VERTIV-QUETZAL-MIB DEFINITIONS ::= BEGIN IMPORTS DisplayString, TEXTUAL-CONVENTION FROM SNMPv2-TC MODULE-IDENTITY, OBJECT-TYPE, enterprises, Gauge32, Integer32, Unsigned32, OBJECT-IDENTITY FROM SNMPv2-SMI; vertiv MODULE-IDENTITY LAST-UPDATED "201908300000Z" ORGANIZATION "Vertiv" CONTACT-INFO "support@geistglobal.com" DESCRIPTION "Vertiv Quetzal MIB (legacy) Note: This MIB is deprecated and will be replaced by VERTIV-V5-MIB" REVISION "201908300000Z" DESCRIPTION "Removed all pdu amps max and volts max fields" REVISION "201906060000Z" DESCRIPTION "Updated pduOutletSwitchControl description" REVISION "201801190000Z" DESCRIPTION "Changed fields in pduOutletSwitchTable to read-write, allowing for configuration of outlet delays and Power-On Actions." REVISION "201606290000Z" DESCRIPTION "MIB revisions to reflect SNMP changes for new architecture. In particular, the STATUS of all fields have been changed to deprecated." REVISION "201209210000Z" DESCRIPTION "Initial version" ::= { enterprises 21239 } DeviceSerial ::= TEXTUAL-CONVENTION STATUS deprecated DESCRIPTION "Unique serial number used to identify a device. A serial number is a string, with a length of 16. The string will only contain the characters 0 to 9, and A to F." SYNTAX OCTET STRING (SIZE (1..16)) DeviceStatus ::= TEXTUAL-CONVENTION STATUS deprecated DESCRIPTION "Indicates the condition of the device" SYNTAX INTEGER { ok(1), notFound(2), ioError(3), unknown(4), deleted(5) } DeviceLabel ::= TEXTUAL-CONVENTION STATUS deprecated DESCRIPTION "User-defined device name" SYNTAX OCTET STRING (SIZE (0..32)) TemperatureUnits ::= TEXTUAL-CONVENTION STATUS deprecated DESCRIPTION "Used to tell the units of a temperature reading" SYNTAX INTEGER { fahrenheit(1), celsius(2) } TemperatureValue ::= TEXTUAL-CONVENTION DISPLAY-HINT "d-1" STATUS deprecated DESCRIPTION "0.1 degree" SYNTAX Integer32 DeciAmps ::= TEXTUAL-CONVENTION DISPLAY-HINT "d-1" STATUS deprecated DESCRIPTION "0.1 Amps" SYNTAX Gauge32 quetzal OBJECT IDENTIFIER ::= { vertiv 6 } devices OBJECT IDENTIFIER ::= { quetzal 1 } legacyPDU OBJECT IDENTIFIER ::= { devices 99 } rtafhd3 OBJECT IDENTIFIER ::= { devices 3 } rt OBJECT IDENTIFIER ::= { devices 8 } t3hd OBJECT IDENTIFIER ::= { devices 9 } thd OBJECT IDENTIFIER ::= { devices 10 } --###########################################################################################-- --pduBaseDeltaTable-- --###########################################################################################-- pduBaseDeltaTable OBJECT-TYPE SYNTAX SEQUENCE OF PduBaseDeltaEntry MAX-ACCESS not-accessible STATUS deprecated DESCRIPTION "Base table for a delta-wired PDU. It contains general information about the PDU. Entries in sub-tables provide data for channels, groups and outlets. The system creates these sub-table entries based on hardware and configuration options, set at the factory." ::= { legacyPDU 1 } pduBaseDeltaEntry OBJECT-TYPE SYNTAX PduBaseDeltaEntry MAX-ACCESS not-accessible STATUS deprecated DESCRIPTION "Entry for a delta PDU device. This table will only have an entry if the main device is a delta-wired PDU." INDEX { pduBaseDeltaIndex } ::= { pduBaseDeltaTable 1 } PduBaseDeltaEntry ::= SEQUENCE { pduBaseDeltaIndex Unsigned32, pduBaseDeltaSerial DeviceSerial, pduBaseDeltaLabel DeviceLabel, pduBaseDeltaStatus DeviceStatus, pduBaseDeltaKWattHrsTotal Gauge32, pduBaseDeltaRealPowerTotal Gauge32, pduBaseDeltaAmpsA DeciAmps, pduBaseDeltaAmpsB DeciAmps, pduBaseDeltaAmpsC DeciAmps } pduBaseDeltaIndex OBJECT-TYPE SYNTAX Unsigned32(1..64) MAX-ACCESS not-accessible STATUS deprecated DESCRIPTION "Table entry index value" ::= { pduBaseDeltaEntry 1 } pduBaseDeltaSerial OBJECT-TYPE SYNTAX DeviceSerial MAX-ACCESS read-only STATUS deprecated DESCRIPTION "PDU's unique ID, used as a reference for channels, groups and outlets" ::= { pduBaseDeltaEntry 2 } pduBaseDeltaLabel OBJECT-TYPE SYNTAX DeviceLabel MAX-ACCESS read-write STATUS deprecated DESCRIPTION "User-defined name for the delta PDU device" ::= { pduBaseDeltaEntry 