WebGraph-AnalogIO-57661-US-MIB DEFINITIONS ::= BEGIN
----------------------------------------------------------------
-- Revison: 1.30
----------------------------------------------------------------
-- 08.01.2010 New: Reports
--
----------------------------------------------------------------
-- Revison: 1.29
----------------------------------------------------------------
-- 01.10.2009 Webio
-- New Analog Out: 57661
----------------------------------------------------------------
-- Revison: 1.28
----------------------------------------------------------------
-- 02.12.2008 Webio
-- New Graphics java script base parameter
----------------------------------------------------------------
-- Revison: 1.27
----------------------------------------------------------------
-- 09.11.2006 Webio
-- DHCP enable
----------------------------------------------------------------
-- Revison: 1.26
----------------------------------------------------------------
-- 28.06.2006 New: Community String Trap
--
----------------------------------------------------------------
-- Revison: 1.25
----------------------------------------------------------------
-- 25.11.2005 #57641, WebGraph AnalogIn
-- OID correction
----------------------------------------------------------------
-- Revison: 1.24
----------------------------------------------------------------
-- 26.07.2005 #57641, WebGraph AnalogIn
-- CRON timer function
----------------------------------------------------------------
-- Revison: 1.23
----------------------------------------------------------------
-- 14.07.2005 #57641, WebGraph AnalogIn
-- FTP functions
----------------------------------------------------------------
-- Revison: 1.22
----------------------------------------------------------------
-- 17.05.2005 #57641, WebGraph AnalogIn
-- Trap NMS annotations
----------------------------------------------------------------
-- Revison: 1.21
----------------------------------------------------------------
-- 19.04.2005 #57605, WebGraph Themometer
-- Mail Authentication
----------------------------------------------------------------
-- Revison: 1.20
----------------------------------------------------------------
-- 05.11.2004 #57606, WebGraph Thermo-Hygrometer
-- New: Syslog
--
----------------------------------------------------------------
-- Revison: 1.19
----------------------------------------------------------------
-- 08.09.2004 #57606 WebGraph Thermo-Hygrometer
-- New:
-- wtWebGraphThermHygroAlarmRHMin
-- wtWebGraphThermHygroAlarmRHMax
-- wtWebGraphThermHygroAlarmRHHysteresis
-- wtWebGraphThermHygroPortSensorSelect
-- wtWebGraphThermHygroAlarmDeltaTemp
-- wtWebGraphThermHygroAlarmAHMin
-- wtWebGraphThermHygroAlarmAHMax
----------------------------------------------------------------
-- Revison: 1.18
----------------------------------------------------------------
-- 21.07.2004 #57601/3/4, Webio Anx
-- New:
-- Diagnosis
----------------------------------------------------------------
-- Revison: 1.17
----------------------------------------------------------------
-- 28.06.2004 #57630/1/2, Webio Digital
-- Neu: Puls Mode
----------------------------------------------------------------
-- Revison: 1.16
----------------------------------------------------------------
-- 16.04.2004 New: #57632, Webio Digital EA24x24
--
-- #57630/1, Webio Digital EA12x12
-- New:
-- wtWebioEA12x12InputCounterClear
----------------------------------------------------------------
-- Revison: 1.15
----------------------------------------------------------------
-- 27.02.2004 #57630/1, Webio Digital EA12x12
-- New:
-- Length changed to 32 Bit:
-- wtWebioEA12x12InputValue
-- wtWebioEA12x12OutputValue
-- wtWebioEA12x12LoadControlView
-- wtWebioEA12x12LCShutDownView
-- wtWebioEA12x12SetOutput
-- wtWebioEA12x12AlarmInputTrigger
-- wtWebioEA12x12AlarmOutputTrigger
-- wtWebioEA12x12PortOutputSafetyState
----------------------------------------------------------------
-- Revison: 1.14
----------------------------------------------------------------
-- 16.02.2004 #57630/1, Webio Digital EA12x12
-- New:
-- Text: Location, Contact
-- SNMP: ColdStart, WarmStart, ComunityString Read/RW
-- Alarm: ColdStart / WarmStart trigger
--
-- #57601, 1xWebThermometer
-- #57603, 2xWebThermometer
-- #57604, 8xWebThermometer
-- New:
-- Alarm Hysteresis
-- Alarm Clear Traps and Mails
----------------------------------------------------------------
-- Revison: 1.13
----------------------------------------------------------------
-- 05.02.2004 #57601, 1xWebThermometer
-- #57603, 2xWebThermometer
-- #57604, 8xWebThermometer
-- New:
-- Text: Location, Contact
-- SNMP: ColdStart, WarmStart, ComunityString Read/RW
-- Alarm: ColdStart / WarmStart trigger
----------------------------------------------------------------
-- Revison: 1.12
----------------------------------------------------------------
-- 05.11.2003 #57601, 1xWebThermometer
-- #57603, 2xWebThermometer
-- #57604, 8xWebThermometer
-- New features:
-- Mail : Option CSV attachment
-- Port : Offset calibration
-- Alarm : TCP Client mode
----------------------------------------------------------------
-- Revison: 1.11
----------------------------------------------------------------
-- 28.10.2003 #57630/1, Webio Digital EA12x12
-- New features:
-- Alarm : TCP Client mode
-- Inputs: Puls filter
----------------------------------------------------------------
-- Revison: 1.10
----------------------------------------------------------------
-- 22.07.2003 #57630, Webio Digital EA12x12
-- New navigation tree, new binary modes
--
----------------------------------------------------------------
-- Revison: 1.09
----------------------------------------------------------------
-- 24.03.2003 Trap Enterprise (Type 1, 2) corrected
----------------------------------------------------------------
-- Revison: 1.08
----------------------------------------------------------------
-- 04.03.2003 reconciled the language versions DE/US
----------------------------------------------------------------
-- Revison: 1.07
----------------------------------------------------------------
-- 25.02.2003 Correction: wtWebioEA12x12LoadControl
----------------------------------------------------------------
-- Revison: 1.06
----------------------------------------------------------------
-- 24.02.2003 New:
-- #57630, Webio EA12x12, LoadControl Group
-- Correction: Trap variable names
----------------------------------------------------------------
-- Revison: 1.05
----------------------------------------------------------------
-- 21.01.2003 New:
-- #57630, Webio EA12x12
----------------------------------------------------------------
-- Revison: 1.04
----------------------------------------------------------------
-- 02.01.2003 New:
-- #57601, 1xWebThermometer
-- #57603, 2xWebThermometer, 8 alarms
----------------------------------------------------------------
-- Revison: 1.03
----------------------------------------------------------------
-- 21.11.2002 New:
-- #57604, 2xWebThermometer, BOOTP, StartupSite
-- #57603, 8xWebThermometer, BOOTP, StartupSite
----------------------------------------------------------------
-- Revison: 1.02
----------------------------------------------------------------
-- 26.07.2002 New:
-- #57604, 2xWebThermometer
-- #57603, 8xWebThermometer
--
IMPORTS
OBJECT-TYPE FROM RFC-1212
TRAP-TYPE FROM RFC-1215
DisplayString, PhysAddress FROM RFC1213-MIB
enterprises, TimeTicks, IpAddress, NetworkAddress FROM RFC1155-SMI;
-- IpAddress ::=
-- [APPLICATION 0]
-- IMPLICIT OCTET STRING (SIZE (4))
-- Counter ::=
-- [APPLICATION 1]
-- IMPLICIT INTEGER (0..4294967295)
-- Gauge ::=
-- [APPLICATION 2]
-- IMPLICIT INTEGER (0..4294967295)
-- TimeTicks ::=
-- [APPLICATION 3]
-- IMPLICIT INTEGER (0..4294967295)
-- DisplayString ::= OCTET STRING
-- PhysAddress ::= OCTET STRING
-- internet OBJECT IDENTIFIER ::= { iso org(3) dod(6) 1 }
-- privat OBJECT IDENTIFIER ::= { internet 4 }
-- enterprises OBJECT IDENTIFIER ::= { privat 1 }
-- Wiesemann & Theis Com-Server MIB
wut OBJECT IDENTIFIER ::= { enterprises 5040 }
wtComServer OBJECT IDENTIFIER ::= { wut 1 }
wtWebio OBJECT IDENTIFIER ::= { wtComServer 2 }
-- wtWebGraph Tree
wtWebGraphAnalog57661 OBJECT IDENTIFIER ::= { wtWebio 28 }
-- wtWebGraphAnalog57661 Tree
wtWebGraphAnalog57661Inventory OBJECT IDENTIFIER ::= { wtWebGraphAnalog57661 1 }
wtWebGraphAnalog57661SessCntrl OBJECT IDENTIFIER ::= { wtWebGraphAnalog57661 2 }
wtWebGraphAnalog57661Config OBJECT IDENTIFIER ::= { wtWebGraphAnalog57661 3 }
wtWebGraphAnalog57661Diag OBJECT IDENTIFIER ::= { wtWebGraphAnalog57661 4 }
-- wtWebGraphAnalog57661Config Tree
wtWebGraphAnalog57661Device OBJECT IDENTIFIER ::= { wtWebGraphAnalog57661Config 1 }
wtWebGraphAnalog57661Ports OBJECT IDENTIFIER ::= { wtWebGraphAnalog57661Config 2 }
wtWebGraphAnalog57661Manufact OBJECT IDENTIFIER ::= { wtWebGraphAnalog57661Config 3 }
-- wtWebGraphAnalog57661Device Tree
wtWebGraphAnalog57661Text OBJECT IDENTIFIER ::= { wtWebGraphAnalog57661Device 1 }
wtWebGraphAnalog57661TimeDate OBJECT IDENTIFIER ::= { wtWebGraphAnalog57661Device 2 }
wtWebGraphAnalog57661Basic OBJECT IDENTIFIER ::= { wtWebGraphAnalog57661Device 3 }
wtWebGraphAnalog57661Datalogger OBJECT IDENTIFIER ::= { wtWebGraphAnalog57661Device 4 }
wtWebGraphAnalog57661Alarm OBJECT IDENTIFIER ::= { wtWebGraphAnalog57661Device 5 }
wtWebGraphAnalog57661Graphics OBJECT IDENTIFIER ::= { wtWebGraphAnalog57661Device 6 }
wtWebGraphAnalog57661Report OBJECT IDENTIFIER ::= { wtWebGraphAnalog57661Device 7 }
-- wtWebGraphAnalog57661TimeDate Tree
wtWebGraphAnalog57661TimeZone OBJECT IDENTIFIER ::= { wtWebGraphAnalog57661TimeDate 1 }
wtWebGraphAnalog57661TimeServer OBJECT IDENTIFIER ::= { wtWebGraphAnalog57661TimeDate 2 }
wtWebGraphAnalog57661DeviceClock OBJECT IDENTIFIER ::= { wtWebGraphAnalog57661TimeDate 3 }
-- wtWebGraphAnalog57661Basic Tree
wtWebGraphAnalog57661Network OBJECT IDENTIFIER ::= { wtWebGraphAnalog57661Basic 1 }
wtWebGraphAnalog57661HTTP OBJECT IDENTIFIER ::= { wtWebGraphAnalog57661Basic 2 }
wtWebGraphAnalog57661Mail OBJECT IDENTIFIER ::= { wtWebGraphAnalog57661Basic 3 }
wtWebGraphAnalog57661SNMP OBJECT IDENTIFIER ::= { wtWebGraphAnalog57661Basic 4 }
wtWebGraphAnalog57661UDP OBJECT IDENTIFIER ::= { wtWebGraphAnalog57661Basic 5 }
wtWebGraphAnalog57661Syslog OBJECT IDENTIFIER ::= { wtWebGraphAnalog57661Basic 6 }
wtWebGraphAnalog57661FTP OBJECT IDENTIFIER ::= { wtWebGraphAnalog57661Basic 7 }
wtWebGraphAnalog57661Language OBJECT IDENTIFIER ::= { wtWebGraphAnalog57661Basic 8 }
wtWebGraphAnalog57661Binary OBJECT IDENTIFIER ::= { wtWebGraphAnalog57661Basic 9 }
-- wtWebGraphAnalog57661Graphics Tree
wtWebGraphAnalog57661GraphicsBase OBJECT IDENTIFIER ::= { wtWebGraphAnalog57661Graphics 1 }
wtWebGraphAnalog57661GraphicsSelect OBJECT IDENTIFIER ::= { wtWebGraphAnalog57661Graphics 2 }
wtWebGraphAnalog57661GraphicsScale OBJECT IDENTIFIER ::= { wtWebGraphAnalog57661Graphics 3 }
-- wtWebGraphAnalog57661Inventory Group
------------------------
wtWebGraphAnalog57661Sensors OBJECT-TYPE
SYNTAX INTEGER (1..2)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of sensors"
::= { wtWebGraphAnalog57661Inventory 1 }
-- Interface Table
wtWebGraphAnalog57661SensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF WtWebGraphAnalog57661SensorEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"List of sensors."
