initial commit; version 22.5.12042
This commit is contained in:
745
mibs/gude/GUDEADS-PDU8340-MIB
Normal file
745
mibs/gude/GUDEADS-PDU8340-MIB
Normal file
@ -0,0 +1,745 @@
|
||||
GUDEADS-PDU8340-MIB DEFINITIONS ::= BEGIN
|
||||
|
||||
IMPORTS
|
||||
enterprises,
|
||||
MODULE-IDENTITY,
|
||||
OBJECT-TYPE,
|
||||
NOTIFICATION-TYPE,
|
||||
Integer32,
|
||||
Unsigned32
|
||||
FROM SNMPv2-SMI
|
||||
OBJECT-GROUP,
|
||||
NOTIFICATION-GROUP
|
||||
FROM SNMPv2-CONF;
|
||||
|
||||
gudeads MODULE-IDENTITY
|
||||
LAST-UPDATED "200703051356Z" -- Mar 5, 2007 1:56:00 PM
|
||||
ORGANIZATION "Gude Analog- und Digitalsysteme GmbH"
|
||||
CONTACT-INFO
|
||||
"http://www.gudeads.com/"
|
||||
DESCRIPTION
|
||||
""
|
||||
REVISION "200703051356Z" -- Mar 5, 2007 1:56:00 PM
|
||||
DESCRIPTION
|
||||
"$Id:$"
|
||||
-- 1.3.6.1.4.1.28507
|
||||
::= { enterprises 28507 }
|
||||
|
||||
|
||||
|
||||
pdu8340AirPressureEvtSen NOTIFICATION-TYPE
|
||||
OBJECTS {
|
||||
pdu8340SensorIndex,
|
||||
pdu8340AirPressure}
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"Air Pressure limits exceeded
|
||||
|
||||
"
|
||||
-- 1.3.6.1.4.1.28507.54.3.4
|
||||
::= { events 4 }
|
||||
|
||||
|
||||
pdu8340DewPtDiffEvtSen NOTIFICATION-TYPE
|
||||
OBJECTS {
|
||||
pdu8340SensorIndex,
|
||||
pdu8340DewPointDiff}
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"Dew Point Difference limits exceeded"
|
||||
-- 1.3.6.1.4.1.28507.54.3.5
|
||||
::= { events 5 }
|
||||
|
||||
|
||||
pdu8340TempEvtSen NOTIFICATION-TYPE
|
||||
OBJECTS {
|
||||
pdu8340SensorIndex,
|
||||
pdu8340TempSensor}
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"temperature limits exceeded"
|
||||
-- 1.3.6.1.4.1.28507.54.3.1
|
||||
::= { events 1 }
|
||||
|
||||
|
||||
pdu8340HygroEvtSen NOTIFICATION-TYPE
|
||||
OBJECTS {
|
||||
pdu8340SensorIndex,
|
||||
pdu8340HygroSensor}
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"hygro limits exceeded"
|
||||
-- 1.3.6.1.4.1.28507.54.3.2
|
||||
::= { events 2 }
|
||||
|
||||
|
||||
pdu8340InputEvtSen NOTIFICATION-TYPE
|
||||
OBJECTS {
|
||||
pdu8340SensorIndex,
|
||||
pdu8340InputSensor}
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"change of logical input sensor state"
|
||||
-- 1.3.6.1.4.1.28507.54.3.3
|
||||
::= { events 3 }
|
||||
|
||||
|
||||
pdu8340LineAmperageEvt NOTIFICATION-TYPE
|
||||
OBJECTS {
|
||||
pdu8340PowerIndex,
|
||||
pdu8340PowerActive,
|
||||
pdu8340Current,
|
||||
pdu8340Voltage,
|
||||
pdu8340Frequency,
|
||||
pdu8340PowerApparent,
|
||||
