Commit version 24.12.13800
This commit is contained in:
887
mibs/netping/DKSF-PWR-OLD-MIB
Normal file
887
mibs/netping/DKSF-PWR-OLD-MIB
Normal file
@ -0,0 +1,887 @@
|
||||
DKSF-PWR-OLD-MIB DEFINITIONS ::= BEGIN
|
||||
|
||||
IMPORTS
|
||||
enterprises,
|
||||
MODULE-IDENTITY,
|
||||
OBJECT-TYPE,
|
||||
Counter32,
|
||||
Gauge32,
|
||||
Counter64,
|
||||
Integer32,
|
||||
TimeTicks,
|
||||
NOTIFICATION-TYPE
|
||||
FROM SNMPv2-SMI
|
||||
TEXTUAL-CONVENTION,
|
||||
DisplayString,
|
||||
TruthValue,
|
||||
TimeStamp
|
||||
FROM SNMPv2-TC
|
||||
snmpTraps
|
||||
FROM SNMPv2-MIB ;
|
||||
|
||||
|
||||
netPing8Pwr MODULE-IDENTITY
|
||||
LAST-UPDATED "201508130000Z"
|
||||
ORGANIZATION "Alentis Electronics"
|
||||
CONTACT-INFO
|
||||
"developers@netping.ru"
|
||||
DESCRIPTION
|
||||
"Generic MIB for NetPing remote sensing and control"
|
||||
|
||||
REVISION "201508130000Z"
|
||||
DESCRIPTION
|
||||
"npRelayFlip variable added"
|
||||
|
||||
REVISION "201506180000Z"
|
||||
DESCRIPTION
|
||||
"npIr branch added"
|
||||
|
||||
REVISION "201505280000Z"
|
||||
DESCRIPTION
|
||||
"npGsmSendSms variable added"
|
||||
|
||||
REVISION "201505060000Z"
|
||||
DESCRIPTION
|
||||
"npRelHumidity, npSmoke branches added"
|
||||
|
||||
REVISION "201503260000Z"
|
||||
DESCRIPTION
|
||||
"npRelayMode values redefined"
|
||||
|
||||
REVISION "201311010000Z"
|
||||
DESCRIPTION
|
||||
"New npRelay branch; npPwr branch is reduced.
|
||||
npRelayMode value for logic changed from 4 to 5"
|
||||
|
||||
REVISION "201304110000Z"
|
||||
DESCRIPTION
|
||||
"partial rewrite for DKSF 48"
|
||||
|
||||
REVISION "201205310000Z"
|
||||
DESCRIPTION
|
||||
"npPwrRelayState branch was added"
|
||||
|
||||
REVISION "201204170000Z"
|
||||
DESCRIPTION
|
||||
"npReboot branch was added"
|
||||
|
||||
REVISION "201203230000Z"
|
||||
DESCRIPTION
|
||||
"Minor changes to IR module for IRC-TRv2"
|
||||
|
||||
REVISION "201109230000Z"
|
||||
DESCRIPTION
|
||||
"4 IO lines,
|
||||
Identification is changed from DKSF 52.4 to DKSF 52.5"
|
||||
|
||||
REVISION "201103240000Z"
|
||||
DESCRIPTION
|
||||
"npIoPulseCounter, npIoSinglePulseDuration, npIoSinglePulseStart is added
|
||||
Identification is changed from DKSF 52.3 to DKSF 52.4"
|
||||
|
||||
REVISION "201010140000Z"
|
||||
DESCRIPTION
|
||||
"IR module support"
|
||||
|
||||
REVISION "201009200000Z"
|
||||
DESCRIPTION
|
||||
"dksf 52.3 subversion"
|
||||
|
||||
REVISION "201005310000Z"
|
||||
DESCRIPTION
|
||||
"dksf 51.3 subversion"
|
||||
|
||||
REVISION "201004140000Z"
|
||||
DESCRIPTION
|
||||
"SMIv2-style rewrite"
|
||||
|
||||
-- lightcom.48 DKSF-48-4-X-X-1::netPing8Pwr
|
||||
-- lightcom.54 DKSF-54-1-X-X-1::netPing4Pwr
|
||||
::= { lightcom 48 }
|
||||
|
||||
|
||||
|
||||
lightcom OBJECT IDENTIFIER::={enterprises 25728 }
|
||||
|
||||
npRelay OBJECT IDENTIFIER::={ lightcom 5500 }
|
||||
|
||||
npRelayTable OBJECT-TYPE
|
||||
