-- SiteBoss 220 MIB -- v 1.01 06/13/13 -- Copyright (c) 2013 by Asentria Corporation. All rights reserved. SITEBOSS-220-STD-MIB DEFINITIONS ::= BEGIN IMPORTS DisplayString FROM SNMPv2-TC IpAddress, TimeTicks, Integer32, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-TYPE FROM SNMPv2-SMI asentria FROM ASENTRIA-ROOT-MIB; --*************************************************************************************** --MODULE IDENTITY --*************************************************************************************** s220 MODULE-IDENTITY LAST-UPDATED "201306130101Z" ORGANIZATION "Asentria Corporation" CONTACT-INFO "Phone: 206-344-8800 Fax: 206-344-2116 Email: support@asentria.com" DESCRIPTION "MIB module for managing Asentria SiteBoss 220" REVISION "201306130101Z" DESCRIPTION "-v1.01 -Added missing esPointConfigAITable branch (UTSK-7). -Applicable since unit version 1.01.002." REVISION "201306070100Z" DESCRIPTION "-v1.00 -Initial release" ::= { asentria 43 } --1.3.6.1.4.1.3052.43 --*************************************************************************************** --MIB View --*************************************************************************************** -- status .1 -- eventSensorStatus .1.1 -- esPointTable .1.1.1 -- esPointEntry .1.1.1.1 -- esIndexES .1.1.1.1.1 -- esIndexPC .1.1.1.1.2 -- esIndexPoint .1.1.1.1.3 -- esPointName .1.1.1.1.4 -- esPointInEventState .1.1.1.1.5 -- esPointValueInt .1.1.1.1.6 -- esPointValueStr .1.1.1.1.7 -- config .2 -- eventSensorBasics .2.1 -- eventSensorPointConfig .2.2 -- esPointConfigTempTable .2.2.1 -- esPointConfigTempEntry .2.2.1.1 -- espcTempIndexES .2.2.1.1.1 -- espcTempIndexPoint .2.2.1.1.2 -- espcTempEnable .2.2.1.1.3 -- espcTempName .2.2.1.1.4 -- espcTempScale .2.2.1.1.5 -- espcTempDeadband .2.2.1.1.6 -- espcTempVHighTemp .2.2.1.1.7 -- espcTempVHighClass .2.2.1.1.9 -- espcTempHighTemp .2.2.1.1.10 -- espcTempHighClass .2.2.1.1.13 -- espcTempNormalClass .2.2.1.1.16 -- espcTempLowTemp .2.2.1.1.17 -- espcTempLowClass .2.2.1.1.20 -- espcTempVLowTemp .2.2.1.1.21 -- espcTempVLowClass .2.2.1.1.24 -- espcTempActions .2.2.1.1.25 -- esPointConfigCCTable .2.2.2 -- esPointConfigCCEntry .2.2.2.1 -- espcCCIndexES .2.2.2.1.1 -- espcCCIndexPoint .2.2.2.1.2 -- espcCCEnable .2.2.2.1.3 -- espcCCName .2.2.2.1.4 -- espcCCEventState .2.2.2.1.5 -- espcCCThreshold .2.2.2.1.6 -- espcCCActions .2.2.2.1.7 -- espcCCEventClass .2.2.2.1.9 -- espcCCNormalClass .2.2.2.1.12 -- espcCCAlarmAlias .2.2.2.1.13 -- espcCCNormalAlias .2.2.2.1.14 -- esPointConfigHumidTable .2.2.3 -- esPointConfigHumidEntry .2.2.3.1 -- espcHumidIndexES .2.2.3.1.1 -- espcHumidIndexPoint .2.2.3.1.2 -- espcHumidEnable .2.2.3.1.3 -- espcHumidName .2.2.3.1.4 -- espcHumidDeadband .2.2.3.1.5 -- espcHumidVHighHumid .2.2.3.1.6 -- espcHumidVHighClass .2.2.3.1.8 -- espcHumidHighHumid .2.2.3.1.9 -- espcHumidHighClass .2.2.3.1.12 -- espcHumidLowHumid .2.2.3.1.16 -- espcHumidLowClass .2.2.3.1.19 -- espcHumidVLowHumid .2.2.3.1.20 -- espcHumidVLowClass .2.2.3.1.23 -- espcHumidActions .2.2.3.1.24 -- esPointConfigAITable .2.2.5 -- esPointConfigAIEntry .2.2.5.1 -- espcAIIndexES .2.2.5.1.1 -- espcAIIndexPoint .2.2.5.1.2 -- espcAIEnable .2.2.5.1.3 -- espcAIName .2.2.5.1.4 -- espcAIDeadband .2.2.5.1.5 -- espcAIVhighValue .2.2.5.1.6 -- espcAIVhighClass .2.2.5.1.8 -- espcAIHighValue .2.2.5.1.9 -- espcAIHighClass .2.2.5.1.12 -- espcAILowValue .2.2.5.1.16 -- espcAILowClass .2.2.5.1.19 -- espcAIVlowValue .2.2.5.1.20 -- espcAIVlowClass .2.2.5.1.23 -- espcAIActions .2.2.5.1.24 -- espcAIConvUnitName .2.2.5.1.25 -- espcAIConvLowValue .2.2.5.1.26 -- espcAIConvLowUnit .2.2.5.1.27 -- espcAIConvHighValue .2.2.5.1.28 -- espcAIConvHighUnit .2.2.5.1.29 -- esPointConfigRelayTable .2.2.6 -- esPointConfigRelayEntry .2.2.6.1 -- espcRelayIndexES .2.2.6.1.1 -- espcRelayIndexPoint .2.2.6.1.2 -- espcRelayEnable .2.2.6.1.3 -- espcRelayName .2.2.6.1.4 -- network .2.4 -- ethernet .2.4.1 -- ipAddress .2.4.1.1 -- subnetMask .2.4.1.2 -- router .2.4.1.3 -- snmp .2.4.8 -- snmpReadCommunity .2.4.8.2 -- snmpWriteCommunity .2.4.8.3 -- snmpTrapCommunity .2.4.8.4 -- snmpTable .2.4.8.6 -- snmpEntry .2.4.8.6.1 -- snmpIndex .2.4.8.6.1.1 -- snmpAddress .2.4.8.6.1.2 -- snmpTestMail .2.4.8.7 -- email .2.4.17 -- emailServer .2.4.17.1 -- emailDomain .2.4.17.2 -- emailAuthEnable .2.4.17.3 -- emailAuthUsername .2.4.17.4 -- emailAuthPassword .2.4.17.5 -- emailTable .2.4.17.6 -- emailEntry .2.4.17.6.1 -- emailIndex .2.4.17.6.1.1 -- emailAddress .2.4.17.6.1.2 -- emailTestMail .2.4.17.7 -- dateTime .2.8 -- date .2.8.1 -- time .2.8.2 -- autodst .2.8.3 -- action .2.14 -- actionSystemAlertAction .2.14.1 -- actionPowerupAlertEnable .2.14.2 -- actionRTNAlertsEnable .2.14.3 -- actionAlarmRepeatFrequency .2.14.4 -- sys .2.16 -- sysSerial .2.16.1 -- sysVersion .2.16.2 -- sysBuild .2.16.3 -- sysSitename .2.16.4 -- sysProduct .2.16.5 -- thisTrapText .2.16.6 --*************************************************************************************** --TOP-LEVEL OBJECT IDENTIFIERS --*************************************************************************************** notification OBJECT IDENTIFIER ::= { s220 0 } --1.3.6.1.4.1.3052.43.0 status OBJECT IDENTIFIER ::= { s220 1 } --1.3.6.1.4.1.3052.43.1 eventSensorStatus OBJECT IDENTIFIER ::= { status 1 } --1.3.6.1.4.1.3052.43.1.1 config OBJECT IDENTIFIER ::= { s220 2 } --1.3.6.1.4.1.3052.43.2 eventSensorPointConfig OBJECT IDENTIFIER ::= { config 2 } --1.3.6.1.4.1.3052.43.2.2 network OBJECT IDENTIFIER ::= { config 4 } --1.3.6.1.4.1.3052.43.2.4 ethernet OBJECT IDENTIFIER ::= { network 