EGNITEPHYSENSOR-MIB DEFINITIONS ::= BEGIN
|
||||
|
||||
IMPORTS
|
||||
enterprises, IpAddress, Gauge, TimeTicks FROM RFC1155-SMI
|
||||
DisplayString FROM RFC1213-MIB
|
||||
TRAP-TYPE FROM RFC-1215
|
||||
MODULE-IDENTITY, OBJECT-TYPE, Integer32, Unsigned32, mib-2 FROM SNMPv2-SMI;
|
||||
|
||||
egniteSensorMIB MODULE-IDENTITY
|
||||
LAST-UPDATED "201606150000Z"
|
||||
ORGANIZATION "egnite GmbH"
|
||||
CONTACT-INFO "http://www.egnite.de"
|
||||
DESCRIPTION
|
||||
"This module defines Querx MIB for physical sensors.
|
||||
|
||||
Copyright (C) 2014-2016 by egnite GmbH. This version
|
||||
is based on RFC 3433; see the RFC itself for full legal notices."
|
||||
|
||||
REVISION "201410080000Z"
|
||||
DESCRIPTION
|
||||
"Updated version of the Querx Sensor MIB module."
|
||||
::= { querx 1 }
|
||||
|
||||
egnite OBJECT IDENTIFIER ::= { enterprises 3444 }
|
||||
products OBJECT IDENTIFIER ::= { egnite 1 }
|
||||
querx OBJECT IDENTIFIER ::= { products 14 }
|
||||
querxSensorObjects OBJECT IDENTIFIER ::= { querx 1 }
|
||||
querxSensorTraps OBJECT IDENTIFIER ::= { querx 2 }
|
||||
|
||||
--
|
||||
-- Textual Conventions
|
||||
--
|
||||
|
||||
QuerxSensorIndex ::= TEXTUAL-CONVENTION
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"A unique value, greater than zero, for each sensor
|
||||
in the managed system."
|
||||
SYNTAX Integer32 (1..2147483647)
|
||||
|
||||
|
||||
QuerxSensorDataType ::= TEXTUAL-CONVENTION
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"An object using this data type represents the Querx Sensor
|
||||
measurement data type associated with a physical sensor
|
||||
value. The actual data units are determined by examining an
|
||||
object of this type together with the associated
|
||||
QuerxSensorDataScale object.
|
||||
|
||||
An object of this type SHOULD be defined together with
|
||||
objects of type QuerxSensorDataScale and
|
||||
QuerxSensorPrecision. Together, associated objects of
|
||||
these three types are used to identify the semantics of an
|
||||
object of type QuerxSensorValue.
|
||||
|
||||
Valid values are:
|
||||
|
||||
other(1): a measure other than those listed below
|
||||
unknown(2): unknown measurement, or arbitrary,
|
||||
relative numbers
|
||||
voltsAC(3): electric potential
|
||||
voltsDC(4): electric potential
|
||||
amperes(5): electric current
|
||||
watts(6): power
|
||||
hertz(7): frequency
|
||||
celsius(8): temperature
|
||||
percentRH(9): percent relative humidity
|
||||
rpm(10): shaft revolutions per minute
|
||||
cmm(11),: cubic meters per minute (airflow)
|
||||
truthvalue(12): value takes { true(1), false(2) }
|
||||
|
||||
"
|
||||
SYNTAX INTEGER {
|
||||
other(1),
|
||||
unknown(2),
|
||||
voltsAC(3),
|
||||
voltsDC(4),
|
||||
amperes(5),
|
||||
watts(6),
|
||||
hertz(7),
|
||||
celsius(8),
|
||||
percentRH(9),
|
||||
rpm(10),
|
||||
cmm(11),
|
||||
truthvalue(12)
|
||||
}
|
||||
|
||||
QuerxSensorDataScale ::= TEXTUAL-CONVENTION
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"An object using this data type represents a data scaling
|
||||
factor, represented with an International System of Units
|
||||
(SI) prefix. The actual data units are determined by
|
||||
examining an object of this type together with the
|
||||
associated QuerxSensorDataType object.
