-- -- defines STS.mib for XPort-SNMP agent -- -- Mib is used for STS Units -- -- Eltek Valere Industrial GmbH - Enterprise 16640 -- renamed from CONVERTRONIC OIDs - Enterprise 16640 -- Version: 1.01 -- Date: 08 January, 2008 -- Developed By: Michael Schulz -- Software Engineer -- Eltek Valere Industrial GmbH -- -- Version: 1.02 -- Date: 18 June, 2009 -- Developed By: Christian Fisch -- Software Engineer -- Eltek Valere Industrial GmbH -- -- Update 18.06.2009: -- Fix: trap definition string "" instead of " -- -- -- Update 25.09.2008: -- Change inv_OutVoltage to inv_InputVoltage -- add text "Bit_" for direct info, this is a Bit-Information -- inv_Bit_ShortCircuit, inv_Bit_OutputVoltage, inv_Bit_InputVoltLow, inv_Bit_InputVoltHigh, -- inv_Bit_OutputVoltLow, inv_Bit_OutputVoltHigh, inv_Bit_OutputCurrHigh, inv_Bit_RemoteOff -- inv_Bit_CentralAlarm -- -- Update 07.10.2008: -- Change trap-descriptions: Modification for HP OpenView -- -- Version: 1.03 -- Date: 06 Jan., 2010 -- Developed By: Dirk Meise-Reckefuss -- Software Engineer -- Eltek Valere Industrial GmbH -- -- Copyright (c) 2010 Eltek Valere Industrial GmbH. -- STS_SEQUENZ-MIB DEFINITIONS ::= BEGIN IMPORTS enterprises, IpAddress, Counter, TimeTicks FROM RFC1155-SMI OBJECT-TYPE FROM RFC-1212 TRAP-TYPE FROM RFC-1215 DisplayString FROM RFC1213-MIB; convertronic OBJECT IDENTIFIER ::= { enterprises 16460 } sts_system MODULE-IDENTITY LAST-UPDATED "201001061200Z" -- Jan. 06 2010 12:00:00 EST ORGANIZATION "Eltek Valere Industrial GmbH" CONTACT-INFO "Michael Schulz Eltek Valere Industrial GmbH Im Obrock 33 D-32278 Kirchlengern Tel: +49 5223 7641 450 Fax: +49 5223 7641 222 E-mail: michael.schulz@eltekvalere.com" DESCRIPTION "The MIB module to describe all object of STS Unit " -- sts_system OBJECT IDENTIFIER ::= { convertronic 4 } measureValues OBJECT IDENTIFIER ::= { sts_system 1 } settings OBJECT IDENTIFIER ::= { sts_system 2 } extendedSettings OBJECT IDENTIFIER ::= { sts_system 3 } tables OBJECT IDENTIFIER ::= { sts_system 4 } traps OBJECT IDENTIFIER ::= { sts_system 5 } sts_measureValues OBJECT IDENTIFIER ::= { measureValues 1 } inverter_measureValues OBJECT IDENTIFIER ::= { measureValues 2 } networkSettings OBJECT IDENTIFIER ::= { settings 1 } unitSettings OBJECT IDENTIFIER ::= { settings 2 } netSyncronisationSet OBJECT IDENTIFIER ::= { extendedSettings 1 } adjustValues OBJECT IDENTIFIER ::= { extendedSettings 2 } baseSettings OBJECT IDENTIFIER ::= { networkSettings 1 } serviceSettings OBJECT IDENTIFIER ::= { networkSettings 2 } basicSettings OBJECT IDENTIFIER ::= { unitSettings 1 } advancedSettings OBJECT IDENTIFIER ::= { unitSettings 2 } advancedSettings2 OBJECT IDENTIFIER ::= { unitSettings 3 } -- **************************************** -- **************************************** -- **************************************** sVal_UN OBJECT-TYPE SYNTAX INTEGER(0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "Mains voltage (V), Value: 230(230V)" ::= { sts_measureValues 1 } sVal_FreqNetz OBJECT-TYPE SYNTAX INTEGER(0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "Mains frequency (Hz), Value: 50(50Hz)" ::= { sts_measureValues 2 } sVal_UWR OBJECT-TYPE SYNTAX INTEGER(0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "Inverter voltage (V), Value: 230(230V)" ::= { sts_measureValues 3 } sVal_FreqWR OBJECT-TYPE SYNTAX INTEGER(0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "Inverter frequency (Hz), Value: 50(50Hz)" ::= { sts_measureValues 4 } sVal_UDC OBJECT-TYPE SYNTAX INTEGER(0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "Battery voltage (V), Value: 120(12V)" ::= { sts_measureValues 5 } sVal_U10 OBJECT-TYPE SYNTAX INTEGER(0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "STS Output Voltage (V), Value: 230(230V)" ::= { sts_measureValues 6 } sVal_IO1 OBJECT-TYPE SYNTAX INTEGER(0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "STS Output current (A), Value: 15(15A)" ::= { sts_measureValues 7 } sVal_P OBJECT-TYPE SYNTAX INTEGER(0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "STS active power (W), Value: 2105(2105W)" ::= { sts_measureValues 8 } sVal_S OBJECT-TYPE SYNTAX INTEGER(0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "STS apparent power (VA), Value: 495(495VA)" ::= { sts_measureValues 9 } sVal_FAN1 OBJECT-TYPE SYNTAX INTEGER(0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "Fan 1 speed (rpm), Value: 4200(4200rpm)" ::= { sts_measureValues 10 } sVal_FAN2 OBJECT-TYPE SYNTAX INTEGER(0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "Fan 2 speed (rpm), Value: 3800(3800rpm)" ::= { sts_measureValues 11 } sVal_TK OBJECT-TYPE SYNTAX INTEGER(0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "STS temperature (°C), Value: 301(30,1°C)" ::= { sts_measureValues 12 } sVal_IO2 OBJECT-TYPE SYNTAX INTEGER(0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "STS output current 2 (A), Value: 18(18A)" ::= { sts_measureValues 13 } sVal_IDC OBJECT-TYPE SYNTAX INTEGER(0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "battery output current (A), Value: 24(24A)" ::= { sts_measureValues 14 } -- **************************************** -- **************************************** -- **************************************** bETHSpeed OBJECT-TYPE SYNTAX INTEGER(0..4) ACCESS read-write STATUS mandatory DESCRIPTION "Communication speed setting: Value: 0= autonegotation 1= 10Mb Halfduplex 2= 10Mb Fullduplex 3= 100Mb Halfduplex 4= 100Mb Fullduplex" ::= { baseSettings 1 } bLocalIP OBJECT-TYPE SYNTAX IpAddress ACCESS read-write STATUS mandatory DESCRIPTION "IP-Adress of the Unit, Value: xxx.xxx.xxx.xxx" ::= { baseSettings 2 } bSubnetMask OBJECT-TYPE SYNTAX IpAddress ACCESS read-write STATUS mandatory DESCRIPTION "Used Subnetmask of the Unit, Value: xxx.xxx.xxx.xxx" ::= { baseSettings 3 } bGateway OBJECT-TYPE SYNTAX IpAddress ACCESS read-write STATUS mandatory DESCRIPTION "IP of the used Gateway, Value: xxx.xxx.xxx.xxx" ::= { baseSettings 4 } bDNSServer OBJECT-TYPE SYNTAX IpAddress ACCESS read-write STATUS mandatory DESCRIPTION "IP of the used Domain Name Service Server, Value: xxx.xxx.xxx.xxx" ::= { baseSettings 5 } bDHCPServer OBJECT-TYPE SYNTAX DisplayString (SIZE (0..16)) ACCESS read-write STATUS mandatory DESCRIPTION "Name of the DHCP-Server to use, Value: max. 16 char." ::= { baseSettings 6 } bFixedIP_OnOff OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Use Fixed connection settings, Value: 1= Use IP set with LocalIP 0= Use automatic IP-Configuration" ::= { baseSettings 7 } bDefaultIP_OnOff OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Usue Fix IP, Value: 0= off 1= Use IP 192.168.0.10" ::= { baseSettings 8 } bDHCP_OnOff OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION " Value: 0= off 1= Use DHCP for automatic Network configuration" ::= { baseSettings 9 } bBOOTP_OnOff OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION " Value: 0= off 1= Use BOOTP for automatic Network configuration" ::= { baseSettings 10 } bLocation OBJECT-TYPE SYNTAX DisplayString (SIZE (0..16)) ACCESS read-write STATUS mandatory DESCRIPTION "Location