--Delta-MIB { iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) delta(2254) ups(2) upsv5(5) }
|
|
|
|
|
|
DeltaUPSv5-MIB DEFINITIONS ::= BEGIN
|
|
|
|
|
|
IMPORTS
|
|
enterprises, IpAddress, TimeTicks
|
|
FROM RFC1155-SMI
|
|
DisplayString
|
|
FROM RFC1213-MIB
|
|
OBJECT-TYPE
|
|
FROM RFC-1212
|
|
TRAP-TYPE
|
|
FROM RFC-1215;
|
|
|
|
|
|
delta OBJECT IDENTIFIER ::= { enterprises 2254 }
|
|
|
|
ups OBJECT IDENTIFIER ::= { delta 2 }
|
|
|
|
upsv5 OBJECT IDENTIFIER ::= { ups 5 }
|
|
|
|
dupsIdent OBJECT IDENTIFIER ::= { upsv5 1 }
|
|
dupsControl OBJECT IDENTIFIER ::= { upsv5 2 }
|
|
dupsConfig OBJECT IDENTIFIER ::= { upsv5 3 }
|
|
dupsInput OBJECT IDENTIFIER ::= { upsv5 4 }
|
|
dupsOutput OBJECT IDENTIFIER ::= { upsv5 5 }
|
|
dupsBypass OBJECT IDENTIFIER ::= { upsv5 6 }
|
|
dupsBattery OBJECT IDENTIFIER ::= { upsv5 7 }
|
|
dupsTest OBJECT IDENTIFIER ::= { upsv5 8 }
|
|
dupsAlarm OBJECT IDENTIFIER ::= { upsv5 9 }
|
|
dupsPowerModule OBJECT IDENTIFIER ::= { upsv5 10 }
|
|
dupsTrapArgs OBJECT IDENTIFIER ::= { upsv5 11 }
|
|
dupsParallel OBJECT IDENTIFIER ::= { upsv5 12 }
|
|
dupsIntegrated OBJECT IDENTIFIER ::= { upsv5 13 }
|
|
dupsTraps OBJECT IDENTIFIER ::= { upsv5 20 }
|
|
|
|
|
|
--
|
|
-- dups Ident group
|
|
--
|
|
dupsIdentManufacturer OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..20))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The name of the UPS manufacturer."
|
|
::= { dupsIdent 1 }
|
|
|
|
dupsIdentModel OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..31))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS Model designation."
|
|
::= { dupsIdent 2 }
|
|
|
|
dupsIdentUPSSoftwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..15))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS firmware/software version(s). This variable
|
|
may or may not has the same value as
|
|
upsIdentAgentSoftwareVersion in some implementations."
|
|
::= { dupsIdent 3 }
|
|
|
|
dupsIdentAgentSoftwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..15))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS agent software version. This variable may or
|
|
may not has the same value as
|
|
upsIdentUPSSoftwareVersion in some implementations."
|
|
::= { dupsIdent 4 }
|
|
|
|
dupsIdentName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..63))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A string identifying the UPS. This object should be
|
|
set by the administrator."
|
|
::= { dupsIdent 5 }
|
|
|
|
dupsAttachedDevices OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..63))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A string identifying the devices attached to the
|
|
output(s) of the UPS. This object should be set by
|
|
the administrator."
|
|
::= { dupsIdent 6 }
|
|
|
|
dupsRatingOutputVA OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "VA"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the nominal output VA rating.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsIdent 7 }
|
|
|
|
dupsRatingOutputVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "Volt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the nominal output voltage rating.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsIdent 8 }
|
|
|
|
dupsRatingOutputFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "Hz"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the nominal output frequency rating.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsIdent 9 }
|
|
|
|
dupsRatingInputVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "Volt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the nominal input voltage rating.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsIdent 10 }
|
|
|
|
dupsRatingInputFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "Hz"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the nominal input frequency rating.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsIdent 11 }
|
|
|
|
dupsRatingBatteryVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "Volt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the nominal battery voltage rating.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsIdent 12 }
|
|
|
|
dupsLowTransferVoltUpBound OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "Volt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The minimum input line voltage upper bound allowed
|
|
before the UPS system transfers to battery backup.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsIdent 13 }
|
|
|
|
dupsLowTransferVoltLowBound OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "Volt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The minimum input line voltage lower bound allowed
|
|
before the UPS system transfers to battery backup.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsIdent 14 }
|
|
|
|
dupsHighTransferVoltUpBound OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "Volt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The maximum input line voltage upper bound allowed
|
|
before the UPS system transfers to battery backup.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsIdent 15 }
|
|
|
|
dupsHighTransferVoltLowBound OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "Volt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The maximum input line voltage lower bound allowed
|
|
before the UPS system transfers to battery backup.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsIdent 16 }
|
|
|
|
dupsLowBattTime OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "Second"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Minutes, time from low battery to low battery shutdown.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsIdent 17 }
|
|
|
|
dupsOutletRelays OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Number of outlet relay. If it is 0, the function is not
|
|
available for the UPS."
|
|
::= { dupsIdent 18 }
|
|
|
|
dupsType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on-line(1),
|
|
off-line(2),
|
|
line-interactive(3),
|
|
three-phase(4),
|
|
splite-phase(5)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicate the UPS type."
|
|
::= { dupsIdent 19 }
|
|
|
|
--
|
|
-- dups Control group
|
|
--
|
|
dupsShutdownType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
output(1),
|
|
system(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"This object determines the nature of the action to be
|
|
taken at the time when the countdown of the
|
|
upsShutdownAfterDelay and upsRebootWithDuration
|
|
objects reaches zero.
|
|
Setting this object to output(1) indicates that
|
|
shutdown requests should cause only the output of the
|
|
UPS to turn off. Setting this object to system(2)
|
|
indicates that shutdown requests will cause the entire
|
|
UPS system to turn off."
|
|
::= { dupsControl 1 }
|
|
|
|
dupsAutoReboot OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"In backup mode, the UPS may shutdown normally by SDA command,
|
|
dry-contact remote shutdown signal or low battery shutdown.
|
|
This command is used to determine the unit should restart or
|
|
not next time when the power restores"
|
|
::= { dupsControl 2 }
|
|
|
|
dupsShutdownAction OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"If the value is greater than 0 the UPS performs
|
|
shutdown action that defined by ShutdownType after
|
|
the seconds. 0, aborted."
|
|
::= { dupsControl 3 }
|
|
|
|
dupsRestartAction OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"UPS will restart after the indicated number of minutes.
|
|
-1, aborted."
|
|
::= { dupsControl 4 }
|
|
|
|
dupsSetOutletRelay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicate which outlet relay, from 1,2,3... ."
|
|
::= { dupsControl 5 }
|
|
|
|
dupsRelayOffDelay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Turn the relay off after the seconds. The relay was indicated
|
|
by SetOutletRelay."
|
|
::= { dupsControl 6 }
|
|
|
|
dupsRelayOnDelay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Turn the relay on after the minutes. The relay was indicated
|
|
by SetOutletRelay."
