-- MIB version: 1.1.104 -- MIB release note -- | date | MIB version | note --------------------------------------------------------------------------------------------------- -- | 2018/02/13 | 1.1.101 | Initial version --------------------------------------------------------------------------------------------------- -- | 2018/03/01 | 1.1.102 | Modify descriptions of bankStatusRatedCur, outletStatusRatedCur, and outletStatusSwitchable --------------------------------------------------------------------------------------------------- -- | 2019/09/09 | 1.1.103 | Add staStatusHasAutoPing, outletStatusAutoPing, outletConfigAutoPing. Modify sensorConfigTable, sensorReadingTable to support port-address indexing --------------------------------------------------------------------------------------------------- -- | 2019/10/08 | 1.1.104 | Add trapNotification. Add netConfigTable to support port indexing for dual-network --------------------------------------------------------------------------------------------------- -- | 2020/11/23 | 1.1.105 | Add deviceLock to change password of SNMP for California passes law --------------------------------------------------------------------------------------------------- -- | 2021/05/06 | 1.1.106 | Add phase layout of outlet and bank --------------------------------------------------------------------------------------------------- -- | 2021/08/24 | 1.1.107 | Add inlet entry and inlet number --------------------------------------------------------------------------------------------------- -- | 2021/10/01 | 1.1.108 | Add smoke sensor in dry contact --------------------------------------------------------------------------------------------------- -- | 2021/11/02 | 1.1.109 | Add InetAddress and InetAddressType for support ipv4/ipv6 --------------------------------------------------------------------------------------------------- -- ATEN International Co., Ltd. -- This file defines the mib struct of Management in PE series -- We attach this mib node on enterprises.aten.atenProducts.overip.poweroverip.pe2 subtree ATEN-PE2-CFG DEFINITIONS ::= BEGIN IMPORTS enterprises, IpAddress, Gauge, TimeTicks FROM RFC1155-SMI DisplayString FROM RFC1213-MIB OBJECT-TYPE FROM RFC-1212 TRAP-TYPE FROM RFC-1215 MODULE-IDENTITY, NOTIFICATION-TYPE FROM SNMPv2-SMI KeyChange FROM SNMP-USER-BASED-SM-MIB MacAddress FROM SNMPv2-TC poweroverip FROM ATEN-PRODUCTS-MIB InetAddressType, InetAddress, InetPortNumber FROM INET-ADDRESS-MIB; pe2 MODULE-IDENTITY LAST-UPDATED "201801231200Z" ORGANIZATION "ATEN" CONTACT-INFO "Aten, Inc." DESCRIPTION "ATEN PE MIB" REVISION "201801231200Z" DESCRIPTION "support stations" ::= { poweroverip 3 } management OBJECT IDENTIFIER ::= { pe2 1 } energy OBJECT IDENTIFIER ::= { pe2 2 } device OBJECT IDENTIFIER ::= { energy 1 } bank OBJECT IDENTIFIER ::= { energy 2 } outlet OBJECT IDENTIFIER ::= { energy 3 } line OBJECT IDENTIFIER ::= { energy 4 } inlet OBJECT IDENTIFIER ::= { energy 5 } environment OBJECT IDENTIFIER ::= { pe2 3 } sensor OBJECT IDENTIFIER ::= { environment 1 } dryContact OBJECT IDENTIFIER ::= { environment 2 } network OBJECT IDENTIFIER ::= { pe2 4 } event OBJECT IDENTIFIER ::= { pe2 5 } trap OBJECT IDENTIFIER ::= { event 1 } trapNotification OBJECT IDENTIFIER ::= { pe2 50 } deviceLock OBJECT IDENTIFIER ::= { pe2 150 } --------------------------------------------------------------------------------------------------- -- Management --------------------------------------------------------------------------------------------------- staCount OBJECT-TYPE SYNTAX INTEGER (1..16) MAX-ACCESS read-only STATUS current DESCRIPTION "The available station count which includes master and slave stations." ::= { management 1 } staStatusTable OBJECT-TYPE SYNTAX SEQUENCE OF StaStatusEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Station status table." ::= { management 2 } staStatusEntry OBJECT-TYPE SYNTAX StaStatusEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single entry containing station status info." INDEX { staId } ::= { staStatusTable 1 } StaStatusEntry ::= SEQUENCE { staId INTEGER, staStatusFWVer DisplayString, staStatusModelName DisplayString, staStatusSwitchable INTEGER, staStatusPerPortReading INTEGER, staStatusBankCount INTEGER, staStatusOutletCount INTEGER, staStatusSensorCount INTEGER, staStatusHasAutoPing INTEGER, staStatusInletCount INTEGER } staId OBJECT-TYPE SYNTAX INTEGER (1..16) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Station ID." ::= { staStatusEntry 1 } staStatusFWVer OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Station FW version. If the station is not available, it returns 'station N/A'." ::= { staStatusEntry 2 } staStatusModelName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Station model name. If the station is not available, it returns 'station N/A'" ::= { staStatusEntry 3 } staStatusSwitchable OBJECT-TYPE SYNTAX INTEGER { staNotAvailable(-3000000), no(1), yes(2), mix(3) } MAX-ACCESS read-only STATUS current DESCRIPTION "Outlets of the station are switchable or not. If the station is not available, it returns value -3000000." ::= { staStatusEntry 4 } staStatusPerPortReading OBJECT-TYPE SYNTAX INTEGER { staNotAvailable(-3000000), no(1), yes(2) } MAX-ACCESS read-only STATUS current DESCRIPTION "Outlets of the station are per-port reading or not. If the station is not available, it returns value -3000000." ::= { staStatusEntry 5 } staStatusBankCount OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Station bank count. If the station is not available, it returns value -3000000." ::= { staStatusEntry 6 } staStatusOutletCount OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Station outlet count. If the station is not available, it returns value -3000000." ::= { staStatusEntry 7 } staStatusSensorCount OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Station sensor count. If the station is not available, it returns value -3000000." ::= { staStatusEntry 8 } staStatusHasAutoPing OBJECT-TYPE SYNTAX INTEGER { staNotAvailable(-3000000), no(1), yes(2) } MAX-ACCESS read-only STATUS current DESCRIPTION "The station supports auto-ping or not. If the station is not available, it returns value -3000000." ::= { staStatusEntry 9 } staStatusInletCount OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Station inlet count. If the station is not available, it returns value -3000000." ::= { staStatusEntry 10 } --------------------------------------------------------------------------------------------------- -- staControlTable --------------------------------------------------------------------------------------------------- staControlTable OBJECT-TYPE SYNTAX SEQUENCE OF StaControlEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Station control table." ::= { management 3 } staControlEntry OBJECT-TYPE SYNTAX StaControlEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single entry containing station control info." INDEX { staId } ::= { staControlTable 1 } StaControlEntry ::= SEQUENCE { staControlReboot INTEGER } staControlReboot OBJECT-TYPE SYNTAX INTEGER { staNotAvailable(-3000000), no(1), yes(2), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Reboot the station. If the station is not available, it returns value -3000000." ::= { staControlEntry 1 } --------------------------------------------------------------------------------------------------- -- rackConfigTable --------------------------------------------------------------------------------------------------- rackConfigTable OBJECT-TYPE SYNTAX SEQUENCE OF RackConfigEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Rack config table." ::= { management 4 } rackConfigEntry OBJECT-TYPE SYNTAX RackConfigEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single entry containing rack config info." INDEX { staId } ::= { rackConfigTable 1 } RackConfigEntry ::= SEQUENCE { rackConfigName DisplayString, rackConfigRow INTEGER, rackConfigColumn INTEGER } rackConfigName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set station's rack name. string length: 1~32 If the station is not available, it returns 'station N/A'. NOTE: Input string as /empty to set this object to NULL." ::= { rackConfigEntry 1 } rackConfigRow OBJECT-TYPE SYNTAX INTEGER (1..26) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set station's rack row number. If the station is not available, it returns value -3000000." ::= { rackConfigEntry 2 } rackConfigColumn OBJECT-TYPE SYNTAX INTEGER (1..26) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set station's rack column number. If the station is not available, it returns value -3000000." ::= { rackConfigEntry 3 } staState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "Cascade stations' state. Return string length equals to the MAX support stations. If station N is alive, display 1 at the N's character, else, display 0. The first character is always 1 as it belongs to the Master." ::= { management 5 } --------------------------------------------------------------------------------------------------- -- devStatusTable --------------------------------------------------------------------------------------------------- devStatusTable OBJECT-TYPE SYNTAX SEQUENCE OF DevStatusEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Device status table." ::= { device 1 } devStatusEntry OBJECT-TYPE SYNTAX DevStatusEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single entry containing device status info." INDEX { staId } ::= { devStatusTable 1 } DevStatusEntry ::= SEQUENCE { devStatusRatedCur INTEGER, devStatusRatedVol INTEGER, devStatusRatedPower INTEGER, devStatusWiredType