-- powertek iPoManIII MIB -- MIB for PWT Products -- -- { iso org(3) dod(6) internet(1) private(4) enterprises(1) powertek(42610) -- product(1) pdu(4) pwt(4) -- ============================================================================================== --- --- Revision History --- --- v0.10 14-Feb-2014 ChainLiu/Ingrasys Created --- v0.11 11-Mar-2014 JimmyYang/Ingrasys Modified --- v0.12 01-Sep-2014 ChainLiu/Ingrasys Add outlets control --- v0.13 24-Nov-2014 ChainLiu/Ingrasys Modified --- v0.14 19-May-2015 ChainLiu/Ingrasys Modified --- v0.15 12-Aug-2015 ChainLiu Modified --- v0.16 18-Jul-2016 EthanHsu/FIT, Added total current threshold and residual current trap --- v0.17 18-Oct-2016 JimmyYang/FIT, Added RCM alarm threshold and modify residual current trap. --- v0.18 17-May-2017 JimmyYang/FIT, Fixed mail & trap description string length bug. --- v1.00 31-Jul-2017 CainLiu/FIT, Add the mib id of outlet voltage. --- v2.00 31-Aug-2017 CainLiu/FIT, Modified the file for 8 Daisy Chain. --- v2.01 17-Nov-2017 CainLiu/FIT, Add the mibs for load balance. --- v2.02 25-Jun-2017 JimmyYang/FIT, Add the mibs for external EMD. --- v2.03 29-Jun-2017 JimmyYang/FIT, Fixd the mibs bug for external EMD/EMD. --- v2.10 10-Sep-2018 JimmyYang/FIT, Integrate SNMP EMD & EMD board. --- v2.11 28-Nov-2018 JimmyYang/FIT, Add AC fail/restore trap for ATS. --- v2.12 20-Jun-2019 JimmyYang/FIT, Add phase[1,2,3] energy clean. --- v2.13 11-Sep-2020 JimmyYang/FIT, Add inlet's frequency, Add inlet's reactive energy. --- v2.14 24-Sep-2020 JimmyYang/FIT, Add inlet's reactive power. -- ============================================================================================== PWTv1-MIB DEFINITIONS ::= BEGIN IMPORTS enterprises FROM RFC1155-SMI OBJECT-TYPE FROM RFC-1212 DisplayString FROM RFC1213-MIB TRAP-TYPE FROM RFC-1215; powertek OBJECT IDENTIFIER ::= { enterprises 42610 } product OBJECT IDENTIFIER ::= { powertek 1 } pdu OBJECT IDENTIFIER ::= { product 4 } pwt OBJECT IDENTIFIER ::= { pdu 4 } pduObjects OBJECT IDENTIFIER ::= { pwt 1 } pduTraps OBJECT IDENTIFIER ::= { pwt 2 } pduIdent OBJECT IDENTIFIER ::= { pduObjects 1 } pduNetwork OBJECT IDENTIFIER ::= { pduObjects 2 } pduSystem OBJECT IDENTIFIER ::= { pduObjects 3 } pduSNMP OBJECT IDENTIFIER ::= { pduObjects 4 } pduEmail OBJECT IDENTIFIER ::= { pduObjects 5 } pduPwrMonitoring OBJECT IDENTIFIER ::= { pduObjects 6 } pduEnvMonitoring OBJECT IDENTIFIER ::= { pduObjects 7 } -- =========================================================================== -- -- pduIdent -- -- pdu Identification Group -- -- =========================================================================== pduIdentAgentSoftwareVersion OBJECT-TYPE SYNTAX DisplayString (SIZE (0..63)) ACCESS read-only STATUS mandatory DESCRIPTION "The firmware version of the device." ::= { pduIdent 1 } pduIdentSerialNumber OBJECT-TYPE SYNTAX DisplayString (SIZE(0..31)) ACCESS read-only STATUS mandatory DESCRIPTION "A Model of this device." ::= { pduIdent 2 } pduNetworkTcpip OBJECT IDENTIFIER ::= { pduNetwork 1 } -- =========================================================================== -- -- pduNetworkTcpip -- -- Network Configuration Group of the device. -- -- =========================================================================== pduNetworkTcpipDhcpControl OBJECT-TYPE SYNTAX INTEGER { disabled(1), enabled(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Enable/disable DHCP protocol" ::= { pduNetworkTcpip 1 } pduNetworkTcpipIpv4 OBJECT IDENTIFIER ::= { pduNetworkTcpip 2 } -- =========================================================================== -- -- pduNetworkTcpipIpv4 -- -- Ip address Configuration Group of the device. -- -- =========================================================================== pduNetworkTcpipIpv4Address OBJECT-TYPE SYNTAX IpAddress ACCESS read-write STATUS mandatory DESCRIPTION "The ip address that NMS can identify the managed device." ::= { pduNetworkTcpipIpv4 1} pduNetworkTcpipIpv4Gateway OBJECT-TYPE SYNTAX IpAddress ACCESS read-write STATUS mandatory DESCRIPTION "The default gateway that allow device managed through routers." ::= { pduNetworkTcpipIpv4 2} pduNetworkTcpipIpv4Subnet OBJECT-TYPE SYNTAX IpAddress ACCESS read-write STATUS mandatory DESCRIPTION "Internet address subnet mask" ::= { pduNetworkTcpipIpv4 3} pduNetworkTcpipIpv4PrimaryDNS OBJECT-TYPE SYNTAX IpAddress ACCESS read-write STATUS mandatory DESCRIPTION "Internet address of Primary DNS Server" ::= { pduNetworkTcpipIpv4 4} pduNetworkTcpipIpv4SecondaryDNS OBJECT-TYPE SYNTAX IpAddress ACCESS read-write STATUS mandatory DESCRIPTION "Internet address of Secondary DNS" ::= { pduNetworkTcpipIpv4 5} pduNetworkTcpipIpv6 OBJECT IDENTIFIER ::= { pduNetworkTcpip 3 } -- =========================================================================== -- -- pduNetworkTcpipIpv6 -- -- Ip address Configuration Group of the device. -- -- =========================================================================== pduNetworkTcpipIpv6Control OBJECT-TYPE SYNTAX INTEGER { disabled(1), enabled(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Enable/disable IPv6 protocol" ::= { pduNetworkTcpipIpv6 1 } pduNetworkTcpipIpv6AutoConfig OBJECT-TYPE SYNTAX INTEGER { auto(1), manual(2) } ACCESS read-write STATUS mandatory DESCRIPTION "IPv6 Auto-config or Maual setting" ::= { pduNetworkTcpipIpv6 2 } pduNetworkTcpipIpv6Address OBJECT-TYPE SYNTAX DisplayString (SIZE (0..63)) ACCESS read-only STATUS mandatory DESCRIPTION "The ipv6 address that NMS can identify the managed device." ::= { pduNetworkTcpipIpv6 3} pduNetworkTcpipIpv6Prefix OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The prefix length for ipv6 address." ::= { pduNetworkTcpipIpv6 4} pduNetworkTcpipIpv6Router OBJECT-TYPE SYNTAX DisplayString (SIZE (0..63)) ACCESS read-only STATUS mandatory DESCRIPTION "The default gateway that allow device managed through routers." ::= { pduNetworkTcpipIpv6 5} pduNetworkTcpipIpv6PrimaryDNS OBJECT-TYPE SYNTAX DisplayString (SIZE (0..63)) ACCESS read-write STATUS mandatory DESCRIPTION "Internet address of Primary DNS Server" ::= { pduNetworkTcpipIpv6 6} pduNetworkTcpipIpv6SecondaryDNS OBJECT-TYPE SYNTAX DisplayString (SIZE (0..63)) ACCESS read-write STATUS mandatory DESCRIPTION "Internet address of Secondary DNS" ::= { pduNetworkTcpipIpv6 7} pduNetworkSecurity OBJECT IDENTIFIER ::= { pduNetwork 2 } -- =========================================================================== -- -- pduNetworkSecurity -- -- Network Security Group of the device. -- -- =========================================================================== pduNetworkSecurityControl OBJECT-TYPE SYNTAX INTEGER { disabled(1), enabled(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Enable/disable Network Access Protection" ::= { pduNetworkSecurity 1 } pduNetworkSecuritySsh OBJECT IDENTIFIER ::= { pduNetworkSecurity 2 } -- =========================================================================== -- -- pduNetworkSecuritySsh -- -- SSH Security Group Group of the device. -- -- =========================================================================== pduNetworkSecuritySshControl OBJECT-TYPE SYNTAX INTEGER { disabled(1), enabled(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Enable/disable SSH Access Protection" ::= { pduNetworkSecuritySsh 1 } pduNetworkSecuritySshInterval OBJECT-TYPE SYNTAX INTEGER { oneMinute(1), fiveMinutes(2), tenMinutes(3), thirtyMinutes(4) } ACCESS read-write STATUS mandatory DESCRIPTION "Detecting Interval of SSH Access Protection" ::= { pduNetworkSecuritySsh 2 } pduNetworkSecuritySshFailTimes OBJECT-TYPE SYNTAX INTEGER { five(1), ten(2), twenty(3), thirty(4), hundred(5) } ACCESS read-write STATUS mandatory DESCRIPTION "Unsuccessful attempts of SSH Access Protection" ::= { pduNetworkSecuritySsh 3 } pduNetworkSecuritySshBlock OBJECT-TYPE SYNTAX INTEGER { fiveMinutes(1), thirtyMinutes(2), oneHour(3), oneDay(4) } ACCESS read-write STATUS mandatory DESCRIPTION "Block Time of SSH Access Protection" ::= { pduNetworkSecuritySsh 4 } pduNetworkSecuritySnmp OBJECT IDENTIFIER ::= { pduNetworkSecurity 3 } -- =========================================================================== -- -- pduNetworkSecuritySnmp -- -- SNMP Security Group Group of the device. -- -- =========================================================================== pduNetworkSecuritySnmpControl OBJECT-TYPE SYNTAX INTEGER { disabled(1), enabled(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Enable/disable SNMP Access Protection" ::= { pduNetworkSecuritySnmp 1 } pduNetworkSecuritySnmpInterval OBJECT-TYPE SYNTAX INTEGER { oneMinute(1), fiveMinutes(2), tenMinutes(3), thirtyMinutes(4) } ACCESS read-write STATUS mandatory DESCRIPTION "Detecting Interval of SNMP Access Protection" ::= { pduNetworkSecuritySnmp 2 } pduNetworkSecuritySnmpFailTimes OBJECT-TYPE SYNTAX INTEGER { five(1), ten(2), twenty(3), thirty(4), hundred(5) } ACCESS read-write STATUS mandatory DESCRIPTION "Unsuccessful attempts of SNMP Access Protection" ::= { pduNetworkSecuritySnmp 3 } pduNetworkSecuritySnmpBlock OBJECT-TYPE SYNTAX INTEGER { fiveMinutes(1), thirtyMinutes(2), oneHour(3), oneDay(4) } ACCESS read-write STATUS mandatory DESCRIPTION "Block Time of SNMP Access Protection" ::= { pduNetworkSecuritySnmp 4 } pduNetworkSecurityHttp OBJECT IDENTIFIER ::= { pduNetworkSecurity 4 } -- =========================================================================== -- -- pduNetworkSecurityHttp -- -- HTTP Security Group Group of the device. -- -- =========================================================================== pduNetworkSecurityHttpControl OBJECT-TYPE SYNTAX INTEGER { disabled(1), enabled(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Enable/disable HTTP Access Protection" ::= { pduNetworkSecurityHttp 1 } pduNetworkSecurityHttpInterval OBJECT-TYPE SYNTAX INTEGER { oneMinute(1), fiveMinutes(2), tenMinutes(3), thirtyMinutes(4) } ACCESS read-write STATUS mandatory DESCRIPTION "Detecting Interval of HTTP Access Protection" ::= { pduNetworkSecurityHttp 2 } pduNetworkSecurityHttpFailTimes OBJECT-TYPE SYNTAX INTEGER { five(1), ten(2), twenty(3), thirty(4), hundred(5) } ACCESS read-write STATUS mandatory DESCRIPTION "Unsuccessful attempts of HTTP Access Protection" ::= { pduNetworkSecurityHttp 3 } pduNetworkSecurityHttpBlock OBJECT-TYPE SYNTAX INTEGER { fiveMinutes(1), thirtyMinutes(2), oneHour(3), oneDay(4) } ACCESS read-write STATUS mandatory DESCRIPTION "Block Time of HTTP Access Protection" ::= { pduNetworkSecurityHttp 4 } pduNetworkService OBJECT IDENTIFIER ::= { pduNetwork 3 } -- =========================================================================== -- -- pduNetworkService -- -- Network Service Group of the device. -- -- =========================================================================== pduNetworkServiceSsh OBJECT IDENTIFIER ::= { pduNetworkService 1 } -- =========================================================================== -- -- pduNetworkServiceSsh -- -- SSH Service Group of the device. -- -- =========================================================================== pduNetworkServiceSshControl OBJECT-TYPE SYNTAX INTEGER { disabled(1), enabled(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Enable/disable SSH Server Service" ::= { pduNetworkServiceSsh 1 } pduNetworkServiceSshPort OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The Port Number of SSH Server Service" ::= { pduNetworkServiceSsh 2 } pduNetworkServiceSsl OBJECT IDENTIFIER ::= { pduNetworkService 2 } -- =========================================================================== -- -- pduNetworkServiceSsl -- -- HTTPs Service Group of the device. -- -- =========================================================================== pduNetworkServiceSslControl OBJECT-TYPE SYNTAX INTEGER { disabled(1), enabled(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Enable/disable HTTPs Server Service" ::= { pduNetworkServiceSsl 1 } pduNetworkServiceSslPort OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The Port Number of HTTPs Server Service" ::= { pduNetworkServiceSsl 2 } pduNetworkServiceSslForce OBJECT-TYPE SYNTAX INTEGER { disabled(1), enabled(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Force use HTTPs Server Service only." ::= { pduNetworkServiceSsl 3 } pduNetworkServicePingControl OBJECT-TYPE SYNTAX INTEGER { disabled(1), enabled(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Enable/disable to response to PING request." ::= { pduNetworkService 3 } pduNetworkServiceRadius OBJECT IDENTIFIER ::= { pduNetworkService 4 } -- =========================================================================== -- -- pduNetworkServiceRadius -- -- RADIUS Client Service Group of the device. -- -- =========================================================================== pduNetworkServiceRadiusControl OBJECT-TYPE SYNTAX INTEGER { disabled(1), enabled(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Enable/disable RADIUS Client Service" ::= { pduNetworkServiceRadius 1 } pduNetworkServiceRadiusIp OBJECT-TYPE SYNTAX DisplayString (SIZE (0..63)) ACCESS read-write STATUS mandatory DESCRIPTION "The IP Address of RADIUS Client Service" ::= { pduNetworkServiceRadius 2 } pduNetworkServiceRadiusPort OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The Port Number of RADIUS Client Service" ::= { pduNetworkServiceRadius 3 } pduNetworkServiceRadiusSecretKey OBJECT-TYPE SYNTAX DisplayString (SIZE (0..31)) ACCESS read-write STATUS mandatory DESCRIPTION "The Secret Key of RADIUS Client Service" ::= { pduNetworkServiceRadius 4 } pduNetworkServiceRadiusTimeout OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The Timeout Interval of RADIUS Client Service in seconds" ::= { pduNetworkServiceRadius 5 } pduNetworkServiceRadiusRetry OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The Retry Times of RADIUS Client Service" ::= { pduNetworkServiceRadius 6 } -- =========================================================================== -- -- pduSystem -- -- System Management Group of the device. -- -- =========================================================================== pduSystemName OBJECT-TYPE SYNTAX DisplayString (SIZE (0..31)) ACCESS read-write STATUS mandatory DESCRIPTION "The name of system." ::= { pduSystem 1 } pduSystemContact OBJECT-TYPE SYNTAX DisplayString (SIZE (0..31)) ACCESS read-write STATUS mandatory DESCRIPTION "The contact of system." ::= { pduSystem 2 } pduSystemLocation OBJECT-TYPE SYNTAX DisplayString (SIZE (0..31)) ACCESS read-write STATUS mandatory DESCRIPTION "The location of system." ::= { pduSystem 3 } pduSystemLogInterval OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The Log Interval of device" ::= { pduSystem 4 } pduSystemWebRefresh OBJECT-TYPE SYNTAX INTEGER (3..60) ACCESS read-write STATUS mandatory DESCRIPTION "The Web Refresh Interval of device" ::= { pduSystem 5 } pduSystemTime OBJECT IDENTIFIER ::= { pduSystem 6 } -- =========================================================================== -- -- pduSystemTime -- -- Date/Time Configuration Group of the device. -- -- =========================================================================== pduSystemTimeDisplay OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The date/time in agent" ::= { pduSystemTime 1 } pduSystemTimeZone OBJECT-TYPE SYNTAX INTEGER { gMT-1200InternationalDateLineWest(1), gMT-1200Eniwetok-Kwajalein(2), gMT-1100MidwayIsland-Samoa(3), gMT-1000Hawaii(4), gMT-0900Alaska(5), gMT-0800PacificTime-Tijuana(6), gMT-0700Arizona-MountainTime(7), gMT-0700Chihuahua-LaPaz-Mazatlan(8), gMT-0700MountainTime(9), gMT-0600CentralAmerica(10), gMT-0600CentralTime(11), gMT-0600Guadalajara-MexicoCity-Monterrey(12), gMT-0600Saskatchewan(13), gMT-0500Bogota-Lima-Quito(14), gMT-0500EasternTime(15), gMT-0500Indiana(16), gMT-0400AtlanticTime(17), gMT-0400Caracas-LaPaz(18), gMT-0400Santiago(19), gMT-0330Newfoundland(20), gMT-0300Brasilia(21), gMT-0300BuenosAires-Georgetown(22), gMT-0300Greenland(23), gMT-0200Mid-Atlantic(24), gMT-0100Azores(25), gMT-0100CapeVerdeIs(26), gMT-0000Casablanca-Monrovia(27), gMT-0000GreenwichMeanTime-Dublin-Edinburgh-Lisbon-London(28), gMT0100Amsterdam-Berlin-Bern-Rome-Stockholm-Vienna(29), gMT0100Belgrade-Bratislava-Budapest-Ljubljana-Prague(30), gMT0100Brussels-Copenhagen-Madrid-Paris(31), gMT0100Sarajevo-Skopje-Warsaw-Zagreb(32), gMT0100WestCentralAfrica(33), gMT0200Athens-Istanbul-Minsk(34), gMT0200Bucharest(35), gMT0200Cairo(36), gMT0200Harare-Pretoria(37), gMT0200Helsinki-Kyiv-Riga-Sofia-Tallinn-Vilnius(38), gMT0200Jerusalem(39), gMT0300Baghdad(40), gMT0300Kuwait-Riyadh(41), gMT0300Moscow-StPetersburg-Volgograd(42), gMT0300Nairobi(43), gMT0330Tehran(44), gMT0400AbuDhabi-Muscat(45), gMT0400Baku-Tbilisi-Yerevan(46), gMT0430Kabul(47), gMT0500Ekaterinburg(48), gMT0500Islamabad-Karachi-Tashkent(49), gMT0530Bombay-Calcutta(50), gMT0530Chennai-Kolkata-Mumbai-NewDelhi(51), gMT0545Kathmandu(52), gMT0600Almaty-Novosibirsk(53), gMT0600Astana-Dhaka(54), gMT0600SriJayawardenepura(55), gMT0630Rangoon(56), gMT0700Bangkok-Hanoi-Jakarta(57), gMT0700Krasnoyarsk(58), gMT0800Beijing-Chongqing-HongKong-Urumqi(59), gMT0800Irkutsk-UlaanBataar(60), gMT0800KualaLumpur-Singapore(61), gMT0800Perth(62), gMT0800Taipei(63), gMT0900Osaka-Sapporo-Tokyo(64), gMT0900Seoul(65), gMT0900Yakutsk(66), gMT0930Adelaide(67), gMT0930Darwin(68), gMT1000Brisbane(69), gMT1000Canberra-Melbourne-Sydney(70), gMT1000Guam-PortMoresby(71), gMT1000Hobart(72), gMT1000Vladivostok(73), gMT1100Magadan-SolomonIs-NewCaledonia(74), gMT1200Auckland-Wellington(75), gMT1200Fiji-Kamchatka-MarshallIs(76), gMT1300NukuAlofa(77) } ACCESS