-- Title : Chloride Power Environment Sensor MIB -- Date : March 24, 2005 -- By : Eric Peterson and Doug Griffin ( Chloride Power ) ------------------------------------------------------------ -- Revision History -- April 04, 2005 -- Initial release. Open for comments. ------------------------------------------------------------ CHLORIDE-ENVIRONMENT-SENSOR-MIB DEFINITIONS ::= BEGIN chloride OBJECT IDENTIFIER ::= {enterprises 1364} environmentSensor OBJECT IDENTIFIER ::= {chloride 10} -- TEMPERATURE SENSOR TABLE numSensors OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "The number of sensors that are currently connected." ::= { environmentSensor 1 } sensorTable OBJECT-TYPE SYNTAX SEQUENCE OF Sensor ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of sensor table entries." ::= { environmentSensor 2 } -- TEMPERATURE SENSOR ENTRY sensorEntry OBJECT-TYPE SYNTAX Sensor ACCESS not-accessible STATUS mandatory DESCRIPTION "" INDEX { address } ::= { sensorTable 1 } Sensor ::= SEQUENCE { name DisplayString (SIZE(0..63)), address INTEGER, status INTEGER, --temperature attributes temperature INTEGER, tempStatus INTEGER, tempHiSeverity INTEGER, tempLoSeverity INTEGER, tempHiThreshold INTEGER, tempLoThreshold INTEGER, --humidity attributes humidity INTEGER, humidityStatus INTEGER, humidityHiSeverity INTEGER, humidityLoSeverity INTEGER, humidityHiThreshold INTEGER, humidityLoThreshold INTEGER --input device attributes inputName1 DisplayString (SIZE(0..63)), inputStatus1 INTEGER, inputNormalState1 INTEGER, inputFaultSeverity1 INTEGER, inputUrl1 DisplayString (SIZE(0..63)) inputName2 DisplayString (SIZE(0..63)), inputStatus2 INTEGER, inputNormalState2 INTEGER, inputFaultSeverity2 INTEGER, inputUrl2 DisplayString (SIZE(0..63)) inputName3 DisplayString (SIZE(0..63)), inputStatus3 INTEGER, inputNormalState3 INTEGER, inputFaultSeverity3 INTEGER, inputUrl3 DisplayString (SIZE(0..63)), --output device attributes outputName DisplayString (SIZE(0..63)), outputState INTEGER, outputUrl DisplayString (SIZE(0..63)) } name OBJECT-TYPE SYNTAX DisplayString (SIZE(0..63)) MAX-ACCESS read-write STATUS current DESCRIPTION "A string identifying the sensor." ::= { sensorEntry 1 } status OBJECT-TYPE SYNTAX INTEGER { normal(1), informational(2), warning(3), severe(4) } ACCESS read-only STATUS mandatory DESCRIPTION "Overall status of the sensor determined by the most severe sensor alarm present." ::= { sensorEntry 2 } address OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The Blue Bus address of the environment sensor." ::= { sensorEntry 3 } --temperature attributes temperature OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Current temperature reading in celsius." ::= { sensorEntry 4 } tempStatus OBJECT-TYPE SYNTAX INTEGER { normal(1), informational(2), warning(3), severe(4) } ACCESS read-only STATUS mandatory DESCRIPTION "Temperature status determined by tempLoSeverity and tempHiSeverity objects." ::= { sensorEntry 5 } tempHiSeverity OBJECT-TYPE SYNTAX INTEGER { disabled(1), informational(2), warning(3), severe(4) } ACCESS read-write STATUS mandatory DESCRIPTION "Severity level when temperature is greater than or equal to tempHiThreshold." ::= { sensorEntry 6 } tempLoSeverity OBJECT-TYPE SYNTAX INTEGER { disabled(1), informational(2), warning(3), severe(4) } ACCESS read-write STATUS mandatory DESCRIPTION "Severity level when temperature is less than or equal to tempLoThreshold." ::= { sensorEntry 7 } tempHiThreshold OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "When the the temperature is greater than or equal to this value, the sensorHiTemperature alarm is generated." ::= { sensorEntry 8 } tempLoThreshold OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "When the the temperature is less than or equal to this value, the sensorLoTemperature alarm is generated." ::= { sensorEntry 9 } --humidity attributes humidity OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Current relative humidity reading