-- IPT PDU SNMP configuration MIB -- -- (c) 2013-2015 IPT Limited -- -- Written by Designer Systems Ltd -- V1.03.00 -- PEN 38218 supplied under license by Designer Systems Ltd PDUSNMP DEFINITIONS ::= BEGIN IMPORTS enterprises, IpAddress, Gauge, TimeTicks FROM RFC1155-SMI DisplayString FROM RFC1213-MIB OBJECT-TYPE FROM RFC-1212 TRAP-TYPE FROM RFC-1215 NOTIFICATION-TYPE FROM SNMPv2-SMI MODULE-IDENTITY FROM SNMPv2-SMI Integer32, Unsigned32 FROM SNMPv2-SMI OBJECT-GROUP FROM SNMPv2-CONF NOTIFICATION-GROUP FROM SNMPv2-CONF MODULE-COMPLIANCE FROM SNMPv2-CONF DateAndTime FROM SNMPv2-TC TEXTUAL-CONVENTION FROM SNMPv2-TC; pdu-SNMP MODULE-IDENTITY LAST-UPDATED "201511271712Z" ORGANIZATION "IPT Limited" CONTACT-INFO "sales@iptltd.com" DESCRIPTION "IPT SNMP PDU MIB definition" -- V1.03.00 REVISION "201511271712Z" DESCRIPTION "Forth release (MIB validation changes to support Open MNS)" -- V1.02.00 REVISION "201511201712Z" DESCRIPTION "Third release (Added socket All ON and all OFF support)" -- V1.01.00 REVISION "201509021712Z" DESCRIPTION "Second release (Added trap clears and renamed existing traps to set type)" -- V1.00.00 REVISION "201309201712Z" DESCRIPTION "First release" ::= { ipt-pdu-SNMP 1 } ipt-pdu-SNMP OBJECT IDENTIFIER ::= { enterprises 38218 } slave-SiteTotals OBJECT IDENTIFIER ::= { pdu-SNMP 1 } slave-Server OBJECT IDENTIFIER ::= { pdu-SNMP 2 } pdu-Configuration OBJECT IDENTIFIER ::= { pdu-SNMP 3 } trap-Destinations OBJECT IDENTIFIER ::= { pdu-SNMP 4 } pdu-Information OBJECT IDENTIFIER ::= { pdu-SNMP 5 } pdu-Meters OBJECT IDENTIFIER ::= { pdu-SNMP 6 } pdu-sockets OBJECT IDENTIFIER ::= { pdu-SNMP 7 } pdu-Environmental OBJECT IDENTIFIER ::= { pdu-SNMP 8 } pdu-Security OBJECT IDENTIFIER ::= { pdu-SNMP 9 } pdu-Logs OBJECT IDENTIFIER ::= { pdu-SNMP 10 } pdu-Traps OBJECT IDENTIFIER ::= { pdu-SNMP 11 } pdu-TrapThresholds OBJECT IDENTIFIER ::= { pdu-Traps 1 } slave-pdus OBJECT IDENTIFIER ::= { ipt-pdu-SNMP 2 } slave-Information OBJECT IDENTIFIER ::= { slave-pdus 2 } slave-Status OBJECT IDENTIFIER ::= { slave-pdus 3 } slave-sockets OBJECT IDENTIFIER ::= { slave-pdus 4 } slave-Environmental OBJECT IDENTIFIER ::= { slave-pdus 5 } slave-Security OBJECT IDENTIFIER ::= { slave-pdus 6 } slave-Traps OBJECT IDENTIFIER ::= { slave-pdus 7 } slave-TrapSetNotifications OBJECT IDENTIFIER ::= { slave-Traps 1 } slave-TrapClearNotifications OBJECT IDENTIFIER ::= { slave-Traps 2 } slave-Global OBJECT IDENTIFIER ::= { ipt-pdu-SNMP 3 } -- pdu-SNMP.slave-SiteTotals slave-SiteTotalkWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Total Energy used by all slaves on site in kWh x10." ::= { slave-SiteTotals 1 } slave-SiteTotalBtu OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Total Energy used by all slaves on site in Btu x10." ::= { slave-SiteTotals 2 } slave-SiteTotalKgCO2 OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Total Energy used by all slaves on site in KgCO2 x10." ::= { slave-SiteTotals 3 } -- pdu-SNMP.slave-Server slave-Nopdus OBJECT-TYPE SYNTAX INTEGER (0..32) MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Number of pdu's connected in SLAVE mode" ::= { slave-Server 1 } slaves-Online OBJECT-TYPE SYNTAX INTEGER (0..32) MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Number of pdu's ONLINE in SLAVE mode." ::= { slave-Server 2 } slave-ServerStatus OBJECT-TYPE SYNTAX INTEGER {stopped(0),running(1),searching(2),getinfo(3),listening(4)} MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Server status" ::= { slave-Server 3 } -- pdu-SNMP.pdu-Configuration pdu-ClientName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Compatible - pdu Client name." ::= { pdu-Configuration 1 } pdu-LocationName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Compatible - pdu Location Name." ::= { pdu-Configuration 2 } pdu-FirmwareVersion OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - pdu firmware version." ::= { pdu-Configuration 3 } pdu-KgCO2Conversion OBJECT-TYPE SYNTAX INTEGER (1..1000) MAX-ACCESS read-write STATUS current DESCRIPTION "Compatible - KgCO2 conversion factor x1000 [544 = 0.544]" ::= { pdu-Configuration 4 } pdu-MODBUSTimeout OBJECT-TYPE SYNTAX INTEGER (500..5000) MAX-ACCESS read-write STATUS current DESCRIPTION "Compatible - MODBUS Timeout in mS." ::= { pdu-Configuration 5 } pdu-MODBUSRetry OBJECT-TYPE SYNTAX INTEGER (1..10) MAX-ACCESS read-write STATUS current DESCRIPTION "Compatible - MODBUS Retry value." ::= { pdu-Configuration 6 } pdu-NotUsed1 OBJECT-TYPE SYNTAX INTEGER (0) MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Not used." ::= { pdu-Configuration 7 } pdu-AlarmPeriod OBJECT-TYPE SYNTAX INTEGER (1..240) MAX-ACCESS read-write STATUS current DESCRIPTION "Compatible - Alarm period check in minutes." ::= { pdu-Configuration 8 } pdu-DHCPStatus OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Compatible - DHCP Enable.Set to 1 to ENABLE or 0 to DISABLE DHCP support." ::= { pdu-Configuration 9 } pdu-IPAddress OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Compatible - pdu IP Address." ::= { pdu-Configuration 10 } pdu-SubNetMask OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Compatible - pdu Sub-net mask." ::= { pdu-Configuration 11 } pdu-CabinetID OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "pdu Cabinet ID." ::= { pdu-Configuration 12 } pdu-socketPeriod OBJECT-TYPE SYNTAX INTEGER (0..5000) MAX-ACCESS read-write STATUS current DESCRIPTION "pdu socket ON sequence period (mS) 0=OFF." ::= { pdu-Configuration 13 } pdu-LockPeriod OBJECT-TYPE SYNTAX INTEGER (1..240) MAX-ACCESS read-write STATUS current DESCRIPTION "pdu Lock activation period (S)." ::= { pdu-Configuration 14 } pdu-RTC-Hour OBJECT-TYPE SYNTAX INTEGER (0..23) MAX-ACCESS read-write STATUS current DESCRIPTION "pdu RTC Hour [24 hour clock]." ::= { pdu-Configuration 15 } pdu-RTC-Minute OBJECT-TYPE SYNTAX INTEGER (1..59) MAX-ACCESS read-write STATUS current DESCRIPTION "pdu RTC Minute." ::= { pdu-Configuration 16 } pdu-RTC-Date OBJECT-TYPE SYNTAX INTEGER (1..31) MAX-ACCESS read-write STATUS current DESCRIPTION "pdu RTC Date." ::= { pdu-Configuration 17 } pdu-RTC-Month OBJECT-TYPE SYNTAX INTEGER (1..12) MAX-ACCESS read-write STATUS current DESCRIPTION "pdu RTC Month." ::= { pdu-Configuration 18 } pdu-RTC-Year OBJECT-TYPE SYNTAX INTEGER (0..99) MAX-ACCESS read-write STATUS current DESCRIPTION "pdu RTC Year [tens only]." ::= { pdu-Configuration 19 } -- pdu-SNMP.trap-Destinations trapDestinationsTable OBJECT-TYPE SYNTAX SEQUENCE OF TrapDestinationsEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "" ::= { trap-Destinations 1 } trapDestinationsEntry OBJECT-TYPE SYNTAX TrapDestinationsEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of Trap notification destinations." INDEX { trapDestinationsIndex } ::= { trapDestinationsTable 1 } TrapDestinationsEntry ::= SEQUENCE { trapDestinationsIndex INTEGER, trapDestinationsStatus INTEGER, trapDestinationsIP IpAddress, trapDestinationsCommunity DisplayString } trapDestinationsIndex OBJECT-TYPE SYNTAX INTEGER (0..1) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Trap destination index [0..1]." ::= { trapDestinationsEntry 1 } trapDestinationsStatus OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Trap destination status. Set to 1 to ENABLE or 0 to DISABLE trap destination." ::= { trapDestinationsEntry 2 } trapDestinationsIP OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Trap destination IP address. Set to the IP address of the destination SNMP manager." ::= { trapDestinationsEntry 3 } trapDestinationsCommunity OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Trap destination SNMP community. Set to the community name to be used with the destination SNMP manager." ::= { trapDestinationsEntry 4 } -- pdu-SNMP.pdu-Information pdu-Firmware OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "pdu Firmware version." ::= { pdu-Information 1 } pdu-Nosockets OBJECT-TYPE SYNTAX INTEGER (0..32) MAX-ACCESS read-only STATUS current DESCRIPTION "pdu Number of sockets." ::= { pdu-Information 2 } pdu-ProductName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "pdu Product name." ::= { pdu-Information 3 } pdu-SerialNumber OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "pdu Serial number." ::= { pdu-Information 4 } -- pdu-SNMP.pdu-Meters pdu-meter1-VRMS OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "pdu Meter 1 RMS Voltage (VAC) x10." ::= { pdu-Meters 1 } pdu-meter1-IRMS OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "pdu Meter 1 RMS Current (A) x100." ::= { pdu-Meters 2 } pdu-meter1-KWH OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "pdu Meter 1 total energy consumption (kW/h) x10." ::= { pdu-Meters 3 } pdu-meter1-KW OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "pdu Meter 1 Kilowatts (kW) x1000." ::= { pdu-Meters 4 } pdu-meter1-TPMU OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "pdu Meter 1 Internal Temperature (C) x10." ::= { pdu-Meters 5 } pdu-meter1-IPK OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "pdu Meter 1 Peak Current (A) x10." ::= { pdu-Meters 6 } pdu-meter1-VPK OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "pdu Meter 1 Peak Voltage (V) x10." ::= { pdu-Meters 7 } pdu-meter1-PF OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "pdu Meter 1 Power Factor x1000" ::= { pdu-Meters 8 } pdu-meter1-Freq OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "pdu Meter 1 Frequency x10" ::= { pdu-Meters 9 } pdu-meter2-VRMS OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "pdu Meter 2 RMS Voltage (VAC) x10." ::= { pdu-Meters 10 } pdu-meter2-IRMS OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "pdu Meter 2 RMS Current (A) x100." ::= { pdu-Meters 11 } pdu-meter2-KWH OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "pdu Meter 2 total energy consumption (kW/h) x10." ::= { pdu-Meters 12 } pdu-meter2-KW OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "pdu Meter 2 Kilowatts (kW) x1000." ::= { pdu-Meters 13 } pdu-meter2-TPMU OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "pdu Meter 2 Internal Temperature (C) x10." ::= { pdu-Meters 14 } pdu-meter2-IPK OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "pdu Meter 2 Peak Current (A) x10." ::= { pdu-Meters 15 } pdu-meter2-VPK OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "pdu Meter 2 Peak Voltage (V) x10." ::= { pdu-Meters 16 } pdu-meter2-PF OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "pdu Meter 2 Power Factor x1000" ::= { pdu-Meters 17 } pdu-meter2-Freq OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "pdu Meter 2 Frequency x10" ::= { pdu-Meters 18 } pdu-meter3-VRMS OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "pdu Meter 3 RMS Voltage (VAC) x100." ::= { pdu-Meters 19 } pdu-meter3-IRMS OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "pdu Meter 3 RMS Current (A) x10." ::= { pdu-Meters 20 } pdu-meter3-KWH OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "pdu Meter 3 total energy consumption (kW/h) x10." ::= { pdu-Meters 21 } pdu-meter3-KW OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "pdu Meter 3 Kilowatts (kW) x1000." ::= { pdu-Meters 22 } pdu-meter3-TPMU OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "pdu Meter 3 Internal Temperature (C) x10." ::= { pdu-Meters 23 } pdu-meter3-IPK OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "pdu Meter 3 Peak Current (A) x10." ::= { pdu-Meters 24 } pdu-meter3-VPK OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "pdu Meter 3 Peak Voltage (V) x10." ::= { pdu-Meters 25 } pdu-meter3-PF OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "pdu Meter 3 Power Factor x1000" ::= { pdu-Meters 26 } pdu-meter3-Freq OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "pdu Meter 3 Frequency x10" ::= { pdu-Meters 27 } -- pdu-SNMP.pdu-sockets pdu-socketsTable OBJECT-TYPE SYNTAX SEQUENCE OF Pdu-socketsEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "" ::= { pdu-sockets 1 } pdu-socketsEntry OBJECT-TYPE SYNTAX Pdu-socketsEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of socket status parameters." INDEX { socket-Index } ::= { pdu-socketsTable 1 } Pdu-socketsEntry ::= SEQUENCE { socket-Index INTEGER, socket-Number INTEGER, socket-Equipment DisplayString, socket-ONOFF INTEGER, socket-AMPS INTEGER, socket-KWH Integer32, socket-INFO INTEGER } socket-Index OBJECT-TYPE SYNTAX INTEGER (0..47) MAX-ACCESS not-accessible STATUS current DESCRIPTION "socket index" ::= { pdu-socketsEntry 1 } socket-Number OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "socket number [Range 1 to 48]" ::= { pdu-socketsEntry 2 } socket-Equipment OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "socket equipment name." ::= { pdu-socketsEntry 3 } socket-ONOFF OBJECT-TYPE SYNTAX INTEGER {off(0),on(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "socket ON/OFF status [Set to 1 to switch ON, 0 to switch