-- -- CAREL-insgrd.MIB -- MIB generated by CAREL -- Friday, 14 March 2003 -- CAREL-insgrd-MIB DEFINITIONS ::= BEGIN IMPORTS OBJECT-GROUP FROM SNMPv2-CONF sysContact, sysName, sysLocation FROM SNMPv2-MIB enterprises, MODULE-IDENTITY FROM SNMPv2-SMI; insgrdMIB MODULE-IDENTITY LAST-UPDATED "200303141725Z" -- March 14, 2003 at 17:25 GMT ORGANIZATION "CAREL SpA" CONTACT-INFO " Simone Ravazzolo Carel SpA Via dell'Industria, 11 35020 Brugine (PD) Italy Tel: +39 049 9716611 E-mail: simone.ravazzolo@carel.com " DESCRIPTION "This is the MIB module for the insgrd device." ::= { instruments 1 } -- -- Node definitions -- -- 1.3.6.1.4.1.9839 carel OBJECT IDENTIFIER ::= { enterprises 9839 } -- 1.3.6.1.4.1.9839.1 systm OBJECT IDENTIFIER ::= { carel 1 } -- 1.3.6.1.4.1.9839.1.1 agentRelease OBJECT-TYPE SYNTAX Integer32 UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Release of the Agent." ::= { systm 1 } -- 1.3.6.1.4.1.9839.1.2 agentCode OBJECT-TYPE SYNTAX Integer32 UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Code of the Agent. 1=WebGate" ::= { systm 2 } -- 1.3.6.1.4.1.9839.2 instruments OBJECT IDENTIFIER ::= { carel 2 } -- 1.3.6.1.4.1.9839.2.0 webGateInfo OBJECT IDENTIFIER ::= { instruments 0 } -- 1.3.6.1.4.1.9839.2.0.1 agentParameters OBJECT IDENTIFIER ::= { webGateInfo 1 } -- 1.3.6.1.4.1.9839.2.0.1.1 netSize OBJECT-TYPE SYNTAX Integer32 (1..16) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "Network size. It corresponds to the number of units connected to the WebGate. " ::= { agentParameters 1 } -- 1.3.6.1.4.1.9839.2.0.1.2 baudRate OBJECT-TYPE SYNTAX Integer32 (1200 | 2400 |4800 |9600 | 19200) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "Baudrate of the Carel network. " ::= { agentParameters 2 } -- 1.3.6.1.4.1.9839.2.0.2 unitTypeGroup OBJECT IDENTIFIER ::= { webGateInfo 2 } -- 1.3.6.1.4.1.9839.2.0.2.1 unit1-Type OBJECT-TYPE SYNTAX DisplayString UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Type of the unit having serial address 1. " ::= { unitTypeGroup 1 } -- ... You will have how many unitX-Type objects as the value of netSize is -- 1.3.6.1.4.1.9839.2.0.3 unitCodeGroup OBJECT IDENTIFIER ::= { webGateInfo 3 } -- 1.3.6.1.4.1.9839.2.0.3.1 unit1-Code OBJECT-TYPE SYNTAX Integer32 UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Code of the unit having serial address 1. " ::= { unitCodeGroup 1 } -- ... You will have how many unitX-Code objects as the value of netSize is -- 1.3.6.1.4.1.9839.2.0.4 unitSoftwareReleaseGroup OBJECT IDENTIFIER ::= { webGateInfo 4 } -- 1.3.6.1.4.1.9839.2.0.3.1 unit1-SoftwareRelease OBJECT-TYPE SYNTAX Integer32 UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Software release of the unit having serial address 1. " ::= { unitSoftwareReleaseGroup 1 } -- ... You will have how many unitX-SoftwareRelease objects as the value of netSize is -- 1.3.6.1.4.1.9839.2.0.5 unitMinSoftwareReleaseGroup OBJECT IDENTIFIER ::= { webGateInfo 5 } -- 1.3.6.1.4.1.9839.2.0.5.1 unit1-MinSoftwareRelease OBJECT-TYPE SYNTAX Integer32 UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Minimum software release of the unit having serial address 1. " ::= { unitMinSoftwareReleaseGroup 1 } -- ... You will have how many unitX-MinSoftwareRelease objects as the value of netSize is -- 1.3.6.1.4.1.9839.2.0.6 unitMaxSoftwareReleaseGroup OBJECT IDENTIFIER ::= { webGateInfo 6 } -- 1.3.6.1.4.1.9839.2.0.6.1 unit1-MaxSoftwareRelease OBJECT-TYPE SYNTAX Integer32 UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Maximum software release of the unit having serial address 1. " ::= { unitMaxSoftwareReleaseGroup 1 } -- ... You will have how many unitX-MaxSoftwareRelease objects as the value