GUDEADS-ENC2111-MIB DEFINITIONS ::= BEGIN IMPORTS enterprises, MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE, Integer32, Unsigned32 FROM SNMPv2-SMI OBJECT-GROUP, NOTIFICATION-GROUP FROM SNMPv2-CONF; gudeads MODULE-IDENTITY LAST-UPDATED "200703051356Z" -- Mar 5, 2007 1:56:00 PM ORGANIZATION "Gude Analog- und Digitalsysteme GmbH" CONTACT-INFO "http://www.gudeads.com/" DESCRIPTION "" REVISION "200703051356Z" -- Mar 5, 2007 1:56:00 PM DESCRIPTION "$Id:$" -- 1.3.6.1.4.1.28507 ::= { enterprises 28507 } enc2111POE OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "0 = no POE, 1 = POE available" MAX-ACCESS read-only STATUS current DESCRIPTION "signals POE availability" -- 1.3.6.1.4.1.28507.60.1.5.10 ::= { enc2111IntSensors 10 } gadsENC2111 OBJECT IDENTIFIER -- 1.3.6.1.4.1.28507.60 ::= { gudeads 60 } -- Notification Types -- events OBJECT IDENTIFIER -- 1.3.6.1.4.1.28507.60.3 ::= { gadsENC2111 3 } -- Scalars and Tables -- enc2111Objects OBJECT IDENTIFIER -- 1.3.6.1.4.1.28507.60.1 ::= { gadsENC2111 1 } enc2111CommonConfig OBJECT IDENTIFIER -- 1.3.6.1.4.1.28507.60.1.1 ::= { enc2111Objects 1 } enc2111SNMPaccess OBJECT IDENTIFIER -- 1.3.6.1.4.1.28507.60.1.1.1 ::= { enc2111CommonConfig 1 } enc2111TrapCtrl OBJECT-TYPE SYNTAX Integer32 (0..3) MAX-ACCESS read-write STATUS current DESCRIPTION "0 = off 1 = Ver. 1 2 = Ver. 2c 3 = Ver. 3" -- 1.3.6.1.4.1.28507.60.1.1.1.1 ::= { enc2111SNMPaccess 1 } enc2111TrapIPTable OBJECT-TYPE SYNTAX SEQUENCE OF Enc2111TrapIPEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "list of all Trap receiver" -- 1.3.6.1.4.1.28507.60.1.1.1.2 ::= { enc2111SNMPaccess 2 } enc2111TrapIPEntry OBJECT-TYPE SYNTAX Enc2111TrapIPEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "an entry containing management informations regarding the list of trap receivers" INDEX { enc2111TrapIPIndex } -- 1.3.6.1.4.1.28507.60.1.1.1.2.1 ::= { enc2111TrapIPTable 1 } Enc2111TrapIPEntry ::= SEQUENCE { enc2111TrapIPIndex Integer32, enc2111TrapAddr OCTET STRING } enc2111TrapIPIndex OBJECT-TYPE SYNTAX Integer32 (1..8) MAX-ACCESS read-only STATUS current DESCRIPTION "A unique value, greater than zero, for each receiver slot." -- 1.3.6.1.4.1.28507.60.1.1.1.2.1.1 ::= { enc2111TrapIPEntry 1 } enc2111TrapAddr OBJECT-TYPE SYNTAX OCTET STRING (SIZE (0..99)) MAX-ACCESS read-write STATUS current DESCRIPTION "DNS name or IP address specifying one Trap receiver slot. A port can optionally be specified: 'name:port' An empty string disables this slot." -- 1.3.6.1.4.1.28507.60.1.1.1.2.1.2 ::= { enc2111TrapIPEntry 2 } enc2111DeviceConfig OBJECT IDENTIFIER -- 1.3.6.1.4.1.28507.60.1.2 ::= { enc2111Objects 2 } enc2111IntActors OBJECT IDENTIFIER -- 1.3.6.1.4.1.28507.60.1.3 ::= { enc2111Objects 3 } enc2111relayports OBJECT IDENTIFIER -- 1.3.6.1.4.1.28507.60.1.3.1 ::= { enc2111IntActors 1 } enc2111portNumber OBJECT-TYPE SYNTAX Integer32 (1..12) MAX-ACCESS read-only STATUS current DESCRIPTION "The number of Relay Ports" -- 1.3.6.1.4.1.28507.60.1.3.1.1 ::= { enc2111relayports 1 } -- the Interfaces table -- The Interfaces table contains information on the entity's -- interfaces. Each sub-layer