pdu8340PowerReactive}
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"Event is triggered when a measured
|
||||
current is crossing the entered limits"
|
||||
-- 1.3.6.1.4.1.28507.54.3.6
|
||||
::= { events 6 }
|
||||
|
||||
gadsPDU8340 OBJECT IDENTIFIER
|
||||
-- 1.3.6.1.4.1.28507.54
|
||||
::= { gudeads 54 }
|
||||
|
||||
-- Notification Types
|
||||
--
|
||||
|
||||
events OBJECT IDENTIFIER
|
||||
-- 1.3.6.1.4.1.28507.54.3
|
||||
::= { gadsPDU8340 3 }
|
||||
|
||||
-- Scalars and Tables
|
||||
--
|
||||
|
||||
pdu8340Objects OBJECT IDENTIFIER
|
||||
-- 1.3.6.1.4.1.28507.54.1
|
||||
::= { gadsPDU8340 1 }
|
||||
|
||||
pdu8340CommonConfig OBJECT IDENTIFIER
|
||||
-- 1.3.6.1.4.1.28507.54.1.1
|
||||
::= { pdu8340Objects 1 }
|
||||
|
||||
pdu8340SNMPaccess OBJECT IDENTIFIER
|
||||
-- 1.3.6.1.4.1.28507.54.1.1.1
|
||||
::= { pdu8340CommonConfig 1 }
|
||||
|
||||
pdu8340TrapCtrl OBJECT-TYPE
|
||||
SYNTAX Integer32 (0..3)
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"0 = off
|
||||
1 = Ver. 1
|
||||
2 = Ver. 2c
|
||||
3 = Ver. 3"
|
||||
-- 1.3.6.1.4.1.28507.54.1.1.1.1
|
||||
::= { pdu8340SNMPaccess 1 }
|
||||
|
||||
|
||||
pdu8340TrapIPTable OBJECT-TYPE
|
||||
SYNTAX SEQUENCE OF Pdu8340TrapIPEntry
|
||||
MAX-ACCESS not-accessible
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"list of all Trap receiver"
|
||||
-- 1.3.6.1.4.1.28507.54.1.1.1.2
|
||||
::= { pdu8340SNMPaccess 2 }
|
||||
|
||||
|
||||
pdu8340TrapIPEntry OBJECT-TYPE
|
||||
SYNTAX Pdu8340TrapIPEntry
|
||||
MAX-ACCESS not-accessible
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"an entry containing management
|
||||
informations regarding the list of trap
|
||||
receivers"
|
||||
INDEX {
|
||||
pdu8340TrapIPIndex }
|
||||
-- 1.3.6.1.4.1.28507.54.1.1.1.2.1
|
||||
::= { pdu8340TrapIPTable 1 }
|
||||
|
||||
|
||||
Pdu8340TrapIPEntry ::= SEQUENCE {
|
||||
|
||||
pdu8340TrapIPIndex Integer32,
|
||||
pdu8340TrapAddr OCTET STRING }
|
||||
|
||||
|
||||
pdu8340TrapIPIndex OBJECT-TYPE
|
||||
SYNTAX Integer32 (1..8)
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"A unique value, greater than zero, for each receiver slot."
|
||||
-- 1.3.6.1.4.1.28507.54.1.1.1.2.1.1
|
||||
::= { pdu8340TrapIPEntry 1 }
|
||||
|
||||
|
||||
pdu8340TrapAddr OBJECT-TYPE
|
||||
SYNTAX OCTET STRING (SIZE (0..99))
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"DNS name or IP address specifying one Trap receiver slot.
|
||||
A port can optionally be specified: 'name:port' An empty
|
||||
string disables this slot."