|
||||
|
||||
An object of this type SHOULD be defined together with
|
||||
objects of type QuerxSensorDataType and
|
||||
QuerxSensorPrecision. Together, associated objects of
|
||||
these three types are used to identify the semantics of an
|
||||
object of type QuerxSensorValue."
|
||||
REFERENCE
|
||||
"The International System of Units (SI),
|
||||
|
||||
|
||||
|
||||
National Institute of Standards and Technology,
|
||||
Spec. Publ. 330, August 1991."
|
||||
SYNTAX INTEGER {
|
||||
yocto(1), -- 10^-24
|
||||
zepto(2), -- 10^-21
|
||||
atto(3), -- 10^-18
|
||||
femto(4), -- 10^-15
|
||||
pico(5), -- 10^-12
|
||||
nano(6), -- 10^-9
|
||||
micro(7), -- 10^-6
|
||||
milli(8), -- 10^-3
|
||||
units(9), -- 10^0
|
||||
kilo(10), -- 10^3
|
||||
mega(11), -- 10^6
|
||||
giga(12), -- 10^9
|
||||
tera(13), -- 10^12
|
||||
exa(14), -- 10^15
|
||||
peta(15), -- 10^18
|
||||
zetta(16), -- 10^21
|
||||
yotta(17) -- 10^24
|
||||
}
|
||||
|
||||
QuerxSensorPrecision ::= TEXTUAL-CONVENTION
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"An object using this data type represents a sensor
|
||||
precision range.
|
||||
|
||||
An object of this type SHOULD be defined together with
|
||||
objects of type QuerxSensorDataType and
|
||||
QuerxSensorDataScale. Together, associated objects of
|
||||
these three types are used to identify the semantics of an
|
||||
object of type QuerxSensorValue.
|
||||
|
||||
If an object of this type contains a value in the range 1 to
|
||||
9, it represents the number of decimal places in the
|
||||
fractional part of an associated QuerxSensorValue fixed-
|
||||
point number.
|
||||
|
||||
If an object of this type contains a value in the range -8
|
||||
to -1, it represents the number of accurate digits in the
|
||||
associated QuerxSensorValue fixed-point number.
|
||||
|
||||
The value zero indicates the associated QuerxSensorValue
|
||||
object is not a fixed-point number.
|
||||
|
||||
Agent implementors must choose a value for the associated
|
||||
QuerxSensorPrecision object so that the precision and
|
||||
|
||||
|
||||
|
||||
accuracy of the associated QuerxSensorValue object is
|
||||
correctly indicated.
|
||||
|
||||
For example, a physical entity representing a temperature
|
||||
sensor that can measure 0 degrees to 100 degrees C in 0.1
|
||||
degree increments, +/- 0.05 degrees, would have an
|
||||
QuerxSensorPrecision value of '1', an QuerxSensorDataScale
|
||||
value of 'units(9)', and an QuerxSensorValue ranging from
|
||||
'0' to '1000'. The QuerxSensorValue would be interpreted
|
||||
as 'degrees C * 10'."
|
||||
SYNTAX Integer32 (-8..9)
|
||||
|
||||
QuerxSensorValue ::= TEXTUAL-CONVENTION
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"An object using this data type represents an Querx Sensor
|
||||
value.
|
||||
An object of this type SHOULD be defined together with
|
||||
objects of type QuerxSensorDataType, QuerxSensorDataScale
|
||||
and QuerxSensorPrecision. Together, associated objects of
|
||||
those three types are used to identify the semantics of an
|
||||
object of this data type.
|
||||
|
||||
The semantics of an object using this data type are
|
||||
determined by the value of the associated
|
||||
QuerxSensorDataType object.
|
||||
|
||||
If the associated QuerxSensorDataType object is equal to
|
||||
'voltsAC(3)', 'voltsDC(4)', 'amperes(5)', 'watts(6),
|
||||
'hertz(7)', 'celsius(8)', or 'cmm(11)', then an object of
|
||||
this type MUST contain a fixed point number ranging from
|
||||
-999,999,999 to +999,999,999. The value -1000000000
|
||||
indicates an underflow error. The value +1000000000
|
||||
indicates an overflow error. The QuerxSensorPrecision
|
||||
indicates how many fractional digits are represented in the
|
||||
associated QuerxSensorValue object.