read-write STATUS mandatory DESCRIPTION "Time Zone to use when synchronize with NTP server." ::= { pduSystemTime 2 } pduSystemTimeFormat OBJECT-TYPE SYNTAX INTEGER { ddmmyyyy(1), mmddyyyy(2), yyyymmdd(3) } ACCESS read-write STATUS mandatory DESCRIPTION "Date Format" ::= { pduSystemTime 3 } pduSystemTimeSetting OBJECT-TYPE SYNTAX INTEGER { twentyFourHrFormat(1), twelveHrFormat(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Time Setting" ::= { pduSystemTime 4 } pduSystemTimeDayLightSaving OBJECT-TYPE SYNTAX INTEGER { disabled(1), enabled(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Enable/disable the Day Light Saving when synchronize with NTP server." ::= { pduSystemTime 5 } pduSystemTimeManual OBJECT IDENTIFIER ::= { pduSystemTime 6 } -- =========================================================================== -- -- pduSystemTimeManual -- -- Manual Time Setting Configuration Group of the device. -- -- =========================================================================== pduSystemTimeManualDate OBJECT-TYPE SYNTAX DisplayString (SIZE (10..10)) ACCESS read-write STATUS mandatory DESCRIPTION "The date in agent, format is (dd/mm/yyyy)" ::= { pduSystemTimeManual 1 } pduSystemTimeManualTime OBJECT-TYPE SYNTAX DisplayString (SIZE (8..8)) ACCESS read-write STATUS mandatory DESCRIPTION "The time in agent, format is (hh:mm:ss)" ::= { pduSystemTimeManual 2 } pduSystemTimeNtp OBJECT IDENTIFIER ::= { pduSystemTime 7 } -- =========================================================================== -- -- pduSystemTimeNtp -- -- NTP Configuration Group of the device. -- -- =========================================================================== pduSystemTimeNtpControl OBJECT-TYPE SYNTAX INTEGER { enabled(1), disabled(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Enable or disable the agent to synchronize date/time with NTP server." ::= { pduSystemTimeNtp 1 } pduSystemTimeNtpServer OBJECT-TYPE SYNTAX DisplayString (SIZE (0..63)) ACCESS read-write STATUS mandatory DESCRIPTION "The ip address of NTP server." ::= { pduSystemTimeNtp 2 } pduSystemTimeNtpSyncInterval OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The Sync Interval with NTP server." ::= { pduSystemTimeNtp 3 } pduSystemTimeNtpSyncUnit OBJECT-TYPE SYNTAX INTEGER { day(1), month(2) } ACCESS read-write STATUS mandatory DESCRIPTION "The Unit of Sync Interval" ::= { pduSystemTimeNtp 4 } pduSystemResetToDefault OBJECT-TYPE SYNTAX INTEGER { nothing(1), reset(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Reset the parameter of PDU to default." ::= { pduSystem 7 } pduSystemReboot OBJECT-TYPE SYNTAX INTEGER { nothing(1), reboot(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Reboot the system of PDU." ::= { pduSystem 8 } -- =========================================================================== -- -- pduSNMP -- -- SNMP Configuration Group of the device. -- -- =========================================================================== pduSnmpControl OBJECT-TYPE SYNTAX INTEGER { disabled(1), enabled(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Enable/disable SNMP protocol." ::= { pduSNMP 1 } pduSnmpPort OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The UDP port for SNMP." ::= { pduSNMP 2} pduSnmpVersion OBJECT-TYPE SYNTAX INTEGER { v1(1), v2(2), v3(3) } ACCESS read-write STATUS mandatory DESCRIPTION "Set SNMP version." ::= { pduSNMP 3 } pduSnmpTrapsReceiversTable OBJECT-TYPE SYNTAX SEQUENCE OF PduSnmpTrapsReceiversEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of managers to send traps to. The number of entries is given by the value of pduSnmpNumTrapReceivers" ::= { pduSNMP 4} pduSnmpTrapsReceiversEntry OBJECT-TYPE SYNTAX PduSnmpTrapsReceiversEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The managers to send traps to." INDEX { trapsIndex} ::= { pduSnmpTrapsReceiversTable 1 } PduSnmpTrapsReceiversEntry ::= SEQUENCE { trapsIndex INTEGER, trapsReceiverAddr DisplayString, receiverEventLevel INTEGER, receiverSnmpVer INTEGER, receiverDescription DisplayString } trapsIndex OBJECT-TYPE SYNTAX INTEGER (0..15) ACCESS read-only STATUS mandatory DESCRIPTION "The index to a trap receiver entry." ::= { pduSnmpTrapsReceiversEntry 1 } trapsReceiverAddr OBJECT-TYPE SYNTAX DisplayString (SIZE(0..31)) ACCESS read-write STATUS mandatory DESCRIPTION "The IP address of the manager to send a trap to." ::= { pduSnmpTrapsReceiversEntry 2 } receiverEventLevel OBJECT-TYPE SYNTAX INTEGER { critical(1), warning(2), informational(3) } ACCESS read-write STATUS mandatory DESCRIPTION "The severity level of traps to be received by this manager." ::= { pduSnmpTrapsReceiversEntry 3 } receiverSnmpVer OBJECT-TYPE SYNTAX INTEGER { v1(1), v2(2), v3(3) } ACCESS read-write STATUS mandatory DESCRIPTION "The SNMP Trap version of trap receivers." ::= { pduSnmpTrapsReceiversEntry 4 } receiverDescription OBJECT-TYPE SYNTAX DisplayString (SIZE(0..31)) ACCESS read-write STATUS mandatory DESCRIPTION "Description of trap receivers" ::= { pduSnmpTrapsReceiversEntry 5 } -- =========================================================================== -- -- pduEmail -- -- Email Configuration Group of the device. -- -- =========================================================================== pduEmailServer OBJECT-TYPE SYNTAX DisplayString (SIZE (0..63)) ACCESS read-write STATUS mandatory DESCRIPTION "The address of Email server." ::= { pduEmail 1 } pduEmailPort OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The UDP port for Email Server." ::= { pduEmail 2} pduEmailSenderEmail OBJECT-TYPE SYNTAX DisplayString (SIZE (0..63)) ACCESS read-write STATUS mandatory DESCRIPTION "The sender's Email address" ::= { pduEmail 3 } pduEmailPrefix OBJECT-TYPE SYNTAX DisplayString (SIZE (0..31)) ACCESS read-write STATUS mandatory DESCRIPTION "The prefix string of mail subject" ::= { pduEmail 4 } pduEmailAuthControl OBJECT-TYPE SYNTAX INTEGER { disabled(1), enabled(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Enable/disable SMTP Authentication." ::= { pduEmail 5 } pduEmailAuthUsername OBJECT-TYPE SYNTAX DisplayString (SIZE (0..31)) ACCESS read-write STATUS mandatory DESCRIPTION "The user name of SMTP Authentication" ::= { pduEmail 6 } pduEmailAuthPassword OBJECT-TYPE SYNTAX DisplayString (SIZE (0..31)) ACCESS read-write STATUS mandatory DESCRIPTION "The password of SMTP Authentication" ::= { pduEmail 7 } pduEmailReceiversTable OBJECT-TYPE SYNTAX SEQUENCE OF PduEmailReceiversEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of managers to send email notification to." ::= { pduEmail 8} pduEmailReceiversEntry OBJECT-TYPE SYNTAX PduEmailReceiversEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The managers to send email notification to." INDEX { mailRecvIndex} ::= { pduEmailReceiversTable 1 } PduEmailReceiversEntry ::= SEQUENCE { mailRecvIndex INTEGER, mailRecvReceiverAddr DisplayString, mailRecvEmailType INTEGER, mailRecvEventLevel INTEGER, mailRecvDescription DisplayString } mailRecvIndex OBJECT-TYPE SYNTAX INTEGER (0..15) ACCESS read-only STATUS mandatory DESCRIPTION "The index to a email notification receiver entry." ::= { pduEmailReceiversEntry 1 } mailRecvReceiverAddr OBJECT-TYPE SYNTAX DisplayString (SIZE(0..63)) ACCESS read-write STATUS mandatory DESCRIPTION "The Email address of the manager to send a email notification to." ::= { pduEmailReceiversEntry 2 } mailRecvEmailType OBJECT-TYPE SYNTAX INTEGER { none(1), events(2), status(3), both(4) } ACCESS read-write STATUS mandatory DESCRIPTION "The Email Type of email notification receivers." ::= { pduEmailReceiversEntry 3 } mailRecvEventLevel OBJECT-TYPE SYNTAX INTEGER { critical(1), warning(2), informational(3) } ACCESS read-write STATUS mandatory DESCRIPTION "The severity level of email notification to be received by this manager." ::= { pduEmailReceiversEntry 4 } mailRecvDescription OBJECT-TYPE SYNTAX DisplayString (SIZE(0..31)) ACCESS read-write STATUS mandatory DESCRIPTION "Description of email notification receivers" ::= { pduEmailReceiversEntry 5 } pduPwrMonitoringInlet OBJECT IDENTIFIER ::= { pduPwrMonitoring 1 } -- =========================================================================== -- -- pduPwrMonitoringInlet -- -- Inlet Management Group of the device. -- -- =========================================================================== pduPwrMonitoringInletNum OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of Inlet." ::= { pduPwrMonitoringInlet 1} -- =========================================================================== -- -- pduPwrMonitoringInletStatusTable -- -- Inlet Status Group -- -- =========================================================================== pduPwrMonitoringInletStatusTable OBJECT-TYPE SYNTAX SEQUENCE OF PduPwrMonitoringInletStatusEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display status of Inlet." ::= { pduPwrMonitoringInlet 2} pduPwrMonitoringInletStatusEntry OBJECT-TYPE SYNTAX PduPwrMonitoringInletStatusEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display status of Inlet." INDEX { inletIndex} ::= { pduPwrMonitoringInletStatusTable 1 } PduPwrMonitoringInletStatusEntry ::= SEQUENCE { inletIndex INTEGER, inletPowerAll INTEGER, inletResetFrom DisplayString, inletEnergy INTEGER, inletStatus INTEGER, inletCurrPhase1b1 INTEGER, inletCurrPhase2b1 INTEGER, inletCurrPhase3b1 INTEGER, inletCurrPhase1b2 INTEGER, inletCurrPhase2b2 INTEGER, inletCurrPhase3b2 INTEGER, inletCurrPhase1 INTEGER, inletCurrPhase2 INTEGER, inletCurrPhase3 INTEGER, inletVoltPhase1 INTEGER, inletVoltPhase2 INTEGER, inletVoltPhase3 INTEGER, inletPwrFactorPhase1b1 INTEGER, inletPwrFactorPhase2b1 INTEGER, inletPwrFactorPhase3b1 INTEGER, inletPwrFactorPhase1b2 INTEGER, inletPwrFactorPhase2b2 INTEGER, inletPwrFactorPhase3b2 INTEGER, inletPowerPhase1b1 INTEGER, inletPowerPhase2b1 INTEGER, inletPowerPhase3b1 INTEGER, inletPowerPhase1b2 INTEGER, inletPowerPhase2b2 INTEGER, inletPowerPhase3b2 INTEGER, inletPowerPhase1 INTEGER, inletPowerPhase2 INTEGER, inletPowerPhase3 INTEGER, inletStatusPhase1 INTEGER, inletStatusPhase2 INTEGER, inletStatusPhase3 INTEGER, inletAppPowerPhase1b1 INTEGER, inletAppPowerPhase2b1 INTEGER, inletAppPowerPhase3b1 INTEGER, inletAppPowerPhase1b2 INTEGER, inletAppPowerPhase2b2 INTEGER, inletAppPowerPhase3b2 INTEGER, inletAppPowerPhase1 INTEGER, inletAppPowerPhase2 INTEGER, inletAppPowerPhase3 INTEGER, inletAppRcmCurrent INTEGER, inletLoadBalance INTEGER, inletLoadBalanceStatus INTEGER, inletResetFromPhase1 DisplayString, inletEnergyPhase1 INTEGER, inletResetFromPhase2 DisplayString, inletEnergyPhase2 INTEGER, inletResetFromPhase3 DisplayString, inletEnergyPhase3 INTEGER, inletFreqPhase1 INTEGER, inletFreqPhase2 INTEGER, inletFreqPhase3 INTEGER, inletReactiveResetFrom DisplayString, inletReactiveEnergy INTEGER, inletReactiveResetFromPhase1 DisplayString, inletReactiveEnergyPhase1 INTEGER, inletReactiveResetFromPhase2 DisplayString, inletReactiveEnergyPhase2 INTEGER, inletReactiveResetFromPhase3 DisplayString, inletReactiveEnergyPhase3 INTEGER, inletVarPowerPhase1b1 INTEGER, inletVarPowerPhase2b1 INTEGER, inletVarPowerPhase3b1 INTEGER, inletVarPowerPhase1b2 INTEGER, inletVarPowerPhase2b2 INTEGER, inletVarPowerPhase3b2 INTEGER, inletVarPowerPhase1 INTEGER, inletVarPowerPhase2 INTEGER, inletVarPowerPhase3 INTEGER } inletIndex OBJECT-TYPE SYNTAX INTEGER (0..3) ACCESS read-only STATUS mandatory DESCRIPTION "The index to Inlet status entry." ::= { pduPwrMonitoringInletStatusEntry 1 } inletPowerAll OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The total power of inlet." ::= { pduPwrMonitoringInletStatusEntry 2 } inletResetFrom OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The reset date of inlet." ::= { pduPwrMonitoringInletStatusEntry 3 } inletEnergy OBJECT-TYPE SYNTAX INTEGER UNITS "KWh" ACCESS read-only STATUS mandatory DESCRIPTION "The total energy of inlet." ::= { pduPwrMonitoringInletStatusEntry 4 } inletStatus OBJECT-TYPE SYNTAX INTEGER { normal(1), warning(2), critical(3) } ACCESS read-only STATUS mandatory DESCRIPTION "The Status of inlet power." ::= { pduPwrMonitoringInletStatusEntry 5 } inletCurrPhase1b1 OBJECT-TYPE SYNTAX INTEGER UNITS "0.01A" ACCESS read-only STATUS mandatory DESCRIPTION "The phase1b1 current of inlet." ::= { pduPwrMonitoringInletStatusEntry 6 } inletCurrPhase2b1 OBJECT-TYPE SYNTAX INTEGER UNITS "0.01A" ACCESS read-only STATUS mandatory DESCRIPTION "The phase2b1 current of inlet." ::= { pduPwrMonitoringInletStatusEntry 7 } inletCurrPhase3b1 OBJECT-TYPE SYNTAX INTEGER UNITS "0.01A" ACCESS read-only STATUS mandatory DESCRIPTION "The phase3b1 current of inlet." ::= { pduPwrMonitoringInletStatusEntry 8 } inletCurrPhase1b2 OBJECT-TYPE SYNTAX INTEGER UNITS "0.01A" ACCESS read-only STATUS mandatory DESCRIPTION "The phase1b2 current of inlet." ::= { pduPwrMonitoringInletStatusEntry 9 } inletCurrPhase2b2 OBJECT-TYPE SYNTAX INTEGER UNITS "0.01A" ACCESS read-only STATUS mandatory DESCRIPTION "The phase2b2 current of inlet." ::= { pduPwrMonitoringInletStatusEntry 10 } inletCurrPhase3b2 OBJECT-TYPE SYNTAX INTEGER UNITS "0.01A" ACCESS read-only STATUS mandatory DESCRIPTION "The phase3b2 current of inlet." ::= { pduPwrMonitoringInletStatusEntry 11 } inletCurrPhase1 OBJECT-TYPE SYNTAX INTEGER UNITS "0.01A" ACCESS read-only STATUS mandatory DESCRIPTION "The phase1 current of inlet." ::= { pduPwrMonitoringInletStatusEntry 12 } inletCurrPhase2 OBJECT-TYPE SYNTAX INTEGER UNITS "0.01A" ACCESS read-only STATUS mandatory DESCRIPTION "The phase2 current of inlet." ::= { pduPwrMonitoringInletStatusEntry 13 } inletCurrPhase3 OBJECT-TYPE SYNTAX INTEGER UNITS "0.01A" ACCESS read-only STATUS mandatory DESCRIPTION "The phase3 current of inlet." ::= { pduPwrMonitoringInletStatusEntry 14 } inletVoltPhase1 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1V" ACCESS read-only STATUS mandatory DESCRIPTION "The phase1 voltage of inlet." ::= { pduPwrMonitoringInletStatusEntry 15 } inletVoltPhase2 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1V" ACCESS read-only STATUS mandatory DESCRIPTION "The phase2 voltage of inlet." ::= { pduPwrMonitoringInletStatusEntry 16 } inletVoltPhase3 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1V" ACCESS read-only STATUS mandatory DESCRIPTION "The phase3 voltage of inlet." ::= { pduPwrMonitoringInletStatusEntry 17 } inletPwrFactorPhase1b1 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1%" ACCESS read-only STATUS mandatory DESCRIPTION "The phase1b1 power factor of inlet." ::= { pduPwrMonitoringInletStatusEntry 18 } inletPwrFactorPhase2b1 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1%" ACCESS read-only STATUS mandatory DESCRIPTION "The phase2b1 power factor of inlet." ::= { pduPwrMonitoringInletStatusEntry 19 } inletPwrFactorPhase3b1 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1%" ACCESS read-only STATUS mandatory DESCRIPTION "The phase3b1 power factor of inlet." ::= { pduPwrMonitoringInletStatusEntry 20 } inletPwrFactorPhase1b2 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1%" ACCESS read-only STATUS mandatory DESCRIPTION "The phase1b2 power factor of inlet." ::= { pduPwrMonitoringInletStatusEntry 21 } inletPwrFactorPhase2b2 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1%" ACCESS read-only STATUS mandatory DESCRIPTION "The phase2b2 power factor of inlet." ::= { pduPwrMonitoringInletStatusEntry 22 } inletPwrFactorPhase3b2 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1%" ACCESS read-only STATUS mandatory DESCRIPTION "The phase3b2 power factor of inlet." ::= { pduPwrMonitoringInletStatusEntry 23 } inletPowerPhase1b1 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The phase1b1 active power of inlet." ::= { pduPwrMonitoringInletStatusEntry 24 } inletPowerPhase2b1 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The phase2b1 active power of inlet." ::= { pduPwrMonitoringInletStatusEntry 25 } inletPowerPhase3b1 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The phase3b1 active power of inlet." ::= { pduPwrMonitoringInletStatusEntry 26 } inletPowerPhase1b2 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The phase1b2 active power of inlet." ::= { pduPwrMonitoringInletStatusEntry 27 } inletPowerPhase2b2 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The