MRV-IR-HDAM-MIB DEFINITIONS ::= BEGIN
|
||||
|
||||
IMPORTS
|
||||
OBJECT-TYPE, MODULE-IDENTITY, enterprises, Counter32
|
||||
FROM SNMPv2-SMI
|
||||
TrapSeverity
|
||||
FROM MRV-IR-SYSTEM-MIB
|
||||
DisplayString
|
||||
FROM SNMPv2-TC;
|
||||
|
||||
mrvBpd OBJECT IDENTIFIER ::= { enterprises 33 }
|
||||
mrvLx OBJECT IDENTIFIER ::= { mrvBpd 100 }
|
||||
|
||||
irHdamMib MODULE-IDENTITY
|
||||
LAST-UPDATED "200703220000Z" -- 22 Mar 2007 (LX v5.1.0)
|
||||
ORGANIZATION "MRV Communications - BPD Division"
|
||||
CONTACT-INFO
|
||||
"Postal: MRV Communications, Inc.
|
||||
295 Foster Street
|
||||
Littleton, MA 01460
|
||||
|
||||
E-mail: support@mrv.com"
|
||||
DESCRIPTION
|
||||
"This is the MRV LX HDAM Alarm MIB module."
|
||||
::= { mrvLx 4 }
|
||||
|
||||
-- HDAM Groups.
|
||||
|
||||
irHdam OBJECT IDENTIFIER ::= { irHdamMib 1 }
|
||||
irHdamAlarm OBJECT IDENTIFIER ::= { irHdamMib 2 }
|
||||
irHdamControl OBJECT IDENTIFIER ::= { irHdamMib 3 }
|
||||
irHdamAnalog OBJECT IDENTIFIER ::= { irHdamMib 4 }
|
||||
|
||||
--
|
||||
-- Textual Conventions
|
||||
--
|
||||
|
||||
--
|
||||
-- HDAM Module type values.
|
||||
--
|
||||
IrHdamModuleType ::= INTEGER {
|
||||
empty(1),
|
||||
alarmModule(2),
|
||||
controlModule(3),
|
||||
analoglModule(4)
|
||||
}
|
||||
|
||||
IrContactState ::= INTEGER {
|
||||
open(1),
|
||||
closed(2)
|
||||
}
|
||||
|
||||
IrAnalogStatus ::= INTEGER {
|
||||
disabled(1),
|
||||
enabled(2)
|
||||
}
|
||||
|
||||
|
||||
--
|
||||
-- HDAM Unit Table.
|
||||
--
|
||||
|
||||
irHdamUnitTable OBJECT-TYPE
|
||||
SYNTAX SEQUENCE OF IrHdamUnitEntry
|
||||
MAX-ACCESS not-accessible
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"A list of hdam unit entries."
|
||||
::= { irHdam 1 }
|
||||
|
||||
irHdamUnitEntry OBJECT-TYPE
|
||||
SYNTAX IrHdamUnitEntry
|
||||
MAX-ACCESS not-accessible
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"An hdam unit entry."
|
||||
INDEX { irHdamUnitPortIndex }
|
||||
::= { irHdamUnitTable 1 }
|
||||
|
||||
IrHdamUnitEntry ::= SEQUENCE {
|
||||
irHdamUnitPortIndex
|
||||
INTEGER,
|
||||
irHdamFwVersion
|
||||
DisplayString,
|
||||
irHdamConnectStatus
|
||||
INTEGER,
|
||||
irHdamPowerType
|
||||
INTEGER,
|
||||
irHdamAction
|
||||
INTEGER
|
||||
}
|
||||
|
||||
irHdamUnitPortIndex OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The port index to which this hdam unit is connected."
|
||||
::= { irHdamUnitEntry 1 }
|
||||
|
||||
irHdamFwVersion OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..32))
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The HDAM unit firmware version string."
|
||||
::= { irHdamUnitEntry 2 }
|
||||
|
||||
irHdamConnectStatus OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
connected(1),
|
||||
disconnected(2)
|
||||
}
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The HDAM unit connection status."