::= { wtWebGraphAnalog57661Inventory 2 }
wtWebGraphAnalog57661SensorEntry OBJECT-TYPE
SYNTAX WtWebGraphAnalog57661SensorEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"List of sensor numbers."
INDEX { wtWebGraphAnalog57661SensorNo }
::= { wtWebGraphAnalog57661SensorTable 1 }
WtWebGraphAnalog57661SensorEntry ::= SEQUENCE {
wtWebGraphAnalog57661SensorNo INTEGER
}
wtWebGraphAnalog57661SensorNo OBJECT-TYPE
SYNTAX INTEGER (1..2)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Sensor number."
::= { wtWebGraphAnalog57661SensorEntry 1 }
-- wtWebGraphAnalog57661Values Table
wtWebGraphAnalog57661ValuesTable OBJECT-TYPE
SYNTAX SEQUENCE OF WtWebGraphAnalog57661ValuesEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"List of measurement values corresponding to the channel numbers."
::= { wtWebGraphAnalog57661Inventory 3 }
wtWebGraphAnalog57661ValuesEntry OBJECT-TYPE
SYNTAX WtWebGraphAnalog57661ValuesEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Measurement values of the sensors."
INDEX { wtWebGraphAnalog57661SensorNo }
::= { wtWebGraphAnalog57661ValuesTable 1 }
WtWebGraphAnalog57661ValuesEntry ::= SEQUENCE{
wtWebGraphAnalog57661Values OCTET STRING
}
wtWebGraphAnalog57661Values OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (5))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Measurement value of the sensor, ASCII.
This value will be translated according to the ports settings
for the read and write operations."
::= { wtWebGraphAnalog57661ValuesEntry 1 }
-- wtWebGraphAnalog57661BinaryValues Table
wtWebGraphAnalog57661BinaryValuesTable OBJECT-TYPE
SYNTAX SEQUENCE OF WtWebGraphAnalog57661BinaryValuesEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"List of binary measurement values corresponding to the channel numbers."
::= { wtWebGraphAnalog57661Inventory 4 }
wtWebGraphAnalog57661BinaryValuesEntry OBJECT-TYPE
SYNTAX WtWebGraphAnalog57661BinaryValuesEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Binary measurement values of the sensors."
INDEX { wtWebGraphAnalog57661SensorNo }
::= { wtWebGraphAnalog57661BinaryValuesTable 1 }
WtWebGraphAnalog57661BinaryValuesEntry ::= SEQUENCE{
wtWebGraphAnalog57661BinaryValues INTEGER
}
wtWebGraphAnalog57661BinaryValues OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary measurement value of the sensor in 1/1000,
signed number, 0x7FFFFFFF indicates an invalid value.
This value will be translated according to the ports settings
for the read and write operations."
::= { wtWebGraphAnalog57661BinaryValuesEntry 1 }
-- wtWebGraphAnalog57661SessCntrl Group
--------------------------------
wtWebGraphAnalog57661SessCntrlPassword OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Entering this password opens a session which is ended by writing a 1 to
wtWebGraphAnalog57661SessCntrlLogout. When read this variable provides a string of
length zero."
::= { wtWebGraphAnalog57661SessCntrl 1 }
wtWebGraphAnalog57661SessCntrlConfigMode OBJECT-TYPE
SYNTAX INTEGER {
wtWebGraphAnalog57661SessCntrl-NoSession(0),
wtWebGraphAnalog57661SessCntrl-Session(1)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"When the device is in SNMP configuration mode, the value 1 is
returned, otherwise 0. If the read value is 0 even though the
password was written, the device is already in config mode and the
variables can only be read."
::= { wtWebGraphAnalog57661SessCntrl 2 }
wtWebGraphAnalog57661SessCntrlLogout OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"If the device is in configuration mode and the session was opened by
this SNMP Manager, writing a 1 to this variable will end the session
and all parameters are stored.
Writing a 2 discards all entries again.
When read this variable provides the value 0."
::= { wtWebGraphAnalog57661SessCntrl 3 }
wtWebGraphAnalog57661SessCntrlAdminPassword OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"This password protects access to the variables with administrator rights.
It can only be changed by the administrator. If no password was assigned,
the valid password is public."
::= { wtWebGraphAnalog57661SessCntrl 4 }
wtWebGraphAnalog57661SessCntrlConfigPassword OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"This password protects access to the variables with configurator rights. It can
be changed by the administrator and by the configurator. If no password was assigned,
the valid password is public. When read this variable provides a null-pointer."
::= { wtWebGraphAnalog57661SessCntrl 5 }
-- wtWebGraphAnalog57661Text Group
------------------------
wtWebGraphAnalog57661DeviceName OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name of the Webio, which is user definable."
::= { wtWebGraphAnalog57661Text 1 }
wtWebGraphAnalog57661DeviceText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Description of the Webio, which is user definable."
::= { wtWebGraphAnalog57661Text 2 }
wtWebGraphAnalog57661DeviceLocation OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Description of the location of the Webio, which is user definable."
::= { wtWebGraphAnalog57661Text 3 }
wtWebGraphAnalog57661DeviceContact OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Contact address of the system operator of the Webio, which is user definable."
::= { wtWebGraphAnalog57661Text 4 }
-- wtWebGraphAnalog57661TimeZone Group
----------------------------
wtWebGraphAnalog57661TzOffsetHrs OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Offset hours for the time zone (winter time) with respect to UTC."
::= { wtWebGraphAnalog57661TimeZone 1 }
wtWebGraphAnalog57661TzOffsetMin OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Offset minutes for the time zone (winter time) with respect to UTC."
::= { wtWebGraphAnalog57661TimeZone 2 }
wtWebGraphAnalog57661TzEnable OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded conditions:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : Apply Timezone"
::= { wtWebGraphAnalog57661TimeZone 3 }
wtWebGraphAnalog57661StTzOffsetHrs OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Offset hours of the time zone (summer time) with respect to UTC."
::= { wtWebGraphAnalog57661TimeZone 4 }
wtWebGraphAnalog57661StTzOffsetMin OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Offset minutes of the time zone (summer time) with respect to UTC."
::= { wtWebGraphAnalog57661TimeZone 5 }
wtWebGraphAnalog57661StTzEnable OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded conditions:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : Apply Summertime"
::= { wtWebGraphAnalog57661TimeZone 6 }
wtWebGraphAnalog57661StTzStartMonth OBJECT-TYPE
SYNTAX INTEGER {
wtWebGraphAnalog57661StartMonth-January(1),
wtWebGraphAnalog57661StartMonth-February(2),
wtWebGraphAnalog57661StartMonth-March(3),
wtWebGraphAnalog57661StartMonth-April(4),
wtWebGraphAnalog57661StartMonth-May(5),
wtWebGraphAnalog57661StartMonth-June(6),
wtWebGraphAnalog57661StartMonth-July(7),
wtWebGraphAnalog57661StartMonth-August(8),
wtWebGraphAnalog57661StartMonth-September(9),
wtWebGraphAnalog57661StartMonth-October(10),
wtWebGraphAnalog57661StartMonth-November(11),
wtWebGraphAnalog57661StartMonth-December(12)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Month in which the change is made from winter time to summer time."
::= { wtWebGraphAnalog57661TimeZone 7 }
wtWebGraphAnalog57661StTzStartMode OBJECT-TYPE
SYNTAX INTEGER {
wtWebGraphAnalog57661StartMode-first(1),
wtWebGraphAnalog57661StartMode-second(2),
wtWebGraphAnalog57661StartMode-third(3),
wtWebGraphAnalog57661StartMode-fourth(4),
wtWebGraphAnalog57661StartMode-last(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Mode of the day of the week for which the change is made from winter time to summer time."
::= { wtWebGraphAnalog57661TimeZone 8 }
wtWebGraphAnalog57661StTzStartWday OBJECT-TYPE
SYNTAX INTEGER {
wtWebGraphAnalog57661StartWday-Sunday(1),
wtWebGraphAnalog57661StartWday-Monday(2),
wtWebGraphAnalog57661StartWday-Tuesday(3),
wtWebGraphAnalog57661StartWday-Thursday(4),
wtWebGraphAnalog57661StartWday-Wednesday(5),
wtWebGraphAnalog57661StartWday-Friday(6),
wtWebGraphAnalog57661StartWday-Saturday(7)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Day of the week on which the change is made from winter time to summer time"
::= { wtWebGraphAnalog57661TimeZone 9 }
wtWebGraphAnalog57661StTzStartHrs OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Hour in which the time zone is changed from winter to summer time with
respect to UTC."
::= { wtWebGraphAnalog57661TimeZone 10 }
wtWebGraphAnalog57661StTzStartMin OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Minute in which the time zone is changed from winter to summer time with
respect to UTC."
::= { wtWebGraphAnalog57661TimeZone 11 }
wtWebGraphAnalog57661StTzStopMonth OBJECT-TYPE
SYNTAX INTEGER {
wtWebGraphAnalog57661StopMonth-January(1),
wtWebGraphAnalog57661StopMonth-February(2),
wtWebGraphAnalog57661StopMonth-March(3),
wtWebGraphAnalog57661StopMonth-April(4),
wtWebGraphAnalog57661StopMonth-May(5),
wtWebGraphAnalog57661StopMonth-June(6),
wtWebGraphAnalog57661StopMonth-July(7),
wtWebGraphAnalog57661StopMonth-August(8),
wtWebGraphAnalog57661StopMonth-September(9),
wtWebGraphAnalog57661StopMonth-October(10),
wtWebGraphAnalog57661StopMonth-November(11),
wtWebGraphAnalog57661StopMonth-December(12)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Month in which the change is made from summer time to winter time."