3 } pduBaseDeltaStatus OBJECT-TYPE SYNTAX DeviceStatus MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Condition of the device" ::= { pduBaseDeltaEntry 4 } pduBaseDeltaKWattHrsTotal OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Total kilowatt hours for the delta PDU" ::= { pduBaseDeltaEntry 5 } pduBaseDeltaRealPowerTotal OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Total real power for the delta PDU" ::= { pduBaseDeltaEntry 6 } pduBaseDeltaAmpsA OBJECT-TYPE SYNTAX DeciAmps MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Current reading for A" ::= { pduBaseDeltaEntry 7 } pduBaseDeltaAmpsB OBJECT-TYPE SYNTAX DeciAmps MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Current reading for B" ::= { pduBaseDeltaEntry 8 } pduBaseDeltaAmpsC OBJECT-TYPE SYNTAX DeciAmps MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Current reading for C" ::= { pduBaseDeltaEntry 9 } --###########################################################################################-- --pduBaseWyeTable-- --###########################################################################################-- pduBaseWyeTable OBJECT-TYPE SYNTAX SEQUENCE OF PduBaseWyeEntry MAX-ACCESS not-accessible STATUS deprecated DESCRIPTION "Base table for a Wye-wired PDU. It contains general information about the PDU. Entries in sub-tables provide data for channels, groups and outlets. The system creates these sub-table entries based on hardware, wiring, and configuration options, set at the factory." ::= { legacyPDU 2 } pduBaseWyeEntry OBJECT-TYPE SYNTAX PduBaseWyeEntry MAX-ACCESS not-accessible STATUS deprecated DESCRIPTION "Entry for a Wye-wired PDU device. This table will only have an entry if the PDU uses a Wye wiring." INDEX { pduBaseWyeIndex } ::= { pduBaseWyeTable 1 } PduBaseWyeEntry ::= SEQUENCE { pduBaseWyeIndex Unsigned32, pduBaseWyeSerial DeviceSerial, pduBaseWyeLabel DeviceLabel, pduBaseWyeStatus DeviceStatus, pduBaseWyeKWattHrsTotal Gauge32, pduBaseWyeRealPowerTotal Gauge32, pduBaseWyeChannelCount Unsigned32 } pduBaseWyeIndex OBJECT-TYPE SYNTAX Unsigned32(1..64) MAX-ACCESS not-accessible STATUS deprecated DESCRIPTION "Table entry index value" ::= { pduBaseWyeEntry 1 } pduBaseWyeSerial OBJECT-TYPE SYNTAX DeviceSerial MAX-ACCESS read-only STATUS deprecated DESCRIPTION "PDU's unique ID, used as a reference for channels, groups and outlets" ::= { pduBaseWyeEntry 2 } pduBaseWyeLabel OBJECT-TYPE SYNTAX DeviceLabel MAX-ACCESS read-write STATUS deprecated DESCRIPTION "User-defined name for the PDU" ::= { pduBaseWyeEntry 3 } pduBaseWyeStatus OBJECT-TYPE SYNTAX DeviceStatus MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Condition of the device" ::= { pduBaseWyeEntry 4 } pduBaseWyeKWattHrsTotal OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Total kilowatt hours for the PDU" ::= { pduBaseWyeEntry 5 } pduBaseWyeRealPowerTotal OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Total real power used by the PDU" ::= { pduBaseWyeEntry 6 } pduBaseWyeChannelCount OBJECT-TYPE SYNTAX Unsigned32(1..3) MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Count of the total number of Wye channels. Data for these channels is found in the pduChannelWyeTable." ::= { pduBaseWyeEntry 7 } --###########################################################################################-- --pduChannelDeltaTable-- --###########################################################################################-- pduChannelDeltaTable OBJECT-TYPE SYNTAX SEQUENCE OF PduChannelDeltaEntry MAX-ACCESS not-accessible STATUS deprecated DESCRIPTION "The pduChannelDeltaTable contains specific channel information for a delta PDU." ::= { legacyPDU 3 } pduChannelDeltaEntry OBJECT-TYPE SYNTAX PduChannelDeltaEntry MAX-ACCESS not-accessible STATUS deprecated DESCRIPTION "Each entry represents a delta channel. Entries are indexed by the PDU instance number and a channel id number. This table will only have entries if a corresponding delta PDU exists." INDEX { pduBaseDeltaIndex, pduChannelDeltaID } ::= { pduChannelDeltaTable 1 } PduChannelDeltaEntry ::= SEQUENCE { pduChannelDeltaID Unsigned32, pduChannelDeltaLabel DeviceLabel, pduChannelDeltaName DisplayString, pduChannelDeltaKWattHrs Gauge32, pduChannelDeltaVolts Gauge32, pduChannelDeltaRealPower Gauge32, pduChannelDeltaApparentPower Gauge32, pduChannelDeltaPowerFactor Gauge32, pduChannelDeltaAmps DeciAmps } pduChannelDeltaID OBJECT-TYPE SYNTAX Unsigned32(1..3) MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Delta channel id number" ::= { pduChannelDeltaEntry 1 } pduChannelDeltaLabel OBJECT-TYPE SYNTAX DeviceLabel MAX-ACCESS read-write STATUS deprecated DESCRIPTION "User-defined name for this channel" ::= { pduChannelDeltaEntry 2 } pduChannelDeltaName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Factory-assigned name for this channel" ::= { pduChannelDeltaEntry 3 } pduChannelDeltaKWattHrs OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Kilowatt hours for this channel" ::= { pduChannelDeltaEntry 4 } pduChannelDeltaVolts OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Volt reading" ::= { pduChannelDeltaEntry 5 } pduChannelDeltaRealPower OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Real power" ::= { pduChannelDeltaEntry 7 } pduChannelDeltaApparentPower OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Apparent Power" ::= { pduChannelDeltaEntry 8 } pduChannelDeltaPowerFactor OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Power Factor" ::= { pduChannelDeltaEntry 9 } pduChannelDeltaAmps OBJECT-TYPE SYNTAX DeciAmps MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Current reading" ::= { pduChannelDeltaEntry 10 } --###########################################################################################-- --pduChannelWyeTable-- --###########################################################################################-- pduChannelWyeTable OBJECT-TYPE SYNTAX SEQUENCE OF PduChannelWyeEntry MAX-ACCESS not-accessible STATUS deprecated DESCRIPTION "The pduChannelWyeTable contains specific channel information for a wye-wired PDU." ::= { legacyPDU 4 } pduChannelWyeEntry OBJECT-TYPE SYNTAX PduChannelWyeEntry MAX-ACCESS not-accessible STATUS deprecated DESCRIPTION "Each entry represents a wye channel. Entries are indexed by the instance number of a PDU and a channel id number. This table will only have entries if a corresponding wye-wired PDU exists." INDEX { pduBaseWyeIndex, pduChannelWyeID } ::= { pduChannelWyeTable 1 } PduChannelWyeEntry ::= SEQUENCE { pduChannelWyeID Unsigned32, pduChannelWyeLabel DeviceLabel, pduChannelWyeName DisplayString, pduChannelWyeKWattHrs Gauge32, pduChannelWyeVolts Gauge32, pduChannelWyeAmps DeciAmps, pduChannelWyeRealPower Gauge32, pduChannelWyeApparentPower Gauge32, pduChannelWyePowerFactor Gauge32 } pduChannelWyeID OBJECT-TYPE SYNTAX Unsigned32(1..3) MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Wye channel id" ::= { pduChannelWyeEntry 1 } pduChannelWyeLabel OBJECT-TYPE SYNTAX DeviceLabel MAX-ACCESS read-write STATUS deprecated DESCRIPTION "User-defined name for this channel" ::= { pduChannelWyeEntry 2 } pduChannelWyeName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Factory-assigned name for this channel" ::= { pduChannelWyeEntry 3 } pduChannelWyeKWattHrs OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Kilowatt hours" ::= { pduChannelWyeEntry 4 } pduChannelWyeVolts OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Volt reading" ::= { pduChannelWyeEntry 5 } pduChannelWyeAmps OBJECT-TYPE SYNTAX DeciAmps MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Current reading" ::= { pduChannelWyeEntry 7 } pduChannelWyeRealPower OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Real power" ::= { pduChannelWyeEntry 9 } pduChannelWyeApparentPower OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Apparent power" ::= { pduChannelWyeEntry 10 } pduChannelWyePowerFactor OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Power factor" ::= { pduChannelWyeEntry 11 } --###########################################################################################-- --pduGroupTable-- --###########################################################################################-- pduGroupTable OBJECT-TYPE SYNTAX SEQUENCE OF PduGroupEntry MAX-ACCESS not-accessible STATUS deprecated DESCRIPTION "Contains meter readings per outlet group" ::= { legacyPDU 5 } pduGroupEntry OBJECT-TYPE SYNTAX PduGroupEntry MAX-ACCESS not-accessible STATUS deprecated DESCRIPTION "Each entry represents an outlet group for a specific PDU. Groups are indexed by a PDU instance number and a group id number. The pduGroupIndex corresponds to a matching instance number in a base PDU table. For group entries to exist, a PDU that supports groups must also exist." INDEX { pduGroupIndex, pduGroupID } ::= { pduGroupTable 1 } PduGroupEntry ::= SEQUENCE { pduGroupIndex Unsigned32, pduGroupSerial DeviceSerial, pduGroupID Unsigned32, pduGroupLabel DeviceLabel, pduGroupName DisplayString, pduGroupAmps DeciAmps, pduGroupApparentPower Gauge32, pduGroupPowerFactor Gauge32, pduGroupRealPower Gauge32, pduGroupVolts Gauge32, pduGroupWattHours Gauge32 } pduGroupIndex OBJECT-TYPE SYNTAX Unsigned32(1..64) MAX-ACCESS not-accessible STATUS deprecated DESCRIPTION "Table entry index value" ::= { pduGroupEntry 1 } pduGroupSerial OBJECT-TYPE SYNTAX DeviceSerial MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Serial number of an existing base PDU" ::= { pduGroupEntry 2 } pduGroupID OBJECT-TYPE SYNTAX Unsigned32(1..8) MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Group id number" ::= { pduGroupEntry 3 } pduGroupLabel OBJECT-TYPE SYNTAX DeviceLabel MAX-ACCESS read-write STATUS deprecated DESCRIPTION "User-defined name for this group" ::= { pduGroupEntry 4 } pduGroupName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Factory-assigned name for this group" ::= { pduGroupEntry 5 } pduGroupAmps OBJECT-TYPE SYNTAX DeciAmps MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Total amps for outlet group" ::= { pduGroupEntry 6 } pduGroupApparentPower OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Total apparent-power for outlet group" ::= { pduGroupEntry 8 } pduGroupPowerFactor OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Total power-factor for outlet group" ::= { pduGroupEntry 9 } pduGroupRealPower OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Total real-power for outlet group" ::= { pduGroupEntry 10 } pduGroupVolts OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Volts reading for outlet group" ::= { pduGroupEntry 11 } pduGroupWattHours OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Watt-hours reading for outlet group" ::= { pduGroupEntry 13 } --###########################################################################################-- --pduOutletMainTable-- --###########################################################################################-- pduOutletMainTable OBJECT-TYPE SYNTAX SEQUENCE OF PduOutletMainEntry MAX-ACCESS not-accessible STATUS deprecated DESCRIPTION "Outlet data common to all outlet types. Other tables provide additional data, based on the outlet type." ::= { legacyPDU 6 } pduOutletMainEntry OBJECT-TYPE SYNTAX PduOutletMainEntry MAX-ACCESS not-accessible STATUS deprecated DESCRIPTION "One entry per outlet. Each entry corresponds to an outlet on a PDU, so they are indexed by the PDU's instance number and an outlet id number. The pduOutletMainIndex corresponds to an instance number for an existing PDU." INDEX { pduOutletMainIndex, pduOutletMainID } ::= { pduOutletMainTable 1 } PduOutletMainEntry ::= SEQUENCE { pduOutletMainIndex Unsigned32, pduOutletMainSerial DeviceSerial, pduOutletMainID Unsigned32, pduOutletMainLabel DeviceLabel, pduOutletMainName DisplayString, pduOutletMainGroup DisplayString, pduOutletMainURL DisplayString } pduOutletMainIndex OBJECT-TYPE SYNTAX Unsigned32(1..64) MAX-ACCESS not-accessible STATUS deprecated DESCRIPTION "Table entry index value" ::= { pduOutletMainEntry 