|
||||
::= { irHdamUnitEntry 3 }
|
||||
|
||||
irHdamPowerType OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
powerAC(1),
|
||||
powerDC(2)
|
||||
}
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The type of power used by the hdam device."
|
||||
::= { irHdamUnitEntry 4 }
|
||||
|
||||
irHdamAction OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
other(1),
|
||||
reset(2)
|
||||
}
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"This object is used to perform an action on the HDAM unit.
|
||||
A read of this object always returns the value other(1).
|
||||
Setting this object to reset(2) causes the unit to be reset."
|
||||
::= { irHdamUnitEntry 5 }
|
||||
|
||||
--
|
||||
-- HDAM Module Table.
|
||||
--
|
||||
|
||||
irHdamModuleTable OBJECT-TYPE
|
||||
SYNTAX SEQUENCE OF IrHdamModuleEntry
|
||||
MAX-ACCESS not-accessible
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"A list of hdam module entries."
|
||||
::= { irHdam 2 }
|
||||
|
||||
irHdamModuleEntry OBJECT-TYPE
|
||||
SYNTAX IrHdamModuleEntry
|
||||
MAX-ACCESS not-accessible
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"An hdam module entry."
|
||||
INDEX { irHdamPortIndex, irHdamSlotIndex }
|
||||
::= { irHdamModuleTable 1 }
|
||||
|
||||
IrHdamModuleEntry ::= SEQUENCE {
|
||||
irHdamPortIndex
|
||||
INTEGER,
|
||||
irHdamSlotIndex
|
||||
INTEGER,
|
||||
irHdamModuleType
|
||||
IrHdamModuleType
|
||||
}
|
||||
|
||||
irHdamPortIndex OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The port index to which this hdam unit is connected."
|
||||
::= { irHdamModuleEntry 1 }
|
||||
|
||||
irHdamSlotIndex OBJECT-TYPE
|
||||
SYNTAX INTEGER (1..4)
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The slot index for this module entry."
|
||||
::= { irHdamModuleEntry 2 }
|
||||
|
||||
irHdamModuleType OBJECT-TYPE
|
||||
SYNTAX IrHdamModuleType
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The type of module in the slot."
|
||||
::= { irHdamModuleEntry 3 }
|
||||
|
||||
--
|
||||
--
|
||||
-- HDAM Power Supply Table.
|
||||
--
|
||||
|
||||
irHdamPowerSupplyTable OBJECT-TYPE
|
||||
SYNTAX SEQUENCE OF IrHdamPowerSupplyEntry
|
||||
MAX-ACCESS not-accessible
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"A list of hdam power supply entries."
|
||||
::= { irHdam 3 }
|
||||
|
||||
irHdamPowerSupplyEntry OBJECT-TYPE
|
||||
SYNTAX IrHdamPowerSupplyEntry
|
||||
MAX-ACCESS not-accessible
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"An hdam power supply entry."
|
||||
INDEX { irHdamPortIndex, irHdamPowerIndex }
|
||||
::= { irHdamPowerSupplyTable 1 }
|
||||
|
||||
IrHdamPowerSupplyEntry ::= SEQUENCE {
|
||||
irHdamPowerPortIndex
|
||||
INTEGER,
|
||||
irHdamPowerIndex
|
||||
INTEGER,
|
||||
irHdamPowerUnitPresent
|
||||
INTEGER,
|
||||
irHdamPowerInputStatus
|
||||
INTEGER,
|
||||
irHdamPowerOutputStatus
|
||||
INTEGER,
|
||||
irHdamPowerStatus
|
||||
INTEGER
|
||||
}
|
||||
|
||||
irHdamPowerPortIndex OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The index of the port to which the hdam unit is attached."
|
||||
::= { irHdamPowerSupplyEntry 1 }
|
||||
|
||||
irHdamPowerIndex OBJECT-TYPE
|
||||
SYNTAX INTEGER (1..2)
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The index of the hdam power unit."
