ND020-MIB DEFINITIONS ::= BEGIN IMPORTS MODULE-IDENTITY, OBJECT-TYPE, Integer32, enterprises, Unsigned32 FROM SNMPv2-SMI; ndMeter MODULE-IDENTITY LAST-UPDATED "201104200000Z" ORGANIZATION "Northern Design (Electronics) Ltd." CONTACT-INFO " Northern Design (Electronics) Ltd. Postal: 228 Bolton Road. Bradford BD3 0QW UK Tel: +44 1274 729533 E-mail: support@ndmeter.co.uk" DESCRIPTION "The Structure of Management Information for Northern Design Energy Meters" REVISION "201104200000Z" DESCRIPTION "Initial version of this MIB module." ::= { enterprises 37778 } -- assigned by IANA meterkWhH OBJECT-TYPE SYNTAX Unsigned32 UNITS "kWh" MAX-ACCESS read-only STATUS current DESCRIPTION "kWh High." ::= { ndMeter 7680 } meterkWhL OBJECT-TYPE SYNTAX Unsigned32 UNITS "kWh" MAX-ACCESS read-only STATUS current DESCRIPTION "kWh Low." ::= { ndMeter 7681 } meterkVAhH OBJECT-TYPE SYNTAX Unsigned32 UNITS "kVAh" MAX-ACCESS read-only STATUS current DESCRIPTION "kVAh High." ::= { ndMeter 7682 } meterkVAhL OBJECT-TYPE SYNTAX Unsigned32 UNITS "kVAh" MAX-ACCESS read-only STATUS current DESCRIPTION "kVAh Low." ::= { ndMeter 7683 } meterkvarhH OBJECT-TYPE SYNTAX Unsigned32 UNITS "kvarh" MAX-ACCESS read-only STATUS current DESCRIPTION "kvarh High." ::= { ndMeter 7684 } meterkvarhL OBJECT-TYPE SYNTAX Unsigned32 UNITS "kvarh" MAX-ACCESS read-only STATUS current DESCRIPTION "kvarh Low." ::= { ndMeter 7685 } meterEkWhH OBJECT-TYPE SYNTAX Unsigned32 UNITS "kvarh" MAX-ACCESS read-only STATUS current DESCRIPTION "Export kWh High." ::= { ndMeter 7686 } meterEkWhL OBJECT-TYPE SYNTAX Unsigned32 UNITS "kvarh" MAX-ACCESS read-only STATUS current DESCRIPTION "Export kWh Low." ::= { ndMeter 7687 } meterP1Amps OBJECT-TYPE SYNTAX Unsigned32 UNITS "Amps" MAX-ACCESS read-only STATUS current DESCRIPTION "Phase 1 current scaled by Ki." ::= { ndMeter 7688 } meterP2Amps OBJECT-TYPE SYNTAX Unsigned32 UNITS "Amps" MAX-ACCESS read-only STATUS current DESCRIPTION "Phase 2 current scaled by Ki." ::= { ndMeter 7689 } meterP3Amps OBJECT-TYPE SYNTAX Unsigned32 UNITS "Amps" MAX-ACCESS read-only STATUS current DESCRIPTION "Phase 3 current scaled by Ki." ::= { ndMeter 7690 } meterP1Volts OBJECT-TYPE SYNTAX Unsigned32 UNITS "Voltsx10" MAX-ACCESS read-only STATUS current DESCRIPTION "Phase 1 voltage scaled by Kvp." ::= { ndMeter 7691 } meterP2Volts OBJECT-TYPE SYNTAX Unsigned32 UNITS "Voltsx10" MAX-ACCESS read-only STATUS current DESCRIPTION "Phase 2 voltage scaled by Kvp." ::= { ndMeter 7692 } meterP3Volts OBJECT-TYPE SYNTAX Unsigned32 UNITS "Voltsx10" MAX-ACCESS read-only STATUS current DESCRIPTION "Phase 3 voltage scaled by Kvp." ::= { ndMeter 7693 } meterP1P2Volts OBJECT-TYPE SYNTAX Unsigned32 UNITS "Voltsx10" MAX-ACCESS read-only STATUS current DESCRIPTION "Phase1 Phase2 voltage scaled by Kvl." ::= { ndMeter 7694 } meterP2P3Volts OBJECT-TYPE SYNTAX Unsigned32 UNITS "Voltsx10" MAX-ACCESS read-only STATUS current DESCRIPTION "Phase2 Phase3 voltage scaled by Kvl." ::= { ndMeter 7695 } meterP3P1Volts OBJECT-TYPE SYNTAX Unsigned32 UNITS "Voltsx10" MAX-ACCESS read-only STATUS current DESCRIPTION "Phase3 Phase1 voltage scaled by Kvl." ::= { ndMeter 7696 } meterFreq