|
||||
-- 1.3.6.1.4.1.28507.54.1.1.1.2.1.2
|
||||
::= { pdu8340TrapIPEntry 2 }
|
||||
|
||||
|
||||
pdu8340DeviceConfig OBJECT IDENTIFIER
|
||||
-- 1.3.6.1.4.1.28507.54.1.2
|
||||
::= { pdu8340Objects 2 }
|
||||
|
||||
pdu8340IntActors OBJECT IDENTIFIER
|
||||
-- 1.3.6.1.4.1.28507.54.1.3
|
||||
::= { pdu8340Objects 3 }
|
||||
|
||||
pdu8340Buzzer OBJECT-TYPE
|
||||
SYNTAX Integer32 (0..1)
|
||||
UNITS "0 = Off, 1 = On"
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"turn Buzzer on and off"
|
||||
-- 1.3.6.1.4.1.28507.54.1.3.10
|
||||
::= { pdu8340IntActors 10 }
|
||||
|
||||
|
||||
pdu8340ExtActors OBJECT IDENTIFIER
|
||||
-- 1.3.6.1.4.1.28507.54.1.4
|
||||
::= { pdu8340Objects 4 }
|
||||
|
||||
pdu8340IntSensors OBJECT IDENTIFIER
|
||||
-- 1.3.6.1.4.1.28507.54.1.5
|
||||
::= { pdu8340Objects 5 }
|
||||
|
||||
pdu8340PowerChan OBJECT IDENTIFIER
|
||||
-- 1.3.6.1.4.1.28507.54.1.5.1
|
||||
::= { pdu8340IntSensors 1 }
|
||||
|
||||
pdu8340ActivePowerChan OBJECT-TYPE
|
||||
SYNTAX Unsigned32 (1..2)
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"Number of suppported Power Channels."
|
||||
-- 1.3.6.1.4.1.28507.54.1.5.1.1
|
||||
::= { pdu8340PowerChan 1 }
|
||||
|
||||
|
||||
pdu8340PowerTable OBJECT-TYPE
|
||||
SYNTAX SEQUENCE OF Pdu8340PowerEntry
|
||||
MAX-ACCESS not-accessible
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"All available Channel Interfaces."
|
||||
-- 1.3.6.1.4.1.28507.54.1.5.1.2
|
||||
::= { pdu8340PowerChan 2 }
|
||||
|
||||
|
||||
pdu8340PowerEntry OBJECT-TYPE
|
||||
SYNTAX Pdu8340PowerEntry
|
||||
MAX-ACCESS not-accessible
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"An entry containing management information
|
||||
applicable to a particular Power Channel."
|
||||
INDEX {
|
||||
pdu8340PowerIndex }
|
||||
-- 1.3.6.1.4.1.28507.54.1.5.1.2.1
|
||||
::= { pdu8340PowerTable 1 }
|
||||
|
||||
|
||||
Pdu8340PowerEntry ::= SEQUENCE {
|
||||
|
||||
pdu8340PowerIndex Integer32,
|
||||
pdu8340ChanStatus Integer32,
|
||||
pdu8340AbsEnergyActive Unsigned32,
|
||||
pdu8340PowerActive Integer32,
|
||||
pdu8340Current Unsigned32,
|
||||
pdu8340Voltage Unsigned32,
|
||||
pdu8340Frequency Unsigned32,
|
||||
pdu8340PowerFactor Integer32,
|
||||
pdu8340Pangle Integer32,
|
||||
pdu8340PowerApparent Integer32,
|
||||
pdu8340PowerReactive Integer32,
|
||||
pdu8340AbsEnergyReactive Unsigned32,
|
||||
pdu8340AbsEnergyActiveResettable Unsigned32,
|
||||
pdu8340AbsEnergyReactiveResettable Unsigned32,
|
||||
pdu8340ResetTime Unsigned32,
|
||||
pdu8340ForwEnergyActive Unsigned32,
|
||||
pdu8340ForwEnergyReactive Unsigned32,
|
||||
pdu8340ForwEnergyActiveResettable Unsigned32,
|
||||
pdu8340ForwEnergyReactiveResettable Unsigned32,
|
||||
pdu8340RevEnergyActive Unsigned32,
|
||||
pdu8340RevEnergyReactive Unsigned32,
|
||||
pdu8340RevEnergyActiveResettable Unsigned32,
|
||||
pdu8340RevEnergyReactiveResettable Unsigned32,
|
||||
pdu8340ResidualCurrent Unsigned32 }
|
||||
|
||||
|
||||
pdu8340ChanStatus OBJECT-TYPE
|
||||
SYNTAX Integer32 (0..1)
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"0 = data not active, 1 = data valid"
|
||||
-- 1.3.6.1.4.1.28507.54.1.5.1.2.1.2
|
||||
::= { pdu8340PowerEntry 2 }
|
||||
|
||||
|
||||
pdu8340AbsEnergyActive OBJECT-TYPE
|
||||
SYNTAX Unsigned32
|
||||
UNITS "Wh"
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"Absolute Active Energy counter."