|
||||
::= { irHdamPowerSupplyEntry 2 }
|
||||
|
||||
irHdamPowerUnitPresent OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
yes(1),
|
||||
no(2)
|
||||
}
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"This indicates if the power unit is present or not."
|
||||
::= { irHdamPowerSupplyEntry 3 }
|
||||
|
||||
irHdamPowerInputStatus OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
on(1),
|
||||
off(2)
|
||||
}
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"This indicates if the power unit is plugged into a power source."
|
||||
::= { irHdamPowerSupplyEntry 4 }
|
||||
|
||||
irHdamPowerOutputStatus OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
on(1),
|
||||
off(2)
|
||||
}
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"This indicates the status of the internal power feed to the device
|
||||
components."
|
||||
::= { irHdamPowerSupplyEntry 5 }
|
||||
|
||||
irHdamPowerStatus OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
on(1),
|
||||
off(2),
|
||||
failed(3)
|
||||
}
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The overall status of the power unit."
|
||||
::= { irHdamPowerSupplyEntry 6 }
|
||||
|
||||
--
|
||||
-- Alarm Module Config Table.
|
||||
--
|
||||
|
||||
irAlarmConfigTable OBJECT-TYPE
|
||||
SYNTAX SEQUENCE OF IrAlarmConfigEntry
|
||||
MAX-ACCESS not-accessible
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"A list of alarm config entries."
|
||||
::= { irHdamAlarm 1 }
|
||||
|
||||
irAlarmConfigEntry OBJECT-TYPE
|
||||
SYNTAX IrAlarmConfigEntry
|
||||
MAX-ACCESS not-accessible
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"An hdam alarm config entry."
|
||||
INDEX { irAlarmPortIndex,
|
||||
irAlarmSlotIndex,
|
||||
irAlarmPointIndex }
|
||||
::= { irAlarmConfigTable 1 }
|
||||
|
||||
IrAlarmConfigEntry ::= SEQUENCE {
|
||||
irAlarmPortIndex
|
||||
INTEGER,
|
||||
irAlarmSlotIndex
|
||||
INTEGER,
|
||||
irAlarmPointIndex
|
||||
INTEGER,
|
||||
irAlarmName
|
||||
DisplayString,
|
||||
irAlarmContactState
|
||||
IrContactState,
|
||||
irAlarmContactFaultState
|
||||
IrContactState,
|
||||
irAlarmDebounceInterval
|
||||
INTEGER,
|
||||
irAlarmAudibleStatus
|
||||
INTEGER,
|
||||
irAlarmTrapStatus
|
||||
INTEGER,
|
||||
irAlarmTrapSeverity
|
||||
TrapSeverity,
|
||||
irAlarmCount
|
||||
Counter32,
|
||||
irAlarmTimestamp
|
||||
DisplayString,
|
||||
irAlarmDescription
|
||||
DisplayString
|
||||
}
|
||||
|
||||
irAlarmPortIndex OBJECT-TYPE
|
||||
SYNTAX INTEGER (1..48)
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The port index on which the alarm unit is attached."
|
||||
::= { irAlarmConfigEntry 1 }
|
||||
|
||||
irAlarmSlotIndex OBJECT-TYPE
|
||||
SYNTAX INTEGER (1..4)
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The slot in the alarm unit which identifies this module."
|
||||
::= { irAlarmConfigEntry 2 }
|
||||
|
||||
irAlarmPointIndex OBJECT-TYPE
|
||||
SYNTAX INTEGER (1..32)
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"An integer which uniquely identifies an alarm on this module."
|
||||
::= { irAlarmConfigEntry 3 }
|
||||
|
||||
irAlarmName OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..32))
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The name assigned to the alarm."
|
||||
::= { irAlarmConfigEntry 4 }
|
||||
|
||||
irAlarmContactState OBJECT-TYPE
|
||||
SYNTAX IrContactState
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The current state of the alarm contacts."
