-- Last edit: Thu Jan 24 13:00:00 2013 -- Jeroen Verheul -- -- File: apnl-modular-pdu-v2.0.mib -- -- Contact -- Vincent Veltens -- Release version V2.0 APNL-MODULAR-PDU-MIB DEFINITIONS ::= BEGIN IMPORTS NOTIFICATION-TYPE, OBJECT-TYPE, MODULE-IDENTITY, enterprises, IpAddress, Unsigned32, Integer32 FROM SNMPv2-SMI DateAndTime, DisplayString FROM SNMPv2-TC; apNederland MODULE-IDENTITY LAST-UPDATED "201301241000Z" ORGANIZATION "AP Nederland" CONTACT-INFO "Vincent Veltens " DESCRIPTION "This MIB module defines the modular PDU version of AP Nederland." REVISION "201301241305Z" DESCRIPTION "Initial Version" ::= { enterprises 29640 } -- Tue Mar 20 2012. -- apnlDirectory OBJECT IDENTIFIER ::= { apNederland 1 } apnlMib OBJECT IDENTIFIER ::= { apNederland 2 } apnlTmp OBJECT IDENTIFIER ::= { apNederland 3 } apnlModules OBJECT IDENTIFIER ::= { apNederland 4 } -- Blackbox CM Communication module (mib definition is in apnl-mib.mib). cm OBJECT IDENTIFIER ::= { apnlModules 1 } cmTraps OBJECT IDENTIFIER ::= { apnlModules 2 } -- Modular PDU Communication module pdu OBJECT IDENTIFIER ::= { apnlModules 3 } pduTraps OBJECT IDENTIFIER ::= { apnlModules 4 } apnlTest OBJECT IDENTIFIER ::= { apNederland 5 } apnlDemo OBJECT IDENTIFIER ::= { apNederland 6 } apnlMIBConformance OBJECT IDENTIFIER ::= { apNederland 7 } pduType OBJECT-TYPE SYNTAX INTEGER { pduModular (0), pduGateway1 (1), pduGateway2 (2) } MAX-ACCESS read-only STATUS current DESCRIPTION "Type of the Pdu. PduModular (0) Modulaire OEC2 PDU communication through SNMPV3, MOD-BUS or AP-BUS in emulation mode. PduGateway1 (1) Gateway to connect OEC1 products with external AP-BUS protocol to OEC2 Manager (SNMPV3). PduGateway2 (2) Gateway to connect OEC2 products with external MOD-BUS to OEC Manager (SNMPV3). " ::= { pdu 1 } -- Product serial number pduProductIdentifier OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Unique serial number to identify a pdu, the number is between 1 and 65535. " ::= { pdu 2 } pduSerialNumber OBJECT-TYPE SYNTAX DisplayString (SIZE(1..16)) MAX-ACCESS read-only STATUS current DESCRIPTION "PDU onboard Serial Number." ::= { pdu 3 } pduStatus OBJECT-TYPE SYNTAX INTEGER { pduBusy (0), pduReady1 (1), pduAlarm (2), pduError (3) } MAX-ACCESS read-only STATUS current DESCRIPTION "Status of the Pdu. pduBusy (0) Indicates that an admin command is in progress. pduReady (1) The execution of an admin command was successfull. pduAlarm (2) This state is not in use. pduError (3) The execution of an admin command failed." ::= { pdu 4 } pduPower OBJECT-TYPE SYNTAX Unsigned32 UNITS "kiloWattHours" MAX-ACCESS read-only STATUS current DESCRIPTION "The total measured pdu power in Kilo Watt's*Hour." ::= { pdu 5 } pduPowerL1 OBJECT-TYPE SYNTAX Unsigned32 UNITS "kiloWattHours" MAX-ACCESS read-only STATUS current DESCRIPTION "The total measured pdu power in Kilo Watt's*Hour for phase 1." ::= { pdu 6 } pduPowerL2 OBJECT-TYPE SYNTAX Unsigned32 UNITS "kiloWattHours" MAX-ACCESS read-only STATUS current DESCRIPTION "The total measured pdu power in Kilo Watt's*Hour for phase 2." ::= { pdu 7 } pduPowerL3 OBJECT-TYPE SYNTAX Unsigned32 