of netSize is -- 1.3.6.1.4.1.9839.2.0.7 unitNoAnswerCounterGroup OBJECT IDENTIFIER ::= { webGateInfo 7 } -- 1.3.6.1.4.1.9839.2.0.7.1 unit1-NoAnswerCounter OBJECT-TYPE SYNTAX Integer32 UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "No answer counter of the unit having serial address 1. " ::= { unitNoAnswerCounterGroup 1 } -- ... You will have how many unitX-NoAnswerCounter objects as the value of netSize is -- 1.3.6.1.4.1.9839.2.0.8 unitErrorChecksumCounterGroup OBJECT IDENTIFIER ::= { webGateInfo 8 } -- 1.3.6.1.4.1.9839.2.0.8.1 unit1-ErrorChecksumCounter OBJECT-TYPE SYNTAX Integer32 UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Error checksum counter of the unit having serial address 1. " ::= { unitErrorChecksumCounterGroup 1 } -- ... You will have how many unitX-ErrorChecksumCounter objects as the value of netSize is -- 1.3.6.1.4.1.9839.2.0.9 unitTimeoutCounterGroup OBJECT IDENTIFIER ::= { webGateInfo 9 } -- 1.3.6.1.4.1.9839.2.0.9.1 unit1-TimeoutCounter OBJECT-TYPE SYNTAX Integer32 UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Timeout counter of the unit having serial address 1. " ::= { unitTimeoutCounterGroup 1 } -- ... You will have how many unitX-TimeoutCounter objects as the value of netSize is -- 1.3.6.1.4.1.9839.2.0.10 unitOnLineStatusGroup OBJECT IDENTIFIER ::= { webGateInfo 10 } -- 1.3.6.1.4.1.9839.2.0.10.1 unit1-OnLineStatus OBJECT-TYPE SYNTAX Integer32 UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "On line status of the unit having serial address 1. " ::= { unitOnLineStatusGroup 1 } -- ... You will have how many unitX-OnLineStatus objects as the value of netSize is -- 1.3.6.1.4.1.9839.2.1 -- insgrdMIB OBJECT IDENTIFIER ::= { instruments 1 } -- 1.3.6.1.4.1.9839.2.1.1 digitalObjects OBJECT IDENTIFIER ::= { insgrdMIB 1 } -- 1.3.6.1.4.1.9839.2.1.1.1 device1 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Status device 1" ::= { digitalObjects 1 } -- 1.3.6.1.4.1.9839.2.1.1.2 device2 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Status device 2" ::= { digitalObjects 2 } -- 1.3.6.1.4.1.9839.2.1.1.3 device3 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Status device 3" ::= { digitalObjects 3 } -- 1.3.6.1.4.1.9839.2.1.1.4 device4 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Status device 4" ::= { digitalObjects 4 } -- 1.3.6.1.4.1.9839.2.1.1.5 device5 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Status device 5" ::= { digitalObjects 5 } -- 1.3.6.1.4.1.9839.2.1.1.6 device6 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Status device 6" ::= { digitalObjects 6 } -- 1.3.6.1.4.1.9839.2.1.1.7 device7 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Status device 7" ::= { digitalObjects 7 } -- 1.3.6.1.4.1.9839.2.1.1.8 device8 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Status device 8" ::= { digitalObjects 8 } -- 1.3.6.1.4.1.9839.2.1.1.9 device9 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Status device 9" ::= { digitalObjects 9 } -- 1.3.6.1.4.1.9839.2.1.1.10 device10 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Status device 10" ::= { digitalObjects 10 } -- 1.3.6.1.4.1.9839.2.1.1.12 compressor1 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "State of the compressor 1." ::= { digitalObjects 12 } -- 1.3.6.1.4.1.9839.2.1.1.13 compressor2 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "State of the compressor 2." ::= { digitalObjects 13 } -- 1.3.6.1.4.1.9839.2.1.1.14 compressor3 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "State of the compressor 3." ::= { digitalObjects 14 } -- 1.3.6.1.4.1.9839.2.1.1.15 compressor4 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "State of the