HM2-POE-MIB DEFINITIONS ::= BEGIN -- -- ************************************************************* -- Hirschmann Power over Ethernet Management MIB -- ************************************************************* -- IMPORTS MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-TYPE, Integer32 FROM SNMPv2-SMI -- RFC 2578 SnmpAdminString FROM SNMP-FRAMEWORK-MIB hm2IfacePhysIndex FROM HM2-DEVMGMT-MIB HmEnabledStatus, HmTimeHHMM24, hm2ConfigurationMibs FROM HM2-TC-MIB; hm2PoeMgmtMib MODULE-IDENTITY LAST-UPDATED "201110310000Z" -- October 31, 2011 ORGANIZATION "Hirschmann Automation and Control GmbH" CONTACT-INFO "Postal: Stuttgarter Str. 45-51 72654 Neckartenzlingen Germany Phone: +49 7127 140 E-mail: hac.support@belden.com" DESCRIPTION "Hirschmann Power over Ethernet Management MIB. This MIB contains the private extensions to the RFC 3621. Copyright (C) 2011. All Rights Reserved." REVISION "201110310000Z" -- October 31, 2011 DESCRIPTION "Initial version." ::= { hm2ConfigurationMibs 12 } -- -- ************************************************************* -- hm2PoeMgmtMib -- ************************************************************* -- hm2PoeMgmtMibNotifications OBJECT IDENTIFIER ::= { hm2PoeMgmtMib 0 } hm2PoeMgmtMibObjects OBJECT IDENTIFIER ::= { hm2PoeMgmtMib 1 } -- hm2PoeMgmtMibConformance OBJECT IDENTIFIER ::= { hm2PoeMgmtMib 2 } -- -- ************************************************************* -- hm2PoeMgmtMib groups -- ************************************************************* -- hm2PoeMgmtGroup OBJECT IDENTIFIER ::= { hm2PoeMgmtMibObjects 1 } -- -- ************************************************************* -- hm2PoeMgmtGlobalGroup -- ************************************************************* -- hm2PoeMgmtGlobalGroup OBJECT IDENTIFIER ::= { hm2PoeMgmtGroup 1 } hm2PoeMgmtAdminStatus OBJECT-TYPE SYNTAX HmEnabledStatus MAX-ACCESS read-write STATUS current DESCRIPTION "Enables/disables Power over Ethernet management on this device." DEFVAL { enable } ::= { hm2PoeMgmtGlobalGroup 1 } hm2PoeMgmtReservedPower OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Reserved system power for active Power over Ethernet ports in Watts." ::= { hm2PoeMgmtGlobalGroup 2 } -- -- ************************************************************* -- hm2PoeMgmtPsuTable -- ************************************************************* -- hm2PoeMgmtPsuTable OBJECT-TYPE SYNTAX SEQUENCE OF Hm2PoeMgmtPsuEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "This table contains objects for each power supply type of the device (internal or external power supply)." ::= { hm2PoeMgmtGroup 2 } hm2PoeMgmtPsuEntry OBJECT-TYPE SYNTAX Hm2PoeMgmtPsuEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "The entries of the hm2PoeMgmtPsuTable." INDEX { hm2PoeMgmtModulePowerSource } ::= { hm2PoeMgmtPsuTable 1 } Hm2PoeMgmtPsuEntry ::= SEQUENCE { hm2PoeMgmtPsuPower Integer32, hm2PoeMgmtPsuReservedPower Integer32, hm2PoeMgmtPsuDeliveredPower Integer32 } hm2PoeMgmtPsuPower OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The power budget per psu type expressed in Watts. Psu types could be internal or external." ::= { hm2PoeMgmtPsuEntry 1 } hm2PoeMgmtPsuReservedPower OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The reserved power (depending on actual power classes) per psu type expressed in Watts." ::= { hm2PoeMgmtPsuEntry 2 } hm2PoeMgmtPsuDeliveredPower OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The measured usage power per psu type expressed in Watts." ::= { hm2PoeMgmtPsuEntry 3 } -- -- ************************************************************* -- hm2PoeMgmtPortTable -- ************************************************************* -- hm2PoeMgmtPortTable