HM2-IOMODULE-MIB DEFINITIONS ::= BEGIN -- -- *********************************************************** -- Hirschmann IO Module MIB -- *********************************************************** -- IMPORTS MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE, Integer32 FROM SNMPv2-SMI InetPortNumber, InetAddressType, InetAddress FROM INET-ADDRESS-MIB HmEnabledStatus, hm2ConfigurationMibs FROM HM2-TC-MIB; hm2IOModuleMib MODULE-IDENTITY LAST-UPDATED "201202100000Z" -- February 10, 2012 ORGANIZATION "Hirschmann Automation and Control GmbH" CONTACT-INFO "Postal: Stuttgarter Str. 45-51 72654 Neckartenzlingen Germany Phone: +49 7127 140 E-mail: hac.support@belden.com" DESCRIPTION "Hirschmann IO Module MIB. Copyright (C) 2012. All Rights Reserved." REVISION "201202100000Z" -- February 10, 2012 DESCRIPTION "Initial version." ::= { hm2ConfigurationMibs 100 } -- -- *********************************************************** -- hm2IOModuleMib -- *********************************************************** -- hm2IOModuleMibNotifications OBJECT IDENTIFIER ::= { hm2IOModuleMib 0 } hm2IOModuleMibObjects OBJECT IDENTIFIER ::= { hm2IOModuleMib 1 } -- hm2IOModuleMibConformance OBJECT IDENTIFIER ::= { hm2IOModuleMib 2 } -- ************************************************************************* -- Group Config -- ************************************************************************* hm2IOModConfigGroup OBJECT IDENTIFIER ::= { hm2IOModuleMibObjects 1 } -- ************************************************************************* -- Group Common Config -- ************************************************************************* hm2IOModConfigCommon OBJECT IDENTIFIER ::= { hm2IOModConfigGroup 1 } hm2IOModConfigDigInputAdminState OBJECT-TYPE SYNTAX HmEnabledStatus MAX-ACCESS read-write STATUS current DESCRIPTION "Enables polling of input values. (if disable(2) input task will do nothing)" DEFVAL { disable } ::= { hm2IOModConfigCommon 1 } hm2IOModConfigDigOutputAdminState OBJECT-TYPE SYNTAX HmEnabledStatus MAX-ACCESS read-write STATUS current DESCRIPTION "Enables mirroring of input values to output ports. (if disable(2) output task will do nothing)" DEFVAL { disable } ::= { hm2IOModConfigCommon 2 } hm2IOModConfigDigInputRefreshInterval OBJECT-TYPE SYNTAX Integer32 (1000..10000) MAX-ACCESS read-write STATUS current DESCRIPTION "The refresh interval (in ms) of the input values. The accuracy of the interval value is 100ms. Minimum 1000ms (1s), Maximum 10000ms (10s)." DEFVAL { 1000 } ::= { hm2IOModConfigCommon 3 } hm2IOModConfigDigOutputRefreshInterval OBJECT-TYPE SYNTAX Integer32 (1000..10000) MAX-ACCESS read-write STATUS current DESCRIPTION "The refresh interval (in ms) of the output values. The accuracy of the interval value is 100ms. Minimum 1000ms (1s), Maximum 10000ms (10s)." DEFVAL { 1000 } ::= { hm2IOModConfigCommon 4 } hm2IOModConfigDigOutputRetryCount OBJECT-TYPE SYNTAX Integer32 (1..10) MAX-ACCESS read-write STATUS current DESCRIPTION "The retry count for the output values. when after the number of configured retries no SNMP get request was answered, the output value (hm2IOModValueDigOutputValue) will be set to invalid (3). Minimum 1, Maximum 10." DEFVAL { 3 } ::= { hm2IOModConfigCommon 5 } -- ************************************************************************* -- Table Digital Input Config -- ************************************************************************* hm2IOModConfigDigInputTable OBJECT-TYPE SYNTAX SEQUENCE OF Hm2IOModConfigDigInputEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "IO