in percent." ::= { sensorEntry 10 } humidityStatus OBJECT-TYPE SYNTAX INTEGER { normal(1), informational(2), warning(3), severe(4) } ACCESS read-only STATUS mandatory DESCRIPTION "Relative humidity status determined by humidityHiSeverity and humidityLoSeverity objects." ::= { sensorEntry 11 } humidityHiSeverity OBJECT-TYPE SYNTAX INTEGER { disabled(1), informational(2), warning(3), severe(4) } ACCESS read-write STATUS mandatory DESCRIPTION "Severity level when relative humidity is greater than or equal to humidityHiThreshold." ::= { sensorEntry 12 } humidityLoSeverity OBJECT-TYPE SYNTAX INTEGER { disabled(1), informational(2), warning(3), severe(4) } ACCESS read-write STATUS mandatory DESCRIPTION "Severity level when relative humidity is less than or equal to humidityLoThreshold." ::= { sensorEntry 13 } humidityHiThreshold OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "When the the relative humidity is greater than or equal to this value, the sensorHiRelativeHumidity alarm is generated." ::= { sensorEntry 14 } humidityLoThreshold OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "When the relative humidity is less than or equal to this value, the sensorLoRelativeHumidity alarm is generated." ::= { sensorEntry 15 } --input attributes inputName1 OBJECT-TYPE SYNTAX DisplayString (SIZE(0..63)) MAX-ACCESS read-write STATUS current DESCRIPTION "A string identifying the device on input 1." ::= { sensorEntry 16 } inputStatus1 OBJECT-TYPE SYNTAX INTEGER { normal(1), informational(2), warning(3), severe(4) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of the current state of input 1." ::= { sensorEntry 17 } inputNormalState1 OBJECT-TYPE SYNTAX INTEGER { open(1), closed(2) } ACCESS read-write STATUS mandatory DESCRIPTION "The normal state of input 1 ( open or closed )." ::= { sensorEntry 18 } inputFaultSeverity1 OBJECT-TYPE SYNTAX INTEGER { disabled(1), informational(2), warning(3), severe(4) } ACCESS read-write STATUS mandatory DESCRIPTION "Severity level when input 1 is not in its normal state as defined by inputNormalState1." ::= { sensorEntry 19 } inputUrl1 OBJECT-TYPE SYNTAX DisplayString (SIZE(0..63)) MAX-ACCESS read-write STATUS current DESCRIPTION "An optional string identifying the URL associated with the device on input 1." ::= { sensorEntry 20 } inputName2 OBJECT-TYPE SYNTAX DisplayString (SIZE(0..63)) MAX-ACCESS read-write STATUS current DESCRIPTION "A string identifying the device on input 2." ::= { sensorEntry 21 } inputStatus2 OBJECT-TYPE SYNTAX INTEGER { normal(1), informational(2), warning(3), severe(4) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of the current state of input 2." ::= { sensorEntry 22 } inputNormalState2 OBJECT-TYPE SYNTAX INTEGER { open(1), closed(2) } ACCESS read-write STATUS mandatory DESCRIPTION "The normal state of input 2 ( open or closed )." ::= { sensorEntry 23 } inputFaultSeverity2 OBJECT-TYPE SYNTAX INTEGER { disabled(1), informational(2), warning(3), severe(4) } ACCESS read-write STATUS mandatory DESCRIPTION "Severity level when input 2 is not in its normal state as defined by inputNormalState2." ::= { sensorEntry 24 } inputUrl2 OBJECT-TYPE SYNTAX DisplayString (SIZE(0..63)) MAX-ACCESS read-write STATUS current DESCRIPTION "An optional string identifying the URL associated with the device on input 2." ::= { sensorEntry 25 } inputName3 OBJECT-TYPE SYNTAX DisplayString (SIZE(0..63)) MAX-ACCESS read-write STATUS current DESCRIPTION "A string identifying the device on input 3." ::= { sensorEntry 26 } inputStatus3 OBJECT-TYPE SYNTAX INTEGER { normal(1), informational(2), warning(3), severe(4) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of the current state of input 3." ::= { sensorEntry 27 } inputNormalState3 OBJECT-TYPE SYNTAX INTEGER { open(1), closed(2) } ACCESS read-write STATUS mandatory DESCRIPTION "The normal state of input 3 ( open or closed )." ::= { sensorEntry 28 } inputFaultSeverity3 OBJECT-TYPE SYNTAX INTEGER { disabled(1), informational(2), warning(3), severe(4) } ACCESS read-write STATUS mandatory DESCRIPTION "Severity level when input 3 is not in its normal state as defined by inputNormalState3." ::= { sensorEntry 29 } inputUrl3 OBJECT-TYPE SYNTAX DisplayString (SIZE(0..63)) MAX-ACCESS read-write STATUS current DESCRIPTION "An optional string identifying the URL associated with the device on input 3." ::= { sensorEntry 30 } outputName OBJECT-TYPE SYNTAX DisplayString (SIZE(0..63)) MAX-ACCESS read-write STATUS current DESCRIPTION "A string identifying the device attached to the output relay." ::= { sensorEntry 31 } outputState OBJECT-TYPE SYNTAX INTEGER { on(1), off(2) } ACCESS read-write STATUS mandatory DESCRIPTION "The state of the output relay ( on = energized, off = de-energized )." ::= { sensorEntry 32 } outputUrl OBJECT-TYPE SYNTAX DisplayString (SIZE(0..63)) MAX-ACCESS read-write STATUS current DESCRIPTION "An optional string identifying the URL associated with the device attached to the output relay." ::= { sensorEntry 33 } --alarm conditions sensorAlarm OBJECT IDENTIFIER ::= { environmentSensor 3 } sensorAlarmsPresent OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Number of alarms present." ::= { sensorAlarm 1 } alarmTable OBJECT-TYPE SYNTAX SEQUENCE OF Alarm ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of alarm entries. " ::= { sensorAlarm 2 } alarmEntry OBJECT-TYPE SYNTAX Alarm ACCESS not-accessible STATUS mandatory DESCRIPTION "" INDEX { address } ::= { alarmTable 1 } Alarm ::= SEQUENCE { alarmAddress INTEGER, alarmDescr AutonomousType, alarmTime TimeStamp } alarmAddress OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS not-accessible STATUS current DESCRIPTION "The Blue Bus address of the sensor which generated the alarm." ::= { alarmEntry 1 } alarmDescr OBJECT-TYPE SYNTAX AutonomousType MAX-ACCESS read-only STATUS current DESCRIPTION "The OID of the alarm generated." ::= { alarmEntry 2 } alarmTime OBJECT-TYPE SYNTAX TimeStamp MAX-ACCESS read-only STATUS current DESCRIPTION "The value of sysUpTime when the alarm condition was detected." ::= { alarmEntry 3 } sensorAlarms OBJECT IDENTIFIER ::= { sensorAlarm 3 } sensorLostComms OBJECT-IDENTITY STATUS current DESCRIPTION "Blue Bus communications to the sensor have been lost." ::= { sensorAlarms 1 } sensorHiRelativeHumidity OBJECT-IDENTITY STATUS current DESCRIPTION "Current relative humidity is greater than or equal to humidityHiThreshold." ::= { sensorAlarms 2 } sensorLoRelativeHumidity OBJECT-IDENTITY STATUS current DESCRIPTION "Current relative humidity is less than or equal to humidityLoThreshold." ::= { sensorAlarms 3 } sensorHiTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "Current temperature is greater than or equal to tempHiThreshold." ::= { sensorAlarms 4 } sensorLoTemperature OBJECT-IDENTITY STATUS current DESCRIPTION "Current temperature is less than or equal to tempLoThreshold." ::= { sensorAlarms 5 } sensorInputFault1 OBJECT-IDENTITY STATUS current DESCRIPTION "The current state of input 1 does not equal inputNormalState1." ::= { sensorAlarms 6 } sensorInputFault2 OBJECT-IDENTITY STATUS current DESCRIPTION "The current state of input 2 does not equal inputNormalState2." ::= { sensorAlarms 7 } sensorInputFault3 OBJECT-IDENTITY STATUS current DESCRIPTION "The current state of input 3 does not equal inputNormalState3." ::= { sensorAlarms 8 } sensorOutputRelayEnergized OBJECT-IDENTITY STATUS current DESCRIPTION "The outputState object equals on." ::= { sensorAlarms 9 } sensorTraps OBJECT IDENTIFIER ::= { environmentSensor 4 } trapEntryAdded NOTIFICATION-TYPE OBJECTS { address, sensorAlarmOid } STATUS current DESCRIPTION "This trap is sent each time an alarm is inserted into to the alarm table. " ::= { sensorTraps 1 } trapEntryRemoved NOTIFICATION-TYPE OBJECTS { address, sensorAlarmOid } STATUS current DESCRIPTION "This trap is sent each time an alarm is removed from the alarm table." ::= { sensorTraps 2 } END