UNITS "kiloWattHours" MAX-ACCESS read-only STATUS current DESCRIPTION "The total measured pdu power in Kilo Watt's*Hour for phase 3." ::= { pdu 8 } pduKvar OBJECT-TYPE SYNTAX Unsigned32 UNITS "KiloWattHours" MAX-ACCESS read-only STATUS current DESCRIPTION "The total Reactive Power of the pdu. It is the power that magnetic equipment (transformer, motor and relay) needs to produce the magnetizing flux." REFERENCE "http://standby.iea-4e.org/files/otherfiles/0000/0059/PowerFactorBasics.pdf" ::= { pdu 9 } pduKvarL1 OBJECT-TYPE SYNTAX Unsigned32 UNITS "KiloWattHours" MAX-ACCESS read-only STATUS current DESCRIPTION "The total Reactive Power of the pdu for phase 1. It is the power that magnetic equipment (transformer, motor and relay) needs to produce the magnetizing flux." REFERENCE "http://standby.iea-4e.org/files/otherfiles/0000/0059/PowerFactorBasics.pdf" ::= { pdu 10 } pduKvarL2 OBJECT-TYPE SYNTAX Unsigned32 UNITS "KiloWattHours" MAX-ACCESS read-only STATUS current DESCRIPTION "The total Reactive Power of the pdu for phase 2. It is the power that magnetic equipment (transformer, motor and relay) needs to produce the magnetizing flux." REFERENCE "http://standby.iea-4e.org/files/otherfiles/0000/0059/PowerFactorBasics.pdf" ::= { pdu 11 } pduKvarL3 OBJECT-TYPE SYNTAX Unsigned32 UNITS "KiloWattHours" MAX-ACCESS read-only STATUS current DESCRIPTION "The total Reactive Power of the pdu for phase 3. It is the power that magnetic equipment (transformer, motor and relay) needs to produce the magnetizing flux." REFERENCE "http://standby.iea-4e.org/files/otherfiles/0000/0059/PowerFactorBasics.pdf" ::= { pdu 12 } pdulAcurrent OBJECT-TYPE SYNTAX Unsigned32 UNITS "DeciAmpers" MAX-ACCESS read-only STATUS current DESCRIPTION "The total measured ac current for the pdu (in 1/10th Amperes) ." ::= { pdu 13 } pduAcurrentL1 OBJECT-TYPE SYNTAX Unsigned32 UNITS "DeciAmpers" MAX-ACCESS read-only STATUS current DESCRIPTION "The total measured ac current for phase 1 (in 1/10th Amperes)." ::= { pdu 14 } pduAcurrentL2 OBJECT-TYPE SYNTAX Unsigned32 UNITS "DeciAmpers" MAX-ACCESS read-only STATUS current DESCRIPTION "The total measured ac current for phase 2 (in 1/10th Amperes)." ::= { pdu 15 } pduAcurrentL3 OBJECT-TYPE SYNTAX Unsigned32 UNITS "DeciAmpers" MAX-ACCESS read-only STATUS current DESCRIPTION "The total measured ac current for phase 3 (in 1/10th Amperes)." ::= { pdu 16 } pduCurIpAddress OBJECT-TYPE SYNTAX IpAddress UNITS "IPv4 Addr" MAX-ACCESS read-only STATUS current DESCRIPTION "The current PDU IPv4 Address by which TCP/IP access is available. " ::= { pdu 17 } pduCurSubNetMask OBJECT-TYPE SYNTAX IpAddress UNITS "IPv4 Addr" MAX-ACCESS read-only STATUS current DESCRIPTION "The current PDU IPv4 Subnet Mask used by the Ipstack (e.g: 255.255.255.0)." ::= { pdu 18 } pduCurDefGwAddress OBJECT-TYPE SYNTAX IpAddress UNITS "IPv4 Addr" MAX-ACCESS read-only STATUS current DESCRIPTION "The current PDU IPv4 default gateway address used by the Ipstack (e.g: 192.168.1.1)." ::= { pdu 19 } -- Number of items in the node table. pduNumberOfNodes OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Number