OFF]" ::= { pdu-socketsEntry 4 } socket-AMPS OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "socket current (Amps) x10." ::= { pdu-socketsEntry 5 } socket-KWH OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "socket Energy (kWh) x10." ::= { pdu-socketsEntry 6 } socket-INFO OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "socket information (status, phase and picture)." ::= { pdu-socketsEntry 7 } -- pdu-SNMP.pdu-Environmental pdu-environmental-Temp1 OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Environmental Temperature probe 1 (C) x100." ::= { pdu-Environmental 1 } pdu-environmental-Temp1-Location OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental Temperature probe 1 location name." ::= { pdu-Environmental 2 } pdu-environmental-Temp2 OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Environmental Temperature probe 2 (C) x100." ::= { pdu-Environmental 3 } pdu-environmental-Temp2-Location OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental Temperature probe 2 location name." ::= { pdu-Environmental 4 } pdu-environmental-Temp3 OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Environmental Temperature probe 3 (C) x100." ::= { pdu-Environmental 5 } pdu-environmental-Temp3-Location OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental Temperature probe 3 location name." ::= { pdu-Environmental 6 } pdu-environmental-Temp4 OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Environmental Temperature probe 4 (C) x100." ::= { pdu-Environmental 7 } pdu-environmental-Temp4-Location OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental Temperature probe 4 location name." ::= { pdu-Environmental 8 } pdu-environmental-Temp5 OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Environmental Temperature probe 5 (C) x100." ::= { pdu-Environmental 9 } pdu-environmental-Temp5-Location OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental Temperature probe 5 location name." ::= { pdu-Environmental 10 } pdu-environmental-Temp6 OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Environmental Temperature probe 6 (C) x100." ::= { pdu-Environmental 11 } pdu-environmental-Temp6-Location OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental Temperature probe 6 location name." ::= { pdu-Environmental 12 } pdu-environmental-Temp7 OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Environmental Temperature probe 7 (C) x100." ::= { pdu-Environmental 13 } pdu-environmental-Temp7-Location OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental Temperature probe 7 location name." ::= { pdu-Environmental 14 } pdu-environmental-Temp8 OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Environmental Temperature probe 8 (C) x100." ::= { pdu-Environmental 15 } pdu-environmental-Temp8-Location OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental Temperature probe 8 location name." ::= { pdu-Environmental 16 } pdu-environmental-HumidityTemp OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Environmental Humidity probe Temperature (C) x100." ::= { pdu-Environmental 17 } pdu-environmental-Humidity OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Environmental humidity probe (%) x100." ::= { pdu-Environmental 18 } pdu-environmental-Contact1 OBJECT-TYPE SYNTAX INTEGER {open(0),closed(1)} MAX-ACCESS read-only STATUS current DESCRIPTION "Environmental contact input 1 status." ::= { pdu-Environmental 19 } pdu-environmental-Contact1-Location OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental contact input 1 location name." ::= { pdu-Environmental 20 } pdu-environmental-Contact2 OBJECT-TYPE SYNTAX INTEGER {open(0),closed(1)} MAX-ACCESS read-only STATUS current DESCRIPTION "Environmental contact input 2 status." ::= { pdu-Environmental 21 } pdu-environmental-Contact2-Location OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental contact input 2 location name." ::= { pdu-Environmental 22 } pdu-environmental-Contact3 OBJECT-TYPE SYNTAX INTEGER {open(0),closed(1)} MAX-ACCESS read-only STATUS current DESCRIPTION "Environmental contact input 3 status." ::= { pdu-Environmental 23 } pdu-environmental-Contact3-Location OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental contact input 3 location name." ::= { pdu-Environmental 24 } -- pdu-SNMP.pdu-Security pdu-Security-Door OBJECT-TYPE SYNTAX INTEGER {open(0),closed(1)} MAX-ACCESS read-only STATUS current DESCRIPTION "Security door contact status." ::= { pdu-Security 1 } pdu-Security-Lock OBJECT-TYPE SYNTAX INTEGER {locked(0),unlocked(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Security lock status [Set to 1 to unlock]" ::= { pdu-Security 2 } pdu-Security-Wild OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Security Card/PIN Wildcard status. Set with 1 to enable or 0 to disable Wildcard feature." ::= { pdu-Security 3 } pdu-Security-UnlockTimeDate OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Time and data of last unlock." ::= { pdu-Security 4 } pdu-SecurityTable OBJECT-TYPE SYNTAX SEQUENCE OF Pdu-SecurityEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "" ::= { pdu-Security 5 } pdu-SecurityEntry OBJECT-TYPE SYNTAX Pdu-SecurityEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of pdu- Card/PIN codes." INDEX { pdu-Security-Index } ::= { pdu-SecurityTable 1 } Pdu-SecurityEntry ::= SEQUENCE { pdu-Security-Index INTEGER, pdu-Security-Code Integer32 } pdu-Security-Index OBJECT-TYPE SYNTAX INTEGER (1..32) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Security Card/PIN code index." ::= { pdu-SecurityEntry 1 } pdu-Security-Code OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Security Card/PIN number." ::= { pdu-SecurityEntry 2 } -- pdu-SNMP.pdu-Logs pdu-Logs-Number OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Log file number of log lines stored." ::= { pdu-Logs 1 } pdu-Logs-Index OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Log file line index pointer. Set to line to be read." ::= { pdu-Logs 2 } pdu-Logs-Data OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Log file log line data." ::= { pdu-Logs 3 } pdu-Logs-Clear OBJECT-TYPE SYNTAX INTEGER {reset(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Log file clear. Set with 1 to clear log file." ::= { pdu-Logs 4 } -- pdu-SNMP.pdu-Traps.pdu-TrapThresholds meter1-VRMSLowAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 1 Voltage LOW alarm disabled/enabled." ::= { pdu-TrapThresholds 1 } meter1-VRMSLow OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "eter 1 Voltage LOW trap threshold x10." ::= { pdu-TrapThresholds 2 } meter1-VRMSHighAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 1 Voltage HIGH alarm disabled/enabled." ::= { pdu-TrapThresholds 3 } meter1-VRMSHigh OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 1 Voltage HIGH trap threshold x10." ::= { pdu-TrapThresholds 4 } meter1-IRMSLowAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 1 Current LOW alarm disabled/enabled." ::= { pdu-TrapThresholds 5 } meter1-IRMSLow OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 1 Current LOW trap threshold x10." ::= { pdu-TrapThresholds 6 } meter1-IRMSHighAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 1 Current HIGH alarm disabled/enabled." ::= { pdu-TrapThresholds 7 } meter1-IRMSHigh OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 1 Current HIGH trap threshold x10." ::= { pdu-TrapThresholds 8 } meter1-KWSLowAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 1 Kilowatts LOW alarm disabled/enabled." ::= { pdu-TrapThresholds 9 } meter1-KWSLow OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 1 Kilowatts LOW trap threshold x10." ::= { pdu-TrapThresholds 10 } meter1-KWSHighAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 1 Kilowatts HIGH alarm disabled/enabled." ::= { pdu-TrapThresholds 11 } meter1-KWSHigh OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 1 Kilowatts HIGH trap threshold x10." ::= { pdu-TrapThresholds 12 } meter1-TempLowAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 1 Internal temperature LOW alarm disabled/enabled." ::= { pdu-TrapThresholds 13 } meter1-TempLow OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 1 Internal temperature LOW trap threshold x10." ::= { pdu-TrapThresholds 14 } meter1-TempHighAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 1 Internal temperature HIGH alarm disabled/enabled." ::= { pdu-TrapThresholds 15 } meter1-TempHigh OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 1 Internal temperature HIGH trap threshold x10." ::= { pdu-TrapThresholds 16 } meter1-PFLowAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 1 Power factor LOW alarm disabled/enabled." ::= { pdu-TrapThresholds 17 } meter1-PFLow OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 1 Power factor LOW trap threshold x10." ::= { pdu-TrapThresholds 18 } meter1-PFHighAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 1 Power factor HIGH alarm disabled/enabled." ::= { pdu-TrapThresholds 19 } meter1-PFHigh OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 1 Power factor HIGH trap threshold x10." ::= { pdu-TrapThresholds 20 } meter1-FreqLowAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 1 Frequency LOW alarm disabled/enabled." ::= { pdu-TrapThresholds 21 } meter1-FreqLow OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 1 Frequency LOW trap threshold x10." ::= { pdu-TrapThresholds 22 } meter1-FreqHighAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 1 Frequency HIGH alarm disabled/enabled." ::= { pdu-TrapThresholds 23 } meter1-FreqHigh OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 1 Frequency HIGH trap threshold x10." ::= { pdu-TrapThresholds 24 } meter2-VRMSLowAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 2 Voltage LOW alarm disabled/enabled." ::= { pdu-TrapThresholds 25 } meter2-VRMSLow OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "eter 1 Voltage LOW trap threshold x10." ::= { pdu-TrapThresholds 26 } meter2-VRMSHighAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 2 Voltage HIGH alarm disabled/enabled." ::= { pdu-TrapThresholds 27 } meter2-VRMSHigh OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 2 Voltage HIGH trap threshold x10." ::= { pdu-TrapThresholds 28 } meter2-IRMSLowAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 2 Current LOW alarm disabled/enabled." ::= { pdu-TrapThresholds 29 } meter2-IRMSLow OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 2 Current LOW trap threshold x10." ::= { pdu-TrapThresholds 30 } meter2-IRMSHighAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 2 Current HIGH alarm disabled/enabled." ::= { pdu-TrapThresholds 31 } meter2-IRMSHigh OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 2 Current HIGH trap threshold x10." ::= { pdu-TrapThresholds 32 } meter2-KWSLowAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 2 Kilowatts LOW alarm disabled/enabled." ::= { pdu-TrapThresholds 33 } meter2-KWSLow OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 2 Kilowatts LOW trap threshold x10." ::= { pdu-TrapThresholds 34 } meter2-KWSHighAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 2 Kilowatts HIGH alarm disabled/enabled." ::= { pdu-TrapThresholds 35 } meter2-KWSHigh OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 2 Kilowatts HIGH trap threshold x10." ::= { pdu-TrapThresholds 36 } meter2-TempLowAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 2 Internal temperature LOW alarm disabled/enabled." ::= { pdu-TrapThresholds 37 } meter2-TempLow OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 2 Internal temperature LOW trap threshold x10." ::= { pdu-TrapThresholds 38 } meter2-TempHighAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 2 Internal temperature HIGH alarm disabled/enabled." ::= { pdu-TrapThresholds 39 } meter2-TempHigh OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 2 Internal temperature HIGH trap threshold x10." ::= { pdu-TrapThresholds 40 } meter2-PFLowAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 2 Power factor LOW alarm disabled/enabled." ::= { pdu-TrapThresholds 41 } meter2-PFLow OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 2 Power factor LOW trap threshold x10." ::= { pdu-TrapThresholds 42 } meter2-PFHighAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 2 Power factor HIGH alarm disabled/enabled." ::= { pdu-TrapThresholds 43 } meter2-PFHigh OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 2 Power factor HIGH trap threshold x10." ::= { pdu-TrapThresholds 44 } meter2-FreqLowAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 2 Frequency LOW alarm disabled/enabled." ::= { pdu-TrapThresholds 45 } meter2-FreqLow OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 2 Frequency LOW trap threshold x10." ::= { pdu-TrapThresholds 46 } meter2-FreqHighAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 