1 } --1.3.6.1.4.1.3052.43.2.4.1 snmp OBJECT IDENTIFIER ::= { network 8 } --1.3.6.1.4.1.3052.43.2.4.8 email OBJECT IDENTIFIER ::= { network 17 } --1.3.6.1.4.1.3052.43.2.4.17 dateTime OBJECT IDENTIFIER ::= { config 8 } --1.3.6.1.4.1.3052.43.2.8 action OBJECT IDENTIFIER ::= { config 14 } --1.3.6.1.4.1.3052.43.2.14 sys OBJECT IDENTIFIER ::= { config 16 } --1.3.6.1.4.1.3052.43.2.16 --*************************************************************************************** --OBJECT DEFINITIONS --*************************************************************************************** --*************************************************************************************** --EventSensor Status Section 1.1 --*************************************************************************************** esPointTable OBJECT-TYPE SYNTAX SEQUENCE OF ESPoint MAX-ACCESS not-accessible STATUS current DESCRIPTION " This table organizes 4 basic attributes of points. A point is a particular sensor on an EventSensor (e.g., temperature, humidity, contact closure 2, relay 5, etc.). The 4 point attributes are its name, whether it's in its event state, the point's value as a number and its value as a string. Points are referenced by a point index. The point index is a string of 3 numbers separated by periods. It contains all the information necessary for getting a piece of data off an event sensor; namely, which EventSensor, point class, and which-sensor-of-that-class (a.k.a. point). " ::= { eventSensorStatus 1 } --1.3.6.1.4.1.3052.43.1.1.1 esPointEntry OBJECT-TYPE SYNTAX ESPoint MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for EventSensor point table" INDEX { esIndexES, esIndexPC, esIndexPoint } ::= { esPointTable 1 } --1.3.6.1.4.1.3052.43.1.1.1.1 esIndexES OBJECT-TYPE SYNTAX Integer32 (1..200) MAX-ACCESS read-only STATUS current DESCRIPTION "The part of the point index that refers to an EventSensor. The point index is a string of 3 numbers separated by periods. It contains all the information necessary for getting a piece of data off an event sensor; namely, which EventSensor, point class, and which-sensor-of-that-class (a.k.a. point). This object's allowable values are 1 through 16, and 200. 200 always refers to the EventSensor inside the unit. 1 through 16 refer to additional attached EventSensors. The number corresponding to an EventSensor is determined by the user at the initial configuration time. If there is an internal sensor in the unit, it will always be the first item in the Sensor Events setup menu. For example, if a new EventSensor is configured as the 2nd entry AFTER the internal EventSensor (if one exists) in the Sensor Events Setup Menu, then that EventSensor will be known from then on as EventSensor 2. All point indeces with esIndexES=2 will now refer to that particular EventSensor. " ::= { esPointEntry 1 } --1.3.6.1.4.1.3052.43.1.1.1.1.1 esIndexPC OBJECT-TYPE SYNTAX Integer32 (1..6) MAX-ACCESS read-only STATUS current DESCRIPTION "The part of the point index that refers to point class. The point index is a string of 3 numbers separated by periods. It contains all the information necessary for getting a piece of data off an event sensor; namely, which EventSensor, point class, and which-sensor-of-that-class (a.k.a. point). The values for this object are: 1=temperature sensor 2=contact closure 3=humidity sensor 4=noise sensor 5=analog input 6=relay " ::= { esPointEntry 2 } --1.3.6.1.4.1.3052.43.1.1.1.1.2 esIndexPoint OBJECT-TYPE SYNTAX Integer32 (1..64) MAX-ACCESS read-only STATUS current DESCRIPTION "The part of the point index that delineates which sensor on the EventSensor. So this combined with esIndexPC (Point Class or type) and esIndexES (which EventSensor) uniquely defines each point (sensor or relay) attached to a unit. For example, if esIndexES is 3, esIndexPC is 1 and esIndexPoint is 4 then this is the Fourth Temperature Sensor on EventSensor number 3." ::= { esPointEntry 3 } --1.3.6.1.4.1.3052.43.1.1.1.1.3 esPointName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "The name of the point on an EventSensor. For example, 'AC temp' (in the case of the temperature sensor on an EventSensor). There can be multiple points of the same point class on an EventSensor (e.g., 8 contact closures) and multiple sensor classes on an EventSensor (e.g., temperature, contact closure, humidity). If the point referenced by a given point index is solitary (e.g., temperature sensor, because there can be only one on an EventSensor), then this object reads as ''. Setting this object for solitary point indices sets the EventSensor name only. On the other hand, if a given point is among other points of the same point class on an EventSensor, then this object reads as ''. Setting this object for these NON- solitary point indices sets the sensor name only - not the EventSensor name." ::= { esPointEntry 4 } --1.3.6.1.4.1.3052.43.1.1.1.1.4 esPointInEventState OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "A number referring to the event state of a point on an EventSensor. This number can have different meanings depending on the point class. If the point class is temperature, humidity, or analog input, then the values of this object are: 1=very low 2=low 3=normal 4=high 5=very high For contact closures the values of this object are: 1=point in event state 2=point in normal state For relays the values of this object are: 1=relay energized (active) 2=relay de-energized (inactive) For any point class and any point, if the event state is undefined, then