of items in the node table." ::= { pdu 20 } -- Number of items in the sensor table. -- pduNumberOfSensors OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Number of items in the sensor table." ::= { pdu 21 } -- apnl upper level scalars -- pduSoftwareVersion OBJECT-TYPE SYNTAX DisplayString (SIZE(1..10)) MAX-ACCESS read-only STATUS current DESCRIPTION "PDU software version number." ::= { pdu 22 } pduFirmwareVersion OBJECT-TYPE SYNTAX DisplayString (SIZE(1..10)) MAX-ACCESS read-only STATUS current DESCRIPTION "PDU firmware version number." ::= { pdu 23 } pduBusProtocol OBJECT-TYPE SYNTAX INTEGER { apbus (0), modbus (1) } MAX-ACCESS read-only STATUS current DESCRIPTION "Selected protocol used on the external bus of the pdu. AP-BUS (0) Protocol used by OEC1 products or by OEC2 products in emulation mode. MOD-BUS (1) Protocol used by OEC2 products." ::= { pdu 24 } pduAdminCommand OBJECT-TYPE SYNTAX INTEGER { noOp (0), rebootPdu (1), rediscover (2), updateSofware (3), resetConfig (4), resetSNMPv3Config (5), resetNetworkSetting (6), readDataFromBusPdu (7), writeDataToBusPdu (8) } MAX-ACCESS read-write STATUS current DESCRIPTION "PDU admin management Commands: noOp (0) No operation. rebootPdu (1) Reboot the PDU (to execute new settings). rediscover (2) Not supported. updateSofware (3) Not supported. resetConfig (4) Node and group tables will be cleared . resetSNMPv3Config (5) Not supported. resetNetworkSetting (6) Reset network params: ip address, defualt gatewy, subnet mask. readDataFromBusPdu (7) Read data from a PDU connected to the external bus (address is set in pduBusAddress). writeDataToBusPdu (8) With this command modified data is writen back to the bus PDU (address is set in pduBusAddress). " ::= { pdu 25 } pduStartupIpAddress OBJECT-TYPE SYNTAX IpAddress UNITS "IPv4 Addr" MAX-ACCESS read-write STATUS current DESCRIPTION "Not supported. " ::= { pdu 26 } pduStartupSubNetMask OBJECT-TYPE SYNTAX IpAddress UNITS "IPv4 Addr" MAX-ACCESS read-write STATUS current DESCRIPTION "Not supported." ::= { pdu 27 } pduStartupDefGwAddress OBJECT-TYPE SYNTAX IpAddress UNITS "IPv4 Addr" MAX-ACCESS read-write STATUS current DESCRIPTION "Not supported." ::= { pdu 28 } pduRealTimeClock OBJECT-TYPE SYNTAX DateAndTime MAX-ACCESS read-write STATUS current DESCRIPTION "PDU Real-Time Clock. Maybe set by the manager." ::= { pdu 29 } pduEnableFeatures OBJECT-TYPE SYNTAX BITS { globalWebEnabled (0), globalUsbEnabled (1), globalSwitchEnabled (2), displaySwitchEnabled (3), webSwitchEnabled (4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Array of bits each one an specific feature within the pdu: globalWebEnabled (0) This bit enables the PDU webpages. globalUsbEnabled (1) This bit enables the USB menu. globalSwitchEnabled (2) This bit enables switching in general. displaySwitchEnabled (3) This bit enables switching through the presentation module. webSwitchEnabled (4) This bit enables switching throuhg the web inteface. " ::= { pdu 30 } pduBusAddress OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Address used to access this PDU via the external bus. When MOD-BUS protocol