2 Frequency HIGH alarm disabled/enabled." ::= { pdu-TrapThresholds 47 } meter2-FreqHigh OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 2 Frequency HIGH trap threshold x10." ::= { pdu-TrapThresholds 48 } meter3-VRMSLowAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 3 Voltage LOW alarm disabled/enabled." ::= { pdu-TrapThresholds 49 } meter3-VRMSLow OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "eter 1 Voltage LOW trap threshold x10." ::= { pdu-TrapThresholds 50 } meter3-VRMSHighAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 3 Voltage HIGH alarm disabled/enabled." ::= { pdu-TrapThresholds 51 } meter3-VRMSHigh OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 3 Voltage HIGH trap threshold x10." ::= { pdu-TrapThresholds 52 } meter3-IRMSLowAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 3 Current LOW alarm disabled/enabled." ::= { pdu-TrapThresholds 53 } meter3-IRMSLow OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 3 Current LOW trap threshold x10." ::= { pdu-TrapThresholds 54 } meter3-IRMSHighAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 3 Current HIGH alarm disabled/enabled." ::= { pdu-TrapThresholds 55 } meter3-IRMSHigh OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 3 Current HIGH trap threshold x10." ::= { pdu-TrapThresholds 56 } meter3-KWSLowAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 3 Kilowatts LOW alarm disabled/enabled." ::= { pdu-TrapThresholds 57 } meter3-KWSLow OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 3 Kilowatts LOW trap threshold x10." ::= { pdu-TrapThresholds 58 } meter3-KWSHighAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 3 Kilowatts HIGH alarm disabled/enabled." ::= { pdu-TrapThresholds 59 } meter3-KWSHigh OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 3 Kilowatts HIGH trap threshold x10." ::= { pdu-TrapThresholds 60 } meter3-TempLowAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 3 Internal temperature LOW alarm disabled/enabled." ::= { pdu-TrapThresholds 61 } meter3-TempLow OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 3 Internal temperature LOW trap threshold x10." ::= { pdu-TrapThresholds 62 } meter3-TempHighAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 3 Internal temperature HIGH alarm disabled/enabled." ::= { pdu-TrapThresholds 63 } meter3-TempHigh OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 3 Internal temperature HIGH trap threshold x10." ::= { pdu-TrapThresholds 64 } meter3-PFLowAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 3 Power factor LOW alarm disabled/enabled." ::= { pdu-TrapThresholds 65 } meter3-PFLow OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 3 Power factor LOW trap threshold x10." ::= { pdu-TrapThresholds 66 } meter3-PFHighAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 3 Power factor HIGH alarm disabled/enabled." ::= { pdu-TrapThresholds 67 } meter3-PFHigh OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 3 Power factor HIGH trap threshold x10." ::= { pdu-TrapThresholds 68 } meter3-FreqLowAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 3 Frequency LOW alarm disabled/enabled." ::= { pdu-TrapThresholds 69 } meter3-FreqLow OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 3 Frequency LOW trap threshold x10." ::= { pdu-TrapThresholds 70 } meter3-FreqHighAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 3 Frequency HIGH alarm disabled/enabled." ::= { pdu-TrapThresholds 71 } meter3-FreqHigh OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Meter 3 Frequency HIGH trap threshold x10." ::= { pdu-TrapThresholds 72 } socket-ThresholdsTable OBJECT-TYPE SYNTAX SEQUENCE OF Socket-ThresholdsEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "" ::= { pdu-TrapThresholds 73 } socket-ThresholdsEntry OBJECT-TYPE SYNTAX Socket-ThresholdsEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of socket trap notification thresholds." INDEX { socket-ThresholdsNumber } ::= { socket-ThresholdsTable 1 } Socket-ThresholdsEntry ::= SEQUENCE { socket-ThresholdsNumber INTEGER, socket-AMPSLowAlarm INTEGER, socket-AMPSLow INTEGER, socket-AMPSHighAlarm INTEGER, socket-AMPSHigh INTEGER } socket-ThresholdsNumber OBJECT-TYPE SYNTAX INTEGER (1..48) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Trap threshold socket- number [1..48]." ::= { socket-ThresholdsEntry 1 } socket-AMPSLowAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "socket Current LOW alarm disabled/enabled." ::= { socket-ThresholdsEntry 2 } socket-AMPSLow OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "socket Current LOW trap threshold x10." ::= { socket-ThresholdsEntry 3 } socket-AMPSHighAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "socket Current HIGH alarm disabled/enabled." ::= { socket-ThresholdsEntry 4 } socket-AMPSHigh OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "socket Current HIGH trap threshold x10." ::= { socket-ThresholdsEntry 5 } environmental-Temp1LowAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental temperature probe 1 LOW alarm disabled/enabled." ::= { pdu-TrapThresholds 74 } environmental-Temp1Low OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental temperature probe 1 LOW trap threshold x10." ::= { pdu-TrapThresholds 75 } environmental-Temp1HighAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental temperature probe 1 HIGH alarm disabled/enabled." ::= { pdu-TrapThresholds 76 } environmental-Temp1High OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental temperature probe 1 HIGH trap threshold x10." ::= { pdu-TrapThresholds 77 } environmental-Temp2LowAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental temperature probe 2 LOW alarm disabled/enabled." ::= { pdu-TrapThresholds 78 } environmental-Temp2Low OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental temperature probe 2 LOW trap threshold x10." ::= { pdu-TrapThresholds 79 } environmental-Temp2HighAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental temperature probe 2 HIGH alarm disabled/enabled." ::= { pdu-TrapThresholds 80 } environmental-Temp2High OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental temperature probe 2 HIGH trap threshold x10." ::= { pdu-TrapThresholds 81 } environmental-Temp3LowAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental temperature probe 3 LOW alarm disabled/enabled." ::= { pdu-TrapThresholds 82 } environmental-Temp3Low OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental temperature probe 3 LOW trap threshold x10." ::= { pdu-TrapThresholds 83 } environmental-Temp3HighAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental temperature probe 3 HIGH alarm disabled/enabled." ::= { pdu-TrapThresholds 84 } environmental-Temp3High OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental temperature probe 3 HIGH trap threshold x10." ::= { pdu-TrapThresholds 85 } environmental-Temp4LowAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental temperature probe 4 LOW alarm disabled/enabled." ::= { pdu-TrapThresholds 86 } environmental-Temp4Low OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental temperature probe 4 LOW trap threshold x10." ::= { pdu-TrapThresholds 87 } environmental-Temp4HighAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental temperature probe 4 HIGH alarm disabled/enabled." ::= { pdu-TrapThresholds 88 } environmental-Temp4High OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental temperature probe 4 HIGH trap threshold x10." ::= { pdu-TrapThresholds 89 } environmental-Temp5LowAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental temperature probe 5 LOW alarm disabled/enabled." ::= { pdu-TrapThresholds 90 } environmental-Temp5Low OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental temperature probe 5 LOW trap threshold x10." ::= { pdu-TrapThresholds 91 } environmental-Temp5HighAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental temperature probe 5 HIGH alarm disabled/enabled." ::= { pdu-TrapThresholds 92 } environmental-Temp5High OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental temperature probe 5 HIGH trap threshold x10." ::= { pdu-TrapThresholds 93 } environmental-Temp6LowAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental temperature probe 6 LOW alarm disabled/enabled." ::= { pdu-TrapThresholds 94 } environmental-Temp6Low OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental temperature probe 6 LOW trap threshold x10." ::= { pdu-TrapThresholds 95 } environmental-Temp6HighAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental temperature probe 6 HIGH alarm disabled/enabled." ::= { pdu-TrapThresholds 96 } environmental-Temp6High OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental temperature probe 6 HIGH trap threshold x10." ::= { pdu-TrapThresholds 97 } environmental-Temp7LowAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental temperature probe 7 LOW alarm disabled/enabled." ::= { pdu-TrapThresholds 98 } environmental-Temp7Low OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental temperature probe 7 LOW trap threshold x10." ::= { pdu-TrapThresholds 99 } environmental-Temp7HighAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental temperature probe 7 HIGH alarm disabled/enabled." ::= { pdu-TrapThresholds 100 } environmental-Temp7High OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental temperature probe 7 HIGH trap threshold x10." ::= { pdu-TrapThresholds 101 } environmental-Temp8LowAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental temperature probe 8 LOW alarm disabled/enabled." ::= { pdu-TrapThresholds 102 } environmental-Temp8Low OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental temperature probe 8 LOW trap threshold x10." ::= { pdu-TrapThresholds 103 } environmental-Temp8HighAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental temperature probe 8 HIGH alarm disabled/enabled." ::= { pdu-TrapThresholds 104 } environmental-Temp8High OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental temperature probe 8 HIGH trap threshold x10." ::= { pdu-TrapThresholds 105 } environmental-HumidityTempLowAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental humidity probe temperature LOW alarm disabled/enabled." ::= { pdu-TrapThresholds 106 } environmental-HumidityTempLow OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental humidity probe temperature LOW trap threshold x10." ::= { pdu-TrapThresholds 107 } environmental-HumidityTempHighAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental humidity probe temperature HIGH alarm disabled/enabled." ::= { pdu-TrapThresholds 108 } environmental-HumidityTempHigh OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental humidity probe temperature HIGH trap threshold x10." ::= { pdu-TrapThresholds 109 } environmental-HumidityLowAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental humidity probe LOW alarm disabled/enabled." ::= { pdu-TrapThresholds 110 } environmental-HumidityLow OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental humidity probe LOW trap threshold x10." ::= { pdu-TrapThresholds 111 } environmental-HumidityHighAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental humidity probe HIGH alarm disabled/enabled." ::= { pdu-TrapThresholds 112 } environmental-HumidityHigh OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental humidity probe HIGH trap threshold x10." ::= { pdu-TrapThresholds 113 } environmental-Contact1OpenedAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental Contact 1 OPENED alarm disabled/enabled." ::= { pdu-TrapThresholds 114 } environmental-Contact1ClosedAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental Contact 1 CLOSED alarm disabled/enabled." ::= { pdu-TrapThresholds 115 } environmental-Contact2OpenedAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental Contact 2 OPENED alarm disabled/enabled." ::= { pdu-TrapThresholds 116 } environmental-Contact2ClosedAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental Contact 2 CLOSED alarm disabled/enabled." ::= { pdu-TrapThresholds 117 } environmental-Contact3OpenedAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental Contact 3 OPENED alarm disabled/enabled." ::= { pdu-TrapThresholds 118 } environmental-Contact3ClosedAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Environmental Contact 3 CLOSED alarm disabled/enabled." ::= { pdu-TrapThresholds 119 } security-DoorOpenedAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Security Door OPENED alarm disabled/enabled." ::= { pdu-TrapThresholds 120 } security-DoorClosedAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Security Door CLOSED alarm disabled/enabled." ::= { pdu-TrapThresholds 121 } security-LockUnlockedAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Security Lock UNLOCKED alarm disabled/enabled." ::= { pdu-TrapThresholds 