|
|
::= { dupsControl 7 }
|
|
|
|
dupsSmartShutdown OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Any value to initiate the Smart Shutdown for the UPS."
|
|
::= { dupsControl 8 }
|
|
|
|
dupsClearEnergy OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Any value to clear the energy record in the UPS."
|
|
::= { dupsControl 9 }
|
|
|
|
--
|
|
-- dups Configure group
|
|
--
|
|
dupsConfigBuzzerAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
alarm(1),
|
|
silence(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"UPS will keep silence but will alarm again when
|
|
next power event is occurred"
|
|
::= { dupsConfig 1 }
|
|
|
|
dupsConfigBuzzerState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enable(1),
|
|
disable(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"If it is disabled then the UPS is always muted."
|
|
::= { dupsConfig 2 }
|
|
|
|
dupsConfigSensitivity OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(1),
|
|
reduced(2),
|
|
low(3)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The seneitivity of the UPS to utility line
|
|
abnormalities or noises."
|
|
::= { dupsConfig 3 }
|
|
|
|
dupsConfigLowVoltageTransferPoint OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "Volt"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The minimum input line voltage allowed before the UPS
|
|
system transfers to battery backup."
|
|
::= { dupsConfig 4 }
|
|
|
|
dupsConfigHighVoltageTransferPoint OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "Volt"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The maximum line voltage allowed before the UPS
|
|
system transfers to battery backup."
|
|
::= { dupsConfig 5 }
|
|
|
|
dupsConfigUPSBootDelay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "Second"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Delay the UPS startup after power restores. The power
|
|
quality may not stable when power restores, this
|
|
feature let the UPS wait a period of time to startup
|
|
the system."
|
|
::= { dupsConfig 6 }
|
|
|
|
dupsConfigExternalBatteryPack OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicate the number of external battery pack."
|
|
::= { dupsConfig 7 }
|
|
|
|
dupsConfigSmartShutdownOSDelay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "Second"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The estimated operating system shutdown delay time for
|
|
Smart Shutdown."
|
|
::= { dupsConfig 8 }
|
|
|
|
dupsConfigSmartShutdownUPSDelay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "Second"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The estimated UPS shutdown delay time for
|
|
Smart Shutdown."
|
|
::= { dupsConfig 9 }
|
|
|
|
dupsConfigEconomicMode OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enable(1),
|
|
disable(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Used to enable or disable the economic mode."
|
|
::= { dupsConfig 10 }
|
|
|
|
--
|
|
-- dups Input group
|
|
--
|
|
dupsInputNumLines OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of input lines utilized in this device."
|
|
::= { dupsInput 1 }
|
|
|
|
dupsInputFrequency1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Hertz"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current input line 1 frequency to the UPS
|
|
system in 1/10 Hz. The value -1 indicates this UPS does
|
|
not support this item."
|
|
::= { dupsInput 2 }
|
|
|
|
dupsInputVoltage1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Volt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Input phase 1 voltage of the UPS system in 1/10 V.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsInput 3 }
|
|
|
|
dupsInputVoltage12 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Volt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Input line 1-2 voltage of the UPS system in 1/10 V.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsInput 4 }
|
|
|
|
dupsInputCurrent1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Amp"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Input line 1 current to the UPS system in 1/10 A.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsInput 5 }
|
|
|
|
dupsInputPower1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 Watt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Input line 1 power to the UPS system in 1 Watt.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsInput 6 }
|
|
|
|
dupsInputFrequency2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Hertz"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current input line 2 frequency to the UPS system
|
|
in 1/10 Hz.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsInput 7 }
|
|
|
|
dupsInputVoltage2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Volt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Input phase 2 voltage of the UPS system in 1/10 V.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsInput 8 }
|
|
|
|
dupsInputVoltage23 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Volt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Input line 2-3 voltage of the UPS system in 1/10 V.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsInput 9 }
|
|
|
|
dupsInputCurrent2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Amp"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Input line 2 current to the UPS system in 1/10 A.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsInput 10 }
|
|
|
|
dupsInputPower2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 Watt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Input line 2 power to the UPS system in 1 Watt.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsInput 11 }
|
|
|
|
dupsInputFrequency3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Hertz"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current input line 3 frequency to the UPS system
|
|
in 1/10 Hz.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsInput 12 }
|
|
|
|
dupsInputVoltage3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Volt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Input phase 3 voltage of the UPS system in 1/10 V.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsInput 13 }
|
|
|
|
dupsInputVoltage31 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Volt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Input line 3-1 voltage of the UPS system in 1/10 V.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsInput 14 }
|
|
|
|
dupsInputCurrent3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Amp"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Input line 3 current to the UPS system in 1/10 A.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsInput 15 }
|
|
|
|
dupsInputPower3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 Watt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Input line 3 power to the UPS system in 1 Watt.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsInput 16 }
|
|
|
|
dupsInputEnergy1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 kWh"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Input line 1 energy to the UPS system in 1 kWh.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsInput 17 }
|
|
|
|
dupsInputEnergy2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 kWh"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Input line 2 energy to the UPS system in 1 kWh.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsInput 18 }
|
|
|
|
dupsInputEnergy3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 kWh"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Input line 3 energy to the UPS system in 1 kWh.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsInput 19 }
|
|
|
|
dupsInputEnergyTotal OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 kWh"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The total Input energy to the UPS system in 1 kWh.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsInput 20 }
|
|
|
|
dupsInputLineFailCause OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
no(1),
|
|
outoftolvolt(2),
|
|
outoftolfreq(3),
|
|
utilityoff(4)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Cause of input outage."
|
|
::= { dupsInput 21 }
|
|
|
|
dupsInputBadStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
yes(1),
|
|
no(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Incorrect input voltage or frequency."
|
|
::= { dupsInput 22 }
|
|
|
|
--
|
|
-- dups Output group
|
|
--
|
|
dupsOutputSource OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(1),
|
|
battery(2),
|
|
bypass(3),
|
|
reducing(4),
|
|
boosting(5),
|
|
manualBypass(6),
|
|
other(7),
|
|
noOutput(8),
|
|
onEco(9)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present source of output power. The enumeration
|
|
noOutput(8) indicates that there is no source of output
|
|
power (and therefore no output power), for example,
|
|
the system has opened the output breaker."
|
|
::= { dupsOutput 1 }
|
|
|
|
dupsOutputFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Hertz"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present output frequency in 1/10 Hz.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsOutput 2 }
|
|
|
|
dupsOutputNumLines OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of output lines utilized in this device."