phase2b2 active power of inlet." ::= { pduPwrMonitoringInletStatusEntry 28 } inletPowerPhase3b2 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The phase3b2 active power of inlet." ::= { pduPwrMonitoringInletStatusEntry 29 } inletPowerPhase1 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The phase1 active power of inlet." ::= { pduPwrMonitoringInletStatusEntry 30 } inletPowerPhase2 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The phase2 active power of inlet." ::= { pduPwrMonitoringInletStatusEntry 31 } inletPowerPhase3 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The phase3 active power of inlet." ::= { pduPwrMonitoringInletStatusEntry 32 } inletStatusPhase1 OBJECT-TYPE SYNTAX INTEGER { normal(1), warning(2), critical(3) } ACCESS read-only STATUS mandatory DESCRIPTION "The phase1 status of inlet." ::= { pduPwrMonitoringInletStatusEntry 33 } inletStatusPhase2 OBJECT-TYPE SYNTAX INTEGER { normal(1), warning(2), critical(3) } ACCESS read-only STATUS mandatory DESCRIPTION "The phase2 status of inlet." ::= { pduPwrMonitoringInletStatusEntry 34 } inletStatusPhase3 OBJECT-TYPE SYNTAX INTEGER { normal(1), warning(2), critical(3) } ACCESS read-only STATUS mandatory DESCRIPTION "The phase3 status of inlet." ::= { pduPwrMonitoringInletStatusEntry 35 } inletAppPowerPhase1b1 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The phase1b1 apparent power of inlet." ::= { pduPwrMonitoringInletStatusEntry 36 } inletAppPowerPhase2b1 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The phase2b1 apparent power of inlet." ::= { pduPwrMonitoringInletStatusEntry 37 } inletAppPowerPhase3b1 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The phase3b1 apparent power of inlet." ::= { pduPwrMonitoringInletStatusEntry 38 } inletAppPowerPhase1b2 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The phase1b2 apparent power of inlet." ::= { pduPwrMonitoringInletStatusEntry 39 } inletAppPowerPhase2b2 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The phase2b2 apparent power of inlet." ::= { pduPwrMonitoringInletStatusEntry 40 } inletAppPowerPhase3b2 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The phase3b2 apparent power of inlet." ::= { pduPwrMonitoringInletStatusEntry 41 } inletAppPowerPhase1 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The phase1 apparent power of inlet." ::= { pduPwrMonitoringInletStatusEntry 42 } inletAppPowerPhase2 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The phase2 apparent power of inlet." ::= { pduPwrMonitoringInletStatusEntry 43 } inletAppPowerPhase3 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The phase3 apparent power of inlet." ::= { pduPwrMonitoringInletStatusEntry 44 } inletAppRcmCurrent OBJECT-TYPE SYNTAX INTEGER UNITS "0.1mA" ACCESS read-only STATUS mandatory DESCRIPTION "The RCM leackage current of inlet." ::= { pduPwrMonitoringInletStatusEntry 45 } inletLoadBalance OBJECT-TYPE SYNTAX INTEGER UNITS "1%" ACCESS read-only STATUS mandatory DESCRIPTION "The load balance of inlet." ::= { pduPwrMonitoringInletStatusEntry 46 } inletLoadBalanceStatus OBJECT-TYPE SYNTAX INTEGER { normal(1), warning(2), critical(3) } ACCESS read-only STATUS mandatory DESCRIPTION "The load balance of status inlet." ::= { pduPwrMonitoringInletStatusEntry 47 } inletResetFromPhase1 OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The reset phase1 date of inlet." ::= { pduPwrMonitoringInletStatusEntry 48 } inletEnergyPhase1 OBJECT-TYPE SYNTAX INTEGER UNITS "KWh" ACCESS read-only STATUS mandatory DESCRIPTION "The phase1 energy of inlet." ::= { pduPwrMonitoringInletStatusEntry 49 } inletResetFromPhase2 OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The reset phase2 date of inlet." ::= { pduPwrMonitoringInletStatusEntry 50 } inletEnergyPhase2 OBJECT-TYPE SYNTAX INTEGER UNITS "KWh" ACCESS read-only STATUS mandatory DESCRIPTION "The phase2 energy of inlet." ::= { pduPwrMonitoringInletStatusEntry 51 } inletResetFromPhase3 OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The reset phase3 date of inlet." ::= { pduPwrMonitoringInletStatusEntry 52 } inletEnergyPhase3 OBJECT-TYPE SYNTAX INTEGER UNITS "KWh" ACCESS read-only STATUS mandatory DESCRIPTION "The phase3 energy of inlet." ::= { pduPwrMonitoringInletStatusEntry 53 } inletFreqPhase1 OBJECT-TYPE SYNTAX INTEGER UNITS "0.01HZ" ACCESS read-only STATUS mandatory DESCRIPTION "The phase1 frequency of inlet." ::= { pduPwrMonitoringInletStatusEntry 54 } inletFreqPhase2 OBJECT-TYPE SYNTAX INTEGER UNITS "0.01HZ" ACCESS read-only STATUS mandatory DESCRIPTION "The phase2 frequency of inlet." ::= { pduPwrMonitoringInletStatusEntry 55 } inletFreqPhase3 OBJECT-TYPE SYNTAX INTEGER UNITS "0.01HZ" ACCESS read-only STATUS mandatory DESCRIPTION "The phase3 frequency of inlet." ::= { pduPwrMonitoringInletStatusEntry 56 } inletReactiveResetFrom OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The reset reactive date of inlet." ::= { pduPwrMonitoringInletStatusEntry 57 } inletReactiveEnergy OBJECT-TYPE SYNTAX INTEGER UNITS "KWh" ACCESS read-only STATUS mandatory DESCRIPTION "The total reactive energy of inlet." ::= { pduPwrMonitoringInletStatusEntry 58 } inletReactiveResetFromPhase1 OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The reset phase1 reactive date of inlet." ::= { pduPwrMonitoringInletStatusEntry 59 } inletReactiveEnergyPhase1 OBJECT-TYPE SYNTAX INTEGER UNITS "KWh" ACCESS read-only STATUS mandatory DESCRIPTION "The phase1 reactive energy of inlet." ::= { pduPwrMonitoringInletStatusEntry 60 } inletReactiveResetFromPhase2 OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The reset phase1 reactive date of inlet." ::= { pduPwrMonitoringInletStatusEntry 61 } inletReactiveEnergyPhase2 OBJECT-TYPE SYNTAX INTEGER UNITS "KWh" ACCESS read-only STATUS mandatory DESCRIPTION "The phase1 reactive energy of inlet." ::= { pduPwrMonitoringInletStatusEntry 62 } inletReactiveResetFromPhase3 OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The reset phase1 reactive date of inlet." ::= { pduPwrMonitoringInletStatusEntry 63 } inletReactiveEnergyPhase3 OBJECT-TYPE SYNTAX INTEGER UNITS "KWh" ACCESS read-only STATUS mandatory DESCRIPTION "The phase1 reactive energy of inlet." ::= { pduPwrMonitoringInletStatusEntry 64 } inletVarPowerPhase1b1 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The phase1b1 reactive power of inlet." ::= { pduPwrMonitoringInletStatusEntry 65 } inletVarPowerPhase2b1 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The phase2b1 reactive power of inlet." ::= { pduPwrMonitoringInletStatusEntry 66 } inletVarPowerPhase3b1 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The phase3b1 reactive power of inlet." ::= { pduPwrMonitoringInletStatusEntry 67 } inletVarPowerPhase1b2 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The phase1b2 reactive power of inlet." ::= { pduPwrMonitoringInletStatusEntry 68 } inletVarPowerPhase2b2 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The phase2b2 reactive power of inlet." ::= { pduPwrMonitoringInletStatusEntry 69 } inletVarPowerPhase3b2 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The phase3b2 reactive power of inlet." ::= { pduPwrMonitoringInletStatusEntry 70 } inletVarPowerPhase1 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The phase1 reactive power of inlet." ::= { pduPwrMonitoringInletStatusEntry 71 } inletVarPowerPhase2 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The phase2 reactive power of inlet." ::= { pduPwrMonitoringInletStatusEntry 72 } inletVarPowerPhase3 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The phase3 reactive power of inlet." ::= { pduPwrMonitoringInletStatusEntry 73 } -- =========================================================================== -- -- pduPwrMonitoringInletCfgTable -- -- Inlet Configuration Group -- -- =========================================================================== pduPwrMonitoringInletCfgTable OBJECT-TYPE SYNTAX SEQUENCE OF PduPwrMonitoringInletCfgEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to configure thresholds of inlet." ::= { pduPwrMonitoringInlet 3} pduPwrMonitoringInletCfgEntry OBJECT-TYPE SYNTAX PduPwrMonitoringInletCfgEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to configure thresholds of inlet." INDEX { inletCfgIndex} ::= { pduPwrMonitoringInletCfgTable 1 } PduPwrMonitoringInletCfgEntry ::= SEQUENCE { inletCfgIndex INTEGER, inletCfgLoadCritical INTEGER, inletCfgLoadWarning INTEGER, inletCfgCurrCritPhase1b1 INTEGER, inletCfgCurrCritPhase2b1 INTEGER, inletCfgCurrCritPhase3b1 INTEGER, inletCfgCurrCritPhase1b2 INTEGER, inletCfgCurrCritPhase2b2 INTEGER, inletCfgCurrCritPhase3b2 INTEGER, inletCfgCurrWarnPhase1b1 INTEGER, inletCfgCurrWarnPhase2b1 INTEGER, inletCfgCurrWarnPhase3b1 INTEGER, inletCfgCurrWarnPhase1b2 INTEGER, inletCfgCurrWarnPhase2b2 INTEGER, inletCfgCurrWarnPhase3b2 INTEGER, inletCfgVoltCritPhase1 INTEGER, inletCfgVoltCritPhase2 INTEGER, inletCfgVoltCritPhase3 INTEGER, inletCfgVoltWarnPhase1 INTEGER, inletCfgVoltWarnPhase2 INTEGER, inletCfgVoltWarnPhase3 INTEGER, inletCfgTotalCurrCritPhase1 INTEGER, inletCfgTotalCurrCritPhase2 INTEGER, inletCfgTotalCurrCritPhase3 INTEGER, inletCfgTotalCurrWarnPhase1 INTEGER, inletCfgTotalCurrWarnPhase2 INTEGER, inletCfgTotalCurrWarnPhase3 INTEGER, inletCfgRcmCurrThreshold INTEGER, inletCfgLoadBalanceCrit INTEGER, inletCfgLoadBalanceWarn INTEGER } inletCfgIndex OBJECT-TYPE SYNTAX INTEGER (0..3) ACCESS read-only STATUS mandatory DESCRIPTION "The index to inlet configuration entry." ::= { pduPwrMonitoringInletCfgEntry 1 } inletCfgLoadCritical OBJECT-TYPE SYNTAX INTEGER UNITS "0.1kW" ACCESS read-write STATUS mandatory DESCRIPTION "The Critical Threshold of inlet load." ::= { pduPwrMonitoringInletCfgEntry 2 } inletCfgLoadWarning OBJECT-TYPE SYNTAX INTEGER UNITS "0.1kW" ACCESS read-write STATUS mandatory DESCRIPTION "The Warning Threshold of inlet load." ::= { pduPwrMonitoringInletCfgEntry 3 } inletCfgCurrCritPhase1b1 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1A" ACCESS read-write STATUS mandatory DESCRIPTION "The Critical Threshold of pahse1b1 current of inlet." ::= { pduPwrMonitoringInletCfgEntry 4 } inletCfgCurrCritPhase2b1 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1A" ACCESS read-write STATUS mandatory DESCRIPTION "The Critical Threshold of pahse2b1 current of inlet." ::= { pduPwrMonitoringInletCfgEntry 5 } inletCfgCurrCritPhase3b1 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1A" ACCESS read-write STATUS mandatory DESCRIPTION "The Critical Threshold of pahse3b1 current of inlet." ::= { pduPwrMonitoringInletCfgEntry 6 } inletCfgCurrCritPhase1b2 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1A" ACCESS read-write STATUS mandatory DESCRIPTION "The Critical Threshold of pahse1b2 current of inlet." ::= { pduPwrMonitoringInletCfgEntry 7 } inletCfgCurrCritPhase2b2 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1A" ACCESS read-write STATUS mandatory DESCRIPTION "The Critical Threshold of pahse2b2 current of inlet." ::= { pduPwrMonitoringInletCfgEntry 8 } inletCfgCurrCritPhase3b2 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1A" ACCESS read-write STATUS mandatory DESCRIPTION "The Critical Threshold of pahse3b2 current of inlet." ::= { pduPwrMonitoringInletCfgEntry 9 } inletCfgCurrWarnPhase1b1 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1A" ACCESS read-write STATUS mandatory DESCRIPTION "The Warning Threshold of pahse1b1 current of inlet." ::= { pduPwrMonitoringInletCfgEntry 10 } inletCfgCurrWarnPhase2b1 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1A" ACCESS read-write STATUS mandatory DESCRIPTION "The Warning Threshold of pahse2b1 current of inlet." ::= { pduPwrMonitoringInletCfgEntry 11 } inletCfgCurrWarnPhase3b1 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1A" ACCESS read-write STATUS mandatory DESCRIPTION "The Warning Threshold of pahse3b1 current of inlet." ::= { pduPwrMonitoringInletCfgEntry 12 } inletCfgCurrWarnPhase1b2 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1A" ACCESS read-write STATUS mandatory DESCRIPTION "The Warning Threshold of pahse1b2 current of inlet." ::= { pduPwrMonitoringInletCfgEntry 13 } inletCfgCurrWarnPhase2b2 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1A" ACCESS read-write STATUS mandatory DESCRIPTION "The Warning Threshold of pahse2b2 current of inlet." ::= { pduPwrMonitoringInletCfgEntry 14 } inletCfgCurrWarnPhase3b2 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1A" ACCESS read-write STATUS mandatory DESCRIPTION "The Warning Threshold of pahse3b2 current of inlet." ::= { pduPwrMonitoringInletCfgEntry 15 } inletCfgVoltCritPhase1 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1V" ACCESS read-write STATUS mandatory DESCRIPTION "The Critical Threshold of pahse1 voltage of inlet." ::= { pduPwrMonitoringInletCfgEntry 16 } inletCfgVoltCritPhase2 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1V" ACCESS read-write STATUS mandatory DESCRIPTION "The Critical Threshold of pahse2 voltage of inlet." ::= { pduPwrMonitoringInletCfgEntry 17 } inletCfgVoltCritPhase3 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1V" ACCESS read-write STATUS mandatory DESCRIPTION "The Critical Threshold of pahse3 voltage of inlet." ::= { pduPwrMonitoringInletCfgEntry 18 } inletCfgVoltWarnPhase1 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1V" ACCESS read-write STATUS mandatory DESCRIPTION "The Warning Threshold of pahse1 voltage of inlet." ::= { pduPwrMonitoringInletCfgEntry 19 } inletCfgVoltWarnPhase2 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1V" ACCESS read-write STATUS mandatory DESCRIPTION "The Warning Threshold of pahse2 voltage of inlet." ::= { pduPwrMonitoringInletCfgEntry 20 } inletCfgVoltWarnPhase3 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1V" ACCESS read-write STATUS mandatory DESCRIPTION "The Warning Threshold of pahse3 voltage of inlet." ::= { pduPwrMonitoringInletCfgEntry 21 } inletCfgTotalCurrCritPhase1 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1A" ACCESS read-write STATUS mandatory DESCRIPTION "The Critical Threshold of pahse1 total current of inlet." ::= { pduPwrMonitoringInletCfgEntry 22 } inletCfgTotalCurrCritPhase2 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1A" ACCESS read-write STATUS mandatory DESCRIPTION "The Critical Threshold of pahse2 total current of inlet." ::= { pduPwrMonitoringInletCfgEntry 23 } inletCfgTotalCurrCritPhase3 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1A" ACCESS read-write STATUS mandatory DESCRIPTION "The Critical Threshold of pahse3 total current of inlet." ::= { pduPwrMonitoringInletCfgEntry 24 } inletCfgTotalCurrWarnPhase1 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1A" ACCESS read-write STATUS mandatory DESCRIPTION "The Warning Threshold of pahse1 total current of inlet." ::= { pduPwrMonitoringInletCfgEntry 25 } inletCfgTotalCurrWarnPhase2 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1A" ACCESS read-write STATUS mandatory DESCRIPTION "The Warning Threshold of pahse2 total current of inlet." ::= { pduPwrMonitoringInletCfgEntry 26 } inletCfgTotalCurrWarnPhase3 OBJECT-TYPE SYNTAX INTEGER UNITS "0.1A" ACCESS read-write STATUS mandatory DESCRIPTION "The Warning Threshold of pahse3 total current of inlet." ::= { pduPwrMonitoringInletCfgEntry 27 } inletCfgRcmCurrThreshold OBJECT-TYPE SYNTAX INTEGER UNITS "1mA" ACCESS read-write STATUS mandatory DESCRIPTION "The RCM Alarm threshold of inlet." ::= { pduPwrMonitoringInletCfgEntry 28 } inletCfgLoadBalanceCrit OBJECT-TYPE SYNTAX INTEGER UNITS "1%" ACCESS read-write STATUS mandatory DESCRIPTION "The Critical Threshold of load balance of inlet." ::= { pduPwrMonitoringInletCfgEntry 29 } inletCfgLoadBalanceWarn OBJECT-TYPE SYNTAX INTEGER UNITS "1%" ACCESS read-write STATUS mandatory DESCRIPTION "The Warning Threshold of load balance of inlet." ::= { pduPwrMonitoringInletCfgEntry 30 } pduPwrMonitoringOutlet OBJECT IDENTIFIER ::= { pduPwrMonitoring 2 } -- =========================================================================== -- -- pduPwrMonitoringOutlet -- -- Outlet Management Group of the device. -- -- =========================================================================== pduPwrMonitoringOutletPduA OBJECT IDENTIFIER ::= { pduPwrMonitoringOutlet 1 } -- =========================================================================== -- -- pduPwrMonitoringOutletPduA -- -- Outlet of Device1 management Group. -- -- =========================================================================== pduPwrMonitoringOutletNumPduA OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of PduA Outlet." ::= { pduPwrMonitoringOutletPduA 1} -- =========================================================================== -- -- pduPwrMonitoringOutletStatusTablePduA -- -- Outlet of Device1 Status Group. -- -- =========================================================================== pduPwrMonitoringOutletStatusTablePduA