OBJECT-TYPE SYNTAX SEQUENCE OF Hm2PoeMgmtPortEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "This table contains objects for each Power over Ethernet interface of the device." ::= { hm2PoeMgmtGroup 3 } hm2PoeMgmtPortEntry OBJECT-TYPE SYNTAX Hm2PoeMgmtPortEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "The entry of the hm2PoeMgmtPortTable." INDEX { hm2IfacePhysIndex } ::= { hm2PoeMgmtPortTable 1 } Hm2PoeMgmtPortEntry ::= SEQUENCE { hm2PoeMgmtPortAdminEnable HmEnabledStatus, hm2PoeMgmtPortConsumptionPower Integer32, hm2PoeMgmtPortDetectionStatus INTEGER, hm2PoeMgmtPortPowerPriority INTEGER, hm2PoeMgmtPortPowerClassification INTEGER, hm2PoeMgmtPortName SnmpAdminString, hm2PoeMgmtPortAllowedClassBits BITS, hm2PoeMgmtPortAutoShutdown HmEnabledStatus, hm2PoeMgmtPortAutoShutdownTimeStart HmTimeHHMM24, hm2PoeMgmtPortAutoShutdownTimeEnd HmTimeHHMM24, hm2PoeMgmtPortClassValid INTEGER, hm2PoeMgmtPortFastStartup HmEnabledStatus, hm2PoeMgmtPortMaxConsumptionPower Integer32, hm2PoeMgmtPortPowerLimit Integer32 } hm2PoeMgmtPortAdminEnable OBJECT-TYPE SYNTAX HmEnabledStatus MAX-ACCESS read-write STATUS current DESCRIPTION "enable (1) An interface which can provide the PSE functions. disable(2) The interface will act - as it would - if it had no PSE function." DEFVAL { enable } ::= { hm2PoeMgmtPortEntry 1 } hm2PoeMgmtPortConsumptionPower OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "Measured usage power per interface expressed in Milliwatts." ::= { hm2PoeMgmtPortEntry 2 } hm2PoeMgmtPortDetectionStatus OBJECT-TYPE SYNTAX INTEGER { disabled(1), searching(2), deliveringPower(3), fault(4), test(5), otherFault(6) } MAX-ACCESS read-only STATUS current DESCRIPTION "Describes the operational status of the port PD detection. A value of disabled(1)- indicates that the PSE State diagram is in the state DISABLED. A value of deliveringPower(3) - indicates that the PSE State diagram is in the state POWER_ON. A value of fault(4) - indicates that the PSE State diagram is in the state TEST_ERROR. A value of test(5) - indicates that the PSE State diagram is in the state TEST_MODE. A value of otherFault(6) - indicates that the PSE State diagram is in the state IDLE due to the variable error_conditions. A value of searching(2)- indicates the PSE State diagram is in a state other than those listed above." ::= { hm2PoeMgmtPortEntry 3 } hm2PoeMgmtPortPowerPriority OBJECT-TYPE SYNTAX INTEGER { critical(1), high(2), low(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "This object controls the priority of the port from the point of view of a power management algorithm. The priority that is set by this variable could be used by a control mechanism that prevents over current situations by disconnecting first ports with lower power priority. Ports that connect devices critical to the operation of the network - like the E911 telephones ports - should be set to higher priority." DEFVAL { low } ::= { hm2PoeMgmtPortEntry 4 } hm2PoeMgmtPortPowerClassification OBJECT-TYPE SYNTAX INTEGER { class0(1), class1(2), class2(3), class3(4), class4(5) } MAX-ACCESS read-only STATUS current DESCRIPTION "Classification is a way to tag different terminals on the Power over LAN network according to their power consumption. Devices such as IP telephones, WLAN access points and others, will be classified according to their power requirements. The meaning of the classification labels is defined in the IEEE specification. This variable is valid only while a PD is being powered, that is, while the attribute hm2PoeMgmtPortDetectionStatus is reporting the enumeration deliveringPower." DEFVAL { class0 } ::= { hm2PoeMgmtPortEntry 5 } hm2PoeMgmtPortName OBJECT-TYPE SYNTAX SnmpAdminString (SIZE(1..32)) MAX-ACCESS read-write STATUS current DESCRIPTION "A manager will set the value of this variable to indicate the type of powered device that is connected to the port. The default value supplied by the agent if no value has ever been set should be a zero-length octet string." DEFVAL { " " } ::= { hm2PoeMgmtPortEntry 6 } hm2PoeMgmtPortAllowedClassBits OBJECT-TYPE SYNTAX BITS { class0(0), class1(1), class2(2), class3(3), class4(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Bit mask which defines allowed classes per interface." DEFVAL { { class0, class1, class2, class3, class4 } } ::= { hm2PoeMgmtPortEntry 7 } hm2PoeMgmtPortAutoShutdown OBJECT-TYPE SYNTAX HmEnabledStatus MAX-ACCESS read-write STATUS current DESCRIPTION "Enables/disables automatic shutdown functionality per interface." DEFVAL { disable } ::= { hm2PoeMgmtPortEntry 8 } hm2PoeMgmtPortAutoShutdownTimeStart OBJECT-TYPE SYNTAX HmTimeHHMM24 MAX-ACCESS read-write STATUS current DESCRIPTION "Start time for the automatic shutdown functionality per interface." DEFVAL { "00:00" } ::= { hm2PoeMgmtPortEntry 9 } hm2PoeMgmtPortAutoShutdownTimeEnd OBJECT-TYPE SYNTAX HmTimeHHMM24 MAX-ACCESS read-write STATUS current DESCRIPTION "End time for the automatic shutdown functionality per interface." DEFVAL { "00:00" } ::= { hm2PoeMgmtPortEntry 10 } hm2PoeMgmtPortClassValid OBJECT-TYPE SYNTAX INTEGER { invalid(0), valid(1) } MAX-ACCESS read-only STATUS current DESCRIPTION "Evaluates if class represented through pethPsePortPowerClassifications is valid or not. Class is valid if PD is delivered with power or in case of power exceeding through a connected device." ::= { hm2PoeMgmtPortEntry 11 } hm2PoeMgmtPortFastStartup OBJECT-TYPE SYNTAX HmEnabledStatus MAX-ACCESS read-write STATUS current DESCRIPTION "Enables/disables Power over Ethernet fast startup mode on given port. The default value is 'disable'." DEFVAL { disable } ::= { hm2PoeMgmtPortEntry 12 } hm2PoeMgmtPortMaxConsumptionPower OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The maximum observed power consumption (hm2PoeMgmtPortMaxConsumptionPower) value expressed in milliwatts used by the PD. The value is reset to 0 if the PoE admin state is set to disable or if a disconnect of the PD is detected." ::= { hm2PoeMgmtPortEntry 13 } hm2PoeMgmtPortPowerLimit OBJECT-TYPE SYNTAX Integer32 (0..30000) MAX-ACCESS read-write STATUS current DESCRIPTION "The power limit per port expressed in milliwatts. If set to zero the power consumption limitation is disabled." DEFVAL { 0 } ::= { hm2PoeMgmtPortEntry 14 } -- -- ************************************************************* -- hm2PoeMgmtModuleTable -- ************************************************************* -- hm2PoeMgmtModuleTable OBJECT-TYPE SYNTAX SEQUENCE OF Hm2PoeMgmtModuleEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "This table contains objects for each plugged PoE module of the device. If the device is non-modular and supports PoE it contains only one entry." ::= { hm2PoeMgmtGroup 4 } hm2PoeMgmtModuleEntry OBJECT-TYPE SYNTAX Hm2PoeMgmtModuleEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "The entries of the hm2PoeMgmtModuleTable." INDEX { hm2PoeMgmtModuleUnitIndex, hm2PoeMgmtModuleSlotIndex } ::= { hm2PoeMgmtModuleTable 1 } Hm2PoeMgmtModuleEntry ::= SEQUENCE { hm2PoeMgmtModuleUnitIndex Integer32, hm2PoeMgmtModuleSlotIndex Integer32, hm2PoeMgmtModulePower Integer32, hm2PoeMgmtModuleMaximumPower Integer32, hm2PoeMgmtModuleReservedPower Integer32, hm2PoeMgmtModuleDeliveredPower Integer32, hm2PoeMgmtModulePowerSource INTEGER, hm2PoeMgmtModuleUsageThreshold Integer32, hm2PoeMgmtModuleNotificationControlEnable