|
||||
-- 1.3.6.1.4.1.28507.54.1.5.1.2.1.3
|
||||
::= { pdu8340PowerEntry 3 }
|
||||
|
||||
|
||||
pdu8340PowerActive OBJECT-TYPE
|
||||
SYNTAX Integer32
|
||||
UNITS "W"
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"Active Power"
|
||||
-- 1.3.6.1.4.1.28507.54.1.5.1.2.1.4
|
||||
::= { pdu8340PowerEntry 4 }
|
||||
|
||||
|
||||
pdu8340Current OBJECT-TYPE
|
||||
SYNTAX Unsigned32
|
||||
UNITS "mA"
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"Actual Current on Power Channel."
|
||||
-- 1.3.6.1.4.1.28507.54.1.5.1.2.1.5
|
||||
::= { pdu8340PowerEntry 5 }
|
||||
|
||||
|
||||
pdu8340ResidualCurrent OBJECT-TYPE
|
||||
SYNTAX Unsigned32
|
||||
UNITS "mA"
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"Actual Residual Current on Power Channel.
|
||||
According Typ A IEC 60755. Only visible on
|
||||
models that support this feature."
|
||||
-- 1.3.6.1.4.1.28507.54.1.5.1.2.1.24
|
||||
::= { pdu8340PowerEntry 24 }
|
||||
|
||||
|
||||
pdu8340Voltage OBJECT-TYPE
|
||||
SYNTAX Unsigned32
|
||||
UNITS "V"
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"Actual Voltage on Power Channel"
|
||||
-- 1.3.6.1.4.1.28507.54.1.5.1.2.1.6
|
||||
::= { pdu8340PowerEntry 6 }
|
||||
|
||||
|
||||
pdu8340Frequency OBJECT-TYPE
|
||||
SYNTAX Unsigned32
|
||||
UNITS "0.01 hz"
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"Frequency of Power Channel"
|
||||
-- 1.3.6.1.4.1.28507.54.1.5.1.2.1.7
|
||||
::= { pdu8340PowerEntry 7 }
|
||||
|
||||
|
||||
pdu8340PowerFactor OBJECT-TYPE
|
||||
SYNTAX Integer32
|
||||
UNITS "0.001"
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"Power Factor of Channel between
|
||||
-1.0 and 1.00"
|
||||
-- 1.3.6.1.4.1.28507.54.1.5.1.2.1.8
|
||||
::= { pdu8340PowerEntry 8 }
|
||||
|
||||
|
||||
pdu8340Pangle OBJECT-TYPE
|
||||
SYNTAX Integer32
|
||||
UNITS "0.1 degree"
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"Phase Angle between Voltage
|
||||
and L Line Current between
|
||||
-180.0 and 180.0"
|
||||
-- 1.3.6.1.4.1.28507.54.1.5.1.2.1.9
|
||||
::= { pdu8340PowerEntry 9 }
|
||||
|
||||
|
||||
pdu8340PowerApparent OBJECT-TYPE
|
||||
SYNTAX Integer32
|
||||
UNITS "VA"
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"L Line Mean Apparent Power"
|
||||
-- 1.3.6.1.4.1.28507.54.1.5.1.2.1.10
|
||||
::= { pdu8340PowerEntry 10 }
|
||||
|
||||
|
||||
pdu8340PowerReactive OBJECT-TYPE
|
||||
SYNTAX Integer32
|
||||
UNITS "VAR"
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"L Line Mean Reactive Power"
|
||||
-- 1.3.6.1.4.1.28507.54.1.5.1.2.1.11
|
||||
::= { pdu8340PowerEntry 11 }
|
||||
|
||||
|
||||
pdu8340AbsEnergyReactive OBJECT-TYPE
|
||||
SYNTAX Unsigned32
|
||||
UNITS "VARh"
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"Absolute Reactive Energy counter."
