GUDEADS-PDU818X-MIB DEFINITIONS ::= BEGIN IMPORTS enterprises, MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE, Integer32, Unsigned32 FROM SNMPv2-SMI OBJECT-GROUP, NOTIFICATION-GROUP FROM SNMPv2-CONF; gudeads MODULE-IDENTITY LAST-UPDATED "200703051356Z" -- Mar 5, 2007 1:56:00 PM ORGANIZATION "Gude Analog- und Digitalsysteme GmbH" CONTACT-INFO "http://www.gudeads.com/" DESCRIPTION "" REVISION "200703051356Z" -- Mar 5, 2007 1:56:00 PM DESCRIPTION "$Id:$" -- 1.3.6.1.4.1.28507 ::= { enterprises 28507 } -- Notification Types -- events OBJECT IDENTIFIER -- 1.3.6.1.4.1.28507.35.0 ::= { gadsPDU818X 0 } pdu818XPowerIndex OBJECT-TYPE SYNTAX Integer32 (1..4) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Index of Power Channel entries" -- 1.3.6.1.4.1.28507.35.1.5.1.2.1.1 ::= { pdu818XPowerEntry 1 } pdu818XTrapIPTable OBJECT-TYPE SYNTAX SEQUENCE OF Epc8TrapIPEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "list of all Trap receiver" -- 1.3.6.1.4.1.28507.35.1.1.1.2 ::= { pdu818XSNMPaccess 2 } pdu818XCurrent OBJECT-TYPE SYNTAX Unsigned32 UNITS "mA" MAX-ACCESS read-only STATUS current DESCRIPTION "Actual Curent on Power Channel." -- 1.3.6.1.4.1.28507.35.1.5.1.2.1.5 ::= { pdu818XPowerEntry 5 } gadsPDU818X OBJECT IDENTIFIER -- 1.3.6.1.4.1.28507.35 ::= { gudeads 35 } pdu818XVoltage OBJECT-TYPE SYNTAX Unsigned32 UNITS "V" MAX-ACCESS read-only STATUS current DESCRIPTION "Actual Voltage on Power Channel" -- 1.3.6.1.4.1.28507.35.1.5.1.2.1.6 ::= { pdu818XPowerEntry 6 } pdu818XTrapIPEntry OBJECT-TYPE SYNTAX Epc8TrapIPEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "an entry containing management informations regarding the list of trap receivers" INDEX { pdu818XTrapIPIndex } -- 1.3.6.1.4.1.28507.35.1.1.1.2.1 ::= { pdu818XTrapIPTable 1 } Epc8TrapIPEntry ::= SEQUENCE { pdu818XTrapIPIndex Integer32, pdu818XTrapAddr OCTET STRING } pdu818XPowerTable OBJECT-TYPE SYNTAX SEQUENCE OF Pdu818XPowerEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "All available Channel Interfaces." -- 1.3.6.1.4.1.28507.35.1.5.1.2 ::= { pdu818XPowerChan 2 } pdu818XPowerEntry OBJECT-TYPE SYNTAX Pdu818XPowerEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "An entry containing management information applicable to a particular Power Channel." INDEX { pdu818XPowerIndex } -- 1.3.6.1.4.1.28507.35.1.5.1.2.1 ::= { pdu818XPowerTable 1 } Pdu818XPowerEntry ::= SEQUENCE { pdu818XPowerIndex Integer32, pdu818XChanStatus Integer32, pdu818XEnergyActive Unsigned32, pdu818XPowerActive Unsigned32, pdu818XCurrent Unsigned32, pdu818XVoltage Unsigned32 } pdu818XTrapIPIndex OBJECT-TYPE SYNTAX Integer32 (1..8) MAX-ACCESS not-accessible STATUS current DESCRIPTION "A unique value, greater than zero, for each receiver slot." -- 1.3.6.1.4.1.28507.35.1.1.1.2.1.1 ::= { pdu818XTrapIPEntry 1 } pdu818XDeviceConfig