|
||||
::= { irAlarmConfigEntry 5 }
|
||||
|
||||
irAlarmContactFaultState OBJECT-TYPE
|
||||
SYNTAX IrContactState
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The contact state (open or closed) which indicates the fault
|
||||
condition. If the value of this object and irAlarmContactState
|
||||
is the same, then the alarm has been triggered."
|
||||
::= { irAlarmConfigEntry 6 }
|
||||
|
||||
irAlarmDebounceInterval OBJECT-TYPE
|
||||
SYNTAX INTEGER (0..1800)
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The number of seconds the alarm must be in the fault state
|
||||
before it is considered valid."
|
||||
::= { irAlarmConfigEntry 7 }
|
||||
|
||||
irAlarmAudibleStatus OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
disabled(1),
|
||||
enabled(2)
|
||||
}
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"This indicates whether the audible alarm on the unit will sound
|
||||
when this alarm is generated."
|
||||
::= { irAlarmConfigEntry 8 }
|
||||
|
||||
irAlarmTrapStatus OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
disabled(1),
|
||||
enabled(2)
|
||||
}
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"This indicates whether an snmp trap will be generated when this
|
||||
alarm is generated."
|
||||
::= { irAlarmConfigEntry 9 }
|
||||
|
||||
irAlarmTrapSeverity OBJECT-TYPE
|
||||
SYNTAX TrapSeverity
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The trap severity assigned to this alarm. This value will be sent
|
||||
when an alarm fires and an snmp trap is generated."
|
||||
::= { irAlarmConfigEntry 10 }
|
||||
|
||||
irAlarmCount OBJECT-TYPE
|
||||
SYNTAX Counter32
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The number of times the alarm has been generated since the unit
|
||||
was started."
|
||||
::= { irAlarmConfigEntry 11 }
|
||||
|
||||
irAlarmTimestamp OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..32))
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"A timestamp string indicating the time the last alarm was generated.
|
||||
A null string indicates that the alarm has not been generated."
|
||||
::= { irAlarmConfigEntry 12 }
|
||||
|
||||
irAlarmDescription OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..64))
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"A user configurable alarm description string."
|
||||
::= { irAlarmConfigEntry 13 }
|
||||
|
||||
--
|
||||
-- Control Module Config Table.
|
||||
--
|
||||
|
||||
irControlConfigTable OBJECT-TYPE
|
||||
SYNTAX SEQUENCE OF IrControlConfigEntry
|
||||
MAX-ACCESS not-accessible
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"A list of control config entries."
|
||||
::= { irHdamControl 1 }
|
||||
|
||||
irControlConfigEntry OBJECT-TYPE
|
||||
SYNTAX IrControlConfigEntry
|
||||
MAX-ACCESS not-accessible
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"A control config entry."
|
||||
INDEX { irControlPortIndex,
|
||||
irControlSlotIndex,
|
||||
irControlPointIndex }
|
||||
::= { irControlConfigTable 1 }
|
||||
|
||||
IrControlConfigEntry ::= SEQUENCE {
|
||||
irControlPortIndex
|
||||
INTEGER,
|
||||
irControlSlotIndex
|
||||
INTEGER,
|
||||
irControlPointIndex
|
||||
INTEGER,
|
||||
irControlName
|
||||
DisplayString,
|
||||
irControlState
|
||||
IrContactState,
|
||||
irControlActiveState
|
||||
IrContactState,
|
||||
irControlDescription
|
||||
DisplayString
|
||||
}
|
||||
|
||||
irControlPortIndex OBJECT-TYPE
|
||||
SYNTAX INTEGER (1..48)
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The port index on which the control unit is attached."
|
||||
::= { irControlConfigEntry 1 }
|
||||
|
||||
irControlSlotIndex OBJECT-TYPE
|
||||
SYNTAX INTEGER (1..4)
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The slot in the control unit which identifies this module."
