|
|
batteryTempCompHighStopVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" When temperature compensation is active, batteryTempCompHighStopVoltage is the
|
|
limit to which float voltage will be reduced.
|
|
For example, to set this voltage to 51.75 volts enter a value of 5175.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBatteryTempGroup 6}
|
|
|
|
batteryTempCompHighSlope OBJECT-TYPE
|
|
SYNTAX INTEGER (0 .. 250)
|
|
UNITS " milli-Volts per degrees Centigrade"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" The rate at which float voltage is changed, within the specified limits,
|
|
when temperature compensation is active.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBatteryTempGroup 7}
|
|
|
|
|
|
batteryTempCompLowStartTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "degrees Centigrade"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" The temperature at which temperature compensation becomes
|
|
active.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBatteryTempGroup 8}
|
|
|
|
batteryTempCompLowStopVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" When temperature compensation is active, batteryTempCompLowStopVoltage is the
|
|
limit to which float voltage will be reduced.
|
|
For example, to set this voltage to 51.75 volts enter a value of 5175.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBatteryTempGroup 9}
|
|
|
|
batteryTempCompLowSlope OBJECT-TYPE
|
|
SYNTAX INTEGER (0 .. 250)
|
|
UNITS " milli-Volts per degrees Centigrade"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" The rate at which float voltage is changed, within the specified limits,
|
|
when temperature compensation is active.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBatteryTempGroup 10}
|
|
|
|
batteryTempCompRunawayTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER (25 .. 60)
|
|
UNITS "degrees Centigrade"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" The temperature at which system voltage will be set to
|
|
batteryTempCompRunawayStopVoltage.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBatteryTempGroup 11}
|
|
|
|
batteryTempCompRunawayStopVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" When temperature compensation is enabled, float voltage will be reduced to
|
|
batteryTempCompRunawayStopVoltage if temperature
|
|
reaches batteryTempCompRunawayTemperature.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBatteryTempGroup 12}
|
|
|
|
batteryTempCompSenseSource OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
external(0),
|
|
internal(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter selects the temperature sensing point for temperature
|
|
compensation (in)activation.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBatteryTempGroup 13}
|
|
|
|
batteryTempCompRunawayState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
inactive(0),
|
|
active(1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter selects the temperature sensing point for temperature
|
|
compensation (in)activation.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBatteryTempGroup 14}
|
|
|
|
thermalProbeTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF ThermalProbeEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table describes battery temperature probes.
|
|
"
|
|
::= { vpwrBatteryTempGroup 15 }
|
|
|
|
thermalProbeEntry OBJECT-TYPE
|
|
SYNTAX ThermalProbeEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular temperature probe."
|
|
-- INDEX { vpwrBatteryTempIndex }
|
|
AUGMENTS {vpwrBatteryTempEntry}
|
|
::= { thermalProbeTable 1 }
|
|
|
|
ThermalProbeEntry ::= SEQUENCE {
|
|
thermalProbeState INTEGER
|
|
}
|
|
|
|
thermalProbeState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
notPresent(0),
|
|
present(1),
|
|
removed(2),
|
|
shorted(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of thermal probe."
|
|
::= { thermalProbeEntry 1}
|
|
|
|
|
|
--
|
|
-- The SNMP Configuration Parameters
|
|
--
|
|
|
|
vpwrTrapTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VpwrTrapEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of possible trap destinations depending upon
|
|
the criticality of the trap.
|
|
"
|
|
::= { vpwrDcPowerSnmpConfig 1 }
|
|
|
|
vpwrTrapEntry OBJECT-TYPE
|
|
SYNTAX VpwrTrapEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular trap destination."
|
|
INDEX { vpwrTrapIpIndex }
|
|
::= { vpwrTrapTable 1 }
|
|
|
|
VpwrTrapEntry ::= SEQUENCE {
|
|
vpwrTrapIpIndex INTEGER,
|
|
vpwrTrapIpAddress IpAddress,
|
|
vpwrTrapCriticality INTEGER
|
|
}
|
|
vpwrTrapIpIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap Entry Index "
|
|
::= { vpwrTrapEntry 1}
|
|
|
|
vpwrTrapIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap destination IP Address"
|
|
::= { vpwrTrapEntry 2}
|
|
|
|
vpwrTrapCriticality OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Criticality of traps sent to this IP Address"
|
|
::= { vpwrTrapEntry 3}
|
|
|
|
|
|
vpwrReadCommunityString OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE (3 .. 8))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This allows setting password to be able to do Get operations"
|
|
::= { vpwrDcPowerSnmpConfig 2 }
|
|
|
|
vpwrWriteCommunityString OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE (3 .. 8))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This allows setting password to be able to do Get and Set
|
|
operations.