the value of this object is 0. For any point class except relay, this object is read-only. For relays, setting this object to 1 puts the relay into its active (energized) state. Setting it to 2 puts the relay into its inactive (de-energized) state. Setting it to any value greater than 2 puts the relay into its active state for that many seconds (up to 3600), after which time it puts the relay into its inactive state. " ::= { esPointEntry 5 } --1.3.6.1.4.1.3052.43.1.1.1.1.5 esPointValueInt OBJECT-TYPE SYNTAX Integer32 (-32768..32767) MAX-ACCESS read-write STATUS current DESCRIPTION "A read-only number referring to the value of a point on an EventSensor. If the point class is temperature, then this object is the temperature in its configured scale (default is Fahrenheit). If the point class is contact closure or relay, then this object is either 0 (open) or 1 (closed). If the point class is humidity, then this object is the percent relative humidity. If the point class is analog input, then this object is the signed input value in tenths of the configured units. If the point class is relay, then this object is either 1 (active a.k.a. energized) or 0 (inactive a.k.a. de-energized). This object cannot be used to control the relay (use esPointInEventState for that). " ::= { esPointEntry 6 } --1.3.6.1.4.1.3052.43.1.1.1.1.6 esPointValueStr OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-only STATUS current DESCRIPTION "A string referring to the value of a point on an EventSensor. For contact closures this object is either 'Open' or 'Closed'. For relays this object is either 'Active' (energized) or 'Inactive' (de-energized). For temperature and humidity point classes, this object is the string representation of the esPointValueInt object. For temperature, 'C' or 'F' is including in the string to indicate scale. For analog inputs, this object is the string representation of the plus/minus input in the configured units appended with the unit name. " ::= { esPointEntry 7 } --1.3.6.1.4.1.3052.43.1.1.1.1.7 --*************************************************************************************** --EventSensor Point Config Section 2.2 --*************************************************************************************** esPointConfigTempTable OBJECT-TYPE SYNTAX SEQUENCE OF ESPointConfigTemp MAX-ACCESS not-accessible STATUS current DESCRIPTION "This table organizes 3 basic attributes of temperature sensor points. A point is a particular sensor on an EventSensor. The 3 point attributes organizes in this table are: 1. the configuration item (e.g., enable, name, etc.) 2. the eventsensor on which this point resides 3. the point number (always 1 for temp sensors) Points are referenced by a point config index. The point config index is a string of 2 numbers separated by periods. It contains all the information necessary for getting a piece of data off an event sensor within the context of this emperature point config table ; namely, which EventSensor, and which sensor (a.k.a. point) (always 1 for temperature sensors). " ::= { eventSensorPointConfig 1 } --1.3.6.1.4.1.3052.43.2.2.1 esPointConfigTempEntry OBJECT-TYPE SYNTAX ESPointConfigTemp MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for EventSensor point config temperature table" INDEX { espcTempIndexES, espcTempIndexPoint } ::= { esPointConfigTempTable 1 } --1.3.6.1.4.1.3052.43.2.2.1.1 espcTempIndexES OBJECT-TYPE SYNTAX Integer32 (1..200) MAX-ACCESS read-only STATUS current DESCRIPTION "The part of the point index that refers to an EventSensor. The point config index is a string of 2 numbers separated by a period. It contains all the information necessary for getting a piece of data off an event sensor within the the context of the eventsensor point config temperature table; namely, which EventSensor, and which sensor (a.k.a. point). This object's allowable values are 1 through 16, and 200. 200 always refers to the EventSensor inside the unit. 1 through 16 refer to additional attached EventSensors. The number corresponding to an EventSensor is determined by the user at the initial configuration time. If there is an internal sensor in the unit, it will always be the first item in the Sensor Events setup menu. For example, if a new EventSensor is configured as the 2nd entry AFTER the internal EventSensor (if one exists) in the Sensor Events Setup Menu, then that EventSensor will be known from then on as EventSensor 2. All point indeces with esIndexES=2 will now refer to that particular EventSensor. " ::= { esPointConfigTempEntry 1 } --1.3.6.1.4.1.3052.43.2.2.1.1.1 espcTempIndexPoint OBJECT-TYPE SYNTAX Integer32 (1..64) MAX-ACCESS read-only STATUS current DESCRIPTION "The part of the point index that delineates which sensor on the EventSensor. So this combined with espcTempIndexES (which EventSensor) uniquely defines each point attached to a unit within the context of temperature point configuration." ::= { esPointConfigTempEntry 2 } --1.3.6.1.4.1.3052.43.2.2.1.1.2 espcTempEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF enable this temperature sensor" ::= { esPointConfigTempEntry 3 } --1.3.6.1.4.1.3052.43.2.2.1.1.3 espcTempName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "The name of this temperature sensor" ::= { esPointConfigTempEntry 4 } --1.3.6.1.4.1.3052.43.2.2.1.1.4 espcTempScale OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Scale (C/F) for this temperature sensor" ::= { esPointConfigTempEntry 5 } --1.3.6.1.4.1.3052.43.2.2.1.1.5 espcTempDeadband OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Deadband for this temperature sensor" ::= { esPointConfigTempEntry 6 } --1.3.6.1.4.1.3052.43.2.2.1.1.6 espcTempVHighTemp OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Very high temperature event threshold for this temperature sensor" ::= { esPointConfigTempEntry 7 } --1.3.6.1.4.1.3052.43.2.2.1.1.7 espcTempVHighClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very high temperature event class for this temperature sensor" ::= { esPointConfigTempEntry 9 } --1.3.6.1.4.1.3052.43.2.2.1.1.9 espcTempHighTemp OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "High temperature event threshold for this temperature sensor" ::= { esPointConfigTempEntry 10 } --1.3.6.1.4.1.3052.43.2.2.1.1.10 espcTempHighClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "High temperature event class for this temperature sensor" ::= { esPointConfigTempEntry 13 } --1.3.6.1.4.1.3052.43.2.2.1.1.13 espcTempLowTemp OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Low temperature event threshold for this temperature sensor" ::= { esPointConfigTempEntry 17 } --1.3.6.1.4.1.3052.43.2.2.1.1.17 espcTempLowClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Low temperature event class for this temperature sensor" ::= { esPointConfigTempEntry 20 } --1.3.6.1.4.1.3052.43.2.2.1.1.20 espcTempVLowTemp OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Very Low temperature event threshold for this temperature sensor" ::= { esPointConfigTempEntry 21 } --1.3.6.1.4.1.3052.43.2.2.1.1.21 espcTempVLowClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very Low temperature event class for this temperature sensor" ::= { esPointConfigTempEntry 24 } --1.3.6.1.4.1.3052.43.2.2.1.1.24 espcTempActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Temperature event Action" ::= { esPointConfigTempEntry 25 } --1.3.6.1.4.1.3052.43.2.2.1.1.25 esPointConfigCCTable OBJECT-TYPE SYNTAX SEQUENCE OF ESPointConfigCC MAX-ACCESS not-accessible STATUS current DESCRIPTION "This table organizes 3 basic attributes of contact closure points. A point is a particular sensor on an EventSensor. The 3 point attributes organizes in this table are: 1. the configuration item (e.g., enable, name, etc.) 2. the eventsensor on which this point resides 3. the point number Points are referenced by a point config index. The point config index is a string of 2 numbers separated by a period. It contains all the information necessary for getting a piece of data off an event sensor within the context of this contact closure point config table ; namely, which EventSensor and which sensor. " ::= { eventSensorPointConfig 2 } --1.3.6.1.4.1.3052.43.2.2.2 esPointConfigCCEntry OBJECT-TYPE SYNTAX ESPointConfigCC MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for EventSensor point config contact closure table" INDEX { espcCCIndexES, espcCCIndexPoint } ::= { esPointConfigCCTable 1 } --1.3.6.1.4.1.3052.43.2.2.2.1 espcCCIndexES OBJECT-TYPE SYNTAX Integer32 (1..200) MAX-ACCESS read-only STATUS current DESCRIPTION "The part of the point index that refers to an EventSensor. The point config index is a string of 2 numbers separated by a period. It contains all the information necessary for getting a piece of data off an event sensor within the the context of the eventsensor point config contact closure table; namely, which EventSensor and which sensor (a.k.a. point). This object's allowable values are 1 through 16, and 200. 200 always refers to the EventSensor inside the unit. 1 through 16 refer to additional attached EventSensors. " ::= { esPointConfigCCEntry 1 } --1.3.6.1.4.1.3052.43.2.2.2.1.1 espcCCIndexPoint OBJECT-TYPE SYNTAX Integer32 (1..64) MAX-ACCESS read-only STATUS current DESCRIPTION "The part of the point index that delineates which sensor on the EventSensor. So this combined with espcCCIndexES (which EventSensor) uniquely defines each point attached to a unit within the context of contact closure point configuration." ::= { esPointConfigCCEntry 2 } --1.3.6.1.4.1.3052.43.2.2.2.1.2 espcCCEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF enable for this contact closure" ::= { esPointConfigCCEntry 3 } --1.3.6.1.4.1.3052.43.2.2.2.1.3 espcCCName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Name for this contact closure" ::= { esPointConfigCCEntry 4 } --1.3.6.1.4.1.3052.43.2.2.2.1.4 espcCCEventState OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Event state for this contact closure" ::= { esPointConfigCCEntry 5 } --1.3.6.1.4.1.3052.43.2.2.2.1.5 espcCCThreshold OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Threshold (seconds) for this contact closure" ::= { esPointConfigCCEntry 6 } --1.3.6.1.4.1.3052.43.2.2.2.1.6 espcCCActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Event class for this contact closure" ::= { esPointConfigCCEntry 7 } --1.3.6.1.4.1.3052.43.2.2.2.1.7 espcCCEventClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Event class for this contact closure" ::= { esPointConfigCCEntry 9 } --1.3.6.1.4.1.3052.43.2.2.2.1.9 espcCCNormalClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Return-to-normal class for this contact closure" ::= { esPointConfigCCEntry 12 } --1.3.6.1.4.1.3052.43.2.2.2.1.12 espcCCAlarmAlias OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Event alias for this contact closure" ::= { esPointConfigCCEntry 13 } --1.3.6.1.4.1.3052.43.2.2.2.1.13 espcCCNormalAlias OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Return-to-normal alias for this contact closure" ::= { esPointConfigCCEntry 14 } --1.3.6.1.4.1.3052.43.2.2.2.1.14 esPointConfigHumidTable OBJECT-TYPE SYNTAX SEQUENCE OF ESPointConfigHumid MAX-ACCESS not-accessible STATUS current DESCRIPTION "This table organizes 3 basic attributes of humidity points. A point is a particular sensor on an EventSensor. The 3 point attributes organizes in this table are: 1. the configuration item (e.g., enable, name, etc.) 2. the eventsensor on which this point resides 3. the point number (always 1 for humidity sensors) Points are referenced by a point config index. The point config index is a string of 2 numbers separated by a period. It contains all the information necessary for getting a piece of data off an event sensor within the context of this humidity point config table ; namely, which EventSensor and which sensor. " ::= { eventSensorPointConfig 3 } --1.3.6.1.4.1.3052.43.2.2.3 esPointConfigHumidEntry OBJECT-TYPE SYNTAX ESPointConfigHumid MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for EventSensor point config humidity table" INDEX { espcHumidIndexES, espcHumidIndexPoint } ::= { esPointConfigHumidTable 1 } --1.3.6.1.4.1.3052.43.2.2.3.1 espcHumidIndexES OBJECT-TYPE SYNTAX Integer32 (1..200) MAX-ACCESS read-only STATUS current DESCRIPTION "The part of the point index that refers to an EventSensor. The point config index is a string of 2 numbers separated by a period. It contains all the information necessary for getting a piece of data off an event sensor within the the context of the eventsensor point config contact closure table; namely, which EventSensor and which sensor (a.k.a. point). This object's allowable values are 1 through 16, and 200. 200 always refers to the EventSensor inside the unit. 1 through 16 refer to additional attached EventSensors. " ::= { esPointConfigHumidEntry 1 } --1.3.6.1.4.1.3052.43.2.2.3.1.1 espcHumidIndexPoint OBJECT-TYPE SYNTAX Integer32 (1..64) MAX-ACCESS read-only STATUS current DESCRIPTION "The part of the point index that delineates which sensor on the EventSensor. So this combined with espcHumidIndexES (which EventSensor) uniquely defines each point attached to a unit within the context of contact closure point configuration." ::= { esPointConfigHumidEntry 2 } --1.3.6.1.4.1.3052.43.2.2.3.1.2 espcHumidEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF enable for this humidity sensor" ::= { esPointConfigHumidEntry 3 } --1.3.6.1.4.1.3052.43.2.2.3.1.3 espcHumidName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "The name for this humidity sensor" ::= { esPointConfigHumidEntry 4 } --1.3.6.1.4.1.3052.43.2.2.3.1.4 espcHumidDeadband OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Deadband for this humidity sensor" ::= { esPointConfigHumidEntry 5 } --1.3.6.1.4.1.3052.43.2.2.3.1.5 espcHumidVHighHumid OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Very high event threshold for this humidity sensor" ::= { esPointConfigHumidEntry 6 } --1.3.6.1.4.1.3052.43.2.2.3.1.6 espcHumidVHighClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very high event class for this humidity sensor" ::= { esPointConfigHumidEntry 8 } --1.3.6.1.4.1.3052.43.2.2.3.1.8 espcHumidHighHumid OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "High event threshold for this humidity sensor" ::= { esPointConfigHumidEntry 9 } --1.3.6.1.4.1.3052.43.2.2.3.1.9 espcHumidHighClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "High event class for this humidity sensor" ::= { esPointConfigHumidEntry 12 } --1.3.6.1.4.1.3052.43.2.2.3.1.12 espcHumidLowHumid OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Low event threshold for this humidity sensor" ::= { esPointConfigHumidEntry 16 } --1.3.6.1.4.1.3052.43.2.2.3.1.16 espcHumidLowClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Low event class for this humidity sensor" ::= { esPointConfigHumidEntry 19 } --1.3.6.1.4.1.3052.43.2.2.3.1.19 espcHumidVLowHumid OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Very low event threshold for this humidity sensor" ::= { esPointConfigHumidEntry 20 } --1.3.6.1.4.1.3052.43.2.2.3.1.20 espcHumidVLowClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very low event class for this humidity sensor" ::= { esPointConfigHumidEntry 23 } --1.3.6.1.4.1.3052.43.2.2.3.1.23 espcHumidActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Humidity event actions for this humidity sensor" ::= { esPointConfigHumidEntry 24 } --1.3.6.1.4.1.3052.43.2.2.3.1.24 esPointConfigAITable OBJECT-TYPE SYNTAX SEQUENCE OF ESPointConfigAnalogInput MAX-ACCESS not-accessible STATUS current DESCRIPTION "This table organizes 3 basic attributes of analog input points. A point is a particular sensor on an EventSensor. The 3 point attributes organizes in this table are: 1. the configuration item (e.g., enable, name, etc.) 2. the eventsensor on which this point resides 3. the point number Points are referenced by a point config index. The point config index is a string of 2 numbers separated by a period. It contains all the information necessary for getting a piece of data off an event sensor within the context of this analog input point config table ; namely, which EventSensor and which sensor. " ::= { eventSensorPointConfig 5 } --1.3.6.1.4.1.3052.8.2.2.5 esPointConfigAIEntry OBJECT-TYPE SYNTAX ESPointConfigAnalogInput MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for EventSensor point config analog input table" INDEX { espcHumidIndexES, espcHumidIndexPoint } ::= { esPointConfigAITable 1 } --1.3.6.1.4.1.3052.8.2.2.5.1 espcAIIndexES OBJECT-TYPE SYNTAX Integer32 (1..200) MAX-ACCESS read-only STATUS current DESCRIPTION "The part of the point index that refers to an EventSensor. The point config index is a string of 2 numbers separated by a period. It contains all the information necessary for getting a piece of data off an event sensor within the the context of the eventsensor point config contact closure table; namely, which EventSensor and which sensor (a.k.a. point). This object's allowable values are 1 through 16, and 200. 