::= { wtWebGraphAnalog57661TimeZone 12 }
wtWebGraphAnalog57661StTzStopMode OBJECT-TYPE
SYNTAX INTEGER {
wtWebGraphAnalog57661StopMode-first(1),
wtWebGraphAnalog57661StopMode-second(2),
wtWebGraphAnalog57661StopMode-third(3),
wtWebGraphAnalog57661StopMode-fourth(4),
wtWebGraphAnalog57661StopMode-last(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Mode of the week day on which the change is made from summer time to winter time."
::= { wtWebGraphAnalog57661TimeZone 13 }
wtWebGraphAnalog57661StTzStopWday OBJECT-TYPE
SYNTAX INTEGER {
wtWebGraphAnalog57661StopWday-Sunday(1),
wtWebGraphAnalog57661StopWday-Monday(2),
wtWebGraphAnalog57661StopWday-Tuesday(3),
wtWebGraphAnalog57661StopWday-Thursday(4),
wtWebGraphAnalog57661StopWday-Wednesday(5),
wtWebGraphAnalog57661StopWday-Friday(6),
wtWebGraphAnalog57661StopWday-Saturday(7)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Day of the week on which the change is made from summer time to winter time."
::= { wtWebGraphAnalog57661TimeZone 14 }
wtWebGraphAnalog57661StTzStopHrs OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Hour at which the time zone is changed from summer to winter time with
respect to UTC."
::= { wtWebGraphAnalog57661TimeZone 15 }
wtWebGraphAnalog57661StTzStopMin OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Minute at which the time zone is changed from summer to winter time with
respect to UTC."
::= { wtWebGraphAnalog57661TimeZone 16 }
-- wtWebGraphAnalog57661TimeServer Group
----------------------------
wtWebGraphAnalog57661TimeServer1 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"IP address or name of the 1st time server in ASCII"
::= { wtWebGraphAnalog57661TimeServer 1 }
wtWebGraphAnalog57661TimeServer2 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"IP address or name of the 2nd time server in ASCII"
::= { wtWebGraphAnalog57661TimeServer 2 }
wtWebGraphAnalog57661TsEnable OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded conditions:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : Apply Time Server"
::= { wtWebGraphAnalog57661TimeServer 3 }
wtWebGraphAnalog57661TsSyncTime OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Daily synchronisation time with the time server (hour: 0-23)."
::= { wtWebGraphAnalog57661TimeServer 4 }
-- wtWebGraphAnalog57661DeviceClock Group
----------------------------
wtWebGraphAnalog57661ClockHrs OBJECT-TYPE
SYNTAX INTEGER (0..23)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Clock hours taking into account the time zone settings."
::= { wtWebGraphAnalog57661DeviceClock 1 }
wtWebGraphAnalog57661ClockMin OBJECT-TYPE
SYNTAX INTEGER (0..59)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Clock minutes taking into account the time zone settings."
::= { wtWebGraphAnalog57661DeviceClock 2 }
wtWebGraphAnalog57661ClockDay OBJECT-TYPE
SYNTAX INTEGER (1..31)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Date: Day of the month, taking into account the time zone settings."
::= { wtWebGraphAnalog57661DeviceClock 3 }
wtWebGraphAnalog57661ClockMonth OBJECT-TYPE
SYNTAX INTEGER {
wtWebGraphAnalog57661ClockMonth-January(1),
wtWebGraphAnalog57661ClockMonth-February(2),
wtWebGraphAnalog57661ClockMonth-March(3),
wtWebGraphAnalog57661ClockMonth-April(4),
wtWebGraphAnalog57661ClockMonth-May(5),
wtWebGraphAnalog57661ClockMonth-June(6),
wtWebGraphAnalog57661ClockMonth-July(7),
wtWebGraphAnalog57661ClockMonth-August(8),
wtWebGraphAnalog57661ClockMonth-September(9),
wtWebGraphAnalog57661ClockMonth-October(10),
wtWebGraphAnalog57661ClockMonth-November(11),
wtWebGraphAnalog57661ClockMonth-December(12)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Date: Month, taking into account the time zone settings."
::= { wtWebGraphAnalog57661DeviceClock 4 }
wtWebGraphAnalog57661ClockYear OBJECT-TYPE
SYNTAX INTEGER (0..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Date: Year, taking into account the time zone settings."
::= { wtWebGraphAnalog57661DeviceClock 5 }
-- wtWebGraphAnalog57661Network Group
------------------------
wtWebGraphAnalog57661IpAddress OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
"IP address of the Webio"
::= { wtWebGraphAnalog57661Network 1 }
wtWebGraphAnalog57661SubnetMask OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Subnet mask of the Webio"
::= { wtWebGraphAnalog57661Network 2 }
wtWebGraphAnalog57661Gateway OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Gateway of the Webio"
::= { wtWebGraphAnalog57661Network 3 }
wtWebGraphAnalog57661DnsServer1 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"IP address of the 1st DNS server in ASCII"
::= { wtWebGraphAnalog57661Network 4 }
wtWebGraphAnalog57661DnsServer2 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"IP address of the 2nd DNS server in ASCII"
::= { wtWebGraphAnalog57661Network 5 }
wtWebGraphAnalog57661AddConfig OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Additional configuration (1=ON):
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1: DHCP disable
Bit 0: BOOTP disable
"
::= { wtWebGraphAnalog57661Network 6 }
-- wtWebGraphAnalog57661HTTP Group
--------------------------------
wtWebGraphAnalog57661Startup OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded start page:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1: Index.htm
Bit 2: Home.htm
Bit 3: User.htm
Only one page may be selected at a time."
::= { wtWebGraphAnalog57661HTTP 1 }
wtWebGraphAnalog57661GetHeaderEnable OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"If these bits are set, every answer of a short form GET question will be lead
by the IP-address and name of the device and/or a HTTP header:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-6: unused
Bit 1 : GET HTTP enable
Bit 0 : GET Header enable"
::= { wtWebGraphAnalog57661HTTP 2 }
wtWebGraphAnalog57661HttpPort OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Definition of the standard HTML port (Default: 80)."
::= { wtWebGraphAnalog57661HTTP 3 }
-- wtWebGraphAnalog57661Mail Group
--------------------------------
wtWebGraphAnalog57661MailAdName OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Device name for mail administration."
::= { wtWebGraphAnalog57661Mail 1 }
wtWebGraphAnalog57661MailReply OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Reply address for the mail server."
::= { wtWebGraphAnalog57661Mail 2 }
wtWebGraphAnalog57661MailServer OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name or IP address of the mail server."
::= { wtWebGraphAnalog57661Mail 3 }
wtWebioAn1MailEnable OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Set this bit to enable the sending of mails:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : Mail enable"
::= { wtWebGraphAnalog57661Mail 4 }
wtWebGraphAnalog57661MailAuthentication OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Selection of the authentication modi:
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output.
Bit 0 corresponds to the LSB.
OCTET 1: unused
OCTET 2: unused
OCTET 3: unused
OCTET 4: Bit 3-7: unused
Bit 2 : POP3 before SMTP
Bit 1 : ESMTP, authentication
Bit 0 : SMTP, no authentication"
::= { wtWebGraphAnalog57661Mail 5 }
wtWebGraphAnalog57661MailAuthUser OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name of the user to be authenticated."
::= { wtWebGraphAnalog57661Mail 6 }
wtWebGraphAnalog57661MailAuthPassword OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Authentication password."
::= { wtWebGraphAnalog57661Mail 7 }
wtWebGraphAnalog57661MailPop3Server OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name or Ip-address of the POP3 Servers."
::= { wtWebGraphAnalog57661Mail 8 }
-- wtWebGraphAnalog57661SNMP Group
--------------------------------
wtWebGraphAnalog57661SnmpCommunityStringRead OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Community string read only"
::= { wtWebGraphAnalog57661SNMP 1 }
wtWebGraphAnalog57661SnmpCommunityStringReadWrite OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Community string read / write"
::= { wtWebGraphAnalog57661SNMP 2 }
wtWebGraphAnalog57661SystemTrapManagerIP OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name or IP address of the TCP server which accepts the system trap."
::= { wtWebGraphAnalog57661SNMP 3 }
wtWebGraphAnalog57661SystemTrapEnable OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded trigger conditions:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0: ColdStart
Bit 1: WarmStart
Bit 2-7: unused"
::= { wtWebGraphAnalog57661SNMP 4 }
wtWebGraphAnalog57661SnmpEnable OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Set bit 0 to enable SNMP.
If disabled, the device did not respond to any SNMP requests.
Bit 1 decided wether the community string of read operations
is compared with the system password or not:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : SNMP enable"
::= { wtWebGraphAnalog57661SNMP 5 }
wtWebGraphAnalog57661SnmpCommunityStringTrap OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Community string send within traps."
::= { wtWebGraphAnalog57661SNMP 6 }
-- wtWebGraphAnalog57661UDP Group
--------------------------------
wtWebGraphAnalog57661UdpPort OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Udp port to which the Udp queries ( short form GET requests) can be sent. This
port number must be unique within the device."
::= { wtWebGraphAnalog57661UDP 1 }
wtWebGraphAnalog57661UdpEnable OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Set this bit to enable UDP support:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : UDP enable"
::= { wtWebGraphAnalog57661UDP 2 }
-- wtWebGraphAnalog57661Syslog Group
--------------------------------
wtWebGraphAnalog57661SyslogServerIP OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name or IP address of the Syslog server, which accepts the Syslog messgaes."
::= { wtWebGraphAnalog57661Syslog 1 }
wtWebGraphAnalog57661SyslogServerPort OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Portnumber of the Syslog servers, default 514."
::= { wtWebGraphAnalog57661Syslog 2 }
wtWebGraphAnalog57661SyslogSystemMessagesEnable OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded trigger conditions:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0: ColdStart
Bit 1: WarmStart
Bit 2: Diag Messages
Bit 3-7: unused"
::= { wtWebGraphAnalog57661Syslog 3 }
wtWebGraphAnalog57661SyslogEnable OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Set bit 0to enable Syslog:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : Syslog enable"
::= { wtWebGraphAnalog57661Syslog 4 }
-- wtWebGraphAnalog57661FTP Group
--------------------------------
wtWebGraphAnalog57661FTPServerIP OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name or IP address of the FTP server, which accepts the FTP messages."
::= { wtWebGraphAnalog57661FTP 1 }
wtWebGraphAnalog57661FTPServerControlPort OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Portnumber of the control port of the FTP server, default 21."
::= { wtWebGraphAnalog57661FTP 2 }
wtWebGraphAnalog57661FTPUserName OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"FTP Loggin: user name."
::= { wtWebGraphAnalog57661FTP 3 }
wtWebGraphAnalog57661FTPPassword OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"FTP Loggin: user password."
::= { wtWebGraphAnalog57661FTP 4 }
wtWebGraphAnalog57661FTPAccount OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"FTP Loggin: name of account."
::= { wtWebGraphAnalog57661FTP 5 }
wtWebGraphAnalog57661FTPOption OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Bit 0 switches the FTP Server in Passiv-Mode,
the Client controls the data connection on its own:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : PASV enable"
::= { wtWebGraphAnalog57661FTP 6 }
wtWebGraphAnalog57661FTPEnable OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Set Bit 0 to enable FTP:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : FTP enable"
::= { wtWebGraphAnalog57661FTP 7 }
-- wtWebGraphAnalog57661Language Group
--------------------------------
wtWebGraphAnalog57661LanguageSelect OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Language selection:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 2-7: unused
Bit 1 : English
Bit 0 : German"
::= { wtWebGraphAnalog57661Language 1 }
-- wtWebGraphAnalog57661Binary Group
--------------------------------
wtWebGraphAnalog57661BinaryModeCount OBJECT-TYPE
SYNTAX INTEGER (1..2)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of independent binary channels."