|
|
The read-access is not allowed in the actual implementation.
|
|
"
|
|
::= { vpwrDcPowerSnmpConfig 3 }
|
|
|
|
vpwrTrapCommunityString OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE (3 .. 8))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This allows setting community string required for the
|
|
trap to be accepted at the destination.
|
|
"
|
|
::= { vpwrDcPowerSnmpConfig 4 }
|
|
|
|
--
|
|
-- traps
|
|
--
|
|
vpwrTrapPowerMajorAlarm TRAP-TYPE
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"Major Alarm"
|
|
::= 1
|
|
|
|
vpwrTrapPowerMinorAlarm TRAP-TYPE
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"Minor Alarm"
|
|
::= 2
|
|
|
|
vpwrTrapACFAlarm TRAP-TYPE
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"AC Fail Alarm"
|
|
::= 3
|
|
|
|
vpwrTrapHVAlarm TRAP-TYPE
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"High Voltage Warning Alarm"
|
|
::= 4
|
|
|
|
vpwrTrapHVSDAlarm TRAP-TYPE
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"High Voltage Shutdown Alarm"
|
|
::= 5
|
|
vpwrTrapBDAlarm TRAP-TYPE
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"Battery on Discharge Alarm"
|
|
::= 6
|
|
vpwrTrapLVDWarningAlarm TRAP-TYPE
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"LVD Warning Alarm"
|
|
::= 7
|
|
|
|
vpwrTrapLVDOpenAlarm TRAP-TYPE
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"LVD Open Alarm"
|
|
::= 8
|
|
|
|
vpwrTrapDistAlarm TRAP-TYPE
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"Distribution Open Alarm"
|
|
::= 9
|
|
|
|
vpwrTrapAuxAlarm TRAP-TYPE
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"Auxiliary System Alarm"
|
|
::= 10
|
|
|
|
vpwrTrapSystemRedundancyAlarm TRAP-TYPE
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"System Redundant Capacity Alarm"
|
|
::= 11
|
|
|
|
vpwrTrapIShareAlarm TRAP-TYPE
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"Rectifier Current Share Alarm"
|
|
::= 12
|
|
vpwrTrapModuleFailAlarm TRAP-TYPE
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"Single Rectifier Fail Alarm"
|
|
::= 13
|
|
|
|
vpwrTrapMultipleModuleFailAlarm TRAP-TYPE
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"Multiple Rectifier Fail Alarm"
|
|
::= 14
|
|
|
|
vpwrTrapModuleCommAlarm TRAP-TYPE
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"Module Communication Alarm"
|
|
::= 15
|
|
vpwrTrapSystemOverTemperatureAlarm TRAP-TYPE
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"System Over Temperature Alarm"
|
|
::= 16
|
|
vpwrTrapSystemOK TRAP-TYPE
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"SYSTEM OK - No Active Alarms"
|
|
::= 17
|
|
|
|
vpwrTrapModuleInserted TRAP-TYPE
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString, vpwrBayIndex, vpwrModuleIndex }
|
|
DESCRIPTION
|
|
"A new module has been inserted into the system."
|
|
::= 18
|
|
|
|
vpwrTrapModuleRemoved TRAP-TYPE
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString,vpwrBayIndex, vpwrModuleIndex }
|
|
DESCRIPTION
|
|
"A module has been removed from the system."
|
|
::= 19
|
|
|
|
|
|
vpwrTrapThermalCompActive TRAP-TYPE
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"Thermal compensation has become active."
|
|
::= 20
|
|
|
|
vpwrTrapThermalCompInactive TRAP-TYPE
|
|
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"Thermal compensation has been de-activated."
|
|
::= 21
|
|
|
|
vpwrTrapInternalTempAlarmSet TRAP-TYPE
|
|
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"Internal Temperature upper threshold exceeded."
|
|
::= 22
|
|
|
|
vpwrTrapInternalTempAlarmCleared TRAP-TYPE
|
|
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"Internal Temperature within limits"
|
|
::= 23
|
|
|
|
vpwrTrapBatteryTempAlarmSet TRAP-TYPE
|
|
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"At least one Battery Temperature exceeded upper threshold."
|
|
::= 24
|
|
|
|
vpwrTrapBatteryTempAlarmCleared TRAP-TYPE
|
|
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"All Battery Temperatures within limits."
|
|
::= 25
|
|
|
|
vpwrTrapLoginFail TRAP-TYPE
|
|
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"Admin login failed due to wrong username/password."
|
|
::= 26
|
|
vpwrTrapLoginSuccess TRAP-TYPE
|
|
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"Admin login successful."