is used the address is valid between 1-247. When AP-BUS protocol is used the address is valid between 1-65535. " ::= { pdu 31 } pduName OBJECT-TYPE SYNTAX DisplayString (SIZE(1..32)) MAX-ACCESS read-write STATUS current DESCRIPTION "Name of the PDU." ::= { pdu 32 } -- The port table. nodeTable OBJECT-TYPE SYNTAX SEQUENCE OF NodeEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A table of the modules on the PDU. Each entry represents an module unit. " ::= { pdu 33 } nodeEntry OBJECT-TYPE SYNTAX NodeEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "An port entry in the port table." INDEX { nodeIndex } ::= { nodeTable 1 } NodeEntry ::= SEQUENCE { nodeIndex Unsigned32, nodeType INTEGER, nodeOutlet Unsigned32, nodeAlarmStatus BITS, nodePower Unsigned32, nodeAcurrent Unsigned32, nodePeakCurrent Unsigned32, nodeVoltage Unsigned32, nodeMinVoltage Unsigned32, nodeKvar Unsigned32, nodeFrequency Unsigned32, nodePowerFactor Unsigned32, nodeSwitchOperStatus INTEGER, nodeSwitchAdminStatus INTEGER, nodeCurrHiThresh Unsigned32, nodeCurrLoThresh Unsigned32, nodeVoltHiThresh Unsigned32, nodeVoltLoThresh Unsigned32, nodeAlarmSelector BITS, nodeName DisplayString, nodePhase INTEGER } nodeIndex OBJECT-TYPE SYNTAX Unsigned32 (1..30) MAX-ACCESS not-accessible STATUS current DESCRIPTION "The node table Index." ::= { nodeEntry 1 } nodeType OBJECT-TYPE SYNTAX INTEGER { typeUnknown (0), typePresModChar (1), typePresModMono (2), typePresModGraph (3), typePowerMeter (4), typePowerMeterSwitch (5), typeSwitch (6) } MAX-ACCESS read-only STATUS current DESCRIPTION "Type of the node. TypeUnknown (0) Unknown node. TypePresModChar (1) PM LCD Character Module. TypePresModMono (2) PM Mono Graphics Module. TypePresModGraph (3) PM Color Graphics Module. TypePowerMeter (4) Power meter. TypePowerMeterSwitch (5) Switchable power meter. TypeSwitch (6) Switch only. " ::= { nodeEntry 2 } nodeOutlet OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS read-only STATUS current DESCRIPTION "The number associated with the physical outlet of the node. The special value of 0 indicates that this entry is not associated with a physical port." ::= { nodeEntry 3 } nodeAlarmStatus OBJECT-TYPE SYNTAX BITS { trapCurrHi (0), trapCurrLo (1), trapVoltHi (2), trapVoltLo (3), switchOn (4), switchOff (5) } MAX-ACCESS read-only STATUS current DESCRIPTION "Array of bits each one indicates an alarm activated in the alarm selector value. TrapCurrHi (0) The current is to high against the high current threshold. TrapCurrLo (1) The current is to low against the low current threshold. TrapVoltHi (2) The voltage is to high against the high voltage threshold. TrapVoltLo (3) The volage is to low against the low voltage threshold. SwitchOn (4) The switch is on against the switch on bitfield. SwitchOff (5) The switch is off against the switch off bitfield. " ::= { nodeEntry 4 } nodePower OBJECT-TYPE SYNTAX Unsigned32 UNITS "kiloWattHours" MAX-ACCESS read-only STATUS current DESCRIPTION "The measured node power in Kilo Watt's*Hour." ::= { nodeEntry 5 } nodeAcurrent OBJECT-TYPE SYNTAX Unsigned32 UNITS "DeciAmpers" MAX-ACCESS