----------------------------------------------------------------------- -- MIB table for H4531 -- -- v1.0 for firmware 9-5-0-0, 2017-04-19 ----------------------------------------------------------------------- H4531-MIB DEFINITIONS ::= BEGIN IMPORTS enterprises FROM RFC1155-SMI OBJECT-TYPE FROM RFC-1212 TRAP-TYPE FROM RFC-1215; DisplayString ::= OCTET STRING comet OBJECT IDENTIFIER ::= { enterprises 22626 } products OBJECT IDENTIFIER ::= { comet 1 } h4531 OBJECT IDENTIFIER ::= { products 2 } values OBJECT IDENTIFIER ::= { h4531 1 } global OBJECT IDENTIFIER ::= { h4531 2 } valuesInt OBJECT IDENTIFIER ::= { h4531 3 } settings OBJECT IDENTIFIER ::= { h4531 4 } traps OBJECT IDENTIFIER ::= { h4531 5 } tables OBJECT IDENTIFIER ::= { h4531 6 } ----------------------------------------------------------------------- -- Measured values - String ----------------------------------------------------------------------- temp OBJECT-TYPE SYNTAX DisplayString (SIZE (0..8)) ACCESS read-only STATUS mandatory DESCRIPTION "Temperature" ::= { values 1 } bin1 OBJECT-TYPE SYNTAX DisplayString (SIZE (0..8)) ACCESS read-only STATUS mandatory DESCRIPTION "BIN Input 1 state; 0 state description, 1 state description" ::= { values 5 } bin2 OBJECT-TYPE SYNTAX DisplayString (SIZE (0..8)) ACCESS read-only STATUS mandatory DESCRIPTION "BIN Input 2 state; 0 state description, 1 state description" ::= { values 6 } bin3 OBJECT-TYPE SYNTAX DisplayString (SIZE (0..8)) ACCESS read-only STATUS mandatory DESCRIPTION "BIN Input 3 state; 0 state description, 1 state description" ::= { values 7 } re1 OBJECT-TYPE SYNTAX DisplayString (SIZE (0..8)) ACCESS read-only STATUS mandatory DESCRIPTION "Relay 1 state; open, closed" ::= { values 8 } re2 OBJECT-TYPE SYNTAX DisplayString (SIZE (0..8)) ACCESS read-only STATUS mandatory DESCRIPTION "Relay 2 state; open, closed" ::= { values 9 } tempAlarm1 OBJECT-TYPE SYNTAX DisplayString (SIZE (0..8)) ACCESS read-only STATUS mandatory DESCRIPTION "Alarm1 on Temperature; none, active" ::= { values 10 } tempAlarm2 OBJECT-TYPE SYNTAX DisplayString (SIZE (0..8)) ACCESS read-only STATUS mandatory DESCRIPTION "Alarm2 on Temperature; none, active" ::= { values 14 } bin1Alarm OBJECT-TYPE SYNTAX DisplayString (SIZE (0..8)) ACCESS read-only STATUS mandatory DESCRIPTION "Alarm on BIN Input 1; none, active" ::= { values 18 } bin2Alarm OBJECT-TYPE SYNTAX DisplayString (SIZE (0..8)) ACCESS read-only STATUS mandatory DESCRIPTION "Alarm on BIN Input 2; none, active" ::= { values 19 } bin3Alarm OBJECT-TYPE SYNTAX DisplayString (SIZE (0..8)) ACCESS read-only STATUS mandatory DESCRIPTION "Alarm on BIN Input 3; none, active" ::= { values 20 } tempUnit OBJECT-TYPE SYNTAX DisplayString (SIZE (0..8)) ACCESS read-only STATUS mandatory DESCRIPTION "Temperature Unit" ::= { values 21 } ----------------------------------------------------------------------- -- Device informations ----------------------------------------------------------------------- sensorName OBJECT-TYPE SYNTAX DisplayString (SIZE (0..68)) ACCESS read-only STATUS mandatory DESCRIPTION "Device name" ::= { global 1 } serialNumber OBJECT-TYPE SYNTAX DisplayString (SIZE (0..16)) ACCESS read-only STATUS mandatory DESCRIPTION "Serial number" ::= { global 2 } deviceType OBJECT-TYPE SYNTAX INTEGER (0..65534) ACCESS read-only STATUS mandatory DESCRIPTION "Device type" ::= { global 3 } ----------------------------------------------------------------------- -- Measured values - Integer ----------------------------------------------------------------------- tempInt OBJECT-TYPE SYNTAX INTEGER (-5000..20000) ACCESS read-only STATUS mandatory DESCRIPTION "Temperature (value*10)" ::= { valuesInt 1 } bin1Int OBJECT-TYPE SYNTAX INTEGER (0..1) ACCESS read-only STATUS mandatory DESCRIPTION "BIN Input 1 state" ::= { valuesInt 5 } bin2Int OBJECT-TYPE SYNTAX INTEGER (0..1) ACCESS read-only STATUS mandatory DESCRIPTION "BIN Input 2 state" ::= { valuesInt 6 } bin3Int OBJECT-TYPE SYNTAX INTEGER (0..1) ACCESS read-only STATUS mandatory DESCRIPTION "BIN Input 3 state" ::= { valuesInt 7 } re1Int OBJECT-TYPE SYNTAX INTEGER (0..1) ACCESS read-only STATUS mandatory