|
|
::= 27
|
|
vpwrTrapLogout TRAP-TYPE
|
|
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"Admin logout."
|
|
::= 28
|
|
|
|
vpwrTrapAdminPwdChange TRAP-TYPE
|
|
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"Config change submitted with invalid access."
|
|
::= 29
|
|
|
|
|
|
vpwrTrapIllegalConfigSubmit TRAP-TYPE
|
|
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"Config change submitted with invalid access."
|
|
::= 30
|
|
vpwrTrapCfgChange TRAP-TYPE
|
|
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"Config change submitted."
|
|
::= 31
|
|
vpwrTrapClearEventHistory TRAP-TYPE
|
|
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"Clear Event history buffer clear request."
|
|
::= 32
|
|
vpwrTrapSwDownloadNoReboot TRAP-TYPE
|
|
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"System software upgrade without reboot."
|
|
::= 33
|
|
vpwrTrapSwDownloadAndReboot TRAP-TYPE
|
|
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"System reboot due to software upgrade."
|
|
::= 34
|
|
|
|
vpwrTrapSystemClockChange TRAP-TYPE
|
|
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"System clock updated."
|
|
::= 35
|
|
vpwrTrapModuleAlarm TRAP-TYPE
|
|
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"Module Alarm."
|
|
::= 36
|
|
|
|
vpwrTrapOIDChange TRAP-TYPE
|
|
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"Change in OID."
|
|
::= 37
|
|
|
|
vpwrTrapThermalRunaway TRAP-TYPE
|
|
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"Thermal Runaway Alarm."
|
|
::= 38
|
|
|
|
vpwrTrapBatteryDischargeTestAlarm TRAP-TYPE
|
|
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"System Voltage dropped to BDT Alarm Setpoint."
|
|
::= 39
|
|
vpwrTrapRingerAAlarm TRAP-TYPE
|
|
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"Ringer A Fail Alarm."
|
|
::= 40
|
|
vpwrTrapRingerBAlarm TRAP-TYPE
|
|
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"Ringer B Fail Alarm."
|
|
::= 41
|
|
vpwrTrapSingleRingerAlarm TRAP-TYPE
|
|
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"Single Ringer Fail Alarm."
|
|
::= 42
|
|
vpwrTrapMultipleRingerAlarm TRAP-TYPE
|
|
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"Multiple Ringer Fail Alarm."
|
|
::= 43
|
|
vpwrTrapThermalProbeAlarm TRAP-TYPE
|
|
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"Thermal Probe Missing Alarm."
|
|
::= 44
|
|
vpwrTrapRingerCommAlarm TRAP-TYPE
|
|
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"Ringer Communication Alarm."
|
|
::= 45
|
|
vpwrTrapDistributionCommAlarm TRAP-TYPE
|
|
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"Distribution Communication Alarm."
|
|
::= 46
|
|
vpwrTrapConverterAlarm TRAP-TYPE
|
|
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"Single Converter Fail Alarm."
|
|
::= 47
|
|
vpwrTrapMultipleConvFailAlarm TRAP-TYPE
|
|
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"Multiple Converter Fail Alarm."
|
|
::= 48
|
|
vpwrTrapUnmappedAddressAlarm TRAP-TYPE
|
|
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"Unmapped I2C Address."
|
|
::= 49
|
|
|
|
vpwrTrapConfigErrorAlarm TRAP-TYPE
|
|
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"Configuration Error."
|
|
::= 50
|
|
vpwrTrapDisplayFirmwareMismatchAlarm TRAP-TYPE
|
|
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"Display Firmware Mismatch."
|
|
::= 51
|
|
vpwrTrapConverterInputFailAlarm TRAP-TYPE
|
|
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"Converter Input Fail Alarm."
|
|
::= 52
|
|
vpwrTrapBatteryRechgIlimitFailAlarm TRAP-TYPE
|
|
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"Battery Recharge Current Limit Fail."
|
|
::= 53
|
|
vpwrTrapSystemAlive TRAP-TYPE
|
|
|
|
ENTERPRISE vpwrDcPowerTraps
|
|
VARIABLES { vpwrTrapsMsgString }
|
|
DESCRIPTION
|
|
"Periodic Keepalive trap."