OBJECT IDENTIFIER -- 1.3.6.1.4.1.28507.35.1.2 ::= { pdu818XObjects 2 } pdu818XExtActors OBJECT IDENTIFIER -- 1.3.6.1.4.1.28507.35.1.4 ::= { pdu818XObjects 4 } pdu818XExtSensors OBJECT IDENTIFIER -- 1.3.6.1.4.1.28507.35.1.6 ::= { pdu818XObjects 6 } pdu818XSensorTable OBJECT-TYPE SYNTAX SEQUENCE OF Pdu818XSensorEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "" -- 1.3.6.1.4.1.28507.35.1.6.1 ::= { pdu818XExtSensors 1 } pdu818XSensorEntry OBJECT-TYPE SYNTAX Pdu818XSensorEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "" INDEX { pdu818XSensorIndex } -- 1.3.6.1.4.1.28507.35.1.6.1.1 ::= { pdu818XSensorTable 1 } Pdu818XSensorEntry ::= SEQUENCE { pdu818XSensorIndex Integer32, pdu818XTempSensor Integer32, pdu818XHygroSensor Integer32 } pdu818XPowerDataEvt1 NOTIFICATION-TYPE OBJECTS { pdu818XEnergyActive, pdu818XPowerActive, pdu818XCurrent, pdu818XVoltage} STATUS current DESCRIPTION "Event is triggered when a data for a Power Channel is incoming" -- 1.3.6.1.4.1.28507.35.0.1 ::= { events 1 } pdu818XPowerDataEvt2 NOTIFICATION-TYPE OBJECTS { pdu818XEnergyActive, pdu818XPowerActive, pdu818XCurrent, pdu818XVoltage} STATUS current DESCRIPTION "Event is triggered when a data for a Power Channel is incoming" -- 1.3.6.1.4.1.28507.35.0.2 ::= { events 2 } pdu818XPowerDataEvt3 NOTIFICATION-TYPE OBJECTS { pdu818XEnergyActive, pdu818XPowerActive, pdu818XCurrent, pdu818XVoltage} STATUS current DESCRIPTION "Event is triggered when a data for a Power Channel is incoming" -- 1.3.6.1.4.1.28507.35.0.3 ::= { events 3 } pdu818XPowerDataEvt4 NOTIFICATION-TYPE OBJECTS { pdu818XEnergyActive, pdu818XPowerActive, pdu818XCurrent, pdu818XVoltage} STATUS current DESCRIPTION "Event is triggered when a data for a Power Channel is incoming" -- 1.3.6.1.4.1.28507.35.0.4 ::= { events 4 } pdu818XSensorIndex OBJECT-TYPE SYNTAX Integer32 (1) MAX-ACCESS not-accessible STATUS current DESCRIPTION "" -- 1.3.6.1.4.1.28507.35.1.6.1.1.1 ::= { pdu818XSensorEntry 1 } pdu818XTempSensor OBJECT-TYPE SYNTAX Integer32 UNITS "10th of degree Celsius" MAX-ACCESS read-only STATUS current DESCRIPTION "actual temperature, a value of -9999 indicates that data is not available" -- 1.3.6.1.4.1.28507.35.1.6.1.1.2 ::= { pdu818XSensorEntry 2 } pdu818XHygroSensor OBJECT-TYPE SYNTAX Integer32 UNITS "10th of percentage humidity" MAX-ACCESS read-only STATUS current DESCRIPTION "actual humidity, a value of -9999 indicates that data is not available" -- 1.3.6.1.4.1.28507.35.1.6.1.1.3 ::= { pdu818XSensorEntry 3 } pdu818XSNMPaccess OBJECT IDENTIFIER -- 1.3.6.1.4.1.28507.35.1.1.1 ::= { pdu818XCommonConfig 1 } pdu818XTrapCtrl OBJECT-TYPE SYNTAX Integer32 (0..2) MAX-ACCESS read-write STATUS current DESCRIPTION "0 = off 1 = Ver. 1 2 = Ver. 2c" -- 1.3.6.1.4.1.28507.35.1.1.1.1 ::= { pdu818XSNMPaccess 1 } -- Scalars and Tables -- pdu818XObjects OBJECT IDENTIFIER -- 1.3.6.1.4.1.28507.35.1 ::= { gadsPDU818X 1 } pdu818XCommonConfig OBJECT IDENTIFIER -- 1.3.6.1.4.1.28507.35.1.1 ::= { pdu818XObjects 1 } pdu818XPowerChan OBJECT IDENTIFIER -- 1.3.6.1.4.1.28507.35.1.5.1 ::= { pdu818XIntSensors 1 } pdu818XIntActors OBJECT IDENTIFIER -- 1.3.6.1.4.1.28507.35.1.3 ::= { pdu818XObjects 3 } pdu818XChanStatus OBJECT-TYPE SYNTAX Integer32 (0..1) MAX-ACCESS read-only STATUS current DESCRIPTION "0 = data not active, 1 = data valid" -- 1.3.6.1.4.1.28507.35.1.5.1.2.1.2 ::= { pdu818XPowerEntry 2 } pdu818XActivePowerChan OBJECT-TYPE SYNTAX Unsigned32 (1..2) MAX-ACCESS read-only STATUS current DESCRIPTION "Number of suppported Power Channels." -- 1.3.6.1.4.1.28507.35.1.5.1.1 ::= { pdu818XPowerChan 1 } pdu818XEnergyActive OBJECT-TYPE SYNTAX Unsigned32 UNITS "Wh" MAX-ACCESS read-only STATUS current DESCRIPTION "Total accumulated Active Energy of Power Channel." -- 1.3.6.1.4.1.28507.35.1.5.1.2.1.3 ::= { pdu818XPowerEntry 3 } pdu818XTrapAddr OBJECT-TYPE SYNTAX OCTET STRING (SIZE (0..99)) MAX-ACCESS read-write STATUS current DESCRIPTION "DNS name or IP address specifying one Trap receiver slot. A port can optionally be specified: 'name:port' An empty string disables this slot." -- 1.3.6.1.4.1.28507.35.1.1.1.2.1.2 ::= { pdu818XTrapIPEntry 2 } pdu818XPowerActive OBJECT-TYPE SYNTAX Unsigned32 UNITS "W" MAX-ACCESS read-only STATUS current DESCRIPTION "Active Power" -- 1.3.6.1.4.1.28507.35.1.5.1.2.1.4 ::= { pdu818XPowerEntry 4 } pdu818XIntSensors OBJECT IDENTIFIER -- 1.3.6.1.4.1.28507.35.1.5 ::= { pdu818XObjects 5 } -- Conformance -- pdu818XConf OBJECT IDENTIFIER -- 1.3.6.1.4.1.28507.35.2 ::= { gadsPDU818X 2 } -- Groups -- pdu818XGroups OBJECT IDENTIFIER -- 1.3.6.1.4.1.28507.35.2.1 ::= { pdu818XConf 1 } -- Compliance -- pdu818XCompls OBJECT IDENTIFIER -- 1.3.6.1.4.1.28507.35.2.2 ::= { pdu818XConf 2 } pdu818XTempEvtSen1 NOTIFICATION-TYPE OBJECTS { pdu818XTempSensor} STATUS current DESCRIPTION "temperature limits exceeded" -- 1.3.6.1.4.1.28507.35.0.6 ::= { events 6 } pdu818XHygroEvtSen1 NOTIFICATION-TYPE OBJECTS { pdu818XHygroSensor} STATUS current DESCRIPTION "hygro limits exceeded" -- 1.3.6.1.4.1.28507.35.0.7 ::= { events 7 } pdu818XBasicGroup OBJECT-GROUP OBJECTS { pdu818XTrapCtrl, pdu818XTrapAddr, pdu818XTempSensor, pdu818XHygroSensor, pdu818XActivePowerChan, pdu818XChanStatus, pdu818XEnergyActive, pdu818XPowerActive, pdu818XCurrent, pdu818XVoltage } STATUS current DESCRIPTION "Basic objects." -- 1.3.6.1.4.1.28507.35.2.1.1 ::= { pdu818XGroups 1 } pdu818XNotificationGroup NOTIFICATION-GROUP NOTIFICATIONS { pdu818XTempEvtSen1, pdu818XHygroEvtSen1, pdu818XPowerDataEvt1, pdu818XPowerDataEvt2, pdu818XPowerDataEvt3, pdu818XPowerDataEvt4 } STATUS current DESCRIPTION "" -- 1.3.6.1.4.1.28507.35.2.1.2 ::= { pdu818XGroups 2 } END