of the seen Unit, Value: max. 16 char." ::= { baseSettings 11 } -- **************************************** -- **************************************** -- **************************************** servSNMP_OnOff OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Use Simple Network Management Protocol, Value: 0= off 1= on" ::= { serviceSettings 1 } servTrapReceiver1 OBJECT-TYPE SYNTAX IpAddress ACCESS read-write STATUS mandatory DESCRIPTION "IP of SNMP-Trapreceiver 1, Value: xxx.xxx.xxx.xxx" ::= { serviceSettings 2 } servTrapReceiver2 OBJECT-TYPE SYNTAX IpAddress ACCESS read-write STATUS mandatory DESCRIPTION "IP of SNMP-Trapreceiver 2, Value: xxx.xxx.xxx.xxx" ::= { serviceSettings 3 } servTrapReceiver3 OBJECT-TYPE SYNTAX IpAddress ACCESS read-write STATUS mandatory DESCRIPTION "IP of SNMP-Trapreceiver 3, Value: xxx.xxx.xxx.xxx" ::= { serviceSettings 4 } servTrapReceiver4 OBJECT-TYPE SYNTAX IpAddress ACCESS read-write STATUS mandatory DESCRIPTION "IP of SNMP-Trapreceiver 4, Value: xxx.xxx.xxx.xxx" ::= { serviceSettings 5 } servReadCommunity OBJECT-TYPE SYNTAX DisplayString (SIZE (0..13)) ACCESS read-write STATUS mandatory DESCRIPTION "SNMP read community, Value: max. 13 char." ::= { serviceSettings 6 } servWriteCommunity OBJECT-TYPE SYNTAX DisplayString (SIZE (0..13)) ACCESS read-write STATUS mandatory DESCRIPTION "SNMP write community, Value: max. 13 char." ::= { serviceSettings 7 } servSMTP_OnOff OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Use Simple Mail Transfer Protocol, Value: 0= off 1= on" ::= { serviceSettings 8 } servMailServer OBJECT-TYPE SYNTAX DisplayString (SIZE (0..19)) ACCESS read-write STATUS mandatory DESCRIPTION "Ip or Name of the used mailserver, Value: max. 19 char." ::= { serviceSettings 9 } servMailUsername OBJECT-TYPE SYNTAX DisplayString (SIZE (0..10)) ACCESS read-write STATUS mandatory DESCRIPTION "Username for the mailserver, Value: max. 10 char." ::= { serviceSettings 10 } servMailPassword OBJECT-TYPE SYNTAX DisplayString (SIZE (0..10)) ACCESS read-write STATUS mandatory DESCRIPTION "Password for the mailserver, Value: max. 10 char." ::= { serviceSettings 11 } servMailReceiver1 OBJECT-TYPE SYNTAX DisplayString (SIZE (0..48)) ACCESS read-write STATUS mandatory DESCRIPTION "First receiver e-mail address, Value: max. 48 char." ::= { serviceSettings 12 } servMailTrapLevel1 OBJECT-TYPE SYNTAX INTEGER(0..3) ACCESS read-write STATUS mandatory DESCRIPTION "Traplevel for first mailreceiver, Value: 0= Off ... 3= send maximum Traps" ::= { serviceSettings 13 } servMailReceiver2 OBJECT-TYPE SYNTAX DisplayString (SIZE (0..48)) ACCESS read-write STATUS mandatory DESCRIPTION "second receiver e-mail address, Value: max. 48 char." ::= { serviceSettings 14 } servMailTrapLevel2 OBJECT-TYPE SYNTAX INTEGER(0..3) ACCESS read-write STATUS mandatory DESCRIPTION "Traplevel for second mailreceiver, Value: 0= Off ... 3= send maximum Traps" ::= { serviceSettings 15 } servSNTP_OnOff OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Simple Network Time Protocol, Value: 0= off 1= on" ::= { serviceSettings 16 } servSNTPServer1 OBJECT-TYPE SYNTAX DisplayString (SIZE (0..19)) ACCESS read-write STATUS mandatory DESCRIPTION "IP or name for first SNTP server, Value: max. 19 char." ::= { serviceSettings 17 } servSNTPServer2 OBJECT-TYPE SYNTAX DisplayString (SIZE (0..19)) ACCESS read-write STATUS mandatory DESCRIPTION "IP or name for second SNTP server, Value: max. 19 char." ::= { serviceSettings 18 } servTelnet_OnOff OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Configuration over Telnet, Value: 0= off 1= on" ::= { serviceSettings 19 } servSyslog_OnOff OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Syslog feature, Value: 0= off 1= on" ::= { serviceSettings 20 } -- **************************************** -- **************************************** -- **************************************** sts_Version OBJECT-TYPE SYNTAX INTEGER(0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "STS Software version, Value: 99(Ver 0.99)" ::= { basicSettings 1 } sts_Inverter OBJECT-TYPE SYNTAX INTEGER(0..15) ACCESS read-write STATUS mandatory DESCRIPTION "STS count of needed inverter, Value: 0 - 15" ::= { basicSettings 2 } sts_SigCF_b0 OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Central failure signal: Source 1 failure, Value: 0= off 1= on" ::= { basicSettings 3 } sts_SigCF_b1 OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Central failure signal: Source 2 failure, Value: 0= off 1= on" ::= { basicSettings 4 } sts_SigCF_b2 OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Central failure signal: Syncronisation error, Value: 0= off 1= on" ::= { basicSettings 5 } sts_SigCF_b3 OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Central failure signal: Inverter failure, Value: 0= off 1= on" ::= { basicSettings 6 } sts_SigCF_b4 OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Central failure signal: STS overtemperature, Value: 0= off 1= on" ::= { basicSettings 7 } sts_SigCF_b5 OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Central failure signal: STS overload, Value: 0= off 1= on" ::= { basicSettings 8 } sts_SigCF_b6 OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Central failure signal: Inverter overload, Value: 0= off 1= on" ::= { basicSettings 9 } sts_SigCF_b7 OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Central failure signal: DC voltage low, Value: 0= off 1= on" ::= { basicSettings 10 } sts_SigCF_b8 OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Central failure signal: DC voltage high, Value: 0= off 1= on" ::= { basicSettings 11 } sts_SigCF_b9 OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Central failure signal: U batterie< warning, Value: 0= off 1= on" ::= { basicSettings 12 } sts_SigCF_b10 OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Central failure signal: U batterie> warning, Value: 0= off 1= on" ::= { basicSettings 13 } sts_SigCF_b11 OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Central failure signal: Fan error, Value: 0= off 1= on" ::= { basicSettings 14 } sts_SigCF_b12 OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Central failure signal: future use" ::= { basicSettings 15 } sts_SigCF_b13 OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Central failure signal: future use" ::= { basicSettings 16 } sts_SigCF_b14 OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Central failure signal: future use" ::= { basicSettings 17 } sts_SigCF_b15 OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Central failure signal: future use" ::= { basicSettings 18 } sts_DelayRelCA OBJECT-TYPE SYNTAX INTEGER(1..60) ACCESS read-write STATUS mandatory DESCRIPTION "Delay of the Central failure relay signaling, Value: 1(1sec.) ... 60(60sec.)" ::= { basicSettings 19 } sts_DelayLEDCA OBJECT-TYPE SYNTAX INTEGER(1..60) ACCESS read-write STATUS mandatory DESCRIPTION "Delay of the Central failure LED signaling, Value: 1(1sec.) ... 60(60sec.)" ::= { basicSettings 20 } sts_LCDContrast OBJECT-TYPE SYNTAX INTEGER(0..100) ACCESS read-write STATUS mandatory DESCRIPTION "LCD contrast from 0% to 100%. Use 10% steps, Value: 0(0%) 10 (10%) 20(20%) ... 