::= { wtWebGraphAnalog57661Binary 1 }
-- Binary Interface Table
wtWebGraphAnalog57661BinaryIfTable OBJECT-TYPE
SYNTAX SEQUENCE OF WtWebGraphAnalog57661BinaryIfEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Table of indices."
::= { wtWebGraphAnalog57661Binary 2 }
wtWebGraphAnalog57661BinaryIfEntry OBJECT-TYPE
SYNTAX WtWebGraphAnalog57661BinaryIfEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Indices of the binary channels."
INDEX { wtWebGraphAnalog57661BinaryModeNo }
::= { wtWebGraphAnalog57661BinaryIfTable 1 }
WtWebGraphAnalog57661BinaryIfEntry ::= SEQUENCE {
wtWebGraphAnalog57661BinaryModeNo INTEGER
}
wtWebGraphAnalog57661BinaryModeNo OBJECT-TYPE
SYNTAX INTEGER (1..2)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of the binary channel."
::= { wtWebGraphAnalog57661BinaryIfEntry 1 }
-- Binary Table
--------------------------------
wtWebGraphAnalog57661BinaryTable OBJECT-TYPE
SYNTAX SEQUENCE OF WtWebGraphAnalog57661BinaryEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Table of properties of the binary mode."
::= { wtWebGraphAnalog57661Binary 3 }
wtWebGraphAnalog57661BinaryEntry OBJECT-TYPE
SYNTAX WtWebGraphAnalog57661BinaryEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Binary properties."
INDEX { wtWebGraphAnalog57661BinaryModeNo }
::= { wtWebGraphAnalog57661BinaryTable 1 }
WtWebGraphAnalog57661BinaryEntry ::= SEQUENCE {
wtWebGraphAnalog57661BinaryOperationMode OCTET STRING,
wtWebGraphAnalog57661BinaryTcpServerLocalPort INTEGER,
wtWebGraphAnalog57661BinaryTcpServerInputTrigger OCTET STRING,
wtWebGraphAnalog57661BinaryTcpServerApplicationMode OCTET STRING,
wtWebGraphAnalog57661BinaryTcpClientLocalPort INTEGER,
wtWebGraphAnalog57661BinaryTcpClientServerPort INTEGER,
wtWebGraphAnalog57661BinaryTcpClientServerIpAddr OCTET STRING,
wtWebGraphAnalog57661BinaryTcpClientServerPassword OCTET STRING,
wtWebGraphAnalog57661BinaryTcpClientInactivity INTEGER,
wtWebGraphAnalog57661BinaryTcpClientInputTrigger OCTET STRING,
wtWebGraphAnalog57661BinaryTcpClientInterval INTEGER,
wtWebGraphAnalog57661BinaryTcpClientApplicationMode OCTET STRING,
wtWebGraphAnalog57661BinaryUdpPeerLocalPort INTEGER,
wtWebGraphAnalog57661BinaryUdpPeerRemotePort INTEGER,
wtWebGraphAnalog57661BinaryUdpPeerRemoteIpAddr OCTET STRING,
wtWebGraphAnalog57661BinaryUdpPeerInputTrigger OCTET STRING,
wtWebGraphAnalog57661BinaryUdpPeerInterval INTEGER,
wtWebGraphAnalog57661BinaryUdpPeerApplicationMode OCTET STRING,
wtWebGraphAnalog57661BinaryConnectedPort INTEGER,
wtWebGraphAnalog57661BinaryConnectedIpAddr IpAddress,
wtWebGraphAnalog57661BinaryTcpServerClientHttpPort INTEGER,
wtWebGraphAnalog57661BinaryTcpClientServerHttpPort INTEGER,
wtWebGraphAnalog57661BinaryTcpServerHysteresis1 OCTET STRING,
wtWebGraphAnalog57661BinaryTcpServerHysteresis2 OCTET STRING,
wtWebGraphAnalog57661BinaryTcpClientHysteresis1 OCTET STRING,
wtWebGraphAnalog57661BinaryTcpClientHysteresis2 OCTET STRING,
wtWebGraphAnalog57661BinaryUdpPeerHysteresis1 OCTET STRING,
wtWebGraphAnalog57661BinaryUdpPeerHysteresis2 OCTET STRING
}
wtWebGraphAnalog57661BinaryOperationMode OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Selection of the operation mode:
The OCTETS are interpreted bit-by-bit,
Bit 0 corresponds to the LSB.
OCTET 1: unused
OCTET 2: unused
OCTET 3: unused
OCTET 4: Bit 3-7: unused
Bit 2 : UDP Peer
Bit 1 : TCP Client
Bit 0 : TCP Server"
::= { wtWebGraphAnalog57661BinaryEntry 1 }
wtWebGraphAnalog57661BinaryTcpServerLocalPort OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Local TCP port for data exchange in this server mode.
This port number must be unique within the device.
Reserved port number must not be used (refere to the manual)."
::= { wtWebGraphAnalog57661BinaryEntry 2 }
wtWebGraphAnalog57661BinaryTcpServerInputTrigger OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted
from this rule. Nevertheless every transmission will contain all input states.
If a bit is set (1), a change of state on the corresponding input
triggers a transmission. If the bit is not set (0), no transmission
takes place.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an input.
Bit 0 corresponds to the LSB.
OCTET 1: unused
OCTET 2: unused
OCTET 3: unused
OCTET 4, Bit 0-1: Analog inputs 0-1"
::= { wtWebGraphAnalog57661BinaryEntry 3 }
wtWebGraphAnalog57661BinaryTcpServerApplicationMode OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Selection of the application mode:
The OCTETS are interpreted bit-by-bit,
Bit 0 corresponds to the LSB.
OCTET 1: unused
OCTET 2: unused
OCTET 3: unused
OCTET 4: Bit 4-7: unused
Bit 3 : OPC Device
Bit 2 : Box2Box Slave
Bit 1 : Compatible 50xxx
Bit 0 : Default"
::= { wtWebGraphAnalog57661BinaryEntry 4 }
wtWebGraphAnalog57661BinaryTcpClientLocalPort OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Local TCP port for data exchange in this client mode.
This port number must be unique within the device.
Reserved port number must not be used (refere to the manual)."
::= { wtWebGraphAnalog57661BinaryEntry 5 }
wtWebGraphAnalog57661BinaryTcpClientServerPort OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Port number of the server. A complete set of port number, IP address
and a valid input/output mask starts this mode.
No data exchange take place when setting the server port to zero."
::= { wtWebGraphAnalog57661BinaryEntry 6 }
wtWebGraphAnalog57661BinaryTcpClientServerIpAddr OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Ip address of the server. A complete set of port number, IP address
and a valid input/output mask starts this mode.
No data exchange take place when setting the server IP address to 0.0.0.0."
::= { wtWebGraphAnalog57661BinaryEntry 7 }
wtWebGraphAnalog57661BinaryTcpClientServerPassword OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Building a connection may be protected by the
administrator password of the server. Enter the server password
to establish the connection, if a server administrator password
exists."
::= { wtWebGraphAnalog57661BinaryEntry 8 }
wtWebGraphAnalog57661BinaryTcpClientInactivity OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Connection timeout in 100ms. If no data are exchanged within the specified
time, the device closes the connection to the server.
The value 0 deactivates the timer. Using the Box2Box mode this function is
disabled."
::= { wtWebGraphAnalog57661BinaryEntry 9 }
wtWebGraphAnalog57661BinaryTcpClientInputTrigger OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted
from this rule. Nevertheless every transmission will contain all input states.
If a bit is set (1), a change of state on the corresponding input
triggers a transmission. If the bit is not set (0), no transmission
takes place.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an input.
Bit 0 corresponds to the LSB.
OCTET 1: unused
OCTET 2: unused
OCTET 3: unused
OCTET 4, Bit 0-1: Analog inputs 0-1"
::= { wtWebGraphAnalog57661BinaryEntry 10 }
wtWebGraphAnalog57661BinaryTcpClientInterval OBJECT-TYPE
SYNTAX INTEGER (0..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Configurable interval with a 100ms base, in which the Webio device sends
data to the configured application. A interval of zero stopps the
periodical sending."
::= { wtWebGraphAnalog57661BinaryEntry 11 }
wtWebGraphAnalog57661BinaryTcpClientApplicationMode OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Selection of the application mode:
The OCTETS are interpreted bit-by-bit,
Bit 0 corresponds to the LSB.
OCTET 1: unused
OCTET 2: unused
OCTET 3: unused
OCTET 4: Bit 3-7: unused
Bit 2 : Box2Box Slave
Bit 1 : Compatible 50xxx
Bit 0 : Default"
::= { wtWebGraphAnalog57661BinaryEntry 12 }
wtWebGraphAnalog57661BinaryUdpPeerLocalPort OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Local UDP port for data exchange in this peer to peer mode.
This port number must be unique within the device.
Reserved port number must not be used (refere to the manual)."
::= { wtWebGraphAnalog57661BinaryEntry 13 }
wtWebGraphAnalog57661BinaryUdpPeerRemotePort OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Port number of the remote device. A complete set of port number, IP address
and a valid input/output mask starts this mode.
No data exchange take place when setting the remote port to zero."
::= { wtWebGraphAnalog57661BinaryEntry 14 }
wtWebGraphAnalog57661BinaryUdpPeerRemoteIpAddr OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Ip address of the remote device. A complete set of port number, IP address
and a valid input/output mask starts this mode.
No data exchange take place when setting the remote device IP address to 0.0.0.0."
::= { wtWebGraphAnalog57661BinaryEntry 15 }
wtWebGraphAnalog57661BinaryUdpPeerInputTrigger OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted
from this rule. Nevertheless every transmission will contain all input states.
If a bit is set (1), a change of state on the corresponding input
triggers a transmission. If the bit is not set (0), no transmission
takes place.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an input.
Bit 0 corresponds to the LSB.
OCTET 1: unused
OCTET 2: unused
OCTET 3: unused
OCTET 4, Bit 0-1: Analog inputs 0-1"
::= { wtWebGraphAnalog57661BinaryEntry 16 }
wtWebGraphAnalog57661BinaryUdpPeerInterval OBJECT-TYPE
SYNTAX INTEGER (0..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Configurable interval with a 100ms base, in which the Webio device sends
data to the configured remote device. A interval of zero stopps the
periodical sending."
::= { wtWebGraphAnalog57661BinaryEntry 17 }
wtWebGraphAnalog57661BinaryUdpPeerApplicationMode OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Selection of the application mode:
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output.
Bit 0 corresponds to the LSB.
OCTET 1: unused
OCTET 2: unused
OCTET 3: unused
OCTET 4: Bit 3-7: unused
Bit 2 : Box2Box Slave
Bit 1 : Compatible 50xxx
Bit 0 : Default"
::= { wtWebGraphAnalog57661BinaryEntry 18 }
wtWebGraphAnalog57661BinaryConnectedPort OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Port number of the remote device, after connection has been established.
In case of no connection or missing port informations a zero will be read."