122 } security-LockLockedAlarm OBJECT-TYPE SYNTAX INTEGER {disabled(0),enabled(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Security Lock LOCKED alarm disabled/enabled." ::= { pdu-TrapThresholds 123 } -- slave-pdu slave-slaveSelected OBJECT-TYPE SYNTAX INTEGER (1..32) MAX-ACCESS read-write STATUS current DESCRIPTION "Compatible - Currently selected slave pdu. Set to number between 1 and slave-Nopdus" ::= { slave-pdus 1 } -- pdu.pduInfo slave-pduName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - slave pdu Name." ::= { slave-Information 1 } slave-pduStatus OBJECT-TYPE SYNTAX INTEGER {offline(0),online(1),disabled(2)} MAX-ACCESS read-write STATUS current DESCRIPTION "Compatible - slave pdu ONLINE / OFFLINE or DISABLED status." ::= { slave-Information 2 } slave-pduAddress OBJECT-TYPE SYNTAX INTEGER (1..32) MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - slave pdu MODBUS Address." ::= { slave-Information 3 } slave-pduFirmware OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - slave pdu Firmware version." ::= { slave-Information 4 } slave-Info-NotUsed2 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Not used." ::= { slave-Information 5 } slave-pduNosockets OBJECT-TYPE SYNTAX INTEGER (0..48) MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - slave pdu Number of sockets." ::= { slave-Information 6 } slave-Info-NotUsed3 OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Not used." ::= { slave-Information 7 } slave-Info-NotUsed4 OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Not used." ::= { slave-Information 8 } slave-Info-pduReset OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Compatible - slave pdu Reset." ::= { slave-Information 9 } slave-Info-pdukWhReset OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Compatible - slave pdu Reset energy." ::= { slave-Information 10 } -- pdu.slave-Status slave-meter1-VRMS OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Compatible - slave Meter 1 RMS Voltage (VAC) x10." ::= { slave-Status 1 } slave-meter1-IRMS OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - slave Meter 1 RMS Current (A) x10." ::= { slave-Status 2 } slave-meter1-KWH OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - slave Meter 1 total energy consumption (kW/h) x10." ::= { slave-Status 3 } slave-meter1-KW OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - slave Meter 1 Kilowatts (kW) x1000." ::= { slave-Status 4 } slave-meter1-TPMU OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - slave Meter 1 Internal Temperature (C) x10." ::= { slave-Status 5 } slave-Status-NotUsed1 OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Not used." ::= { slave-Status 6 } slave-Status-NotUsed2 OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Not used." ::= { slave-Status 7 } slave-meter1-IPK OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - slave Meter 1 Peak Current (A) x10." ::= { slave-Status 8 } slave-meter1-VPK OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - slave Meter 1 Peak Voltage (V) x10." ::= { slave-Status 9 } slave-meter1-PF OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - slave Meter 1 Power Factor x1000" ::= { slave-Status 10 } slave-Status-NotUsed3 OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Not used." ::= { slave-Status 11 } slave-Status-NotUsed4 OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Not used." ::= { slave-Status 12 } slave-Status-NotUsed5 OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Not used." ::= { slave-Status 13 } slave-meter1-Freq OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - slave Meter 1 Frequency x10" ::= { slave-Status 14 } slave-meter2-VRMS OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - slave Meter 2 RMS Voltage (VAC) x10." ::= { slave-Status 15 } slave-meter2-IRMS OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - slave Meter 2 RMS Current (A) x10." ::= { slave-Status 16 } slave-meter2-KWH OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - slave Meter 2 total energy consumption (kW/h) x10." ::= { slave-Status 17 } slave-meter2-KW OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - slave Meter 2 Kilowatts (kW) x1000." ::= { slave-Status 18 } slave-meter2-TPMU OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - slave Meter 2 Internal Temperature (C) x10." ::= { slave-Status 19 } slave-meter2-IPK OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - slave Meter 2 Peak Current (A) x10." ::= { slave-Status 20 } slave-meter2-VPK OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - slave Meter 2 Peak Voltage (V) x10." ::= { slave-Status 21 } slave-meter2-PF OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - slave Meter 2 Power Factor x1000" ::= { slave-Status 22 } slave-meter2-Freq OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - slave Meter 2 Frequency x10" ::= { slave-Status 23 } slave-meter3-VRMS OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - slave Meter 3 RMS Voltage (VAC) x10." ::= { slave-Status 24 } slave-meter3-IRMS OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - slave Meter 3 RMS Current (A) x10." ::= { slave-Status 25 } slave-meter3-KWH OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - slave Meter 3 total energy consumption (kW/h) x10." ::= { slave-Status 26 } slave-meter3-KW OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - slave Meter 3 Kilowatts (kW) x1000." ::= { slave-Status 27 } slave-meter3-TPMU OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - slave Meter 3 Internal Temperature (C) x10." ::= { slave-Status 28 } slave-meter3-IPK OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - slave Meter 3 Peak Current (A) x10." ::= { slave-Status 29 } slave-meter3-VPK OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - slave Meter 3 Peak Voltage (V) x10." ::= { slave-Status 30 } slave-meter3-PF OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - slave Meter 3 Power Factor x1000" ::= { slave-Status 31 } slave-meter3-Freq OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - slave Meter 3 Frequency x10" ::= { slave-Status 32 } -- pdu.slave-sockets slave-socketsTable OBJECT-TYPE SYNTAX SEQUENCE OF Slave-socketsEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "" ::= { slave-sockets 1 } slave-socketsEntry OBJECT-TYPE SYNTAX Slave-socketsEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of socket status parameters." INDEX { slave-socket-Index } ::= { slave-socketsTable 1 } Slave-socketsEntry ::= SEQUENCE { slave-socket-Index INTEGER, slave-socket-Number INTEGER, slave-socket-NotUsed1 DisplayString, slave-socket-ONOFF INTEGER, slave-socket-AMPS INTEGER, slave-socket-KWH Integer32 } slave-socket-Index OBJECT-TYPE SYNTAX INTEGER (1..48) MAX-ACCESS not-accessible STATUS current DESCRIPTION "socket index" ::= { slave-socketsEntry 1 } slave-socket-Number OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS not-accessible STATUS current DESCRIPTION "socket number [Range 1 to 48]" ::= { slave-socketsEntry 2 } slave-socket-NotUsed1 OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Not used." ::= { slave-socketsEntry 3 } slave-socket-ONOFF OBJECT-TYPE SYNTAX INTEGER {off(0),on(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "socket ON/OFF status [Compatible - Write ignored]" ::= { slave-socketsEntry 4 } slave-socket-AMPS OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "socket current (Amps) x10." ::= { slave-socketsEntry 5 } slave-socket-KWH OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "socket Energy (kWh) x10." ::= { slave-socketsEntry 6 } socket-Selected OBJECT-TYPE SYNTAX INTEGER (1..48) MAX-ACCESS read-write STATUS current DESCRIPTION "Compatible - Currently selected socket. Set to number between 1 and slave-pduNosockets" ::= { slave-sockets 2 } socket-AllON OBJECT-TYPE SYNTAX INTEGER (1) MAX-ACCESS read-write STATUS current DESCRIPTION "Set all sockets in system to ON." ::= { slave-sockets 3 } socket-AllOFF OBJECT-TYPE SYNTAX INTEGER (1) MAX-ACCESS read-write STATUS current DESCRIPTION "Set all sockets in system to OFF." ::= { slave-sockets 4 } -- pdu.slave-Environmental slave-environmental-Temp1 OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Environmental Temperature probe 1 (C) x100." ::= { slave-Environmental 1 } slave-environmental-Temp2 OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Environmental Temperature probe 2 (C) x100." ::= { slave-Environmental 2 } slave-environmental-Temp3 OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Environmental Temperature probe 3 (C) x100." ::= { slave-Environmental 3 } slave-environmental-Temp4 OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Environmental Temperature probe 4 (C) x100." ::= { slave-Environmental 4 } slave-environmental-Temp5 OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Environmental Temperature probe 5 (C) x100." ::= { slave-Environmental 5 } slave-environmental-Temp6 OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Environmental Temperature probe 6 (C) x100." ::= { slave-Environmental 6 } slave-environmental-Temp7 OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Environmental Temperature probe 7 (C) x100." ::= { slave-Environmental 7 } slave-environmental-Temp8 OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Environmental Temperature probe 8 (C) x100." ::= { slave-Environmental 8 } slave-environmental-HumidityTemp OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Environmental Humidity probe Temperature (C) x100." ::= { slave-Environmental 9 } slave-environmental-Humidity OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Environmental humidity probe (%) x100." ::= { slave-Environmental 10 } slave-environmental-Contact1 OBJECT-TYPE SYNTAX INTEGER {open(0),closed(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Compatible - Environmental contact input 1 status." ::= { slave-Environmental 11 } slave-environmental-Contact2 OBJECT-TYPE SYNTAX INTEGER {open(0),closed(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Compatible - Environmental contact input 2 status." ::= { slave-Environmental 12 } slave-environmental-Contact3 OBJECT-TYPE SYNTAX INTEGER {open(0),closed(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Compatible - Environmental contact input 3 status." ::= { slave-Environmental 13 } -- pdu.slave-Security slave-Security-Door OBJECT-TYPE SYNTAX INTEGER {open(0),closed(1)} MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Security door contact status." ::= { slave-Security 1 } slave-Security-Lock OBJECT-TYPE SYNTAX INTEGER {locked(0),unlocked(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Compatible - Security lock status. Set with any data to force unlock." ::= { slave-Security 2 } -- slave-Traps.slave-TrapSetNotifications slave-Set-meter1-VRMSLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-VRMS } STATUS current DESCRIPTION "Meter 1 Voltage LOW trap SET notification" ::= { slave-TrapSetNotifications 1 } slave-Set-meter1-VRMSHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-VRMS } STATUS current DESCRIPTION "Meter 1 Voltage HIGH trap SET notification" ::= { slave-TrapSetNotifications 2 } slave-Set-meter1-IRMSLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-IRMS } STATUS current DESCRIPTION "Meter 1 Amps LOW trap SET notification" ::= { slave-TrapSetNotifications 3 } slave-Set-meter1-IRMSHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-IRMS } STATUS current DESCRIPTION "Meter 1 Amps HIGH trap SET notification" ::= { slave-TrapSetNotifications 4 } slave-Set-meter1-KWSLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-KW } STATUS current DESCRIPTION "Meter 1 Kilowatts LOW trap SET notification" ::= { slave-TrapSetNotifications 5 } slave-Set-meter1-KWSHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-KW } STATUS current DESCRIPTION "Meter 1 Kilowatts HIGH trap SET notification" ::= { slave-TrapSetNotifications 6 } slave-Set-meter1-TempLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-TPMU } STATUS current DESCRIPTION "Meter 1 Temperature LOW trap SET notification" ::= { slave-TrapSetNotifications 7 } slave-Set-meter1-TempHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-TPMU } STATUS current DESCRIPTION "Meter 1 Temperature HIGH trap SET notification" ::= { slave-TrapSetNotifications 8 } slave-Set-socket-AMPSLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, socket-Number } STATUS current DESCRIPTION "socket Amps LOW trap SET notification" ::= { slave-TrapSetNotifications 9 } slave-Set-socket-AMPSHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, socket-Number } STATUS current DESCRIPTION "socket Amps HIGH trap SET notification" ::= { slave-TrapSetNotifications 10 } slave-Set-environmental-Temp1Low NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp1 } STATUS current DESCRIPTION "Environmental