read-only STATUS current DESCRIPTION "The measured ac current at the node (in 1/10th Amperes)." ::= { nodeEntry 6 } nodePeakCurrent OBJECT-TYPE SYNTAX Unsigned32 UNITS "DeciAmpers" MAX-ACCESS read-only STATUS current DESCRIPTION "The measured max current since last reset of the node (in 1/10th Amperes)." ::= { nodeEntry 7 } nodeVoltage OBJECT-TYPE SYNTAX Unsigned32 UNITS "Volts" MAX-ACCESS read-only STATUS current DESCRIPTION "The measured voltage on the node." ::= { nodeEntry 8 } nodeMinVoltage OBJECT-TYPE SYNTAX Unsigned32 UNITS "Volts" MAX-ACCESS read-only STATUS current DESCRIPTION "The measured minimum voltage at the node since last reset." ::= { nodeEntry 9 } nodeKvar OBJECT-TYPE SYNTAX Unsigned32 UNITS "KiloWattHours" MAX-ACCESS read-only STATUS current DESCRIPTION "The Reactive Power. It is the power that magnetic equipment (transformer, motor and relay) needs to produce the magnetizing flux." REFERENCE "http://standby.iea-4e.org/files/otherfiles/0000/0059/PowerFactorBasics.pdf" ::= { nodeEntry 10 } nodeFrequency OBJECT-TYPE SYNTAX Unsigned32 UNITS "Hertz" MAX-ACCESS read-only STATUS current DESCRIPTION "The frequency of alternating current in Hertz. e.g 50 in Europe or 60 in USA." REFERENCE "http://en.wikipedia.org/wiki/Hertz" ::= { nodeEntry 11 } nodePowerFactor OBJECT-TYPE SYNTAX Unsigned32 UNITS "Percent" MAX-ACCESS read-only STATUS current DESCRIPTION "The effective power facton (Cosinus Phi) in percents of the node." REFERENCE "http://en.wikipedia.org/wiki/Power_factor" ::= { nodeEntry 12 } nodeSwitchOperStatus OBJECT-TYPE SYNTAX INTEGER { unknown (0), off (1), on (2) } MAX-ACCESS read-only STATUS current DESCRIPTION "The actual operational Status of the node. Unknown (0) not known status. Off (1) switch is off. On (2) switch is on." ::= { nodeEntry 13 } nodeSwitchAdminStatus OBJECT-TYPE SYNTAX INTEGER { unknown (0), off (1), on (2) } MAX-ACCESS read-write STATUS current DESCRIPTION "The desired admin Status of the switch. Unknown (0) not known. Off (1) switch is off. On (2) switch is on." ::= { nodeEntry 14 } nodeCurrHiThresh OBJECT-TYPE SYNTAX Unsigned32 UNITS "DeciAmpers" MAX-ACCESS read-write STATUS current DESCRIPTION "The current high threshold (in 1/10th Amperes)." ::= { nodeEntry 15 } nodeCurrLoThresh OBJECT-TYPE SYNTAX Unsigned32 UNITS "DeciAmpers" MAX-ACCESS read-write STATUS current DESCRIPTION "The current low threshold (in 1/10th Amperes)." ::= { nodeEntry 16 } nodeVoltHiThresh OBJECT-TYPE SYNTAX Unsigned32 UNITS "Volts" MAX-ACCESS read-write STATUS current DESCRIPTION "The voltage high threshold." ::= { nodeEntry 17 } nodeVoltLoThresh OBJECT-TYPE SYNTAX Unsigned32 UNITS "Volts" MAX-ACCESS read-write STATUS current DESCRIPTION "The voltage low threshold." ::= { nodeEntry 18 } nodeAlarmSelector OBJECT-TYPE SYNTAX BITS { trapCurrHi (0), trapCurrLo (1), trapVoltHi (2), trapVoltLo (3), switchOn (4), switchOff (5) } MAX-ACCESS read-write STATUS current DESCRIPTION "Array of bits each one controls one alarm. TrapCurrHi (0) Enable/disable the high current alarm. TrapCurrLo (1) Enable/disable the low current alarm. TrapVoltHi (2) Enable/disable