90(90%) 100(100%)" ::= { basicSettings 21 } sts_Language OBJECT-TYPE SYNTAX INTEGER(0..4) ACCESS read-write STATUS mandatory DESCRIPTION "LCD Language, Value: 0= English 1= German 2= Polish 3= Swedish 4= Italian" ::= { basicSettings 22 } -- **************************************** -- **************************************** -- **************************************** sts_OpMode OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Operation mode, Value: 0= Inverter priority 1= Mains priority" ::= { advancedSettings 1 } sts_UpperSwitchLimS1 OBJECT-TYPE SYNTAX INTEGER(5..20) ACCESS read-write STATUS mandatory DESCRIPTION "Source 1 upper switch limit in % of nominal voltage, Value: 5(5%) ... 20(20%)" ::= { advancedSettings 2 } sts_LowerSwitchLimS1 OBJECT-TYPE SYNTAX INTEGER(5..20) ACCESS read-write STATUS mandatory DESCRIPTION "Source 1 lower switch limit in % of nominal voltage, Value: 5(5%) ... 20(20%)" ::= { advancedSettings 3 } sts_SwitchDelayS1 OBJECT-TYPE SYNTAX INTEGER(1..8) ACCESS read-write STATUS mandatory DESCRIPTION "Source 1 switching delay, if source 1 leave limits, Value: 1= 0.5ms 2= 1.0ms 3= 1.5ms 4= 2.0ms 5= 2.5ms 6= 3.0ms 7= 3.5ms 8= 4.0ms" ::= { advancedSettings 4 } sts_UpperSwitchLimS2 OBJECT-TYPE SYNTAX INTEGER(5..20) ACCESS read-write STATUS mandatory DESCRIPTION "Source 2 upper switch limit in % of nominal voltage, Value: 5(5%) ... 20(20%)" ::= { advancedSettings 5 } sts_LowerSwitchLimS2 OBJECT-TYPE SYNTAX INTEGER(5..20) ACCESS read-write STATUS mandatory DESCRIPTION "Source 2 lower switch limit in % of nominal voltage, Value: 5(5%) ... 20(20%)" ::= { advancedSettings 6 } sts_SwitchDelayS2 OBJECT-TYPE SYNTAX INTEGER(1..8) ACCESS read-write STATUS mandatory DESCRIPTION "Source 2 switching delay, if source 2 leave limits, Value: 1= 0.5ms 2= 1.0ms 3= 1.5ms 4= 2.0ms 5= 2.5ms 6= 3.0ms 7= 3.5ms 8= 4.0ms" ::= { advancedSettings 7 } sts_MaxCellVolt1 OBJECT-TYPE SYNTAX INTEGER(200..300) ACCESS read-write STATUS mandatory DESCRIPTION "Umax1 voltage/cell 2,0V - 3,0V, Value: 200(2,0V) ... 300(3,0V)" ::= { advancedSettings 8 } sts_MinCellVolt1 OBJECT-TYPE SYNTAX INTEGER(70..250) ACCESS read-write STATUS mandatory DESCRIPTION "Umin1 voltage/cell 0,7V - 2,5V, Value: 70(0,7V) ... 250(2,5V)" ::= { advancedSettings 9 } sts_MinCellVolt2 OBJECT-TYPE SYNTAX INTEGER(60..250) ACCESS read-write STATUS mandatory DESCRIPTION "Umin2 voltage/cell 0,6V - 2,5V, Value: 60(0,6V) ... 250(2,5V)" ::= { advancedSettings 10 } sts_MinULimit OBJECT-TYPE SYNTAX INTEGER(170..210) ACCESS read-write STATUS mandatory DESCRIPTION "Lower limit voltage/cell for generating error, 1,7V - 2,1V, Value: 170(1,7V) ... 210(2,1V)" ::= { advancedSettings 11 } sts_MaxULimit OBJECT-TYPE SYNTAX INTEGER(220..250) ACCESS read-write STATUS mandatory DESCRIPTION "Upper limit voltage/cell for generating error, 2,2V - 2,5V, Value: 220(2,2V) ... 250(2,5V)" ::= { advancedSettings 12 } -- **************************************** -- **************************************** -- **************************************** sts_NomPower OBJECT-TYPE SYNTAX INTEGER(120..500) ACCESS read-write STATUS mandatory DESCRIPTION "Power 1,2KVA - 5KVA, Value: 120(1,2KVA) ... 500(5KVA)" ::= { advancedSettings2 1 } sts_NomVolt OBJECT-TYPE SYNTAX INTEGER(200..250) ACCESS read-write STATUS mandatory DESCRIPTION "Nominal voltage 200VAC - 250VAC, Value: 200(200VAC) ... 250(250VAC)" ::= { advancedSettings2 2 } sts_NomFreq OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Nominal frequency 50Hz or 60Hz, Value: 0= 50Hz 1= 60Hz" ::= { advancedSettings2 3 } sts_FreqRange OBJECT-TYPE SYNTAX INTEGER(1..20) ACCESS read-write STATUS mandatory DESCRIPTION "Frequency range 0,1Hz - 2,0Hz, Value: 1(0,1Hz) ... 20(2,0Hz)" ::= { advancedSettings2 4 } sts_MaxCurrent OBJECT-TYPE SYNTAX INTEGER(10..2500) ACCESS read-write STATUS mandatory DESCRIPTION "Max output current 1,0A - 250A, Value: 10(1,0A) ... 2500(250A)" ::= { advancedSettings2 5 } sts_PresentCell OBJECT-TYPE SYNTAX INTEGER(12..200) ACCESS read-write STATUS mandatory DESCRIPTION "Number of present battery cell 12 - 200, Value: 12 ... 200" ::= { advancedSettings2 6 } sts_CellVoltage OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Voltage per Cell, Value: 0=2.0V 1=1.2V" ::= { advancedSettings2 7 } sts_Adress OBJECT-TYPE SYNTAX INTEGER(0..31) ACCESS read-write STATUS mandatory DESCRIPTION "" ::= { advancedSettings2 8 } sts_SigRel2_b0 OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Relay 2 failure signal: Source 1 failure, Value: 0= off 1= on" ::= { advancedSettings2 9 } sts_SigRel2_b1 OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Relay 2 failure signal: Source 2 failure, Value: 0= off 1= on" ::= { advancedSettings2 10 } sts_SigRel2_b2 OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Relay 2 failure signal: Syncronisation error, Value: 0= off 1= on" ::= { advancedSettings2 11 } sts_SigRel2_b3 OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Relay 2 failure signal: Inverter failure, Value: 0= off 1= on" ::= { advancedSettings2 12 } sts_SigRel2_b4 OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Relay 2 failure signal: STS overtemperature, Value: 0= off 1= on" ::= { advancedSettings2 13 } sts_SigRel2_b5 OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Relay 2 failure signal: STS overload, Value: 0= off 1= on" ::= { advancedSettings2 14 } sts_SigRel2_b6 OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Relay 2 failure signal: Inverter overload, Value: 0= off 1= on" ::= { advancedSettings2 15 } sts_SigRel2_b7 OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Relay 2 failure signal: DC voltage low, Value: 0= off 1= on" ::= { advancedSettings2 16 } sts_SigRel2_b8 OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Relay 2 failure signal: DC voltage high, Value: 0= off 1= on" ::= { advancedSettings2 17 } sts_SigRel2_b9 OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Relay 2 failure signal: U batterie< warning, Value: 0= off 1= on" ::= { advancedSettings2 18 } sts_SigRel2_b10 OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Relay 2 failure signal: U batterie> warning, Value: 0= off 1= on" ::= { advancedSettings2 19 } sts_SigRel2_b11 OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Relay 2 failure signal: Fan error, Value: 0= off 1= on" ::= { advancedSettings2 20 } sts_SigRel2_b12 OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Relay 2 failure signal: future use" ::= { advancedSettings2 21 } sts_SigRel2_b13 OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Relay 2 failure signal: future use" ::= { advancedSettings2 22 } sts_SigRel2_b14 OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Relay 2 failure signal: future use" ::= { advancedSettings2 23 } sts_SigRel2_b15 OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Relay 2 failure signal: future use" ::= { advancedSettings2 24 } sts_ModeRel2 OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS read-write STATUS mandatory DESCRIPTION "Relay 2 mode, Value: 0= normal operation 1= inverted operation" ::= { advancedSettings2 25 } sts_DelayRel2 OBJECT-TYPE SYNTAX INTEGER(1..60) ACCESS read-write STATUS mandatory DESCRIPTION "Delay of relay 2 signaling 1sec. - 60sec., Value: 1(1sec.) ... 