initial commit; version 22.5.12042
This commit is contained in:
298
mibs/comet/T4611-MIB
Normal file
298
mibs/comet/T4611-MIB
Normal file
@ -0,0 +1,298 @@
|
||||
-----------------------------------------------------------------------
|
||||
-- MIB table for T4611
|
||||
--
|
||||
-- v3.0 for firmware 1-5-7-2, 2016-04-11
|
||||
-----------------------------------------------------------------------
|
||||
T4611-MIB DEFINITIONS ::= BEGIN
|
||||
|
||||
|
||||
IMPORTS
|
||||
enterprises
|
||||
FROM RFC1155-SMI
|
||||
OBJECT-TYPE
|
||||
FROM RFC-1212
|
||||
TRAP-TYPE
|
||||
FROM RFC-1215;
|
||||
|
||||
DisplayString ::= OCTET STRING
|
||||
|
||||
|
||||
comet OBJECT IDENTIFIER ::= { enterprises 22626 }
|
||||
products OBJECT IDENTIFIER ::= { comet 1 }
|
||||
t4611 OBJECT IDENTIFIER ::= { products 2 }
|
||||
values OBJECT IDENTIFIER ::= { t4611 1 }
|
||||
global OBJECT IDENTIFIER ::= { t4611 2 }
|
||||
valuesInt OBJECT IDENTIFIER ::= { t4611 3 }
|
||||
settings OBJECT IDENTIFIER ::= { t4611 4 }
|
||||
traps OBJECT IDENTIFIER ::= { t4611 5 }
|
||||
tables OBJECT IDENTIFIER ::= { t4611 6 }
|
||||
|
||||
|
||||
-----------------------------------------------------------------------
|
||||
-- Measured values - String
|
||||
-----------------------------------------------------------------------
|
||||
temp OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..8))
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Temperature"
|
||||
::= { values 1 }
|
||||
|
||||
tempAlarm OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..8))
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Alarm on Temperature; none, high, low"
|
||||
::= { values 5 }
|
||||
|
||||
tempUnit OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..8))
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Temperature Unit"
|
||||
::= { values 9 }
|
||||
|
||||
tempMin OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..8))
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Minimal temperature"
|
||||
::= { values 13 }
|
||||
|
||||
tempMax OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..8))
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Maximal temperature"
|
||||
::= { values 17 }
|
||||
|
||||
|
||||
-----------------------------------------------------------------------
|
||||
-- Device informations
|
||||
-----------------------------------------------------------------------
|
||||
sensorName OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..68))
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Device name"
|
||||
::= { global 1 }
|
||||
|
||||
serialNumber OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..16))
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Serial number"
|
||||
::= { global 2 }
|
||||
|
||||
deviceType OBJECT-TYPE
|
||||
SYNTAX INTEGER (0..65534)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Device type"
|
||||
::= { global 3 }
|
||||
|
||||
|
||||
-----------------------------------------------------------------------
|
||||
-- Measured values - Integer
|
||||
-----------------------------------------------------------------------
|
||||
tempInt OBJECT-TYPE
|
||||
SYNTAX INTEGER (-5000..20000)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Temperature (value*10)"
|
||||
::= { valuesInt 1 }
|
||||
|
||||
tempAlarmInt OBJECT-TYPE
|
||||
SYNTAX INTEGER (0..2)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Alarm on Temperature; 0 - No, 1 - High, 2 - Low"
|
||||
::= { valuesInt 5 }
|
||||
|
||||
|
||||
-----------------------------------------------------------------------
|
||||
-- Alarm settings
|
||||
-----------------------------------------------------------------------
|
||||
tempLowInt OBJECT-TYPE
|
||||
SYNTAX INTEGER (-5000..20000)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Temperature Limit Low (value*10)"
|
||||
::= { settings 1 }
|
||||
|
||||
tempHighInt OBJECT-TYPE
|
||||
SYNTAX INTEGER (-5000..20000)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Temperature Limit High (value*10)"
|
||||
::= { settings 2 }
|
||||
|
||||
tempDelayInt OBJECT-TYPE
|
||||
SYNTAX INTEGER (0..4500)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Temperature alaram delay [sec]"
|
||||
::= { settings 7 }
|
||||
|
||||
tempHystInt OBJECT-TYPE
|
||||
SYNTAX INTEGER (0..10000)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Temperature hysteresis (value*10)"
|
||||
::= { settings 10 }
|
||||
|
||||
|
||||