INTEGER } devStatusRatedCur OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Device input Current value. unit:(0.1mA) If the station does not support this OID, we show value 0. If the station is not available, it returns value -3000000." ::= { devStatusEntry 1 } devStatusRatedVol OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Device input Voltage value. unit:(0.1mV) If the station does not support this OID, we show value 0. If the station is not available, it returns value -3000000." ::= { devStatusEntry 2 } devStatusRatedPower OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Device power Capacity value. unit:(0.1mVA) If the station does not support this OID, we show value 0. If the station is not available, it returns value -3000000." ::= { devStatusEntry 3 } devStatusWiredType OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Device circuit wired type Example: 1 for 1 phase, 2 for 3 phase wye, 3 for 3 phase delta If the station does not support this OID, we show value 0. If the station is not available, it returns value -3000000." ::= { devStatusEntry 4 } --------------------------------------------------------------------------------------------------- -- devConfigTable --------------------------------------------------------------------------------------------------- devConfigTable OBJECT-TYPE SYNTAX SEQUENCE OF DevConfigEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Device config table." ::= { device 2 } devConfigEntry OBJECT-TYPE SYNTAX DevConfigEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single entry containing device config info." INDEX { staId } ::= { devConfigTable 1 } DevConfigEntry ::= SEQUENCE { devConfigDevName DisplayString, devConfigPowerOnScheduleEn INTEGER, devConfigOutletsSequentialRebootEn INTEGER, devConfigMinCurThresh INTEGER, devConfigMaxCurThresh INTEGER, devConfigMinVolThresh INTEGER, devConfigMaxVolThresh INTEGER, devConfigMinPowerThresh INTEGER, devConfigMaxPowerThresh INTEGER, devConfigMaxPDThresh INTEGER } devConfigDevName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "The name of the device. string length: 1~39 If the station is not available, it returns 'station N/A'. NOTE: Input string as /empty to set this object to NULL." ::= { devConfigEntry 1 } devConfigPowerOnScheduleEn OBJECT-TYPE SYNTAX INTEGER { staNotAvailable(-3000000), no-delaytime(1), delaytime(2), not-support(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set whether power on schedule or not. If the station is not available, it returns value -3000000." ::= { devConfigEntry 2 } devConfigOutletsSequentialRebootEn OBJECT-TYPE SYNTAX INTEGER { staNotAvailable(-3000000), no(1), yes(2), not-support(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "This function is used to enable or disable all outlet ports to sequential reboot. If the station is not available, it returns value -3000000." ::= { devConfigEntry 3 } devConfigMinCurThresh OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set device minimum electric current measurement threshold. Example: range 0.0~32.0 represents 0~320. NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { devConfigEntry 4 } devConfigMaxCurThresh OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set device maximum electric current measurement threshold. Example: range 0.0~32.0 represents 0~320 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { devConfigEntry 5 } devConfigMinVolThresh OBJECT-TYPE SYNTAX INTEGER (-3000 | 900..2600) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set device minimum voltage measurement threshold. Example: range 90.0~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { devConfigEntry 6 } devConfigMaxVolThresh OBJECT-TYPE SYNTAX INTEGER (-3000 | 900..2600) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set device maximum voltage measurement threshold. Example: range 90.0~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { devConfigEntry 7 } devConfigMinPowerThresh OBJECT-TYPE SYNTAX INTEGER (-3000 | 0..99999) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set device minimum power measurement threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { devConfigEntry 8 } devConfigMaxPowerThresh OBJECT-TYPE SYNTAX INTEGER (-3000 | 0..99999) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set device maximum power measurement threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { devConfigEntry 9 } devConfigMaxPDThresh OBJECT-TYPE SYNTAX INTEGER (-3000 | 0..999990) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set device maximum power dissipation measurement threshold. Example: range 0.0 ~ 99999.0 represents 0~999990 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { devConfigEntry 10 } --------------------------------------------------------------------------------------------------- -- devControlTable --------------------------------------------------------------------------------------------------- devControlTable OBJECT-TYPE SYNTAX SEQUENCE OF DevControlEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Device control table." ::= { device 3 } devControlEntry OBJECT-TYPE SYNTAX DevControlEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single entry containing device control info." INDEX { staId } ::= { devControlTable 1 } DevControlEntry ::= SEQUENCE { devControlOperation INTEGER } devControlOperation OBJECT-TYPE SYNTAX INTEGER { staNotAvailable(-3000000), off(1), on(2), reboot(3), nostatus(4), not-support(5) } MAX-ACCESS read-write STATUS current DESCRIPTION "This function is used for outlet control of device. Set off(1) to turn off for outlet control of device. Set on(2) to turn on for all outlet control of device. Set reboot(3) to reboot for outlet control of device. Get this object always return nostatus(3), because there is no device status. If the station is not available, it returns value -3000000." ::= { devControlEntry 1 } --------------------------------------------------------------------------------------------------- -- devReadingTable --------------------------------------------------------------------------------------------------- devReadingTable OBJECT-TYPE SYNTAX SEQUENCE OF DevReadingEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Device reading table." ::= { device 4 } devReadingEntry OBJECT-TYPE SYNTAX DevReadingEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single entry containing device reading info." INDEX { staId } ::= { devReadingTable 1 } DevReadingEntry ::= SEQUENCE { devReadingCur INTEGER, devReadingVol INTEGER, devReadingPower INTEGER, devReadingPD INTEGER, devReadingPF INTEGER } devReadingCur OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Device electric current value. This value indicates that 10,000 times. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { devReadingEntry 1 } devReadingVol OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Device voltage value. This value indicates that 10,000 times. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { devReadingEntry 2 } devReadingPower OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Device power value. This value indicates that 10,000 times. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { devReadingEntry 3 } devReadingPD OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Device power dissipation value. This value indicates that 10,000 times. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { devReadingEntry 4 } devReadingPF OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Device power factor value. This value indicates that 100 times. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { devReadingEntry 5 } --------------------------------------------------------------------------------------------------- -- popConfigTable --------------------------------------------------------------------------------------------------- popConfigTable OBJECT-TYPE SYNTAX SEQUENCE OF PopConfigEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "POP config table." ::= { device 5 } popConfigEntry OBJECT-TYPE SYNTAX PopConfigEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single entry containing POP config info." INDEX { staId } ::= { popConfigTable 1 } PopConfigEntry ::= SEQUENCE { popConfigOutletModeEn INTEGER, popConfigLIFOModeEn INTEGER, popConfigPriorityModeEn INTEGER, popConfigPriorityList DisplayString } popConfigOutletModeEn OBJECT-TYPE SYNTAX INTEGER { staNotAvailable(-3000000), no(1), yes(2), not-support(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set whether outlet POP mode is enabled or not. If the station is not available, it returns value -3000000." ::= { popConfigEntry 1 } popConfigLIFOModeEn OBJECT-TYPE SYNTAX INTEGER { staNotAvailable(-3000000), no(1), yes(2), not-support(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set whether LIFO POP mode is enabled or not. If the station is not available, it returns value -3000000." ::= { popConfigEntry 2 } popConfigPriorityModeEn OBJECT-TYPE SYNTAX INTEGER { staNotAvailable(-3000000), no(1), yes(2), not-support(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set whether priority POP mode is enabled or not. If the station is not available, it returns value -3000000." ::= { popConfigEntry 3 } popConfigPriorityList OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Indicate Outlets' power OFF priorities under Priority POP mode. Outlet Separator ',' Bank Separator '#' Assign each priority in each bank by Outlet index or zero (indicate N/A) with separators in ascendant order. e.g. for model PE8324 ( Bank1: outlet 1 ~ 16, Bank2: outlet 17 ~ 24 ) If you want to assign priority 2, 