200 always refers to the EventSensor inside the unit. 1 through 16 refer to additional attached EventSensors. " ::= { esPointConfigAIEntry 1 } --1.3.6.1.4.1.3052.43.2.2.5.1.1 espcAIIndexPoint OBJECT-TYPE SYNTAX Integer32 (1..64) MAX-ACCESS read-only STATUS current DESCRIPTION "The part of the point index that delineates which sensor on the EventSensor. So this combined with espcAIIndexES (which EventSensor) uniquely defines each point attached to a unit within the context of contact closure point configuration." ::= { esPointConfigAIEntry 2 } --1.3.6.1.4.1.3052.43.2.2.5.1.2 espcAIEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF for this analog input sensor" ::= { esPointConfigAIEntry 3 } --1.3.6.1.4.1.3052.43.2.2.5.1.3 espcAIName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Name for this analog input sensor" ::= { esPointConfigAIEntry 4 } --1.3.6.1.4.1.3052.43.2.2.5.1.4 espcAIDeadband OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Deadband for this analog input sensor" ::= { esPointConfigAIEntry 5 } --1.3.6.1.4.1.3052.43.2.2.5.1.5 espcAIVhighValue OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Very high event threshold (decivolts or tenths of milliamps) for this analog input sensor" ::= { esPointConfigAIEntry 6 } --1.3.6.1.4.1.3052.43.2.2.5.1.6 espcAIVhighClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very high event class for this analog input sensor" ::= { esPointConfigAIEntry 8 } --1.3.6.1.4.1.3052.43.2.2.5.1.8 espcAIHighValue OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "High event threshold (decivolts or tenths of milliamps) for this analog input sensor" ::= { esPointConfigAIEntry 9 } --1.3.6.1.4.1.3052.43.2.2.5.1.9 espcAIHighClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "High event class for this analog input sensor" ::= { esPointConfigAIEntry 12 } --1.3.6.1.4.1.3052.43.2.2.5.1.12 espcAILowValue OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Low event threshold (decivolts or tenths of milliamps) for this analog input sensor" ::= { esPointConfigAIEntry 16 } --1.3.6.1.4.1.3052.43.2.2.5.1.16 espcAILowClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Low event class for this analog input sensor" ::= { esPointConfigAIEntry 19 } --1.3.6.1.4.1.3052.43.2.2.5.1.19 espcAIVlowValue OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Very low event threshold (decivolts or tenths of milliamps) for this analog input sensor" ::= { esPointConfigAIEntry 20 } --1.3.6.1.4.1.3052.43.2.2.5.1.20 espcAIVlowClass OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Very low event class for this analog input sensor" ::= { esPointConfigAIEntry 23 } --1.3.6.1.4.1.3052.43.2.2.5.1.23 espcAIActions OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Event actions for this analog input sensor" ::= { esPointConfigAIEntry 24 } --1.3.6.1.4.1.3052.43.2.2.5.1.24 espcAIConvUnitName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Conversion unit name for this analog input sensor" ::= { esPointConfigAIEntry 25 } --1.3.6.1.4.1.3052.43.2.2.5.1.25 espcAIConvLowValue OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Conversion low value for this analog input sensor" ::= { esPointConfigAIEntry 26 } --1.3.6.1.4.1.3052.43.2.2.5.1.26 espcAIConvLowUnit OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Conversion low unit value for this analog input sensor" ::= { esPointConfigAIEntry 27 } --1.3.6.1.4.1.3052.43.2.2.5.1.27 espcAIConvHighValue OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Conversion high value for this analog input sensor" ::= { esPointConfigAIEntry 28 } --1.3.6.1.4.1.3052.43.2.2.5.1.28 espcAIConvHighUnit OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Conversion high unit value for this analog input sensor" ::= { esPointConfigAIEntry 29 } --1.3.6.1.4.1.3052.43.2.2.5.1.29 esPointConfigRelayTable OBJECT-TYPE SYNTAX SEQUENCE OF ESPointConfigRelay MAX-ACCESS not-accessible STATUS current DESCRIPTION "This table organizes 3 basic attributes of relay points. A point is a particular sensor on an EventSensor. The 3 point attributes organizes in this table are: 1. the configuration item (e.g., enable, name, etc.) 2. the eventsensor on which this point resides 3. the point number Points are referenced by a point config index. The point config index is a string of 2 numbers separated by a period. It contains all the information necessary for getting a piece of data off an event sensor within the context of this relay point config table ; namely, which EventSensor and which sensor. " ::= { eventSensorPointConfig 6 } --1.3.6.1.4.1.3052.43.2.2.6 esPointConfigRelayEntry OBJECT-TYPE SYNTAX ESPointConfigRelay MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for EventSensor point config relay table" INDEX { espcRelayIndexES, espcRelayIndexPoint } ::= { esPointConfigRelayTable 1 } --1.3.6.1.4.1.3052.43.2.2.6.1 espcRelayIndexES OBJECT-TYPE SYNTAX Integer32 (1..200) MAX-ACCESS read-only STATUS current DESCRIPTION "The part of the point index that refers to an EventSensor. The point config index is a string of 2 numbers separated by a period. It contains all the information necessary for getting a piece of data off an event sensor within the the context of the eventsensor point config relay table; namely, which EventSensor and which sensor (a.k.a. point). This object's allowable values are 1 through 16, and 200. 