60(60sec.)" ::= { advancedSettings2 26 } sts_OverTemp OBJECT-TYPE SYNTAX INTEGER(358..358) ACCESS read-only STATUS mandatory DESCRIPTION "STS Overtemperature 85(°C), Value: 85(85°C)" ::= { advancedSettings2 27 } -- **************************************** -- **************************************** -- **************************************** net_EdgeDetectionDelay OBJECT-TYPE SYNTAX INTEGER(0..20) ACCESS read-write STATUS mandatory DESCRIPTION "Edge detection delay 0ms - 20ms, Value: 0(0ms) ... 20(20ms)" ::= { netSyncronisationSet 1 } net_TimeOutDelay OBJECT-TYPE SYNTAX INTEGER(0..20) ACCESS read-write STATUS mandatory DESCRIPTION "Timeout delay 0ms - 20ms, Value: 0(0ms) ... 20(20ms)" ::= { netSyncronisationSet 2 } net_MaxCorrPhi OBJECT-TYPE SYNTAX INTEGER(1..255) ACCESS read-write STATUS mandatory DESCRIPTION "Max correction cosinus Phi. 333ns - 84915ns (1dig.=>333ns), Value: 1(333ns) ... 255(84915ns)" ::= { netSyncronisationSet 3 } net_DivDeltaPhi OBJECT-TYPE SYNTAX INTEGER(0..8) ACCESS read-write STATUS mandatory DESCRIPTION "1 - 1/256, Value: 0=1 1=1/2 2=1/4 3=1/8 4=1/16 5=1/32 6=1/64 7=1/128 8=1/256" ::= { netSyncronisationSet 4 } net_DivCorrPhi_I OBJECT-TYPE SYNTAX INTEGER(0..8) ACCESS read-write STATUS mandatory DESCRIPTION " 1 - 1/256, Value: 0=1 1=1/2 2=1/4 3=1/8 4=1/16 5=1/32 6=1/64 7=1/128 8=1/256" ::= { netSyncronisationSet 5 } net_MaxCorrT OBJECT-TYPE SYNTAX INTEGER(1..255) ACCESS read-write STATUS mandatory DESCRIPTION "333ns - 84915ns (1dig.=>333ns), Value: 1(333ns) ... 255(84915ns)" ::= { netSyncronisationSet 6 } net_DivDeltaT OBJECT-TYPE SYNTAX INTEGER(0..8) ACCESS read-write STATUS mandatory DESCRIPTION "1 - 1/256, Value: 0=1 1=1/2 2=1/4 3=1/8 4=1/16 5=1/32 6=1/64 7=1/128 8=1/256" ::= { netSyncronisationSet 7 } net_SyncOKNr OBJECT-TYPE SYNTAX INTEGER(1..255) ACCESS read-write STATUS mandatory DESCRIPTION "1 - 255, Value: 1 ... 255" ::= { netSyncronisationSet 8 } net_SyncErrorNr OBJECT-TYPE SYNTAX INTEGER(1..255) ACCESS read-write STATUS mandatory DESCRIPTION "1 - 255, Value: 1 ... 255" ::= { netSyncronisationSet 9 } net_P_Diff OBJECT-TYPE SYNTAX INTEGER(150..15000) ACCESS read-write STATUS mandatory DESCRIPTION "150 - 1500, Value: 150 ... 1500" ::= { netSyncronisationSet 10 } -- **************************************** -- **************************************** -- **************************************** adj_UMains OBJECT-TYPE SYNTAX INTEGER(368..432) ACCESS read-write STATUS mandatory DESCRIPTION "" ::= { adjustValues 1 } adj_UInv OBJECT-TYPE SYNTAX INTEGER(368..432) ACCESS read-write STATUS mandatory DESCRIPTION "" ::= { adjustValues 2 } adj_UDC OBJECT-TYPE SYNTAX INTEGER(1372..1628) ACCESS read-write STATUS mandatory DESCRIPTION "" ::= { adjustValues 3 } adj_Uout OBJECT-TYPE SYNTAX INTEGER(368..432) ACCESS read-write STATUS mandatory DESCRIPTION "" ::= { adjustValues 4 } adj_Iout OBJECT-TYPE SYNTAX INTEGER(1988..3012) ACCESS read-write STATUS mandatory DESCRIPTION "" ::= { adjustValues 5 } -- **************************************** -- **************************************** -- **************************************** -- **************************************** -- **************************************** -- **************************************** trapLastMessageStringTest OBJECT-TYPE SYNTAX OCTET STRING ACCESS not-accessible STATUS mandatory DESCRIPTION "Message giving more detailed information on alarms." ::= { traps 1 } trapLastMessageNbrTest OBJECT-TYPE SYNTAX INTEGER(16..46) ACCESS not-accessible STATUS mandatory DESCRIPTION "Referenced Trap number" ::= { traps 2 } trapSourceIPTest OBJECT-TYPE SYNTAX IpAddress ACCESS not-accessible STATUS mandatory DESCRIPTION "Alarm Source IP address" ::= { traps 3 } -- source_mains_failue_present NOTIFICATION-TYPE -- STATUS obsolete -- DESCRIPTION "Error with Source mains present" -- ::= { traps 17 } trap_source_mains_failue_present OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS not-accessible STATUS mandatory DESCRIPTION "STS mains failure present" ::= { traps 17 } source_mains_failue_present_trap TRAP-TYPE ENTERPRISE convertronic VARIABLES { trap_source_mains_failue_present, trapLastMessageStringTest, trapLastMessageNbrTest, trapSourceIPTest } DESCRIPTION "Error with Source mains present" -- NMS trap annotation --#TYPE "Error with Source mains present" --#SUMMARY "Failure %d, Text: %s, No: %d." --#ARGUMENTS {0,1,2} --#SEVERITY MAJOR --#TIMEINDEX 99 --#STATE OPERATIONAL ::= 16 -- source_inverter_failure_present NOTIFICATION-TYPE -- STATUS mandatory -- DESCRIPTION "Error with Source inverter present" -- ::= { traps 18 } trap_source_inverter_failure_present OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS not-accessible STATUS mandatory DESCRIPTION "STS inverter source failure present" ::= { traps 18 } source_inverter_failure_present TRAP-TYPE ENTERPRISE convertronic VARIABLES { trap_source_inverter_failure_present, trapLastMessageStringTest, trapLastMessageNbrTest, trapSourceIPTest } DESCRIPTION "Error with Source inverter present" -- NMS trap annotation --#TYPE "Error with Source inverter present" --#SUMMARY "Failure %d, Text: %s, No: %d." --#ARGUMENTS {0,1,2} --#SEVERITY MAJOR --#TIMEINDEX 99 --#STATE OPERATIONAL ::= 17 -- -- syncronisation_error_present NOTIFICATION-TYPE -- STATUS mandatory -- DESCRIPTION "Syncronisation between Source Mains and Source Inverter lost" -- ::= { traps 19 } trap_syncronisation_error_present OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS not-accessible STATUS mandatory DESCRIPTION "STS syncronisation error present" ::= { traps 19 } syncronisation_error_present TRAP-TYPE ENTERPRISE convertronic VARIABLES { trap_syncronisation_error_present, trapLastMessageStringTest, trapLastMessageNbrTest, trapSourceIPTest } DESCRIPTION "Syncronisation between Source Mains and Source Inverter lost" -- NMS trap annotation --#TYPE "Syncronisation between Source Mains and Source Inverter lost" --#SUMMARY "Failure %d, Text: %s, No: %d." --#ARGUMENTS {0,1,2} --#SEVERITY MAJOR --#TIMEINDEX 99 --#STATE OPERATIONAL ::= 18 -- -- inverter_failure_present NOTIFICATION-TYPE -- STATUS mandatory -- DESCRIPTION "Inverter failure active" -- ::= { traps 20 } trap_inverter_failure_present OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS not-accessible STATUS mandatory DESCRIPTION "STS inverter failure present" ::= { traps 20 } inverter_failure_present TRAP-TYPE ENTERPRISE convertronic VARIABLES { trap_inverter_failure_present, trapLastMessageStringTest, trapLastMessageNbrTest, trapSourceIPTest } DESCRIPTION "Inverter failure active" -- NMS trap annotation --#TYPE "Inverter failure active" --#SUMMARY "Failure %d, Text: %s, No: %d." --#ARGUMENTS {0,1,2} --#SEVERITY MAJOR --#TIMEINDEX 99 --#STATE OPERATIONAL ::= 19 -- -- no_redundant_inverter_present NOTIFICATION-TYPE -- STATUS mandatory -- DESCRIPTION "No more