|
||||
::= { irControlConfigEntry 2 }
|
||||
|
||||
irControlPointIndex OBJECT-TYPE
|
||||
SYNTAX INTEGER (1..8)
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"An integer which uniquely identifies a control on this module."
|
||||
::= { irControlConfigEntry 3 }
|
||||
|
||||
irControlName OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..32))
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The name assigned to the control."
|
||||
::= { irControlConfigEntry 4 }
|
||||
|
||||
irControlState OBJECT-TYPE
|
||||
SYNTAX IrContactState
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The current value of the control state."
|
||||
::= { irControlConfigEntry 5 }
|
||||
|
||||
irControlActiveState OBJECT-TYPE
|
||||
SYNTAX IrContactState
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The value of the control state that activates the attached
|
||||
device."
|
||||
::= { irControlConfigEntry 6 }
|
||||
|
||||
irControlDescription OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..64))
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"A user configurable control description string."
|
||||
::= { irControlConfigEntry 7 }
|
||||
|
||||
--
|
||||
-- Analog (Sensor) Module Config Table.
|
||||
--
|
||||
|
||||
irAnalogConfigTable OBJECT-TYPE
|
||||
SYNTAX SEQUENCE OF IrAnalogConfigEntry
|
||||
MAX-ACCESS not-accessible
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"A list of analog loop config entries."
|
||||
::= { irHdamAnalog 1 }
|
||||
|
||||
irAnalogConfigEntry OBJECT-TYPE
|
||||
SYNTAX IrAnalogConfigEntry
|
||||
MAX-ACCESS not-accessible
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"An analog loop config entry."
|
||||
INDEX { irAnalogPortIndex,
|
||||
irAnalogSlotIndex,
|
||||
irAnalogPointIndex }
|
||||
::= { irAnalogConfigTable 1 }
|
||||
|
||||
IrAnalogConfigEntry ::= SEQUENCE {
|
||||
irAnalogPortIndex
|
||||
INTEGER,
|
||||
irAnalogSlotIndex
|
||||
INTEGER,
|
||||
irAnalogPointIndex
|
||||
INTEGER,
|
||||
irAnalogName
|
||||
DisplayString,
|
||||
irAnalogDescription
|
||||
DisplayString,
|
||||
irAnalogStatus
|
||||
IrAnalogStatus,
|
||||
irAnalogValue
|
||||
DisplayString,
|
||||
irAnalogCalValue
|
||||
DisplayString,
|
||||
irAnalogCalMinValue
|
||||
DisplayString,
|
||||
irAnalogCalMaxValue
|
||||
DisplayString,
|
||||
irAnalogCalMargin
|
||||
DisplayString,
|
||||
irAnalogCalUnits
|
||||
DisplayString,
|
||||
irAnalogThresholdHigh
|
||||
DisplayString,
|
||||
irAnalogThresholdLow
|
||||
DisplayString,
|
||||
irAnalogThresholdSeverity
|
||||
TrapSeverity,
|
||||
irAnalogThresholdHysteresis
|
||||
DisplayString,
|
||||
irAnalogThresholdHighAlarmCount
|
||||
Counter32,
|
||||
irAnalogThresholdLowAlarmCount
|
||||
Counter32,
|
||||
irAnalogThresholdHighTimestamp
|
||||
DisplayString,
|
||||
irAnalogThresholdLowTimestamp
|
||||
DisplayString
|
||||
}
|
||||
|
||||
irAnalogPortIndex OBJECT-TYPE
|
||||
SYNTAX INTEGER (1..48)
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The port index on which the analog unit is attached."
|
||||
::= { irAnalogConfigEntry 1 }
|
||||
|
||||
irAnalogSlotIndex OBJECT-TYPE
|
||||
SYNTAX INTEGER (1..4)
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The slot in the analog unit which identifies this module."
|
||||
::= { irAnalogConfigEntry 2 }
|
||||
|
||||
irAnalogPointIndex OBJECT-TYPE
|
||||
SYNTAX INTEGER (1..8)
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"An integer which uniquely identifies an analog point on this module."