|
||||
-- 1.3.6.1.4.1.28507.54.1.5.1.2.1.12
|
||||
::= { pdu8340PowerEntry 12 }
|
||||
|
||||
|
||||
pdu8340AbsEnergyActiveResettable OBJECT-TYPE
|
||||
SYNTAX Unsigned32
|
||||
UNITS "Wh"
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"Resettable Absolute Active Energy counter.
|
||||
Writing '0' resets all resettable counter."
|
||||
-- 1.3.6.1.4.1.28507.54.1.5.1.2.1.13
|
||||
::= { pdu8340PowerEntry 13 }
|
||||
|
||||
|
||||
pdu8340AbsEnergyReactiveResettable OBJECT-TYPE
|
||||
SYNTAX Unsigned32
|
||||
UNITS "VARh"
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"Resettable Absolute Reactive Energy counter."
|
||||
-- 1.3.6.1.4.1.28507.54.1.5.1.2.1.14
|
||||
::= { pdu8340PowerEntry 14 }
|
||||
|
||||
|
||||
pdu8340ResetTime OBJECT-TYPE
|
||||
SYNTAX Unsigned32
|
||||
UNITS "s"
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"Time in seconds since last Energy
|
||||
Counter reset."
|
||||
-- 1.3.6.1.4.1.28507.54.1.5.1.2.1.15
|
||||
::= { pdu8340PowerEntry 15 }
|
||||
|
||||
|
||||
pdu8340ForwEnergyActive OBJECT-TYPE
|
||||
SYNTAX Unsigned32
|
||||
UNITS "Wh"
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"Forward Active Energy counter."
|
||||
-- 1.3.6.1.4.1.28507.54.1.5.1.2.1.16
|
||||
::= { pdu8340PowerEntry 16 }
|
||||
|
||||
|
||||
pdu8340ForwEnergyReactive OBJECT-TYPE
|
||||
SYNTAX Unsigned32
|
||||
UNITS "VARh"
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"Forward Reactive Energy counter."
|
||||
-- 1.3.6.1.4.1.28507.54.1.5.1.2.1.17
|
||||
::= { pdu8340PowerEntry 17 }
|
||||
|
||||
|
||||
pdu8340ForwEnergyActiveResettable OBJECT-TYPE
|
||||
SYNTAX Unsigned32
|
||||
UNITS "Wh"
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"Resettable Forward Active Energy counter."
|
||||
-- 1.3.6.1.4.1.28507.54.1.5.1.2.1.18
|
||||
::= { pdu8340PowerEntry 18 }
|
||||
|
||||
|
||||
pdu8340ForwEnergyReactiveResettable OBJECT-TYPE
|
||||
SYNTAX Unsigned32
|
||||
UNITS "VARh"
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"Resettable Forward Reactive Energy counter."
|
||||
-- 1.3.6.1.4.1.28507.54.1.5.1.2.1.19
|
||||
::= { pdu8340PowerEntry 19 }
|
||||
|
||||
|
||||
pdu8340RevEnergyActive OBJECT-TYPE
|
||||
SYNTAX Unsigned32
|
||||
UNITS "Wh"
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"Reverse Active Energy counter."
|
||||
-- 1.3.6.1.4.1.28507.54.1.5.1.2.1.20
|
||||
::= { pdu8340PowerEntry 20 }
|
||||
|
||||
|
||||
pdu8340RevEnergyReactive OBJECT-TYPE
|
||||
SYNTAX Unsigned32
|
||||
UNITS "VARh"
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"Reverse Reactive Energy counter."
|
||||
-- 1.3.6.1.4.1.28507.54.1.5.1.2.1.21
|
||||
::= { pdu8340PowerEntry 21 }
|
||||
|
||||
|
||||
pdu8340RevEnergyActiveResettable OBJECT-TYPE
|
||||
SYNTAX Unsigned32
|
||||
UNITS "Wh"
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"Resettable Reverse Active Energy counter."
|
||||
-- 1.3.6.1.4.1.28507.54.1.5.1.2.1.22
|
||||
::= { pdu8340PowerEntry 22 }
|
||||
|
||||
|
||||
pdu8340RevEnergyReactiveResettable OBJECT-TYPE
|
||||
SYNTAX Unsigned32
|
||||
UNITS "VARh"
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"Resettable Reverse Reactive Energy counter."