OBJECT-TYPE SYNTAX Unsigned32 UNITS "Hz x 10" MAX-ACCESS read-only STATUS current DESCRIPTION "Frequency x 10." ::= { ndMeter 7697 } meterPh1PF OBJECT-TYPE SYNTAX Integer32 UNITS "PF x 100" MAX-ACCESS read-only STATUS current DESCRIPTION "Phase1 PF x 100." ::= { ndMeter 7698 } meterPh2PF OBJECT-TYPE SYNTAX Integer32 UNITS "PF x 100" MAX-ACCESS read-only STATUS current DESCRIPTION "Phase2 PF x 100." ::= { ndMeter 7699 } meterPh3PF OBJECT-TYPE SYNTAX Integer32 UNITS "PF x 100" MAX-ACCESS read-only STATUS current DESCRIPTION "Phase3 PF x 100." ::= { ndMeter 7700 } meterSysPh1PF OBJECT-TYPE SYNTAX Integer32 UNITS "PF x 100" MAX-ACCESS read-only STATUS current DESCRIPTION "System PF x 100." ::= { ndMeter 7701 } meterP1kW OBJECT-TYPE SYNTAX Integer32 UNITS "kW" MAX-ACCESS read-only STATUS current DESCRIPTION "Phase 1 kW scaled by Kp." ::= { ndMeter 7702 } meterP2kW OBJECT-TYPE SYNTAX Integer32 UNITS "kW" MAX-ACCESS read-only STATUS current DESCRIPTION "Phase 2 kW scaled by Kp." ::= { ndMeter 7703 } meterP3kW OBJECT-TYPE SYNTAX Integer32 UNITS "kW" MAX-ACCESS read-only STATUS current DESCRIPTION "Phase 3 kW scaled by Kp." ::= { ndMeter 7704 } meterSyskW OBJECT-TYPE SYNTAX Integer32 UNITS "kW" MAX-ACCESS read-only STATUS current DESCRIPTION "System kW scaled by Kp." ::= { ndMeter 7705 } meterP1kVA OBJECT-TYPE SYNTAX Unsigned32 UNITS "kVA" MAX-ACCESS read-only STATUS current DESCRIPTION "Phase 1 kVA scaled by Kp." ::= { ndMeter 7706 } meterP2kVA OBJECT-TYPE SYNTAX Unsigned32 UNITS "kVA" MAX-ACCESS read-only STATUS current DESCRIPTION "Phase 2 kVA scaled by Kp." ::= { ndMeter 7707 } meterP3kVA OBJECT-TYPE SYNTAX Unsigned32 UNITS "kVA" MAX-ACCESS read-only STATUS current DESCRIPTION "Phase 3 kVA scaled by Kp." ::= { ndMeter 7708 } meterSyskVA OBJECT-TYPE SYNTAX Unsigned32 UNITS "kVA" MAX-ACCESS read-only STATUS current DESCRIPTION "System kVA scaled by Kp." ::= { ndMeter 7709 } meterP1kvar OBJECT-TYPE SYNTAX Integer32 UNITS "kvar" MAX-ACCESS read-only STATUS current DESCRIPTION "Phase 1 kvar scaled by Kp." ::= { ndMeter 7710 } meterP2kvar OBJECT-TYPE SYNTAX Integer32 UNITS "kvar" MAX-ACCESS read-only STATUS current DESCRIPTION "Phase 2 kvar scaled by Kp." ::= { ndMeter 7711 } meterP3kvar OBJECT-TYPE SYNTAX Integer32 UNITS "kvar" MAX-ACCESS read-only STATUS current DESCRIPTION "Phase 3 kvar scaled by Kp." ::= { ndMeter 7712 } meterSyskvar OBJECT-TYPE SYNTAX Integer32 UNITS "kvar" MAX-ACCESS read-only STATUS current DESCRIPTION "System kvar scaled by Kp." ::= { ndMeter 7713 } meterP1AmpsDem OBJECT-TYPE SYNTAX Unsigned32 UNITS "Amps" MAX-ACCESS read-only STATUS current DESCRIPTION "Phase 1 current demand scaled by Ki." ::= { ndMeter 7714 } meterP2AmpsDem OBJECT-TYPE SYNTAX Unsigned32 UNITS "Amps" MAX-ACCESS read-only STATUS current DESCRIPTION "Phase 2 current demand scaled by Ki." ::= { ndMeter 7715 } meterP3AmpsDem OBJECT-TYPE SYNTAX Unsigned32 UNITS "Amps" MAX-ACCESS read-only STATUS current DESCRIPTION "Phase 3 current demand scaled by Ki." ::= { ndMeter 7716 } meterP1VoltsDem OBJECT-TYPE SYNTAX Unsigned32 UNITS "Voltsx10" MAX-ACCESS read-only STATUS current DESCRIPTION "Phase 1 voltage demand scaled by