Temperature probe 1 LOW trap SET notification" ::= { slave-TrapSetNotifications 11 } slave-Set-environmental-Temp1High NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp1 } STATUS current DESCRIPTION "Environmental Temperature probe 1 HIGH trap SET notification" ::= { slave-TrapSetNotifications 12 } slave-Set-environmental-Temp2Low NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp2 } STATUS current DESCRIPTION "Environmental Temperature probe 2 LOW trap SET notification" ::= { slave-TrapSetNotifications 13 } slave-Set-environmental-Temp2High NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp2 } STATUS current DESCRIPTION "Environmental Temperature probe 2 HIGH trap SET notification" ::= { slave-TrapSetNotifications 14 } slave-Set-environmental-Temp3Low NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp3 } STATUS current DESCRIPTION "Environmental Temperature probe 3 LOW trap SET notification" ::= { slave-TrapSetNotifications 15 } slave-Set-environmental-Temp3High NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp3 } STATUS current DESCRIPTION "Environmental Temperature probe 3 HIGH trap SET notification" ::= { slave-TrapSetNotifications 16 } slave-Set-environmental-Temp4Low NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp4 } STATUS current DESCRIPTION "Environmental Temperature probe 4 LOW trap SET notification" ::= { slave-TrapSetNotifications 17 } slave-Set-environmental-Temp4High NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp4 } STATUS current DESCRIPTION "Environmental Temperature probe 4 HIGH trap SET notification" ::= { slave-TrapSetNotifications 18 } slave-Set-environmental-Temp5Low NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp5 } STATUS current DESCRIPTION "Environmental Temperature probe 5 LOW trap SET notification" ::= { slave-TrapSetNotifications 19 } slave-Set-environmental-Temp5High NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp5 } STATUS current DESCRIPTION "Environmental Temperature probe 5 HIGH trap SET notification" ::= { slave-TrapSetNotifications 20 } slave-Set-environmental-Temp6Low NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp6 } STATUS current DESCRIPTION "Environmental Temperature probe 6 LOW trap SET notification" ::= { slave-TrapSetNotifications 21 } slave-Set-environmental-Temp6High NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp6 } STATUS current DESCRIPTION "Environmental Temperature probe 6 HIGH trap SET notification" ::= { slave-TrapSetNotifications 22 } slave-Set-environmental-Temp7Low NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp7 } STATUS current DESCRIPTION "Environmental Temperature probe 7 LOW trap SET notification" ::= { slave-TrapSetNotifications 23 } slave-Set-environmental-Temp7High NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp7 } STATUS current DESCRIPTION "Environmental Temperature probe 7 HIGH trap SET notification" ::= { slave-TrapSetNotifications 24 } slave-Set-environmental-Temp8Low NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp8 } STATUS current DESCRIPTION "Environmental Temperature probe 8 LOW trap SET notification" ::= { slave-TrapSetNotifications 25 } slave-Set-environmental-Temp8High NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp8 } STATUS current DESCRIPTION "Environmental Temperature probe 8 HIGH trap SET notification" ::= { slave-TrapSetNotifications 26 } slave-Set-environmental-HumidityTempLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-HumidityTemp } STATUS current DESCRIPTION "Environmental Humidity probe Temperature LOW trap SET notification" ::= { slave-TrapSetNotifications 27 } slave-Set-environmental-HumidityTempHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-HumidityTemp } STATUS current DESCRIPTION "Environmental Humidity probe Temperature HIGH trap SET notification" ::= { slave-TrapSetNotifications 28 } slave-Set-environmental-HumidityLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Humidity } STATUS current DESCRIPTION "Environmental Humidity probe LOW trap SET notification" ::= { slave-TrapSetNotifications 29 } slave-Set-environmental-HumidityHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Humidity } STATUS current DESCRIPTION "Environmental Humidity probe HIGH trap SET notification" ::= { slave-TrapSetNotifications 30 } slave-Set-environmental-Contact1Open NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Contact1 } STATUS current DESCRIPTION "Environmental Contact 1 OPEN trap SET notification" ::= { slave-TrapSetNotifications 31 } slave-Set-environmental-Contact1Closed NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Contact1 } STATUS current DESCRIPTION "Environmental Contact 1 CLOSED trap SET notification" ::= { slave-TrapSetNotifications 32 } slave-Set-environmental-Contact2Open NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Contact2 } STATUS current DESCRIPTION "Environmental Contact 2 OPEN trap SET notification" ::= { slave-TrapSetNotifications 33 } slave-Set-environmental-Contact2Closed NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Contact2 } STATUS current DESCRIPTION "Environmental Contact 2 CLOSED trap SET notification" ::= { slave-TrapSetNotifications 34 } slave-Set-environmental-Contact3Open NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Contact3 } STATUS current DESCRIPTION "Environmental Contact 3 OPEN trap SET notification" ::= { slave-TrapSetNotifications 35 } slave-Set-environmental-Contact3Closed NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Contact3 } STATUS current DESCRIPTION "Environmental Contact 3 CLOSED trap SET notification" ::= { slave-TrapSetNotifications 36 } slave-Set-Security-DoorOpen NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-Security-Door } STATUS current DESCRIPTION "Environmental Door OPEN trap SET notification" ::= { slave-TrapSetNotifications 37 } slave-Set-Security-DoorClosed NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-Security-Door } STATUS current DESCRIPTION "Environmental Door CLOSED trap SET notification" ::= { slave-TrapSetNotifications 38 } slave-Set-Security-LockUnlocked NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-Security-Lock } STATUS current DESCRIPTION "Environmental Lock UNLOCKED trap SET notification" ::= { slave-TrapSetNotifications 39 } slave-Set-Security-LockLocked NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-Security-Lock } STATUS current DESCRIPTION "Environmental Lock LOCKED trap SET notification" ::= { slave-TrapSetNotifications 40 } slave-Set-pduOffline NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-pduStatus } STATUS current DESCRIPTION "pdu OFFLINE trap SET notification" ::= { slave-TrapSetNotifications 41 } slave-Set-meter1-PFLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-PF } STATUS current DESCRIPTION "Meter 1 Power Factor LOW trap SET notification" ::= { slave-TrapSetNotifications 42 } slave-Set-meter1-PFHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-PF } STATUS current DESCRIPTION "Meter 1 Power Factor HIGH trap SET notification" ::= { slave-TrapSetNotifications 43 } slave-Set-meter1-FreqLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-Freq } STATUS current DESCRIPTION "Meter 1 Frequency LOW trap SET notification" ::= { slave-TrapSetNotifications 44 } slave-Set-meter1-FreqHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-Freq } STATUS current DESCRIPTION "Meter 1 Frequency HIGH trap SET notification" ::= { slave-TrapSetNotifications 45 } slave-Set-meter2-VRMSLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-VRMS } STATUS current DESCRIPTION "Meter 2 Voltage LOW trap SET notification" ::= { slave-TrapSetNotifications 46 } slave-Set-meter2-VRMSHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-VRMS } STATUS current DESCRIPTION "Meter 2 Voltage HIGH trap SET notification" ::= { slave-TrapSetNotifications 47 } slave-Set-meter2-IRMSLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-IRMS } STATUS current DESCRIPTION "Meter 2 Amps LOW trap SET notification" ::= { slave-TrapSetNotifications 48 } slave-Set-meter2-IRMSHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-IRMS } STATUS current DESCRIPTION "Meter 2 Amps HIGH trap SET notification" ::= { slave-TrapSetNotifications 49 } slave-Set-meter2-KWSLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-KW } STATUS current DESCRIPTION "Meter 2 Kilowatts LOW trap SET notification" ::= { slave-TrapSetNotifications 50 } slave-Set-meter2-KWSHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-KW } STATUS current DESCRIPTION "Meter 2 Kilowatts HIGH trap SET notification" ::= { slave-TrapSetNotifications 51 } slave-Set-meter2-TempLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-TPMU } STATUS current DESCRIPTION "Meter 2 Temperature LOW trap SET notification" ::= { slave-TrapSetNotifications 52 } slave-Set-meter2-TempHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-TPMU } STATUS current DESCRIPTION "Meter 2 Temperature HIGH trap SET notification" ::= { slave-TrapSetNotifications 53 } slave-Set-meter2-PFLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-PF } STATUS current DESCRIPTION "Meter 2 Power Factor LOW trap SET notification" ::= { slave-TrapSetNotifications 54 } slave-Set-meter2-PFHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-PF } STATUS current DESCRIPTION "Meter 2 Power Factor HIGH trap SET notification" ::= { slave-TrapSetNotifications 55 } slave-Set-meter2-FreqLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-Freq } STATUS current DESCRIPTION "Meter 2 Frequency LOW trap SET notification" ::= { slave-TrapSetNotifications 56 } slave-Set-meter2-FreqHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-Freq } STATUS current DESCRIPTION "Meter 2 Frequency HIGH trap SET notification" ::= { slave-TrapSetNotifications 57 } slave-Set-meter3-VRMSLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-VRMS } STATUS current DESCRIPTION "Meter 3 Voltage LOW trap SET notification" ::= { slave-TrapSetNotifications 58 } slave-Set-meter3-VRMSHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-VRMS } STATUS current DESCRIPTION "Meter 3 Voltage HIGH trap SET notification" ::= { slave-TrapSetNotifications 59 } slave-Set-meter3-IRMSLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-IRMS } STATUS current DESCRIPTION "Meter 3 Amps LOW trap SET notification" ::= { slave-TrapSetNotifications 60 } slave-Set-meter3-IRMSHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-IRMS } STATUS current DESCRIPTION "Meter 3 Amps HIGH trap SET notification" ::= { slave-TrapSetNotifications 61 } slave-Set-meter3-KWSLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-KW } STATUS current DESCRIPTION "Meter 3 Kilowatts LOW trap SET notification" ::= { slave-TrapSetNotifications 62 } slave-Set-meter3-KWSHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-KW } STATUS current DESCRIPTION "Meter 3 Kilowatts HIGH trap SET notification" ::= { slave-TrapSetNotifications 63 } slave-Set-meter3-TempLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-TPMU } STATUS current DESCRIPTION "Meter 3 Temperature LOW trap SET notification" ::= { slave-TrapSetNotifications 64 } slave-Set-meter3-TempHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-TPMU } STATUS current DESCRIPTION "Meter 3 Temperature HIGH trap SET notification" ::= { slave-TrapSetNotifications 65 } slave-Set-meter3-PFLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-PF } STATUS current DESCRIPTION "Meter 3 Power Factor LOW trap SET notification" ::= { slave-TrapSetNotifications 66 } slave-Set-meter3-PFHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-PF } STATUS current DESCRIPTION "Meter 3 Power Factor HIGH trap SET notification" ::= { slave-TrapSetNotifications 67 } slave-Set-meter3-FreqLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-Freq } STATUS current DESCRIPTION "Meter 3 Frequency LOW trap SET notification" ::= { slave-TrapSetNotifications 68 } slave-Set-meter3-FreqHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-Freq } STATUS current DESCRIPTION "Meter 3 Frequency HIGH trap SET notification" ::= { slave-TrapSetNotifications 69 } -- slave-Traps.slave-TrapClearNotifications slave-Clear-meter1-VRMSLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-VRMS } STATUS current DESCRIPTION "Meter 1 Voltage LOW trap CLEAR notification" ::= { slave-TrapClearNotifications 1 } slave-Clear-meter1-VRMSHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-VRMS } STATUS current DESCRIPTION "Meter 1 Voltage HIGH trap CLEAR notification" ::= { slave-TrapClearNotifications 2 } slave-Clear-meter1-IRMSLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-IRMS } STATUS current DESCRIPTION "Meter 1 Amps LOW trap CLEAR notification" ::= { slave-TrapClearNotifications 3 } slave-Clear-meter1-IRMSHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-IRMS } STATUS