|
||||
|
||||
If the associated QuerxSensorDataType object is equal to
|
||||
'percentRH(9)', then an object of this type MUST contain a
|
||||
number ranging from 0 to 100.
|
||||
|
||||
If the associated QuerxSensorDataType object is equal to
|
||||
'rpm(10)', then an object of this type MUST contain a number
|
||||
ranging from -999,999,999 to +999,999,999.
|
||||
|
||||
If the associated QuerxSensorDataType object is equal to
|
||||
'truthvalue(12)', then an object of this type MUST contain
|
||||
either the value 'true(1)' or the value 'false(2)'.
|
||||
|
||||
|
||||
|
||||
If the associated QuerxSensorDataType object is equal to
|
||||
'other(1)' or unknown(2)', then an object of this type MUST
|
||||
contain a number ranging from -1000000000 to 1000000000."
|
||||
SYNTAX Integer32 (-1000000000..1000000000)
|
||||
|
||||
QuerxSensorStatus ::= TEXTUAL-CONVENTION
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"An object using this data type represents the operational
|
||||
status of a physical sensor.
|
||||
|
||||
The value 'ok(1)' indicates that the agent can obtain the
|
||||
sensor value.
|
||||
|
||||
The value 'unavailable(2)' indicates that the agent
|
||||
presently cannot obtain the sensor value.
|
||||
|
||||
The value 'nonoperational(3)' indicates that the agent
|
||||
believes the sensor is broken. The sensor could have a hard
|
||||
failure (disconnected wire), or a soft failure such as out-
|
||||
of-range, jittery, or wildly fluctuating readings."
|
||||
SYNTAX INTEGER {
|
||||
ok(1),
|
||||
unavailable(2),
|
||||
nonoperational(3)
|
||||
}
|
||||
|
||||
querxPhySensorNumber OBJECT-TYPE
|
||||
SYNTAX Integer32
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The number of sensors present on this system."
|
||||
::= { querxSensorObjects 1 }
|
||||
|
||||
--
|
||||
-- Querx Sensor Table
|
||||
--
|
||||
|
||||
querxPhySensorTable OBJECT-TYPE
|
||||
SYNTAX SEQUENCE OF QuerxPhySensorEntry
|
||||
MAX-ACCESS not-accessible
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"This table contains one row per physical sensor."
|
||||
::= { querxSensorObjects 2 }
|
||||
|
||||
querxPhySensorEntry OBJECT-TYPE
|
||||
SYNTAX QuerxPhySensorEntry
|
||||
MAX-ACCESS not-accessible
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"Information about a particular physical sensor.
|
||||
|
||||
An entry in this table describes the present reading of a
|
||||
sensor, the measurement units and scale, and sensor
|
||||
operational status.
|
||||
|
||||
Entries are created in this table by the agent."
|
||||
INDEX { querxPhySensorIndex } -- SPARSE-AUGMENTS
|
||||
::= { querxPhySensorTable 1 }
|
||||
|
||||
QuerxPhySensorEntry ::= SEQUENCE {
|
||||
querxPhySensorIndex QuerxSensorIndex,
|
||||
querxPhySensorType QuerxSensorDataType,
|
||||
querxPhySensorScale QuerxSensorDataScale,
|
||||
querxPhySensorPrecision QuerxSensorPrecision,
|
||||
querxPhySensorValue QuerxSensorValue,
|
||||
querxPhySensorOperStatus QuerxSensorStatus,
|
||||
querxPhySensorUnitsDisplay DisplayString,
|
||||
querxPhySensorValueTimeStamp TimeStamp,
|
||||
querxPhySensorValueUpdateRate Unsigned32
|
||||
}
|
||||
|
||||
querxPhySensorIndex OBJECT-TYPE
|
||||
SYNTAX QuerxSensorIndex
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"A unique value, greater than zero, for each sensor."
|
||||
::= { querxPhySensorEntry 1 }
|
||||
|
||||
querxPhySensorType OBJECT-TYPE
|
||||
SYNTAX QuerxSensorDataType
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The type of data returned by the associated
|
||||
querxPhySensorValue object.