|
|
::= { dupsOutput 3 }
|
|
|
|
dupsOutputVoltage1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Volt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Output phase 1 voltage of the UPS system in 1/10 V.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsOutput 4 }
|
|
|
|
dupsOutputVoltage12 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Volt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Output line 1-2 voltage of the UPS system in 1/10 V.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsOutput 5 }
|
|
|
|
dupsOutputCurrent1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Amp"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Output line 1 current of the UPS system in 1/10 A.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsOutput 6 }
|
|
|
|
dupsOutputPower1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 Watt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Output line 1 active power of the UPS system in watts.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsOutput 7 }
|
|
|
|
dupsOutputLoad1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 Percent"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current UPS output line 1 load expressed in percent
|
|
of rated capacity.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsOutput 8 }
|
|
|
|
dupsOutputVoltage2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Volt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Output phase 2 voltage of the UPS system in 1/10 V.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsOutput 9 }
|
|
|
|
dupsOutputVoltage23 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Volt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Output line 2-3 voltage of the UPS system in 1/10 V.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsOutput 10 }
|
|
|
|
dupsOutputCurrent2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Amp"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Output line 2 current of the UPS system in 1/10 A.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsOutput 11 }
|
|
|
|
dupsOutputPower2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 Watt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Output line 2 active power of the UPS system in watts.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsOutput 12 }
|
|
|
|
dupsOutputLoad2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 Percent"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current UPS output line 2 load expressed in percent
|
|
of rated capacity.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsOutput 13 }
|
|
|
|
dupsOutputVoltage3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Volt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Output phase 3 voltage of the UPS system in 1/10 V.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsOutput 14 }
|
|
|
|
dupsOutputVoltage31 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Volt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Output line 3-1 voltage of the UPS system in 1/10 V.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsOutput 15 }
|
|
|
|
dupsOutputCurrent3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Amp"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Output line 3 current of the UPS system in 1/10 A.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsOutput 16 }
|
|
|
|
dupsOutputPower3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 Watt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Output line 3 active power of the UPS system in watts.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsOutput 17 }
|
|
|
|
dupsOutputLoad3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 Percent"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current UPS output line 3 load expressed in percent
|
|
of rated capacity.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsOutput 18 }
|
|
|
|
dupsOutputTotalActivePower OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 kW"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The total output active power of the UPS system in 0.1 kW.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsOutput 19 }
|
|
|
|
dupsOutputTotalApparentPower OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 kVA"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The total output apparent power of the UPS system in 0.1 kVA.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsOutput 20 }
|
|
|
|
dupsOutputTotalPowerFactor OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 Percent"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The total output power factor of the UPS system.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsOutput 21 }
|
|
|
|
dupsOutputEnergy1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 kWh"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS output line 1 energy in kWh.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsOutput 22 }
|
|
|
|
dupsOutputEnergy2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 kWh"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS output line 2 energy in kWh.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsOutput 23 }
|
|
|
|
dupsOutputEnergy3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 kWh"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS output line 3 energy in kWh.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsOutput 24 }
|
|
|
|
dupsOutputEnergyTotal OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 kWh"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS total output energy in kWh.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsOutput 25 }
|
|
|
|
--
|
|
-- dups Bypass group
|
|
--
|
|
dupsBypassFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Hertz"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present bypass frequency in 1/10 Hz.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsBypass 1 }
|
|
|
|
dupsBypassNumLines OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of bypass lines utilized in this device."
|
|
::= { dupsBypass 2 }
|
|
|
|
dupsBypassVoltage1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Volt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The bypass phase 1 voltage of the UPS system in 1/10 V.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsBypass 3 }
|
|
|
|
dupsBypassVoltage12 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Volt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The bypass line 1-2 voltage of the UPS system in 1/10 V.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsBypass 4 }
|
|
|
|
dupsBypassCurrent1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Amp"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The bypass line 1 current of the UPS system in 1/10 A.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsBypass 5 }
|
|
|
|
dupsBypassPower1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 Watt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The bypass line 1 real power of the UPS system in watts.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsBypass 6 }
|
|
|
|
dupsBypassVoltage2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Volt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The bypass phase 2 voltage of the UPS system in 1/10 V.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsBypass 7 }
|
|
|
|
dupsBypassVoltage23 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Volt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The bypass line 2-3 voltage of the UPS system in 1/10 V.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsBypass 8 }
|
|
|
|
dupsBypassCurrent2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Amp"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The bypass line 2 current of the UPS system in 1/10 A.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsBypass 9 }
|
|
|
|
dupsBypassPower2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 Watt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The bypass line 2 real power of the UPS system in watts.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsBypass 10 }
|
|
|
|
dupsBypassVoltage3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Volt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The bypass phase 3 voltage of the UPS system in 1/10 V.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsBypass 11 }
|
|
|
|
dupsBypassVoltage31 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Volt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The bypass line 3-1 voltage of the UPS system in 1/10 V.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsBypass 12 }
|
|
|
|
dupsBypassCurrent3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Amp"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The bypass line 3 current of the UPS system in 1/10 A.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsBypass 13 }
|
|
|
|
dupsBypassPower3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 Watt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The bypass line 3 real power of the UPS system in watts.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsBypass 14 }
|
|
|
|
dupsBypassSTSTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 Degree Celsius"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The measurement of bypass STS temperature.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsBypass 15 }
|
|
|
|
--
|
|
-- dups Battery group
|
|
--
|
|
dupsBatteryCondition OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
good(1),
|
|
weak(2),
|
|
replace(3)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The indication of the capacity remaining in the UPS
|
|
system's batteries when AC normal."
|
|
::= { dupsBattery 1 }
|
|
|
|
dupsBatteryStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
ok(1),
|
|
low(2),
|
|
depleted(3)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The indication of the capacity remaining in the UPS
|
|
system's batteries when AC failed. A value of ok
|
|
indicates that the remaining run-time is greater than
|
|
upsConfigLowBattTime. A value of low indicates
|
|
that the remaining battery run-time is less than or
|
|
equal to upsConfigLowBattTime. A value of
|
|
depleted indicates that the UPS will be unable
|
|
to sustain the present load when and if the utility
|
|
power is lost (including the possibility that the
|
|
utility power is currently absent and the UPS is
|
|
unable to sustain the output)."
|
|
::= { dupsBattery 2 }
|
|
|
|
dupsBatteryCharge OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
floating(1),
|
|
charging(2),
|
|
resting(3),
|
|
discharging(4)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Representing the battery charge status."
|
|
::= { dupsBattery 3 }
|
|
|
|
dupsSecondsOnBattery OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 Second"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"If the unit is on battery power, the elapsed time
|
|
since the UPS last switched to battery power, or the
|
|
time since the network management subsystem was last
|
|
restarted, whichever is less. Zero shall be returned
|
|
if the unit is not on battery power."
|
|
::= { dupsBattery 4 }
|
|
|
|
dupsBatteryEstimatedTime OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 Minute"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Estimated time from backup to low battery shutdown."
|
|
::= { dupsBattery 5 }
|
|
|
|
dupsBatteryPosVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Volt DC"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present positive battery voltage
|
|
in 1/10 V."
|
|
::= { dupsBattery 6 }
|
|
|
|
dupsBatteryNegVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "-0.1 Volt DC"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present negative battery voltage
|
|
in -1/10 V."
|
|
::= { dupsBattery 7 }
|
|
|
|
dupsBatteryPosCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Amp DC"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present positive battery current in 1/10 A."
|
|
::= { dupsBattery 8 }
|
|
|
|
dupsBatteryNegCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Amp DC"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present negative battery current in 1/10 A."