::= { wtWebGraphAnalog57661BinaryEntry 19 }
wtWebGraphAnalog57661BinaryConnectedIpAddr OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-only
STATUS mandatory
DESCRIPTION
"IP address of the remote device, after connection has been established.
In case of no connection or missing port informations 0.0.0.0 will be read."
::= { wtWebGraphAnalog57661BinaryEntry 20 }
wtWebGraphAnalog57661BinaryTcpServerClientHttpPort OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"HTTP port number of the remote device at TCP Server Mode. If an mailfunction occurs
status informations will be send to this port.
Not used at mode Compatible 50xxx."
::= { wtWebGraphAnalog57661BinaryEntry 21 }
wtWebGraphAnalog57661BinaryTcpClientServerHttpPort OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"HTTP port number of the remote device at TCP Client Mode. In the operating mode
Box2Box connection status informations will be exchanged through this port."
::= { wtWebGraphAnalog57661BinaryEntry 22 }
wtWebGraphAnalog57661BinaryTcpServerHysteresis1 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A change greater than this value initiate a transmission of the corresponding input value.
The input 1 must be selected at wtWebGraphAnalog57661BinaryTcpServerInputTrigger.
With a hysteresis of zero any change will be transmitted."
::= { wtWebGraphAnalog57661BinaryEntry 23 }
wtWebGraphAnalog57661BinaryTcpServerHysteresis2 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A change greater than this value initiate a transmission of the corresponding input value.
The input 2 must be selected at wtWebGraphAnalog57661BinaryTcpServerInputTrigger.
With a hysteresis of zero any change will be transmitted."
::= { wtWebGraphAnalog57661BinaryEntry 24 }
wtWebGraphAnalog57661BinaryTcpClientHysteresis1 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A change greater than this value initiate a transmission of the corresponding input value.
The input 1 must be selected at wtWebGraphAnalog57661BinaryTcpClientInputTrigger.
With a hysteresis of zero any change will be transmitted."
::= { wtWebGraphAnalog57661BinaryEntry 25 }
wtWebGraphAnalog57661BinaryTcpClientHysteresis2 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A change greater than this value initiate a transmission of the corresponding input value.
The input 2 must be selected at wtWebGraphAnalog57661BinaryTcpClientInputTrigger.
With a hysteresis of zero any change will be transmitted."
::= { wtWebGraphAnalog57661BinaryEntry 26 }
wtWebGraphAnalog57661BinaryUdpPeerHysteresis1 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A change greater than this value initiate a transmission of the corresponding input value.
The input 1 must be selected at wtWebGraphAnalog57661BinaryUdpPeerInputTrigger.
With a hysteresis of zero any change will be transmitted."
::= { wtWebGraphAnalog57661BinaryEntry 27 }
wtWebGraphAnalog57661BinaryUdpPeerHysteresis2 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A change greater than this value initiate a transmission of the corresponding input value.
The input 2 must be selected at wtWebGraphAnalog57661BinaryUdpPeerInputTrigger.
With a hysteresis of zero any change will be transmitted."
::= { wtWebGraphAnalog57661BinaryEntry 28 }
-- wtWebGraphAnalog57661Datalogger Group
--------------------------------
wtWebGraphAnalog57661LoggerTimebase OBJECT-TYPE
SYNTAX INTEGER {
wtWebGraphAnalog57661Datalogger-15Sec(1),
wtWebGraphAnalog57661Datalogger-30Sec(2),
wtWebGraphAnalog57661Datalogger-1Min(3),
wtWebGraphAnalog57661Datalogger-5Min(4),
wtWebGraphAnalog57661Datalogger-15Min(5),
wtWebGraphAnalog57661Datalogger-60Min(6)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Time base of the data logger"
::= { wtWebGraphAnalog57661Datalogger 1 }
wtWebGraphAnalog57661LoggerSensorSel OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded trigger conditions:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0: Sensor 1
Bit 1: Sensor 2
Bit 2-7: unused"
::= { wtWebGraphAnalog57661Datalogger 2 }
wtWebGraphAnalog57661DisplaySensorSel OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded sensor selection:
only selected sensors will be shown in the graphical presentation:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0: Sensor 1
Bit 1: Sensor 2
Bit 2-7: unused"
::= { wtWebGraphAnalog57661Datalogger 3 }
-- Graph Sensor Color Table
wtWebGraphAnalog57661SensorColorTable OBJECT-TYPE
SYNTAX SEQUENCE OF WtWebGraphAnalog57661SensorColorEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"List of sensor colors for the praphical presentation."
::= { wtWebGraphAnalog57661Datalogger 4 }
wtWebGraphAnalog57661SensorColorEntry OBJECT-TYPE
SYNTAX WtWebGraphAnalog57661SensorColorEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Index numbers of the sensors."
INDEX { wtWebGraphAnalog57661SensorNo }
::= { wtWebGraphAnalog57661SensorColorTable 1 }
WtWebGraphAnalog57661SensorColorEntry ::= SEQUENCE {
wtWebGraphAnalog57661SensorColor OCTET STRING
}
wtWebGraphAnalog57661SensorColor OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(3))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Color of the sensors at the praphical presention."
::= { wtWebGraphAnalog57661SensorColorEntry 1 }
wtWebGraphAnalog57661AutoScaleEnable OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"If bit 0 is set, vertical auto scale is enabled:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : Auto Scale enable"
::= { wtWebGraphAnalog57661Datalogger 5 }
wtWebGraphAnalog57661VerticalUpperLimit OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"This value defines the maximum temperature shown in the graphical presentation,
if no auto scaling is selected.
Temperature in degrees with maximum 2 decimal places."
::= { wtWebGraphAnalog57661Datalogger 6 }
wtWebGraphAnalog57661VerticalLowerLimit OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"This value defines the minimum temperature shown in the graphical presentation,
if no auto scaling is selected.
Temperature in degrees with maximum 2 decimal places."
::= { wtWebGraphAnalog57661Datalogger 7 }
wtWebGraphAnalog57661HorizontalZoom OBJECT-TYPE
SYNTAX INTEGER {
wtWebGraphAnalog57661Zoom-25min(1),
wtWebGraphAnalog57661Zoom-75min(2),
wtWebGraphAnalog57661Zoom-5hrs(3),
wtWebGraphAnalog57661Zoom-30hrs(4),
wtWebGraphAnalog57661Zoom-5days(5),
wtWebGraphAnalog57661Zoom-25days(6)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Defines the default zoom stage, if no auto scaling is selected."
::= { wtWebGraphAnalog57661Datalogger 8 }
-- wtWebGraphAnalog57661Alarm Group
----------------------------
wtWebGraphAnalog57661AlarmCount OBJECT-TYPE
SYNTAX INTEGER (1..8)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of independent alarms."
::= { wtWebGraphAnalog57661Alarm 1 }
-- Alarm Interface Table
wtWebGraphAnalog57661AlarmIfTable OBJECT-TYPE
SYNTAX SEQUENCE OF WtWebGraphAnalog57661AlarmIfEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"List of alarm indices."
::= { wtWebGraphAnalog57661Alarm 2 }
wtWebGraphAnalog57661AlarmIfEntry OBJECT-TYPE
SYNTAX WtWebGraphAnalog57661AlarmIfEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Numbers of the alarms."
INDEX { wtWebGraphAnalog57661AlarmNo }
::= { wtWebGraphAnalog57661AlarmIfTable 1 }
WtWebGraphAnalog57661AlarmIfEntry ::= SEQUENCE {
wtWebGraphAnalog57661AlarmNo INTEGER
}
wtWebGraphAnalog57661AlarmNo OBJECT-TYPE
SYNTAX INTEGER (1..8)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Alarm number."
::= { wtWebGraphAnalog57661AlarmIfEntry 1 }
-- Alarm Table
wtWebGraphAnalog57661AlarmTable OBJECT-TYPE
SYNTAX SEQUENCE OF WtWebGraphAnalog57661AlarmEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"List of settings depending on the alarm number."
::= { wtWebGraphAnalog57661Alarm 3 }
wtWebGraphAnalog57661AlarmEntry OBJECT-TYPE
SYNTAX WtWebGraphAnalog57661AlarmEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Alarm parameters of the individual alarms."
INDEX { wtWebGraphAnalog57661AlarmNo }
::= { wtWebGraphAnalog57661AlarmTable 1 }
WtWebGraphAnalog57661AlarmEntry ::= SEQUENCE {
wtWebGraphAnalog57661AlarmTrigger OCTET STRING,
wtWebGraphAnalog57661AlarmMin1 OCTET STRING,
wtWebGraphAnalog57661AlarmMax1 OCTET STRING,
wtWebGraphAnalog57661AlarmHysteresis1 OCTET STRING,
wtWebGraphAnalog57661AlarmDelay OCTET STRING,
wtWebGraphAnalog57661AlarmInterval OCTET STRING,
wtWebGraphAnalog57661AlarmEnable OCTET STRING,
wtWebGraphAnalog57661AlarmEMailAddr OCTET STRING,
wtWebGraphAnalog57661AlarmMailSubject OCTET STRING,
wtWebGraphAnalog57661AlarmMailText OCTET STRING,
wtWebGraphAnalog57661AlarmManagerIP OCTET STRING,
wtWebGraphAnalog57661AlarmTrapText OCTET STRING,
wtWebGraphAnalog57661AlarmMailOptions OCTET STRING,
wtWebGraphAnalog57661AlarmTcpIpAddr OCTET STRING,
wtWebGraphAnalog57661AlarmTcpPort INTEGER,
wtWebGraphAnalog57661AlarmTcpText OCTET STRING,
wtWebGraphAnalog57661AlarmClearMailSubject OCTET STRING,
wtWebGraphAnalog57661AlarmClearMailText OCTET STRING,
wtWebGraphAnalog57661AlarmClearTrapText OCTET STRING,
wtWebGraphAnalog57661AlarmClearTcpText OCTET STRING,
wtWebGraphAnalog57661AlarmMin2 OCTET STRING,
wtWebGraphAnalog57661AlarmMax2 OCTET STRING,
wtWebGraphAnalog57661AlarmHysteresis2 OCTET STRING,
wtWebGraphAnalog57661AlarmSyslogIpAddr OCTET STRING,
wtWebGraphAnalog57661AlarmSyslogPort INTEGER,
wtWebGraphAnalog57661AlarmSyslogText OCTET STRING,
wtWebGraphAnalog57661AlarmSyslogClearText OCTET STRING,
wtWebGraphAnalog57661AlarmFtpDataPort OCTET STRING,
wtWebGraphAnalog57661AlarmFtpFileName OCTET STRING,
wtWebGraphAnalog57661AlarmFtpText OCTET STRING,
wtWebGraphAnalog57661AlarmFtpClearText OCTET STRING,
wtWebGraphAnalog57661AlarmFtpOption OCTET STRING,
wtWebGraphAnalog57661AlarmTimerCron OCTET STRING
}
wtWebGraphAnalog57661AlarmTrigger OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded trigger conditions:
Octet 1: unused
Octet 2: unused
Octet 3:
Bit 0: Timer
Bit 1: ColdStart
Bit 2: WarmStart
Octet 4:
Bit 0: Sensor 1
Bit 1: Sensor 2
Bit 2-7: unused"
::= { wtWebGraphAnalog57661AlarmEntry 1 }
wtWebGraphAnalog57661AlarmMin1 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Minimum sensor 1 with maximum 3 decimal places."