the high voltage alarm. TrapVoltLo (3) Enable/disable the low voltage alarm. SwitchOn (4) Enable/disable the specific switch on alarm. SwitchOff (5) Enable/disable the specific switch off alarm." ::= { nodeEntry 19 } nodeName OBJECT-TYPE SYNTAX DisplayString (SIZE(1..14)) MAX-ACCESS read-write STATUS current DESCRIPTION "The node name. My be set by manager." ::= { nodeEntry 20 } nodePhase OBJECT-TYPE SYNTAX INTEGER { phaseUnknown (0), phaseL1 (1), phaseL2 (2), phaseL3 (3) } MAX-ACCESS read-write STATUS current DESCRIPTION "The measured phase of the node. Maybe assigned when not configured in production. PhaseUnknown (0). PhaseL1 (1). PhaseL2 (2). PhaseL3 (3). " ::= { nodeEntry 21 } -- -- The Sensors Table -- sensorTable OBJECT-TYPE SYNTAX SEQUENCE OF SensorEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A table of the Sensors on the PDU. Each entry represents an an Sensor unit. " ::= { pdu 34 } sensorEntry OBJECT-TYPE SYNTAX SensorEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "An Sensor Entry in the Sensor table" INDEX { sensorIndex } ::= { sensorTable 1 } SensorEntry ::= SEQUENCE { sensorIndex Unsigned32, sensorType INTEGER, sensorAlarmStatus BITS, sensorValue Integer32, sensorSwitchOperStatus INTEGER, sensorSwitchAdminStatus INTEGER, sensorHiThresh Integer32, sensorLoThresh Integer32, sensorAlarmSelector BITS, sensorName DisplayString } sensorIndex OBJECT-TYPE SYNTAX Unsigned32 (1..4) MAX-ACCESS not-accessible STATUS current DESCRIPTION "The Sensor table Index." ::= { sensorEntry 1 } sensorType OBJECT-TYPE SYNTAX INTEGER { other (0), temperature (1), humidity (2), smoke (3), co1 (4), vibration (5), doorStatus (6) } MAX-ACCESS read-only STATUS current DESCRIPTION "Sensor Typ: Measured values are used according to sensor type. Other (0) unknown sensor type. Temperature (1) . Humidity (2). Smoke (3). CO1 (4). Vibration (5). Doorstatus (6)." ::= { sensorEntry 2 } sensorAlarmStatus OBJECT-TYPE SYNTAX BITS { trapHi (0), trapLo (1), switchOn (2), switchOff (3), beeperHi (4), beeperLo (5) } MAX-ACCESS read-only STATUS current DESCRIPTION "Array of bits each one indicates an alarm activated in the alarm selector value." ::= { sensorEntry 3 } sensorValue OBJECT-TYPE SYNTAX Integer32 UNITS "by type" MAX-ACCESS read-only STATUS current DESCRIPTION "The measured value of the sensor, units are depending on sensor type." ::= { sensorEntry 4 } sensorSwitchOperStatus OBJECT-TYPE SYNTAX INTEGER { unknown (0), off (1), on (2) } MAX-ACCESS read-only STATUS current DESCRIPTION "The actual operational Status of the switch." ::= { sensorEntry 5 } sensorSwitchAdminStatus OBJECT-TYPE SYNTAX INTEGER { unknown (0), off (1), on (2) } MAX-ACCESS read-write STATUS current DESCRIPTION "The desired admin Status of the switch." ::= { sensorEntry 6 } -- thresholds sensorHiThresh OBJECT-TYPE SYNTAX Integer32 UNITS "by type" MAX-ACCESS read-write STATUS current DESCRIPTION "High threshold." ::= { sensorEntry 7 } sensorLoThresh OBJECT-TYPE SYNTAX Integer32 UNITS "by type" MAX-ACCESS read-write STATUS current DESCRIPTION "Low threshold." ::= { sensorEntry 8 } sensorAlarmSelector