OBJECT-TYPE SYNTAX SEQUENCE OF PduPwrMonitoringOutletStatusPduAEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display status of PduA outlet." ::= { pduPwrMonitoringOutletPduA 2} pduPwrMonitoringOutletStatusPduAEntry OBJECT-TYPE SYNTAX PduPwrMonitoringOutletStatusPduAEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display status of PduA outlet." INDEX { outletPduAIndex} ::= { pduPwrMonitoringOutletStatusTablePduA 1 } PduPwrMonitoringOutletStatusPduAEntry ::= SEQUENCE { outletPduAIndex INTEGER, outletPduAState INTEGER, outletPduACurrent INTEGER, outletPduAPwrFactor INTEGER, outletPduAPower INTEGER, outletPduAEnergy INTEGER, outletPduAResetFrom DisplayString, outletPduAStatus INTEGER, outletPduAAppPower INTEGER, outletPduAVoltage INTEGER } outletPduAIndex OBJECT-TYPE SYNTAX INTEGER (0..41) ACCESS read-only STATUS mandatory DESCRIPTION "The index to outlet status of PduA." ::= { pduPwrMonitoringOutletStatusPduAEntry 1 } outletPduAState OBJECT-TYPE SYNTAX INTEGER { off(1), on(2) } ACCESS read-only STATUS mandatory DESCRIPTION "The state of PduA outlet." ::= { pduPwrMonitoringOutletStatusPduAEntry 2 } outletPduACurrent OBJECT-TYPE SYNTAX INTEGER UNITS "0.01A" ACCESS read-only STATUS mandatory DESCRIPTION "The current of PduA outlet." ::= { pduPwrMonitoringOutletStatusPduAEntry 3 } outletPduAPwrFactor OBJECT-TYPE SYNTAX INTEGER UNITS "0.1%" ACCESS read-only STATUS mandatory DESCRIPTION "The power factor of PduA outlet." ::= { pduPwrMonitoringOutletStatusPduAEntry 4 } outletPduAPower OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The active power of PduA outlet." ::= { pduPwrMonitoringOutletStatusPduAEntry 5 } outletPduAEnergy OBJECT-TYPE SYNTAX INTEGER UNITS "KWh" ACCESS read-only STATUS mandatory DESCRIPTION "The energy of PduA outlet." ::= { pduPwrMonitoringOutletStatusPduAEntry 6 } outletPduAResetFrom OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The reset date of PduA outlet." ::= { pduPwrMonitoringOutletStatusPduAEntry 7 } outletPduAStatus OBJECT-TYPE SYNTAX INTEGER { normal(1), warning(2), critical(3) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of PduA outlet." ::= { pduPwrMonitoringOutletStatusPduAEntry 8 } outletPduAAppPower OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The apparent power of PduA outlet." ::= { pduPwrMonitoringOutletStatusPduAEntry 9 } outletPduAVoltage OBJECT-TYPE SYNTAX INTEGER UNITS "0.1V" ACCESS read-only STATUS mandatory DESCRIPTION "The voltage of PduA outlet." ::= { pduPwrMonitoringOutletStatusPduAEntry 10 } -- =========================================================================== -- -- pduPwrMonitoringOutletCfgTablePduA -- -- Outlet of Device1 Configuration Group. -- -- =========================================================================== pduPwrMonitoringOutletCfgTablePduA OBJECT-TYPE SYNTAX SEQUENCE OF PduPwrMonitoringOutletCfgPduAEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display configuration of PduA outlet." ::= { pduPwrMonitoringOutletPduA 3} pduPwrMonitoringOutletCfgPduAEntry OBJECT-TYPE SYNTAX PduPwrMonitoringOutletCfgPduAEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display configuration of PduA outlet." INDEX { outletCfgPduAIndex} ::= { pduPwrMonitoringOutletCfgTablePduA 1 } PduPwrMonitoringOutletCfgPduAEntry ::= SEQUENCE { outletCfgPduAIndex INTEGER, outletCfgPduAName DisplayString, outletCfgPduADelayOnStatus INTEGER, outletCfgPduADelayOnTime INTEGER, outletCfgPduADelayOffStatus INTEGER, outletCfgPduADelayOffTime INTEGER, outletCfgPduAReboot INTEGER, outletCfgPduAOverCurrCritical INTEGER, outletCfgPduAOverCurrWarning INTEGER, outletCfgPduAOverPwrCritical INTEGER, outletCfgPduAOverPwrWarning INTEGER } outletCfgPduAIndex OBJECT-TYPE SYNTAX INTEGER (0..41) ACCESS read-only STATUS mandatory DESCRIPTION "The index to outlet configuration of PduA." ::= { pduPwrMonitoringOutletCfgPduAEntry 1 } outletCfgPduAName OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The name for outlet of PduA." ::= { pduPwrMonitoringOutletCfgPduAEntry 2 } outletCfgPduADelayOnStatus OBJECT-TYPE SYNTAX INTEGER { nodelay(1), delay(2) } ACCESS read-write STATUS mandatory DESCRIPTION "The Delay On status of PduA outlet." ::= { pduPwrMonitoringOutletCfgPduAEntry 3 } outletCfgPduADelayOnTime OBJECT-TYPE SYNTAX INTEGER UNITS "seconds" ACCESS read-write STATUS mandatory DESCRIPTION "The Delay On time of PduA outlet." ::= { pduPwrMonitoringOutletCfgPduAEntry 4 } outletCfgPduADelayOffStatus OBJECT-TYPE SYNTAX INTEGER { nodelay(1), delay(2) } ACCESS read-write STATUS mandatory DESCRIPTION "The Delay Off status of PduA outlet." ::= { pduPwrMonitoringOutletCfgPduAEntry 5 } outletCfgPduADelayOffTime OBJECT-TYPE SYNTAX INTEGER UNITS "seconds" ACCESS read-write STATUS mandatory DESCRIPTION "The Delay Off time of PduA outlet." ::= { pduPwrMonitoringOutletCfgPduAEntry 6 } outletCfgPduAReboot OBJECT-TYPE SYNTAX INTEGER UNITS "seconds" ACCESS read-write STATUS mandatory DESCRIPTION "The Delay On reboot duration of PduA outlet." ::= { pduPwrMonitoringOutletCfgPduAEntry 7 } outletCfgPduAOverCurrCritical OBJECT-TYPE SYNTAX INTEGER UNITS "0.1A" ACCESS read-write STATUS mandatory DESCRIPTION "The Critical Threshold of current of PduA outlet." ::= { pduPwrMonitoringOutletCfgPduAEntry 8 } outletCfgPduAOverCurrWarning OBJECT-TYPE SYNTAX INTEGER UNITS "0.1A" ACCESS read-write STATUS mandatory DESCRIPTION "The Warning Threshold of current of PduA outlet." ::= { pduPwrMonitoringOutletCfgPduAEntry 9 } outletCfgPduAOverPwrCritical OBJECT-TYPE SYNTAX INTEGER UNITS "1W" ACCESS read-write STATUS mandatory DESCRIPTION "The Critical Threshold of power of PduA outlet." ::= { pduPwrMonitoringOutletCfgPduAEntry 10 } outletCfgPduAOverPwrWarning OBJECT-TYPE SYNTAX INTEGER UNITS "1W" ACCESS read-write STATUS mandatory DESCRIPTION "The Warning Threshold of power of PduA outlet." ::= { pduPwrMonitoringOutletCfgPduAEntry 11 } -- =========================================================================== -- -- pduPwrMonitoringOutletCtlTablePduA -- -- Outlet of Device1 Control Group. -- -- =========================================================================== pduPwrMonitoringOutletCtlTablePduA OBJECT-TYPE SYNTAX SEQUENCE OF PduPwrMonitoringOutletCtlPduAEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display control of PduA outlet." ::= { pduPwrMonitoringOutletPduA 4} pduPwrMonitoringOutletCtlPduAEntry OBJECT-TYPE SYNTAX PduPwrMonitoringOutletCtlPduAEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display control of PduA outlet." INDEX { outletCtlPduAIndex} ::= { pduPwrMonitoringOutletCtlTablePduA 1 } PduPwrMonitoringOutletCtlPduAEntry ::= SEQUENCE { outletCtlPduAIndex INTEGER, outletCtlPduAControl INTEGER } outletCtlPduAIndex OBJECT-TYPE SYNTAX INTEGER (0..41) ACCESS read-only STATUS mandatory DESCRIPTION "The index to outlet control of PduA." ::= { pduPwrMonitoringOutletCtlPduAEntry 1 } outletCtlPduAControl OBJECT-TYPE SYNTAX INTEGER { nothing(1), immediateOn(2), delayedOn(3), immediateOff(4), delayedOff(5), immediateCycle(6), delayedCycle(7) } ACCESS read-write STATUS mandatory DESCRIPTION "The control-type of PduA outlet." ::= { pduPwrMonitoringOutletCtlPduAEntry 2 } pduPwrMonitoringOutletPduB OBJECT IDENTIFIER ::= { pduPwrMonitoringOutlet 2 } -- =========================================================================== -- -- pduPwrMonitoringOutletPduB -- -- Outlet of Device2 management Group. -- -- =========================================================================== pduPwrMonitoringOutletNumPduB OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of PduB Outlet." ::= { pduPwrMonitoringOutletPduB 1} -- =========================================================================== -- -- pduPwrMonitoringOutletStatusTablePduB -- -- Outlet of Device2 Status Group. -- -- =========================================================================== pduPwrMonitoringOutletStatusTablePduB OBJECT-TYPE SYNTAX SEQUENCE OF PduPwrMonitoringOutletStatusPduBEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display status of PduB outlet." ::= { pduPwrMonitoringOutletPduB 2} pduPwrMonitoringOutletStatusPduBEntry OBJECT-TYPE SYNTAX PduPwrMonitoringOutletStatusPduBEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display status of PduB outlet." INDEX { outletPduBIndex} ::= { pduPwrMonitoringOutletStatusTablePduB 1 } PduPwrMonitoringOutletStatusPduBEntry ::= SEQUENCE { outletPduBIndex INTEGER, outletPduBState INTEGER, outletPduBCurrent INTEGER, outletPduBPwrFactor INTEGER, outletPduBPower INTEGER, outletPduBEnergy INTEGER, outletPduBResetFrom DisplayString, outletPduBStatus INTEGER, outletPduBAppPower INTEGER, outletPduBVoltage INTEGER } outletPduBIndex OBJECT-TYPE SYNTAX INTEGER (0..41) ACCESS read-only STATUS mandatory DESCRIPTION "The index to outlet status of PduB." ::= { pduPwrMonitoringOutletStatusPduBEntry 1 } outletPduBState OBJECT-TYPE SYNTAX INTEGER { off(1), on(2) } ACCESS read-only STATUS mandatory DESCRIPTION "The state of PduB outlet." ::= { pduPwrMonitoringOutletStatusPduBEntry 2 } outletPduBCurrent OBJECT-TYPE SYNTAX INTEGER UNITS "0.01A" ACCESS read-only STATUS mandatory DESCRIPTION "The current of PduB outlet." ::= { pduPwrMonitoringOutletStatusPduBEntry 3 } outletPduBPwrFactor OBJECT-TYPE SYNTAX INTEGER UNITS "0.1%" ACCESS read-only STATUS mandatory DESCRIPTION "The power factor of PduB outlet." ::= { pduPwrMonitoringOutletStatusPduBEntry 4 } outletPduBPower OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The active power of PduB outlet." ::= { pduPwrMonitoringOutletStatusPduBEntry 5 } outletPduBEnergy OBJECT-TYPE SYNTAX INTEGER UNITS "KWh" ACCESS read-only STATUS mandatory DESCRIPTION "The energy of PduB outlet." ::= { pduPwrMonitoringOutletStatusPduBEntry 6 } outletPduBResetFrom OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The reset date of PduB outlet." ::= { pduPwrMonitoringOutletStatusPduBEntry 7 } outletPduBStatus OBJECT-TYPE SYNTAX INTEGER { normal(1), warning(2), critical(3) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of PduB outlet." ::= { pduPwrMonitoringOutletStatusPduBEntry 8 } outletPduBAppPower OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The apparent power of PduB outlet." ::= { pduPwrMonitoringOutletStatusPduBEntry 9 } outletPduBVoltage OBJECT-TYPE SYNTAX INTEGER UNITS "0.1V" ACCESS read-only STATUS mandatory DESCRIPTION "The voltage of PduB outlet." ::= { pduPwrMonitoringOutletStatusPduBEntry 10 } -- =========================================================================== -- -- pduPwrMonitoringOutletCfgTablePduB -- -- Outlet of Device2 Configuration Group. -- -- =========================================================================== pduPwrMonitoringOutletCfgTablePduB OBJECT-TYPE SYNTAX SEQUENCE OF PduPwrMonitoringOutletCfgPduBEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display configuration of PduB outlet." ::= { pduPwrMonitoringOutletPduB 3} pduPwrMonitoringOutletCfgPduBEntry OBJECT-TYPE SYNTAX PduPwrMonitoringOutletCfgPduBEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display configuration of PduB outlet." INDEX { outletCfgPduBIndex} ::= { pduPwrMonitoringOutletCfgTablePduB 1 } PduPwrMonitoringOutletCfgPduBEntry ::= SEQUENCE { outletCfgPduBIndex INTEGER, outletCfgPduBName DisplayString, outletCfgPduBDelayOnStatus INTEGER, outletCfgPduBDelayOnTime INTEGER, outletCfgPduBDelayOffStatus INTEGER, outletCfgPduBDelayOffTime INTEGER, outletCfgPduBReboot INTEGER, outletCfgPduBOverCurrCritical INTEGER, outletCfgPduBOverCurrWarning INTEGER, outletCfgPduBOverPwrCritical INTEGER, outletCfgPduBOverPwrWarning INTEGER } outletCfgPduBIndex OBJECT-TYPE SYNTAX INTEGER (0..41) ACCESS read-only STATUS mandatory DESCRIPTION "The index to outlet configuration of PduB." ::= { pduPwrMonitoringOutletCfgPduBEntry 1 } outletCfgPduBName OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The name for outlet of PduB." ::= { pduPwrMonitoringOutletCfgPduBEntry 2 } outletCfgPduBDelayOnStatus OBJECT-TYPE SYNTAX INTEGER { nodelay(1), delay(2) } ACCESS read-write STATUS mandatory DESCRIPTION "The Delay On status of PduB outlet." ::= { pduPwrMonitoringOutletCfgPduBEntry 3 } outletCfgPduBDelayOnTime OBJECT-TYPE SYNTAX INTEGER UNITS "seconds" ACCESS read-write STATUS mandatory DESCRIPTION "The Delay On time of PduB outlet." ::= { pduPwrMonitoringOutletCfgPduBEntry 4 } outletCfgPduBDelayOffStatus OBJECT-TYPE SYNTAX INTEGER { nodelay(1), delay(2) } ACCESS read-write STATUS mandatory DESCRIPTION "The Delay Off status of PduB outlet." ::= { pduPwrMonitoringOutletCfgPduBEntry 5 } outletCfgPduBDelayOffTime OBJECT-TYPE SYNTAX INTEGER UNITS "seconds" ACCESS read-write STATUS mandatory DESCRIPTION "The Delay Off time of PduB outlet." ::= { pduPwrMonitoringOutletCfgPduBEntry 6 } outletCfgPduBReboot OBJECT-TYPE SYNTAX INTEGER UNITS "seconds" ACCESS read-write STATUS mandatory DESCRIPTION "The Delay On reboot duration of PduB outlet." ::= { pduPwrMonitoringOutletCfgPduBEntry 7 } outletCfgPduBOverCurrCritical OBJECT-TYPE SYNTAX INTEGER UNITS "0.1A" ACCESS read-write STATUS mandatory DESCRIPTION "The Critical Threshold of current of PduB outlet." ::= { pduPwrMonitoringOutletCfgPduBEntry 8 } outletCfgPduBOverCurrWarning OBJECT-TYPE SYNTAX INTEGER UNITS "0.1A" ACCESS read-write STATUS mandatory DESCRIPTION "The Warning Threshold of current of PduB outlet." ::= { pduPwrMonitoringOutletCfgPduBEntry 9 } outletCfgPduBOverPwrCritical OBJECT-TYPE SYNTAX INTEGER UNITS "1W" ACCESS read-write STATUS mandatory DESCRIPTION "The Critical Threshold of power of PduB outlet." ::= { pduPwrMonitoringOutletCfgPduBEntry 10 } outletCfgPduBOverPwrWarning OBJECT-TYPE SYNTAX INTEGER UNITS "1W" ACCESS read-write STATUS mandatory DESCRIPTION "The Warning Threshold of power of PduB outlet." ::= { pduPwrMonitoringOutletCfgPduBEntry 11 } -- =========================================================================== -- -- pduPwrMonitoringOutletCtlTablePduB -- -- Outlet of Device2 Control Group. -- -- =========================================================================== pduPwrMonitoringOutletCtlTablePduB OBJECT-TYPE SYNTAX SEQUENCE OF PduPwrMonitoringOutletCtlPduBEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display control of PduB outlet." ::= { pduPwrMonitoringOutletPduB 4} pduPwrMonitoringOutletCtlPduBEntry OBJECT-TYPE SYNTAX PduPwrMonitoringOutletCtlPduBEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display control of PduB outlet." INDEX { outletCtlPduBIndex} ::= { pduPwrMonitoringOutletCtlTablePduB 1 } PduPwrMonitoringOutletCtlPduBEntry ::= SEQUENCE { outletCtlPduBIndex INTEGER, outletCtlPduBControl INTEGER } outletCtlPduBIndex OBJECT-TYPE SYNTAX INTEGER (0..41) ACCESS read-only STATUS mandatory DESCRIPTION "The index to outlet control of PduB." ::= { pduPwrMonitoringOutletCtlPduBEntry 1 } outletCtlPduBControl OBJECT-TYPE SYNTAX INTEGER { nothing(1), immediateOn(2), delayedOn(3), immediateOff(4), delayedOff(5), immediateCycle(6), delayedCycle(7) } ACCESS read-write STATUS mandatory DESCRIPTION "The control-type of PduB outlet." ::= { pduPwrMonitoringOutletCtlPduBEntry 2 } pduPwrMonitoringOutletPduC OBJECT IDENTIFIER ::= { pduPwrMonitoringOutlet 3 } -- =========================================================================== -- -- pduPwrMonitoringOutletPduC -- -- Outlet of Device3 management Group. -- -- =========================================================================== pduPwrMonitoringOutletNumPduC OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of PduC Outlet." ::= { pduPwrMonitoringOutletPduC 1} -- =========================================================================== -- -- pduPwrMonitoringOutletStatusTablePduC -- -- Outlet of Device3 Status Group. -- -- =========================================================================== pduPwrMonitoringOutletStatusTablePduC OBJECT-TYPE SYNTAX SEQUENCE OF PduPwrMonitoringOutletStatusPduCEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display status of PduC outlet." ::= { pduPwrMonitoringOutletPduC 2} pduPwrMonitoringOutletStatusPduCEntry OBJECT-TYPE SYNTAX PduPwrMonitoringOutletStatusPduCEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display status of PduC outlet." INDEX { outletPduCIndex} ::= { pduPwrMonitoringOutletStatusTablePduC 1 } PduPwrMonitoringOutletStatusPduCEntry ::= SEQUENCE { outletPduCIndex INTEGER, outletPduCState INTEGER, outletPduCCurrent INTEGER, outletPduCPwrFactor INTEGER, outletPduCPower INTEGER, outletPduCEnergy INTEGER, outletPduCResetFrom DisplayString, outletPduCStatus INTEGER, outletPduCAppPower INTEGER, outletPduCVoltage INTEGER } outletPduCIndex OBJECT-TYPE SYNTAX INTEGER (0..41) ACCESS read-only STATUS mandatory DESCRIPTION "The index to outlet status of PduC." ::= { pduPwrMonitoringOutletStatusPduCEntry 1 } outletPduCState OBJECT-TYPE SYNTAX INTEGER { off(1), on(2) } ACCESS read-only STATUS mandatory DESCRIPTION "The state of PduC outlet." ::= { pduPwrMonitoringOutletStatusPduCEntry 2 } outletPduCCurrent OBJECT-TYPE SYNTAX INTEGER UNITS "0.01A" ACCESS read-only STATUS mandatory DESCRIPTION "The current of PduC outlet." ::= { pduPwrMonitoringOutletStatusPduCEntry 3 } outletPduCPwrFactor OBJECT-TYPE SYNTAX INTEGER UNITS "0.1%" ACCESS read-only STATUS mandatory DESCRIPTION "The power factor of PduC outlet." ::= { pduPwrMonitoringOutletStatusPduCEntry 4 } outletPduCPower OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The active power of PduC outlet." ::= { pduPwrMonitoringOutletStatusPduCEntry 5 } outletPduCEnergy OBJECT-TYPE SYNTAX INTEGER UNITS "KWh" ACCESS read-only STATUS mandatory DESCRIPTION "The energy of PduC outlet." ::= { pduPwrMonitoringOutletStatusPduCEntry 6 } outletPduCResetFrom OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The reset date of PduC outlet." ::= { pduPwrMonitoringOutletStatusPduCEntry 7 } outletPduCStatus OBJECT-TYPE SYNTAX INTEGER { normal(1), warning(2), critical(3) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of PduC outlet." ::= { pduPwrMonitoringOutletStatusPduCEntry 8 } outletPduCAppPower OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The apparent power of PduC outlet." ::= { pduPwrMonitoringOutletStatusPduCEntry 9 } outletPduCVoltage OBJECT-TYPE SYNTAX INTEGER UNITS "0.1V" ACCESS read-only STATUS mandatory DESCRIPTION "The voltage of PduC outlet." ::= { pduPwrMonitoringOutletStatusPduCEntry 10 } -- =========================================================================== -- -- pduPwrMonitoringOutletCfgTablePduC -- -- Outlet of Device3 Configuration Group. -- -- =========================================================================== pduPwrMonitoringOutletCfgTablePduC OBJECT-TYPE SYNTAX SEQUENCE OF PduPwrMonitoringOutletCfgPduCEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display configuration of PduC outlet." ::= { pduPwrMonitoringOutletPduC 3} pduPwrMonitoringOutletCfgPduCEntry OBJECT-TYPE SYNTAX PduPwrMonitoringOutletCfgPduCEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display configuration of PduC outlet." INDEX { outletCfgPduCIndex} ::= { pduPwrMonitoringOutletCfgTablePduC 1 } PduPwrMonitoringOutletCfgPduCEntry ::= SEQUENCE { outletCfgPduCIndex INTEGER, outletCfgPduCName DisplayString, outletCfgPduCDelayOnStatus INTEGER, outletCfgPduCDelayOnTime INTEGER, outletCfgPduCDelayOffStatus INTEGER, outletCfgPduCDelayOffTime INTEGER, outletCfgPduCReboot INTEGER, outletCfgPduCOverCurrCritical INTEGER, outletCfgPduCOverCurrWarning INTEGER, outletCfgPduCOverPwrCritical INTEGER, outletCfgPduCOverPwrWarning INTEGER } outletCfgPduCIndex OBJECT-TYPE SYNTAX INTEGER (0..41) ACCESS read-only STATUS mandatory DESCRIPTION "The index to outlet configuration of PduC." ::= { pduPwrMonitoringOutletCfgPduCEntry 1 } outletCfgPduCName OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The name for outlet of PduC." ::= { pduPwrMonitoringOutletCfgPduCEntry 2 } outletCfgPduCDelayOnStatus OBJECT-TYPE SYNTAX INTEGER { nodelay(1), delay(2) } ACCESS read-write STATUS mandatory DESCRIPTION "The Delay On status of PduC outlet." ::= { pduPwrMonitoringOutletCfgPduCEntry 3 } outletCfgPduCDelayOnTime OBJECT-TYPE SYNTAX INTEGER UNITS "seconds" ACCESS read-write STATUS mandatory DESCRIPTION "The Delay On time of PduC outlet." ::= { pduPwrMonitoringOutletCfgPduCEntry 4 } outletCfgPduCDelayOffStatus OBJECT-TYPE SYNTAX INTEGER { nodelay(1), delay(2) } ACCESS read-write STATUS mandatory DESCRIPTION "The Delay Off status of PduC outlet." ::= { pduPwrMonitoringOutletCfgPduCEntry 5 } outletCfgPduCDelayOffTime OBJECT-TYPE SYNTAX INTEGER UNITS "seconds" ACCESS read-write STATUS mandatory DESCRIPTION "The Delay Off time of PduC outlet." ::= { pduPwrMonitoringOutletCfgPduCEntry 6 } outletCfgPduCReboot OBJECT-TYPE SYNTAX INTEGER UNITS "seconds" ACCESS read-write STATUS mandatory DESCRIPTION "The Delay On reboot duration of PduC outlet." ::= { pduPwrMonitoringOutletCfgPduCEntry 7 } outletCfgPduCOverCurrCritical OBJECT-TYPE SYNTAX INTEGER UNITS "0.1A" ACCESS read-write STATUS mandatory DESCRIPTION "The Critical Threshold of current of PduC outlet." ::= { pduPwrMonitoringOutletCfgPduCEntry 8 } outletCfgPduCOverCurrWarning OBJECT-TYPE SYNTAX INTEGER UNITS "0.1A" ACCESS read-write STATUS mandatory DESCRIPTION "The Warning Threshold of current of PduC outlet." ::= { pduPwrMonitoringOutletCfgPduCEntry 9 } outletCfgPduCOverPwrCritical OBJECT-TYPE SYNTAX INTEGER UNITS "1W" ACCESS read-write STATUS mandatory DESCRIPTION "The Critical Threshold of power of PduC outlet." ::= { pduPwrMonitoringOutletCfgPduCEntry 10 } outletCfgPduCOverPwrWarning OBJECT-TYPE SYNTAX INTEGER UNITS "1W" ACCESS read-write STATUS mandatory DESCRIPTION "The Warning Threshold of power of PduC outlet." ::= { pduPwrMonitoringOutletCfgPduCEntry 11 } -- =========================================================================== -- -- pduPwrMonitoringOutletCtlTablePduC -- -- Outlet of Device3 Control Group. -- -- =========================================================================== pduPwrMonitoringOutletCtlTablePduC OBJECT-TYPE SYNTAX SEQUENCE OF PduPwrMonitoringOutletCtlPduCEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display control of PduC outlet." ::= { pduPwrMonitoringOutletPduC 4} pduPwrMonitoringOutletCtlPduCEntry OBJECT-TYPE SYNTAX PduPwrMonitoringOutletCtlPduCEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display control of PduC outlet." INDEX { outletCtlPduCIndex} ::= { pduPwrMonitoringOutletCtlTablePduC 1 } PduPwrMonitoringOutletCtlPduCEntry ::= SEQUENCE { outletCtlPduCIndex INTEGER, outletCtlPduCControl INTEGER } outletCtlPduCIndex OBJECT-TYPE SYNTAX INTEGER (0..41) ACCESS read-only STATUS mandatory DESCRIPTION "The index to outlet control of PduC." ::= { pduPwrMonitoringOutletCtlPduCEntry 1 } outletCtlPduCControl OBJECT-TYPE SYNTAX INTEGER { nothing(1), immediateOn(2), delayedOn(3), immediateOff(4), delayedOff(5), immediateCycle(6), delayedCycle(7) } ACCESS read-write STATUS mandatory DESCRIPTION "The control-type of PduC outlet." ::= { pduPwrMonitoringOutletCtlPduCEntry 2 } pduPwrMonitoringOutletPduD OBJECT IDENTIFIER ::= { pduPwrMonitoringOutlet 4 } -- =========================================================================== -- -- pduPwrMonitoringOutletPduD -- -- Outlet of Device4 management Group. -- -- =========================================================================== pduPwrMonitoringOutletNumPduD OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of PduD Outlet." ::= { pduPwrMonitoringOutletPduD 1} -- =========================================================================== -- -- pduPwrMonitoringOutletStatusTablePduD -- -- Outlet of Device4 Status Group. -- -- =========================================================================== pduPwrMonitoringOutletStatusTablePduD OBJECT-TYPE SYNTAX SEQUENCE OF PduPwrMonitoringOutletStatusPduDEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display status of PduD outlet." ::= { pduPwrMonitoringOutletPduD 2} pduPwrMonitoringOutletStatusPduDEntry OBJECT-TYPE SYNTAX PduPwrMonitoringOutletStatusPduDEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display status of PduD outlet." INDEX { outletPduDIndex} ::= { pduPwrMonitoringOutletStatusTablePduD 1 } PduPwrMonitoringOutletStatusPduDEntry ::= SEQUENCE { outletPduDIndex INTEGER, outletPduDState INTEGER, outletPduDCurrent INTEGER, outletPduDPwrFactor INTEGER, outletPduDPower INTEGER, outletPduDEnergy INTEGER, outletPduDResetFrom DisplayString, outletPduDStatus INTEGER, outletPduDAppPower INTEGER, outletPduDVoltage INTEGER } outletPduDIndex OBJECT-TYPE SYNTAX INTEGER (0..41) ACCESS read-only STATUS mandatory DESCRIPTION "The index to outlet status of PduD." ::= { pduPwrMonitoringOutletStatusPduDEntry 1 } outletPduDState OBJECT-TYPE SYNTAX INTEGER { off(1), on(2) } ACCESS read-only STATUS mandatory DESCRIPTION "The state of PduD outlet." ::= { pduPwrMonitoringOutletStatusPduDEntry 2 } outletPduDCurrent OBJECT-TYPE SYNTAX INTEGER UNITS "0.01A" ACCESS read-only STATUS mandatory DESCRIPTION "The current of PduD outlet." ::= { pduPwrMonitoringOutletStatusPduDEntry 3 } outletPduDPwrFactor OBJECT-TYPE SYNTAX INTEGER UNITS "0.1%" ACCESS read-only STATUS mandatory DESCRIPTION "The power factor of PduD outlet." ::= { pduPwrMonitoringOutletStatusPduDEntry 4 } outletPduDPower OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The active power of PduD outlet." ::= { pduPwrMonitoringOutletStatusPduDEntry 5 } outletPduDEnergy OBJECT-TYPE SYNTAX INTEGER UNITS "KWh" ACCESS read-only STATUS mandatory DESCRIPTION "The energy of PduD outlet." ::= { pduPwrMonitoringOutletStatusPduDEntry 6 } outletPduDResetFrom OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The reset date of PduD outlet." ::= { pduPwrMonitoringOutletStatusPduDEntry 7 } outletPduDStatus OBJECT-TYPE SYNTAX INTEGER { normal(1), warning(2), critical(3) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of PduD outlet." ::= { pduPwrMonitoringOutletStatusPduDEntry 8 } outletPduDAppPower OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The apparent power of PduD outlet." ::= { pduPwrMonitoringOutletStatusPduDEntry 9 } outletPduDVoltage OBJECT-TYPE SYNTAX INTEGER UNITS "0.1V" ACCESS read-only STATUS mandatory DESCRIPTION "The voltage of PduD outlet." ::= { pduPwrMonitoringOutletStatusPduDEntry 10 } -- =========================================================================== -- -- pduPwrMonitoringOutletCfgTablePduD -- -- Outlet of Device4 Configuration Group. -- -- =========================================================================== pduPwrMonitoringOutletCfgTablePduD OBJECT-TYPE SYNTAX SEQUENCE OF PduPwrMonitoringOutletCfgPduDEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display configuration of PduD outlet." ::= { pduPwrMonitoringOutletPduD 3} pduPwrMonitoringOutletCfgPduDEntry OBJECT-TYPE SYNTAX PduPwrMonitoringOutletCfgPduDEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display configuration of PduD outlet." INDEX { outletCfgPduDIndex} ::= { pduPwrMonitoringOutletCfgTablePduD 1 } PduPwrMonitoringOutletCfgPduDEntry ::= SEQUENCE { outletCfgPduDIndex INTEGER, outletCfgPduDName DisplayString, outletCfgPduDDelayOnStatus INTEGER, outletCfgPduDDelayOnTime INTEGER, outletCfgPduDDelayOffStatus INTEGER, outletCfgPduDDelayOffTime INTEGER, outletCfgPduDReboot INTEGER, outletCfgPduDOverCurrCritical INTEGER, outletCfgPduDOverCurrWarning INTEGER, outletCfgPduDOverPwrCritical INTEGER, outletCfgPduDOverPwrWarning INTEGER } outletCfgPduDIndex OBJECT-TYPE SYNTAX INTEGER (0..41) ACCESS read-only STATUS mandatory DESCRIPTION "The index to outlet configuration of PduD." ::= { pduPwrMonitoringOutletCfgPduDEntry 1 } outletCfgPduDName OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The name for outlet of PduD." ::= { pduPwrMonitoringOutletCfgPduDEntry 2 } outletCfgPduDDelayOnStatus OBJECT-TYPE SYNTAX INTEGER { nodelay(1), delay(2) } ACCESS read-write STATUS mandatory DESCRIPTION "The Delay On status of PduD outlet." ::= { pduPwrMonitoringOutletCfgPduDEntry 3 } outletCfgPduDDelayOnTime OBJECT-TYPE SYNTAX INTEGER UNITS "seconds" ACCESS read-write STATUS mandatory DESCRIPTION "The Delay On time of PduD outlet." ::= { pduPwrMonitoringOutletCfgPduDEntry 4 } outletCfgPduDDelayOffStatus OBJECT-TYPE SYNTAX INTEGER { nodelay(1), delay(2) } ACCESS read-write STATUS mandatory DESCRIPTION "The Delay Off status of PduD outlet." ::= { pduPwrMonitoringOutletCfgPduDEntry 5 } outletCfgPduDDelayOffTime OBJECT-TYPE SYNTAX INTEGER UNITS "seconds" ACCESS read-write STATUS mandatory DESCRIPTION "The Delay Off time of PduD outlet." ::= { pduPwrMonitoringOutletCfgPduDEntry 6 } outletCfgPduDReboot OBJECT-TYPE SYNTAX INTEGER UNITS "seconds" ACCESS read-write STATUS mandatory DESCRIPTION "The Delay On reboot duration of PduD outlet." ::= { pduPwrMonitoringOutletCfgPduDEntry 7 } outletCfgPduDOverCurrCritical OBJECT-TYPE SYNTAX INTEGER UNITS "0.1A" ACCESS read-write STATUS mandatory DESCRIPTION "The Critical Threshold of current of PduD outlet." ::= { pduPwrMonitoringOutletCfgPduDEntry 8 } outletCfgPduDOverCurrWarning OBJECT-TYPE SYNTAX INTEGER UNITS "0.1A" ACCESS read-write STATUS mandatory DESCRIPTION "The Warning Threshold of current of PduD outlet." ::= { pduPwrMonitoringOutletCfgPduDEntry 9 } outletCfgPduDOverPwrCritical OBJECT-TYPE SYNTAX INTEGER UNITS "1W" ACCESS read-write STATUS mandatory DESCRIPTION "The Critical Threshold of power of PduD outlet." ::= { pduPwrMonitoringOutletCfgPduDEntry 10 } outletCfgPduDOverPwrWarning OBJECT-TYPE SYNTAX INTEGER UNITS "1W" ACCESS read-write STATUS mandatory DESCRIPTION "The Warning Threshold of power of PduD outlet." ::= { pduPwrMonitoringOutletCfgPduDEntry 11 } -- =========================================================================== -- -- pduPwrMonitoringOutletCtlTablePduD -- -- Outlet of Device4 Control Group. -- -- =========================================================================== pduPwrMonitoringOutletCtlTablePduD OBJECT-TYPE SYNTAX SEQUENCE OF PduPwrMonitoringOutletCtlPduDEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display control of PduD outlet." ::= { pduPwrMonitoringOutletPduD 4} pduPwrMonitoringOutletCtlPduDEntry OBJECT-TYPE SYNTAX PduPwrMonitoringOutletCtlPduDEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display control of PduD outlet." INDEX { outletCtlPduDIndex} ::= { pduPwrMonitoringOutletCtlTablePduD 1 } PduPwrMonitoringOutletCtlPduDEntry ::= SEQUENCE { outletCtlPduDIndex INTEGER, outletCtlPduDControl INTEGER } outletCtlPduDIndex OBJECT-TYPE SYNTAX INTEGER (0..41) ACCESS read-only STATUS mandatory DESCRIPTION "The index to outlet control of PduD." ::= { pduPwrMonitoringOutletCtlPduDEntry 1 } outletCtlPduDControl OBJECT-TYPE SYNTAX INTEGER { nothing(1), immediateOn(2), delayedOn(3), immediateOff(4), delayedOff(5), immediateCycle(6), delayedCycle(7) } ACCESS read-write STATUS mandatory DESCRIPTION "The control-type of PduD outlet." ::= { pduPwrMonitoringOutletCtlPduDEntry 2 } pduPwrMonitoringOutletPduE OBJECT IDENTIFIER ::= { pduPwrMonitoringOutlet 5 } -- =========================================================================== -- -- pduPwrMonitoringOutletPduE -- -- Outlet of Device5 management Group. -- -- =========================================================================== pduPwrMonitoringOutletNumPduE OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of PduE Outlet." ::= { pduPwrMonitoringOutletPduE 1} -- =========================================================================== -- -- pduPwrMonitoringOutletStatusTablePduE -- -- Outlet of Device5 Status Group. -- -- =========================================================================== pduPwrMonitoringOutletStatusTablePduE OBJECT-TYPE SYNTAX SEQUENCE OF PduPwrMonitoringOutletStatusPduEEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display status of PduE outlet." ::= { pduPwrMonitoringOutletPduE 2} pduPwrMonitoringOutletStatusPduEEntry OBJECT-TYPE SYNTAX PduPwrMonitoringOutletStatusPduEEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display status of PduE outlet." INDEX { outletPduEIndex} ::= { pduPwrMonitoringOutletStatusTablePduE 1 } PduPwrMonitoringOutletStatusPduEEntry ::= SEQUENCE { outletPduEIndex INTEGER, outletPduEState INTEGER, outletPduECurrent INTEGER, outletPduEPwrFactor INTEGER, outletPduEPower INTEGER, outletPduEEnergy INTEGER, outletPduEResetFrom DisplayString, outletPduEStatus INTEGER, outletPduEAppPower INTEGER, outletPduEVoltage INTEGER } outletPduEIndex OBJECT-TYPE SYNTAX INTEGER (0..41) ACCESS read-only STATUS mandatory DESCRIPTION "The index to outlet status of PduE." ::= { pduPwrMonitoringOutletStatusPduEEntry 1 } outletPduEState OBJECT-TYPE SYNTAX INTEGER { off(1), on(2) } ACCESS read-only STATUS mandatory DESCRIPTION "The state of PduE outlet." ::= { pduPwrMonitoringOutletStatusPduEEntry 2 } outletPduECurrent OBJECT-TYPE SYNTAX INTEGER UNITS "0.01A" ACCESS read-only STATUS mandatory DESCRIPTION "The current of PduE outlet." ::= { pduPwrMonitoringOutletStatusPduEEntry 3 } outletPduEPwrFactor OBJECT-TYPE SYNTAX INTEGER UNITS "0.1%" ACCESS read-only STATUS mandatory DESCRIPTION "The power factor of PduE outlet." ::= { pduPwrMonitoringOutletStatusPduEEntry 4 } outletPduEPower OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The active power of PduE outlet." ::= { pduPwrMonitoringOutletStatusPduEEntry 5 } outletPduEEnergy OBJECT-TYPE SYNTAX INTEGER UNITS "KWh" ACCESS read-only STATUS mandatory DESCRIPTION "The energy of PduE outlet." ::= { pduPwrMonitoringOutletStatusPduEEntry 6 } outletPduEResetFrom OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The reset date of PduE outlet." ::= { pduPwrMonitoringOutletStatusPduEEntry 7 } outletPduEStatus OBJECT-TYPE SYNTAX INTEGER { normal(1), warning(2), critical(3) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of PduE outlet." ::= { pduPwrMonitoringOutletStatusPduEEntry 8 } outletPduEAppPower OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The