|
||||
|
||||
This object SHOULD be set by the agent during entry
|
||||
creation, and the value SHOULD NOT change during operation."
|
||||
::= { querxPhySensorEntry 2 }
|
||||
|
||||
querxPhySensorScale OBJECT-TYPE
|
||||
SYNTAX QuerxSensorDataScale
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The exponent to apply to values returned by the associated
|
||||
querxPhySensorValue object."
|
||||
::= { querxPhySensorEntry 3 }
|
||||
|
||||
querxPhySensorPrecision OBJECT-TYPE
|
||||
SYNTAX QuerxSensorPrecision
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The number of decimal places of precision in fixed-point
|
||||
sensor values returned by the associated querxPhySensorValue
|
||||
object.
|
||||
|
||||
This object SHOULD be set to '0' when the associated
|
||||
querxPhySensorType value is not a fixed-point type: e.g.,
|
||||
'percentRH(9)', 'rpm(10)', 'cmm(11)', or 'truthvalue(12)'.
|
||||
|
||||
This object SHOULD be set by the agent during entry
|
||||
creation, and the value SHOULD NOT change during operation."
|
||||
::= { querxPhySensorEntry 4 }
|
||||
|
||||
querxPhySensorValue OBJECT-TYPE
|
||||
SYNTAX QuerxSensorValue
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The most recent measurement obtained by the agent for this
|
||||
sensor.
|
||||
|
||||
To correctly interpret the value of this object, the
|
||||
associated querxPhySensorType, querxPhySensorScale, and
|
||||
querxPhySensorPrecision objects must also be examined."
|
||||
::= { querxPhySensorEntry 5 }
|
||||
|
||||
querxPhySensorOperStatus OBJECT-TYPE
|
||||
SYNTAX QuerxSensorStatus
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The operational status of the sensor."
|
||||
::= { querxPhySensorEntry 6 }
|
||||
|
||||
querxPhySensorUnitsDisplay OBJECT-TYPE
|
||||
SYNTAX DisplayString
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"A textual description of the data units that should be used
|
||||
in the display of querxPhySensorValue."
|
||||
::= { querxPhySensorEntry 7 }
|
||||
|
||||
querxPhySensorValueTimeStamp OBJECT-TYPE
|
||||
SYNTAX TimeStamp
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The value of sysUpTime at the time the status and/or value
|
||||
of this sensor was last obtained by the agent."
|
||||
::= { querxPhySensorEntry 8 }
|
||||
|
||||
querxPhySensorValueUpdateRate OBJECT-TYPE
|
||||
SYNTAX Unsigned32
|
||||
UNITS "milliseconds"
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"An indication of the frequency that the agent updates the
|
||||
associated querxPhySensorValue object, representing in
|
||||
milliseconds.
|
||||
|
||||
The value zero indicates:
|
||||
|
||||
- the sensor value is updated on demand (e.g.,
|
||||
when polled by the agent for a get-request),
|
||||
- the sensor value is updated when the sensor
|
||||
value changes (event-driven),
|
||||
- the agent does not know the update rate.
|
||||
|
||||
"
|
||||
::= { querxPhySensorEntry 9 }
|
||||
|
||||
querxPhySensorName OBJECT-TYPE
|
||||
SYNTAX OCTET STRING (SIZE (0..31))
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"The textual name of the physical sensor.
|
||||
|
||||
If there is no local name, or if this object is otherwise
|
||||
not applicable, then this object contains a zero-length
|
||||
string."
|
||||
::= { querxPhySensorEntry 10 }
|
||||
|
||||
|
||||
querxPhySensorNormal TRAP-TYPE
|
||||
ENTERPRISE querxSensorTraps
|
||||
VARIABLES { querxPhySensorIndex, querxPhySensorValue }
|
||||
DESCRIPTION "Sensor state changed back to normal."
|
||||
::= 101
|
||||
|
||||
querxPhySensorAlert TRAP-TYPE
|
||||
ENTERPRISE querxSensorTraps
|
||||
VARIABLES { querxPhySensorIndex, querxPhySensorValue }
|
||||
DESCRIPTION "Sensor in critical state after value reached limit."
|
||||
::= 102
|
||||
|
||||
END
|