::= { wtWebGraphAnalog57661AlarmEntry 2 }
wtWebGraphAnalog57661AlarmMax1 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Maximum sensor 1 with maximum 3 decimal places."
::= { wtWebGraphAnalog57661AlarmEntry 3 }
wtWebGraphAnalog57661AlarmHysteresis1 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Reading changes of this size clears the alarm state (MAX-hyst, MIN+hyst.)
with maximum 3 decimal places."
::= { wtWebGraphAnalog57661AlarmEntry 4 }
wtWebGraphAnalog57661AlarmDelay OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alarm will be delayed by setting this time while stable alarm
condition occur (time in minutes)."
::= { wtWebGraphAnalog57661AlarmEntry 5 }
wtWebGraphAnalog57661AlarmInterval OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Send interval for alarm messages."
::= { wtWebGraphAnalog57661AlarmEntry 6 }
wtWebGraphAnalog57661AlarmEnable OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded alarm enable:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0: Mail Enable
Bit 1: SNMP Trap enable
Bit 2: TCP Client enable
Bit 3: Syslog enable
Bit 4: FTP Client enable"
::= { wtWebGraphAnalog57661AlarmEntry 7 }
wtWebGraphAnalog57661AlarmEMailAddr OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"E-Mail address for sending the alarm mail to."
::= { wtWebGraphAnalog57661AlarmEntry 8 }
wtWebGraphAnalog57661AlarmMailSubject OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Subject line for alarm mail."
::= { wtWebGraphAnalog57661AlarmEntry 9 }
wtWebGraphAnalog57661AlarmMailText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alarm mail text: <Mn> provides the current temperature; n = 1..2.
<Z> provides the current time."
::= { wtWebGraphAnalog57661AlarmEntry 10 }
wtWebGraphAnalog57661AlarmManagerIP OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name or IP address of the SNMP Manager which accepts the trap."
::= { wtWebGraphAnalog57661AlarmEntry 11 }
wtWebGraphAnalog57661AlarmTrapText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"This text is sent in the trap body."
::= { wtWebGraphAnalog57661AlarmEntry 12 }
wtWebGraphAnalog57661AlarmMailOptions OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded options:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : Attach Logger.csv Enable
Bit 1 : CSV-Data_since_last_report
Bit 2-7: unused"
::= { wtWebGraphAnalog57661AlarmEntry 13 }
wtWebGraphAnalog57661AlarmTcpIpAddr OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name or IP address of the TCP server which accepts the trap."
::= { wtWebGraphAnalog57661AlarmEntry 14 }
wtWebGraphAnalog57661AlarmTcpPort OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Port number of the TCP server which accepts the trap."
::= { wtWebGraphAnalog57661AlarmEntry 15 }
wtWebGraphAnalog57661AlarmTcpText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"This text is sent in the TCP trap body."
::= { wtWebGraphAnalog57661AlarmEntry 16 }
wtWebGraphAnalog57661AlarmClearMailSubject OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Subject line for alarm clear mail."
::= { wtWebGraphAnalog57661AlarmEntry 17 }
wtWebGraphAnalog57661AlarmClearMailText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alarm clear mail text: <Mn> provides the current temperature; n = 1..2.
<Z> provides the current time."
::= { wtWebGraphAnalog57661AlarmEntry 18 }
wtWebGraphAnalog57661AlarmClearTrapText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"This text is sent in the trap body."
::= { wtWebGraphAnalog57661AlarmEntry 19 }
wtWebGraphAnalog57661AlarmClearTcpText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"This text is sent in the TCP trap body."
::= { wtWebGraphAnalog57661AlarmEntry 20 }
wtWebGraphAnalog57661AlarmMin2 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Minimum sensor 2 with maximum 3 decimal places."
::= { wtWebGraphAnalog57661AlarmEntry 21 }
wtWebGraphAnalog57661AlarmMax2 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Maximum sensor 2 with maximum 2 decimal places."
::= { wtWebGraphAnalog57661AlarmEntry 22 }
wtWebGraphAnalog57661AlarmHysteresis2 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Hysterese rel. sensor 2 with maximum 3 decimal places."
::= { wtWebGraphAnalog57661AlarmEntry 23 }
wtWebGraphAnalog57661AlarmSyslogIpAddr OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"IP address of the syslog server to which the Webio device should send syslog messages."
::= { wtWebGraphAnalog57661AlarmEntry 24 }
wtWebGraphAnalog57661AlarmSyslogPort OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Port number of the syslog server to which the Webio device should send syslog messages."
::= { wtWebGraphAnalog57661AlarmEntry 25 }
wtWebGraphAnalog57661AlarmSyslogText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body."
::= { wtWebGraphAnalog57661AlarmEntry 26 }
wtWebGraphAnalog57661AlarmSyslogClearText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body of a alarm clear message."
::= { wtWebGraphAnalog57661AlarmEntry 27 }
wtWebGraphAnalog57661AlarmFtpDataPort OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Local data port: 1..65535 or AUTO: the next free port will be assigned."
::= { wtWebGraphAnalog57661AlarmEntry 28 }
wtWebGraphAnalog57661AlarmFtpFileName OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name of the file including path informations."
::= { wtWebGraphAnalog57661AlarmEntry 29 }
wtWebGraphAnalog57661AlarmFtpText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Message text to store on the FTP server."
::= { wtWebGraphAnalog57661AlarmEntry 30 }
wtWebGraphAnalog57661AlarmFtpClearText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alarm clear message to store on the FTP server."
::= { wtWebGraphAnalog57661AlarmEntry 31 }
wtWebGraphAnalog57661AlarmFtpOption OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded options, select only one option at the same time:
STORE = replace file
APPEND = append message at the end of the file
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : STORE
Bit 1 : APPEND
Bit 2-7: unused"
::= { wtWebGraphAnalog57661AlarmEntry 32 }
wtWebGraphAnalog57661AlarmTimerCron OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"This entry defines a time window for alarm 1-8 and a activation time for the report.
A time window is definied by start and stop time stamp, seperated by a space or tab.
The activation time of the report is defined by a single start time stamp.
Each time stamp contains 5 space or tab seperated text fields for time trigger definition.
Each field must match with the actual time to trigger an action, weekday and day of month
are interpreted separatley.
1: Minutes Range 0-59
2. Hours Range 0-23, 0 is midnight
3: Day of month Range 1-31
4: Month Range 1-12
5: Weekday Range 0-6, 0 is sunday
Syntax for every field:
- an asterix (*) enables every possible setting of a field
- single numbers seperated by commas (i.e.: 2,14,22)
- a partition within the allowed range (i.e.: 1-5)
- step size within a partition of the allowed range (i.e.: 0-59/2 every second minute)."
::= { wtWebGraphAnalog57661AlarmEntry 33 }
-- wtWebGraphAnalog57661GraphicsBase Group
----------------------------
wtWebGraphAnalog57661GraphicsBaseEnable OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Defines the viewing options of the graphic:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : Auto scroll enable
Bit 1 : Show table
Bit 2 : Show graph
Bit 3 : Show control buttons
Bit 4 : Show config menu
Bit 5-7: unused"
::= { wtWebGraphAnalog57661GraphicsBase 1 }
wtWebGraphAnalog57661GraphicsBaseWidth OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Defines the width of the graphic in pixels."
::= { wtWebGraphAnalog57661GraphicsBase 2 }
wtWebGraphAnalog57661GraphicsBaseHeight OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Defines the height of the graphic in pixels."
::= { wtWebGraphAnalog57661GraphicsBase 3 }
wtWebGraphAnalog57661GraphicsBaseFrameColor OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(3))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Frame color definition in RGB."
::= { wtWebGraphAnalog57661GraphicsBase 4 }
wtWebGraphAnalog57661GraphicsBaseBackgroundColor OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(3))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Background color definition in RGB."
::= { wtWebGraphAnalog57661GraphicsBase 5 }
wtWebGraphAnalog57661GraphicsBasePollingrate OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Defines the pollingrate in seconds,
which defines the refreshing intervall of the graphic."
::= { wtWebGraphAnalog57661GraphicsBase 6 }
-- wtWebGraphAnalog57661GraphicsSelect Group
----------------------------
wtWebGraphAnalog57661GraphicsSelectDisplaySensorSel OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded sensor selection:
only selected sensors will be shown in the graphical presentation:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0: Sensor 1
Bit 1: Sensor 2
Bit 2-7: unused"
::= { wtWebGraphAnalog57661GraphicsSelect 1 }
wtWebGraphAnalog57661GraphicsSelectDisplayShowExtrem OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded sensor selection:
only selected sensors will be shown with minima and maxima:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0: Sensor 1
Bit 1: Sensor 2
Bit 2-7: unused"
::= { wtWebGraphAnalog57661GraphicsSelect 2 }
-- Graph Sensor Color Table
wtWebGraphAnalog57661SensorColor2Table OBJECT-TYPE
SYNTAX SEQUENCE OF WtWebGraphAnalog57661SensorColor2Entry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"List of sensor colors for the praphical presentation."
::= { wtWebGraphAnalog57661GraphicsSelect 3 }
wtWebGraphAnalog57661SensorColor2Entry OBJECT-TYPE
SYNTAX WtWebGraphAnalog57661SensorColor2Entry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Numbers of the sensors."
INDEX { wtWebGraphAnalog57661SensorNo }
::= { wtWebGraphAnalog57661SensorColor2Table 1 }
WtWebGraphAnalog57661SensorColor2Entry ::= SEQUENCE {
wtWebGraphAnalog57661GraphicsSensorColor OCTET STRING,
wtWebGraphAnalog57661GraphicsSelectScale OCTET STRING
}
wtWebGraphAnalog57661GraphicsSensorColor OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(3))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Color of the sensors at the praphical presention."
::= { wtWebGraphAnalog57661SensorColor2Entry 1 }
wtWebGraphAnalog57661GraphicsSelectScale OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Assignes one of 4 scales to a sensor:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : Use Scale 1
Bit 1 : Use Scale 2
Bit 2-7: unused"
::= { wtWebGraphAnalog57661SensorColor2Entry 2 }
-- wtWebGraphAnalog57661GraphicsScale Group
----------------------------
wtWebGraphAnalog57661GraphicsScaleAutoScaleEnable OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Select the Auto Scale Mode:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : Scale 1 Auto scale enable
Bit 1 : Scale 2 Auto scale enable
Bit 2-7: unused"
::= { wtWebGraphAnalog57661GraphicsScale 1 }
wtWebGraphAnalog57661GraphicsScaleAutoFitEnable OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Select the Auto Fit Mode::
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : Scale 1 Auto fit enable
Bit 1 : Scale 2 Auto fit enable
Bit 2-7: unused"
::= { wtWebGraphAnalog57661GraphicsScale 2 }
wtWebGraphAnalog57661GraphicsScale1Min OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Scale 1: Minimum."
::= { wtWebGraphAnalog57661GraphicsScale 3 }
wtWebGraphAnalog57661GraphicsScale2Min OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Scale 2: Minimum."
::= { wtWebGraphAnalog57661GraphicsScale 4 }
wtWebGraphAnalog57661GraphicsScale1Max OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Scale 1: Maximum."
::= { wtWebGraphAnalog57661GraphicsScale 7 }
wtWebGraphAnalog57661GraphicsScale2Max OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Scale 2: Maximum."
::= { wtWebGraphAnalog57661GraphicsScale 8 }
wtWebGraphAnalog57661GraphicsScale1Unit OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Scale 1: Unit."