5 of Bank 1 with Outlet 14, 3, and priority 2, 6, 8 with of Bank 2 with Outlet 17, 23, 24 and left the rest with N/A, please type: 0,14,0,0,3,0,0,0,0,0,0,0,0,0,0,0#0,17,0,0,0,23,0,24. If the station is not available, it returns 'station N/A'." ::= { popConfigEntry 4 } --------------------------------------------------------------------------------------------------- -- capConfigTable --------------------------------------------------------------------------------------------------- capConfigTable OBJECT-TYPE SYNTAX SEQUENCE OF CapConfigEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "CAP config table." ::= { device 6 } capConfigEntry OBJECT-TYPE SYNTAX CapConfigEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single entry containing CAP config info." INDEX { staId, outletId } ::= { capConfigTable 1 } CapConfigEntry ::= SEQUENCE { capConfigModeEn INTEGER } capConfigModeEn OBJECT-TYPE SYNTAX INTEGER { staNotAvailable(-3000000), no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set whether CAP mode is enabled or not. If the station is not available, it returns value -3000000." ::= { capConfigEntry 1 } --------------------------------------------------------------------------------------------------- -- capPriorityConfigTable --------------------------------------------------------------------------------------------------- capPriorityConfigTable OBJECT-TYPE SYNTAX SEQUENCE OF CapPriorityConfigEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "CAP priority config table." ::= { device 7 } capPriorityConfigEntry OBJECT-TYPE SYNTAX CapPriorityConfigEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single entry containing CAP priority config info." INDEX { staId, outletId } ::= { capPriorityConfigTable 1 } CapPriorityConfigEntry ::= SEQUENCE { capPriorityConfigOutlet INTEGER } capPriorityConfigOutlet OBJECT-TYPE SYNTAX INTEGER (0..99) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the CAP Priority of outlet. Priority 0 means this outlet does not support this OID. If the station is not available, it returns value -3000000." ::= { capPriorityConfigEntry 1 } --------------------------------------------------------------------------------------------------- -- bankStatusTable --------------------------------------------------------------------------------------------------- bankStatusTable OBJECT-TYPE SYNTAX SEQUENCE OF BankStatusEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Bank status table." ::= { bank 1 } bankStatusEntry OBJECT-TYPE SYNTAX BankStatusEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single entry containing bank status info." INDEX { staId, bankId } ::= { bankStatusTable 1 } BankStatusEntry ::= SEQUENCE { bankId INTEGER, bankStatusRatedCur INTEGER, bankStatusAttachStatus INTEGER, bankStatusBreakerStatus INTEGER, bankStatusPhaseLayout INTEGER } bankId OBJECT-TYPE SYNTAX INTEGER (1..30) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Bank ID." ::= { bankStatusEntry 1 } bankStatusRatedCur OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "The Bank Max Current value. unit: (0.1mA). If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { bankStatusEntry 2 } bankStatusAttachStatus OBJECT-TYPE SYNTAX INTEGER { staNotAvailable(-3000000), noattached(1), attached(2), error(3), noexisted(4) } MAX-ACCESS read-only STATUS current DESCRIPTION "The bank attached status. If the station is not available, it returns value -3000000." ::= { bankStatusEntry 3 } bankStatusBreakerStatus OBJECT-TYPE SYNTAX INTEGER { staNotAvailable(-3000000), off(1), on(2), not-support(3) } MAX-ACCESS read-only STATUS current DESCRIPTION "The breaker status. If the station is not available, it returns value -3000000." ::= { bankStatusEntry 4 } bankStatusPhaseLayout OBJECT-TYPE SYNTAX INTEGER { staNotAvailable(-3000000), not-support(-2000000), l1-n(1), l2-n(2), l3-n(3), l1-l2(4), l2-l3(5), l3-l1(6) } MAX-ACCESS read-only STATUS current DESCRIPTION "Display the phase layout of bank. Example: range 1 ~ 3 represents Line1-LineNeutral ~ Line3-lineNeutral. 4 ~ 6 represents Line1-Line2, Line2-Line3, Line3-Line1. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { bankStatusEntry 5 } --------------------------------------------------------------------------------------------------- -- bankConfigTable --------------------------------------------------------------------------------------------------- bankConfigTable OBJECT-TYPE SYNTAX SEQUENCE OF BankConfigEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Bank config table." ::= { bank 2 } bankConfigEntry OBJECT-TYPE SYNTAX BankConfigEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single entry containing bank config info." INDEX { staId, bankId } ::= { bankConfigTable 1 } BankConfigEntry ::= SEQUENCE { bankConfigName DisplayString, bankConfigMinCurThresh INTEGER, bankConfigMaxCurThresh INTEGER, bankConfigMinVolThresh INTEGER, bankConfigMaxVolThresh INTEGER, bankConfigMinPowerThresh INTEGER, bankConfigMaxPowerThresh INTEGER, bankConfigMaxPDThresh INTEGER } bankConfigName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the name of the bank. When this model does not support the OID, we show n/a. string length: 0~15 If the station is not available, it returns 'station N/A'. NOTE: Input string as /empty to set this object to NULL." ::= { bankConfigEntry 1 } bankConfigMinCurThresh OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the bank minimum electric current measurement threshold. Example: range 0.0 ~16.0 represents 0~160 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { bankConfigEntry 2 } bankConfigMaxCurThresh OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the bank maximum electric current measurement threshold. Example: range 0.0 ~16.0 represents 0~160 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { bankConfigEntry 3 } bankConfigMinVolThresh OBJECT-TYPE SYNTAX INTEGER (-2000000 | -3000 | 900..2600) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the bank minimum voltage measurement threshold. Example: range 90.0 ~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { bankConfigEntry 4 } bankConfigMaxVolThresh OBJECT-TYPE SYNTAX INTEGER (-2000000 | -3000 | 900..2600) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the bank maximum voltage measurement threshold. Example: range 90.0 ~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { bankConfigEntry 5 } bankConfigMinPowerThresh OBJECT-TYPE SYNTAX INTEGER (-2000000 | -3000 | 0..99999) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the bank minimum power measurement threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { bankConfigEntry 6 } bankConfigMaxPowerThresh OBJECT-TYPE SYNTAX INTEGER (-2000000 | -3000 | 0..99999) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the bank maximum power measurement threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { bankConfigEntry 7 } bankConfigMaxPDThresh OBJECT-TYPE SYNTAX INTEGER (-2000000 | -3000 | 0..999990) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the bank maximum power dissipation measurement threshold. Example: range 0.0 ~ 99999.0 represents 0~999990 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { bankConfigEntry 8 } --------------------------------------------------------------------------------------------------- -- bankControlTable --------------------------------------------------------------------------------------------------- bankControlTable OBJECT-TYPE SYNTAX SEQUENCE OF BankControlEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Bank control table." ::= { bank 3 } bankControlEntry OBJECT-TYPE SYNTAX BankControlEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single entry containing bank control info." INDEX { staId, bankId } ::= { bankControlTable 1 } BankControlEntry ::= SEQUENCE { bankControlOperation INTEGER } bankControlOperation OBJECT-TYPE SYNTAX INTEGER { staNotAvailable(-3000000), off(1), on(2), reboot(3), nostatus(4), not-support(5) } MAX-ACCESS read-write STATUS current DESCRIPTION "This function is used for outlet control of bank. Set off(1) to turn off for outlet control of bank. Set on(2) to turn on for all outlet control of bank. Set reboot(3) to reboot for outlet control of bank. Get this object always return nostatus(3), because there is no bank status. If the station is not available, it returns value -3000000." ::= { bankControlEntry 1 } --------------------------------------------------------------------------------------------------- -- bankReadingTable --------------------------------------------------------------------------------------------------- bankReadingTable OBJECT-TYPE SYNTAX SEQUENCE OF BankReadingEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Bank reading table." ::= { bank 4 } bankReadingEntry OBJECT-TYPE SYNTAX BankReadingEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single entry containing bank reading info." INDEX { staId, bankId } ::= { bankReadingTable 1 } BankReadingEntry ::= SEQUENCE { bankReadingCur INTEGER, bankReadingVol INTEGER, bankReadingPower INTEGER, bankReadingPD INTEGER, bankReadingPF INTEGER } bankReadingCur OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Bank electric current value. This value indicates that 10,000 times. If this measurement value is not available, it returns value -1000000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { bankReadingEntry 1 } bankReadingVol OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Bank voltage value. This value indicates that 10,000 times. If this measurement value is not available, it returns value -1000000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { bankReadingEntry 2 } bankReadingPower OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Bank power value. This value indicates that 10,000 times. If this measurement value is not available, it returns value -1000000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { bankReadingEntry 3 } bankReadingPD OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Bank power dissipation value. This value indicates that 10,000 times. If this measurement value is not available, it returns value -1000000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { bankReadingEntry 4 } bankReadingPF OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Bank power Factor value. This value indicates that 100 times. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { bankReadingEntry 5 } --------------------------------------------------------------------------------------------------- -- outletStatusTable --------------------------------------------------------------------------------------------------- outletStatusTable OBJECT-TYPE SYNTAX SEQUENCE OF OutletStatusEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Outlet status table." ::= { outlet 1 } outletStatusEntry OBJECT-TYPE SYNTAX OutletStatusEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single entry containing outlet status info." INDEX { staId, outletId } ::= { outletStatusTable 1 } OutletStatusEntry ::= SEQUENCE { outletId INTEGER, outletStatusRatedCur INTEGER, outletStatusSwitchable INTEGER, outletStatusAutoPing INTEGER, outletStatusPhaseLayout INTEGER } outletId OBJECT-TYPE SYNTAX INTEGER (1..42) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Outlet ID." ::= { outletStatusEntry 1 } outletStatusRatedCur OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Outlet Max Current value. unit: (0.1mA). If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { outletStatusEntry 2 } outletStatusSwitchable OBJECT-TYPE SYNTAX INTEGER { staNotAvailable(-3000000), not-support(-2000000), no(1), yes(2) } MAX-ACCESS read-only STATUS current DESCRIPTION "Outlet switchable. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { outletStatusEntry 3 } outletStatusAutoPing OBJECT-TYPE SYNTAX INTEGER { staNotAvailable(-3000000), not-support(-2000000), na(1), online(2), not-reachable(3) } MAX-ACCESS read-only STATUS current DESCRIPTION "Outlet latest auto-ping result. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { outletStatusEntry 4 } outletStatusPhaseLayout OBJECT-TYPE SYNTAX INTEGER { staNotAvailable(-3000000), not-support(-2000000), l1-n(1), l2-n(2), l3-n(3), l1-l2(4), l2-l3(5), l3-l1(6) } MAX-ACCESS read-only STATUS current DESCRIPTION "Display the phase layout of outlet. Example: range 1 ~ 3 represents Line1-LineNeutral ~ Line3-lineNeutral. 4 ~ 6 represents Line1-Line2, Line2-Line3, Line3-Line1. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { outletStatusEntry 5 } --------------------------------------------------------------------------------------------------- -- outletConfigTable --------------------------------------------------------------------------------------------------- outletConfigTable OBJECT-TYPE SYNTAX SEQUENCE OF OutletConfigEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Outlet config table." ::= { outlet 2 } outletConfigEntry OBJECT-TYPE SYNTAX OutletConfigEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single entry containing outlet config info." INDEX { staId, outletId } ::= { outletConfigTable 1 } OutletConfigEntry ::= SEQUENCE { outletConfigName DisplayString, outletConfigConfirmationEn INTEGER, outletConfigOnDelayTime INTEGER, outletConfigOffDelayTime INTEGER, outletConfigShutdownMethod INTEGER, outletConfigMAC MacAddress, outletConfigLocalAccessLock INTEGER, outletConfigMinCurThresh INTEGER, outletConfigMaxCurThresh INTEGER, outletConfigMinVolThresh INTEGER, outletConfigMaxVolThresh INTEGER, outletConfigMinPowerThresh INTEGER, outletConfigMaxPowerThresh INTEGER, outletConfigMaxPDThresh INTEGER, outletConfigAutoPingContFailTimes INTEGER, outletConfigAutoPingIntervalSec INTEGER, outletConfigAutoPingRetryTimes INTEGER, outletConfigAutoPingPowerUpDelaySec INTEGER, outletConfigAutoPingRemoteIPAddr IpAddress, outletConfigAutoPingEnable INTEGER, outletConfigAutoPingEnableReboot INTEGER } outletConfigName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the name of the outlet. If the station does not support this OID, we show n/a. string length: 0~48 If the station is not available, it returns 'station N/A'. NOTE: Input string as /empty to set this object to NULL." ::= { outletConfigEntry 1 } outletConfigConfirmationEn OBJECT-TYPE SYNTAX INTEGER { staNotAvailable(-3000000), no(1), yes(2) , noauth(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the confirmation of the outlet. If the station is not available, it returns value -3000000." ::= { outletConfigEntry 2 } outletConfigOnDelayTime OBJECT-TYPE SYNTAX INTEGER (-1 | 0..999) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the ON delay time of the outlet. When this model does not support the OID, we show value -1. If the station is not available, it returns value -3000000." ::= { outletConfigEntry 3 } outletConfigOffDelayTime OBJECT-TYPE SYNTAX INTEGER (-1 | 0..999) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the OFF delay time of the outlet. When this model does not support the OID, we show value -1. If the station is not available, it returns value -3000000." ::= { outletConfigEntry 4 } outletConfigShutdownMethod OBJECT-TYPE SYNTAX INTEGER { staNotAvailable(-3000000), kill-the-power(1), wake-on-lan(2), after-ac-back(3), not-support(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the shutdown method of the outlet. If the station is not available, it returns value -3000000." ::= { outletConfigEntry 5 } outletConfigMAC OBJECT-TYPE SYNTAX MacAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the MAC address of shutdown method. The value is hex format with length 12. If the station does not support this OID, it return '00-00-00-00-00-00'. If the station is not available, it returns '00-00-00-00-00-00'." ::= { outletConfigEntry 6 } outletConfigLocalAccessLock OBJECT-TYPE SYNTAX INTEGER { staNotAvailable(-3000000), unlocked(1), locked(2), not-support(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set whether the local access of the outlet is locked by remote or not. If the station is not available, it returns value -3000000." ::= { outletConfigEntry 7 } outletConfigMinCurThresh OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the outlet minimum electric current measurement threshold. Example: range 0.0 ~16.0 represents 0~160 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { outletConfigEntry 8 } outletConfigMaxCurThresh OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the outlet maximum electric current measurement threshold. Example: range 0.0 ~16.0 represents 0~160 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { outletConfigEntry 9 } outletConfigMinVolThresh OBJECT-TYPE SYNTAX INTEGER (-2000000 | -3000 | 900..2600) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the outlet minimum voltage measurement threshold. Example: range 90.0 ~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { outletConfigEntry 10 } outletConfigMaxVolThresh OBJECT-TYPE SYNTAX INTEGER (-2000000 | -3000 | 900..2600) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the outlet maximum voltage measurement threshold. Example: range 90.0 ~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { outletConfigEntry 11 } outletConfigMinPowerThresh OBJECT-TYPE SYNTAX INTEGER (-2000000 | -3000 | 0..99999) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the outlet minimum power measurement threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { outletConfigEntry 12 } outletConfigMaxPowerThresh OBJECT-TYPE SYNTAX INTEGER (-2000000 | -3000 | 0..99999) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the outlet maximum power measurement threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { outletConfigEntry 13 } outletConfigMaxPDThresh OBJECT-TYPE SYNTAX INTEGER (-2000000 | -3000 | 0..999990) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the outlet maximum power dissipation measurement threshold. Example: range 0.0 ~ 99999.0 represents 0~999990 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { outletConfigEntry 14 } outletConfigAutoPingContFailTimes OBJECT-TYPE SYNTAX INTEGER (-2000000 | -3000 | 0..10) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the outlet auto-ping continuously-failed time to reset outlet. Example: range 0 ~ 5 Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { outletConfigEntry 15 } outletConfigAutoPingIntervalSec OBJECT-TYPE SYNTAX INTEGER (-2000000 | -3000 | 0..60) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the outlet auto-ping pinging interval in seconds. Example: range 10 ~ 600 Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { outletConfigEntry 16 } outletConfigAutoPingRetryTimes OBJECT-TYPE SYNTAX INTEGER (-2000000 | -3000 | 0..10) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the outlet auto-ping max retry times. Example: range 0 ~ 5 Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { outletConfigEntry 17 } outletConfigAutoPingPowerUpDelaySec OBJECT-TYPE SYNTAX INTEGER (-2000000 | -3000 | 0..60) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the outlet auto-ping first-ping-delay in seconds after outlet switches on. Example: range 10 ~ 600 Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { outletConfigEntry 18 } outletConfigAutoPingRemoteIPAddr OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Outlet auto-ping destination IP address. If the station does not support this OID, it returns value '0.0.0.0'. If the station is not available, it returns '0.0.0.0'." ::= { outletConfigEntry 19 } outletConfigAutoPingEnable OBJECT-TYPE SYNTAX INTEGER { staNotAvailable(-3000000), not-support(-2000000), disable(1), enable(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the outlet auto-ping enable state. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { outletConfigEntry 20 } outletConfigAutoPingEnableReboot OBJECT-TYPE SYNTAX INTEGER { staNotAvailable(-3000000), not-support(-2000000), disable(1), enable(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the outlet auto-ping reboot enable state. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { outletConfigEntry 21 } --------------------------------------------------------------------------------------------------- -- outletControlTable --------------------------------------------------------------------------------------------------- outletControlTable OBJECT-TYPE SYNTAX SEQUENCE OF OutletControlEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Outlet control table." ::= { outlet 3 } outletControlEntry OBJECT-TYPE SYNTAX OutletControlEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single entry containing outlet control info." INDEX { staId, outletId } ::= { outletControlTable 1 } OutletControlEntry ::= SEQUENCE { outletControlOperation INTEGER } outletControlOperation OBJECT-TYPE SYNTAX INTEGER { staNotAvailable(-3000000), off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8) } MAX-ACCESS read-write STATUS current DESCRIPTION "This function is used for the outlet control. Set off(1) to turn off the outlet. Set on(2) to turn on the outlet. Set reboot(3) to reboot the outlet. pending(3), fault(5), noauth(6), not-suport(7), pop(8) can't be set. If the station is not available, it returns value -3000000." ::= { outletControlEntry 1 } --------------------------------------------------------------------------------------------------- -- outletReadingTable --------------------------------------------------------------------------------------------------- outletReadingTable OBJECT-TYPE SYNTAX SEQUENCE OF OutletReadingEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Outlet reading table." ::= { outlet 4 } outletReadingEntry OBJECT-TYPE SYNTAX OutletReadingEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single entry containing outlet reading info." INDEX { staId, outletId } ::= { outletReadingTable 1 } OutletReadingEntry ::= SEQUENCE { outletReadingCur INTEGER, outletReadingVol INTEGER, outletReadingPower INTEGER, outletReadingPD INTEGER, outletReadingPF INTEGER } outletReadingCur OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Outlet electric current value. This value indicates that 10,000 times. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { outletReadingEntry 1 } outletReadingVol OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Outlet voltage value. This value indicates that 10,000 times. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { outletReadingEntry 2 } outletReadingPower OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Outlet power value. This value indicates that 10,000 times. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { outletReadingEntry 3 } outletReadingPD OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Outlet power dissipation value. This value indicates that 10,000 times. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { outletReadingEntry 4 } outletReadingPF OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Outlet Power Factor value. This value indicates that 100 times. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { outletReadingEntry 5 } --------------------------------------------------------------------------------------------------- -- outletAutoPingIpTable --------------------------------------------------------------------------------------------------- outletAutoPingIpTable OBJECT-TYPE SYNTAX SEQUENCE OF OutletAutoPingIpEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Outlet auto-ping table." ::= { outlet 5 } outletAutoPingIpEntry OBJECT-TYPE SYNTAX OutletAutoPingIpEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single entry containing outlet auto-ping ip info." INDEX { staId, outletId } ::= { outletAutoPingIpTable 1 } OutletAutoPingIpEntry ::= SEQUENCE { outletConfigAutoPingRemoteIPType InetAddressType, outletConfigAutoPingRemoteIP InetAddress } outletConfigAutoPingRemoteIPType OBJECT-TYPE SYNTAX InetAddressType {ipv4(1), ipv6(2)} MAX-ACCESS read-only STATUS current DESCRIPTION "Represents the type of the corresponding instance of outletConfigAutoPingRemoteIP object. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { outletAutoPingIpEntry 1 } outletConfigAutoPingRemoteIP OBJECT-TYPE SYNTAX InetAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Outlet auto-ping destination IP address. If the station does not support this OID, it returns value '0.0.0.0'. If the station is not available, it returns '0.0.0.0'." ::= { outletAutoPingIpEntry 2 } --------------------------------------------------------------------------------------------------- -- lineStatusTable --------------------------------------------------------------------------------------------------- lineStatusTable OBJECT-TYPE SYNTAX SEQUENCE OF LineStatusEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Line status table." ::= { line 1 } lineStatusEntry OBJECT-TYPE SYNTAX LineStatusEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single entry containing line status info." INDEX { staId, lineId } ::= { lineStatusTable 1 } LineStatusEntry ::= SEQUENCE { lineId INTEGER, lineStatusRatedCur INTEGER } lineId OBJECT-TYPE SYNTAX INTEGER (1..3) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Line ID." ::= { lineStatusEntry 1 } lineStatusRatedCur OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "The Max Line Current value. unit: (0.1mA) If the station is not available, it returns value -3000000." ::= { lineStatusEntry 2 } --------------------------------------------------------------------------------------------------- -- lineConfigTable --------------------------------------------------------------------------------------------------- lineConfigTable OBJECT-TYPE SYNTAX SEQUENCE OF LineConfigEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Line config table." ::= { line 2 } lineConfigEntry OBJECT-TYPE SYNTAX LineConfigEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single entry containing line config info." INDEX { staId, lineId } ::= { lineConfigTable 1 } LineConfigEntry ::= SEQUENCE { lineConfigMinCurThresh INTEGER, lineConfigMaxCurThresh INTEGER, lineConfigMinVolThresh INTEGER, lineConfigMaxVolThresh INTEGER, lineConfigMinPowerThresh INTEGER, lineConfigMaxPowerThresh INTEGER } lineConfigMinCurThresh OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the line Minimum current measurement threshold. Example: range 0.0 ~16.0 represents 0~160 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { lineConfigEntry 1 } lineConfigMaxCurThresh OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the line Maximum electric current measurement threshold. Example: range 0.0 ~16.0 represents 0~160 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { lineConfigEntry 2 } lineConfigMinVolThresh OBJECT-TYPE SYNTAX INTEGER (-2000000 | -3000 | 900..3800) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the line minimum voltage measurement threshold. Example: range 90.0 ~380.0 represents 900~3800 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { lineConfigEntry 3 } lineConfigMaxVolThresh OBJECT-TYPE SYNTAX INTEGER (-2000000 | -3000 | 900..3800) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the line maximum voltage measurement threshold. Example: range 90.0 ~380.0 represents 900~3800 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { lineConfigEntry 4 } lineConfigMinPowerThresh OBJECT-TYPE SYNTAX INTEGER (-2000000 | -3000 | 0..99999) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the line minimum power measurement threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { lineConfigEntry 5 } lineConfigMaxPowerThresh OBJECT-TYPE SYNTAX INTEGER (-2000000 | -3000 | 0..99999) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the line maximum power measurement threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { lineConfigEntry 6 } --------------------------------------------------------------------------------------------------- -- lineReadingTable --------------------------------------------------------------------------------------------------- lineReadingTable OBJECT-TYPE SYNTAX SEQUENCE OF LineReadingEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Line reading table." ::= { line 3 } lineReadingEntry OBJECT-TYPE SYNTAX LineReadingEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single entry containing line reading info." INDEX { staId, lineId } ::= { lineReadingTable 1 } LineReadingEntry ::= SEQUENCE { lineReadingCur INTEGER, lineReadingVol INTEGER, lineReadingPower INTEGER } lineReadingCur OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Line current value. This value indicates that 10,000 times. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { lineReadingEntry 1 } lineReadingVol OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Line voltage value. This value indicates that 10,000 times. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { lineReadingEntry 2 } lineReadingPower OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Line power value. This value indicates that 10,000 times. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { lineReadingEntry 3 } --------------------------------------------------------------------------------------------------- -- neutralStatusTable --------------------------------------------------------------------------------------------------- neutralStatusTable OBJECT-TYPE SYNTAX SEQUENCE OF NeutralStatusEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Line reading table." ::= { line 4 } neutralStatusEntry OBJECT-TYPE SYNTAX NeutralStatusEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single entry containing line reading info." INDEX { staId } ::= { neutralStatusTable 1 } NeutralStatusEntry ::= SEQUENCE { neutralStatusLeakageCur INTEGER } neutralStatusLeakageCur OBJECT-TYPE SYNTAX INTEGER { staNotAvailable(-3000000), no-detection(1), detection(2), not-support(3) } MAX-ACCESS read-only STATUS current DESCRIPTION "Neutral leakage current status. If the station is not available, it returns value -3000000." ::= { neutralStatusEntry 1 } --------------------------------------------------------------------------------------------------- -- inletStatusTable --------------------------------------------------------------------------------------------------- inletStatusTable OBJECT-TYPE SYNTAX SEQUENCE OF InletStatusEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Inlet status table." ::= { inlet 1 } inletStatusEntry OBJECT-TYPE SYNTAX InletStatusEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single entry containing inlet status info." INDEX { staId, inletId } ::= { inletStatusTable 1 } InletStatusEntry ::= SEQUENCE { inletId INTEGER, inletStatusRatedCur INTEGER } inletId OBJECT-TYPE SYNTAX INTEGER (1..3) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Line ID." ::= { inletStatusEntry 1 } inletStatusRatedCur OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "The Inlet Max Current value. unit: (0.1mA). If device is phase wye, then means L1 or L2 or L3 current. If device is phase delta, then means L1L2 or L2L3 or L3L1 current. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { inletStatusEntry 2 } --------------------------------------------------------------------------------------------------- -- inletConfigTable --------------------------------------------------------------------------------------------------- inletConfigTable OBJECT-TYPE SYNTAX SEQUENCE OF InletConfigEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Inlet config table." ::= { inlet 2 } inletConfigEntry OBJECT-TYPE SYNTAX InletConfigEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single entry containing inlet config info." INDEX { staId, inletId } ::= { inletConfigTable 1 } InletConfigEntry ::= SEQUENCE { inletConfigMinCurThresh INTEGER, inletConfigMaxCurThresh INTEGER, inletConfigMinVolThresh INTEGER, inletConfigMaxVolThresh INTEGER, inletConfigMinPowerThresh INTEGER, inletConfigMaxPowerThresh INTEGER, inletConfigMaxPDThresh INTEGER } inletConfigMinCurThresh OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the inlet Minimum current measurement threshold. Example: range 0.0 ~16.0 represents 0~160 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { inletConfigEntry 1 } inletConfigMaxCurThresh OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the inlet Maximum electric current measurement threshold. Example: range 0.0 ~16.0 represents 0~160 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { inletConfigEntry 2 } inletConfigMinVolThresh OBJECT-TYPE SYNTAX INTEGER (-2000000 | -3000 | 900..3800) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the inlet minimum voltage measurement threshold. Example: range 90.0 ~380.0 represents 900~3800 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { inletConfigEntry 3 } inletConfigMaxVolThresh OBJECT-TYPE SYNTAX INTEGER (-2000000 | -3000 | 900..3800) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the inlet maximum voltage measurement threshold. Example: range 90.0 ~380.0 represents 900~3800 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { inletConfigEntry 4 } inletConfigMinPowerThresh OBJECT-TYPE SYNTAX INTEGER (-2000000 | -3000 | 0..99999) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the inlet minimum power measurement threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { inletConfigEntry 5 } inletConfigMaxPowerThresh OBJECT-TYPE SYNTAX INTEGER (-2000000 | -3000 | 0..99999) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the inlet maximum power measurement threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { inletConfigEntry 6 } inletConfigMaxPDThresh OBJECT-TYPE SYNTAX INTEGER (-2000000 | -3000 | 0..999990) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the inlet maximum power dissipation measurement threshold. Example: range 0.0 ~ 99999.0 represents 0~999990 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { inletConfigEntry 7 } --------------------------------------------------------------------------------------------------- -- inletReadingTable --------------------------------------------------------------------------------------------------- inletReadingTable OBJECT-TYPE SYNTAX SEQUENCE OF InletReadingEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Inlet reading table." ::= { inlet 3 } inletReadingEntry OBJECT-TYPE SYNTAX InletReadingEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single entry containing inlet reading info." INDEX { staId, inletId } ::= { inletReadingTable 1 } InletReadingEntry ::= SEQUENCE { inletReadingCur INTEGER, inletReadingVol INTEGER, inletReadingPower INTEGER, inletReadingPD INTEGER } inletReadingCur OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Inlet current value. If device is phase wye, then means L1 or L2 or L3 current. If device is phase delta, then means L1L2 or L2L3 or L3L1 current. This value indicates that 10,000 times. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { inletReadingEntry 1 } inletReadingVol OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Inlet voltage value. If device is phase wye, then means L1 or L2 or L3 voltage. If device is phase delta, then means L1L2 or L2L3 or L3L1 voltage. This value indicates that 10,000 times. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { inletReadingEntry 2 } inletReadingPower OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Inlet power value. If device is phase wye, then means L1 or L2 or L3 power. If device is phase delta, then means L1L2 or L2L3 or L3L1 power. This value indicates that 10,000 times. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { inletReadingEntry 3 } inletReadingPD OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Inlet power value. If device is phase wye, then means L1 or L2 or L3 power dissipation. If device is phase delta, then means L1L2 or L2L3 or L3L1 power dissipation. This value indicates that 10,000 times. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { inletReadingEntry 4 } --------------------------------------------------------------------------------------------------- -- sensorConfigTable --------------------------------------------------------------------------------------------------- sensorConfigTable OBJECT-TYPE SYNTAX SEQUENCE OF SensorConfigEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Sensor config table. Use port/addr as indexes to access sensor configurations." ::= { sensor 3 } sensorConfigEntry OBJECT-TYPE SYNTAX SensorConfigEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single entry containing sensor config info." INDEX { staId, sensorPort, sensorAddr } ::= { sensorConfigTable 1 } SensorConfigEntry ::= SEQUENCE { sensorPort INTEGER, sensorAddr INTEGER, sensorConfigMinTempThresh INTEGER, sensorConfigMaxTempThresh INTEGER, sensorConfigMinHumThresh INTEGER, sensorConfigMaxHumThresh INTEGER, sensorConfigMinPressThresh INTEGER, sensorConfigMaxPressThresh INTEGER } sensorPort OBJECT-TYPE SYNTAX INTEGER (1..4) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Sensor Port Number." ::= { sensorConfigEntry 1 } sensorAddr OBJECT-TYPE SYNTAX INTEGER (1..31) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Sensor Address." ::= { sensorConfigEntry 2 } sensorConfigMinTempThresh OBJECT-TYPE SYNTAX INTEGER (-3000 | -200..600) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set sensor minimum temperature measurement threshold. Example: range -20.0 ~ 60.0 represents -200~600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { sensorConfigEntry 3 } sensorConfigMaxTempThresh OBJECT-TYPE SYNTAX INTEGER (-3000 | -200..600) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set sensor maximum temperature measurement threshold. Example: range -20.0 ~ 60.0 represents -200~600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { sensorConfigEntry 4 } sensorConfigMinHumThresh OBJECT-TYPE SYNTAX INTEGER (-3000 | 100..950) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set sensor minimum humidity measurement threshold. Example: range 10.0 ~ 95.0 represents 100~950 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { sensorConfigEntry 5 } sensorConfigMaxHumThresh OBJECT-TYPE SYNTAX INTEGER (-3000 | 100..950) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set sensor maximum humidity measurement threshold. Example: range 10.0 ~ 95.0 represents 100~950 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { sensorConfigEntry 6 } sensorConfigMinPressThresh OBJECT-TYPE SYNTAX INTEGER (-3000 | -2500..2500) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set sensor minimum pressure measurement threshold. Example: range -250.0 ~ 250.0 