|
||||
::= { irAnalogConfigEntry 3 }
|
||||
|
||||
irAnalogName OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..32))
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The name assigned to the analog."
|
||||
::= { irAnalogConfigEntry 4 }
|
||||
|
||||
irAnalogDescription OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..64))
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"A user configurable analog description string."
|
||||
::= { irAnalogConfigEntry 5 }
|
||||
|
||||
irAnalogStatus OBJECT-TYPE
|
||||
SYNTAX IrAnalogStatus
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The status of the analog point."
|
||||
::= { irAnalogConfigEntry 6 }
|
||||
|
||||
irAnalogValue OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..24))
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The current analog sensor reading in milliAmps."
|
||||
::= { irAnalogConfigEntry 7 }
|
||||
|
||||
irAnalogCalValue OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..8))
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The current analog sensor calibrated value."
|
||||
::= { irAnalogConfigEntry 8 }
|
||||
|
||||
irAnalogCalMinValue OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..10))
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The calibration value assigned to the minimum sensor reading."
|
||||
::= { irAnalogConfigEntry 9 }
|
||||
|
||||
irAnalogCalMaxValue OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..10))
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The calibration value assigned to the maximum analog sensor reading."
|
||||
::= { irAnalogConfigEntry 10 }
|
||||
|
||||
irAnalogCalMargin OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..10))
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The calibration margin value. This will be added to the
|
||||
calibrated analog sensor value."
|
||||
::= { irAnalogConfigEntry 11 }
|
||||
|
||||
irAnalogCalUnits OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..8))
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"A user defined string describing the calibrated units for the
|
||||
analog sensor."
|
||||
::= { irAnalogConfigEntry 12 }
|
||||
|
||||
irAnalogThresholdHigh OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..10))
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The analog sensor high threshold value. A value of -0 indicates
|
||||
threshold is not configured."
|
||||
::= { irAnalogConfigEntry 13 }
|
||||
|
||||
irAnalogThresholdLow OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..10))
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The analog sensor low threshold value. A value of -0 indicates
|
||||
threshold is not configured."
|
||||
::= { irAnalogConfigEntry 14 }
|
||||
|
||||
irAnalogThresholdSeverity OBJECT-TYPE
|
||||
SYNTAX TrapSeverity
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The severity value of the analog sensor assigned to the low threshold.
|
||||
This value will be sent in the threshold trap."
|
||||
::= { irAnalogConfigEntry 15 }
|
||||
|
||||
irAnalogThresholdHysteresis OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..10))
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"After crossing a threshold, the delta by which the caliberated
|
||||
value must drop within the normal range before the alarm
|
||||
condition is cleared (i.e. a cleared alarm is generated)."
|
||||
::= { irAnalogConfigEntry 16 }
|
||||
|
||||
irAnalogThresholdHighAlarmCount OBJECT-TYPE
|
||||
SYNTAX Counter32
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The number of times the analog sensor high threshold has been
|
||||
crossed since the unit was started."
|
||||
::= { irAnalogConfigEntry 17 }
|
||||
|
||||
irAnalogThresholdLowAlarmCount OBJECT-TYPE
|
||||
SYNTAX Counter32
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The number of times the analog sensor low threshold has been
|
||||
crossed since the unit was started."
|
||||
::= { irAnalogConfigEntry 18 }
|
||||
|
||||
irAnalogThresholdHighTimestamp OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..32))
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"A timestamp string indicating the time the analog sensor last
|
||||
crossed the high threshold. A null string indicates that the
|
||||
alarm has not been crossed."
|
||||
::= { irAnalogConfigEntry 19 }
|
||||
|
||||
irAnalogThresholdLowTimestamp OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..32))
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"A timestamp string indicating the time the analog sensor last
|
||||
crossed the low threshold. A null string indicates that the
|
||||
alarm has not been crossed."
|
||||
::= { irAnalogConfigEntry 20 }
|
||||
|
||||
END
|
||||
|