200 always refers to the EventSensor inside the unit. 1 through 16 refer to additional attached EventSensors. " ::= { esPointConfigRelayEntry 1 } --1.3.6.1.4.1.3052.43.2.2.6.1.1 espcRelayIndexPoint OBJECT-TYPE SYNTAX Integer32 (1..64) MAX-ACCESS read-only STATUS current DESCRIPTION "The part of the point index that delineates which sensor on the EventSensor. So this combined with espcRelayIndexES (which EventSensor) uniquely defines each point attached to a unit within the context of relay point configuration." ::= { esPointConfigRelayEntry 2 } --1.3.6.1.4.1.3052.43.2.2.6.1.2 espcRelayEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF enable for this relay" ::= { esPointConfigRelayEntry 3 } --1.3.6.1.4.1.3052.43.2.2.6.1.3 espcRelayName OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Name for this relay" ::= { esPointConfigRelayEntry 4 } --1.3.6.1.4.1.3052.43.2.2.6.1.4 --*************************************************************************************** --Network Section 2.4 --*************************************************************************************** ipAddress OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet IP address" ::= { ethernet 1 } --1.3.6.1.4.1.3052.43.2.4.1.1 subnetMask OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet subnet mask" ::= { ethernet 2 } --1.3.6.1.4.1.3052.43.2.4.1.2 router OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Ethernet router" ::= { ethernet 3 } --1.3.6.1.4.1.3052.43.2.4.1.3 -- SNMP snmpReadCommunity OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "SNMP read community" ::= { snmp 2 } --1.3.6.1.4.1.3052.43.2.4.8.2 snmpWriteCommunity OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "SNMP write community" ::= { snmp 3 } --1.3.6.1.4.1.3052.43.2.4.8.3 snmpTrapCommunity OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "SNMP trap community" ::= { snmp 4 } --1.3.6.1.4.1.3052.43.2.4.8.4 snmpServerTable OBJECT-TYPE SYNTAX SEQUENCE OF ActionSNMPConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of network hosts to use for network-based actions" ::= { snmp 6 } --1.3.6.1.4.1.3052.43.2.8.6 snmpServerEntry OBJECT-TYPE SYNTAX ActionSNMPConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table of network hosts to use for network-based actions" INDEX { snmpServerIndex } ::= { snmpServerTable 1 } --1.3.6.1.4.1.3052.43.2.8.6.1 snmpServerIndex OBJECT-TYPE SYNTAX Integer32 (1..6) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of network hosts to use for network-based actions" ::= { snmpServerEntry 1 } --1.3.6.1.4.1.3052.43.2.8.6.1.1 snmpServer OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "Hostname/IP address used as destination for network-based action (e.g., trap)" ::= { snmpServerEntry 2 } --1.3.6.1.4.1.3052.43.2.8.6.1.2 snmpTestTrap OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "SNMP trap community" ::= { snmp 7 } --1.3.6.1.4.1.3052.43.2.4.8.7 -- Email emailServer OBJECT-TYPE SYNTAX IpAddress MAX-ACCESS read-write STATUS current DESCRIPTION "SMTP server to which the unit sends email" ::= { email 1 } --1.3.6.1.4.1.3052.43.2.4.17.1 emailDomain OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Domain to use in recipient address" ::= { email 2 } --1.3.6.1.4.1.3052.43.2.4.17.2 emailAuthEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF enable SMTP authentication" ::= { email 3 } --1.3.6.1.4.1.3052.43.2.4.17.3 emailAuthUsername OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Username for SMTP authentication" ::= { email 4 } --1.3.6.1.4.1.3052.43.2.4.17.4 emailAuthPassword OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Password for SMTP authentication" ::= { email 5 } --1.3.6.1.4.1.3052.43.2.4.17.5 emailTable OBJECT-TYPE SYNTAX SEQUENCE OF ActionEmailConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Table of email addresses to use for email actions" ::= { email 6 } --1.3.6.1.4.1.3052.43.2.4.17.6 emailEntry OBJECT-TYPE SYNTAX ActionEmailConfig MAX-ACCESS not-accessible STATUS current DESCRIPTION "Entry for table of email addresses to use for email actions" INDEX { emailIndex } ::= { emailTable 1 } --1.3.6.1.4.1.3052.43.2.4.17.6.1 emailIndex OBJECT-TYPE SYNTAX Integer32 (1..6) MAX-ACCESS read-only STATUS current DESCRIPTION "Index for table of email addresses to use for email actions" ::= { emailEntry 1 } --1.3.6.1.4.1.3052.43.2.4.17.6.1.1 emailAddress OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "email address" ::= { emailEntry 2 } --1.3.6.1.4.1.3052.43.2.4.17.6.1.2 emailTestMail OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Password for SMTP authentication" ::= { email 7 } --1.3.6.1.4.1.3052.43.2.4.17.7 --*************************************************************************************** --dateTime Section 2.8 --*************************************************************************************** date OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Text string for date." ::= { dateTime 1 } --1.3.6.1.4.1.3052.43.2.8.1 time OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Text string for time." ::= { dateTime 2 } --1.3.6.1.4.1.3052.43.2.8.2 autodst OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "ON/OFF automatically adjust for Daylight Savings Time" ::= { dateTime 3 } --1.3.6.1.4.1.3052.43.2.8.3 --*************************************************************************************** --Action Section 2.14 --*************************************************************************************** actionSystemAlertAction OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "System Alert Actions are actions that occur when the system needs to alert the user of something. The only time this occurs currently is a powerup alert." ::= { action 1 } --1.3.6.1.4.1.3052.43.2.14.1 actionPowerupAlertEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "action Powerup Alert Enable" ::= { action 2 } --1.3.6.1.4.1.3052.43.2.14.2 actionRTNAlertsEnable OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Return to Normal Alerts Enabled" ::= { action 3 } --1.3.6.1.4.1.3052.43.2.14.3 actionAlarmRepeatFrequency OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Frequency in minutes of repeats" ::= { action 4 } --1.3.6.1.4.1.3052.43.2.14.4 --*************************************************************************************** --System Section 2.16 --*************************************************************************************** sysSerial OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Serial Number" ::= { sys 1 } --1.3.6.1.4.1.3052.43.2.16.1 sysVersion OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Serial Number" ::= { sys 2 } --1.3.6.1.4.1.3052.43.2.16.2 sysBuild OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Serial Number" ::= { sys 3 } --1.3.6.1.4.1.3052.43.2.16.3 sysSitename OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Serial Number" ::= { sys 4 } --1.3.6.1.4.1.3052.43.2.16.4 sysProduct OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "Serial Number" ::= { sys 5 } --1.3.6.1.4.1.3052.43.2.16.5 thisTrapText OBJECT-TYPE SYNTAX DisplayString MAX-ACCESS read-write STATUS current DESCRIPTION "A text string included in all traps" ::= { sys 6 } --1.3.6.1.4.1.3052.43.2.16.6 --*************************************************************************************** --TABLE DEFINITIONS --*************************************************************************************** ESPointConfigTemp ::= SEQUENCE { espcTempIndexES Integer32, espcTempIndexPoint Integer32, espcTempEnable DisplayString, espcTempName DisplayString, espcTempScale DisplayString, espcTempDeadband Integer32, espcTempVHighTemp Integer32, espcTempVHighClass DisplayString, espcTempHighTemp Integer32, espcTempHighClass DisplayString, espcTempLowTemp Integer32, espcTempLowClass DisplayString, espcTempVLowTemp Integer32, espcTempVLowClass DisplayString, espcTempActions DisplayString } ESPointConfigCC ::= SEQUENCE { espcCCIndexES Integer32, espcCCIndexPoint Integer32, espcCCEnable DisplayString, espcCCName DisplayString, espcCCEventState DisplayString, espcCCThreshold Integer32, espcCCActions DisplayString, espcCCEventClass DisplayString, espcCCNormalClass DisplayString, espcCCAlarmAlias DisplayString, espcCCNormalAlias DisplayString } ESPointConfigHumid ::= SEQUENCE { espcHumidIndexES Integer32, espcHumidIndexPoint Integer32, espcHumidEnable DisplayString, espcHumidName DisplayString, espcHumidDeadband Integer32, espcHumidVHighHumid Integer32, espcHumidVHighClass DisplayString, espcHumidHighHumid Integer32, espcHumidHighClass DisplayString, espcHumidLowHumid Integer32, espcHumidLowClass DisplayString, espcHumidVLowHumid Integer32, espcHumidVLowClass DisplayString, espcHumidActions DisplayString } ESPointConfigAnalogInput ::= SEQUENCE { espcAIIndexES Integer32, espcAIIndexPoint Integer32, espcAIEnable DisplayString, espcAIName DisplayString, espcAIDeadband Integer32, espcAIVhighValue Integer32, espcAIVhighClass DisplayString, espcAIHighValue Integer32, espcAIHighClass DisplayString, espcAILowValue Integer32, espcAILowClass DisplayString, espcAIVlowValue Integer32, espcAIVlowClass DisplayString, espcAIActions DisplayString, espcAIConvUnitName DisplayString, espcAIConvLowValue Integer32, espcAIConvLowUnit Integer32, espcAIConvHighValue Integer32, espcAIConvHighUnit Integer32 } ESPointConfigRelay::= SEQUENCE { espcRelayIndexES Integer32, espcRelayIndexPoint Integer32, espcRelayEnable DisplayString, espcRelayName DisplayString } ActionEmailConfig ::= SEQUENCE { emailIndex Integer32, emailAddress DisplayString } ESPoint ::= SEQUENCE { esIndexES Integer32, esIndexPC Integer32, esIndexPoint Integer32, esPointName DisplayString, esPointInEventState Integer32, esPointValueInt Integer32, esPointValueStr DisplayString } ActionSNMPConfig ::= SEQUENCE { snmpServerIndex Integer32, snmpServer IpAddress } --*************************************************************************************** --TRAP DEFINITIONS --*************************************************************************************** s220PowerUpTrap NOTIFICATION-TYPE OBJECTS { thisTrapText, sysSitename } STATUS current DESCRIPTION "Sent upon System Alert at power up." ::= { s220 20000 } s220ContactTrap NOTIFICATION-TYPE OBJECTS { thisTrapText, sysSitename } STATUS current DESCRIPTION "Sent to show a contact is in the alarm state." ::= { s220 20001 } s220TempTrap NOTIFICATION-TYPE OBJECTS { thisTrapText, sysSitename } STATUS current DESCRIPTION "Sent to show temperature exceeded threshold." ::= { s220 20010 } s220HumidTrap NOTIFICATION-TYPE OBJECTS { thisTrapText, sysSitename } STATUS current DESCRIPTION "Sent to show humidity exceeded threshold" ::= { s220 20020 } s220TestTrap NOTIFICATION-TYPE OBJECTS { thisTrapText, sysSitename } STATUS current DESCRIPTION "Sent to test IP route(s) for traps." ::= { s220 22000 } END