represents -2500 ~ 2500 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { sensorConfigEntry 7 } sensorConfigMaxPressThresh OBJECT-TYPE SYNTAX INTEGER (-3000 | -2500..2500) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set sensor maximum pressure measurement threshold. Example: range -250.0 ~ 250.0 represents -2500 ~ 2500 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { sensorConfigEntry 8 } --------------------------------------------------------------------------------------------------- -- sensorReadingTable --------------------------------------------------------------------------------------------------- sensorReadingTable OBJECT-TYPE SYNTAX SEQUENCE OF SensorReadingEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Sensor reading table. Use port/addr as indexes to access sensor readings." ::= { sensor 4 } sensorReadingEntry OBJECT-TYPE SYNTAX SensorReadingEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single entry containing sensor reading info." INDEX { staId, sensorPort, sensorAddr } ::= { sensorReadingTable 1 } SensorReadingEntry ::= SEQUENCE { sensorReadingTemp INTEGER, sensorReadingHum INTEGER, sensorReadingPress INTEGER } sensorReadingTemp OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Sensor's Temperature value. This value indicates that 1,000 times. If this measurement value is not available, it returns value -1000000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { sensorReadingEntry 1 } sensorReadingHum OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Sensor's Humidity value. This value indicates that 1,000 times. If this measurement value is not available, it returns value -1000000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { sensorReadingEntry 2 } sensorReadingPress OBJECT-TYPE SYNTAX INTEGER MAX-ACCESS read-only STATUS current DESCRIPTION "Sensor's Pressure value. This value indicates that 1,000 times. If this measurement value is not available, it returns value -1000000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { sensorReadingEntry 3 } --------------------------------------------------------------------------------------------------- -- dryContactStatusTable --------------------------------------------------------------------------------------------------- dryContactStatusTable OBJECT-TYPE SYNTAX SEQUENCE OF DryContactStatusEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Dry contact status table." ::= { dryContact 1 } dryContactStatusEntry OBJECT-TYPE SYNTAX DryContactStatusEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single entry containing dry contact status info." INDEX { staId, dryContactId } ::= { dryContactStatusTable 1 } DryContactStatusEntry ::= SEQUENCE { dryContactId INTEGER, dryContactStatus INTEGER } dryContactId OBJECT-TYPE SYNTAX INTEGER (1..2) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Dry contact ID." ::= { dryContactStatusEntry 1 } dryContactStatus OBJECT-TYPE SYNTAX INTEGER { staNotAvailable(-3000000), close(0), open(1), not-attached(2), not-support(10) } MAX-ACCESS read-only STATUS current DESCRIPTION "Display dry contact status. close(0) represents door close. open(1) represents door open. not-attached(2) represents door sensor don't attach to device. If the station is not available, it returns value -3000000." ::= { dryContactStatusEntry 2 } --------------------------------------------------------------------------------------------------- -- dryContactConfigTable --------------------------------------------------------------------------------------------------- dryContactConfigTable OBJECT-TYPE SYNTAX SEQUENCE OF DryContactConfigEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Dry contact config table." ::= { dryContact 2 } dryContactConfigEntry OBJECT-TYPE SYNTAX DryContactConfigEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single entry containing dry contact config info." INDEX { staId, dryContactId } ::= { dryContactConfigTable 1 } DryContactConfigEntry ::= SEQUENCE { dryContactConfigType INTEGER } dryContactConfigType OBJECT-TYPE SYNTAX INTEGER { staNotAvailable(-3000000), notinstalled(0), photo(1), inductiveproximity(2), reed(3), waterleakage(4), smoke(5), not-support(10) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set dry contact type. If the station is not available, it returns value -3000000." ::= { dryContactConfigEntry 1 } --------------------------------------------------------------------------------------------------- -- netStatusTable --------------------------------------------------------------------------------------------------- netStatusTable OBJECT-TYPE SYNTAX SEQUENCE OF NetStatusEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Net status table." ::= { network 1 } netStatusEntry OBJECT-TYPE SYNTAX NetStatusEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single entry containing net status info." INDEX { staId } ::= { netStatusTable 1 } NetStatusEntry ::= SEQUENCE { netStatusMAC MacAddress } netStatusMAC OBJECT-TYPE SYNTAX MacAddress MAX-ACCESS read-only STATUS current DESCRIPTION "Station MAC address. The value is hex format with length 12. If the station does not support this OID, it return '00-00-00-00-00-00'. If the station is not available, it returns '00-00-00-00-00-00'." ::= { netStatusEntry 1 } --------------------------------------------------------------------------------------------------- -- httpConfigTable --------------------------------------------------------------------------------------------------- httpConfigTable OBJECT-TYPE SYNTAX SEQUENCE OF HttpConfigEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "HTTP config table." ::= { network 2 } httpConfigEntry OBJECT-TYPE SYNTAX HttpConfigEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single entry containing HTTP config info." INDEX { staId } ::= { httpConfigTable 1 } HttpConfigEntry ::= SEQUENCE { httpConfigHttpPort INTEGER, httpConfigHttpsPort INTEGER, httpConfigHttpsOnlyEn INTEGER } httpConfigHttpPort OBJECT-TYPE SYNTAX INTEGER (1..65535) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the HTTP port of the station. If the station is not available, it returns value -3000000." ::= { httpConfigEntry 1 } httpConfigHttpsPort OBJECT-TYPE SYNTAX INTEGER (1..65535) MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set the HTTPs port of the station. If the station is not available, it returns value -3000000." ::= { httpConfigEntry 2 } httpConfigHttpsOnlyEn OBJECT-TYPE SYNTAX INTEGER { staNotAvailable(-3000000), no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set whether to use HTTPS only or HTTP/HTTPS for the web page. If the station is not available, it returns value -3000000." ::= { httpConfigEntry 3 } --------------------------------------------------------------------------------------------------- -- netConfigTable --------------------------------------------------------------------------------------------------- netConfigTable OBJECT-TYPE SYNTAX SEQUENCE OF NetConfigEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Net config table." ::= { network 3 } netConfigEntry OBJECT-TYPE SYNTAX NetConfigEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single entry containing net config info." INDEX { staId, netCablePort } ::= { netConfigTable 1 } NetConfigEntry ::= SEQUENCE { netCablePort INTEGER, netConfigAutoIP INTEGER, netConfigIPv4 IpAddress, netConfigSubMask IpAddress, netConfigGateway IpAddress, netConfigAutoDNS INTEGER, netConfigPreferDNSIPv4 IpAddress, netConfigAlterDNSIPv4 IpAddress } netCablePort OBJECT-TYPE SYNTAX INTEGER (1..2) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Network Port Number." ::= { netConfigEntry 1 } netConfigAutoIP OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set IPv4 address automatically or not" ::= { netConfigEntry 2 } netConfigIPv4 OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set fixed IPv4 address" ::= { netConfigEntry 3 } netConfigSubMask OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set subnet mask address" ::= { netConfigEntry 4 } netConfigGateway OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set gateway address" ::= { netConfigEntry 5 } netConfigAutoDNS OBJECT-TYPE SYNTAX INTEGER { no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set DNS address automatically or not" ::= { netConfigEntry 6 } netConfigPreferDNSIPv4 OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set prefer DNS address" ::= { netConfigEntry 7 } netConfigAlterDNSIPv4 OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set alternate DNS address" ::= { netConfigEntry 8 } --------------------------------------------------------------------------------------------------- -- trapConfigTable --------------------------------------------------------------------------------------------------- trapConfigTable OBJECT-TYPE SYNTAX SEQUENCE OF TrapConfigEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Trap config table." ::= { trap 1 } trapConfigEntry OBJECT-TYPE SYNTAX TrapConfigEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single entry containing trap config info." INDEX { staId } ::= { trapConfigTable 1 } TrapConfigEntry ::= SEQUENCE { trapConfigEn INTEGER, trapConfigVer INTEGER } trapConfigEn OBJECT-TYPE SYNTAX INTEGER { staNotAvailable(-3000000), no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set whether this trap entry is enabled or not. You should set the username/auth-password/priv-password first, when choosing snmpv3. You should set the community string first, when choosing snmpv1/v2c. If the station is not available, it returns value -3000000." ::= { trapConfigEntry 1 } trapConfigVer OBJECT-TYPE