compressor 4." ::= { digitalObjects 15 } -- 1.3.6.1.4.1.9839.2.1.1.16 compressor5 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "State of the compressor 5." ::= { digitalObjects 16 } -- 1.3.6.1.4.1.9839.2.1.1.17 compressor6 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "State of the compressor 6." ::= { digitalObjects 17 } -- 1.3.6.1.4.1.9839.2.1.1.18 compressor7 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "State of the compressor 7." ::= { digitalObjects 18 } -- 1.3.6.1.4.1.9839.2.1.1.19 compressor8 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "State of the compressor 8." ::= { digitalObjects 19 } -- 1.3.6.1.4.1.9839.2.1.1.20 compressor9 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "State of the compressor 9." ::= { digitalObjects 20 } -- 1.3.6.1.4.1.9839.2.1.1.21 compressor10 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "State of the compressor 10." ::= { digitalObjects 21 } -- 1.3.6.1.4.1.9839.2.1.1.22 compressor11 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "State of the compressor 11 or fan inverter." ::= { digitalObjects 22 } -- 1.3.6.1.4.1.9839.2.1.1.23 fan1 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Fan1" ::= { digitalObjects 23 } -- 1.3.6.1.4.1.9839.2.1.1.24 fan2 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Fan2" ::= { digitalObjects 24 } -- 1.3.6.1.4.1.9839.2.1.1.25 fan3 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Fan3" ::= { digitalObjects 25 } -- 1.3.6.1.4.1.9839.2.1.1.26 fan4 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Fan4" ::= { digitalObjects 26 } -- 1.3.6.1.4.1.9839.2.1.1.27 fan5 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Fan5" ::= { digitalObjects 27 } -- 1.3.6.1.4.1.9839.2.1.1.28 fan6 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Fan6" ::= { digitalObjects 28 } -- 1.3.6.1.4.1.9839.2.1.1.29 fan7 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Fan7" ::= { digitalObjects 29 } -- 1.3.6.1.4.1.9839.2.1.1.30 fan8 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Fan8" ::= { digitalObjects 30 } -- 1.3.6.1.4.1.9839.2.1.1.31 fan9 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Fan9" ::= { digitalObjects 31 } -- 1.3.6.1.4.1.9839.2.1.1.32 fan10 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Fan10" ::= { digitalObjects 32 } -- 1.3.6.1.4.1.9839.2.1.1.33 fan11 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Fan11" ::= { digitalObjects 33 } -- 1.3.6.1.4.1.9839.2.1.1.42 mal_maint_dev1 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Exceeded threshold of the device 1 operation hours" ::= { digitalObjects 42 } -- 1.3.6.1.4.1.9839.2.1.1.43 mal_maint_dev2 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Exceeded threshold of the device 2 operation hours" ::= { digitalObjects 43 } -- 1.3.6.1.4.1.9839.2.1.1.44 mal_maint_dev3 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Exceeded threshold of the device 3 operation hours" ::= { digitalObjects 44 } -- 1.3.6.1.4.1.9839.2.1.1.45 mal_maint_dev4 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Exceeded threshold of the device 4 operation hours" ::= { digitalObjects 45 } -- 1.3.6.1.4.1.9839.2.1.1.46 mal_maint_dev5 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Exceeded threshold of the device 5 operation hours" ::= { digitalObjects 46 } -- 1.3.6.1.4.1.9839.2.1.1.47 mal_maint_dev6 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Exceeded threshold of the device 6 operation hours" ::= { digitalObjects 47 } -- 1.3.6.1.4.1.9839.2.1.1.48 mal_maint_dev7 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Exceeded threshold of the device 7 operation hours" ::= { digitalObjects 48 } -- 1.3.6.1.4.1.9839.2.1.1.49 