OBJECT-TYPE SYNTAX BITS { trapHi (0), trapLo (1), switchOn (2), switchOff (3), beeperHi (4), beeperLo (5) } MAX-ACCESS read-write STATUS current DESCRIPTION "Array of bits each one controls one alarm. E.g trap, beeper etc." ::= { sensorEntry 9 } sensorName OBJECT-TYPE SYNTAX DisplayString (SIZE(1..12)) MAX-ACCESS read-write STATUS current DESCRIPTION "The sensor name. May be set by the manager." ::= { sensorEntry 10 } -- -- PDU traps -- -- Trap to inform the manager about: -- 1. voltage -- 2. current -- 4. sensor (temperature, humidity) -- 5. switch -- 6. startup -- 7. power -- Trap Type enumration to indicate the kind of alarm that sent trapType OBJECT-TYPE SYNTAX INTEGER { voltageHiAlarm (0), voltageLoAlarm (1), currentHiAlarm (2), currentLoAlarm (3), tempHiAlarm (4), tempLoAlarm (5), humidityHiAlarm (6), humidityLoAlarm (7), switchOnAlarm (8), switchOffAlarm (9), powerHiAlarm (10), blackBoxColdTrap (11) } MAX-ACCESS accessible-for-notify STATUS current DESCRIPTION "An enumation value to indicate an Alarm trap: pduPduAlarm." ::= { pduTraps 1 } pduTableType OBJECT-TYPE SYNTAX INTEGER { pduNodeTable (0), pduSensorTable (1) } MAX-ACCESS accessible-for-notify STATUS current DESCRIPTION "The table type." ::= { pduTraps 2 } -- -- The Index of the table entry for which the trap is made. -- It has the same value of the table index (which is not-accessible -- trapTableIndex OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS accessible-for-notify STATUS current DESCRIPTION "The index of the table entry for which the trap is issued." ::= { pduTraps 3 } -- The thershold type which the trap is made. -- trapThreshHoldType OBJECT-TYPE SYNTAX INTEGER { trapThresholdOther (0), trapThresholdHi (1), trapThresholdLo (2) } MAX-ACCESS accessible-for-notify STATUS current DESCRIPTION "The threshold type for which the trap is made." ::= { pduTraps 4 } -- The reference threshold value -- trapThreshHold OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS accessible-for-notify STATUS current DESCRIPTION "The threshold reference value." ::= { pduTraps 5 } -- -- traps definitions -- pduVoltageAlarm NOTIFICATION-TYPE OBJECTS { trapType, trapTableIndex, trapThreshHoldType, trapThreshHold } STATUS current DESCRIPTION "Voltage alarm." ::= { pduTraps 6 } pduCurrentAlarm NOTIFICATION-TYPE OBJECTS { trapType, trapTableIndex, trapThreshHoldType, trapThreshHold } STATUS current DESCRIPTION "Current alaram." ::= { pduTraps 7 } pduPowerAlarm NOTIFICATION-TYPE OBJECTS { trapType, trapTableIndex, trapThreshHoldType, trapThreshHold } STATUS current DESCRIPTION "Power alarm." ::= { pduTraps 8 } sensorAlarm NOTIFICATION-TYPE OBJECTS { trapType, trapTableIndex, trapThreshHoldType, trapThreshHold } STATUS current DESCRIPTION "Sensor Alarm: Temperature, Humidity or another type. The sensorType indicates the type of alarm. The sensorValue indicate the measured value." ::= { pduTraps 9 } pduSwitchAlarm NOTIFICATION-TYPE OBJECTS { trapType, trapTableIndex } STATUS current DESCRIPTION "Not supported." ::= { pduTraps 10 } END -- This MIB was created using NuDesign Team's Visual MIBuilder (Ver 4.9).