SYNTAX INTEGER { staNotAvailable(-3000000), v1(1), v2c(2), v3(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set SNMP trap version for sending trap. You should set the username/auth-password/priv-password first, when choosing snmpv3. You should set the community string first, when choosing snmpv1/v2c. If the station is not available, it returns value -3000000." ::= { trapConfigEntry 2 } --------------------------------------------------------------------------------------------------- -- trapReceiverConfigTable --------------------------------------------------------------------------------------------------- trapReceiverConfigTable OBJECT-TYPE SYNTAX SEQUENCE OF TrapReceiverConfigEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "SNMP agent trap setup table. If users want to use trap, they must set enable trap, IP and community first." ::= { trap 2 } trapReceiverConfigEntry OBJECT-TYPE SYNTAX TrapReceiverConfigEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single entry containing trap receiver config info." INDEX { staId, trapReceiverConfigIdx } ::= { trapReceiverConfigTable 1 } TrapReceiverConfigEntry ::= SEQUENCE { trapReceiverConfigIdx INTEGER, trapReceiverConfigIp IpAddress, trapReceiverConfigPort INTEGER, trapReceiverConfigCommunity DisplayString, trapReceiverConfigUsername DisplayString, trapReceiverConfigAuthPwd DisplayString, trapReceiverConfigPrivacyPwd DisplayString } trapReceiverConfigIdx OBJECT-TYPE SYNTAX INTEGER (1..2) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Index of trap receiver." ::= { trapReceiverConfigEntry 1 } trapReceiverConfigIp OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Trap receiver IP address. If the station does not support this OID, it returns value '0.0.0.0'. If the station is not available, it returns '0.0.0.0'." ::= { trapReceiverConfigEntry 2 } trapReceiverConfigPort OBJECT-TYPE SYNTAX INTEGER (1..65535) MAX-ACCESS read-write STATUS current DESCRIPTION "NMS trap port to be used by agent to send trap. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { trapReceiverConfigEntry 3 } trapReceiverConfigCommunity OBJECT-TYPE SYNTAX DisplayString (SIZE (0..20)) MAX-ACCESS read-write STATUS current DESCRIPTION "If use SNMPv1/v2c to receive trap should set this community string. MAX string length: 20 If the station does not support this OID, it returns value 'not-support'. If the station is not available, it returns 'station N/A'. NOTE: Input string as /empty to set this object to NULL." ::= { trapReceiverConfigEntry 4 } trapReceiverConfigUsername OBJECT-TYPE SYNTAX DisplayString (SIZE (0..20)) MAX-ACCESS read-write STATUS current DESCRIPTION "If use SNMPv3 to receive trap should set this username string. MAX string length: 20. If the station does not support this OID, it returns value 'not-support'. If the station is not available, it returns 'station N/A'. NOTE: Input string as /empty to set this object to NULL." ::= { trapReceiverConfigEntry 5 } trapReceiverConfigAuthPwd OBJECT-TYPE SYNTAX DisplayString (SIZE (8..20)) MAX-ACCESS read-write STATUS current DESCRIPTION "If use SNMPv3 to receive trap should set this auth password string. MAX string length: 20 If the station does not support this OID, it returns value 'not-support'. If the station is not available, it returns 'station N/A'. NOTE: Input string as /empty to set this object to NULL." ::= { trapReceiverConfigEntry 6 } trapReceiverConfigPrivacyPwd OBJECT-TYPE SYNTAX DisplayString (SIZE (8..20)) MAX-ACCESS read-write STATUS current DESCRIPTION "If use SNMPv3 to receive trap should set this privacy password string. MAX string length: 20 If the station does not support this OID, it returns value 'not-support'. If the station is not available, it returns 'station N/A'. NOTE: Input string as /empty to set this object to NULL." ::= { trapReceiverConfigEntry 7 } --------------------------------------------------------------------------------------------------- -- trapReceiverIpTable --------------------------------------------------------------------------------------------------- trapReceiverIpTable OBJECT-TYPE SYNTAX SEQUENCE OF TrapReceiverIpEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Trap Receiver Ip table." ::= { trap 3 } trapReceiverIpEntry OBJECT-TYPE SYNTAX TrapReceiverIpEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single entry containing trap receiver ip info." INDEX { staId, trapReceiverIpIdx } ::= { trapReceiverIpTable 1 } TrapReceiverIpEntry ::= SEQUENCE { trapReceiverIpIdx INTEGER, trapReceiverIpType InetAddressType, trapReceiverIp InetAddress } trapReceiverIpIdx OBJECT-TYPE SYNTAX INTEGER (1..2) MAX-ACCESS not-accessible STATUS current DESCRIPTION "Index of trap receiver." ::= { trapReceiverIpEntry 1 } trapReceiverIpType OBJECT-TYPE SYNTAX InetAddressType {ipv4(1), ipv6(2)} MAX-ACCESS read-only STATUS current DESCRIPTION "Represents the type of the corresponding instance of trapReceiverIp object. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000." ::= { trapReceiverIpEntry 2 } trapReceiverIp OBJECT-TYPE SYNTAX InetAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Outlet auto-ping destination IP address. If the station does not support this OID, it returns value '0.0.0.0'. If the station is not available, it returns '0.0.0.0'." ::= { trapReceiverIpEntry 3 } --------------------------------------------------------------------------------------------------- -- trapNotifConfigTable --------------------------------------------------------------------------------------------------- trapNotifConfigTable OBJECT-TYPE SYNTAX SEQUENCE OF TrapNotifConfigEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Trap notification config table." ::= { trapNotification 1 } trapNotifConfigEntry OBJECT-TYPE SYNTAX TrapNotifConfigEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single entry containing trap notification config info." INDEX { staId } ::= { trapNotifConfigTable 1 } TrapNotifConfigEntry ::= SEQUENCE { trapNotifConfigEn INTEGER } trapNotifConfigEn OBJECT-TYPE SYNTAX INTEGER { staNotAvailable(-3000000), no(1), yes(2) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display or set whether this trap entry is enabled or not. You should set the username/auth-password/priv-password first, when choosing snmpv3. You should set the community string first, when choosing snmpv1/v2c. If the station is not available, it returns value -3000000." ::= { trapNotifConfigEntry 1 } --------------------------------------------------------------------------------------------------- -- trapNotifAlarmTable --------------------------------------------------------------------------------------------------- trapNotifAlarmTable OBJECT-TYPE SYNTAX SEQUENCE OF TrapNotifAlarmEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Trap notification alarm table." ::= { trapNotification 2 } trapNotifAlarmEntry OBJECT-TYPE SYNTAX TrapNotifAlarmEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Single entry containing trap notification alarm info." INDEX { staId } ::= { trapNotifAlarmTable 1 } TrapNotifAlarmEntry ::= SEQUENCE { trapNotifAlarmBreakerStatus INTEGER, trapNotifAlarmCurrentStatus INTEGER, trapNotifAlarmVoltageStatus INTEGER, trapNotifAlarmPowerStatus INTEGER, trapNotifAlarmSensorStatus INTEGER } trapNotifAlarmBreakerStatus OBJECT-TYPE SYNTAX INTEGER { staNotAvailable(-3000000), normal(0), alarm(1) } MAX-ACCESS read-only STATUS current DESCRIPTION "Station breaker alarm status. If the station is not available, it returns value -3000000." ::= { trapNotifAlarmEntry 1 } trapNotifAlarmCurrentStatus OBJECT-TYPE SYNTAX INTEGER { staNotAvailable(-3000000), normal(0), alarm(1) } MAX-ACCESS read-only STATUS current DESCRIPTION "Station current alarm status. If the station is not available, it returns value -3000000." ::= { trapNotifAlarmEntry 2 } trapNotifAlarmVoltageStatus OBJECT-TYPE SYNTAX INTEGER { staNotAvailable(-3000000), normal(0), alarm(1) } MAX-ACCESS read-only STATUS current DESCRIPTION "Station voltage alarm status. If the station is not available, it returns value -3000000." ::= { trapNotifAlarmEntry 3 } trapNotifAlarmPowerStatus OBJECT-TYPE SYNTAX INTEGER { staNotAvailable(-3000000), normal(0), alarm(1) } MAX-ACCESS read-only STATUS current DESCRIPTION "Station power alarm status. If the station is not available, it returns value -3000000." ::= { trapNotifAlarmEntry 4 } trapNotifAlarmSensorStatus OBJECT-TYPE SYNTAX INTEGER { staNotAvailable(-3000000), normal(0), alarm(1) } MAX-ACCESS read-only STATUS current DESCRIPTION "Station sensor alarm status. If the station is not available, it returns value -3000000." ::= { trapNotifAlarmEntry 5 } --------------------------------------------------------------------------------------------------- -- trapNotifEvent --------------------------------------------------------------------------------------------------- trapNotifEvent NOTIFICATION-TYPE STATUS current DESCRIPTION "Display trap notification alarm status." ::= { trapNotification 3 } --------------------------------------------------------------------------------------------------- -- deviceLock --------------------------------------------------------------------------------------------------- staCommunityLock OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Change SNMPV1 or SNMPV2 community for California passes law. Please follow the format as readcommunity||writecommunity" ::= { deviceLock 1 } staPasswordLock OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Change SNMPV3 password for California passes law. Please follow the format as authpassword||privpassword" ::= { deviceLock 2 } END