mal_maint_dev8 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Exceeded threshold of the device 8 operation hours" ::= { digitalObjects 49 } -- 1.3.6.1.4.1.9839.2.1.1.50 mal_maint_dev9 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Exceeded threshold of the device 9 operation hours" ::= { digitalObjects 50 } -- 1.3.6.1.4.1.9839.2.1.1.51 mal_maint_dev10 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Exceeded threshold of the device 10 operation hours" ::= { digitalObjects 51 } -- 1.3.6.1.4.1.9839.2.1.1.52 mal_maint_dev11 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Exceeded threshold of the device 11 operation hours" ::= { digitalObjects 52 } -- 1.3.6.1.4.1.9839.2.1.1.53 mal_m_invdev1 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Exceed. hour threshold of the device 1/valve inverter" ::= { digitalObjects 53 } -- 1.3.6.1.4.1.9839.2.1.1.54 mal_broke_pr1 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Probe 1 is not connected or does not operate" ::= { digitalObjects 54 } -- 1.3.6.1.4.1.9839.2.1.1.55 mal_broke_pr2 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Probe 2 is not connected or does not operate" ::= { digitalObjects 55 } -- 1.3.6.1.4.1.9839.2.1.1.56 mal_broke_pr3 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Probe 3 is not connected and does not operate" ::= { digitalObjects 56 } -- 1.3.6.1.4.1.9839.2.1.1.57 mal_pres_hpres OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Detection of high-pressure switch/antifreeze" ::= { digitalObjects 57 } -- 1.3.6.1.4.1.9839.2.1.1.58 mal_pres_lpres OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Detection of low-pressure switch/flow regulator" ::= { digitalObjects 58 } -- 1.3.6.1.4.1.9839.2.1.1.59 mal_block_dev1 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Stop of device 1" ::= { digitalObjects 59 } -- 1.3.6.1.4.1.9839.2.1.1.60 mal_block_dev2 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Stop of device 2" ::= { digitalObjects 60 } -- 1.3.6.1.4.1.9839.2.1.1.61 mal_block_dev3 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Stop of device 3" ::= { digitalObjects 61 } -- 1.3.6.1.4.1.9839.2.1.1.62 mal_block_dev4 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Stop of device 4" ::= { digitalObjects 62 } -- 1.3.6.1.4.1.9839.2.1.1.63 mal_block_dev5 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Stop of device 5" ::= { digitalObjects 63 } -- 1.3.6.1.4.1.9839.2.1.1.64 mal_block_dev6 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Stop of device 6" ::= { digitalObjects 64 } -- 1.3.6.1.4.1.9839.2.1.1.65 mal_block_dev7 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Stop of device 7" ::= { digitalObjects 65 } -- 1.3.6.1.4.1.9839.2.1.1.66 mal_block_dev8 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Stop of device 8" ::= { digitalObjects 66 } -- 1.3.6.1.4.1.9839.2.1.1.67 mal_block_dev9 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Stop of device 9" ::= { digitalObjects 67 } -- 1.3.6.1.4.1.9839.2.1.1.68 mal_block_dev10 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Stop of device 10" ::= { digitalObjects 68 } -- 1.3.6.1.4.1.9839.2.1.1.69 mal_block_dev11 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Stop of device 11 or stop of the fan inverter" ::= { digitalObjects 69 } -- 1.3.6.1.4.1.9839.2.1.1.70 mal_high1 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Probe 1 threshold of high is exeeded" ::= { digitalObjects 70 } -- 1.3.6.1.4.1.9839.2.1.1.71 mal_low1 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Probe 1 threshold of low is exeeded" ::= { digitalObjects 71 } -- 1.3.6.1.4.1.9839.2.1.1.72 mal_high2 