|
|
::= 54
|
|
|
|
--
|
|
-- LVD Alarm Group
|
|
--
|
|
|
|
vpwrLvdAlarmContactorOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Contactor open"
|
|
::= {vpwrLvdAlarmGroup 1 }
|
|
|
|
|
|
vpwrLvdAlarmCBOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Circuit Breaker open"
|
|
::= {vpwrLvdAlarmGroup 2 }
|
|
|
|
vpwrTrapLvdFuseOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Fuse open"
|
|
::= {vpwrLvdAlarmGroup 3 }
|
|
vpwrLvdAlarmWarning OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Plant Voltage below warning threshold"
|
|
::= {vpwrLvdAlarmGroup 4 }
|
|
|
|
--
|
|
-- Rectifier Alarm Group
|
|
--
|
|
|
|
vpwrRectAlarmDCFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= {vpwrRectifierAlarmGroup 1}
|
|
|
|
vpwrRectAlarmBoostFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= {vpwrRectifierAlarmGroup 2}
|
|
|
|
vpwrRectAlarmACFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= {vpwrRectifierAlarmGroup 3}
|
|
|
|
vpwrRectAlarmHVSD OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= {vpwrRectifierAlarmGroup 4}
|
|
|
|
vpwrRectAlarmFanFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= {vpwrRectifierAlarmGroup 5}
|
|
|
|
vpwrRectAlarmAmbTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= {vpwrRectifierAlarmGroup 6}
|
|
vpwrRectAlarmIntTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= {vpwrRectifierAlarmGroup 7}
|
|
|
|
vpwrRectAlarmIShare OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= {vpwrRectifierAlarmGroup 8}
|
|
|
|
vpwrRectAlarmUV OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= {vpwrRectifierAlarmGroup 9}
|
|
|
|
vpwrRectAlarmLowVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= {vpwrRectifierAlarmGroup 10}
|
|
|
|
vpwrRectAlarmReserved OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= {vpwrRectifierAlarmGroup 11}
|
|
|
|
vpwrRectAlarmDCEnable OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= {vpwrRectifierAlarmGroup 12}
|
|
|
|
vpwrRectAlarmRemoteShutdown OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= {vpwrRectifierAlarmGroup 13}
|
|
|
|
vpwrRectAlarmModDisableShutdown OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= {vpwrRectifierAlarmGroup 14}
|
|
|
|
vpwrRectAlarmShortPinShutdown OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= {vpwrRectifierAlarmGroup 15}
|
|
|
|
vpwrRectAlarmBoostComm OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= {vpwrRectifierAlarmGroup 16}
|
|
|
|
|
|
vpwrTrapsMsgString OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE (0 .. 127))
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
" Place holder for trap notification message string"
|
|
::= { vpwrDcPowerTrapsMsgString 1 }
|
|
|
|
vpwrTrapUserIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Place holder for IP address of the user accessing the system"
|
|
::= { vpwrDcPowerTrapsMsgString 2}
|
|
|
|
vpwrTrapEventTimeStamp OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Place holder for time-stamp."
|
|
::= { vpwrDcPowerTrapsMsgString 3}
|
|
|
|
sysRelayConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF SysRelayConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table describes battery temperature probes.
|
|
"
|
|
::= { vpwrDcPowerAlarmGroup 3 }
|
|
|
|
sysRelayConfigEntry OBJECT-TYPE
|
|
SYNTAX SysRelayConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular temperature probe."
|
|
INDEX { sysRelayIndex }
|
|
::= { sysRelayConfigTable 1 }
|
|
|
|
SysRelayConfigEntry ::= SEQUENCE {
|
|
sysRelayIndex INTEGER,
|
|
sysRelayDefaultName DisplayString,
|
|
sysRelayCustomName DisplayString,
|
|
sysRelayAlarmSeverity INTEGER
|
|
}
|
|
|
|
sysRelayIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Index into temperature table"
|
|
::= { sysRelayConfigEntry 1}
|
|
|
|
sysRelayDefaultName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (1 .. 8))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A string identifying probe location."
|
|
::= { sysRelayConfigEntry 2}
|
|
|
|
sysRelayCustomName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (1 .. 8))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A string identifying probe location."
|
|
::= { sysRelayConfigEntry 3}
|
|
|
|
sysRelayAlarmSeverity OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
alarmNone(0),
|
|
alarmMajor(1),
|
|
alarmMinor(2),
|
|
alarmMajorAndMinor(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Current temperature as recorded by the probe."
|
|
::= { sysRelayConfigEntry 4}
|
|
|
|
|
|
sysAlarmConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF SysAlarmConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table describes battery temperature probes.
|
|
"
|
|
::= { vpwrDcPowerAlarmGroup 4 }
|
|
|
|
sysAlarmConfigEntry OBJECT-TYPE
|
|
SYNTAX SysAlarmConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular temperature probe."