::= { wtWebGraphAnalog57661GraphicsScale 11 }
wtWebGraphAnalog57661GraphicsScale2Unit OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Scale 2: Unit."
::= { wtWebGraphAnalog57661GraphicsScale 12 }
-- wtWebGraphAnalog57661Report Group
----------------------------
wtWebGraphAnalog57661ReportCount OBJECT-TYPE
SYNTAX INTEGER (1..8)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of independent Reports."
::= { wtWebGraphAnalog57661Report 1 }
-- Report Interface Table
wtWebGraphAnalog57661ReportIfTable OBJECT-TYPE
SYNTAX SEQUENCE OF WtWebGraphAnalog57661ReportIfEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"List of Report indices."
::= { wtWebGraphAnalog57661Report 2 }
wtWebGraphAnalog57661ReportIfEntry OBJECT-TYPE
SYNTAX WtWebGraphAnalog57661ReportIfEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Numbers of the Reports."
INDEX { wtWebGraphAnalog57661ReportNo }
::= { wtWebGraphAnalog57661ReportIfTable 1 }
WtWebGraphAnalog57661ReportIfEntry ::= SEQUENCE {
wtWebGraphAnalog57661ReportNo INTEGER
}
wtWebGraphAnalog57661ReportNo OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Report number."
::= { wtWebGraphAnalog57661ReportIfEntry 1 }
-- Report Table
wtWebGraphAnalog57661ReportTable OBJECT-TYPE
SYNTAX SEQUENCE OF WtWebGraphAnalog57661ReportEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"List of settings depending on the Report number."
::= { wtWebGraphAnalog57661Report 3 }
wtWebGraphAnalog57661ReportEntry OBJECT-TYPE
SYNTAX WtWebGraphAnalog57661ReportEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Report parameters of the individual Reports."
INDEX { wtWebGraphAnalog57661ReportNo }
::= { wtWebGraphAnalog57661ReportTable 1 }
WtWebGraphAnalog57661ReportEntry ::= SEQUENCE {
wtWebGraphAnalog57661ReportEnable OCTET STRING,
wtWebGraphAnalog57661ReportTimerCron OCTET STRING,
wtWebGraphAnalog57661ReportMethodeEnable OCTET STRING,
wtWebGraphAnalog57661ReportEMailAddr OCTET STRING,
wtWebGraphAnalog57661ReportMailSubject OCTET STRING,
wtWebGraphAnalog57661ReportMailText OCTET STRING,
wtWebGraphAnalog57661ReportManagerIP OCTET STRING,
wtWebGraphAnalog57661ReportTrapText OCTET STRING,
wtWebGraphAnalog57661ReportMailOptions OCTET STRING,
wtWebGraphAnalog57661ReportTcpIpAddr OCTET STRING,
wtWebGraphAnalog57661ReportTcpPort INTEGER,
wtWebGraphAnalog57661ReportTcpText OCTET STRING,
wtWebGraphAnalog57661ReportClearMailSubject OCTET STRING,
wtWebGraphAnalog57661ReportClearMailText OCTET STRING,
wtWebGraphAnalog57661ReportClearTrapText OCTET STRING,
wtWebGraphAnalog57661ReportClearTcpText OCTET STRING,
wtWebGraphAnalog57661ReportSyslogIpAddr OCTET STRING,
wtWebGraphAnalog57661ReportSyslogPort INTEGER,
wtWebGraphAnalog57661ReportSyslogText OCTET STRING,
wtWebGraphAnalog57661ReportSyslogClearText OCTET STRING,
wtWebGraphAnalog57661ReportFtpDataPort OCTET STRING,
wtWebGraphAnalog57661ReportFtpFileName OCTET STRING,
wtWebGraphAnalog57661ReportFtpText OCTET STRING,
wtWebGraphAnalog57661ReportFtpClearText OCTET STRING,
wtWebGraphAnalog57661ReportFtpOption OCTET STRING
}
wtWebGraphAnalog57661ReportEnable OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Bin<69>r kodierte Triggerbedingungen:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0: Report enable
Bit 1-7: unused"
::= { wtWebGraphAnalog57661ReportEntry 1 }
wtWebGraphAnalog57661ReportTimerCron OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"This entry defines a time window for alarm 1-8 and a activation time for the report.
A time window is definied by start and stop time stamp, seperated by a space or tab.
The activation time of the report is defined by a single start time stamp.
Each time stamp contains 5 space or tab seperated text fields for time trigger definition.
Each field must match with the actual time to trigger an action, weekday and day of month
are interpreted separatley.
1: Minutes Range 0-59
2. Hours Range 0-23, 0 is midnight
3: Day of month Range 1-31
4: Month Range 1-12
5: Weekday Range 0-6, 0 is sunday
Syntax for every field:
- an asterix (*) enables every possible setting of a field
- single numbers seperated by commas (i.e.: 2,14,22)
- a partition within the allowed range (i.e.: 1-5)
- step size within a partition of the allowed range (i.e.: 0-59/2 every second minute)."
::= { wtWebGraphAnalog57661ReportEntry 2 }
wtWebGraphAnalog57661ReportMethodeEnable OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded alarm enable:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0: Mail Enable
Bit 1: SNMP Trap enable
Bit 2: TCP Client enable
Bit 3: Syslog enable
Bit 4: FTP Client enable"
::= { wtWebGraphAnalog57661ReportEntry 3 }
wtWebGraphAnalog57661ReportEMailAddr OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"E-Mail address for sending the alarm mail to."
::= { wtWebGraphAnalog57661ReportEntry 8 }
wtWebGraphAnalog57661ReportMailSubject OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Subject line for alarm mail."
::= { wtWebGraphAnalog57661ReportEntry 9 }
wtWebGraphAnalog57661ReportMailText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Report mail text: <Mn> provides the current temperature; n = 1..2.
<Z> provides the current time."
::= { wtWebGraphAnalog57661ReportEntry 10 }
wtWebGraphAnalog57661ReportManagerIP OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name or IP address of the SNMP Manager which accepts the trap."
::= { wtWebGraphAnalog57661ReportEntry 11 }
wtWebGraphAnalog57661ReportTrapText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"This text is sent in the trap body."
::= { wtWebGraphAnalog57661ReportEntry 12 }
wtWebGraphAnalog57661ReportMailOptions OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded options:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : Attach Logger.csv Enable
Bit 1 : CSV-Data_since_last_report
Bit 2-7: unused"
::= { wtWebGraphAnalog57661ReportEntry 13 }
wtWebGraphAnalog57661ReportTcpIpAddr OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name or IP address of the TCP server which accepts the trap."
::= { wtWebGraphAnalog57661ReportEntry 14 }
wtWebGraphAnalog57661ReportTcpPort OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Port number of the TCP server which accepts the trap."
::= { wtWebGraphAnalog57661ReportEntry 15 }
wtWebGraphAnalog57661ReportTcpText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"This text is sent in the TCP trap body."
::= { wtWebGraphAnalog57661ReportEntry 16 }
wtWebGraphAnalog57661ReportClearMailSubject OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Subject line for alarm clear mail."
::= { wtWebGraphAnalog57661ReportEntry 17 }
wtWebGraphAnalog57661ReportClearMailText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Report clear mail text: <Mn> provides the current temperature; n = 1..2.
<Z> provides the current time."
::= { wtWebGraphAnalog57661ReportEntry 18 }
wtWebGraphAnalog57661ReportClearTrapText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"This text is sent in the trap body."
::= { wtWebGraphAnalog57661ReportEntry 19 }
wtWebGraphAnalog57661ReportClearTcpText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"This text is sent in the TCP trap body."
::= { wtWebGraphAnalog57661ReportEntry 20 }
wtWebGraphAnalog57661ReportSyslogIpAddr OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"IP address of the syslog server to which the Webio device should send syslog messages."
::= { wtWebGraphAnalog57661ReportEntry 24 }
wtWebGraphAnalog57661ReportSyslogPort OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Port number of the syslog server to which the Webio device should send syslog messages."
::= { wtWebGraphAnalog57661ReportEntry 25 }
wtWebGraphAnalog57661ReportSyslogText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body."
::= { wtWebGraphAnalog57661ReportEntry 26 }
wtWebGraphAnalog57661ReportSyslogClearText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body of a alarm clear message."
::= { wtWebGraphAnalog57661ReportEntry 27 }
wtWebGraphAnalog57661ReportFtpDataPort OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Local data port: 1..65535 or AUTO: the next free port will be assigned."
::= { wtWebGraphAnalog57661ReportEntry 28 }
wtWebGraphAnalog57661ReportFtpFileName OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name of the file including path informations."
::= { wtWebGraphAnalog57661ReportEntry 29 }
wtWebGraphAnalog57661ReportFtpText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Message text to store on the FTP server."
::= { wtWebGraphAnalog57661ReportEntry 30 }
wtWebGraphAnalog57661ReportFtpClearText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Report clear message to store on the FTP server."
::= { wtWebGraphAnalog57661ReportEntry 31 }
wtWebGraphAnalog57661ReportFtpOption OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded options, select only one option at the same time:
STORE = replace file
APPEND = append message at the end of the file
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : STORE
Bit 1 : APPEND
Bit 2-7: unused"
::= { wtWebGraphAnalog57661ReportEntry 32 }
-- wtWebGraphAnalog57661Ports Group
----------------------------
-- Table
wtWebGraphAnalog57661PortTable OBJECT-TYPE
SYNTAX SEQUENCE OF WtWebGraphAnalog57661PortEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"List of settings depending on the sensor number."
::= { wtWebGraphAnalog57661Ports 1 }
wtWebGraphAnalog57661PortEntry OBJECT-TYPE
SYNTAX WtWebGraphAnalog57661PortEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Sensor parameters for the individual sensors."
INDEX { wtWebGraphAnalog57661SensorNo }
::= { wtWebGraphAnalog57661PortTable 1 }
WtWebGraphAnalog57661PortEntry ::= SEQUENCE {
wtWebGraphAnalog57661PortName OCTET STRING,
wtWebGraphAnalog57661PortText OCTET STRING,
wtWebGraphAnalog57661PortOffset1 OCTET STRING,
wtWebGraphAnalog57661SetPoint1 OCTET STRING,
wtWebGraphAnalog57661PortOffset2 OCTET STRING,
wtWebGraphAnalog57661SetPoint2 OCTET STRING,
wtWebGraphAnalog57661PortComment OCTET STRING,
wtWebGraphAnalog57661PortSensorSelect OCTET STRING,
wtWebGraphAnalog57661PortUnit OCTET STRING,
wtWebGraphAnalog57661PortScale0 OCTET STRING,
wtWebGraphAnalog57661PortScale100 OCTET STRING,
wtWebGraphAnalog57661PortOutputMode OCTET STRING,
wtWebGraphAnalog57661PortInputMode OCTET STRING
}
wtWebGraphAnalog57661PortName OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name of the sensor."
::= { wtWebGraphAnalog57661PortEntry 1 }
wtWebGraphAnalog57661PortText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Description of the sensor."
::= { wtWebGraphAnalog57661PortEntry 2 }
wtWebGraphAnalog57661PortOffset1 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Offset calibration: Offset in degrees with maximum 3 decimal places at set point 1."
::= { wtWebGraphAnalog57661PortEntry 3 }
wtWebGraphAnalog57661SetPoint1 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Offset calibration: Reference set point 1 in degrees with maximum 3 decimal places."