below the internetwork-layer -- of a network interface is considered to be an interface. enc2111portTable OBJECT-TYPE SYNTAX SEQUENCE OF Enc2111portEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "list of all EPC Relay Ports" -- 1.3.6.1.4.1.28507.60.1.3.1.2 ::= { enc2111relayports 2 } enc2111portEntry OBJECT-TYPE SYNTAX Enc2111portEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "An entry containing management information applicable to a particular relay port." INDEX { enc2111PortIndex } -- 1.3.6.1.4.1.28507.60.1.3.1.2.1 ::= { enc2111portTable 1 } Enc2111portEntry ::= SEQUENCE { enc2111PortIndex Integer32, enc2111PortName OCTET STRING, enc2111PortState INTEGER, enc2111PortSwitchCount Integer32, enc2111PortStartupMode INTEGER, enc2111PortStartupDelay Integer32, enc2111PortRepowerTime Integer32 } enc2111PortIndex OBJECT-TYPE SYNTAX Integer32 (1..4) MAX-ACCESS read-only STATUS current DESCRIPTION "A unique value, greater than zero, for each Relay Port." -- 1.3.6.1.4.1.28507.60.1.3.1.2.1.1 ::= { enc2111portEntry 1 } enc2111PortName OBJECT-TYPE SYNTAX OCTET STRING (SIZE (0..15)) MAX-ACCESS read-write STATUS current DESCRIPTION "A textual string containing name of a Relay Port." -- 1.3.6.1.4.1.28507.60.1.3.1.2.1.2 ::= { enc2111portEntry 2 } enc2111PortState OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } MAX-ACCESS read-write STATUS current DESCRIPTION "current state of a Relay Port" -- 1.3.6.1.4.1.28507.60.1.3.1.2.1.3 ::= { enc2111portEntry 3 } enc2111PortSwitchCount OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The total number of switch actions ocurred on a Relay Port. Does not count switch commands which will not switch the ralay state, so just real relay switches are displayed here." -- 1.3.6.1.4.1.28507.60.1.3.1.2.1.4 ::= { enc2111portEntry 4 } enc2111PortStartupMode OBJECT-TYPE SYNTAX INTEGER { off(0), on(1), laststate(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "set Mode of startup sequence (off, on , remember last state)" DEFVAL { off } -- 1.3.6.1.4.1.28507.60.1.3.1.2.1.5 ::= { enc2111portEntry 5 } enc2111PortStartupDelay OBJECT-TYPE SYNTAX Integer32 UNITS "seconds" MAX-ACCESS read-write STATUS current DESCRIPTION "Delay in sec for startup action" DEFVAL { 0 } -- 1.3.6.1.4.1.28507.60.1.3.1.2.1.6 ::= { enc2111portEntry 6 } enc2111PortRepowerTime OBJECT-TYPE SYNTAX Integer32 (0..65535) UNITS "seconds" MAX-ACCESS read-write STATUS current DESCRIPTION "Delay in sec for repower port after switching off" DEFVAL { 0 } -- 1.3.6.1.4.1.28507.60.1.3.1.2.1.7 ::= { enc2111portEntry 7 } enc2111ExtActors OBJECT IDENTIFIER -- 1.3.6.1.4.1.28507.60.1.4 ::= { enc2111Objects 4 } enc2111IntSensors OBJECT IDENTIFIER -- 1.3.6.1.4.1.28507.60.1.5 ::= { enc2111Objects 5 } enc2111VoltageInfo OBJECT IDENTIFIER -- 1.3.6.1.4.1.28507.60.1.5.7 ::= { enc2111IntSensors 7 } enc2111ExtSensors OBJECT IDENTIFIER -- 1.3.6.1.4.1.28507.60.1.6 ::= { enc2111Objects 6 } enc2111SensorTable OBJECT-TYPE SYNTAX SEQUENCE OF Enc2111SensorEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "" -- 1.3.6.1.4.1.28507.60.1.6.1 ::= { enc2111ExtSensors 1 } enc2111SensorEntry