1 } pduOutletMainSerial OBJECT-TYPE SYNTAX DeviceSerial MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Serial number of an existing PDU device" ::= { pduOutletMainEntry 2 } pduOutletMainID OBJECT-TYPE SYNTAX Unsigned32(1..64) MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Outlet id number" ::= { pduOutletMainEntry 3 } pduOutletMainLabel OBJECT-TYPE SYNTAX DeviceLabel MAX-ACCESS read-write STATUS deprecated DESCRIPTION "User-defined outlet name" ::= { pduOutletMainEntry 4 } pduOutletMainName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Factory-assigned outlet name" ::= { pduOutletMainEntry 5 } pduOutletMainGroup OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Outlet's group name" ::= { pduOutletMainEntry 6 } pduOutletMainURL OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Link info for outlet" ::= { pduOutletMainEntry 7 } --###########################################################################################-- --pduOutletSwitchTable-- --###########################################################################################-- pduOutletSwitchTable OBJECT-TYPE SYNTAX SEQUENCE OF PduOutletSwitchEntry MAX-ACCESS not-accessible STATUS deprecated DESCRIPTION "Contains entries for outlets that support switching. This table supplements the corresponding entries in pduOutletMainTable." ::= { legacyPDU 7 } pduOutletSwitchEntry OBJECT-TYPE SYNTAX PduOutletSwitchEntry MAX-ACCESS not-accessible STATUS deprecated DESCRIPTION "One entry is created per switching outlet. These entries correspond to an outlet entry in pduOutletMainTable. Each entry in this table uses the index and outlet id from the pduOutletMainTable." INDEX { pduOutletMainIndex, pduOutletMainID } ::= { pduOutletSwitchTable 1 } PduOutletSwitchEntry ::= SEQUENCE { pduOutletSwitchState INTEGER, pduOutletSwitchStateChangeTime Unsigned32, pduOutletSwitchCurrentAction INTEGER, pduOutletSwitchOnDelay Unsigned32, pduOutletSwitchOffDelay Unsigned32, pduOutletSwitchRebootDelay Unsigned32, pduOutletSwitchRebootHold Unsigned32, pduOutletSwitchStartupAction INTEGER, pduOutletSwitchStartupStateDelay Unsigned32, pduOutletSwitchControl INTEGER } pduOutletSwitchState OBJECT-TYPE SYNTAX INTEGER { outletOff(0), outletOn(1), outletError(2) } MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Switch state of the outlet" ::= { pduOutletSwitchEntry 1 } pduOutletSwitchStateChangeTime OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Seconds until an action will occur" ::= { pduOutletSwitchEntry 2 } pduOutletSwitchCurrentAction OBJECT-TYPE SYNTAX INTEGER { manual(1), reboot(2), startUp(3), other(4) } MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Outlet action in progress" ::= { pduOutletSwitchEntry 3 } pduOutletSwitchOnDelay OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS read-write STATUS deprecated DESCRIPTION "Delay used in turning the outlet on" ::= { pduOutletSwitchEntry 4 } pduOutletSwitchOffDelay OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS read-write STATUS deprecated DESCRIPTION "Delay used in turning the outlet off" ::= { pduOutletSwitchEntry 5 } pduOutletSwitchRebootDelay OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS read-write STATUS deprecated DESCRIPTION "Delay used prior to outlet reboot" ::= { pduOutletSwitchEntry 6 } pduOutletSwitchRebootHold OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS read-write STATUS deprecated DESCRIPTION "Time the outlet is kept off during a reboot" ::= { pduOutletSwitchEntry 7 } pduOutletSwitchStartupAction OBJECT-TYPE SYNTAX INTEGER { startOff(0), startOn(1), lastKnown(2) } MAX-ACCESS read-write STATUS deprecated DESCRIPTION "State the outlet should take at startup (first powered)" ::= { pduOutletSwitchEntry 8 } pduOutletSwitchStartupStateDelay OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS read-write STATUS deprecated DESCRIPTION "Delay from startup before the outlet changes to the StartupAction" ::= { pduOutletSwitchEntry 9 } pduOutletSwitchControl OBJECT-TYPE