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Probe 2 threshold of high is exeeded" ::= { digitalObjects 72 } -- 1.3.6.1.4.1.9839.2.1.1.73 mal_low2 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Probe 2 threshold of low is exeeded" ::= { digitalObjects 73 } -- 1.3.6.1.4.1.9839.2.1.1.74 mal_n_devices OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Number of devices being selected exceed the outputs actually available" ::= { digitalObjects 74 } -- 1.3.6.1.4.1.9839.2.1.1.75 mepromnook OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Not operating Eeprom" ::= { digitalObjects 75 } -- 1.3.6.1.4.1.9839.2.1.1.76 mal_clock OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Clock board is broken or not connected" ::= { digitalObjects 76 } -- 1.3.6.1.4.1.9839.2.1.1.77 syson OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "System ON/OFF" ::= { digitalObjects 77 } -- 1.3.6.1.4.1.9839.2.1.1.114 control_type1 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "Type of regulation of the probe circuit 1" DEFVAL { 0 } ::= { digitalObjects 114 } -- 1.3.6.1.4.1.9839.2.1.1.115 control_type2 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "sec" MAX-ACCESS read-write STATUS current DESCRIPTION "Type of regulation of the probe circuit 2" DEFVAL { 600 } ::= { digitalObjects 115 } -- 1.3.6.1.4.1.9839.2.1.1.116 en_inv_dev1 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "Device 1/valve inverter enabling" DEFVAL { 0 } ::= { digitalObjects 116 } -- 1.3.6.1.4.1.9839.2.1.1.117 en_rotation1 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "Rotation circuit 1 enabling" DEFVAL { 1 } ::= { digitalObjects 117 } -- 1.3.6.1.4.1.9839.2.1.1.118 en_rotation2 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "Rotation circuit 2 enabling" DEFVAL { 1 } ::= { digitalObjects 118 } -- 1.3.6.1.4.1.9839.2.1.1.119 on_off_boss OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "Remote On/Off selection" DEFVAL { 0 } ::= { digitalObjects 119 } -- 1.3.6.1.4.1.9839.2.1.1.120 cel_fahr OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "sec" MAX-ACCESS read-write STATUS current DESCRIPTION "Celsius/fahrenait selection" DEFVAL { 40 } ::= { digitalObjects 120 } -- 1.3.6.1.4.1.9839.2.1.1.121 en_air_temp OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "Air temperature probe enabling" DEFVAL { 0 } ::= { digitalObjects 121 } -- 1.3.6.1.4.1.9839.2.1.1.124 bool_device11 OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "State of the device 11" ::= { digitalObjects 124 } -- 1.3.6.1.4.1.9839.2.1.1.125 off_mode OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "Circuit 1 devices switch off mode" DEFVAL { 0 } ::= { digitalObjects 125 } -- 1.3.6.1.4.1.9839.2.1.1.126 cool_heat OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "cold / warm" DEFVAL { 0 } ::= { digitalObjects 126 } -- 1.3.6.1.4.1.9839.2.1.2 analogObjects OBJECT IDENTIFIER ::= { insgrdMIB 2 } -- 1.3.6.1.4.1.9839.2.1.2.1 probe_circ1 OBJECT-TYPE SYNTAX Integer32 (-990..999) UNITS "°C x10" MAX-ACCESS read-only STATUS current DESCRIPTION "Probe 1" ::= { analogObjects 1 } -- 1.3.6.1.4.1.9839.2.1.2.2 probe_circ2 OBJECT-TYPE SYNTAX Integer32 (-990..999) UNITS "°C x10" MAX-ACCESS read-only STATUS current DESCRIPTION "Probe 2" ::= { analogObjects 2 } -- 1.3.6.1.4.1.9839.2.1.2.3 setp_air_temp OBJECT-TYPE SYNTAX Integer32 (-990..999) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "Meaning of the analog imput B3" ::= { analogObjects 3 } -- 1.3.6.1.4.1.9839.2.1.2.4 inverter_fan OBJECT-TYPE SYNTAX Integer32 (0..100) UNITS "V x10" MAX-ACCESS read-only STATUS current DESCRIPTION "Display of the state of the fan inverter" ::= { analogObjects 4 } -- 1.3.6.1.4.1.9839.2.1.2.5 