|
|
::= { dupsBattery 9 }
|
|
|
|
dupsBatteryPosCapacity OBJECT-TYPE
|
|
SYNTAX INTEGER (0..100)
|
|
UNITS "1 Percent"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An estimate of the positive battery charge remaining
|
|
expressed as a percent of full charge."
|
|
::= { dupsBattery 10 }
|
|
|
|
dupsBatteryNegCapacity OBJECT-TYPE
|
|
SYNTAX INTEGER (0..100)
|
|
UNITS "1 Percent"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An estimate of the negative battery charge remaining
|
|
expressed as a percent of full charge."
|
|
::= { dupsBattery 11 }
|
|
|
|
dupsTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 Degrees Centigrade"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The measurement of internal temperature in the UPS."
|
|
::= { dupsBattery 12 }
|
|
|
|
dupsLastReplaceDate OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..8))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The last battery replacement date. The format is YYYYMMDD."
|
|
::= { dupsBattery 13 }
|
|
|
|
dupsNextReplaceDate OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..8))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The next battery replacement date. The format is YYYYMMDD."
|
|
::= { dupsBattery 14 }
|
|
|
|
dupsBatteryBreaker OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
open(1),
|
|
close(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicate the battery breaker status."
|
|
::= { dupsBattery 15 }
|
|
|
|
dupsBatteryCab1Tempurature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 Degrees Centigrade"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Temperature of battery cabnet 1."
|
|
::= { dupsBattery 16 }
|
|
|
|
dupsBatteryCab2Tempurature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 Degrees Centigrade"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Temperature of battery cabnet 2."
|
|
::= { dupsBattery 17 }
|
|
|
|
dupsBatteryCab3Tempurature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 Degrees Centigrade"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Temperature of battery cabnet 3."
|
|
::= { dupsBattery 18 }
|
|
|
|
dupsBatteryCab4Tempurature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 Degrees Centigrade"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Temperature of battery cabnet 4."
|
|
::= { dupsBattery 19 }
|
|
|
|
--
|
|
-- dups Test group
|
|
--
|
|
dupsTestType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
abort(1),
|
|
generalTest(2),
|
|
batteryTest(3),
|
|
testFor10sec(4),
|
|
testUntilBattlow(5)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Perform the UPS Test procedure."
|
|
::= { dupsTest 1 }
|
|
|
|
dupsTestResultsSummary OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noTestsInitiated(1),
|
|
donePass(2),
|
|
inProgress(3),
|
|
generalTestFail(4),
|
|
batteryTestFail(5),
|
|
deepBatteryTestFail(6)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The results of the current or last UPS diagnostics
|
|
test performed. The values for donePass(1),
|
|
generalTestFail(3), and batteryTestFail(4) indicate that the
|
|
test completed either successfully, with a warning, or
|
|
with an error, respectively.Tests which have not yet
|
|
concluded are indicated by inProgress(2). The value
|
|
noTestsInitiated(1) indicates that no previous test
|
|
results are available."
|
|
::= { dupsTest 2 }
|
|
|
|
dupsTestResultsDetail OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..255))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Additional information about upsTestResultsSummary.
|
|
If no additional information available, a zero length
|
|
string is returned."
|
|
::= { dupsTest 3 }
|
|
|
|
dupsGeneratorTest OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
abort(1),
|
|
start(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Perform the Generator Test procedure."
|
|
::= { dupsTest 4 }
|
|
|
|
dupsGeneratorTestStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
inProgress(1),
|
|
none(2),
|
|
inhibitTest(3),
|
|
abnormallyTerminate(4),
|
|
byInstruction(5),
|
|
byTimeout(6)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The results of the current or last generator diagnostics
|
|
test performed.The values for None(2), InhibitTest(3),
|
|
AbnormallyTerminate(4), ByInstruction(5), and ByTimeout(6)
|
|
indicate that the tye of termination test. Tests which have
|
|
not yet concluded are indicated by inProgress(1)"
|
|
::= { dupsTest 5 }
|
|
|
|
--
|
|
-- dups Alarm group
|
|
--
|
|
dupsAlarmDisconnect OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicate the communication of the UPS is connected
|
|
or disconnect?"
|
|
::= { dupsAlarm 1 }
|
|
|
|
dupsAlarmInputOutOfRange OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Representing the input power is out of tolerance.
|
|
This item is used to indicate the input power fail,
|
|
a test condition should not set this item on."
|
|
::= { dupsAlarm 2 }
|
|
|
|
dupsAlarmBatteryLow OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Are the UPS batteries low?"
|
|
::= { dupsAlarm 3 }
|
|
|
|
dupsAlarmLoadOnBypass OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the UPS load on bypass?"
|
|
::= { dupsAlarm 4 }
|
|
|
|
dupsAlarmOther OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicate there is an alarm detected but which
|
|
is not defined here."
|
|
::= { dupsAlarm 5 }
|
|
|
|
dupsAlarmBatteryGroundFault OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"To indicate the battery ground fault has
|
|
been detected."
|
|
::= { dupsAlarm 6 }
|
|
|
|
dupsAlarmTestInProgress OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the UPS test in progress?"
|
|
::= { dupsAlarm 7 }
|
|
|
|
dupsAlarmBatteryTestFail OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the UPS test fail?"
|
|
::= { dupsAlarm 8 }
|
|
|
|
dupsAlarmFuseFailure OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The failure of one or more fuses has been detected."
|
|
::= { dupsAlarm 9 }
|
|
|
|
dupsAlarmOutputOverload OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The output load exceeds the UPS output capacity."
|
|
::= { dupsAlarm 10 }
|
|
|
|
dupsAlarmInverterAbnormal OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Representing the inverter fail alarm."
|
|
::= { dupsAlarm 11 }
|
|
|
|
dupsAlarmLoadOnReserve OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the UPS load on reserve?"
|
|
::= { dupsAlarm 12 }
|
|
|
|
dupsAlarmTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Representing one of the temperature sensors has
|
|
been determined its value is out of the limits."
|
|
::= { dupsAlarm 13 }
|
|
|
|
dupsAlarmBypassOutOfRange OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The bypass power is out of range."
|
|
::= { dupsAlarm 14 }
|
|
|
|
dupsAlarmStandby OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS system is in the standby state."
|
|
::= { dupsAlarm 15 }
|
|
|
|
dupsAlarmChargerFail OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An incorrected problem has been detected
|
|
within the UPS charger subsystem"
|
|
::= { dupsAlarm 16 }
|
|
|
|
dupsAlarmFanFail OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The failure of one or more fans in the UPS
|
|
has been detected."
|
|
::= { dupsAlarm 17 }
|
|
|
|
dupsAlarmEconomicMode OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS is working in the economic mode
|
|
(act like an off-line UPS)."
|
|
::= { dupsAlarm 18 }
|
|
|
|
dupsAlarmOutputOff OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"UPS output is turned off."
|
|
::= { dupsAlarm 19 }
|
|
|
|
dupsAlarmSmartShutdown OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates whether the Smart Shutdown is in progress."
|
|
::= { dupsAlarm 20 }
|
|
|
|
dupsAlarmEmergencyPowerOff OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Representing the UPS is shutdown due to the
|
|
Emergency Power Off button is pressed."