DESCRIPTION "Relay 1 state" ::= { valuesInt 8 } re2Int OBJECT-TYPE SYNTAX INTEGER (0..1) ACCESS read-only STATUS mandatory DESCRIPTION "Relay 2 state" ::= { valuesInt 9 } tempAlarm1Int OBJECT-TYPE SYNTAX INTEGER (0..1) ACCESS read-only STATUS mandatory DESCRIPTION "Alarm1 on Temperature" ::= { valuesInt 10 } tempAlarm2Int OBJECT-TYPE SYNTAX INTEGER (0..1) ACCESS read-only STATUS mandatory DESCRIPTION "Alarm2 on Temperature" ::= { valuesInt 14 } bin1AlarmInt OBJECT-TYPE SYNTAX INTEGER (0..1) ACCESS read-only STATUS mandatory DESCRIPTION "Alarm on BIN Input 1" ::= { valuesInt 18 } bin2AlarmInt OBJECT-TYPE SYNTAX INTEGER (0..1) ACCESS read-only STATUS mandatory DESCRIPTION "Alarm on BIN Input 2" ::= { valuesInt 19 } bin3AlarmInt OBJECT-TYPE SYNTAX INTEGER (0..1) ACCESS read-only STATUS mandatory DESCRIPTION "Alarm on BIN Input 3" ::= { valuesInt 20 } ----------------------------------------------------------------------- -- Alarm settings ----------------------------------------------------------------------- tempLim1Int OBJECT-TYPE SYNTAX INTEGER (-5000..20000) ACCESS read-only STATUS mandatory DESCRIPTION "Temperature Alarm1 Limit (value*10)" ::= { settings 1 } tempLim2Int OBJECT-TYPE SYNTAX INTEGER (-5000..20000) ACCESS read-only STATUS mandatory DESCRIPTION "Temperature Alarm2 Limit (value*10)" ::= { settings 5 } tempHyst1Int OBJECT-TYPE SYNTAX INTEGER (0..10000) ACCESS read-only STATUS mandatory DESCRIPTION "Temperature Alarm1 Hysteresis (value*10)" ::= { settings 9 } tempHyst2Int OBJECT-TYPE SYNTAX INTEGER (0..10000) ACCESS read-only STATUS mandatory DESCRIPTION "Temperature Alarm2 Hysteresis (value*10)" ::= { settings 13 } tempDelay1Int OBJECT-TYPE SYNTAX INTEGER (0..30000) ACCESS read-only STATUS mandatory DESCRIPTION "Temperature Alarm1 Delay [sec]" ::= { settings 17 } tempDelay2Int OBJECT-TYPE SYNTAX INTEGER (0..30000) ACCESS read-only STATUS mandatory DESCRIPTION "Temperature Alarm2 Delay [sec]" ::= { settings 21 } tempType1Int OBJECT-TYPE SYNTAX INTEGER (0..2) ACCESS read-only STATUS mandatory DESCRIPTION "Temperature Alarm1 Type; 0-disbaled, 1-low, 2-high" ::= { settings 25 } tempType2Int OBJECT-TYPE SYNTAX INTEGER (0..2) ACCESS read-only STATUS mandatory DESCRIPTION "Temperature Alarm2 Type; 0-disbaled, 1-low, 2-high" ::= { settings 29 } bin1DelayInt OBJECT-TYPE SYNTAX INTEGER (0..30000) ACCESS read-only STATUS mandatory DESCRIPTION "BIN Input 1 Delay [sec]" ::= { settings 33 } bin2DelayInt OBJECT-TYPE SYNTAX INTEGER (0..30000) ACCESS read-only STATUS mandatory DESCRIPTION "BIN Input 2 Delay [sec]" ::= { settings 34 } bin3DelayInt OBJECT-TYPE SYNTAX INTEGER (0..30000) ACCESS read-only STATUS mandatory DESCRIPTION "BIN Input 3 Delay [sec]" ::= { settings 35 } bin1TypeInt OBJECT-TYPE SYNTAX INTEGER (0..2) ACCESS read-only STATUS mandatory DESCRIPTION "BIN Input 1 Type; 0-disbaled, 1-low state, 2-high state" ::= { settings 36 } bin2TypeInt OBJECT-TYPE SYNTAX INTEGER (0..2) ACCESS read-only STATUS mandatory DESCRIPTION "BIN Input 2 Type; 0-disbaled, 1-low state, 2-high state" ::= { settings 37 } bin3TypeInt OBJECT-TYPE SYNTAX INTEGER (0..2) ACCESS read-only STATUS mandatory DESCRIPTION "BIN Input 3 Type; 0-disbaled, 1-low state, 2-high state" ::= { settings 38 } ----------------------------------------------------------------------- -- Trap message ----------------------------------------------------------------------- messageString OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "Message giving more detailed information on trap" ::= { traps 1 } ----------------------------------------------------------------------- -- Tables ----------------------------------------------------------------------- historyTable OBJECT-TYPE SYNTAX SEQUENCE OF HistoryEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Table of the history values" ::= { tables 1 } historyEntry OBJECT-TYPE SYNTAX HistoryEntry ACCESS not-accessible STATUS optional DESCRIPTION "History values entries" INDEX { histTemp } ::= { historyTable 1 } HistoryEntry ::= SEQUENCE { histTemp INTEGER } histTemp OBJECT-TYPE SYNTAX INTEGER(-5000..20000) ACCESS read-only STATUS mandatory DESCRIPTION "Temperature reading" ::= { historyEntry 1 } ----------------------------------------------------------------------- -- Traps definition ----------------------------------------------------------------------- trapTest TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString } DESCRIPTION "Testing trap, testing trap by TSensor software" ::= 0 trapNTPError TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString } DESCRIPTION "Error on time synchronisation via NTP" ::= 1 trapEmailErrLogin TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString } DESCRIPTION "SMTP error - unknown server" ::= 2 trapEmailErrAuth TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString } DESCRIPTION "SMTP error - authentication error" ::= 3 trapEmailErrSome TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString } DESCRIPTION "SMTP error - error during communication with server, unexpected return code" ::= 4 trapEmailErrSocket TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString } DESCRIPTION "SMTP error - socket error, server is not available" ::= 5 trapEmailErrDNS TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString } DESCRIPTION "SMTP error - DNS error" ::= 6 trapSOAPErrFile TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString } DESCRIPTION "SOAP error - file SOAP not found" ::= 7 trapSOAPErrDNS TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString } DESCRIPTION "SOAP error - DNS error" ::= 8 trapSOAPErrSocket TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString } DESCRIPTION "SOAP error - socket error, server is not available" ::= 9 trapSOAPErrDelivery TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString } DESCRIPTION "SOAP error - delivery error, wrong return code from server" ::= 10 trapTempAlarm1 TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString, temp, tempAlarm1Int } DESCRIPTION "Trap for alarm1 on Temperature" ::= 11 trapTempAlarm2 TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString, temp, tempAlarm2Int } DESCRIPTION "Trap for alarm2 on Temperature" ::= 21 trapTempClrAlarm1 TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString, temp, tempAlarm1Int } DESCRIPTION "Trap for clearing alarm 1 on Temperature" ::= 31 trapTempClrAlarm2 TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString, temp, tempAlarm2Int } DESCRIPTION "Trap for clearing alarm 2 on Temperature" ::= 41 trapBin1Alarm TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString, bin1Int, bin1AlarmInt } DESCRIPTION "Trap for alarm on BIN Input 1" ::= 51 trapBin2Alarm TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString, bin2Int, bin2AlarmInt } DESCRIPTION "Trap for alarm on BIN Input 2" ::= 52 trapBin3Alarm TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString, bin3Int, bin3AlarmInt } DESCRIPTION "Trap for alarm on BIN Input 3" ::= 53 trapBin1ClrAlarm TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString, bin1Int, bin1AlarmInt } DESCRIPTION "Trap for clearing alarm on BIN Input 1" ::= 61 trapBin2ClrAlarm TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString, bin2Int, bin2AlarmInt } DESCRIPTION "Trap for clearing alarm on BIN Input 2" ::= 62 trapBin3ClrAlarm TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString, bin3Int, bin3AlarmInt } DESCRIPTION "Trap for clearing alarm on BIN Input 3" ::= 63 trapRelay1Closed TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString, re1Int } DESCRIPTION "Trap for closed Relay 1" ::= 70 trapRelay2Closed TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString, re2Int } DESCRIPTION "Trap for closed Relay 2" ::= 71 trapRelay1Open TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString, re1Int } DESCRIPTION "Trap for open Relay 1" ::= 72 trapRelay2Open TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString, re2Int } DESCRIPTION "Trap for open Relay 2" ::= 73 trapAcousticActivated TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString } DESCRIPTION "Trap for activated acoustic" ::= 74 trapAcousticDeactivated TRAP-TYPE ENTERPRISE comet VARIABLES { sensorName, messageString } DESCRIPTION "Trap for deactivated acoustic" ::= 75 END