|
|
INDEX { sysAlarmIndex }
|
|
::= { sysAlarmConfigTable 1 }
|
|
|
|
SysAlarmConfigEntry ::= SEQUENCE {
|
|
sysAlarmIndex INTEGER,
|
|
sysAlarmDefaultName DisplayString,
|
|
sysAlarmCustomName DisplayString,
|
|
sysAlarmSeverity INTEGER ,
|
|
sysAlarmToRelayMapping DisplayString ,
|
|
sysAlarmOperStatus INTEGER
|
|
}
|
|
|
|
sysAlarmIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Index into temperature table"
|
|
::= { sysAlarmConfigEntry 1}
|
|
|
|
sysAlarmDefaultName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (1 .. 8))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A string identifying probe location."
|
|
::= { sysAlarmConfigEntry 2}
|
|
|
|
sysAlarmCustomName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (1 .. 8))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A string identifying probe location."
|
|
::= { sysAlarmConfigEntry 3}
|
|
|
|
sysAlarmSeverity OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none(0),
|
|
major(1),
|
|
minor(2),
|
|
majorAndMinor(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Alarm Severity as denoted by Major and Minor Alarm Mask"
|
|
::= { sysAlarmConfigEntry 4}
|
|
|
|
sysAlarmToRelayMapping OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (1 .. 8))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"No additional mapping = 0
|
|
Map to Relay A = 1
|
|
Map to Relay B = 2
|
|
Map to Relay C = 4
|
|
Map to Relay D = 8
|
|
Map to Relay E = 16
|
|
Map to Relay F = 32
|
|
Map to Relay A and B = (1 + 2) and so on
|
|
The major/minor classification of alarms automatically
|
|
associates it with Major/Minor relay. Assigning a null
|
|
mapping here does not override sysRelayAlarmSeverity for
|
|
the alarm.
|
|
It should be used to define mapping to additional relays.
|
|
"
|
|
::= { sysAlarmConfigEntry 5}
|
|
|
|
sysAlarmOperStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
inactive(0),
|
|
active(1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates current alarm status"
|
|
::= { sysAlarmConfigEntry 6}
|
|
|
|
|
|
sysAuxAlarmConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF SysAuxAlarmConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table describes battery temperature probes.
|
|
"
|
|
::= { vpwrDcPowerAlarmGroup 5 }
|
|
|
|
sysAuxAlarmConfigEntry OBJECT-TYPE
|
|
SYNTAX SysAuxAlarmConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular temperature probe."
|
|
INDEX { sysAuxAlarmIndex }
|
|
::= { sysAuxAlarmConfigTable 1 }
|
|
|
|
SysAuxAlarmConfigEntry ::= SEQUENCE {
|
|
sysAuxAlarmIndex INTEGER,
|
|
sysAuxAlarmDefaultName DisplayString,
|
|
sysAuxAlarmCustomName DisplayString,
|
|
sysAuxAlarmSeverity INTEGER ,
|
|
sysAuxAlarmToRelayMapping DisplayString ,
|
|
sysAuxAlarmPolarity INTEGER ,
|
|
sysAuxAlarmOperStatus INTEGER
|
|
}
|
|
|
|
sysAuxAlarmIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Index into temperature table"
|
|
::= { sysAuxAlarmConfigEntry 1}
|
|
|
|
sysAuxAlarmDefaultName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (1 .. 8))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A string identifying probe location."
|
|
::= { sysAuxAlarmConfigEntry 2}
|
|
|
|
sysAuxAlarmCustomName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (1 .. 8))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A string identifying probe location."
|
|
::= { sysAuxAlarmConfigEntry 3}
|
|
|
|
sysAuxAlarmSeverity OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none(0),
|
|
major(1),
|
|
minor(2),
|
|
majorAndMinor(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Aux Alarm Severity"
|
|
::= { sysAuxAlarmConfigEntry 4}
|
|
|
|
sysAuxAlarmToRelayMapping OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (1 .. 8))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"No additional mapping = 0
|
|
Map to Relay A = 1
|
|
Map to Relay B = 2
|
|
Map to Relay C = 4
|
|
Map to Relay D = 8
|
|
Map to Relay E = 16
|
|
Map to Relay F = 32
|
|
Map to Relay A and B = (1 + 2) and so on
|
|
The major/minor classification of alarms automatically
|
|
associates it with Major/Minor relay. Assigning a null
|
|
mapping here does not override sysRelayAlarmSeverity for
|
|
the alarm.
|
|
It should be used to define mapping to additional relays.
|
|
"
|
|
::= { sysAuxAlarmConfigEntry 5}
|
|
|
|
sysAuxAlarmPolarity OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
alarmOnOpen(0),
|
|
alarmOnClose(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Current temperature as recorded by the probe."