|
|
::= { dupsAlarm 21 }
|
|
|
|
dupsAlarmUPSShutdown OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS has been shutdown including remote and
|
|
fault shutdown."
|
|
::= { dupsAlarm 22 }
|
|
|
|
dupsAlarmEPO OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Representing the UPS is shutdown due to the
|
|
Emergency Power Off button is pressed."
|
|
::= { dupsAlarm 23 }
|
|
|
|
dupsAlarmOutVoltOverLimit OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"To indicate the output voltage is over limit."
|
|
::= { dupsAlarm 24 }
|
|
|
|
dupsAlarmOutVoltUnderLimit OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"To indicate the output voltage is under limit."
|
|
::= { dupsAlarm 25 }
|
|
|
|
dupsAlarmPowerModule OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"To indicate there is at least one alarm from power module."
|
|
::= { dupsAlarm 26 }
|
|
|
|
dupsAlarmOutputBreaker OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
open(1),
|
|
close(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"To indicate the output breaker is detected open or close."
|
|
::= { dupsAlarm 27 }
|
|
|
|
dupsAlarmOutletBank1Breaker OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
open(1),
|
|
close(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"To indicate the outlet bank-1 breaker is detected open or close."
|
|
::= { dupsAlarm 28 }
|
|
|
|
dupsAlarmOutletBank2Breaker OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
open(1),
|
|
close(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"To indicate the outlet bank-2 breaker is detected open or close."
|
|
::= { dupsAlarm 29 }
|
|
|
|
dupsAlarmOutletBank3Breaker OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
open(1),
|
|
close(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"To indicate the outlet bank-3 breaker is detected open or close."
|
|
::= { dupsAlarm 30 }
|
|
|
|
dupsAlarmOutletBank4Breaker OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
open(1),
|
|
close(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"To indicate the outlet bank-4 breaker is detected open or close."
|
|
::= { dupsAlarm 31 }
|
|
|
|
dupsAlarmSummary OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
none(1),
|
|
informational(2),
|
|
warning(3),
|
|
alarm(4)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"To indicate the alarm level for the UPS."
|
|
::= { dupsAlarm 32 }
|
|
|
|
dupsAlarmRedundancyLoss OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"To indicate the capacity of redundancy lost in a modular UPS."
|
|
::= { dupsAlarm 33 }
|
|
|
|
dupsAlarmPhaseAsynchronous OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
asynchronous(1),
|
|
synchronous(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"To indicate the Phase is detected asynchronous or synchronous."
|
|
::= { dupsAlarm 34 }
|
|
|
|
dupsAlarmRectifierAbnormal OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
alarm(1),
|
|
normal(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"To indicate the Rectifier is detected alarm or normal."
|
|
::= { dupsAlarm 35 }
|
|
|
|
dupsAlarmBypassBreakerOpen OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
open(1),
|
|
close(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"To indicate the bypass breaker is detected open or close."
|
|
::= { dupsAlarm 36 }
|
|
|
|
dupsAlarmMainInputBreakerOpen OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
open(1),
|
|
close(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"To indicate the main input breaker is detected open or close."
|
|
::= { dupsAlarm 37 }
|
|
|
|
dupsAlarmManualBypassBreaker OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
open(1),
|
|
close(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"To indicate the manual bypass breaker is detected open or close."
|
|
::= { dupsAlarm 38 }
|
|
|
|
--
|
|
-- dups Power Module group
|
|
--
|
|
|
|
dupsPMBypassInputAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the bypass voltage/frequency is abnormal."
|
|
::= { dupsPowerModule 1 }
|
|
|
|
dupsPMBypassPhaseAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the bypass phase sequence is abnormal."
|
|
::= { dupsPowerModule 2 }
|
|
|
|
dupsPMBypassSTSOverloadAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the bypass STS overload."
|
|
::= { dupsPowerModule 3 }
|
|
|
|
dupsPMBypassSTSOverTempAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the bypass STS over temperature."
|
|
::= { dupsPowerModule 4 }
|
|
|
|
dupsPMBypassSTSFailAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the bypass STS fail."
|
|
::= { dupsPowerModule 5 }
|
|
|
|
dupsPMTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DupsPMEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of power module table entries."
|
|
::= { dupsPowerModule 6 }
|
|
|
|
dupsPMEntry OBJECT-TYPE
|
|
SYNTAX DupsPMEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a particular
|
|
power module."
|
|
INDEX { dupsPMID }
|
|
::= { dupsPMTable 1 }
|
|
|
|
DupsPMEntry ::= SEQUENCE {
|
|
dupsPMID INTEGER,
|
|
dupsPMPFCTemp INTEGER,
|
|
dupsPMINVTemp INTEGER,
|
|
dupsPMINVTempR INTEGER,
|
|
dupsPMINVTempS INTEGER,
|
|
dupsPMINVTempT INTEGER,
|
|
dupsPMINVVolt1 INTEGER,
|
|
dupsPMINVVolt2 INTEGER,
|
|
dupsPMINVVolt3 INTEGER,
|
|
dupsPMStsNotExist INTEGER,
|
|
dupsPMStsOff INTEGER,
|
|
dupsPMStsRepair INTEGER,
|
|
dupsPMStsFaultShutdown INTEGER,
|
|
dupsPMStsPFCFuseFail INTEGER,
|
|
dupsPMStsPFCOverTempWarning INTEGER,
|
|
dupsPMStsPFCOverTempShutdown INTEGER,
|
|
dupsPMStsPFCOverVoltWarning INTEGER,
|
|
dupsPMStsPFCOverVoltShutdown INTEGER,
|
|
dupsPMStsPFCUnderVoltWarning INTEGER,
|
|
dupsPMStsPFCUnderVoltShutdown INTEGER,
|
|
dupsPMStsPFCGeneralFault INTEGER,
|
|
dupsPMStsPFCFanFail INTEGER,
|
|
dupsPMStsPFCCurrentLimit INTEGER,
|
|
dupsPMStsPFCOff INTEGER,
|
|
dupsPMStsPFCInnerCommFail INTEGER,
|
|
dupsPMStsPFCNotCalibrated INTEGER,
|
|
dupsPMStsINVFuseFail INTEGER,
|
|
dupsPMStsINVOverTempWarning INTEGER,
|
|
dupsPMStsINVOverTempShutdown INTEGER,
|
|
dupsPMStsINVFanFail INTEGER,
|
|
dupsPMStsINVShortCircuit INTEGER,
|
|
dupsPMStsINVSTSFail INTEGER,
|
|
dupsPMStsINVCircuitFail INTEGER,
|
|
dupsPMStsINVOverVolt INTEGER,
|
|
dupsPMStsINVOverload INTEGER,
|
|
dupsPMStsINVInnerCommFail INTEGER,
|
|
dupsPMStsINVEPO INTEGER,
|
|
dupsPMStsINVParallelCommFail INTEGER,
|
|
dupsPMStsINVParallelFail INTEGER,
|
|
dupsPMStsINVSTSOn INTEGER,
|
|
dupsPMStsINVNotCalibrated INTEGER,
|
|
dupsPMStsChargerFail INTEGER,
|
|
dupsPMSummaryStatus INTEGER,
|
|
dupsPMPFCTempR INTEGER,
|
|
dupsPMPFCTempS INTEGER,
|
|
dupsPMPFCTempT INTEGER
|
|
}
|
|
|
|
dupsPMID OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The power module identifier."