redundant inverter present" -- ::= { traps 21 } trap_no_redundant_inverter_present OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS not-accessible STATUS mandatory DESCRIPTION "STS no redundant inverter present" ::= { traps 21 } no_redundant_inverter_present TRAP-TYPE ENTERPRISE convertronic VARIABLES { trap_no_redundant_inverter_present, trapLastMessageStringTest, trapLastMessageNbrTest, trapSourceIPTest } DESCRIPTION "No more redundant inverter present" -- NMS trap annotation --#TYPE "No more redundant inverter present" --#SUMMARY "Failure %d, Text: %s, No: %d." --#ARGUMENTS {0,1,2} --#SEVERITY MINOR --#TIMEINDEX 99 --#STATE OPERATIONAL ::= 20 -- -- critical_inverter_quantity_present NOTIFICATION-TYPE -- STATUS mandatory -- DESCRIPTION "Inverter quantity is lower than needed" -- ::= { traps 22 } trap_critical_inverter_quantity_present OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS not-accessible STATUS mandatory DESCRIPTION "STS critical inverter quantity present" ::= { traps 22 } critical_inverter_quantity_present TRAP-TYPE ENTERPRISE convertronic VARIABLES { trap_critical_inverter_quantity_present, trapLastMessageStringTest, trapLastMessageNbrTest, trapSourceIPTest } DESCRIPTION "Inverter quantity is lower than needed" -- NMS trap annotation --#TYPE "Inverter quantity is lower than needed" --#SUMMARY "Failure %d, Text: %s, No: %d." --#ARGUMENTS {0,1,2} --#SEVERITY MAJOR --#TIMEINDEX 99 --#STATE OPERATIONAL ::= 21 -- -- sts_overtemperature_present NOTIFICATION-TYPE -- STATUS mandatory -- DESCRIPTION "STS temperature warning is active" -- ::= { traps 23 } trap_sts_overtemperature_present OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS not-accessible STATUS mandatory DESCRIPTION "STS sts overtemperature present" ::= { traps 23 } sts_overtemperature_present TRAP-TYPE ENTERPRISE convertronic VARIABLES { trap_sts_overtemperature_present, trapLastMessageStringTest, trapLastMessageNbrTest, trapSourceIPTest } DESCRIPTION "STS temperature warning is active" -- NMS trap annotation --#TYPE "STS temperature warning is active" --#SUMMARY "Failure %d, Text: %s, No: %d." --#ARGUMENTS {0,1,2} --#SEVERITY MAJOR --#TIMEINDEX 99 --#STATE OPERATIONAL ::= 22 -- -- sts_overload_present NOTIFICATION-TYPE -- STATUS mandatory -- DESCRIPTION "STS overload is active" -- ::= { traps 24 } trap_sts_overload_present OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS not-accessible STATUS mandatory DESCRIPTION "STS sts overload present" ::= { traps 24 } sts_overload_present TRAP-TYPE ENTERPRISE convertronic VARIABLES { trap_sts_overload_present, trapLastMessageStringTest, trapLastMessageNbrTest, trapSourceIPTest } DESCRIPTION "STS overload is active" -- NMS trap annotation --#TYPE "STS overload is active" --#SUMMARY "Failure %d, Text: %s, No: %d." --#ARGUMENTS {0,1,2} --#SEVERITY MAJOR --#TIMEINDEX 99 --#STATE OPERATIONAL ::= 23 -- -- inverter_overload_present NOTIFICATION-TYPE -- STATUS mandatory -- DESCRIPTION "Inverter overload is active" -- ::= { traps 25 } trap_inverter_overload_present OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS not-accessible STATUS mandatory DESCRIPTION "STS inverter overload present" ::= { traps 25 } inverter_overload_present TRAP-TYPE ENTERPRISE convertronic VARIABLES { trap_inverter_overload_present, trapLastMessageStringTest, trapLastMessageNbrTest, trapSourceIPTest } DESCRIPTION "Inverter overload is active" -- NMS trap annotation --#TYPE "Inverter overload is active" --#SUMMARY "Failure %d, Text: %s, No: %d." --#ARGUMENTS {0,1,2} --#SEVERITY MAJOR --#TIMEINDEX 99 --#STATE OPERATIONAL ::= 24 -- -- sts_current_need_redandancy_present NOTIFICATION-TYPE -- STATUS mandatory -- DESCRIPTION "STS actual current need an redundant inverter" -- ::= { traps 26 } trap_sts_current_need_redandancy_present OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS not-accessible STATUS mandatory DESCRIPTION "STS current need redandancy present" ::= { traps 26 } sts_current_need_redandancy_present TRAP-TYPE ENTERPRISE convertronic VARIABLES { trap_sts_current_need_redandancy_present, trapLastMessageStringTest, trapLastMessageNbrTest, trapSourceIPTest } DESCRIPTION "STS actual current need an redundant inverter" -- NMS trap annotation --#TYPE "STS actual current need an redundant inverter" --#SUMMARY "Failure %d, Text: %s, No: %d." --#ARGUMENTS {0,1,2} --#SEVERITY MINOR --#TIMEINDEX 99 --#STATE OPERATIONAL ::= 25 -- -- dc_voltage_low_present NOTIFICATION-TYPE -- STATUS mandatory -- DESCRIPTION "DC voltage is low" -- ::= { traps 27 } trap_dc_voltage_low_present OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS not-accessible STATUS mandatory DESCRIPTION "STS dc voltage low present" ::= { traps 27 } dc_voltage_low_present TRAP-TYPE ENTERPRISE convertronic VARIABLES { trap_dc_voltage_low_present, trapLastMessageStringTest, trapLastMessageNbrTest, trapSourceIPTest } DESCRIPTION "DC voltage is low" -- NMS trap annotation --#TYPE "DC voltage is low" --#SUMMARY "Failure %d, Text: %s, No: %d." --#ARGUMENTS {0,1,2} --#SEVERITY MAJOR --#TIMEINDEX 99 --#STATE OPERATIONAL ::= 26 -- -- dc_voltage_high_present NOTIFICATION-TYPE -- STATUS mandatory -- DESCRIPTION "DC voltage is high" -- ::= { traps 28 } trap_dc_voltage_high_present OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS not-accessible STATUS mandatory DESCRIPTION "STS DC voltage is high" ::= { traps 28 } dc_voltage_high_present TRAP-TYPE ENTERPRISE convertronic VARIABLES { trap_dc_voltage_high_present, trapLastMessageStringTest, trapLastMessageNbrTest, trapSourceIPTest } DESCRIPTION "DC voltage is high" -- NMS trap annotation --#TYPE "DC voltage is high" --#SUMMARY "Failure %d, Text: %s, No: %d." --#ARGUMENTS {0,1,2} --#SEVERITY MAJOR --#TIMEINDEX 99 --#STATE OPERATIONAL ::= 27 -- -- fan_error_present NOTIFICATION-TYPE -- STATUS mandatory -- DESCRIPTION "Fan is in error-state" -- ::= { traps 29 } trap_fan_error_present OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS not-accessible STATUS mandatory DESCRIPTION "STS Fan is in error-state" ::= { traps 29 } fan_error_present TRAP-TYPE ENTERPRISE convertronic VARIABLES { trap_fan_error_present, trapLastMessageStringTest, trapLastMessageNbrTest, trapSourceIPTest } DESCRIPTION "Fan is in error-state" -- NMS trap annotation --#TYPE "Fan is in error-state" --#SUMMARY "Failure %d, Text: %s, No: %d." --#ARGUMENTS {0,1,2} --#SEVERITY MAJOR --#TIMEINDEX 99 --#STATE OPERATIONAL ::= 28 -- -- uout_low_present NOTIFICATION-TYPE -- STATUS mandatory -- DESCRIPTION "STS outputvoltage is low" -- ::= { traps 30 } trap_uout_low_present OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS not-accessible STATUS mandatory DESCRIPTION "STS outputvoltage is low" ::= { traps 30 } uout_low_present TRAP-TYPE ENTERPRISE convertronic VARIABLES { trap_uout_low_present, trapLastMessageStringTest, trapLastMessageNbrTest, trapSourceIPTest } DESCRIPTION "STS outputvoltage is low" -- NMS trap annotation --#TYPE "STS outputvoltage is low" --#SUMMARY "Failure %d, Text: %s, No: %d." --#ARGUMENTS {0,1,2} --#SEVERITY MAJOR --#TIMEINDEX 