|
|
::= { sysAuxAlarmConfigEntry 6}
|
|
|
|
sysAuxAlarmOperStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
inactive(0),
|
|
active(1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates current alarm status"
|
|
::= { sysAuxAlarmConfigEntry 7}
|
|
|
|
sysAlarmComFailState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(0),
|
|
enabled(1),
|
|
other(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enable/Disable generation of comm fail alarm."
|
|
::= { vpwrDcPowerAlarmGroup 6 }
|
|
|
|
sysAlarmIShareState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(0),
|
|
enabled(1),
|
|
other(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enable/Disable generation of current share alarm."
|
|
::= { vpwrDcPowerAlarmGroup 7}
|
|
|
|
sysAlarmRedundancyState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(0),
|
|
nPlus1(1),
|
|
nPlus2(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enable/Disable generation of redundancy alarm."
|
|
::= { vpwrDcPowerAlarmGroup 8}
|
|
|
|
--
|
|
-- The Ringer Configuration Parameters group.
|
|
--
|
|
|
|
|
|
vpwrRingerParameterTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VpwrRingerParameterEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of alarm table entries. The table contains
|
|
zero, one, or many rows at any moment, depending upon
|
|
the number of alarm conditions in effect. The table
|
|
is initially empty at agent startup. The agent
|
|
creates a row in the table each time a condition is
|
|
detected and deletes that row when that condition no
|
|
longer pertains.
|
|
The vpwrAlarmIndex, for each type of module starts at 1
|
|
and is limited by the total number of alarams that can be
|
|
generated by the module.
|
|
|
|
Alarms are named by an AutonomousType (OBJECT
|
|
IDENTIFIER), vpwrAlarmDescr, to allow a single table to
|
|
reflect alarms for different type of modules.
|
|
|
|
The number of rows in the table at any given time is
|
|
reflected by the value of vpwrAlarmsPresent."
|
|
|
|
::= { vpwrRingerConfigGroup 1 }
|
|
|
|
vpwrRingerParameterEntry OBJECT-TYPE
|
|
SYNTAX VpwrRingerParameterEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular alarm."
|
|
INDEX { vpwrModuleIndex,vpwrRingerIndex}
|
|
::= { vpwrRingerParameterTable 1 }
|
|
|
|
VpwrRingerParameterEntry ::= SEQUENCE {
|
|
vpwrRingerIndex INTEGER,
|
|
vpwrRingerParameterAdminState INTEGER,
|
|
vpwrRingerParameterAcVoltage INTEGER,
|
|
vpwrRingerParameterDcVoltage INTEGER,
|
|
vpwrRingerParameterFrequency INTEGER
|
|
}
|
|
vpwrRingerIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter allows selecting ringer A or Ringer B as the active ringer.
|
|
"
|
|
REFERENCE " "
|
|
|
|
::= {vpwrRingerParameterEntry 1}
|
|
|
|
vpwrRingerParameterAdminState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
ringerDisabled(0),
|
|
ringerAOn(1) ,
|
|
ringerBOn(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter allows selecting ringer A or Ringer B as the active ringer.
|
|
"
|
|
REFERENCE " "
|
|
|
|
::= {vpwrRingerParameterEntry 2}
|
|
|
|
vpwrRingerParameterAcVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER (7000 .. 11000)
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrRingerParameterEntry 3}
|
|
|
|
vpwrRingerParameterDcVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER (0 .. 5600 )
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrRingerParameterEntry 4}
|
|
|
|
vpwrRingerParameterFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER (17 .. 50)
|
|
UNITS " Hz"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrRingerParameterEntry 5}
|
|
|
|
vpwrRingerNumberPresent OBJECT-TYPE
|
|
SYNTAX Gauge32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present number of active alarm conditions."
|
|
::= { vpwrRingerConfigGroup 2 }
|
|
|
|
|
|
--
|
|
-- ringer Alarm Group
|
|
--
|
|
|
|
vpwrRingerAlarmaAFailed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ringer A Failed"
|
|
::= {vpwrRingerAlarmGroup 1 }
|
|
|
|
vpwrRingerAlarmAOTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ringer A Heatsink Over-Temperature"
|
|
::= {vpwrRingerAlarmGroup 2 }
|
|
|
|
vpwrRingerAlarmAOCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ringer A Over-Current protection"
|
|
::= {vpwrRingerAlarmGroup 3 }
|
|
|
|
vpwrRingerAlarmaBFailed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ringer A Failed"
|
|
::= {vpwrRingerAlarmGroup 4 }
|
|
|
|
vpwrRingerAlarmBOverTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ringer A Heatsink Over-Temperature"
|
|
::= {vpwrRingerAlarmGroup 5 }
|
|
|
|
vpwrRingerAlarmBOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ringer A Over-Current protection"
|
|
::= {vpwrRingerAlarmGroup 6 }
|
|
|
|
|
|
|
|
vpwrBoostAdminState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
boostDisabled(0),
|
|
boostEnabled(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter allows enabling or disabling boost.