|
|
::= { dupsPMEntry 1 }
|
|
|
|
dupsPMPFCTemp OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 Degree Celsius"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The power module PFC temperature."
|
|
::= { dupsPMEntry 2 }
|
|
|
|
dupsPMINVTemp OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 Degree Celsius"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The power module inverter temperature."
|
|
::= { dupsPMEntry 3 }
|
|
|
|
dupsPMINVTempR OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 Degree Celsius"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The power module inverter-R temperature."
|
|
::= { dupsPMEntry 4 }
|
|
|
|
dupsPMINVTempS OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 Degree Celsius"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The power module inverter-S temperature."
|
|
::= { dupsPMEntry 5 }
|
|
|
|
dupsPMINVTempT OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 Degree Celsius"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The power module inverter-T temperature."
|
|
::= { dupsPMEntry 6 }
|
|
|
|
dupsPMINVVolt1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Volt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The inverter line 1 voltage of the power module in 1/10 V."
|
|
::= { dupsPMEntry 7 }
|
|
|
|
dupsPMINVVolt2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Volt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The inverter line 2 voltage of the power module in 1/10 V."
|
|
::= { dupsPMEntry 8 }
|
|
|
|
dupsPMINVVolt3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Volt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The inverter line 3 voltage of the power module in 1/10 V."
|
|
::= { dupsPMEntry 9 }
|
|
|
|
dupsPMStsNotExist OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
notExist(1),
|
|
existed(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the power module is existed or not?"
|
|
::= { dupsPMEntry 10 }
|
|
|
|
dupsPMStsOff OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
pmOff(1),
|
|
pmOn(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the power module is on or off?"
|
|
::= { dupsPMEntry 11 }
|
|
|
|
dupsPMStsRepair OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
repair(1),
|
|
notRepair(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the power module is in repair mode or not?"
|
|
::= { dupsPMEntry 12 }
|
|
|
|
dupsPMStsFaultShutdown OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
alarm(1),
|
|
normal(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the power module status of fault shutdown."
|
|
::= { dupsPMEntry 13 }
|
|
|
|
dupsPMStsPFCFuseFail OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
alarm(1),
|
|
normal(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the power module PFC fuse open or close?"
|
|
::= { dupsPMEntry 14 }
|
|
|
|
dupsPMStsPFCOverTempWarning OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
warning(1),
|
|
normal(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the power module PFC over temperature warning."
|
|
::= { dupsPMEntry 15 }
|
|
|
|
dupsPMStsPFCOverTempShutdown OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
alarm(1),
|
|
normal(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the power module PFC over temperature shutdown."
|
|
::= { dupsPMEntry 16 }
|
|
|
|
dupsPMStsPFCOverVoltWarning OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
warning(1),
|
|
normal(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the power module PFC over voltage warning."
|
|
::= { dupsPMEntry 17 }
|
|
|
|
dupsPMStsPFCOverVoltShutdown OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
alarm(1),
|
|
normal(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the power module PFC over voltage shutdown."
|
|
::= { dupsPMEntry 18 }
|
|
|
|
dupsPMStsPFCUnderVoltWarning OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
warning(1),
|
|
normal(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the power module PFC under voltage warning."
|
|
::= { dupsPMEntry 19 }
|
|
|
|
dupsPMStsPFCUnderVoltShutdown OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
alarm(1),
|
|
normal(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the power module PFC under voltage shutdown."
|
|
::= { dupsPMEntry 20 }
|
|
|
|
dupsPMStsPFCGeneralFault OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
alarm(1),
|
|
normal(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the power module PFC genreal fault."
|
|
::= { dupsPMEntry 21 }
|
|
|
|
dupsPMStsPFCFanFail OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
alarm(1),
|
|
normal(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the power module PFC fan fail."
|
|
::= { dupsPMEntry 22 }
|
|
|
|
dupsPMStsPFCCurrentLimit OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
alarm(1),
|
|
normal(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the power module PFC output current limit."
|
|
::= { dupsPMEntry 23 }
|
|
|
|
dupsPMStsPFCOff OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
alarm(1),
|
|
normal(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the power module PFC off."
|
|
::= { dupsPMEntry 24 }
|
|
|
|
dupsPMStsPFCInnerCommFail OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
alarm(1),
|
|
normal(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the power module PFC inner communication fail."
|
|
::= { dupsPMEntry 25 }
|
|
|
|
dupsPMStsPFCNotCalibrated OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
alarm(1),
|
|
normal(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the power module PFC is not calibrated."
|
|
::= { dupsPMEntry 26 }
|
|
|
|
dupsPMStsINVFuseFail OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
open(1),
|
|
close(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the power module Inverter fuse open or close?"
|
|
::= { dupsPMEntry 27 }
|
|
|
|
dupsPMStsINVOverTempWarning OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
warning(1),
|
|
normal(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the power module Inverter over temperature warning."
|
|
::= { dupsPMEntry 28 }
|
|
|
|
dupsPMStsINVOverTempShutdown OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
alarm(1),
|
|
normal(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the power module Inverter over temperature shutdown."
|
|
::= { dupsPMEntry 29 }
|
|
|
|
dupsPMStsINVFanFail OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
alarm(1),
|
|
normal(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the power module Inverter fan fail."
|
|
::= { dupsPMEntry 30 }
|
|
|
|
dupsPMStsINVShortCircuit OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
alarm(1),
|
|
normal(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the power module Inverter short circuit."
|
|
::= { dupsPMEntry 31 }
|
|
|
|
dupsPMStsINVSTSFail OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
alarm(1),
|
|
normal(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the power module Inverter STS fail."
|
|
::= { dupsPMEntry 32 }
|
|
|
|
dupsPMStsINVCircuitFail OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
alarm(1),
|
|
normal(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the power module Inverter circuit fail shutdown."
|
|
::= { dupsPMEntry 33 }
|
|
|
|
dupsPMStsINVOverVolt OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
alarm(1),
|
|
normal(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the power module Inverter over voltage shutdown."
|
|
::= { dupsPMEntry 34 }
|
|
|
|
dupsPMStsINVOverload OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
alarm(1),
|
|
normal(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the power module Inverter overload."
|
|
::= { dupsPMEntry 35 }
|
|
|
|
dupsPMStsINVInnerCommFail OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
alarm(1),
|
|
normal(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the power module Inverter inner communication fail."
|
|
::= { dupsPMEntry 36 }
|
|
|
|
dupsPMStsINVEPO OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
alarm(1),
|
|
normal(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the power module Inverter EPO shutdown."
|
|
::= { dupsPMEntry 37 }
|
|
|
|
dupsPMStsINVParallelCommFail OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
alarm(1),
|
|
normal(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the power module Inverter parallel communication fail."