current DESCRIPTION "Meter 1 Amps HIGH trap CLEAR notification" ::= { slave-TrapClearNotifications 4 } slave-Clear-meter1-KWSLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-KW } STATUS current DESCRIPTION "Meter 1 Kilowatts LOW trap CLEAR notification" ::= { slave-TrapClearNotifications 5 } slave-Clear-meter1-KWSHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-KW } STATUS current DESCRIPTION "Meter 1 Kilowatts HIGH trap CLEAR notification" ::= { slave-TrapClearNotifications 6 } slave-Clear-meter1-TempLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-TPMU } STATUS current DESCRIPTION "Meter 1 Temperature LOW trap CLEAR notification" ::= { slave-TrapClearNotifications 7 } slave-Clear-meter1-TempHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-TPMU } STATUS current DESCRIPTION "Meter 1 Temperature HIGH trap CLEAR notification" ::= { slave-TrapClearNotifications 8 } slave-Clear-socket-AMPSLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, socket-Number } STATUS current DESCRIPTION "socket Amps LOW trap CLEAR notification" ::= { slave-TrapClearNotifications 9 } slave-Clear-socket-AMPSHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, socket-Number } STATUS current DESCRIPTION "socket Amps HIGH trap CLEAR notification" ::= { slave-TrapClearNotifications 10 } slave-Clear-environmental-Temp1Low NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp1 } STATUS current DESCRIPTION "Environmental Temperature probe 1 LOW trap CLEAR notification" ::= { slave-TrapClearNotifications 11 } slave-Clear-environmental-Temp1High NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp1 } STATUS current DESCRIPTION "Environmental Temperature probe 1 HIGH trap CLEAR notification" ::= { slave-TrapClearNotifications 12 } slave-Clear-environmental-Temp2Low NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp2 } STATUS current DESCRIPTION "Environmental Temperature probe 2 LOW trap CLEAR notification" ::= { slave-TrapClearNotifications 13 } slave-Clear-environmental-Temp2High NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp2 } STATUS current DESCRIPTION "Environmental Temperature probe 2 HIGH trap CLEAR notification" ::= { slave-TrapClearNotifications 14 } slave-Clear-environmental-Temp3Low NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp3 } STATUS current DESCRIPTION "Environmental Temperature probe 3 LOW trap CLEAR notification" ::= { slave-TrapClearNotifications 15 } slave-Clear-environmental-Temp3High NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp3 } STATUS current DESCRIPTION "Environmental Temperature probe 3 HIGH trap CLEAR notification" ::= { slave-TrapClearNotifications 16 } slave-Clear-environmental-Temp4Low NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp4 } STATUS current DESCRIPTION "Environmental Temperature probe 4 LOW trap CLEAR notification" ::= { slave-TrapClearNotifications 17 } slave-Clear-environmental-Temp4High NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp4 } STATUS current DESCRIPTION "Environmental Temperature probe 4 HIGH trap CLEAR notification" ::= { slave-TrapClearNotifications 18 } slave-Clear-environmental-Temp5Low NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp5 } STATUS current DESCRIPTION "Environmental Temperature probe 5 LOW trap CLEAR notification" ::= { slave-TrapClearNotifications 19 } slave-Clear-environmental-Temp5High NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp5 } STATUS current DESCRIPTION "Environmental Temperature probe 5 HIGH trap CLEAR notification" ::= { slave-TrapClearNotifications 20 } slave-Clear-environmental-Temp6Low NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp6 } STATUS current DESCRIPTION "Environmental Temperature probe 6 LOW trap CLEAR notification" ::= { slave-TrapClearNotifications 21 } slave-Clear-environmental-Temp6High NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp6 } STATUS current DESCRIPTION "Environmental Temperature probe 6 HIGH trap CLEAR notification" ::= { slave-TrapClearNotifications 22 } slave-Clear-environmental-Temp7Low NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp7 } STATUS current DESCRIPTION "Environmental Temperature probe 7 LOW trap CLEAR notification" ::= { slave-TrapClearNotifications 23 } slave-Clear-environmental-Temp7High NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp7 } STATUS current DESCRIPTION "Environmental Temperature probe 7 HIGH trap CLEAR notification" ::= { slave-TrapClearNotifications 24 } slave-Clear-environmental-Temp8Low NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp8 } STATUS current DESCRIPTION "Environmental Temperature probe 8 LOW trap CLEAR notification" ::= { slave-TrapClearNotifications 25 } slave-Clear-environmental-Temp8High NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Temp8 } STATUS current DESCRIPTION "Environmental Temperature probe 8 HIGH trap CLEAR notification" ::= { slave-TrapClearNotifications 26 } slave-Clear-environmental-HumidityTempLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-HumidityTemp } STATUS current DESCRIPTION "Environmental Humidity probe Temperature LOW trap CLEAR notification" ::= { slave-TrapClearNotifications 27 } slave-Clear-environmental-HumidityTempHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-HumidityTemp } STATUS current DESCRIPTION "Environmental Humidity probe Temperature HIGH trap CLEAR notification" ::= { slave-TrapClearNotifications 28 } slave-Clear-environmental-HumidityLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Humidity } STATUS current DESCRIPTION "Environmental Humidity probe LOW trap CLEAR notification" ::= { slave-TrapClearNotifications 29 } slave-Clear-environmental-HumidityHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Humidity } STATUS current DESCRIPTION "Environmental Humidity probe HIGH trap CLEAR notification" ::= { slave-TrapClearNotifications 30 } slave-Clear-environmental-Contact1Open NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Contact1 } STATUS current DESCRIPTION "Environmental Contact 1 OPEN trap CLEAR notification" ::= { slave-TrapClearNotifications 31 } slave-Clear-environmental-Contact1Closed NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Contact1 } STATUS current DESCRIPTION "Environmental Contact 1 CLOSED trap CLEAR notification" ::= { slave-TrapClearNotifications 32 } slave-Clear-environmental-Contact2Open NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Contact2 } STATUS current DESCRIPTION "Environmental Contact 2 OPEN trap CLEAR notification" ::= { slave-TrapClearNotifications 33 } slave-Clear-environmental-Contact2Closed NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Contact2 } STATUS current DESCRIPTION "Environmental Contact 2 CLOSED trap CLEAR notification" ::= { slave-TrapClearNotifications 34 } slave-Clear-environmental-Contact3Open NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Contact3 } STATUS current DESCRIPTION "Environmental Contact 3 OPEN trap CLEAR notification" ::= { slave-TrapClearNotifications 35 } slave-Clear-environmental-Contact3Closed NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-environmental-Contact3 } STATUS current DESCRIPTION "Environmental Contact 3 CLOSED trap CLEAR notification" ::= { slave-TrapClearNotifications 36 } slave-Clear-Security-DoorOpen NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-Security-Door } STATUS current DESCRIPTION "Environmental Door OPEN trap CLEAR notification" ::= { slave-TrapClearNotifications 37 } slave-Clear-Security-DoorClosed NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-Security-Door } STATUS current DESCRIPTION "Environmental Door CLOSED trap CLEAR notification" ::= { slave-TrapClearNotifications 38 } slave-Clear-Security-LockUnlocked NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-Security-Lock } STATUS current DESCRIPTION "Environmental Lock UNLOCKED trap CLEAR notification" ::= { slave-TrapClearNotifications 39 } slave-Clear-Security-LockLocked NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-Security-Lock } STATUS current DESCRIPTION "Environmental Lock LOCKED trap CLEAR notification" ::= { slave-TrapClearNotifications 40 } slave-Clear-pduOffline NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-pduStatus } STATUS current DESCRIPTION "pdu OFFLINE trap CLEAR notification" ::= { slave-TrapClearNotifications 41 } slave-Clear-meter1-PFLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-PF } STATUS current DESCRIPTION "Meter 1 Power Factor LOW trap CLEAR notification" ::= { slave-TrapClearNotifications 42 } slave-Clear-meter1-PFHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-PF } STATUS current DESCRIPTION "Meter 1 Power Factor HIGH trap CLEAR notification" ::= { slave-TrapClearNotifications 43 } slave-Clear-meter1-FreqLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-Freq } STATUS current DESCRIPTION "Meter 1 Frequency LOW trap CLEAR notification" ::= { slave-TrapClearNotifications 44 } slave-Clear-meter1-FreqHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter1-Freq } STATUS current DESCRIPTION "Meter 1 Frequency HIGH trap CLEAR notification" ::= { slave-TrapClearNotifications 45 } slave-Clear-meter2-VRMSLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-VRMS } STATUS current DESCRIPTION "Meter 2 Voltage LOW trap CLEAR notification" ::= { slave-TrapClearNotifications 46 } slave-Clear-meter2-VRMSHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-VRMS } STATUS current DESCRIPTION "Meter 2 Voltage HIGH trap CLEAR notification" ::= { slave-TrapClearNotifications 47 } slave-Clear-meter2-IRMSLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-IRMS } STATUS current DESCRIPTION "Meter 2 Amps LOW trap CLEAR notification" ::= { slave-TrapClearNotifications 48 } slave-Clear-meter2-IRMSHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-IRMS } STATUS current DESCRIPTION "Meter 2 Amps HIGH trap CLEAR notification" ::= { slave-TrapClearNotifications 49 } slave-Clear-meter2-KWSLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-KW } STATUS current DESCRIPTION "Meter 2 Kilowatts LOW trap CLEAR notification" ::= { slave-TrapClearNotifications 50 } slave-Clear-meter2-KWSHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-KW } STATUS current DESCRIPTION "Meter 2 Kilowatts HIGH trap CLEAR notification" ::= { slave-TrapClearNotifications 51 } slave-Clear-meter2-TempLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-TPMU } STATUS current DESCRIPTION "Meter 2 Temperature LOW trap CLEAR notification" ::= { slave-TrapClearNotifications 52 } slave-Clear-meter2-TempHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-TPMU } STATUS current DESCRIPTION "Meter 2 Temperature HIGH trap CLEAR notification" ::= { slave-TrapClearNotifications 53 } slave-Clear-meter2-PFLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-PF } STATUS current DESCRIPTION "Meter 2 Power Factor LOW trap CLEAR notification" ::= { slave-TrapClearNotifications 54 } slave-Clear-meter2-PFHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-PF } STATUS current DESCRIPTION "Meter 2 Power Factor HIGH trap CLEAR notification" ::= { slave-TrapClearNotifications 55 } slave-Clear-meter2-FreqLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-Freq } STATUS current DESCRIPTION "Meter 2 Frequency LOW trap CLEAR notification" ::= { slave-TrapClearNotifications 56 } slave-Clear-meter2-FreqHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter2-Freq } STATUS current DESCRIPTION "Meter 2 Frequency HIGH trap CLEAR notification" ::= { slave-TrapClearNotifications 57 } slave-Clear-meter3-VRMSLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-VRMS } STATUS current DESCRIPTION "Meter 3 Voltage LOW trap CLEAR notification" ::= { slave-TrapClearNotifications 58 } slave-Clear-meter3-VRMSHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-VRMS } STATUS current DESCRIPTION "Meter 3 Voltage HIGH trap CLEAR notification" ::= { slave-TrapClearNotifications 59 } slave-Clear-meter3-IRMSLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-IRMS } STATUS current DESCRIPTION "Meter 3 Amps LOW trap CLEAR notification" ::= { slave-TrapClearNotifications 60 } slave-Clear-meter3-IRMSHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-IRMS } STATUS current DESCRIPTION "Meter 3 Amps HIGH trap CLEAR notification" ::= { slave-TrapClearNotifications 61 } slave-Clear-meter3-KWSLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-KW } STATUS current DESCRIPTION "Meter 3 Kilowatts LOW trap CLEAR notification" ::= { slave-TrapClearNotifications 62 } slave-Clear-meter3-KWSHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-KW } STATUS current DESCRIPTION "Meter 3 Kilowatts HIGH trap CLEAR notification" ::= { slave-TrapClearNotifications 63 } slave-Clear-meter3-TempLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-TPMU } STATUS current DESCRIPTION "Meter 3 Temperature LOW trap CLEAR notification" ::= { slave-TrapClearNotifications 64 } slave-Clear-meter3-TempHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-TPMU } STATUS current DESCRIPTION "Meter 3 Temperature HIGH trap CLEAR notification" ::= { slave-TrapClearNotifications 65 } slave-Clear-meter3-PFLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-PF } STATUS current DESCRIPTION "Meter 3 Power Factor LOW trap CLEAR notification" ::= { slave-TrapClearNotifications 66 } slave-Clear-meter3-PFHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-PF } STATUS current DESCRIPTION "Meter 3 Power Factor HIGH trap CLEAR notification" ::= { slave-TrapClearNotifications 67 } slave-Clear-meter3-FreqLow NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-Freq } STATUS current DESCRIPTION "Meter 3 Frequency LOW trap CLEAR notification" ::= { slave-TrapClearNotifications 68 } slave-Clear-meter3-FreqHigh NOTIFICATION-TYPE OBJECTS { pdu-ClientName, pdu-LocationName, slave-pduAddress, slave-meter3-Freq } STATUS current DESCRIPTION "Meter 3 Frequency HIGH trap CLEAR notification" ::= { slave-TrapClearNotifications 69 } -- slave-Global slave-Global-Table OBJECT-TYPE SYNTAX SEQUENCE OF Slave-Global-Entry MAX-ACCESS not-accessible STATUS current DESCRIPTION "" ::= { slave-Global 1 } slave-Global-Entry OBJECT-TYPE SYNTAX Slave-Global-Entry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of Trap notification destinations." INDEX { slave-Global-Index } ::= { slave-Global-Table 1 } Slave-Global-Entry ::= SEQUENCE { slave-Global-Index INTEGER, slave-Global-Status INTEGER, slave-Global-Address INTEGER, slave-Global-Nosockets INTEGER, slave-Global-meter1-VRMS INTEGER, slave-Global-meter1-IRMS INTEGER, slave-Global-meter1-VRMS INTEGER, slave-Global-meter1-KWH Integer32, slave-Global-meter1-KW INTEGER, slave-Global-meter1-TPMU INTEGER, slave-Global-meter1-PF INTEGER, slave-Global-environmental-Temp1 INTEGER, slave-Global-environmental-Temp2 INTEGER, slave-Global-environmental-Temp3 INTEGER, slave-Global-environmental-Temp4 INTEGER, slave-Global-environmental-Temp5 INTEGER, slave-Global-environmental-Temp6 INTEGER, slave-Global-environmental-Temp7 INTEGER, slave-Global-environmental-Temp8 INTEGER, slave-Global-environmental-HumidityTemp INTEGER, slave-Global-environmental-Humidity INTEGER, slave-Global-environmental-Contact1 INTEGER, slave-Global-environmental-Contact2 INTEGER, slave-Global-environmental-Contact3 INTEGER, slave-Global-Security-Door INTEGER, slave-Global-Security-Lock INTEGER, slave-Global-sockets Integer32, slave-Global-socket1Amps INTEGER, slave-Global-socket2Amps INTEGER, slave-Global-socket3Amps INTEGER, slave-Global-socket4Amps INTEGER, slave-Global-socket5Amps INTEGER, slave-Global-socket6Amps INTEGER, slave-Global-socket7Amps INTEGER, slave-Global-socket8Amps INTEGER, slave-Global-socket9Amps INTEGER, slave-Global-socket10Amps INTEGER, slave-Global-socket11Amps INTEGER, slave-Global-socket12Amps INTEGER, slave-Global-socket13Amps INTEGER, slave-Global-socket14Amps INTEGER, slave-Global-socket15Amps INTEGER, slave-Global-socket16Amps INTEGER, slave-Global-socket17Amps INTEGER, slave-Global-socket18Amps INTEGER, slave-Global-socket19Amps INTEGER, slave-Global-socket20Amps INTEGER, slave-Global-socket21Amps INTEGER, slave-Global-socket22Amps INTEGER, slave-Global-socket23Amps INTEGER, slave-Global-socket24Amps INTEGER, slave-Global-socket25Amps INTEGER, slave-Global-socket26Amps INTEGER, slave-Global-socket27Amps INTEGER, slave-Global-socket28Amps INTEGER, slave-Global-socket29Amps INTEGER, slave-Global-socket30Amps INTEGER, slave-Global-socket31Amps INTEGER, slave-Global-socket32Amps INTEGER, slave-Global-socket1kWh Integer32, slave-Global-socket2kWh Integer32, slave-Global-socket3kWh Integer32, slave-Global-socket4kWh Integer32, slave-Global-socket5kWh Integer32, slave-Global-socket6kWh Integer32, slave-Global-socket7kWh Integer32, slave-Global-socket8kWh Integer32, slave-Global-socket9kWh Integer32, slave-Global-socket10kWh Integer32, slave-Global-socket11kWh Integer32, slave-Global-socket12kWh Integer32, slave-Global-socket13kWh Integer32, slave-Global-socket14kWh Integer32, slave-Global-socket15kWh Integer32, slave-Global-socket16kWh Integer32, slave-Global-socket17kWh Integer32, slave-Global-socket18kWh Integer32, slave-Global-socket19kWh Integer32, slave-Global-socket20kWh Integer32, slave-Global-socket21kWh Integer32, slave-Global-socket22kWh Integer32, slave-Global-socket23kWh Integer32, slave-Global-socket24kWh Integer32, slave-Global-socket25kWh Integer32, slave-Global-socket26kWh Integer32, slave-Global-socket27kWh Integer32, slave-Global-socket28kWh Integer32, slave-Global-socket29kWh Integer32, slave-Global-socket30kWh Integer32, slave-Global-socket31kWh Integer32, slave-Global-socket32kWh Integer32, slave-Global-socket33Amps INTEGER, slave-Global-socket34Amps INTEGER, slave-Global-socket35Amps INTEGER, slave-Global-socket36Amps INTEGER, slave-Global-socket37Amps INTEGER, slave-Global-socket38Amps INTEGER, slave-Global-socket39Amps INTEGER, slave-Global-socket40Amps INTEGER, slave-Global-socket41Amps INTEGER, slave-Global-socket42Amps INTEGER, slave-Global-socket43Amps INTEGER, slave-Global-socket44Amps INTEGER, slave-Global-socket45Amps INTEGER, slave-Global-socket46Amps INTEGER, slave-Global-socket47Amps INTEGER, slave-Global-socket48Amps INTEGER, slave-Global-socket33kWh Integer32, slave-Global-socket34kWh Integer32, slave-Global-socket35kWh Integer32, slave-Global-socket36kWh Integer32, slave-Global-socket37kWh Integer32, slave-Global-socket38kWh Integer32, slave-Global-socket39kWh Integer32, slave-Global-socket40kWh Integer32, slave-Global-socket41kWh Integer32, slave-Global-socket42kWh Integer32, slave-Global-socket43kWh Integer32, slave-Global-socket44kWh Integer32, slave-Global-socket45kWh Integer32, slave-Global-socket46kWh Integer32, slave-Global-socket47kWh Integer32, slave-Global-socket48kWh Integer32, slave-Global-sockets2 Integer32, slave-Global-meter1-Freq INTEGER, slave-Global-meter2-VRMS INTEGER, slave-Global-meter2-IRMS INTEGER, slave-Global-meter2-VRMS INTEGER, slave-Global-meter2-KWH Integer32, slave-Global-meter2-KW INTEGER, slave-Global-meter2-TPMU INTEGER, slave-Global-meter2-PF INTEGER, slave-Global-meter2-Freq INTEGER, slave-Global-meter3-VRMS INTEGER, slave-Global-meter3-IRMS INTEGER, slave-Global-meter3-VRMS INTEGER, slave-Global-meter3-KWH Integer32, slave-Global-meter3-KW INTEGER, slave-Global-meter3-TPMU INTEGER, slave-Global-meter3-PF INTEGER, slave-Global-meter3-Freq INTEGER } slave-Global-Index OBJECT-TYPE SYNTAX INTEGER (0..31) MAX-ACCESS not-accessible STATUS current DESCRIPTION "pdu index [0..Nopdus]." ::= { slave-Global-Entry 1 } slave-Global-Status OBJECT-TYPE SYNTAX INTEGER {offline(0),online(1),disabled(2)} MAX-ACCESS read-write STATUS current DESCRIPTION "Compatible - pdu ONLINE / OFFLINE or DISABLED status." ::= { slave-Global-Entry 2 } slave-Global-Address OBJECT-TYPE SYNTAX INTEGER (1..32) MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - pdu MODBUS Address." ::= { slave-Global-Entry 3 } slave-Global-Nosockets OBJECT-TYPE SYNTAX INTEGER (0..48) MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - pdu Number of sockets." ::= { slave-Global-Entry 4 } slave-Global-meter1-VRMS OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Meter 1 RMS Voltage (VAC) x10." ::= { slave-Global-Entry 5 } slave-Global-meter1-IRMS OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Meter 1 RMS Current (A) x10." ::= { slave-Global-Entry 6 } slave-Global-meter1-KWH OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Meter 1 Total energy consumption (kW/h) x10." ::= { slave-Global-Entry 7 } slave-Global-meter1-KW OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Meter 1 Kilowatts (kW) x1000." ::= { slave-Global-Entry 8 } slave-Global-meter1-TPMU OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Meter 1 Internal Temperature (C) x10." ::= { slave-Global-Entry 9 } slave-Global-meter1-PF OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Meter 1 Power Factor x1000" ::= { slave-Global-Entry 10 } slave-Global-environmental-Temp1 OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Environmental Temperature probe 1 (C) x100." ::= { slave-Global-Entry 11 } slave-Global-environmental-Temp2 OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Environmental Temperature probe 2 (C) x100." ::= { slave-Global-Entry 12 } slave-Global-environmental-Temp3 OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Environmental Temperature probe 3 (C) x100." ::= { slave-Global-Entry 13 } slave-Global-environmental-Temp4 OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Environmental Temperature probe 4 (C) x100." ::= { slave-Global-Entry 14 } slave-Global-environmental-Temp5 OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Environmental Temperature probe 5 (C) x100." ::= { slave-Global-Entry 15 } slave-Global-environmental-Temp6 OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Environmental Temperature probe 6 (C) x100." ::= { slave-Global-Entry 16 } slave-Global-environmental-Temp7 OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Environmental Temperature probe 7 (C) x100." ::= { slave-Global-Entry 17 } slave-Global-environmental-Temp8 OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Environmental Temperature probe 8 (C) x100." ::= { slave-Global-Entry 18 } slave-Global-environmental-HumidityTemp OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Environmental Humidity probe Temperature (C) x100." ::= { slave-Global-Entry 19 } slave-Global-environmental-Humidity OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Environmental humidity probe (%) x100." ::= { slave-Global-Entry 20 } slave-Global-environmental-Contact1 OBJECT-TYPE SYNTAX INTEGER {open(0),closed(1),none(3)} MAX-ACCESS read-write STATUS current DESCRIPTION "Compatible - Environmental contact input 1 status. Set with any data to clear status." ::= { slave-Global-Entry 21 } slave-Global-environmental-Contact2 OBJECT-TYPE SYNTAX INTEGER {open(0),closed(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Compatible - Environmental contact input 2 status. Set with any data to clear status." ::= { slave-Global-Entry 22 } slave-Global-environmental-Contact3 OBJECT-TYPE SYNTAX INTEGER {open(0),closed(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Compatible - Environmental contact input 3 status. Set with any data to clear status." ::= { slave-Global-Entry 23 } slave-Global-Security-Door OBJECT-TYPE SYNTAX INTEGER {open(0),closed(1)} MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - Environmental door contact status." ::= { slave-Global-Entry 24 } slave-Global-Security-Lock OBJECT-TYPE SYNTAX INTEGER {locked(0),unlocked(1)} MAX-ACCESS read-write STATUS current DESCRIPTION "Compatible - Environmental lock status. Set with any data to force unlock." ::= { slave-Global-Entry 25 } slave-Global-sockets OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Compatible - socket status bits 1 to 32 Set or clear bit to control socket, Bit 0 = socket 1, Bit 31 = socket 32" ::= { slave-Global-Entry 26 } slave-Global-socket1Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket Amps value x10." ::= { slave-Global-Entry 27 } slave-Global-socket2Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket Amps value x10." ::= { slave-Global-Entry 28 } slave-Global-socket3Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket Amps value x10." ::= { slave-Global-Entry 29 } slave-Global-socket4Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket Amps value x10." ::= { slave-Global-Entry 30 } slave-Global-socket5Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket Amps value x10." ::= { slave-Global-Entry 31 } slave-Global-socket6Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket Amps value x10." ::= { slave-Global-Entry 32 } slave-Global-socket7Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket Amps value x10." ::= { slave-Global-Entry 33 } slave-Global-socket8Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket Amps value x10." ::= { slave-Global-Entry 34 } slave-Global-socket9Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket Amps value x10." ::= { slave-Global-Entry 35 } slave-Global-socket10Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket Amps value x10." ::= { slave-Global-Entry 36 } slave-Global-socket11Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket Amps value x10." ::= { slave-Global-Entry 37 } slave-Global-socket12Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket Amps value x10." ::= { slave-Global-Entry 38 } slave-Global-socket13Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket Amps value x10." ::= { slave-Global-Entry 39 } slave-Global-socket14Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket Amps value x10." ::= { slave-Global-Entry 40 } slave-Global-socket15Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket Amps value x10." ::= { slave-Global-Entry 41 } slave-Global-socket16Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket Amps value x10." ::= { slave-Global-Entry 42 } slave-Global-socket17Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket Amps value x10." ::= { slave-Global-Entry 43 } slave-Global-socket18Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket Amps value x10." ::= { slave-Global-Entry 44 } slave-Global-socket19Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket Amps value x10." ::= { slave-Global-Entry 45 } slave-Global-socket20Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket Amps value x10." ::= { slave-Global-Entry 46 } slave-Global-socket21Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket Amps value x10." ::= { slave-Global-Entry 47 } slave-Global-socket22Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket Amps value x10." ::= { slave-Global-Entry 48 } slave-Global-socket23Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket Amps value x10." ::= { slave-Global-Entry 49 } slave-Global-socket24Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket Amps value x10." ::= { slave-Global-Entry 50 } slave-Global-socket25Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket Amps value x10." ::= { slave-Global-Entry 51 } slave-Global-socket26Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket Amps value x10." ::= { slave-Global-Entry 52 } slave-Global-socket27Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket Amps value x10." ::= { slave-Global-Entry 53 } slave-Global-socket28Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket Amps value x10." ::= { slave-Global-Entry 54 } slave-Global-socket29Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket Amps value x10." ::= { slave-Global-Entry 55 } slave-Global-socket30Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket Amps value x10." ::= { slave-Global-Entry 56 } slave-Global-socket31Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket Amps value x10." ::= { slave-Global-Entry 57 } slave-Global-socket32Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket Amps value x10." ::= { slave-Global-Entry 58 } slave-Global-socket1kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket kWh value x10." ::= { slave-Global-Entry 59 } slave-Global-socket2kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket kWh value x10." ::= { slave-Global-Entry 60 } slave-Global-socket3kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket kWh value x10." ::= { slave-Global-Entry 61 } slave-Global-socket4kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket kWh value x10." ::= { slave-Global-Entry 62 } slave-Global-socket5kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket kWh value x10." ::= { slave-Global-Entry 63 } slave-Global-socket6kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket kWh value x10." ::= { slave-Global-Entry 64 } slave-Global-socket7kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket kWh value x10." ::= { slave-Global-Entry 65 } slave-Global-socket8kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket kWh value x10." ::= { slave-Global-Entry 66 } slave-Global-socket9kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket kWh value x10." ::= { slave-Global-Entry 67 } slave-Global-socket10kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket kWh value x10." ::= { slave-Global-Entry 68 } slave-Global-socket11kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket kWh value x10." ::= { slave-Global-Entry 69 } slave-Global-socket12kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket kWh value x10." ::= { slave-Global-Entry 70 } slave-Global-socket13kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket kWh value x10." ::= { slave-Global-Entry 71 } slave-Global-socket14kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket kWh value x10." ::= { slave-Global-Entry 72 } slave-Global-socket15kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket kWh value x10." ::= { slave-Global-Entry 73 } slave-Global-socket16kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket kWh value x10." ::= { slave-Global-Entry 74 } slave-Global-socket17kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket kWh value x10." ::= { slave-Global-Entry 75 } slave-Global-socket18kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket kWh value x10." ::= { slave-Global-Entry 76 } slave-Global-socket19kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket kWh value x10." ::= { slave-Global-Entry 77 } slave-Global-socket20kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket kWh value x10." ::= { slave-Global-Entry 78 } slave-Global-socket21kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket kWh value x10." ::= { slave-Global-Entry 79 } slave-Global-socket22kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket kWh value x10." ::= { slave-Global-Entry 80 } slave-Global-socket23kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket kWh value x10." ::= { slave-Global-Entry 81 } slave-Global-socket24kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket kWh value x10." ::= { slave-Global-Entry 82 } slave-Global-socket25kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket kWh value x10." ::= { slave-Global-Entry 83 } slave-Global-socket26kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket kWh value x10." ::= { slave-Global-Entry 84 } slave-Global-socket27kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket kWh value x10." ::= { slave-Global-Entry 85 } slave-Global-socket28kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket kWh value x10." ::= { slave-Global-Entry 86 } slave-Global-socket29kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket kWh value x10." ::= { slave-Global-Entry 87 } slave-Global-socket30kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket kWh value x10." ::= { slave-Global-Entry 88 } slave-Global-socket31kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket kWh value x10." ::= { slave-Global-Entry 89 } slave-Global-socket32kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Compatible - socket kWh value x10." ::= { slave-Global-Entry 90 } slave-Global-socket33Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "socket Amps value x10." ::= { slave-Global-Entry 91 } slave-Global-socket34Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "socket Amps value x10." ::= { slave-Global-Entry 92 } slave-Global-socket35Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "socket Amps value x10." ::= { slave-Global-Entry 93 } slave-Global-socket36Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "socket Amps value x10." ::= { slave-Global-Entry 94 } slave-Global-socket37Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "socket Amps value x10." ::= { slave-Global-Entry 95 } slave-Global-socket38Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "socket Amps value x10." ::= { slave-Global-Entry 96 } slave-Global-socket39Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "socket Amps value x10." ::= { slave-Global-Entry 97 } slave-Global-socket40Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "socket Amps value x10." ::= { slave-Global-Entry 98 } slave-Global-socket41Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "socket Amps value x10." ::= { slave-Global-Entry 99 } slave-Global-socket42Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "socket Amps value x10." ::= { slave-Global-Entry 100 } slave-Global-socket43Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "socket Amps value x10." ::= { slave-Global-Entry 101 } slave-Global-socket44Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "socket Amps value x10." ::= { slave-Global-Entry 102 } slave-Global-socket45Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "socket Amps value x10." ::= { slave-Global-Entry 103 } slave-Global-socket46Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "socket Amps value x10." ::= { slave-Global-Entry 104 } slave-Global-socket47Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "socket Amps value x10." ::= { slave-Global-Entry 105 } slave-Global-socket48Amps OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "socket Amps value x10." ::= { slave-Global-Entry 106 } slave-Global-socket33kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "socket kWh value x10." ::= { slave-Global-Entry 107 } slave-Global-socket34kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "socket kWh value x10." ::= { slave-Global-Entry 108 } slave-Global-socket35kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "socket kWh value x10." ::= { slave-Global-Entry 109 } slave-Global-socket36kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "socket kWh value x10." ::= { slave-Global-Entry 110 } slave-Global-socket37kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "socket kWh value x10." ::= { slave-Global-Entry 111 } slave-Global-socket38kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "socket kWh value x10." ::= { slave-Global-Entry 112 } slave-Global-socket39kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "socket kWh value x10." ::= { slave-Global-Entry 113 } slave-Global-socket40kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "socket kWh value x10." ::= { slave-Global-Entry 114 } slave-Global-socket41kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "socket kWh value x10." ::= { slave-Global-Entry 115 } slave-Global-socket42kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "socket kWh value x10." ::= { slave-Global-Entry 116 } slave-Global-socket43kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "socket kWh value x10." ::= { slave-Global-Entry 117 } slave-Global-socket44kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "socket kWh value x10." ::= { slave-Global-Entry 118 } slave-Global-socket45kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "socket kWh value x10." ::= { slave-Global-Entry 119 } slave-Global-socket46kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "socket kWh value x10." ::= { slave-Global-Entry 120 } slave-Global-socket47kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "socket kWh value x10." ::= { slave-Global-Entry 121 } slave-Global-socket48kWh OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "socket kWh value x10." ::= { slave-Global-Entry 122 } slave-Global-sockets2 OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "socket status bits 33-48 Set or clear bit to control socket, Bit 0 = socket 33, Bit 15 = socket 48" ::= { slave-Global-Entry 123 } slave-Global-meter1-Freq OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Meter 1 Frequency x10" ::= { slave-Global-Entry 124 } slave-Global-meter2-VRMS OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Meter 2 RMS Voltage (VAC) x10." ::= { slave-Global-Entry 125 } slave-Global-meter2-IRMS OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Meter 2 RMS Current (A) x10." ::= { slave-Global-Entry 126 } slave-Global-meter2-KWH OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Meter 2 Total energy consumption (kW/h) x10." ::= { slave-Global-Entry 127 } slave-Global-meter2-KW OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Meter 2 Kilowatts (kW) x1000." ::= { slave-Global-Entry 128 } slave-Global-meter2-TPMU OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Meter 2 Internal Temperature (C) x10." ::= { slave-Global-Entry 129 } slave-Global-meter2-PF OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Meter 2 Power Factor x1000" ::= { slave-Global-Entry 130 } slave-Global-meter2-Freq OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Meter 2 Frequency x10" ::= { slave-Global-Entry 131 } slave-Global-meter3-VRMS OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Meter 3 RMS Voltage (VAC) x10." ::= { slave-Global-Entry 132 } slave-Global-meter3-IRMS OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Meter 3 RMS Current (A) x10." ::= { slave-Global-Entry 133 } slave-Global-meter3-KWH OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Meter 3 Total energy consumption (kW/h) x10." ::= { slave-Global-Entry 134 } slave-Global-meter3-KW OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Meter 3 Kilowatts (kW) x1000." ::= { slave-Global-Entry 135 } slave-Global-meter3-TPMU OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Meter 3 Internal Temperature (C) x10." ::= { slave-Global-Entry 136 } slave-Global-meter3-PF OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Meter 3 Power Factor x1000" ::= { slave-Global-Entry 137 } slave-Global-meter3-Freq OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Meter 3 Frequency x10" ::= { slave-Global-Entry 138 } END