apparent power of PduE outlet." ::= { pduPwrMonitoringOutletStatusPduEEntry 9 } outletPduEVoltage OBJECT-TYPE SYNTAX INTEGER UNITS "0.1V" ACCESS read-only STATUS mandatory DESCRIPTION "The voltage of PduE outlet." ::= { pduPwrMonitoringOutletStatusPduEEntry 10 } -- =========================================================================== -- -- pduPwrMonitoringOutletCfgTablePduE -- -- Outlet of Device5 Configuration Group. -- -- =========================================================================== pduPwrMonitoringOutletCfgTablePduE OBJECT-TYPE SYNTAX SEQUENCE OF PduPwrMonitoringOutletCfgPduEEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display configuration of PduE outlet." ::= { pduPwrMonitoringOutletPduE 3} pduPwrMonitoringOutletCfgPduEEntry OBJECT-TYPE SYNTAX PduPwrMonitoringOutletCfgPduEEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display configuration of PduE outlet." INDEX { outletCfgPduEIndex} ::= { pduPwrMonitoringOutletCfgTablePduE 1 } PduPwrMonitoringOutletCfgPduEEntry ::= SEQUENCE { outletCfgPduEIndex INTEGER, outletCfgPduEName DisplayString, outletCfgPduEDelayOnStatus INTEGER, outletCfgPduEDelayOnTime INTEGER, outletCfgPduEDelayOffStatus INTEGER, outletCfgPduEDelayOffTime INTEGER, outletCfgPduEReboot INTEGER, outletCfgPduEOverCurrCritical INTEGER, outletCfgPduEOverCurrWarning INTEGER, outletCfgPduEOverPwrCritical INTEGER, outletCfgPduEOverPwrWarning INTEGER } outletCfgPduEIndex OBJECT-TYPE SYNTAX INTEGER (0..41) ACCESS read-only STATUS mandatory DESCRIPTION "The index to outlet configuration of PduE." ::= { pduPwrMonitoringOutletCfgPduEEntry 1 } outletCfgPduEName OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The name for outlet of PduE." ::= { pduPwrMonitoringOutletCfgPduEEntry 2 } outletCfgPduEDelayOnStatus OBJECT-TYPE SYNTAX INTEGER { nodelay(1), delay(2) } ACCESS read-write STATUS mandatory DESCRIPTION "The Delay On status of PduE outlet." ::= { pduPwrMonitoringOutletCfgPduEEntry 3 } outletCfgPduEDelayOnTime OBJECT-TYPE SYNTAX INTEGER UNITS "seconds" ACCESS read-write STATUS mandatory DESCRIPTION "The Delay On time of PduE outlet." ::= { pduPwrMonitoringOutletCfgPduEEntry 4 } outletCfgPduEDelayOffStatus OBJECT-TYPE SYNTAX INTEGER { nodelay(1), delay(2) } ACCESS read-write STATUS mandatory DESCRIPTION "The Delay Off status of PduE outlet." ::= { pduPwrMonitoringOutletCfgPduEEntry 5 } outletCfgPduEDelayOffTime OBJECT-TYPE SYNTAX INTEGER UNITS "seconds" ACCESS read-write STATUS mandatory DESCRIPTION "The Delay Off time of PduE outlet." ::= { pduPwrMonitoringOutletCfgPduEEntry 6 } outletCfgPduEReboot OBJECT-TYPE SYNTAX INTEGER UNITS "seconds" ACCESS read-write STATUS mandatory DESCRIPTION "The Delay On reboot duration of PduE outlet." ::= { pduPwrMonitoringOutletCfgPduEEntry 7 } outletCfgPduEOverCurrCritical OBJECT-TYPE SYNTAX INTEGER UNITS "0.1A" ACCESS read-write STATUS mandatory DESCRIPTION "The Critical Threshold of current of PduE outlet." ::= { pduPwrMonitoringOutletCfgPduEEntry 8 } outletCfgPduEOverCurrWarning OBJECT-TYPE SYNTAX INTEGER UNITS "0.1A" ACCESS read-write STATUS mandatory DESCRIPTION "The Warning Threshold of current of PduE outlet." ::= { pduPwrMonitoringOutletCfgPduEEntry 9 } outletCfgPduEOverPwrCritical OBJECT-TYPE SYNTAX INTEGER UNITS "1W" ACCESS read-write STATUS mandatory DESCRIPTION "The Critical Threshold of power of PduE outlet." ::= { pduPwrMonitoringOutletCfgPduEEntry 10 } outletCfgPduEOverPwrWarning OBJECT-TYPE SYNTAX INTEGER UNITS "1W" ACCESS read-write STATUS mandatory DESCRIPTION "The Warning Threshold of power of PduE outlet." ::= { pduPwrMonitoringOutletCfgPduEEntry 11 } -- =========================================================================== -- -- pduPwrMonitoringOutletCtlTablePduE -- -- Outlet of Device5 Control Group. -- -- =========================================================================== pduPwrMonitoringOutletCtlTablePduE OBJECT-TYPE SYNTAX SEQUENCE OF PduPwrMonitoringOutletCtlPduEEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display control of PduE outlet." ::= { pduPwrMonitoringOutletPduE 4} pduPwrMonitoringOutletCtlPduEEntry OBJECT-TYPE SYNTAX PduPwrMonitoringOutletCtlPduEEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display control of PduE outlet." INDEX { outletCtlPduEIndex} ::= { pduPwrMonitoringOutletCtlTablePduE 1 } PduPwrMonitoringOutletCtlPduEEntry ::= SEQUENCE { outletCtlPduEIndex INTEGER, outletCtlPduEControl INTEGER } outletCtlPduEIndex OBJECT-TYPE SYNTAX INTEGER (0..41) ACCESS read-only STATUS mandatory DESCRIPTION "The index to outlet control of PduE." ::= { pduPwrMonitoringOutletCtlPduEEntry 1 } outletCtlPduEControl OBJECT-TYPE SYNTAX INTEGER { nothing(1), immediateOn(2), delayedOn(3), immediateOff(4), delayedOff(5), immediateCycle(6), delayedCycle(7) } ACCESS read-write STATUS mandatory DESCRIPTION "The control-type of PduE outlet." ::= { pduPwrMonitoringOutletCtlPduEEntry 2 } pduPwrMonitoringOutletPduF OBJECT IDENTIFIER ::= { pduPwrMonitoringOutlet 6 } -- =========================================================================== -- -- pduPwrMonitoringOutletPduF -- -- Outlet of Device6 management Group. -- -- =========================================================================== pduPwrMonitoringOutletNumPduF OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of PduF Outlet." ::= { pduPwrMonitoringOutletPduF 1} -- =========================================================================== -- -- pduPwrMonitoringOutletStatusTablePduF -- -- Outlet of Device6 Status Group. -- -- =========================================================================== pduPwrMonitoringOutletStatusTablePduF OBJECT-TYPE SYNTAX SEQUENCE OF PduPwrMonitoringOutletStatusPduFEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display status of PduF outlet." ::= { pduPwrMonitoringOutletPduF 2} pduPwrMonitoringOutletStatusPduFEntry OBJECT-TYPE SYNTAX PduPwrMonitoringOutletStatusPduFEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display status of PduF outlet." INDEX { outletPduFIndex} ::= { pduPwrMonitoringOutletStatusTablePduF 1 } PduPwrMonitoringOutletStatusPduFEntry ::= SEQUENCE { outletPduFIndex INTEGER, outletPduFState INTEGER, outletPduFCurrent INTEGER, outletPduFPwrFactor INTEGER, outletPduFPower INTEGER, outletPduFEnergy INTEGER, outletPduFResetFrom DisplayString, outletPduFStatus INTEGER, outletPduFAppPower INTEGER, outletPduFVoltage INTEGER } outletPduFIndex OBJECT-TYPE SYNTAX INTEGER (0..41) ACCESS read-only STATUS mandatory DESCRIPTION "The index to outlet status of PduF." ::= { pduPwrMonitoringOutletStatusPduFEntry 1 } outletPduFState OBJECT-TYPE SYNTAX INTEGER { off(1), on(2) } ACCESS read-only STATUS mandatory DESCRIPTION "The state of PduF outlet." ::= { pduPwrMonitoringOutletStatusPduFEntry 2 } outletPduFCurrent OBJECT-TYPE SYNTAX INTEGER UNITS "0.01A" ACCESS read-only STATUS mandatory DESCRIPTION "The current of PduF outlet." ::= { pduPwrMonitoringOutletStatusPduFEntry 3 } outletPduFPwrFactor OBJECT-TYPE SYNTAX INTEGER UNITS "0.1%" ACCESS read-only STATUS mandatory DESCRIPTION "The power factor of PduF outlet." ::= { pduPwrMonitoringOutletStatusPduFEntry 4 } outletPduFPower OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The active power of PduF outlet." ::= { pduPwrMonitoringOutletStatusPduFEntry 5 } outletPduFEnergy OBJECT-TYPE SYNTAX INTEGER UNITS "KWh" ACCESS read-only STATUS mandatory DESCRIPTION "The energy of PduF outlet." ::= { pduPwrMonitoringOutletStatusPduFEntry 6 } outletPduFResetFrom OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The reset date of PduF outlet." ::= { pduPwrMonitoringOutletStatusPduFEntry 7 } outletPduFStatus OBJECT-TYPE SYNTAX INTEGER { normal(1), warning(2), critical(3) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of PduF outlet." ::= { pduPwrMonitoringOutletStatusPduFEntry 8 } outletPduFAppPower OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The apparent power of PduF outlet." ::= { pduPwrMonitoringOutletStatusPduFEntry 9 } outletPduFVoltage OBJECT-TYPE SYNTAX INTEGER UNITS "0.1V" ACCESS read-only STATUS mandatory DESCRIPTION "The voltage of PduF outlet." ::= { pduPwrMonitoringOutletStatusPduFEntry 10 } -- =========================================================================== -- -- pduPwrMonitoringOutletCfgTablePduF -- -- Outlet of Device6 Configuration Group. -- -- =========================================================================== pduPwrMonitoringOutletCfgTablePduF OBJECT-TYPE SYNTAX SEQUENCE OF PduPwrMonitoringOutletCfgPduFEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display configuration of PduF outlet." ::= { pduPwrMonitoringOutletPduF 3} pduPwrMonitoringOutletCfgPduFEntry OBJECT-TYPE SYNTAX PduPwrMonitoringOutletCfgPduFEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display configuration of PduF outlet." INDEX { outletCfgPduFIndex} ::= { pduPwrMonitoringOutletCfgTablePduF 1 } PduPwrMonitoringOutletCfgPduFEntry ::= SEQUENCE { outletCfgPduFIndex INTEGER, outletCfgPduFName DisplayString, outletCfgPduFDelayOnStatus INTEGER, outletCfgPduFDelayOnTime INTEGER, outletCfgPduFDelayOffStatus INTEGER, outletCfgPduFDelayOffTime INTEGER, outletCfgPduFReboot INTEGER, outletCfgPduFOverCurrCritical INTEGER, outletCfgPduFOverCurrWarning INTEGER, outletCfgPduFOverPwrCritical INTEGER, outletCfgPduFOverPwrWarning INTEGER } outletCfgPduFIndex OBJECT-TYPE SYNTAX INTEGER (0..41) ACCESS read-only STATUS mandatory DESCRIPTION "The index to outlet configuration of PduF." ::= { pduPwrMonitoringOutletCfgPduFEntry 1 } outletCfgPduFName OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The name for outlet of PduF." ::= { pduPwrMonitoringOutletCfgPduFEntry 2 } outletCfgPduFDelayOnStatus OBJECT-TYPE SYNTAX INTEGER { nodelay(1), delay(2) } ACCESS read-write STATUS mandatory DESCRIPTION "The Delay On status of PduF outlet." ::= { pduPwrMonitoringOutletCfgPduFEntry 3 } outletCfgPduFDelayOnTime OBJECT-TYPE SYNTAX INTEGER UNITS "seconds" ACCESS read-write STATUS mandatory DESCRIPTION "The Delay On time of PduF outlet." ::= { pduPwrMonitoringOutletCfgPduFEntry 4 } outletCfgPduFDelayOffStatus OBJECT-TYPE SYNTAX INTEGER { nodelay(1), delay(2) } ACCESS read-write STATUS mandatory DESCRIPTION "The Delay Off status of PduF outlet." ::= { pduPwrMonitoringOutletCfgPduFEntry 5 } outletCfgPduFDelayOffTime OBJECT-TYPE SYNTAX INTEGER UNITS "seconds" ACCESS read-write STATUS mandatory DESCRIPTION "The Delay Off time of PduF outlet." ::= { pduPwrMonitoringOutletCfgPduFEntry 6 } outletCfgPduFReboot OBJECT-TYPE SYNTAX INTEGER UNITS "seconds" ACCESS read-write STATUS mandatory DESCRIPTION "The Delay On reboot duration of PduF outlet." ::= { pduPwrMonitoringOutletCfgPduFEntry 7 } outletCfgPduFOverCurrCritical OBJECT-TYPE SYNTAX INTEGER UNITS "0.1A" ACCESS read-write STATUS mandatory DESCRIPTION "The Critical Threshold of current of PduF outlet." ::= { pduPwrMonitoringOutletCfgPduFEntry 8 } outletCfgPduFOverCurrWarning OBJECT-TYPE SYNTAX INTEGER UNITS "0.1A" ACCESS read-write STATUS mandatory DESCRIPTION "The Warning Threshold of current of PduF outlet." ::= { pduPwrMonitoringOutletCfgPduFEntry 9 } outletCfgPduFOverPwrCritical OBJECT-TYPE SYNTAX INTEGER UNITS "1W" ACCESS read-write STATUS mandatory DESCRIPTION "The Critical Threshold of power of PduF outlet." ::= { pduPwrMonitoringOutletCfgPduFEntry 10 } outletCfgPduFOverPwrWarning OBJECT-TYPE SYNTAX INTEGER UNITS "1W" ACCESS read-write STATUS mandatory DESCRIPTION "The Warning Threshold of power of PduF outlet." ::= { pduPwrMonitoringOutletCfgPduFEntry 11 } -- =========================================================================== -- -- pduPwrMonitoringOutletCtlTablePduF -- -- Outlet of Device6 Control Group. -- -- =========================================================================== pduPwrMonitoringOutletCtlTablePduF OBJECT-TYPE SYNTAX SEQUENCE OF PduPwrMonitoringOutletCtlPduFEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display control of PduF outlet." ::= { pduPwrMonitoringOutletPduF 4} pduPwrMonitoringOutletCtlPduFEntry OBJECT-TYPE SYNTAX PduPwrMonitoringOutletCtlPduFEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display control of PduF outlet." INDEX { outletCtlPduFIndex} ::= { pduPwrMonitoringOutletCtlTablePduF 1 } PduPwrMonitoringOutletCtlPduFEntry ::= SEQUENCE { outletCtlPduFIndex INTEGER, outletCtlPduFControl INTEGER } outletCtlPduFIndex OBJECT-TYPE SYNTAX INTEGER (0..41) ACCESS read-only STATUS mandatory DESCRIPTION "The index to outlet control of PduF." ::= { pduPwrMonitoringOutletCtlPduFEntry 1 } outletCtlPduFControl OBJECT-TYPE SYNTAX INTEGER { nothing(1), immediateOn(2), delayedOn(3), immediateOff(4), delayedOff(5), immediateCycle(6), delayedCycle(7) } ACCESS read-write STATUS mandatory DESCRIPTION "The control-type of PduF outlet." ::= { pduPwrMonitoringOutletCtlPduFEntry 2 } pduPwrMonitoringOutletPduG OBJECT IDENTIFIER ::= { pduPwrMonitoringOutlet 7 } -- =========================================================================== -- -- pduPwrMonitoringOutletPduG -- -- Outlet of Device7 management Group. -- -- =========================================================================== pduPwrMonitoringOutletNumPduG OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of PduG Outlet." ::= { pduPwrMonitoringOutletPduG 1} -- =========================================================================== -- -- pduPwrMonitoringOutletStatusTablePduG -- -- Outlet of Device7 Status Group. -- -- =========================================================================== pduPwrMonitoringOutletStatusTablePduG OBJECT-TYPE SYNTAX SEQUENCE OF PduPwrMonitoringOutletStatusPduGEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display status of PduG outlet." ::= { pduPwrMonitoringOutletPduG 2} pduPwrMonitoringOutletStatusPduGEntry OBJECT-TYPE SYNTAX PduPwrMonitoringOutletStatusPduGEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display status of PduG outlet." INDEX { outletPduGIndex} ::= { pduPwrMonitoringOutletStatusTablePduG 1 } PduPwrMonitoringOutletStatusPduGEntry ::= SEQUENCE { outletPduGIndex INTEGER, outletPduGState INTEGER, outletPduGCurrent INTEGER, outletPduGPwrFactor INTEGER, outletPduGPower INTEGER, outletPduGEnergy INTEGER, outletPduGResetFrom DisplayString, outletPduGStatus INTEGER, outletPduGAppPower INTEGER, outletPduGVoltage INTEGER } outletPduGIndex OBJECT-TYPE SYNTAX INTEGER (0..41) ACCESS read-only STATUS mandatory DESCRIPTION "The index to outlet status of PduG." ::= { pduPwrMonitoringOutletStatusPduGEntry 1 } outletPduGState OBJECT-TYPE SYNTAX INTEGER { off(1), on(2) } ACCESS read-only STATUS mandatory DESCRIPTION "The state of PduG outlet." ::= { pduPwrMonitoringOutletStatusPduGEntry 2 } outletPduGCurrent OBJECT-TYPE SYNTAX INTEGER UNITS "0.01A" ACCESS read-only STATUS mandatory DESCRIPTION "The current of PduG outlet." ::= { pduPwrMonitoringOutletStatusPduGEntry 3 } outletPduGPwrFactor OBJECT-TYPE SYNTAX INTEGER UNITS "0.1%" ACCESS read-only STATUS mandatory DESCRIPTION "The power factor of PduG outlet." ::= { pduPwrMonitoringOutletStatusPduGEntry 4 } outletPduGPower OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The active power of PduG outlet." ::= { pduPwrMonitoringOutletStatusPduGEntry 5 } outletPduGEnergy OBJECT-TYPE SYNTAX INTEGER UNITS "KWh" ACCESS read-only STATUS mandatory DESCRIPTION "The energy of PduG outlet." ::= { pduPwrMonitoringOutletStatusPduGEntry 6 } outletPduGResetFrom OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The reset date of PduG outlet." ::= { pduPwrMonitoringOutletStatusPduGEntry 7 } outletPduGStatus OBJECT-TYPE SYNTAX INTEGER { normal(1), warning(2), critical(3) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of PduG outlet." ::= { pduPwrMonitoringOutletStatusPduGEntry 8 } outletPduGAppPower OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The apparent power of PduG outlet." ::= { pduPwrMonitoringOutletStatusPduGEntry 9 } outletPduGVoltage OBJECT-TYPE SYNTAX INTEGER UNITS "0.1V" ACCESS read-only STATUS mandatory DESCRIPTION "The voltage of PduG outlet." ::= { pduPwrMonitoringOutletStatusPduGEntry 10 } -- =========================================================================== -- -- pduPwrMonitoringOutletCfgTablePduG -- -- Outlet of Device7 Configuration Group. -- -- =========================================================================== pduPwrMonitoringOutletCfgTablePduG OBJECT-TYPE SYNTAX SEQUENCE OF PduPwrMonitoringOutletCfgPduGEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display configuration of PduG outlet." ::= { pduPwrMonitoringOutletPduG 3} pduPwrMonitoringOutletCfgPduGEntry OBJECT-TYPE SYNTAX PduPwrMonitoringOutletCfgPduGEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display configuration of PduG outlet." INDEX { outletCfgPduGIndex} ::= { pduPwrMonitoringOutletCfgTablePduG 1 } PduPwrMonitoringOutletCfgPduGEntry ::= SEQUENCE { outletCfgPduGIndex INTEGER, outletCfgPduGName DisplayString, outletCfgPduGDelayOnStatus