SYNTAX INTEGER { none(0), cancelActions(1), onNoDelay(2), onDelay(3), offNoDelay(4), offDelay(5), rebootNoDelay(6), rebootDelay(7) } MAX-ACCESS read-write STATUS deprecated DESCRIPTION "Used for manual control of the outlet. The default is none(0). When set, it keeps this value until the operation is complete. Then the value goes back to none(0). Outlet must be in manual mode to set, otherwise it causes an inconsistentValue error. Can be set to one of the following: 1 = Cancel pending action 2 = Turn outlet on without delay 3 = After delay, turn outlet on 4 = Turn outlet off without delay 5 = After delay, turn outlet off 6 = Reboot outlet without delay 7 = After delay, reboot outlet" ::= { pduOutletSwitchEntry 10 } --###########################################################################################-- --pduOutletMeterTable-- --###########################################################################################-- pduOutletMeterTable OBJECT-TYPE SYNTAX SEQUENCE OF PduOutletMeterEntry MAX-ACCESS not-accessible STATUS deprecated DESCRIPTION "Contains entries for outlets that support metering. This table supplements the corresponding entries in pduOutletMainTable." ::= { legacyPDU 8 } pduOutletMeterEntry OBJECT-TYPE SYNTAX PduOutletMeterEntry MAX-ACCESS not-accessible STATUS deprecated DESCRIPTION "One entry is created per metering outlet. These entries correspond to an outlet entry in pduOutletMainTable. Each entry in this table uses the index and outlet id from the pduOutletMainTable." INDEX { pduOutletMainIndex, pduOutletMainID } ::= { pduOutletMeterTable 1 } PduOutletMeterEntry ::= SEQUENCE { pduOutletMeterKWattHrs Gauge32, pduOutletMeterAmps DeciAmps, pduOutletMeterPower Gauge32 } pduOutletMeterKWattHrs OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Kilowatt hours for outlet" ::= { pduOutletMeterEntry 1 } pduOutletMeterAmps OBJECT-TYPE SYNTAX DeciAmps MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Current reading for outlet" ::= { pduOutletMeterEntry 2 } pduOutletMeterPower OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Power measurement for outlet" ::= { pduOutletMeterEntry 3 } --###########################################################################################-- --rtafhd3Table-- --###########################################################################################-- rtafhd3Table OBJECT-TYPE SYNTAX SEQUENCE OF Rtafhd3Entry MAX-ACCESS not-accessible STATUS deprecated DESCRIPTION "Combo airflow, temp, humidity and dewpoint sensor" ::= { rtafhd3 1 } rtafhd3Entry OBJECT-TYPE SYNTAX Rtafhd3Entry MAX-ACCESS not-accessible STATUS deprecated DESCRIPTION "One entry per device. Indexed by an instance number." INDEX { rtafhd3Index } ::= { rtafhd3Table 1 } Rtafhd3Entry ::= SEQUENCE { rtafhd3Index Unsigned32, rtafhd3Serial DeviceSerial, rtafhd3Label DeviceLabel, rtafhd3Status DeviceStatus, rtafhd3Airflow Gauge32, rtafhd3Humidity Gauge32, rtafhd3Temp TemperatureValue, rtafhd3DewPoint TemperatureValue, rtafhd3TDUnits TemperatureUnits } rtafhd3Index OBJECT-TYPE SYNTAX Unsigned32(1..64) MAX-ACCESS not-accessible STATUS deprecated DESCRIPTION "Table entry index value" ::= { rtafhd3Entry 1 } rtafhd3Serial OBJECT-TYPE SYNTAX DeviceSerial MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Unique device id" ::= { rtafhd3Entry 2 } rtafhd3Label OBJECT-TYPE SYNTAX DeviceLabel MAX-ACCESS read-write STATUS deprecated DESCRIPTION "User-defined name" ::= { rtafhd3Entry 3 } rtafhd3Status OBJECT-TYPE SYNTAX DeviceStatus MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Sensor condition" ::= { rtafhd3Entry 4 } rtafhd3Airflow OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Airflow reading" ::= { rtafhd3Entry 5 } rtafhd3Humidity OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Humidity reading" ::= { rtafhd3Entry 6 } rtafhd3Temp OBJECT-TYPE SYNTAX TemperatureValue MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Temperature reading in units indicated by rtafhd3TDUnits." ::= { rtafhd3Entry 7 } rtafhd3DewPoint OBJECT-TYPE SYNTAX TemperatureValue MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Dewpoint reading in units indicated by rtafhd3TDUnits." ::= { rtafhd3Entry 8 } rtafhd3TDUnits OBJECT-TYPE SYNTAX TemperatureUnits MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Tells what units are used for temperature and dewpoint." ::= { rtafhd3Entry 9 } --###########################################################################################-- --rtTable-- --###########################################################################################-- rtTable OBJECT-TYPE SYNTAX SEQUENCE OF RtEntry MAX-ACCESS not-accessible STATUS deprecated DESCRIPTION "Contains entries for remote temperature devices" ::= { rt 1 } rtEntry OBJECT-TYPE SYNTAX RtEntry MAX-ACCESS not-accessible STATUS deprecated DESCRIPTION "One entry per device. Indexed by an instance number." INDEX { rtIndex } ::= { rtTable 1 } RtEntry ::= SEQUENCE { rtIndex Unsigned32, rtSerial DeviceSerial, rtLabel DeviceLabel, rtStatus DeviceStatus, rtTemp TemperatureValue, rtUnits TemperatureUnits } rtIndex OBJECT-TYPE SYNTAX Unsigned32(1..64) MAX-ACCESS not-accessible STATUS deprecated DESCRIPTION "Table entry index value" ::= { rtEntry 1 } rtSerial OBJECT-TYPE SYNTAX DeviceSerial MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Unique device id" ::= { rtEntry 2 } rtLabel OBJECT-TYPE SYNTAX DeviceLabel MAX-ACCESS read-write STATUS deprecated DESCRIPTION "User-defined name" ::= { rtEntry 3 } rtStatus OBJECT-TYPE SYNTAX DeviceStatus MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Device condition" ::= { rtEntry 4 } rtTemp OBJECT-TYPE SYNTAX TemperatureValue MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Temperature reading. The units for this measurement are given by rtUnits." ::= { rtEntry 5 } rtUnits OBJECT-TYPE SYNTAX TemperatureUnits MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Indicates what units rtTemp will be given in." ::= { rtEntry 6 } --###########################################################################################-- --t3hdTable-- --###########################################################################################-- t3hdTable OBJECT-TYPE SYNTAX SEQUENCE OF T3hdEntry MAX-ACCESS not-accessible STATUS deprecated DESCRIPTION "Contains entries for T3HD devices" ::= { t3hd 1 } t3hdEntry OBJECT-TYPE SYNTAX T3hdEntry MAX-ACCESS not-accessible STATUS deprecated DESCRIPTION "Each entry represents a T3HD device. They are indexed by an instance number." INDEX { t3hdIndex } ::= { t3hdTable 1 } T3hdEntry ::= SEQUENCE { t3hdIndex Unsigned32, t3hdSerial DeviceSerial, t3hdLabel DeviceLabel, t3hdStatus DeviceStatus, t3hdMainLabel DeviceLabel, t3hdMainTemp TemperatureValue, t3hdMainHumidity Gauge32, t3hdMainDewPoint TemperatureValue, t3hdExt1Status INTEGER, t3hdExt1Label DeviceLabel, t3hdExt1Temp TemperatureValue, t3hdExt2Status INTEGER, t3hdExt2Label DeviceLabel, t3hdExt2Temp TemperatureValue, t3hdTDUnits TemperatureUnits } t3hdIndex OBJECT-TYPE SYNTAX Unsigned32(1..64) MAX-ACCESS not-accessible STATUS deprecated DESCRIPTION "Table entry index value" ::= { t3hdEntry 1 } t3hdSerial OBJECT-TYPE SYNTAX DeviceSerial MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Unique device id" ::= { t3hdEntry 2 } t3hdLabel OBJECT-TYPE SYNTAX DeviceLabel MAX-ACCESS read-write STATUS deprecated DESCRIPTION "User-defined name" ::= { t3hdEntry 3 } t3hdStatus OBJECT-TYPE SYNTAX DeviceStatus MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Device condition" ::= { t3hdEntry 4 } t3hdMainLabel OBJECT-TYPE SYNTAX DeviceLabel MAX-ACCESS read-write STATUS deprecated DESCRIPTION "User-defined label for measurements from the main device" ::= { t3hdEntry 5 } t3hdMainTemp OBJECT-TYPE SYNTAX TemperatureValue MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Temperature reading from the main device" ::= { t3hdEntry 6 } t3hdMainHumidity OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Humidity reading from the main device" ::= { t3hdEntry 7 } t3hdMainDewPoint OBJECT-TYPE SYNTAX TemperatureValue MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Dew Point value from the main device" ::= { t3hdEntry 8 } t3hdExt1Status OBJECT-TYPE SYNTAX INTEGER { unplugged(0), normal(1), error(2) } MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Sensor status for external temp 1. The status is one of the following values: 0 = Sensor unplugged 1 = Normal operation 2 = Sensor error" ::= { t3hdEntry 9 } t3hdExt1Label OBJECT-TYPE SYNTAX DeviceLabel MAX-ACCESS read-write STATUS deprecated DESCRIPTION "User-defined name for external temp 1" ::= { t3hdEntry 10 } t3hdExt1Temp OBJECT-TYPE SYNTAX TemperatureValue MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Temperature reading from external temp 1" ::= { t3hdEntry 11 } t3hdExt2Status OBJECT-TYPE SYNTAX INTEGER { unplugged(0), normal(1), error(2) } MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Sensor status for external temp 2. The status is one of the following values: 0 = Sensor unplugged 1 = Normal operation 2 = Sensor error" ::= { t3hdEntry 12 } t3hdExt2Label OBJECT-TYPE SYNTAX DeviceLabel MAX-ACCESS read-write STATUS deprecated DESCRIPTION "User-defined name for external temp 2" ::= { t3hdEntry 13 } t3hdExt2Temp OBJECT-TYPE SYNTAX TemperatureValue MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Temperature reading from external temp 2" ::= { t3hdEntry 14 } t3hdTDUnits OBJECT-TYPE SYNTAX TemperatureUnits MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Tells what units are used for temperatures and dewpoint." ::= { t3hdEntry 15 } --###########################################################################################-- --thdTable-- --###########################################################################################-- thdTable OBJECT-TYPE SYNTAX SEQUENCE OF ThdEntry MAX-ACCESS not-accessible STATUS deprecated DESCRIPTION "Contains entries for THD devices" ::= { thd 1 } thdEntry OBJECT-TYPE SYNTAX ThdEntry MAX-ACCESS not-accessible STATUS deprecated DESCRIPTION "Each entry represents a THD device. They are indexed by an instance number." INDEX { thdIndex } ::= { thdTable 1 } ThdEntry ::= SEQUENCE { thdIndex Unsigned32, thdSerial DeviceSerial, thdLabel DeviceLabel, thdStatus DeviceStatus, thdTemp TemperatureValue, thdHumidity Gauge32, thdDewPoint TemperatureValue, thdTDUnits TemperatureUnits } thdIndex OBJECT-TYPE SYNTAX Unsigned32(1..64) MAX-ACCESS not-accessible STATUS deprecated DESCRIPTION "Table entry index value" ::= { thdEntry 1 } thdSerial OBJECT-TYPE SYNTAX DeviceSerial MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Unique device id" ::= { thdEntry 2 } thdLabel OBJECT-TYPE SYNTAX DeviceLabel MAX-ACCESS read-write STATUS deprecated DESCRIPTION "User-defined name" ::= { thdEntry 3 } thdStatus OBJECT-TYPE SYNTAX DeviceStatus MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Device condition" ::= { thdEntry 4 } thdTemp OBJECT-TYPE SYNTAX TemperatureValue MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Temperature reading" ::= { thdEntry 5 } thdHumidity OBJECT-TYPE SYNTAX Gauge32 MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Humidity reading" ::= { thdEntry 6 } thdDewPoint OBJECT-TYPE SYNTAX TemperatureValue MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Dew Point value" ::= { thdEntry 7 } thdTDUnits OBJECT-TYPE SYNTAX TemperatureUnits MAX-ACCESS read-only STATUS deprecated DESCRIPTION "Units used for temperature and dew point." ::= { thdEntry 8 } --###########################################################################################-- --common group-- --###########################################################################################-- common OBJECT IDENTIFIER ::= { vertiv 42 } identity OBJECT IDENTIFIER ::= { common 1 } r05 OBJECT-IDENTITY STATUS current DESCRIPTION "Value given for sysObjectID on R-Series units" ::= { identity 15 } i03 OBJECT-IDENTITY STATUS current DESCRIPTION "Value given for sysObjectID on IMD3 units" ::= { identity 53 } END