OBJECT-TYPE SYNTAX Enc2111SensorEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "" INDEX { enc2111SensorIndex } -- 1.3.6.1.4.1.28507.60.1.6.1.1 ::= { enc2111SensorTable 1 } Enc2111SensorEntry ::= SEQUENCE { enc2111SensorIndex Integer32, enc2111TempSensor Integer32, enc2111HygroSensor Integer32, enc2111InputSensor INTEGER, enc2111AirPressure Integer32, enc2111DewPoint Integer32, enc2111DewPointDiff Integer32 } enc2111SensorIndex OBJECT-TYPE SYNTAX Integer32 (1..4) MAX-ACCESS read-only STATUS current DESCRIPTION "" -- 1.3.6.1.4.1.28507.60.1.6.1.1.1 ::= { enc2111SensorEntry 1 } enc2111State3V OBJECT-TYPE SYNTAX INTEGER { on(1), error(3) } MAX-ACCESS read-only STATUS current DESCRIPTION "Show state of internal 3.3V" -- 1.3.6.1.4.1.28507.60.1.5.7.2 ::= { enc2111VoltageInfo 2 } enc2111TempSensor OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 degree Celsius" MAX-ACCESS read-only STATUS current DESCRIPTION "actual temperature" -- 1.3.6.1.4.1.28507.60.1.6.1.1.2 ::= { enc2111SensorEntry 2 } enc2111HygroSensor OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 percent humidity" MAX-ACCESS read-only STATUS current DESCRIPTION "actual humidity" -- 1.3.6.1.4.1.28507.60.1.6.1.1.3 ::= { enc2111SensorEntry 3 } enc2111InputSensor OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } MAX-ACCESS read-only STATUS current DESCRIPTION "logical state of input sensor" -- 1.3.6.1.4.1.28507.60.1.6.1.1.4 ::= { enc2111SensorEntry 4 } -- Conformance -- enc2111Conf OBJECT IDENTIFIER -- 1.3.6.1.4.1.28507.60.2 ::= { gadsENC2111 2 } -- Groups -- enc2111Groups OBJECT IDENTIFIER -- 1.3.6.1.4.1.28507.60.2.1 ::= { enc2111Conf 1 } -- Compliance -- enc2111Compls OBJECT IDENTIFIER -- 1.3.6.1.4.1.28507.60.2.2 ::= { enc2111Conf 2 } enc2111BasicGroup OBJECT-GROUP OBJECTS { enc2111TrapCtrl, enc2111TrapIPIndex, enc2111TrapAddr, enc2111portNumber, enc2111PortIndex, enc2111PortName, enc2111PortState, enc2111PortSwitchCount, enc2111PortStartupMode, enc2111PortStartupDelay, enc2111PortRepowerTime, enc2111ActiveInputs, enc2111InputIndex, enc2111Input, enc2111State12V, enc2111State3V, enc2111POE, enc2111SensorIndex, enc2111TempSensor, enc2111HygroSensor, enc2111InputSensor, enc2111AirPressure, enc2111DewPoint, enc2111DewPointDiff } STATUS current DESCRIPTION "Basic objects." -- 1.3.6.1.4.1.28507.60.2.1.1 ::= { enc2111Groups 1 } enc2111NotificationGroup NOTIFICATION-GROUP NOTIFICATIONS { enc2111SwitchEvtPort, enc2111InputEvt, enc2111TempEvtSen, enc2111HygroEvtSen, enc2111InputEvtSen, enc2111AirPressureEvtSen, enc2111DewPtDiffEvtSen, enc2111POEEvt } STATUS current DESCRIPTION "" -- 1.3.6.1.4.1.28507.60.2.1.2 ::= { enc2111Groups 2 } enc2111Inputs OBJECT IDENTIFIER -- 1.3.6.1.4.1.28507.60.1.5.6 ::= { enc2111IntSensors 6 } enc2111InputEntry OBJECT-TYPE SYNTAX Enc2111InputEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "" INDEX { enc2111InputIndex } -- 1.3.6.1.4.1.28507.60.1.5.6.2.1 ::= { enc2111InputTable 1 } Enc2111InputEntry ::= SEQUENCE { enc2111InputIndex Integer32, enc2111Input INTEGER } enc2111Input OBJECT-TYPE SYNTAX INTEGER { lo(0), hi(1) } MAX-ACCESS read-only STATUS current DESCRIPTION "Input state of device" -- 1.3.6.1.4.1.28507.60.1.5.6.2.1.2 ::= { enc2111InputEntry 2 } enc2111ActiveInputs OBJECT-TYPE SYNTAX Unsigned32 (1..12) MAX-ACCESS read-only STATUS current DESCRIPTION "Number of suppported Input Channels." -- 1.3.6.1.4.1.28507.60.1.5.6.1 ::= { enc2111Inputs 1 } enc2111InputTable OBJECT-TYPE SYNTAX SEQUENCE OF Enc2111InputEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "" -- 1.3.6.1.4.1.28507.60.1.5.6.2 ::= { enc2111Inputs 2 } enc2111InputIndex OBJECT-TYPE SYNTAX Integer32 (1..12) MAX-ACCESS read-only STATUS current DESCRIPTION "" -- 1.3.6.1.4.1.28507.60.1.5.6.2.1.1 ::= { enc2111InputEntry 1 } enc2111State12V OBJECT-TYPE SYNTAX INTEGER { off(0), low(1), high(2), error(3) } MAX-ACCESS read-only STATUS current DESCRIPTION "Show state of internal 12V" -- 1.3.6.1.4.1.28507.60.1.5.7.1 ::= { enc2111VoltageInfo 1 } enc2111AirPressure OBJECT-TYPE SYNTAX Integer32 UNITS "1 hPA (hectopascal) ~ 1 milibar" MAX-ACCESS read-only STATUS current DESCRIPTION "actual air pressure" -- 1.3.6.1.4.1.28507.60.1.6.1.1.5 ::= { enc2111SensorEntry 5 } enc2111DewPoint OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 degree Celsius" MAX-ACCESS read-only STATUS current DESCRIPTION "dew point for actual temperature and humidity" -- 1.3.6.1.4.1.28507.60.1.6.1.1.6 ::= { enc2111SensorEntry 6 } enc2111DewPointDiff OBJECT-TYPE SYNTAX Integer32 UNITS "0.1 degree Celsius" MAX-ACCESS read-only STATUS current DESCRIPTION "difference between dew point and actual temperature (Temp - DewPoint)" -- 1.3.6.1.4.1.28507.60.1.6.1.1.7 ::= { enc2111SensorEntry 7 } enc2111POEEvt NOTIFICATION-TYPE OBJECTS { enc2111POE} STATUS current DESCRIPTION "Power over Ethernet changed" -- 1.3.6.1.4.1.28507.60.3.8 ::= { events 8 } enc2111InputEvt NOTIFICATION-TYPE OBJECTS { enc2111InputIndex, enc2111Input} STATUS current DESCRIPTION "Change of device input." -- 1.3.6.1.4.1.28507.60.3.2 ::= { events 2 } enc2111HygroEvtSen NOTIFICATION-TYPE OBJECTS { enc2111SensorIndex, enc2111HygroSensor} STATUS current DESCRIPTION "hygro limits exceeded" -- 1.3.6.1.4.1.28507.60.3.4 ::= { events 4 } enc2111InputEvtSen NOTIFICATION-TYPE OBJECTS { enc2111SensorIndex, enc2111InputSensor} STATUS current DESCRIPTION "change of logical input sensor state" -- 1.3.6.1.4.1.28507.60.3.5 ::= { events 5 } enc2111AirPressureEvtSen NOTIFICATION-TYPE OBJECTS { enc2111SensorIndex, enc2111AirPressure} STATUS current DESCRIPTION "Air Pressure limits exceeded " -- 1.3.6.1.4.1.28507.60.3.6 ::= { events 6 } enc2111DewPtDiffEvtSen NOTIFICATION-TYPE OBJECTS { enc2111SensorIndex, enc2111DewPointDiff} STATUS current DESCRIPTION "Dew Point Difference limits exceeded" -- 1.3.6.1.4.1.28507.60.3.7 ::= { events 7 } enc2111TempEvtSen NOTIFICATION-TYPE OBJECTS { enc2111SensorIndex, enc2111TempSensor} STATUS current DESCRIPTION "temperature limits exceeded" -- 1.3.6.1.4.1.28507.60.3.3 ::= { events 3 } enc2111SwitchEvtPort NOTIFICATION-TYPE OBJECTS { enc2111PortIndex, enc2111PortName, enc2111PortState, enc2111PortSwitchCount} STATUS current DESCRIPTION "Event is triggered when a port is switched" -- 1.3.6.1.4.1.28507.60.3.1 ::= { events 1 } END