|
||||
-- 1.3.6.1.4.1.28507.54.1.5.1.2.1.23
|
||||
::= { pdu8340PowerEntry 23 }
|
||||
|
||||
|
||||
pdu8340ExtSensors OBJECT IDENTIFIER
|
||||
-- 1.3.6.1.4.1.28507.54.1.6
|
||||
::= { pdu8340Objects 6 }
|
||||
|
||||
pdu8340SensorTable OBJECT-TYPE
|
||||
SYNTAX SEQUENCE OF Pdu8340SensorEntry
|
||||
MAX-ACCESS not-accessible
|
||||
STATUS current
|
||||
DESCRIPTION ""
|
||||
-- 1.3.6.1.4.1.28507.54.1.6.1
|
||||
::= { pdu8340ExtSensors 1 }
|
||||
|
||||
|
||||
pdu8340SensorEntry OBJECT-TYPE
|
||||
SYNTAX Pdu8340SensorEntry
|
||||
MAX-ACCESS not-accessible
|
||||
STATUS current
|
||||
DESCRIPTION ""
|
||||
INDEX {
|
||||
pdu8340SensorIndex }
|
||||
-- 1.3.6.1.4.1.28507.54.1.6.1.1
|
||||
::= { pdu8340SensorTable 1 }
|
||||
|
||||
|
||||
Pdu8340SensorEntry ::= SEQUENCE {
|
||||
|
||||
pdu8340SensorIndex Integer32,
|
||||
pdu8340TempSensor Integer32,
|
||||
pdu8340HygroSensor Integer32,
|
||||
pdu8340InputSensor INTEGER,
|
||||
pdu8340AirPressure Integer32,
|
||||
pdu8340DewPoint Integer32,
|
||||
pdu8340DewPointDiff Integer32 }
|
||||
|
||||
|
||||
pdu8340SensorIndex OBJECT-TYPE
|
||||
SYNTAX Integer32 (1..2)
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION ""
|
||||
-- 1.3.6.1.4.1.28507.54.1.6.1.1.1
|
||||
::= { pdu8340SensorEntry 1 }
|
||||
|
||||
|
||||
pdu8340TempSensor OBJECT-TYPE
|
||||
SYNTAX Integer32
|
||||
UNITS "0.1 degree Celsius"
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"actual temperature"
|
||||
-- 1.3.6.1.4.1.28507.54.1.6.1.1.2
|
||||
::= { pdu8340SensorEntry 2 }
|
||||
|
||||
|
||||
pdu8340HygroSensor OBJECT-TYPE
|
||||
SYNTAX Integer32
|
||||
UNITS "0.1 percent humidity"
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"actual humidity"
|
||||
-- 1.3.6.1.4.1.28507.54.1.6.1.1.3
|
||||
::= { pdu8340SensorEntry 3 }
|
||||
|
||||
|
||||
pdu8340InputSensor OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
off(0),
|
||||
on(1) }
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"logical state of input sensor"
|
||||
-- 1.3.6.1.4.1.28507.54.1.6.1.1.4
|
||||
::= { pdu8340SensorEntry 4 }
|
||||
|
||||
|
||||
-- Conformance
|
||||
--
|
||||
|
||||
pdu8340Conf OBJECT IDENTIFIER
|
||||
-- 1.3.6.1.4.1.28507.54.2
|
||||
::= { gadsPDU8340 2 }
|
||||
|
||||
-- Groups
|
||||
--
|
||||
|
||||
pdu8340Groups OBJECT IDENTIFIER
|
||||
-- 1.3.6.1.4.1.28507.54.2.1
|
||||
::= { pdu8340Conf 1 }
|
||||
|
||||
-- Compliance
|
||||
--
|
||||
|
||||
pdu8340Compls OBJECT IDENTIFIER
|
||||
-- 1.3.6.1.4.1.28507.54.2.2
|
||||
::= { pdu8340Conf 2 }
|
||||
|
||||
pdu8340BasicGroup OBJECT-GROUP
|
||||
OBJECTS {
|
||||
pdu8340TrapCtrl,
|
||||
pdu8340TrapIPIndex,
|
||||
pdu8340TrapAddr,
|
||||
pdu8340Buzzer,