::= { wtWebGraphAnalog57661PortEntry 4 }
wtWebGraphAnalog57661PortOffset2 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Offset calibration: Offset in degrees with maximum 3 decimal places at set point 2."
::= { wtWebGraphAnalog57661PortEntry 5 }
wtWebGraphAnalog57661SetPoint2 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Offset calibration: Reference set point 2 in degrees with maximum 3 decimal places."
::= { wtWebGraphAnalog57661PortEntry 6 }
wtWebGraphAnalog57661PortComment OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Offset calibration: informations of date, name of operator, reference devices."
::= { wtWebGraphAnalog57661PortEntry 7 }
wtWebGraphAnalog57661PortSensorSelect OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binary coded options for sensor 1:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : 0-20mA (default)
Bit 1 : 4-20mA
Bit 2 : Disconnect
Bit 3-7: unused"
::= { wtWebGraphAnalog57661PortEntry 8 }
wtWebGraphAnalog57661PortUnit OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"User scale: displayed unit."
::= { wtWebGraphAnalog57661PortEntry 9 }
wtWebGraphAnalog57661PortScale0 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"User scale: displayed value in 1/1000 at 0% full scale range.
Range: -999999.999 to 999999.999"
::= { wtWebGraphAnalog57661PortEntry 10 }
wtWebGraphAnalog57661PortScale100 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"User scale: displayed value in 1/1000 at 100% full scale range.
Range: -999999.999 to 999999.999"
::= { wtWebGraphAnalog57661PortEntry 11 }
wtWebGraphAnalog57661PortOutputMode OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"This binary coded output mode defines the individual operation mode for any
output. More than one mode must not be selected. If an output mode is selected,
Bit 2 in wtWebGraphAnalog57661PortInputMode will be set automatically.
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB.
OCTET 1: unused
OCTET 2: unused
OCTET 3: unused
OCTET 4: Bit 6-7: unused
Bit 5 : Output OFF
Bit 4 : Binary 2
Bit 3 : Binary 1
Bit 2 : SNMP
Bit 1 : UDP ASCII
Bit 0 : HTTP"
::= { wtWebGraphAnalog57661PortEntry 12 }
wtWebGraphAnalog57661PortInputMode OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"This binary coded input mode defines the individual operation mode for any
input. More than one mode must not be selected. If an input mode is selected,
Bit 5 in wtWebGraphAnalog57661PortOutputMode will be set automatically.
The OCTETS are interpreted bit-by-bit,Bit 0 corresponds to the LSB.
OCTET 1: ungenutzt
OCTET 2: ungenutzt
OCTET 3: ungenutzt
OCTET 4: Bit 3-7: unused
Bit 2 : I-Output
Bit 1 : I-Input, active
Bit 0 : I-Input, passive"
::= { wtWebGraphAnalog57661PortEntry 13 }
-- wtWebGraphAnalog57661Manufact Group
----------------------------
wtWebGraphAnalog57661MfName OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Manufacturer company name"
::= { wtWebGraphAnalog57661Manufact 1 }
wtWebGraphAnalog57661MfAddr OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Manufacturer address."
::= { wtWebGraphAnalog57661Manufact 2 }
wtWebGraphAnalog57661MfHotline OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Manufacturer hotline."
::= { wtWebGraphAnalog57661Manufact 3 }
wtWebGraphAnalog57661MfInternet OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Manufacturer Internet address."
::= { wtWebGraphAnalog57661Manufact 4 }
wtWebGraphAnalog57661MfDeviceTyp OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Manufacturer device name (model number)."
::= { wtWebGraphAnalog57661Manufact 5 }
wtWebGraphAnalog57661MfOrderNo OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Manufacturer part number."
::= { wtWebGraphAnalog57661Manufact 6 }
-- wtWebGraphAnalog57661Diag Group
----------------------------
wtWebGraphAnalog57661DiagErrorCount OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of entries in the error memory."
::= { wtWebGraphAnalog57661Diag 1 }
wtWebGraphAnalog57661DiagBinaryError OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Error causes coded bit-by-bit."
::= { wtWebGraphAnalog57661Diag 2 }
wtWebGraphAnalog57661DiagErrorIndex OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The value of this variable is used as an index to read
an error massege from wtWebGraphAnalog57661DiagErrorMessage.
Errors are numbered from 1 to wtWebGraphAnalog57661DiagErrorCount.
Writing a valid value into this variable, making the appropriate
message readable from wtWebGraphAnalog57661DiagErrorMessage."
::= { wtWebGraphAnalog57661Diag 3 }
wtWebGraphAnalog57661DiagErrorMessage OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Using wtWebGraphAnalog57661DiagErrorIndex as an index, the appropriate message is available."
::= { wtWebGraphAnalog57661Diag 4 }
wtWebGraphAnalog57661DiagErrorClear OBJECT-TYPE
SYNTAX INTEGER
ACCESS write-only
STATUS mandatory
DESCRIPTION
"Writing 1 into this variable clears all diagnosis messages."
::= { wtWebGraphAnalog57661Diag 5 }
-- TRAP DEFINITIONS
-- Diese SNMP-Traps werden gesendet, wenn die Alarmtriggerbedingungen zutreffen
wtWebGraphAnalog57661Alert1 TRAP-TYPE
ENTERPRISE wtWebGraphAnalog57661
VARIABLES { wtWebGraphAnalog57661AlarmTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 1 was triggered,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Web-IO Analog-InOut Alarm 1"
--#SUMMARY "Alarm 1: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 31
wtWebGraphAnalog57661Alert2 TRAP-TYPE
ENTERPRISE wtWebGraphAnalog57661
VARIABLES { wtWebGraphAnalog57661AlarmTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 2 was triggered,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Web-IO Analog-InOut Alarm 2"
--#SUMMARY "Alarm 2: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 32
wtWebGraphAnalog57661Alert3 TRAP-TYPE
ENTERPRISE wtWebGraphAnalog57661
VARIABLES { wtWebGraphAnalog57661AlarmTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 3 was triggered,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Web-IO Analog-InOut Alarm 3"
--#SUMMARY "Alarm 3: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 33
wtWebGraphAnalog57661Alert4 TRAP-TYPE
ENTERPRISE wtWebGraphAnalog57661
VARIABLES { wtWebGraphAnalog57661AlarmTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 4 was triggered,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Web-IO Analog-InOut Alarm 4"
--#SUMMARY "Alarm 4: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 34
wtWebGraphAnalog57661Alert5 TRAP-TYPE
ENTERPRISE wtWebGraphAnalog57661
VARIABLES { wtWebGraphAnalog57661AlarmTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 5 was triggered,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Web-IO Analog-InOut Alarm 5"
--#SUMMARY "Alarm 5: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 35
wtWebGraphAnalog57661Alert6 TRAP-TYPE
ENTERPRISE wtWebGraphAnalog57661
VARIABLES { wtWebGraphAnalog57661AlarmTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 6 was triggered,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Web-IO Analog-InOut Alarm 6"
--#SUMMARY "Alarm 6: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 36
wtWebGraphAnalog57661Alert7 TRAP-TYPE
ENTERPRISE wtWebGraphAnalog57661
VARIABLES { wtWebGraphAnalog57661AlarmTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 7 was triggered,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Web-IO Analog-InOut Alarm 7"
--#SUMMARY "Alarm 7: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 37
wtWebGraphAnalog57661Alert8 TRAP-TYPE
ENTERPRISE wtWebGraphAnalog57661
VARIABLES { wtWebGraphAnalog57661AlarmTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 8 was triggered,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Web-IO Analog-InOut Alarm 8"
--#SUMMARY "Alarm 8: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 38
wtWebGraphAnalog57661Alert9 TRAP-TYPE
ENTERPRISE wtWebGraphAnalog57661
VARIABLES { wtWebGraphAnalog57661AlarmClearTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 1 was cleared,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Web-IO Analog-InOut Release Alarm 1"
--#SUMMARY "Release Alarm 1: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 91
wtWebGraphAnalog57661Alert10 TRAP-TYPE
ENTERPRISE wtWebGraphAnalog57661
VARIABLES { wtWebGraphAnalog57661AlarmClearTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 2 was cleared,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Web-IO Analog-InOut Release Alarm 2"
--#SUMMARY "Release Alarm 2: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 92
wtWebGraphAnalog57661Alert11 TRAP-TYPE
ENTERPRISE wtWebGraphAnalog57661
VARIABLES { wtWebGraphAnalog57661AlarmClearTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 3 was cleared,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Web-IO Analog-InOut Release Alarm 3"
--#SUMMARY "Release Alarm 3: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 93
wtWebGraphAnalog57661Alert12 TRAP-TYPE
ENTERPRISE wtWebGraphAnalog57661
VARIABLES { wtWebGraphAnalog57661AlarmClearTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 4 was cleared,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Web-IO Analog-InOut Release Alarm 4"
--#SUMMARY "Release Alarm 4: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 94
wtWebGraphAnalog57661Alert13 TRAP-TYPE
ENTERPRISE wtWebGraphAnalog57661
VARIABLES { wtWebGraphAnalog57661AlarmClearTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 5 was cleared,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Web-IO Analog-InOut Release Alarm 5"
--#SUMMARY "Release Alarm 5: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 95
wtWebGraphAnalog57661Alert14 TRAP-TYPE
ENTERPRISE wtWebGraphAnalog57661
VARIABLES { wtWebGraphAnalog57661AlarmClearTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 6 was cleared,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Web-IO Analog-InOut Release Alarm 6"
--#SUMMARY "Release Alarm 6: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 96
wtWebGraphAnalog57661Alert15 TRAP-TYPE
ENTERPRISE wtWebGraphAnalog57661
VARIABLES { wtWebGraphAnalog57661AlarmClearTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 7 was cleared,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Web-IO Analog-InOut Release Alarm 7"
--#SUMMARY "Release Alarm 7: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 97
wtWebGraphAnalog57661Alert16 TRAP-TYPE
ENTERPRISE wtWebGraphAnalog57661
VARIABLES { wtWebGraphAnalog57661AlarmClearTrapText }
DESCRIPTION
"This SNMP trap is generated when Alarm 8 was cleared,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Web-IO Analog-InOut Release Alarm 8"
--#SUMMARY "Release Alarm 8: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 98
wtWebGraphAnalog57661AlertReport TRAP-TYPE
ENTERPRISE wtWebGraphAnalog57661
VARIABLES { wtWebGraphAnalog57661AlarmTrapText }
DESCRIPTION
"This SNMP trap is generated when the report was triggered,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Web-IO Analog-InOut Report"
--#SUMMARY "Report: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 39
wtWebGraphAnalog57661AlertDiag TRAP-TYPE
ENTERPRISE wtWebGraphAnalog57661
VARIABLES {
wtWebGraphAnalog57661DiagErrorIndex,
wtWebGraphAnalog57661DiagErrorMessage
}
DESCRIPTION
"This SNMP trap is generated when a diagnosis/error message was triggered,
SNMP trap enable is set and
SNMP is enabled."
-- NMS trap annotation
--#TYPE "Web-IO Analog-InOut Diagnose Error"
--#SUMMARY "Diagnose error index: %d, Message: %s."
--#ARGUMENTS {0,1}
--#SEVERITY MAJOR
--#TIMEINDEX 99
--#STATE DEGRADED
::= 110
END