module config table for inputs" ::= { hm2IOModConfigGroup 2 } hm2IOModConfigDigInputEntry OBJECT-TYPE SYNTAX Hm2IOModConfigDigInputEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "IO module config entry for inputs" INDEX { hm2IOModConfigDigInputModID, hm2IOModConfigDigInputID} ::= { hm2IOModConfigDigInputTable 1 } Hm2IOModConfigDigInputEntry ::= SEQUENCE { hm2IOModConfigDigInputModID Integer32, hm2IOModConfigDigInputID Integer32, hm2IOModConfigDigInputLogEvent HmEnabledStatus, hm2IOModConfigDigInputSnmpTrap HmEnabledStatus } hm2IOModConfigDigInputModID OBJECT-TYPE SYNTAX Integer32 (0..7) MAX-ACCESS not-accessible STATUS current DESCRIPTION "The module ID of an input. Module ID 0 corresponds to the power supply module." ::= { hm2IOModConfigDigInputEntry 1 } hm2IOModConfigDigInputID OBJECT-TYPE SYNTAX Integer32 (1..4) MAX-ACCESS not-accessible STATUS current DESCRIPTION "The ID of an input." ::= { hm2IOModConfigDigInputEntry 2 } hm2IOModConfigDigInputLogEvent OBJECT-TYPE SYNTAX HmEnabledStatus MAX-ACCESS read-write STATUS current DESCRIPTION "Trigger an event log when input status changes. If the value is disable (2), no event log entry will be written. If the value is enable (1), an event log entry will be written when the input state changes. The input state will be checked according to the refresh interval entered in hm2IOModConfigDigInputRefreshInterval." DEFVAL { disable } ::= { hm2IOModConfigDigInputEntry 3 } hm2IOModConfigDigInputSnmpTrap OBJECT-TYPE SYNTAX HmEnabledStatus MAX-ACCESS read-write STATUS current DESCRIPTION "Trigger an SNMP trap log when input status changes. If the value is disable (2), no SNMP trap will be sent. If the value is enable (1), a SNMP trap will be sent when the input state changes. The SNMP trap will be sent to all receivers configured in the snmpTargetAddrTable. The input state will be checked according to the refresh interval entered in hm2IOModConfigDigInputRefreshInterval." DEFVAL { disable } ::= { hm2IOModConfigDigInputEntry 4 } -- ************************************************************************* -- Table Digital Output Config -- ************************************************************************* hm2IOModConfigDigOutputTable OBJECT-TYPE SYNTAX SEQUENCE OF Hm2IOModConfigDigOutputEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "IO module config table for outputs." ::= { hm2IOModConfigGroup 3 } hm2IOModConfigDigOutputEntry OBJECT-TYPE SYNTAX Hm2IOModConfigDigOutputEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "IO module config entry for outputs" INDEX { hm2IOModConfigDigOutputModID, hm2IOModConfigDigOutputID } ::= { hm2IOModConfigDigOutputTable 1 } Hm2IOModConfigDigOutputEntry ::= SEQUENCE { hm2IOModConfigDigOutputModID Integer32, hm2IOModConfigDigOutputID Integer32, hm2IOModConfigDigOutputLogEvent HmEnabledStatus, hm2IOModConfigDigOutputSnmpTrap HmEnabledStatus, hm2IOModConfigDigOutputSourceAddressType InetAddressType, hm2IOModConfigDigOutputSourceAddress InetAddress, hm2IOModConfigDigOutputSourcePort InetPortNumber, hm2IOModConfigDigOutputSourceModID Integer32, hm2IOModConfigDigOutputSourceID Integer32 } hm2IOModConfigDigOutputModID OBJECT-TYPE SYNTAX Integer32 (0..7) MAX-ACCESS not-accessible STATUS current DESCRIPTION "The module ID of an output. Module ID 0 corresponds to the power supply module." ::= { hm2IOModConfigDigOutputEntry 1 } hm2IOModConfigDigOutputID OBJECT-TYPE SYNTAX Integer32 (1..4) MAX-ACCESS not-accessible STATUS current DESCRIPTION "The ID of an output." ::= { hm2IOModConfigDigOutputEntry 2 } hm2IOModConfigDigOutputLogEvent OBJECT-TYPE SYNTAX HmEnabledStatus MAX-ACCESS read-write STATUS current DESCRIPTION "Trigger an event log when output status changes. If the value is disable (2), no event log entry will be written. If the value is enable (1), an event log entry will be written when the output state changes. The output state will be checked according to the refresh interval entered in hm2IOModConfigDigOutputRefreshInterval." DEFVAL { disable } ::= { hm2IOModConfigDigOutputEntry 3 } hm2IOModConfigDigOutputSnmpTrap OBJECT-TYPE SYNTAX HmEnabledStatus MAX-ACCESS read-write STATUS current DESCRIPTION "Trigger an SNMP trap log when output status changes. If the value is disable (2), no SNMP trap will be sent. If the value is enable (1), a SNMP trap will be sent when the output state changes. The SNMP trap will be sent to all receivers configured in the snmpTargetAddrTable. The output state will be checked according to the refresh interval entered in hm2IOModConfigDigOutputRefreshInterval." DEFVAL { disable } ::= { hm2IOModConfigDigOutputEntry 4 } hm2IOModConfigDigOutputSourceAddressType OBJECT-TYPE SYNTAX InetAddressType MAX-ACCESS read-write STATUS current DESCRIPTION "Address type of an input mirrored to the output. Currently, only ipv4 is supported." DEFVAL { ipv4 } ::= { hm2IOModConfigDigOutputEntry 5 } hm2IOModConfigDigOutputSourceAddress OBJECT-TYPE SYNTAX InetAddress MAX-ACCESS read-write STATUS current DESCRIPTION "The IP address of an input mirrored to the output. Use 0.0.0.0 if the output should not be set. In this case hm2IOModValueDigOutputValue is not-configured(4). Use 127.0.0.1 if a local input should be used." DEFVAL { '00000000'H } -- 0.0.0.0 ::= { hm2IOModConfigDigOutputEntry 6 } hm2IOModConfigDigOutputSourcePort OBJECT-TYPE SYNTAX InetPortNumber MAX-ACCESS read-write STATUS current DESCRIPTION "The SNMP port number being used by the input mirrored to the output. This port would be the destination of the SNMP requests for polling the state of the input." DEFVAL { 161 } ::= { hm2IOModConfigDigOutputEntry 7 } hm2IOModConfigDigOutputSourceModID OBJECT-TYPE SYNTAX Integer32 (0..7) MAX-ACCESS read-write STATUS current DESCRIPTION "The module ID of an input mirrored to the output. Module ID 0 corresponds to the power supply module. Ignored when hm2IOModConfigDigOutputSourceIP is 0.0.0.0." DEFVAL { 1 } ::= { hm2IOModConfigDigOutputEntry 8 } hm2IOModConfigDigOutputSourceID OBJECT-TYPE SYNTAX Integer32 (1..4) MAX-ACCESS read-write STATUS current DESCRIPTION "The ID of an input mirrored to the output. Ignored when hm2IOModConfigDigOutputSourceIP is 0.0.0.0." DEFVAL { 1 } ::= { hm2IOModConfigDigOutputEntry 9 } -- ************************************************************************* -- Group Value -- ************************************************************************* hm2IOModValueGroup OBJECT IDENTIFIER ::= { hm2IOModuleMibObjects 2 } -- ************************************************************************* -- Table Digital Input Value -- ************************************************************************* hm2IOModValueDigInputTable OBJECT-TYPE SYNTAX SEQUENCE OF Hm2IOModValueDigInputEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "IO module value table for inputs" ::= { hm2IOModValueGroup 1 } hm2IOModValueDigInputEntry OBJECT-TYPE SYNTAX Hm2IOModValueDigInputEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "IO module value entry for inputs" INDEX { hm2IOModValueDigInputModID, hm2IOModValueDigInputID} ::= { hm2IOModValueDigInputTable 1 } Hm2IOModValueDigInputEntry ::= SEQUENCE { hm2IOModValueDigInputModID Integer32, hm2IOModValueDigInputID Integer32, hm2IOModValueDigInputValue INTEGER} hm2IOModValueDigInputModID OBJECT-TYPE SYNTAX Integer32 (0..7) MAX-ACCESS not-accessible STATUS current DESCRIPTION "The module ID of an input. Module ID 0 corresponds to the power supply module." ::= { hm2IOModValueDigInputEntry 1 } hm2IOModValueDigInputID OBJECT-TYPE SYNTAX Integer32 (1..4) MAX-ACCESS not-accessible STATUS current DESCRIPTION "The ID of an input." ::= { hm2IOModValueDigInputEntry 2 } hm2IOModValueDigInputValue OBJECT-TYPE SYNTAX INTEGER { not-available (0), high (1), low (2)} MAX-ACCESS read-only STATUS current DESCRIPTION "Status of the input. If the value is not-available(0), then the IO module is not plugged in, if the value is high(1), the input has high (+24V) value, if the value is low(2), the input has low (0V) value." ::= { hm2IOModValueDigInputEntry 3 } -- ************************************************************************* -- Table Digital Output Value -- ************************************************************************* hm2IOModValueDigOutputTable OBJECT-TYPE SYNTAX SEQUENCE OF Hm2IOModValueDigOutputEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "IO module value table for outputs" ::= { hm2IOModValueGroup 2 } hm2IOModValueDigOutputEntry OBJECT-TYPE SYNTAX Hm2IOModValueDigOutputEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "IO module value entry for outputs" INDEX { hm2IOModValueDigOutputModID, hm2IOModValueDigOutputID } ::= { hm2IOModValueDigOutputTable 1 } Hm2IOModValueDigOutputEntry ::= SEQUENCE { hm2IOModValueDigOutputModID Integer32, hm2IOModValueDigOutputID Integer32, hm2IOModValueDigOutputValue INTEGER} hm2IOModValueDigOutputModID OBJECT-TYPE SYNTAX Integer32 (0..7) MAX-ACCESS not-accessible STATUS current DESCRIPTION "The module ID of an Output. Module ID 0 corresponds to the power supply module." ::= { hm2IOModValueDigOutputEntry 1 } hm2IOModValueDigOutputID OBJECT-TYPE SYNTAX Integer32 (1..4) MAX-ACCESS not-accessible STATUS current DESCRIPTION "The ID of an Output." ::= { hm2IOModValueDigOutputEntry 2 } hm2IOModValueDigOutputValue OBJECT-TYPE SYNTAX INTEGER { not-available (0), high (1), low (2), invalid (3), not-configured (4)} MAX-ACCESS read-only STATUS current DESCRIPTION "Status of the output. If the value is not-available(0), then the IO module is not plugged in, if the value is high(1), the output has high (+24V) value, if the value is low(2), the output has low (0V) value. If the value is invalid (3), the output has low (0V) value and the IO input source is configured but cannot be read. If the value is not-configured (4), the output has low (0V) value and has no IO input source configured." ::= { hm2IOModValueDigOutputEntry 3 } -- ************************************************************************* -- TRAP's -- ************************************************************************* hm2IOModDigInputChangeTrap NOTIFICATION-TYPE OBJECTS { hm2IOModValueDigInputValue} STATUS current DESCRIPTION "This trap is sent if the state of an input changes. This trap is sent only when hm2IOModConfigDigInputSnmpTrap is set to enabled (1)." ::= { hm2IOModuleMibNotifications 1 } hm2IOModDigOutputChangeTrap NOTIFICATION-TYPE OBJECTS { hm2IOModValueDigOutputValue} STATUS current DESCRIPTION "This trap is sent if the state of an input changes. This trap is sent when hm2IOModConfigDigOutputSnmpTrap is set to enabled (1) or when the output value changes from or to invalid (3)." ::= { hm2IOModuleMibNotifications 2 } END