INTEGER, outletCfgPduGDelayOnTime INTEGER, outletCfgPduGDelayOffStatus INTEGER, outletCfgPduGDelayOffTime INTEGER, outletCfgPduGReboot INTEGER, outletCfgPduGOverCurrCritical INTEGER, outletCfgPduGOverCurrWarning INTEGER, outletCfgPduGOverPwrCritical INTEGER, outletCfgPduGOverPwrWarning INTEGER } outletCfgPduGIndex OBJECT-TYPE SYNTAX INTEGER (0..41) ACCESS read-only STATUS mandatory DESCRIPTION "The index to outlet configuration of PduG." ::= { pduPwrMonitoringOutletCfgPduGEntry 1 } outletCfgPduGName OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The name for outlet of PduG." ::= { pduPwrMonitoringOutletCfgPduGEntry 2 } outletCfgPduGDelayOnStatus OBJECT-TYPE SYNTAX INTEGER { nodelay(1), delay(2) } ACCESS read-write STATUS mandatory DESCRIPTION "The Delay On status of PduG outlet." ::= { pduPwrMonitoringOutletCfgPduGEntry 3 } outletCfgPduGDelayOnTime OBJECT-TYPE SYNTAX INTEGER UNITS "seconds" ACCESS read-write STATUS mandatory DESCRIPTION "The Delay On time of PduG outlet." ::= { pduPwrMonitoringOutletCfgPduGEntry 4 } outletCfgPduGDelayOffStatus OBJECT-TYPE SYNTAX INTEGER { nodelay(1), delay(2) } ACCESS read-write STATUS mandatory DESCRIPTION "The Delay Off status of PduG outlet." ::= { pduPwrMonitoringOutletCfgPduGEntry 5 } outletCfgPduGDelayOffTime OBJECT-TYPE SYNTAX INTEGER UNITS "seconds" ACCESS read-write STATUS mandatory DESCRIPTION "The Delay Off time of PduG outlet." ::= { pduPwrMonitoringOutletCfgPduGEntry 6 } outletCfgPduGReboot OBJECT-TYPE SYNTAX INTEGER UNITS "seconds" ACCESS read-write STATUS mandatory DESCRIPTION "The Delay On reboot duration of PduG outlet." ::= { pduPwrMonitoringOutletCfgPduGEntry 7 } outletCfgPduGOverCurrCritical OBJECT-TYPE SYNTAX INTEGER UNITS "0.1A" ACCESS read-write STATUS mandatory DESCRIPTION "The Critical Threshold of current of PduG outlet." ::= { pduPwrMonitoringOutletCfgPduGEntry 8 } outletCfgPduGOverCurrWarning OBJECT-TYPE SYNTAX INTEGER UNITS "0.1A" ACCESS read-write STATUS mandatory DESCRIPTION "The Warning Threshold of current of PduG outlet." ::= { pduPwrMonitoringOutletCfgPduGEntry 9 } outletCfgPduGOverPwrCritical OBJECT-TYPE SYNTAX INTEGER UNITS "1W" ACCESS read-write STATUS mandatory DESCRIPTION "The Critical Threshold of power of PduG outlet." ::= { pduPwrMonitoringOutletCfgPduGEntry 10 } outletCfgPduGOverPwrWarning OBJECT-TYPE SYNTAX INTEGER UNITS "1W" ACCESS read-write STATUS mandatory DESCRIPTION "The Warning Threshold of power of PduG outlet." ::= { pduPwrMonitoringOutletCfgPduGEntry 11 } -- =========================================================================== -- -- pduPwrMonitoringOutletCtlTablePduG -- -- Outlet of Device7 Control Group. -- -- =========================================================================== pduPwrMonitoringOutletCtlTablePduG OBJECT-TYPE SYNTAX SEQUENCE OF PduPwrMonitoringOutletCtlPduGEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display control of PduG outlet." ::= { pduPwrMonitoringOutletPduG 4} pduPwrMonitoringOutletCtlPduGEntry OBJECT-TYPE SYNTAX PduPwrMonitoringOutletCtlPduGEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display control of PduG outlet." INDEX { outletCtlPduGIndex} ::= { pduPwrMonitoringOutletCtlTablePduG 1 } PduPwrMonitoringOutletCtlPduGEntry ::= SEQUENCE { outletCtlPduGIndex INTEGER, outletCtlPduGControl INTEGER } outletCtlPduGIndex OBJECT-TYPE SYNTAX INTEGER (0..41) ACCESS read-only STATUS mandatory DESCRIPTION "The index to outlet control of PduG." ::= { pduPwrMonitoringOutletCtlPduGEntry 1 } outletCtlPduGControl OBJECT-TYPE SYNTAX INTEGER { nothing(1), immediateOn(2), delayedOn(3), immediateOff(4), delayedOff(5), immediateCycle(6), delayedCycle(7) } ACCESS read-write STATUS mandatory DESCRIPTION "The control-type of PduG outlet." ::= { pduPwrMonitoringOutletCtlPduGEntry 2 } pduPwrMonitoringOutletPduH OBJECT IDENTIFIER ::= { pduPwrMonitoringOutlet 8 } -- =========================================================================== -- -- pduPwrMonitoringOutletPduH -- -- Outlet of Device8 management Group. -- -- =========================================================================== pduPwrMonitoringOutletNumPduH OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of PduH Outlet." ::= { pduPwrMonitoringOutletPduH 1} -- =========================================================================== -- -- pduPwrMonitoringOutletStatusTablePduH -- -- Outlet of Device8 Status Group. -- -- =========================================================================== pduPwrMonitoringOutletStatusTablePduH OBJECT-TYPE SYNTAX SEQUENCE OF PduPwrMonitoringOutletStatusPduHEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display status of PduH outlet." ::= { pduPwrMonitoringOutletPduH 2} pduPwrMonitoringOutletStatusPduHEntry OBJECT-TYPE SYNTAX PduPwrMonitoringOutletStatusPduHEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display status of PduH outlet." INDEX { outletPduHIndex} ::= { pduPwrMonitoringOutletStatusTablePduH 1 } PduPwrMonitoringOutletStatusPduHEntry ::= SEQUENCE { outletPduHIndex INTEGER, outletPduHState INTEGER, outletPduHCurrent INTEGER, outletPduHPwrFactor INTEGER, outletPduHPower INTEGER, outletPduHEnergy INTEGER, outletPduHResetFrom DisplayString, outletPduHStatus INTEGER, outletPduHAppPower INTEGER, outletPduHVoltage INTEGER } outletPduHIndex OBJECT-TYPE SYNTAX INTEGER (0..41) ACCESS read-only STATUS mandatory DESCRIPTION "The index to outlet status of PduH." ::= { pduPwrMonitoringOutletStatusPduHEntry 1 } outletPduHState OBJECT-TYPE SYNTAX INTEGER { off(1), on(2) } ACCESS read-only STATUS mandatory DESCRIPTION "The state of PduH outlet." ::= { pduPwrMonitoringOutletStatusPduHEntry 2 } outletPduHCurrent OBJECT-TYPE SYNTAX INTEGER UNITS "0.01A" ACCESS read-only STATUS mandatory DESCRIPTION "The current of PduH outlet." ::= { pduPwrMonitoringOutletStatusPduHEntry 3 } outletPduHPwrFactor OBJECT-TYPE SYNTAX INTEGER UNITS "0.1%" ACCESS read-only STATUS mandatory DESCRIPTION "The power factor of PduH outlet." ::= { pduPwrMonitoringOutletStatusPduHEntry 4 } outletPduHPower OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The active power of PduH outlet." ::= { pduPwrMonitoringOutletStatusPduHEntry 5 } outletPduHEnergy OBJECT-TYPE SYNTAX INTEGER UNITS "KWh" ACCESS read-only STATUS mandatory DESCRIPTION "The energy of PduH outlet." ::= { pduPwrMonitoringOutletStatusPduHEntry 6 } outletPduHResetFrom OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The reset date of PduH outlet." ::= { pduPwrMonitoringOutletStatusPduHEntry 7 } outletPduHStatus OBJECT-TYPE SYNTAX INTEGER { normal(1), warning(2), critical(3) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of PduH outlet." ::= { pduPwrMonitoringOutletStatusPduHEntry 8 } outletPduHAppPower OBJECT-TYPE SYNTAX INTEGER UNITS "0.1W" ACCESS read-only STATUS mandatory DESCRIPTION "The apparent power of PduH outlet." ::= { pduPwrMonitoringOutletStatusPduHEntry 9 } outletPduHVoltage OBJECT-TYPE SYNTAX INTEGER UNITS "0.1V" ACCESS read-only STATUS mandatory DESCRIPTION "The voltage of PduH outlet." ::= { pduPwrMonitoringOutletStatusPduHEntry 10 } -- =========================================================================== -- -- pduPwrMonitoringOutletCfgTablePduH -- -- Outlet of Device8 Configuration Group. -- -- =========================================================================== pduPwrMonitoringOutletCfgTablePduH OBJECT-TYPE SYNTAX SEQUENCE OF PduPwrMonitoringOutletCfgPduHEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display configuration of PduH outlet." ::= { pduPwrMonitoringOutletPduH 3} pduPwrMonitoringOutletCfgPduHEntry OBJECT-TYPE SYNTAX PduPwrMonitoringOutletCfgPduHEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display configuration of PduH outlet." INDEX { outletCfgPduHIndex} ::= { pduPwrMonitoringOutletCfgTablePduH 1 } PduPwrMonitoringOutletCfgPduHEntry ::= SEQUENCE { outletCfgPduHIndex INTEGER, outletCfgPduHName DisplayString, outletCfgPduHDelayOnStatus INTEGER, outletCfgPduHDelayOnTime INTEGER, outletCfgPduHDelayOffStatus INTEGER, outletCfgPduHDelayOffTime INTEGER, outletCfgPduHReboot INTEGER, outletCfgPduHOverCurrCritical INTEGER, outletCfgPduHOverCurrWarning INTEGER, outletCfgPduHOverPwrCritical INTEGER, outletCfgPduHOverPwrWarning INTEGER } outletCfgPduHIndex OBJECT-TYPE SYNTAX INTEGER (0..41) ACCESS read-only STATUS mandatory DESCRIPTION "The index to outlet configuration of PduH." ::= { pduPwrMonitoringOutletCfgPduHEntry 1 } outletCfgPduHName OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The name for outlet of PduH." ::= { pduPwrMonitoringOutletCfgPduHEntry 2 } outletCfgPduHDelayOnStatus OBJECT-TYPE SYNTAX INTEGER { nodelay(1), delay(2) } ACCESS read-write STATUS mandatory DESCRIPTION "The Delay On status of PduH outlet." ::= { pduPwrMonitoringOutletCfgPduHEntry 3 } outletCfgPduHDelayOnTime OBJECT-TYPE SYNTAX INTEGER UNITS "seconds" ACCESS read-write STATUS mandatory DESCRIPTION "The Delay On time of PduH outlet." ::= { pduPwrMonitoringOutletCfgPduHEntry 4 } outletCfgPduHDelayOffStatus OBJECT-TYPE SYNTAX INTEGER { nodelay(1), delay(2) } ACCESS read-write STATUS mandatory DESCRIPTION "The Delay Off status of PduH outlet." ::= { pduPwrMonitoringOutletCfgPduHEntry 5 } outletCfgPduHDelayOffTime OBJECT-TYPE SYNTAX INTEGER UNITS "seconds" ACCESS read-write STATUS mandatory DESCRIPTION "The Delay Off time of PduH outlet." ::= { pduPwrMonitoringOutletCfgPduHEntry 6 } outletCfgPduHReboot OBJECT-TYPE SYNTAX INTEGER UNITS "seconds" ACCESS read-write STATUS mandatory DESCRIPTION "The Delay On reboot duration of PduH outlet." ::= { pduPwrMonitoringOutletCfgPduHEntry 7 } outletCfgPduHOverCurrCritical OBJECT-TYPE SYNTAX INTEGER UNITS "0.1A" ACCESS read-write STATUS mandatory DESCRIPTION "The Critical Threshold of current of PduH outlet." ::= { pduPwrMonitoringOutletCfgPduHEntry 8 } outletCfgPduHOverCurrWarning OBJECT-TYPE SYNTAX INTEGER UNITS "0.1A" ACCESS read-write STATUS mandatory DESCRIPTION "The Warning Threshold of current of PduH outlet." ::= { pduPwrMonitoringOutletCfgPduHEntry 9 } outletCfgPduHOverPwrCritical OBJECT-TYPE SYNTAX INTEGER UNITS "1W" ACCESS read-write STATUS mandatory DESCRIPTION "The Critical Threshold of power of PduH outlet." ::= { pduPwrMonitoringOutletCfgPduHEntry 10 } outletCfgPduHOverPwrWarning OBJECT-TYPE SYNTAX INTEGER UNITS "1W" ACCESS read-write STATUS mandatory DESCRIPTION "The Warning Threshold of power of PduH outlet." ::= { pduPwrMonitoringOutletCfgPduHEntry 11 } -- =========================================================================== -- -- pduPwrMonitoringOutletCtlTablePduH -- -- Outlet of Device8 Control Group. -- -- =========================================================================== pduPwrMonitoringOutletCtlTablePduH OBJECT-TYPE SYNTAX SEQUENCE OF PduPwrMonitoringOutletCtlPduHEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display control of PduH outlet." ::= { pduPwrMonitoringOutletPduH 4} pduPwrMonitoringOutletCtlPduHEntry OBJECT-TYPE SYNTAX PduPwrMonitoringOutletCtlPduHEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display control of PduH outlet." INDEX { outletCtlPduHIndex} ::= { pduPwrMonitoringOutletCtlTablePduH 1 } PduPwrMonitoringOutletCtlPduHEntry ::= SEQUENCE { outletCtlPduHIndex INTEGER, outletCtlPduHControl INTEGER } outletCtlPduHIndex OBJECT-TYPE SYNTAX INTEGER (0..41) ACCESS read-only STATUS mandatory DESCRIPTION "The index to outlet control of PduH." ::= { pduPwrMonitoringOutletCtlPduHEntry 1 } outletCtlPduHControl OBJECT-TYPE SYNTAX INTEGER { nothing(1), immediateOn(2), delayedOn(3), immediateOff(4), delayedOff(5), immediateCycle(6), delayedCycle(7) } ACCESS read-write STATUS mandatory DESCRIPTION "The control-type of PduH outlet." ::= { pduPwrMonitoringOutletCtlPduHEntry 2 } -- =========================================================================== -- -- PduEnvMonitoringStatus -- -- Emd Status Group. -- -- =========================================================================== pduEmdStatusTable OBJECT-TYPE SYNTAX SEQUENCE OF PduEnvMonitoringStatus ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display status of EMD." ::= { pduEnvMonitoring 1 } pduEnvMonitoringStatus OBJECT-TYPE SYNTAX PduEnvMonitoringStatus ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display status of EMD." INDEX { pduEnvStatusIndex} ::= { pduEmdStatusTable 1 } PduEnvMonitoringStatus ::= SEQUENCE { pduEnvStatusIndex INTEGER, pduEnvMonitoringTemp INTEGER, pduEnvMonitoringHumi INTEGER, pduEnvMonitoringTempAlarm INTEGER, pduEnvMonitoringHumiAlarm INTEGER, pduEnvMonitoringAlarm1 INTEGER, pduEnvMonitoringAlarm2 INTEGER } pduEnvStatusIndex OBJECT-TYPE SYNTAX INTEGER (0..4) ACCESS read-only STATUS mandatory DESCRIPTION "The index to EMD status entry." ::= { pduEnvMonitoringStatus 1 } pduEnvMonitoringTemp OBJECT-TYPE SYNTAX INTEGER UNITS "degC" ACCESS read-only STATUS mandatory DESCRIPTION "The temperature of EMD." ::= { pduEnvMonitoringStatus 2 } pduEnvMonitoringHumi OBJECT-TYPE SYNTAX INTEGER UNITS "0.1%" ACCESS read-only STATUS mandatory DESCRIPTION "The humidity of EMD." ::= { pduEnvMonitoringStatus 3 } pduEnvMonitoringTempAlarm OBJECT-TYPE SYNTAX INTEGER { normal(1), warning(2), critical(3) } ACCESS read-only STATUS mandatory DESCRIPTION "The temperature status of EMD." ::= { pduEnvMonitoringStatus 4 } pduEnvMonitoringHumiAlarm OBJECT-TYPE SYNTAX INTEGER { normal(1), warning(2), critical(3) } ACCESS read-only STATUS mandatory DESCRIPTION "The humidity status of EMD." ::= { pduEnvMonitoringStatus 5 } pduEnvMonitoringAlarm1 OBJECT-TYPE SYNTAX INTEGER { disabled(1), inactive(2), active(3) } ACCESS read-only STATUS mandatory DESCRIPTION "The alarm-1 status of EMD." ::= { pduEnvMonitoringStatus 6 } pduEnvMonitoringAlarm2 OBJECT-TYPE SYNTAX INTEGER { disabled(1), inactive(2), active(3) } ACCESS read-only STATUS mandatory DESCRIPTION "The alarm-2 status of EMD." ::= { pduEnvMonitoringStatus 7 } -- =========================================================================== -- -- PduEnvMonitoringCfg -- -- Emd Configuration Group. -- -- =========================================================================== pduEmdCfgTable OBJECT-TYPE SYNTAX SEQUENCE OF PduEnvMonitoringCfg ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display configure of EMD." ::= { pduEnvMonitoring 2 } pduEnvMonitoringCfg OBJECT-TYPE SYNTAX PduEnvMonitoringCfg ACCESS not-accessible STATUS mandatory DESCRIPTION "A list to display configure of EMD." INDEX { pduEnvCfgIndex } ::= { pduEmdCfgTable 1 } PduEnvMonitoringCfg ::= SEQUENCE { pduEnvCfgIndex INTEGER, pduEnvMonitoringControl INTEGER, pduEnvMonitoringTempHighCritical INTEGER, pduEnvMonitoringTempHighWarning INTEGER, pduEnvMonitoringTempLowCritical INTEGER, pduEnvMonitoringTempLowWarning INTEGER, pduEnvMonitoringTempHystersis INTEGER, pduEnvMonitoringTempOffset INTEGER, pduEnvMonitoringHumiHighCritical INTEGER, pduEnvMonitoringHumiHighWarning INTEGER, pduEnvMonitoringHumiLowCritical INTEGER, pduEnvMonitoringHumiLowWarning INTEGER, pduEnvMonitoringHumiHystersis INTEGER, pduEnvMonitoringHumiOffset INTEGER, pduEnvMonitoringAlarm1Setup INTEGER, pduEnvMonitoringAlarm2Setup INTEGER } pduEnvCfgIndex OBJECT-TYPE SYNTAX INTEGER (0..3) ACCESS read-only STATUS mandatory DESCRIPTION "The index to EMD configure entry." ::= { pduEnvMonitoringCfg 1 } pduEnvMonitoringControl OBJECT-TYPE SYNTAX INTEGER { disabled(1), enabled(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Enable/disable the EMD alarm configuration." ::= { pduEnvMonitoringCfg 2 } pduEnvMonitoringTempHighCritical OBJECT-TYPE SYNTAX INTEGER UNITS "degC" ACCESS read-write STATUS mandatory DESCRIPTION "The High Critical Threshold of temperature of EMD." ::= { pduEnvMonitoringCfg 3 } pduEnvMonitoringTempHighWarning OBJECT-TYPE SYNTAX INTEGER UNITS "degC" ACCESS read-write STATUS mandatory DESCRIPTION "The High Warning Threshold of temperature of EMD." ::= { pduEnvMonitoringCfg 4 } pduEnvMonitoringTempLowCritical OBJECT-TYPE SYNTAX INTEGER UNITS "degC" ACCESS read-write STATUS mandatory DESCRIPTION "The Low Critical Threshold of temperature of EMD." ::= { pduEnvMonitoringCfg 5 } pduEnvMonitoringTempLowWarning OBJECT-TYPE SYNTAX INTEGER UNITS "degC" ACCESS read-write STATUS mandatory DESCRIPTION "The Low Warning Threshold of temperature of EMD." ::= { pduEnvMonitoringCfg 6 } pduEnvMonitoringTempHystersis OBJECT-TYPE SYNTAX INTEGER UNITS "degC" ACCESS read-write STATUS mandatory DESCRIPTION "The Hystersis of Temperature of EMD." ::= { pduEnvMonitoringCfg 7 } pduEnvMonitoringTempOffset OBJECT-TYPE SYNTAX INTEGER UNITS "degC" ACCESS read-write STATUS mandatory DESCRIPTION "The Offset of Temperature of EMD." ::= { pduEnvMonitoringCfg 8 } pduEnvMonitoringHumiHighCritical OBJECT-TYPE SYNTAX INTEGER UNITS "0.1%" ACCESS read-write STATUS mandatory DESCRIPTION "The High Crtitcal Threshold of humidity of EMD." ::= { pduEnvMonitoringCfg 9 } pduEnvMonitoringHumiHighWarning OBJECT-TYPE SYNTAX INTEGER UNITS "0.1%" ACCESS read-write STATUS mandatory DESCRIPTION "The High Warning Threshold of humidity of EMD." ::= { pduEnvMonitoringCfg 10 } pduEnvMonitoringHumiLowCritical OBJECT-TYPE SYNTAX INTEGER UNITS "0.1%" ACCESS read-write STATUS mandatory DESCRIPTION "The Low Crtitcal Threshold of humidity of EMD." ::= { pduEnvMonitoringCfg 11 } pduEnvMonitoringHumiLowWarning OBJECT-TYPE SYNTAX INTEGER UNITS "0.1%" ACCESS read-write STATUS mandatory DESCRIPTION "The Low Warning Threshold of humidity of EMD." ::= { pduEnvMonitoringCfg 12 } pduEnvMonitoringHumiHystersis OBJECT-TYPE SYNTAX INTEGER UNITS "0.1%" ACCESS read-write STATUS mandatory DESCRIPTION "The Hystersis of Humidity of EMD." ::= { pduEnvMonitoringCfg 13 } pduEnvMonitoringHumiOffset OBJECT-TYPE SYNTAX INTEGER UNITS "0.1%" ACCESS read-write STATUS mandatory DESCRIPTION "The Ofset of Humidity of EMD." ::= { pduEnvMonitoringCfg 14 } pduEnvMonitoringAlarm1Setup OBJECT-TYPE SYNTAX INTEGER { disabled(1), no(2), nc(3) } ACCESS read-write STATUS mandatory DESCRIPTION "The Alarm-1 setup of EMD." ::= { pduEnvMonitoringCfg 15 } pduEnvMonitoringAlarm2Setup OBJECT-TYPE SYNTAX INTEGER { disabled(1), no(2), nc(3) } ACCESS read-write STATUS mandatory DESCRIPTION "The Alarm-2 setup of EMD." ::= { pduEnvMonitoringCfg 16 } -- =========================================================================== -- pduTraps -- -- iPoManIII Trap group -- =========================================================================== -- This section defines the well-known notifications sent by -- agents. pduSystemColdBoot TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Cold boot." ::= 1 pduSystemWarmBoot TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Warm boot." ::= 2 pduSystemRestart TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: System restart." ::= 3 pduResetToDefault TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Parameters reset to default." ::= 4 pduFirmUpgrade TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Firmware upgrade." ::= 5 pduSystemLogClear TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: System log cleared." ::= 6 pduEventlogClear TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Event log cleared." ::= 7 pduInletHistoryClear TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Inlet history log cleared." ::= 8 pduOutletHistoryClear TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Outlet history log cleared." ::= 9 pduSystemTimeChangeUser TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Time changed by user." ::= 10 pduSystemTimeChangeNtp TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Time synced with NTP server." ::= 11 pduSystemTimeChangeRtc TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Time changed by RTC." ::= 12 pduMailTestPass TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Test mail pass." ::= 13 pduMailTestFail TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Test mail failed." ::= 14 pduMailSentPass TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Mail sent successfully." ::= 15 pduMailSentFail TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Mail sent failed." ::= 16 pduSystemCfgChange TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Parameter changed." ::= 17 pduSystemParamImport TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Import XML configuration." ::= 18 pduInletCommLost TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Inlet communication lost." ::= 19 pduInletCommRestore TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Inlet communication restore." ::= 20 pduOutletCommLost TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Outlet communication lost." ::= 21 pduOutletCommRestore TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Outlet communication restore" ::= 22 pduOutletOnUser TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Outlet turned on by user." ::= 23 pduOutletOnSchedule TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Outlet turned on by schedule." ::= 24 pduOutletOffUser TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Outlet turned off by user." ::= 25 pduOutletOffSchedule TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Outlet turned off by schedule." ::= 26 pduOutletRebootUser TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Outlet reboot by user." ::= 27 pduOutletRebootSchedule TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Outlet reboot by schedule." ::= 28 pduInletEnergyReset TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Inlet active energy reset." ::= 29 pduOutletEnergyReset TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Outlet energy reset." ::= 30 pduSetUser TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Assign outlet to user." ::= 31 pduDeletUser TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Delete user." ::= 32 pduUpgradeInletSuccess TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Inlet upgrade successfully." ::= 33 pduUpgradeInletFail TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Inlet upgrade fail." ::= 34 pduUpgradeOutletSuccess TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Outlet upgrade successfully." ::= 35 pduUpgradeOutletFail TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Outlet upgrade fail." ::= 36 pduEmdHistoryLogClear TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: EMD history log cleared." ::= 37 pduAccountResetDefault TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: The default accounts had been reset to default value." ::= 38 pduUpgradeExtEmdSuccess TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: External EMD board upgrade successfully." ::= 39 pduUpgradeExtEmdFail TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: External EMD board upgrade fail." ::= 40 pduGroupOutletChanged TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: The Administrator has changed the authority of Outlet Manager, the Grouping setting will be cleared synchronously." ::= 41 pduScheduleOutletChanged TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: The Administrator has changed the authority of Outlet Manager, the Schedule setting will be cleared synchronously." ::= 42 pduGroupChanged TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: The Outlet Manger has changed the setting of Outlet Grouping, the Schedule will be cleared synchronously." ::= 43 pduSnmpConflicts TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Inlet polling issues due to SNMP conflicts." ::= 44 pduInletEnergyResetPhase1 TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Inlet phase1 active energy reset." ::= 45 pduInletEnergyResetPhase2 TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Inlet phase2 active energy reset." ::= 46 pduInletEnergyResetPhase3 TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Inlet phase3 active energy reset." ::= 47 pduInletREnergyReset TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Inlet reactive energy reset." ::= 48 pduInletREnergyResetPhase1 TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Inlet phase1 reactive energy reset." ::= 49 pduInletREnergyResetPhase2 TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Inlet phase2 reactive energy reset." ::= 50 pduInletREnergyResetPhase3 TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Inlet phase3 reactive energy reset." ::= 51 pduEmdTempHighWarnToNormal TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Temperature had returned from high warning to normal." ::= 101 pduEmdTempHighWarn TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Warning: Temperature was higher than high warning set point." ::= 102 pduEmdTempLowWarnToNormal TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Temperature had returned from low warning to normal." ::= 103 pduEmdTempLowWarn TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Warning: Temperature was lower than low warning set point." ::= 104 pduEmdTempHighCritToWarn TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Temperature had returned from high critical to high warning." ::= 105 pduEmdTempHighCritical TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Critical: Temperature was higher than high critical set point." ::= 106 pduEmdTempLowCritToWarn TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Temperature had returned from low critical to low warning." ::= 107 pduEmdTempLowCritical TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Critical: Temperature was lower than low critical set point." ::= 108 pduEmdHumiHighWarnToNormal TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Humidity had returned from high warning to normal." ::= 109 pduEmdHumiHighWarn TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Warning: Humidity was higher than high warning set point." ::= 110 pduEmdHumiLowWarnToNormal TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Humidity had returned from low warning to normal." ::= 111 pduEmdHumiLowWarn TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Warning: Humidity was lower than low warning set point." ::= 112 pduEmdHumiHighCritToWarn TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Humidity had returned from high critical to high warning." ::= 113 pduEmdHumiHighCritical TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Critical: Humidity was higher than high critical set point." ::= 114 pduEmdHumiLowCritToWarn TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Humidity had returned from low critical to low warning." ::= 115 pduEmdHumiLowCritical TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Critical: Humidity was lower than low critical set point." ::= 116 pduEmdAlarm1NotActive TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Alarm-1 became inactive." ::= 117 pduEmdAlarm1Active TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Warning: Alarm-1 became active." ::= 118 pduEmdAlarm2NotActive TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Alarm-2 became inactive." ::= 119 pduEmdAlarm2Active TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Warning: Alarm-2 became active." ::= 120 pduRs485Online TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: RS485 Sensor was online." ::= 121 pduRs485Offline TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Warning: RS485 Sensor was offline." ::= 122 pduInletLoadCritToWarn TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Inlet load had returned from critical to warning." ::= 123 pduInletLoadCritical TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Critical: Inlet load was higher than critical set point." ::= 124 pduInletLoadWarnToNormal TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Inlet load had returned from warning to normal." ::= 125 pduInletLoadWarn TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Warning: Inlet load was higher than warning set point." ::= 126 pduInletCurrPhase1CritToWarn TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Inlet phase1 current had returned from critical to warning." ::= 127 pduInletCurrPhase1Critical TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Critical: Inlet phase1 current was higher than critical set point." ::= 128 pduInletCurrPhase1WarnToNormal TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Inlet phase1 current had returned from warning to normal." ::= 129 pduInletCurrPhase1Warn TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Warning: Inlet phase1 current was higher than warning set point." ::= 130 pduInletCurrPhase2CritToWarn TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Inlet phase2 current had returned from critical to warning." ::= 131 pduInletCurrPhase2Critical TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Critical: Inlet phase2 current was higher than critical set point." ::= 132 pduInletCurrPhase2WarnToNormal TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Inlet phase2 current had returned from warning to normal." ::= 133 pduInletCurrPhase2Warn TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Warning: Inlet phase2 current was higher than warning set point." ::= 134 pduInletCurrPhase3CritToWarn TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Inlet phase3 current had returned from critical to warning." ::= 135 pduInletCurrPhase3Critical TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Critical: Inlet phase3 current was higher than critical set point." ::= 136 pduInletCurrPhase3WarnToNormal TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Inlet phase3 current had returned from warning to normal." ::= 137 pduInletCurrPhase3Warn TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Warning: Inlet phase3 current had returned from critical to warning." ::= 138 pduInletVoltPhase1CritToWarn TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Inlet phase1 voltage had returned from critical to warning." ::= 139 pduInletVoltPhase1Critical TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Critical: Inlet phase1 voltage was higher than critical set point." ::= 140 pduInletVoltPhase1WarnToNormal TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Inlet phase1 voltage had returned from warning to normal." ::= 141 pduInletVoltPhase1Warn TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Warning: Inlet phase1 voltage was higher than warning set point." ::= 142 pduInletVoltPhase2CritToWarn TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Inlet phase2 voltage had returned from critical to warning." ::= 143 pduInletVoltPhase2Critical TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Critical: Inlet phase2 voltage was higher than critical set point." ::= 144 pduInletVoltPhase2WarnToNormal TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Inlet phase2 voltage had returned from warning to normal." ::= 145 pduInletVoltPhase2Warn TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Warning: Inlet phase2 voltage was higher than warning set point." ::= 146 pduInletVoltPhase3CritToWarn TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Inlet phase3 voltage had returned from critical to warning." ::= 147 pduInletVoltPhase3Critical TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Critical: Inlet phase3 voltage was higher than critical set point." ::= 148 pduInletVoltPhase3WarnToNormal TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Inlet phase3 voltage had returned from warning to normal." ::= 149 pduInletVoltPhase3Warn TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Warning: Inlet phase3 voltage was higher than warning set point." ::= 150 pduOutletCurrCritToWarn TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Outlet current had returned from critical to warning." ::= 151 pduOutletCurrCritical TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Critical: Outlet current was higher than critical set point." ::= 152 pduOutletCurrWarnToNormal TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Outlet current had returned from warning to normal." ::= 153 pduOutletCurrWarn TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Warning: Outlet current was higher than warning set point." ::= 154 pduOutletPwrCritTOWarn TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Outlet power had returned from critical to warning." ::= 155 pduOutletPwrCritical TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Critical: Outlet power was higher than critical set point." ::= 156 pduOutletPwrWarnToNormal TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Outlet power had returned from warning to normal." ::= 157 pduOutletPwrWarn TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Warning: Outlet power was higher than warning set point." ::= 158 pduAlarm1Disabled TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Alarm-1 became disabled." ::= 159 pduAlarm2Disabled TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Alarm-2 became disabled." ::= 160 pduIntetResidualCurrect1Occured TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Critical: Inlet Residual current occurred." ::= 161 pduIntetResidualCurrect1Remove TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Inlet Residual current removed." ::= 162 pduInletLoadBalanceCritToWarn TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Inlet load balance had returned from critical to warning." ::= 163 pduInletLoadBalanceCritical TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Critical: Inlet load balance was higher than critical set point." ::= 164 pduInletLoadBalanceWarnToNormal TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Informational: Inlet load balance had returned from warning to normal." ::= 165 pduInletLoadBalanceWarn TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Warning: Inlet load balance was higher than warning set point." ::= 166 pduInletAcFail TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Critical: INPUT AC fail." ::= 167 pduInletAcRestore TRAP-TYPE ENTERPRISE pduTraps DESCRIPTION "Warning: INPUT AC restore." ::= 168 END