99 --#STATE OPERATIONAL ::= 29 -- -- u_batterie_lower_warning_present NOTIFICATION-TYPE -- STATUS mandatory -- DESCRIPTION "Battery voltage is lower warninglevel" -- ::= { traps 31 } trap_u_batterie_lower_warning_present OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS not-accessible STATUS mandatory DESCRIPTION "STS Battery voltage is lower warninglevel" ::= { traps 31 } u_batterie_lower_warning_present TRAP-TYPE ENTERPRISE convertronic VARIABLES { trap_u_batterie_lower_warning_present, trapLastMessageStringTest, trapLastMessageNbrTest, trapSourceIPTest } DESCRIPTION "Battery voltage is lower warninglevel" -- NMS trap annotation --#TYPE "Battery voltage is lower warninglevel" --#SUMMARY "Failure %d, Text: %s, No: %d." --#ARGUMENTS {0,1,2} --#SEVERITY MINOR --#TIMEINDEX 99 --#STATE OPERATIONAL ::= 30 -- -- u_batterie_higher_warning_present NOTIFICATION-TYPE -- STATUS mandatory -- DESCRIPTION "Battery voltage is higher warninglevel" -- ::= { traps 32 } trap_u_batterie_higher_warning_present OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS not-accessible STATUS mandatory DESCRIPTION "Battery voltage is higher warninglevel" ::= { traps 32 } u_batterie_higher_warning_present TRAP-TYPE ENTERPRISE convertronic VARIABLES { trap_u_batterie_higher_warning_present, trapLastMessageStringTest, trapLastMessageNbrTest, trapSourceIPTest } DESCRIPTION "Battery voltage is higher warninglevel" -- NMS trap annotation --#TYPE "Battery voltage is higher warninglevel" --#SUMMARY "Failure %d, Text: %s, No: %d." --#ARGUMENTS {0,1,2} --#SEVERITY MINOR --#TIMEINDEX 99 --#STATE OPERATIONAL ::= 31 -- -- source_mains_failure_removed NOTIFICATION-TYPE -- STATUS mandatory -- DESCRIPTION "Error with Source mains, state is not active" -- ::= { traps 33 } trap_source_mains_failure_removed OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS not-accessible STATUS mandatory DESCRIPTION "Error with Source mains, state is not active" ::= { traps 33 } source_mains_failure_removed TRAP-TYPE ENTERPRISE convertronic VARIABLES { trap_source_mains_failure_removed, trapLastMessageStringTest, trapLastMessageNbrTest, trapSourceIPTest } DESCRIPTION "Error with Source mains, state is not active" -- NMS trap annotation --#TYPE "Error with Source mains, state is not active" --#SUMMARY "OK %d, Text: %s, No: %d." --#ARGUMENTS {0,1,2} --#SEVERITY INFORMATIONAL --#TIMEINDEX 99 --#STATE OPERATIONAL ::= 32 -- -- source_inverter_failure_removed NOTIFICATION-TYPE -- STATUS mandatory -- DESCRIPTION "Error with Source inverter present, state is not active" -- ::= { traps 34 } trap_source_inverter_failure_removed OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS not-accessible STATUS mandatory DESCRIPTION "Error with Source inverter present, state is not active" ::= { traps 34 } source_inverter_failure_removed TRAP-TYPE ENTERPRISE convertronic VARIABLES { trap_source_inverter_failure_removed, trapLastMessageStringTest, trapLastMessageNbrTest, trapSourceIPTest } DESCRIPTION "Error with Source inverter present, state is not active" -- NMS trap annotation --#TYPE "Error with Source inverter present, state is not active" --#SUMMARY "OK %d, Text: %s, No: %d." --#ARGUMENTS {0,1,2} --#SEVERITY INFORMATIONAL --#TIMEINDEX 99 --#STATE OPERATIONAL ::= 33 -- -- syncronisation_error_removed NOTIFICATION-TYPE -- STATUS mandatory -- DESCRIPTION "Syncronisation between Source Mains and Source Inverter lost, state is not active" -- ::= { traps 35 } trap_syncronisation_error_removed OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS not-accessible STATUS mandatory DESCRIPTION "Syncronisation between Source Mains and Source Inverter lost, state is not active" ::= { traps 35 } syncronisation_error_removed TRAP-TYPE ENTERPRISE convertronic VARIABLES { trap_syncronisation_error_removed, trapLastMessageStringTest, trapLastMessageNbrTest, trapSourceIPTest } DESCRIPTION "Syncronisation between Source Mains and Source Inverter lost, state is not active" -- NMS trap annotation --#TYPE "Syncronisation between Source Mains and Source Inverter lost, state is not active" --#SUMMARY "OK %d, Text: %s, No: %d." --#ARGUMENTS {0,1,2} --#SEVERITY INFORMATIONAL --#TIMEINDEX 99 --#STATE OPERATIONAL ::= 34 -- -- inverter_failure_removed NOTIFICATION-TYPE -- STATUS mandatory -- DESCRIPTION "Inverter failure, state is not active" -- ::= { traps 36 } trap_inverter_failure_removed OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS not-accessible STATUS mandatory DESCRIPTION "Inverter failure, state is not active" ::= { traps 36 } inverter_failure_removed TRAP-TYPE ENTERPRISE convertronic VARIABLES { trap_inverter_failure_removed, trapLastMessageStringTest, trapLastMessageNbrTest, trapSourceIPTest } DESCRIPTION "Inverter failure, state is not active" -- NMS trap annotation --#TYPE "Inverter failure, state is not active" --#SUMMARY "OK %d, Text: %s, No: %d." --#ARGUMENTS {0,1,2} --#SEVERITY INFORMATIONAL --#TIMEINDEX 99 --#STATE OPERATIONAL ::= 35 -- -- no_redundant_inverter_removed NOTIFICATION-TYPE -- STATUS mandatory -- DESCRIPTION "No more redundant inverter present, state is not active" -- ::= { traps 37 } trap_no_redundant_inverter_removed OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS not-accessible STATUS mandatory DESCRIPTION "No more redundant inverter present, state is not active" ::= { traps 37 } no_redundant_inverter_removed TRAP-TYPE ENTERPRISE convertronic VARIABLES { trap_no_redundant_inverter_removed, trapLastMessageStringTest, trapLastMessageNbrTest, trapSourceIPTest } DESCRIPTION "No more redundant inverter present, state is not active" -- NMS trap annotation --#TYPE "No more redundant inverter present, state is not active" --#SUMMARY "OK %d, Text: %s, No: %d." --#ARGUMENTS {0,1,2} --#SEVERITY INFORMATIONAL --#TIMEINDEX 99 --#STATE OPERATIONAL ::= 36 -- -- critical_inverter_quantity_removed NOTIFICATION-TYPE -- STATUS mandatory -- DESCRIPTION "Inverter quantity is lower than needed, state is not active" -- ::= { traps 38 } trap_critical_inverter_quantity_removed OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS not-accessible STATUS mandatory DESCRIPTION "Inverter quantity is lower than needed, state is not active" ::= { traps 38 } critical_inverter_quantity_removed TRAP-TYPE ENTERPRISE convertronic VARIABLES { trap_critical_inverter_quantity_removed, trapLastMessageStringTest, trapLastMessageNbrTest, trapSourceIPTest } DESCRIPTION "Inverter quantity is lower than needed, state is not active" -- NMS trap annotation --#TYPE "Inverter quantity is lower than needed, state is not active" --#SUMMARY "OK %d, Text: %s, No: %d." --#ARGUMENTS {0,1,2} --#SEVERITY INFORMATIONAL --#TIMEINDEX 99 --#STATE OPERATIONAL ::= 37 -- -- sts_overtemperature_removed NOTIFICATION-TYPE -- STATUS mandatory -- DESCRIPTION "STS temperature warning is not active" -- ::= { traps 39 } trap_sts_overtemperature_removed OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS not-accessible STATUS mandatory DESCRIPTION "STS temperature warning is not active" ::= { traps 39 } sts_overtemperature_removed