|
|
"
|
|
REFERENCE " "
|
|
|
|
::= {vpwrBatteryBoostGroup 1}
|
|
|
|
vpwrBoostVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER (7000 .. 11000)
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBatteryBoostGroup 2}
|
|
|
|
vpwrBoostDuration OBJECT-TYPE
|
|
SYNTAX INTEGER (0 .. 100 )
|
|
UNITS "Hours"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBatteryBoostGroup 3}
|
|
|
|
|
|
vpwrBoostOperState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
boostInactive(0),
|
|
boostActive(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter allows starting or stoping boost if it is enabled.
|
|
"
|
|
REFERENCE " "
|
|
|
|
::= {vpwrBatteryBoostGroup 4}
|
|
|
|
|
|
vpwrBatteryCurrentLimitAdminState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
battetyCurrentLimitDisabled(0),
|
|
battetyCurrentLimitEnabled(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter allows enabling or disabling battery current limit.
|
|
"
|
|
REFERENCE " "
|
|
|
|
::= {vpwrBatteryCurrentGroup 1}
|
|
|
|
vpwrBattetyCurrentLimitValue OBJECT-TYPE
|
|
SYNTAX INTEGER (5 .. 40)
|
|
UNITS "Ampere"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBatteryCurrentGroup 2}
|
|
|
|
vpwrBattetyCurrentValue OBJECT-TYPE
|
|
SYNTAX INTEGER (5 .. 40)
|
|
UNITS "Ampere"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBatteryCurrentGroup 3}
|
|
|
|
|
|
|
|
vpwrBDTAdminState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
bdtDisabled(0),
|
|
bdtEnabled(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" Enable /Disable Battery Discharge Test execution.
|
|
"
|
|
REFERENCE " "
|
|
|
|
::= {vpwrBatteryDischargeTestGroup 1}
|
|
|
|
vpwrBDTDuration OBJECT-TYPE
|
|
SYNTAX INTEGER (17 .. 50)
|
|
UNITS "Minutes"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBatteryDischargeTestGroup 2}
|
|
vpwrBDTAlarmVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER (7000 .. 11000)
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBatteryDischargeTestGroup 3}
|
|
|
|
vpwrBDTAbortVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER (0 .. 5600 )
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBatteryDischargeTestGroup 4}
|
|
|
|
vpwrBDTAlarmCoefficient OBJECT-TYPE
|
|
SYNTAX INTEGER (0 .. 1 )
|
|
UNITS "None"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBatteryDischargeTestGroup 5}
|
|
|
|
vpwrBDTOperState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
bdtInactive(0),
|
|
bdtActive(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" Start/Stop Battery Discharge Test execution.
|
|
"
|
|
REFERENCE " "
|
|
|
|
::= {vpwrBatteryDischargeTestGroup 6}
|
|
|
|
vpwrBDTClearAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
bdtNoAlarm(0)
|
|
bdtAlarmPresent(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" Clears any active bdt alarm.
|
|
"
|
|
REFERENCE " "
|
|
|
|
::= {vpwrBatteryDischargeTestGroup 7}
|
|
|
|
--
|
|
-- Module identification information
|
|
--
|
|
vpwrModuleIdentTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VpwrModuleIdentEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This table describes shelves and modules
|
|
that make up the sysetm.
|
|
"
|
|
::= { vpwrDcPowerModuleIdent 1 }
|
|
|
|
--
|
|
-- The Module Identifier Entry. Defines the sequence for module tables.
|
|
--
|
|
vpwrModuleIdentEntry OBJECT-TYPE
|
|
SYNTAX VpwrModuleIdentEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular Module."
|
|
AUGMENTS {vpwrSystemIdentEntry }
|
|
::= { vpwrModuleIdentTable 1 }
|
|
|
|
|
|
VpwrModuleIdentEntry ::= SEQUENCE {
|
|
vpwrModuleSerialNumber DisplayString ,
|
|
vpwrModuleModelNumber DisplayString ,
|
|
vpwrModuleFwVersion DisplayString ,
|
|
vpwrModuleTestDate DisplayString ,
|
|
vpwrModuleOperHours Counter32
|
|
}
|
|
|
|
vpwrModuleSerialNumber OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Serial Number of the module"
|
|
::= { vpwrModuleIdentEntry 1}
|
|
|
|
vpwrModuleModelNumber OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Model Number of the module."