HmEnabledStatus } hm2PoeMgmtModuleUnitIndex OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS not-accessible STATUS current DESCRIPTION "Unit number - for stacking devices." ::= { hm2PoeMgmtModuleEntry 1 } hm2PoeMgmtModuleSlotIndex OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS not-accessible STATUS current DESCRIPTION "Slot number of the plugged PoE module." ::= { hm2PoeMgmtModuleEntry 2 } hm2PoeMgmtModulePower OBJECT-TYPE SYNTAX Integer32 (0..1000) MAX-ACCESS read-write STATUS current DESCRIPTION "Configurable power budget per module expressed in Watts. The default value is hm2PoeMgmtModuleMaximumPower and depends on the hardware." DEFVAL { 1000 } ::= { hm2PoeMgmtModuleEntry 3 } hm2PoeMgmtModuleMaximumPower OBJECT-TYPE SYNTAX Integer32 (0..1000) MAX-ACCESS read-only STATUS current DESCRIPTION "Maximum available power budget per module expressed in Watts. This value depends on the device or module." ::= { hm2PoeMgmtModuleEntry 4 } hm2PoeMgmtModuleReservedPower OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The reserved power (depending on actual power classes) per module expressed in Watts." ::= { hm2PoeMgmtModuleEntry 5 } hm2PoeMgmtModuleDeliveredPower OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-only STATUS current DESCRIPTION "The measured usage power per module expressed in Watts." ::= { hm2PoeMgmtModuleEntry 6 } hm2PoeMgmtModulePowerSource OBJECT-TYPE SYNTAX INTEGER { internal(0), external(1) } MAX-ACCESS read-only STATUS current DESCRIPTION "This object displays the type of the PoE power source. internal (0) means that the PoE power is used from the internal PSU and external (1) means that a external PoE PSU must be installed and connected to this module." ::= { hm2PoeMgmtModuleEntry 7 } hm2PoeMgmtModuleUsageThreshold OBJECT-TYPE SYNTAX Integer32 (1..99) MAX-ACCESS read-write STATUS current DESCRIPTION "The usage power threshold per module expressed in percent. If this threshold is exceeded a alarm is initiated." DEFVAL { 90 } ::= { hm2PoeMgmtModuleEntry 8 } hm2PoeMgmtModuleNotificationControlEnable OBJECT-TYPE SYNTAX HmEnabledStatus MAX-ACCESS read-write STATUS current DESCRIPTION "This object controls, on a per-module basis, whether or not notifications from the agent are enabled. " DEFVAL { enable } ::= { hm2PoeMgmtModuleEntry 9 } -- -- ************************************************************* -- hm2PoeMgmtMibNotifications -- ************************************************************* -- hm2PoeMgmtModulePowerUsageOnNotification NOTIFICATION-TYPE OBJECTS { hm2PoeMgmtModuleDeliveredPower } STATUS current DESCRIPTION "This Notification indicate PSE Threshold usage indication is on, the usage power is above the threshold. At least 500 msec must elapse between notifications being emitted by the same object instance." ::= { hm2PoeMgmtMibNotifications 1 } hm2PoeMgmtModulePowerUsageOffNotification NOTIFICATION-TYPE OBJECTS { hm2PoeMgmtModuleDeliveredPower } STATUS current DESCRIPTION "This Notification indicate PSE Threshold usage indication is on, the usage power is below the threshold. At least 500 msec must elapse between notifications being emitted by the same object instance." ::= { hm2PoeMgmtMibNotifications 2 } hm2PoeMgmtPortMaxConfiguredPowerLimitExceeded NOTIFICATION-TYPE OBJECTS { hm2IfacePhysIndex, hm2PoeMgmtPortMaxConsumptionPower, hm2PoeMgmtPortPowerLimit } STATUS current DESCRIPTION "This trap reports an exceeding of the configured power limit. This notification indicates that a PD consumes more power that the maximum configured on the port and the system reserved the maximum power required for the negotiated class." ::= { hm2PoeMgmtMibNotifications 3 } END