TRAP-TYPE ENTERPRISE convertronic VARIABLES { trap_sts_overtemperature_removed, trapLastMessageStringTest, trapLastMessageNbrTest, trapSourceIPTest } DESCRIPTION "STS temperature warning is not active" -- NMS trap annotation --#TYPE "STS temperature warning is not active" --#SUMMARY "OK %d, Text: %s, No: %d." --#ARGUMENTS {0,1,2} --#SEVERITY INFORMATIONAL --#TIMEINDEX 99 --#STATE OPERATIONAL ::= 38 -- -- sts_overload_removed NOTIFICATION-TYPE -- STATUS mandatory -- DESCRIPTION "STS overload is not active" -- ::= { traps 40 } trap_sts_overload_removed OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS not-accessible STATUS mandatory DESCRIPTION "STS temperature warning is not active" ::= { traps 40 } sts_overload_removed TRAP-TYPE ENTERPRISE convertronic VARIABLES { trap_sts_overload_removed, trapLastMessageStringTest, trapLastMessageNbrTest, trapSourceIPTest } DESCRIPTION "STS overload is not active" -- NMS trap annotation --#TYPE "STS overload is not active" --#SUMMARY "OK %d, Text: %s, No: %d." --#ARGUMENTS {0,1,2} --#SEVERITY INFORMATIONAL --#TIMEINDEX 99 --#STATE OPERATIONAL ::= 39 -- -- inverter_overload_removed NOTIFICATION-TYPE -- STATUS mandatory -- DESCRIPTION "Inverter overload is not active" -- ::= { traps 41 } trap_inverter_overload_removed OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS not-accessible STATUS mandatory DESCRIPTION "Inverter overload is not active" ::= { traps 41 } inverter_overload_removed TRAP-TYPE ENTERPRISE convertronic VARIABLES { trap_inverter_overload_removed, trapLastMessageStringTest, trapLastMessageNbrTest, trapSourceIPTest } DESCRIPTION "Inverter overload is not active" -- NMS trap annotation --#TYPE "Inverter overload is not active" --#SUMMARY "OK %d, Text: %s, No: %d." --#ARGUMENTS {0,1,2} --#SEVERITY INFORMATIONAL --#TIMEINDEX 99 --#STATE OPERATIONAL ::= 40 -- -- sts_current_need_redandancy_removed NOTIFICATION-TYPE -- STATUS mandatory -- DESCRIPTION "STS actual current do not need an redundant inverter" -- ::= { traps 42 } trap_sts_current_need_redandancy_removed OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS not-accessible STATUS mandatory DESCRIPTION "STS actual current do not need an redundant inverter" ::= { traps 42 } sts_current_need_redandancy_removed TRAP-TYPE ENTERPRISE convertronic VARIABLES { trap_sts_current_need_redandancy_removed, trapLastMessageStringTest, trapLastMessageNbrTest, trapSourceIPTest } DESCRIPTION "STS actual current do not need an redundant inverter" -- NMS trap annotation --#TYPE "STS actual current do not need an redundant inverter" --#SUMMARY "OK %d, Text: %s, No: %d." --#ARGUMENTS {0,1,2} --#SEVERITY INFORMATIONAL --#TIMEINDEX 99 --#STATE OPERATIONAL ::= 41 -- -- dc_voltage_low_removed NOTIFICATION-TYPE -- STATUS mandatory -- DESCRIPTION "DC voltage is low, state is not active" -- ::= { traps 43 } trap_dc_voltage_low_removed OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS not-accessible STATUS mandatory DESCRIPTION "DC voltage is low, state is not active" ::= { traps 43 } dc_voltage_low_removed TRAP-TYPE ENTERPRISE convertronic VARIABLES { trap_dc_voltage_low_removed, trapLastMessageStringTest, trapLastMessageNbrTest, trapSourceIPTest } DESCRIPTION "DC voltage is low, state is not active" -- NMS trap annotation --#TYPE "DC voltage is low, state is not active" --#SUMMARY "OK %d, Text: %s, No: %d." --#ARGUMENTS {0,1,2} --#SEVERITY INFORMATIONAL --#TIMEINDEX 99 --#STATE OPERATIONAL ::= 42 -- -- dc_voltage_high_added_removed NOTIFICATION-TYPE -- STATUS mandatory -- DESCRIPTION "DC voltage is high, state is not active" -- ::= { traps 44 } trap_dc_voltage_high_added_removed OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS not-accessible STATUS mandatory DESCRIPTION "DC voltage is high, state is not active" ::= { traps 44 } dc_voltage_high_added_removed TRAP-TYPE ENTERPRISE convertronic VARIABLES { trap_dc_voltage_high_added_removed, trapLastMessageStringTest, trapLastMessageNbrTest, trapSourceIPTest } DESCRIPTION "DC voltage is high, state is not active" -- NMS trap annotation --#TYPE "DC voltage is high, state is not active" --#SUMMARY "OK %d, Text: %s, No: %d." --#ARGUMENTS {0,1,2} --#SEVERITY INFORMATIONAL --#TIMEINDEX 99 --#STATE OPERATIONAL ::= 43 -- -- fan_error_removed NOTIFICATION-TYPE -- STATUS mandatory -- DESCRIPTION "Fan is not in error-state" -- ::= { traps 45 } trap_fan_error_removed OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS not-accessible STATUS mandatory DESCRIPTION "Fan is not in error-state" ::= { traps 45 } fan_error_removed TRAP-TYPE ENTERPRISE convertronic VARIABLES { trap_fan_error_removed, trapLastMessageStringTest, trapLastMessageNbrTest, trapSourceIPTest } DESCRIPTION "Fan is not in error-state" -- NMS trap annotation --#TYPE "Fan is not in error-state" --#SUMMARY "OK %d, Text: %s, No: %d." --#ARGUMENTS {0,1,2} --#SEVERITY INFORMATIONAL --#TIMEINDEX 99 --#STATE OPERATIONAL ::= 44 -- -- uout_low_removed NOTIFICATION-TYPE -- STATUS mandatory -- DESCRIPTION "STS outputvoltage is low, state is not active" -- ::= { traps 46 } trap_uout_low_removed OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS not-accessible STATUS mandatory DESCRIPTION "STS outputvoltage is low, state is not active" ::= { traps 46 } uout_low_removed TRAP-TYPE ENTERPRISE convertronic VARIABLES { trap_uout_low_removed, trapLastMessageStringTest, trapLastMessageNbrTest, trapSourceIPTest } DESCRIPTION "STS outputvoltage is low, state is not active" -- NMS trap annotation --#TYPE "STS outputvoltage is low, state is not active" --#SUMMARY "OK %d, Text: %s, No: %d." --#ARGUMENTS {0,1,2} --#SEVERITY INFORMATIONAL --#TIMEINDEX 99 --#STATE OPERATIONAL ::= 45 -- -- u_batterie_lower_warning_removed NOTIFICATION-TYPE -- STATUS mandatory -- DESCRIPTION "Battery voltage is lower warninglevel, state is not active" -- ::= { traps 47 } trap_u_batterie_lower_warning_removed OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS not-accessible STATUS mandatory DESCRIPTION "Battery voltage is lower warninglevel, state is not active" ::= { traps 47 } u_batterie_lower_warning_removed TRAP-TYPE ENTERPRISE convertronic VARIABLES { trap_u_batterie_lower_warning_removed, trapLastMessageStringTest, trapLastMessageNbrTest, trapSourceIPTest } DESCRIPTION "Battery voltage is lower warninglevel, state is not active" -- NMS trap annotation --#TYPE "Battery voltage is lower warninglevel, state is not active" --#SUMMARY "OK %d, Text: %s, No: %d." --#ARGUMENTS {0,1,2} --#SEVERITY INFORMATIONAL --#TIMEINDEX 99 --#STATE OPERATIONAL ::= 46 -- -- u_batterie_higher_warning_removed NOTIFICATION-TYPE -- STATUS mandatory -- DESCRIPTION "Battery voltage is higher warninglevel, state is not active" -- ::= { traps 48 } trap_u_batterie_higher_warning_removed OBJECT-TYPE SYNTAX INTEGER(0..1) ACCESS not-accessible STATUS mandatory DESCRIPTION "Battery voltage is higher warninglevel, state is not active" ::= { traps 48 } u_batterie_higher_warning_removed TRAP-TYPE ENTERPRISE convertronic VARIABLES { trap_u_batterie_higher_warning_removed, trapLastMessageStringTest, trapLastMessageNbrTest, trapSourceIPTest } DESCRIPTION "Battery voltage is higher warninglevel, state is not active" -- NMS trap annotation --#TYPE "Battery voltage is higher warninglevel, state is not active" --#SUMMARY "OK %d, Text: %s, No: %d." --#ARGUMENTS {0,1,2} --#SEVERITY INFORMATIONAL --#TIMEINDEX 99 --#STATE OPERATIONAL ::= 47 -- **************************************** -- **************************************** -- **************************************** inverter_Table OBJECT-TYPE SYNTAX SEQUENCE OF Inverter_Entry ACCESS not-accessible STATUS mandatory DESCRIPTION "Table of CAN-nodes." ::= { inverter_measureValues 1 } inverter_Entry OBJECT-TYPE SYNTAX Inverter_Entry ACCESS not-accessible STATUS optional DESCRIPTION "CAN-node entries." INDEX { inv_Index } -- INDEX { index } ::= { inverter_Table 1 } Inverter_Entry ::= SEQUENCE { inv_Index INTEGER, inv_Nbr INTEGER, inv_InCurrent INTEGER, inv_OutCurrent INTEGER, inv_Temperature INTEGER, inv_InputVoltage INTEGER, inv_STi_great INTEGER, inv_Fan INTEGER, inv_RemoteOffCan INTEGER, inv_UoutOff INTEGER, inv_Bit_ShortCircuit INTEGER, inv_Bit_OutputVoltage INTEGER, inv_Bit_InputVoltLow INTEGER, inv_Bit_InputVoltHigh INTEGER, inv_Bit_OutputVoltLow INTEGER, inv_Bit_OutputVoltHigh INTEGER, inv_Bit_OutputCurrHigh INTEGER, inv_Bit_RemoteOff INTEGER, inv_Bit_CentralAlarm INTEGER, inv_Type DisplayString, inv_Mat_CD DisplayString, inv_SerialNo DisplayString, inv_HardwareVersion DisplayString, inv_SoftwareVersion DisplayString } inv_Index OBJECT-TYPE SYNTAX INTEGER (1..16) UNITS "NA" MAX-ACCESS not-accessible STATUS current DESCRIPTION "NA" ::= { inverter_Entry 0 } inv_Nbr OBJECT-TYPE SYNTAX INTEGER (0..15) ACCESS read-only STATUS mandatory DESCRIPTION "Inverter Number, Value: 1 ... 15" ::= { inverter_Entry 1 } inv_InCurrent OBJECT-TYPE SYNTAX INTEGER(0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "In-Current of the Inverter, Value: todo" ::= { inverter_Entry 2 } inv_OutCurrent OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "Out-Current of the Inverter, Value: todo" ::= { inverter_Entry 3 } inv_Temperature OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "Temperature of the Inverter, Value: todo" ::= { inverter_Entry 4 } inv_InputVoltage OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "Input Voltage of the Inverter, Value: todo" ::= { inverter_Entry 5 } inv_STi_great OBJECT-TYPE SYNTAX INTEGER (0..1) ACCESS read-only STATUS mandatory DESCRIPTION "Internal temperature high, Value: 0= < limit 1= > limit" ::= { inverter_Entry 6 } inv_Fan OBJECT-TYPE SYNTAX INTEGER (0..1) ACCESS read-only STATUS mandatory DESCRIPTION "Fan error, Value: 0= no Error 1= error active" ::= { inverter_Entry 7 } inv_RemoteOffCan OBJECT-TYPE SYNTAX INTEGER (0..1) ACCESS read-only STATUS mandatory DESCRIPTION "Far off via can-controll, Value: 0= not off 1= far off is active" ::= { inverter_Entry 8 } inv_UoutOff OBJECT-TYPE SYNTAX INTEGER (0..1) ACCESS read-only STATUS mandatory DESCRIPTION "State of Output voltage, Value: 0= voltage is on 1= voltage shut down" ::= { inverter_Entry 9 } inv_Bit_ShortCircuit OBJECT-TYPE SYNTAX INTEGER (0..1) ACCESS read-only STATUS mandatory DESCRIPTION "Short circuit is present, Value: 0= normal operation 1= Short circuit" ::= { inverter_Entry 10 } inv_Bit_OutputVoltage OBJECT-TYPE SYNTAX INTEGER (0..1) ACCESS read-only STATUS mandatory DESCRIPTION "State of the output voltage, Value: 0= voltage off, error state 1= voltage ok,normal operation" ::= { inverter_Entry 11 } inv_Bit_InputVoltLow OBJECT-TYPE SYNTAX INTEGER (0..1) ACCESS read-only STATUS mandatory DESCRIPTION "Input voltage reached lover limit, Value: 0= normal operation 1= error present" ::= { inverter_Entry 12 } inv_Bit_InputVoltHigh OBJECT-TYPE SYNTAX INTEGER (0..1) ACCESS read-only STATUS mandatory DESCRIPTION "Input voltage reached upper limit, Value: 0= normal operation 1= error present" ::= { inverter_Entry 13 } inv_Bit_OutputVoltLow OBJECT-TYPE SYNTAX INTEGER (0..1) ACCESS read-only STATUS mandatory DESCRIPTION "Output voltage reached lower limit, Value: 0= normal operation 1= error present" ::= { inverter_Entry 14 } inv_Bit_OutputVoltHigh OBJECT-TYPE SYNTAX INTEGER (0..1) ACCESS read-only STATUS mandatory DESCRIPTION "Output voltage reached upper limit, Value: 0= normal operation 1= error present" ::= { inverter_Entry 15 } inv_Bit_OutputCurrHigh OBJECT-TYPE SYNTAX INTEGER (0..1) ACCESS read-only STATUS mandatory DESCRIPTION "Output current reached upper limit, Value: 0= normal operation 1= error present" ::= { inverter_Entry 16 } inv_Bit_RemoteOff OBJECT-TYPE SYNTAX INTEGER (0..1) ACCESS read-only STATUS mandatory DESCRIPTION "Inverter has shut-down, Value: 0= normal operation 1= shut-down" ::= { inverter_Entry 17 } inv_Bit_CentralAlarm OBJECT-TYPE SYNTAX INTEGER (0..1) ACCESS read-only STATUS mandatory DESCRIPTION "Central alarm has triggert, Value: 0= normal operation 1= error present" ::= { inverter_Entry 18 } inv_Type OBJECT-TYPE SYNTAX DisplayString (SIZE (0..16)) ACCESS read-only STATUS mandatory DESCRIPTION "Type description" ::= { inverter_Entry 19 } inv_Mat_CD OBJECT-TYPE SYNTAX DisplayString (SIZE (0..16)) ACCESS read-only STATUS mandatory DESCRIPTION "Order number" ::= { inverter_Entry 20 } inv_SerialNo OBJECT-TYPE SYNTAX DisplayString (SIZE (0..16)) ACCESS read-only STATUS mandatory DESCRIPTION "Serial number" ::= { inverter_Entry 21 } inv_HardwareVersion OBJECT-TYPE SYNTAX DisplayString (SIZE (0..8)) ACCESS read-only STATUS mandatory DESCRIPTION "Hardware version" ::= { inverter_Entry 22 } inv_SoftwareVersion OBJECT-TYPE SYNTAX DisplayString (SIZE (0..8)) ACCESS read-only STATUS mandatory DESCRIPTION "Software Version" ::= { inverter_Entry 23 } -- **************************************** -- **************************************** -- **************************************** -- History historyTable OBJECT-TYPE SYNTAX SEQUENCE OF HistoryEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Table of last 20 history events." ::= { tables 1 } historyEntry OBJECT-TYPE SYNTAX HistoryEntry ACCESS not-accessible STATUS optional DESCRIPTION "History values entries." INDEX { histIndex } -- INDEX { index } ::= { historyTable 1 } HistoryEntry ::= SEQUENCE { histIndex INTEGER, histInd INTEGER, histDateTime INTEGER, histEvent INTEGER, histDescription DisplayString } histIndex OBJECT-TYPE SYNTAX INTEGER (1..20) UNITS "NA" MAX-ACCESS not-accessible STATUS current DESCRIPTION "Index" ::= { historyEntry 0 } histInd OBJECT-TYPE SYNTAX INTEGER (1..65535) ACCESS read-only STATUS mandatory DESCRIPTION "Index" ::= { historyEntry 1 } histDateTime OBJECT-TYPE SYNTAX INTEGER(0..400000000) ACCESS read-only STATUS mandatory DESCRIPTION "Date and time of event in UNIX notation" ::= { historyEntry 2 } histEvent OBJECT-TYPE SYNTAX INTEGER (1..65535) ACCESS read-only STATUS mandatory DESCRIPTION "History event" ::= { historyEntry 3 } --histDescription OBJECT-TYPE -- SYNTAX DisplayString (SIZE (0..16)) -- ACCESS read-only -- STATUS mandatory -- DESCRIPTION "textual description of event" --::= { historyEntry 4 } END