|
||||
pdu8340ActivePowerChan,
|
||||
pdu8340PowerIndex,
|
||||
pdu8340ChanStatus,
|
||||
pdu8340AbsEnergyActive,
|
||||
pdu8340PowerActive,
|
||||
pdu8340Current,
|
||||
pdu8340Voltage,
|
||||
pdu8340Frequency,
|
||||
pdu8340PowerFactor,
|
||||
pdu8340Pangle,
|
||||
pdu8340PowerApparent,
|
||||
pdu8340PowerReactive,
|
||||
pdu8340AbsEnergyReactive,
|
||||
pdu8340AbsEnergyActiveResettable,
|
||||
pdu8340AbsEnergyReactiveResettable,
|
||||
pdu8340ResetTime,
|
||||
pdu8340ForwEnergyActive,
|
||||
pdu8340ForwEnergyReactive,
|
||||
pdu8340ForwEnergyActiveResettable,
|
||||
pdu8340ForwEnergyReactiveResettable,
|
||||
pdu8340RevEnergyActive,
|
||||
pdu8340RevEnergyReactive,
|
||||
pdu8340RevEnergyActiveResettable,
|
||||
pdu8340RevEnergyReactiveResettable,
|
||||
pdu8340ResidualCurrent,
|
||||
pdu8340SensorIndex,
|
||||
pdu8340TempSensor,
|
||||
pdu8340HygroSensor,
|
||||
pdu8340InputSensor,
|
||||
pdu8340AirPressure,
|
||||
pdu8340DewPoint,
|
||||
pdu8340DewPointDiff }
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"Basic objects."
|
||||
-- 1.3.6.1.4.1.28507.54.2.1.1
|
||||
::= { pdu8340Groups 1 }
|
||||
|
||||
pdu8340NotificationGroup NOTIFICATION-GROUP
|
||||
NOTIFICATIONS {
|
||||
pdu8340TempEvtSen,
|
||||
pdu8340HygroEvtSen,
|
||||
pdu8340InputEvtSen,
|
||||
pdu8340AirPressureEvtSen,
|
||||
pdu8340DewPtDiffEvtSen,
|
||||
pdu8340LineAmperageEvt }
|
||||
STATUS current
|
||||
DESCRIPTION ""
|
||||
-- 1.3.6.1.4.1.28507.54.2.1.2
|
||||
::= { pdu8340Groups 2 }
|
||||
|
||||
pdu8340PowerIndex OBJECT-TYPE
|
||||
SYNTAX Integer32 (1..2)
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"Index of Power Channel entries"
|
||||
-- 1.3.6.1.4.1.28507.54.1.5.1.2.1.1
|
||||
::= { pdu8340PowerEntry 1 }
|
||||
|
||||
|
||||
pdu8340AirPressure OBJECT-TYPE
|
||||
SYNTAX Integer32
|
||||
UNITS "1 hPA (hectopascal) ~ 1 milibar"
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"actual air pressure"
|
||||
-- 1.3.6.1.4.1.28507.54.1.6.1.1.5
|
||||
::= { pdu8340SensorEntry 5 }
|
||||
|
||||
|
||||
pdu8340DewPoint OBJECT-TYPE
|
||||
SYNTAX Integer32
|
||||
UNITS "0.1 degree Celsius"
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"dew point for actual temperature and humidity"
|
||||
-- 1.3.6.1.4.1.28507.54.1.6.1.1.6
|
||||
::= { pdu8340SensorEntry 6 }
|
||||
|
||||
|
||||
pdu8340DewPointDiff OBJECT-TYPE
|
||||
SYNTAX Integer32
|
||||
UNITS "0.1 degree Celsius"
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"difference between dew point and actual
|
||||
temperature (Temp - DewPoint)"
|
||||
-- 1.3.6.1.4.1.28507.54.1.6.1.1.7
|
||||
::= { pdu8340SensorEntry 7 }
|
||||
|
||||
|
||||
END
|
Reference in New Issue