Kvp." ::= { ndMeter 7717 } meterP2VoltsDem OBJECT-TYPE SYNTAX Unsigned32 UNITS "Voltsx10" MAX-ACCESS read-only STATUS current DESCRIPTION "Phase 2 voltage demand scaled by Kvp." ::= { ndMeter 7718 } meterP3VoltsDem OBJECT-TYPE SYNTAX Unsigned32 UNITS "Voltsx10" MAX-ACCESS read-only STATUS current DESCRIPTION "Phase 3 voltage demand scaled by Kvp." ::= { ndMeter 7719 } meterPkP1Amps OBJECT-TYPE SYNTAX Unsigned32 UNITS "Amps" MAX-ACCESS read-only STATUS current DESCRIPTION "Peak Phase 1 current scaled by Ki." ::= { ndMeter 7720 } meterPkP2Amps OBJECT-TYPE SYNTAX Unsigned32 UNITS "Amps" MAX-ACCESS read-only STATUS current DESCRIPTION "Peak Phase 2 current scaled by Ki." ::= { ndMeter 7721 } meterPkP3Amps OBJECT-TYPE SYNTAX Unsigned32 UNITS "Amps" MAX-ACCESS read-only STATUS current DESCRIPTION "Peak Phase 3 current scaled by Ki." ::= { ndMeter 7722 } meterPkP1Volts OBJECT-TYPE SYNTAX Unsigned32 UNITS "Voltsx10" MAX-ACCESS read-only STATUS current DESCRIPTION "Peak Phase 1 voltage scaled by Kvp." ::= { ndMeter 7723 } meterPkP2Volts OBJECT-TYPE SYNTAX Unsigned32 UNITS "Voltsx10" MAX-ACCESS read-only STATUS current DESCRIPTION "Peak Phase 2 voltage scaled by Kvp." ::= { ndMeter 7724 } meterPkP3Volts OBJECT-TYPE SYNTAX Unsigned32 UNITS "Voltsx10" MAX-ACCESS read-only STATUS current DESCRIPTION "Peak Phase 3 voltage scaled by Kvp." ::= { ndMeter 7725 } meterkWDem OBJECT-TYPE SYNTAX Integer32 UNITS "kW" MAX-ACCESS read-only STATUS current DESCRIPTION "kW Demand scaled with Kp." ::= { ndMeter 7726 } meterkVADem OBJECT-TYPE SYNTAX Unsigned32 UNITS "kVA" MAX-ACCESS read-only STATUS current DESCRIPTION "kVA Demand scaled with Kp." ::= { ndMeter 7727 } meterkvarDem OBJECT-TYPE SYNTAX Integer32 UNITS "kvar" MAX-ACCESS read-only STATUS current DESCRIPTION "kvar Demand scaled with Kp." ::= { ndMeter 7728 } meterPkkWDem OBJECT-TYPE SYNTAX Integer32 UNITS "kW" MAX-ACCESS read-only STATUS current DESCRIPTION "Peak kW Demand scaled with Kp." ::= { ndMeter 7729 } meterPkkVADem OBJECT-TYPE SYNTAX Unsigned32 UNITS "kVA" MAX-ACCESS read-only STATUS current DESCRIPTION "Peak kVA Demand scaled with Kp." ::= { ndMeter 7730 } meterPkkvarDem OBJECT-TYPE SYNTAX Integer32 UNITS "kvar" MAX-ACCESS read-only STATUS current DESCRIPTION "Peak kvar Demand scaled with Kp." ::= { ndMeter 7731 } meterNeuAmps OBJECT-TYPE SYNTAX Unsigned32 UNITS "Amps" MAX-ACCESS read-only STATUS current DESCRIPTION "Neutral current x 10." ::= { ndMeter 7732 } meterAmpsScal OBJECT-TYPE SYNTAX Unsigned32 UNITS "Ki" MAX-ACCESS read-only STATUS current DESCRIPTION "Amps scale." ::= { ndMeter 7733 } meterPhVoltScal OBJECT-TYPE SYNTAX Unsigned32 UNITS "Kvp" MAX-ACCESS read-only STATUS current DESCRIPTION "Phase Volts scale." ::= { ndMeter 7734 } meterLLVoltScal OBJECT-TYPE SYNTAX Unsigned32 UNITS "Kvl" MAX-ACCESS read-only STATUS current DESCRIPTION "Line Volts scale." ::= { ndMeter 7735 } meterPowerScal OBJECT-TYPE SYNTAX Unsigned32 UNITS "Kp" MAX-ACCESS read-only STATUS current DESCRIPTION "Power scale." ::= { ndMeter 7736 } meterEnergyScal OBJECT-TYPE SYNTAX Unsigned32 UNITS "Ke" MAX-ACCESS read-only STATUS current DESCRIPTION "Energy scale." ::= { ndMeter 7737 } END