|
|
::= { dupsPMEntry 38 }
|
|
|
|
dupsPMStsINVParallelFail OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
alarm(1),
|
|
normal(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the power module Inverter parallel fail."
|
|
::= { dupsPMEntry 39 }
|
|
|
|
dupsPMStsINVSTSOn OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the status of power module Inverter state."
|
|
::= { dupsPMEntry 40 }
|
|
|
|
dupsPMStsINVNotCalibrated OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
alarm(1),
|
|
normal(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the power module Inverter is not calibrated."
|
|
::= { dupsPMEntry 41 }
|
|
|
|
dupsPMStsChargerFail OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
alarm(1),
|
|
normal(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the power module Charger fail."
|
|
::= { dupsPMEntry 42 }
|
|
|
|
dupsPMSummaryStatus OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
abnormal(1),
|
|
normal(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The power module summary status."
|
|
::= { dupsPMEntry 43 }
|
|
|
|
dupsPMPFCTempR OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 Degree Celsius"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The power module pfc-R temperature."
|
|
::= { dupsPMEntry 44 }
|
|
|
|
dupsPMPFCTempS OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 Degree Celsius"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The power module pfc-S temperature."
|
|
::= { dupsPMEntry 45 }
|
|
|
|
dupsPMPFCTempT OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 Degree Celsius"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The power module pfc-T temperature."
|
|
::= { dupsPMEntry 46 }
|
|
|
|
--
|
|
-- dups Trap Args
|
|
--
|
|
dupsDescription OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"This OID is used for traps to send with a string argument.
|
|
A get of this OID will return an empty string."
|
|
::= { dupsTrapArgs 1 }
|
|
|
|
dupsTimeTicks OBJECT-TYPE
|
|
SYNTAX TimeTicks
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"This OID is used for traps to send with a TimeTicks argument.
|
|
A get of this OID will return 0."
|
|
::= { dupsTrapArgs 2 }
|
|
|
|
--
|
|
-- dups Parallel group
|
|
--
|
|
dupsParallelRatingVA OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 VA"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The summary rating VA to the parallel UPSs system."
|
|
::= { dupsParallel 1 }
|
|
|
|
dupsParallelRatingPower OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 Watt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The summary rating power to the parallel UPSs system."
|
|
::= { dupsParallel 2 }
|
|
|
|
dupsParallelInCurrent1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Amp"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The summary input line 1 current to the parallel UPSs system in 1/10 A.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsParallel 3 }
|
|
|
|
dupsParallelInCurrent2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Amp"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The summary input line 2 current to the parallel UPSs system in 1/!0 A.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsParallel 4 }
|
|
|
|
dupsParallelInCurrent3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Amp"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The summary input line 3 current to the parallel UPSs system in 1/!0 A.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsParallel 5 }
|
|
|
|
dupsParallelOutCurrent1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Amp"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The summary output line 1 current to the parallel UPSs system in 1/10 A.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsParallel 6 }
|
|
|
|
dupsParallelOutCurrent2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Amp"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The summary output line 2 current to the parallel UPSs system in 1/10 A.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsParallel 7 }
|
|
|
|
dupsParallelOutCurrent3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Amp"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The summary output line 3 current to the parallel UPSs system in 1/10 A.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsParallel 8 }
|
|
|
|
dupsParallelOutPower1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 Watt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The summary output line 1 power to the parallel UPSs system.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsParallel 9 }
|
|
|
|
dupsParallelOutPower2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 Watt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The summary output line 2 power to the parallel UPSs system.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsParallel 10 }
|
|
|
|
dupsParallelOutPower3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 Watt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The summary output line 3 power to the parallel UPSs system.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsParallel 11 }
|
|
|
|
dupsParallelInEnergy1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 kWh"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The summary input line 1 energy to the parallel UPSs system.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsParallel 12 }
|
|
|
|
dupsParallelInEnergy2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 kWh"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The summary input line 2 energy to the parallel UPSs system.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsParallel 13 }
|
|
|
|
dupsParallelInEnergy3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 kWh"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The summary input line 3 energy to the parallel UPSs system.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsParallel 14 }
|
|
|
|
dupsParallelInEnergyTotal OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 kWh"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The summary total input energy to the parallel UPSs system.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsParallel 15 }
|
|
|
|
dupsParallelOutEnergy1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 kWh"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The summary output line 1 energy to the parallel UPSs system.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsParallel 16 }
|
|
|
|
dupsParallelOutEnergy2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 kWh"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The summary output line 2 energy to the parallel UPSs system.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsParallel 17 }
|
|
|
|
dupsParallelOutEnergy3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 kWh"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The summary output line 3 energy to the parallel UPSs system.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsParallel 18 }
|
|
|
|
dupsParallelOutEnergyTotal OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1 kWh"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The summary total output energy to the parallel UPSs system.
|
|
The value -1 indicates this UPS does not support this item."
|
|
::= { dupsParallel 19 }
|
|
|
|
--
|
|
-- dups Integrated group
|
|
--
|
|
dupsIntegratedParallel OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
parallel(1),
|
|
noParallel(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Multiple frame with the same group present."
|
|
::= { dupsIntegrated 1 }
|
|
|
|
dupsIntegratedDryInput1 OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
active(1),
|
|
inactive(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Dry1 Input state."
|
|
::= { dupsIntegrated 2 }
|
|
|
|
dupsIntegratedDryInput2 OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
active(1),
|
|
inactive(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Dry2 Input state."
|
|
::= { dupsIntegrated 3 }
|
|
|
|
dupsIntegratedDryInput3 OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
active(1),
|
|
inactive(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Dry3 Input state."
|
|
::= { dupsIntegrated 4 }
|
|
|
|
dupsIntegratedDryInput4 OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
active(1),
|
|
inactive(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Dry4 Input state."
|
|
::= { dupsIntegrated 5 }
|
|
|
|
|
|
--
|
|
-- dups Trap group
|
|
--
|
|
|
|
dupsCommunicationLost TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"SEVER: Communication with the UPS failed."
|
|
::= 1
|
|
|
|
dupsCommunicationEstablished TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"INFORMATION: Communication with the UPS reestablished."
|
|
::= 2
|
|
|
|
dupsPowerFail TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"WARNING: Power failed! The UPS is operating on battery power."
|
|
::= 3
|
|
|
|
dupsPowerRestored TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"INFORMATION: Power restored! The utility power restored."
|
|
::= 4
|
|
|
|
dupsLowBattery TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"SEVER: The UPS batteries are low and will soon be exhausted."
|
|
::= 5
|
|
|
|
dupsReturnFromLowBattery TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS has returned from a low battery condition."
|
|
::= 6
|
|
|
|
dupsLoadOnBypass TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"SEVER: The UPS loads on bypass."
|
|
::= 7
|
|
|
|
dupsNoLongerLoadOnBypass TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS is not on bypass mode."
|
|
::= 8
|
|
|
|
dupsUPSFault TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"SEVER: A general fault caused in the UPS."
|
|
::= 9
|
|
|
|
dupsReturnFromUPSFault TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS is returned from general fault."