|
|
::= { vpwrModuleIdentEntry 2}
|
|
|
|
vpwrModuleFwVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Firmware version of the module."
|
|
::= { vpwrModuleIdentEntry 3}
|
|
|
|
vpwrModuleTestDate OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Date when the module was last tested."
|
|
::= { vpwrModuleIdentEntry 4}
|
|
|
|
vpwrModuleOperHours OBJECT-TYPE
|
|
SYNTAX Counter32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Cumulative Operating Hours."
|
|
::= { vpwrModuleIdentEntry 5}
|
|
|
|
--
|
|
-- Panel Module inventory info
|
|
--
|
|
vpwrPanelModuleIdentTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VpwrPanelModuleIdentEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This table describes shelves and modules
|
|
that make up the sysetm.
|
|
"
|
|
::= { vpwrDcPowerModuleIdent 2 }
|
|
|
|
--
|
|
-- The Module Identifier Entry. Defines the sequence for module tables.
|
|
--
|
|
vpwrPanelModuleIdentEntry OBJECT-TYPE
|
|
SYNTAX VpwrPanelModuleIdentEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular alarm."
|
|
AUGMENTS {VpwrPanelIdentEntry }
|
|
::= { vpwrPanelModuleIdentTable 1 }
|
|
|
|
|
|
VpwrPanelModuleIdentEntry ::= SEQUENCE {
|
|
vpwrPanelModuleSerialNumber DisplayString ,
|
|
vpwrPanelModuleModelNumber DisplayString ,
|
|
vpwrPanelModuleFwVersion DisplayString ,
|
|
vpwrPanelModuleTestDate DisplayString ,
|
|
vpwrPanelModuleOperHours Counter32
|
|
}
|
|
|
|
vpwrPanelModuleSerialNumber OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Serial Number of the module"
|
|
::= { vpwrPanelModuleIdentEntry 1}
|
|
|
|
vpwrPanelModuleModelNumber OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Model Number of the module."
|
|
::= { vpwrPanelModuleIdentEntry 2}
|
|
|
|
vpwrPanelModuleFwVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Firmware version of the module."
|
|
::= { vpwrPanelModuleIdentEntry 3}
|
|
|
|
vpwrPanelModuleTestDate OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Date when the module was last tested."
|
|
::= { vpwrPanelModuleIdentEntry 4}
|
|
|
|
vpwrPanelModuleOperHours OBJECT-TYPE
|
|
SYNTAX Counter32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Cumulative Operating Hours."
|
|
::= { vpwrPanelModuleIdentEntry 5}
|
|
--
|
|
-- Bayctrl Module inventory info
|
|
--
|
|
vpwrBayctrlModuleIdentTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VpwrBayctrlModuleIdentEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This table describes bay controllers that make up the sysetm.
|
|
"
|
|
::= { vpwrDcPowerModuleIdent 3 }
|
|
|
|
--
|
|
-- The Module Identifier Entry. Defines the sequence for module tables.
|
|
--
|
|
vpwrBayctrlModuleIdentEntry OBJECT-TYPE
|
|
SYNTAX VpwrBayctrlModuleIdentEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a particular bay controller."
|
|
AUGMENTS {VpwrBayctrlIdentEntry }
|
|
::= { vpwrBayctrlModuleIdentTable 1 }
|
|
|
|
|
|
VpwrBayctrlModuleIdentEntry ::= SEQUENCE {
|
|
vpwrBayctrlSerialNumber DisplayString ,
|
|
vpwrBayctrlModelNumber DisplayString ,
|
|
vpwrBayctrlFwVersion DisplayString ,
|
|
vpwrBayctrlTestDate DisplayString ,
|
|
vpwrBayctrlOperHours Counter32
|
|
}
|
|
|
|
vpwrBayctrlSerialNumber OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Serial Number of the bay controller"
|
|
::= { vpwrBayctrlModuleIdentEntry 1}
|
|
|
|
vpwrBayctrlModelNumber OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Model Number of the bay controller."
|
|
::= { vpwrBayctrlModuleIdentEntry 2}
|
|
|
|
vpwrBayctrlFwVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Firmware version of the bay controller."
|
|
::= { vpwrBayctrlModuleIdentEntry 3}
|
|
|
|
vpwrBayctrlTestDate OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Date when the bayctrl was last tested."
|
|
::= { vpwrBayctrlModuleIdentEntry 4}
|
|
|
|
vpwrBayctrlOperHours OBJECT-TYPE
|
|
SYNTAX Counter32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Cumulative Operating Hours."
|
|
::= { vpwrBayctrlModuleIdentEntry 5}
|
|
|
|
|
|
|
|
END
|
|
|