inverter_dev1 OBJECT-TYPE SYNTAX Integer32 (0..100) UNITS "V x10" MAX-ACCESS read-only STATUS current DESCRIPTION "Display of the state of the device 1/valve" ::= { analogObjects 5 } -- 1.3.6.1.4.1.9839.2.1.2.6 set_circuit1 OBJECT-TYPE SYNTAX Integer32 (-32767..32767) UNITS "°C/°F/bar x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Selection of probe 1 setpoint" DEFVAL { 25 } ::= { analogObjects 6 } -- 1.3.6.1.4.1.9839.2.1.2.7 set_c1_mask OBJECT-TYPE SYNTAX Integer32 (-32767..32767) UNITS "°C/°F/bar x10" MAX-ACCESS read-only STATUS current DESCRIPTION "Display of the probe 1 actual setpoint" ::= { analogObjects 7 } -- 1.3.6.1.4.1.9839.2.1.2.8 reduced_set OBJECT-TYPE SYNTAX Integer32 (-990..999) UNITS "°C/°F/bar x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Secondary setpoint selection" DEFVAL { 30 } ::= { analogObjects 8 } -- 1.3.6.1.4.1.9839.2.1.2.9 set_inv_dev1 OBJECT-TYPE SYNTAX Integer32 (-32767..32767) UNITS "°C/°F/bar x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Setpoint selection of the probe 1/valve inverter" DEFVAL { 25 } ::= { analogObjects 9 } -- 1.3.6.1.4.1.9839.2.1.2.10 set_inv_fan OBJECT-TYPE SYNTAX Integer32 (-32767..32767) UNITS "°C/°F/bar x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Selection of fan inverter setpoint" DEFVAL { 160 } ::= { analogObjects 10 } -- 1.3.6.1.4.1.9839.2.1.2.11 comp_setp OBJECT-TYPE SYNTAX Integer32 (-990..999) UNITS "min x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Compensation setpoint" DEFVAL { 250 } ::= { analogObjects 11 } -- 1.3.6.1.4.1.9839.2.1.2.12 set_circuit2 OBJECT-TYPE SYNTAX Integer32 (-32767..32767) UNITS "°C/°F/bar x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Selection of probe 2 setpoint" DEFVAL { 160 } ::= { analogObjects 12 } -- 1.3.6.1.4.1.9839.2.1.2.13 diff_circuit1 OBJECT-TYPE SYNTAX Integer32 (0..200) UNITS "°C/°F/bar x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Probe 1 differential selection" DEFVAL { 5 } ::= { analogObjects 13 } -- 1.3.6.1.4.1.9839.2.1.2.14 diff_circuit2 OBJECT-TYPE SYNTAX Integer32 (0..200) UNITS "°C/°F/bar x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Probe 2 differential selection" DEFVAL { 20 } ::= { analogObjects 14 } -- 1.3.6.1.4.1.9839.2.1.2.15 thresh_low1 OBJECT-TYPE SYNTAX Integer32 (-990..999) UNITS "°C/°F/bar x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Threshold low pression probe 1" DEFVAL { 10 } ::= { analogObjects 15 } -- 1.3.6.1.4.1.9839.2.1.2.16 thresh_low2 OBJECT-TYPE SYNTAX Integer32 (-990..999) UNITS "°C/°F/bar x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Threshold low pression probe 2" DEFVAL { 0 } ::= { analogObjects 16 } -- 1.3.6.1.4.1.9839.2.1.2.17 thresh_high1 OBJECT-TYPE SYNTAX Integer32 (-990..999) UNITS "°C/°F/bar x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Threshold high pression probe 1" DEFVAL { 50 } ::= { analogObjects 17 } -- 1.3.6.1.4.1.9839.2.1.2.18 thresh_high2 OBJECT-TYPE SYNTAX Integer32 (-990..999) UNITS "°C/°F/bar x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Threshold high pression probe 2" DEFVAL { 200 } ::= { analogObjects 18 } -- 1.3.6.1.4.1.9839.2.1.2.19 min_setp1 OBJECT-TYPE SYNTAX Integer32 (-990..999) UNITS "°C/°F/bar x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Selection of the probe 1 minimum setpoint" DEFVAL { 0 } ::= { analogObjects 19 } -- 1.3.6.1.4.1.9839.2.1.2.20 min_setp2 OBJECT-TYPE SYNTAX Integer32 (-990..999) UNITS "°C/°F/bar x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Selection of the probe 2 minimum setpoint" DEFVAL { 100 } ::= { analogObjects 20 } -- 1.3.6.1.4.1.9839.2.1.2.21 max_setp1 OBJECT-TYPE SYNTAX Integer32 (-990..999) UNITS "°C/°F/bar x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Selection of the probe 1 maximum setpoint" DEFVAL { 50 } ::= { analogObjects 21 } -- 1.3.6.1.4.1.9839.2.1.2.22 max_setp2 OBJECT-TYPE SYNTAX Integer32 (-990..999) UNITS "°C/°F/bar x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Selection of the probe 2 maximum setpoint" DEFVAL { 240 } ::= { analogObjects 22 } -- 1.3.6.1.4.1.9839.2.1.2.23 diff_inv_dev1 OBJECT-TYPE SYNTAX Integer32 (0..200) UNITS "°C/°F/bar x10" MAX-ACCESS read-write STATUS current DESCRIPTION "Device 1/valve inverter differential" DEFVAL { 10 } ::= { analogObjects 23 } -- 1.3.6.1.4.1.9839.2.1.2.24 diff_inv_fan OBJECT-TYPE SYNTAX Integer32 (0..200) UNITS "°C/°F/bar x10" MAX-ACCESS read-write STATUS current DESCRIPTION "selection of the fan inverter differential" DEFVAL { 20 } ::= { analogObjects 24 } -- 1.3.6.1.4.1.9839.2.1.3 integerObjects OBJECT IDENTIFIER ::= { insgrdMIB 3 } -- 1.3.6.1.4.1.9839.2.1.3.34 day OBJECT-TYPE SYNTAX Integer32 (1..31) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Day display (only if P41=1)" ::= { integerObjects 34 } -- 1.3.6.1.4.1.9839.2.1.3.35 month OBJECT-TYPE SYNTAX Integer32 (0..12) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Month display (only if P41=1)" ::= { integerObjects 35 } -- 1.3.6.1.4.1.9839.2.1.3.36 pyear OBJECT-TYPE SYNTAX Integer32 (0..99) UNITS "N/A" MAX-ACCESS read-only STATUS current DESCRIPTION "Year display (only if P41=1)" ::= { integerObjects 36 } -- 1.3.6.1.4.1.9839.2.1.3.37 lday OBJECT-TYPE SYNTAX Integer32 (1..31) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "Day selection (only if P41=1)" DEFVAL { 0 } ::= { integerObjects 37 } -- 1.3.6.1.4.1.9839.2.1.3.38 lmonth OBJECT-TYPE SYNTAX Integer32 (1..12) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "Month selection (only if P41=1)" DEFVAL { 0 } ::= { integerObjects 38 } -- 1.3.6.1.4.1.9839.2.1.3.39 lyear OBJECT-TYPE SYNTAX Integer32 (0..99) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "Year selection (only if P41=1)" DEFVAL { 0 } ::= { integerObjects 39 } -- 1.3.6.1.4.1.9839.2.1.3.40 hour OBJECT-TYPE SYNTAX Integer32 (0..23) UNITS "hour" MAX-ACCESS read-only STATUS current DESCRIPTION "Hour display (only if P41=1)" ::= { integerObjects 40 } -- 1.3.6.1.4.1.9839.2.1.3.41 minute OBJECT-TYPE SYNTAX Integer32 (0..59) UNITS "min" MAX-ACCESS read-only STATUS current DESCRIPTION "Minute display (only if P41=1)" ::= { integerObjects 41 } -- 1.3.6.1.4.1.9839.2.1.3.42 lhour OBJECT-TYPE SYNTAX Integer32 (0..23) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "Hour selection (only if P41=1)" DEFVAL { 0 } ::= { integerObjects 42 } -- 1.3.6.1.4.1.9839.2.1.3.43 lminute OBJECT-TYPE SYNTAX Integer32 (0..59) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "Minute selection (only if P41=1)" DEFVAL { 0 } ::= { integerObjects 43 } -- 1.3.6.1.4.1.9839.2.1.3.44 delay_low_press OBJECT-TYPE SYNTAX Integer32 (0..1) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "Alarm delay of low pressure / low regulation" ::= { integerObjects 44 } -- 1.3.6.1.4.1.9839.2.1.3.45 n_devices1 OBJECT-TYPE SYNTAX Integer32 (0..11) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "Probe 1 device bumber" DEFVAL { 3 } ::= { integerObjects 45 } -- 1.3.6.1.4.1.9839.2.1.3.46 n_devices2 OBJECT-TYPE SYNTAX Integer32 (0..11) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "Probe 2 device number" DEFVAL { 5 } ::= { integerObjects 46 } -- 1.3.6.1.4.1.9839.2.1.3.47 n_partial OBJECT-TYPE SYNTAX Integer32 (0..3) UNITS "N/A" MAX-ACCESS read-write STATUS current DESCRIPTION "Number of voltage variations" DEFVAL { 1 } ::= { integerObjects 47 } END -- -- CAREL-insgrd.MIB --