|
|
::= 10
|
|
|
|
dupsBatteryGroundFault TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"SEVER: The UPS battery ground fault."
|
|
::= 11
|
|
|
|
dupsNoLongerBatteryFault TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS recovered from battery ground fault."
|
|
::= 12
|
|
|
|
dupsTestInProgress TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS test in progress."
|
|
::= 13
|
|
|
|
dupsBatteryTestFail TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"SEVER: The UPS test fail."
|
|
::= 14
|
|
|
|
dupsFuseFailure TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"SEVER: The UPS fuse failed."
|
|
::= 15
|
|
|
|
dupsFuseRecovered TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS fuse recovered."
|
|
::= 16
|
|
|
|
dupsOutputOverload TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"SEVER: The UPS overload!."
|
|
::= 17
|
|
|
|
dupsNoLongerOverload TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"INFORMATION: Recovered from UPS overload."
|
|
::= 18
|
|
|
|
dupsInverterAbnormal TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"SEVER: The UPS inverter abnormal."
|
|
::= 19
|
|
|
|
dupsInverterRecovered TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"INFORMATION: Recovered from UPS inverter abnormal."
|
|
::= 20
|
|
|
|
dupsSmartShutdownInit TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"SEVER: Smart Shutdown is initiated."
|
|
::= 21
|
|
|
|
dupsCancelShutdown TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"INFORMATION: Cancel UPS Shutdown."
|
|
::= 22
|
|
|
|
dupsTestCompleted TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"INFORMATION: This trap is sent upon completion of a UPS diagnostic test."
|
|
::= 23
|
|
|
|
dupsEPOON TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"INFORMATION: This trap is sent when emergency power off is on."
|
|
::= 24
|
|
|
|
dupsEPOOFF TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"INFORMATION: This trap is sent when UPS recover from emergency power off."
|
|
::= 25
|
|
|
|
dupsTemperatureAlarm TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"SEVER: This trap is sent when the UPS temperature out of range."
|
|
::= 26
|
|
|
|
dupsTemperatureNormal TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"INFORMATION: This trap is sent when UPS temperature back to normal."
|
|
::= 27
|
|
|
|
dupsBattReplace TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"WARNING: The battery needs to be replaced."
|
|
::= 28
|
|
|
|
dupsReturnFromBattReplace TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS recovered from battery replacement."
|
|
::= 29
|
|
|
|
dupsOutputOff TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"SEVER: Indicate the UPS output is turned off."
|
|
::= 30
|
|
|
|
dupsReturnFromOutputOff TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS recovered from output off."
|
|
::= 31
|
|
|
|
dupsShutdown TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"SEVER: The UPS has been shutdown including remote and fault shutdown."
|
|
::= 32
|
|
|
|
dupsReturnFromShutdown TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS recovered from shutdown."
|
|
::= 33
|
|
|
|
dupsChargerFail TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"SEVER: An incorrected problem has been detected within the UPS charger subsystem."
|
|
::= 34
|
|
|
|
dupsReturnFromChargerFail TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS recovered from charger fail."
|
|
::= 35
|
|
|
|
dupsOnStandby TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"SEVER: The UPS system is in the standby state."
|
|
::= 36
|
|
|
|
dupsReturnFromStandby TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS no longer on standby mode."
|
|
::= 37
|
|
|
|
dupsFanFail TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"SEVER: The failure of one or more fans in the UPS has been detected."
|
|
::= 38
|
|
|
|
dupsReturnFromFanFail TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS recover from fan fail."
|
|
::= 39
|
|
|
|
dupsOnEconomic TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS is working in the economic mode (act like an off-line UPS)."
|
|
::= 40
|
|
|
|
dupsReturnFromEconomic TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS no longer on economic mode."
|
|
::= 41
|
|
|
|
dupsPowerModuleFail TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"INFORMATION: One of the power modules is detected failed."
|
|
::= 42
|
|
|
|
dupsReturnFromPowerModuleFail TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"INFORMATION: The power module is back to normal."
|
|
::= 43
|
|
|
|
dupsOutputBreakerOff TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"INFORMATION: The output breaker is detected off."
|
|
::= 44
|
|
|
|
dupsReturnFromOutputBreakerOff TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"INFORMATION: The output breaker is back to on."
|
|
::= 45
|
|
|
|
dupsBatteryDepleted TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"SEVER: The UPS batteries are depleted and will soon be exhausted."
|
|
::= 46
|
|
|
|
dupsReturnFromBatteryDepleted TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS has returned from a battery depleted condition."
|
|
::= 47
|
|
|
|
dupsLoadOnManualBypass TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"SEVER: The UPS loads on manual bypass."
|
|
::= 48
|
|
|
|
dupsNoLongerLoadOnManualBypass TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS is not on manual bypass mode."
|
|
::= 49
|
|
|
|
dupsBatteryBreakerOpen TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"SEVER: The battery breaker is detected open."
|
|
::= 50
|
|
|
|
dupsReturnFromBatteryBreakerOpen TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"INFORMATION: The battery breaker is returned from open."
|
|
::= 51
|
|
|
|
dupsOutletBankOn TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"SEVER: The outlet bank was turned on."
|
|
::= 52
|
|
|
|
dupsOutletBankOff TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"INFORMATION: The outlet bank was turned off."
|
|
::= 53
|
|
|
|
dupsRedundancyLoss TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"WARNING: The redundancy capacity lost in a modular UPS."
|
|
::= 54
|
|
|
|
dupsReturnFromRedundancyLoss TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"INFORMATION: The redundancy capacity recoverd in a modular UPS."
|
|
::= 55
|
|
|
|
dupsPhaseAsynchronous TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"SEVER: The phase is detected asynchronous."
|
|
::= 56
|
|
|
|
dupsReturnFromPhaseAsynchronous TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"INFORMATION: The phase is returned from asynchronous."
|
|
::= 57
|
|
|
|
dupsRectifierAbnormal TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"SEVER: The rectifier is detected abnormal."
|
|
::= 58
|
|
|
|
dupsReturnFromRectifierAbnormal TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"INFORMATION: The rectifier is returned from abnormal."
|
|
::= 59
|
|
|
|
dupsBypassBreakerOpen TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"SEVER: The bypass breaker is detected open."
|
|
::= 60
|
|
|
|
dupsReturnFromBypassBreakerOpen TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"INFORMATION: The bypass breaker is returned from open."
|
|
::= 61
|
|
|
|
dupsMainInputBreakerOpen TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"SEVER: The main inputs breaker is detected open."
|
|
::= 62
|
|
|
|
dupsReturnFromMainInputBreakerOpen TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"INFORMATION: The main input breaker is returned from open."
|
|
::= 63
|
|
|
|
|
|
dupsManualBypassBreakerOpen TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"SEVER: The manual bypass breaker is detected open."
|
|
::= 64
|
|
|
|
dupsReturnFromManualBypassBreakerOpen TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
VARIABLES { dupsTimeTicks, dupsDescription }
|
|
DESCRIPTION
|
|
"INFORMATION: The manual bypass breaker is returned from open."
|
|
::= 65
|
|
|
|
END
|