-----------------------------------------------------------------------
|
||||
-- Trap message
|
||||
-----------------------------------------------------------------------
|
||||
messageString OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE (0..32))
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Message giving more detailed information on alarms"
|
||||
::= { traps 1 }
|
||||
|
||||
|
||||
-----------------------------------------------------------------------
|
||||
-- Tables
|
||||
-----------------------------------------------------------------------
|
||||
historyTable OBJECT-TYPE
|
||||
SYNTAX SEQUENCE OF HistoryEntry
|
||||
ACCESS not-accessible
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Table of the history values"
|
||||
::= { tables 1 }
|
||||
|
||||
historyEntry OBJECT-TYPE
|
||||
SYNTAX HistoryEntry
|
||||
ACCESS not-accessible
|
||||
STATUS optional
|
||||
DESCRIPTION "History values entries"
|
||||
INDEX { histTemp }
|
||||
::= { historyTable 1 }
|
||||
|
||||
HistoryEntry ::=
|
||||
SEQUENCE {
|
||||
histTemp
|
||||
INTEGER
|
||||
}
|
||||
|
||||
histTemp OBJECT-TYPE
|
||||
SYNTAX INTEGER(-5000..20000)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Temperature reading"
|
||||
::= { historyEntry 1 }
|
||||
|
||||
|
||||
-----------------------------------------------------------------------
|
||||
-- Traps definition
|
||||
-----------------------------------------------------------------------
|
||||
|
||||
trapTest TRAP-TYPE
|
||||
ENTERPRISE comet
|
||||
VARIABLES { sensorName, messageString }
|
||||
DESCRIPTION
|
||||
"Testing trap, testing trap by TSensor software"
|
||||
::= 0
|
||||
|
||||
trapNTPError TRAP-TYPE
|
||||
ENTERPRISE comet
|
||||
VARIABLES { sensorName, messageString }
|
||||
DESCRIPTION
|
||||
"Error on time synchronisation via NTP"
|
||||
::= 1
|
||||
|
||||
trapEmailErrLogin TRAP-TYPE
|
||||
ENTERPRISE comet
|
||||
VARIABLES { sensorName, messageString }
|
||||
DESCRIPTION
|
||||
"SMTP error - unknown server"
|
||||
::= 2
|
||||
|
||||
trapEmailErrAuth TRAP-TYPE
|
||||
ENTERPRISE comet
|
||||
VARIABLES { sensorName, messageString }
|
||||
DESCRIPTION
|
||||
"SMTP error - authentication error"
|
||||
::= 3
|
||||
|
||||
trapEmailErrSome TRAP-TYPE
|
||||
ENTERPRISE comet
|
||||
VARIABLES { sensorName, messageString }
|
||||
DESCRIPTION
|
||||
"SMTP error - error during communication with server, unexpected return code"
|
||||
::= 4
|
||||
|
||||
trapEmailErrSocket TRAP-TYPE
|
||||
ENTERPRISE comet
|
||||
VARIABLES { sensorName, messageString }
|
||||
DESCRIPTION
|
||||
"SMTP error - socket error, server is not available"
|
||||
::= 5
|
||||
|
||||
trapEmailErrDNS TRAP-TYPE
|
||||
ENTERPRISE comet
|
||||
VARIABLES { sensorName, messageString }
|
||||
DESCRIPTION
|
||||
"SMTP error - DNS error"
|
||||
::= 6
|
||||
|
||||
trapSOAPErrFile TRAP-TYPE
|
||||
ENTERPRISE comet
|
||||
VARIABLES { sensorName, messageString }
|
||||
DESCRIPTION
|
||||
"SOAP error - file SOAP not found"
|
||||
::= 7
|
||||
|
||||
trapSOAPErrDNS TRAP-TYPE
|
||||
ENTERPRISE comet
|
||||
VARIABLES { sensorName, messageString }
|
||||
DESCRIPTION
|
||||
"SOAP error - DNS error"
|
||||
::= 8
|
||||
|
||||
trapSOAPErrSocket TRAP-TYPE
|
||||
ENTERPRISE comet
|
||||
VARIABLES { sensorName, messageString }
|
||||
DESCRIPTION
|
||||
"SOAP error - socket error, server is not available"
|
||||
::= 9
|
||||
|
||||
trapSOAPErrDelivery TRAP-TYPE
|
||||
ENTERPRISE comet
|
||||
VARIABLES { sensorName, messageString }
|
||||
DESCRIPTION
|
||||
"SOAP error - delivery error, wrong return code from server"
|
||||
::= 10
|
||||
|
||||
trapTempHighAlarm TRAP-TYPE
|
||||
ENTERPRISE comet
|
||||
VARIABLES { sensorName, messageString, temp, tempAlarmInt }
|
||||
DESCRIPTION
|
||||
"Trap for high alarm on temperature"
|
||||
::= 11
|
||||
|
||||
trapTempLowAlarm TRAP-TYPE
|
||||
ENTERPRISE comet
|
||||
VARIABLES { sensorName, messageString, temp, tempAlarmInt }
|
||||
DESCRIPTION
|
||||
"Trap for low alarm on temperature"
|
||||
::= 21
|
||||
|
||||
trapTempClrAlarm TRAP-TYPE
|
||||
ENTERPRISE comet
|
||||
VARIABLES { sensorName, messageString, temp, tempAlarmInt }
|
||||
DESCRIPTION
|
||||
"Trap for clearing alarm on temperature"
|
||||
::= 31
|
||||
|
||||
trapTempError TRAP-TYPE
|
||||
ENTERPRISE comet
|
||||
VARIABLES { sensorName, messageString, temp, tempAlarmInt }
|
||||
DESCRIPTION
|
||||
"Trap for error on temperature"
|
||||
::= 41
|
||||
|
||||
|
||||
END
|
Reference in New Issue