SYNTAX SEQUENCE OF NpRelayEntry
|
||||
MAX-ACCESS not-accessible
|
||||
STATUS current
|
||||
DESCRIPTION "Watchdog and outlet/relay control table"
|
||||
::= { npRelay 5 }
|
||||
|
||||
npRelayEntry OBJECT-TYPE
|
||||
SYNTAX NpRelayEntry
|
||||
MAX-ACCESS not-accessible
|
||||
STATUS current
|
||||
DESCRIPTION "Relay/outlet table row"
|
||||
INDEX { npRelayN }
|
||||
::= { npRelayTable 1 }
|
||||
|
||||
NpRelayEntry ::= SEQUENCE {
|
||||
npRelayN INTEGER,
|
||||
npRelayMode INTEGER,
|
||||
npRelayStartReset INTEGER,
|
||||
npRelayMemo DisplayString,
|
||||
npRelayFlip INTEGER,
|
||||
npRelayState INTEGER,
|
||||
npRelayPowered INTEGER
|
||||
}
|
||||
|
||||
npRelayN OBJECT-TYPE
|
||||
SYNTAX INTEGER (1..8)
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "The N of output relay"
|
||||
::= { npRelayEntry 1 }
|
||||
|
||||
npRelayMode OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
flip(-1),
|
||||
off(0),
|
||||
on(1),
|
||||
watchdog(2),
|
||||
schedule(3),
|
||||
scheduleAndWatchdog(4),
|
||||
logic(5)
|
||||
}
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION "Control of relay:
|
||||
-1 - flip between on(1) and off(0)
|
||||
0 - manual off
|
||||
1 - manual on
|
||||
2 - watchdog
|
||||
3 - schedule
|
||||
4 - both schedule and watchdog (while switched on by schedule)
|
||||
5 - logic"
|
||||
::={npRelayEntry 2}
|
||||
|
||||
npRelayStartReset OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION "Write 1 to start reset (switch relay off for some time)"
|
||||
::={npRelayEntry 3}
|
||||
|
||||
npRelayMemo OBJECT-TYPE
|
||||
SYNTAX DisplayString
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "Relay memo"
|
||||
::={npRelayEntry 6}
|
||||
|
||||
npRelayFlip OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
flip(-1)
|
||||
}
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "Write -1 to flip between manual on and manual off states of relay"
|
||||
::={npRelayEntry 14}
|
||||
|
||||
npRelayState OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
off(0),
|
||||
on(1)
|
||||
}
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "Actual relay state at the moment,
|
||||
regardless of source of control.
|
||||
0 - relay is off
|
||||
1 - relay is on"
|
||||
::={npRelayEntry 15}
|
||||
|
||||
npRelayPowered OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
no(0),
|
||||
yes(1)
|
||||
}
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "AC presence on output.
|
||||
0 - no AC dew to relay switched off or no ac on input
|
||||
1 - AC is present"
|
||||
::={npRelayEntry 16}
|
||||
|
||||
|
||||
npPwr OBJECT IDENTIFIER::={ lightcom 5800 }
|
||||
|
||||
npPwrTable OBJECT-TYPE
|
||||
SYNTAX SEQUENCE OF NpPwrEntry
|
||||
MAX-ACCESS not-accessible
|
||||
STATUS current
|
||||
DESCRIPTION "Watchdog and outlet/relay control table"
|
||||
::= { npPwr 3 }
|
||||
|
||||
npPwrEntry OBJECT-TYPE
|
||||
SYNTAX NpPwrEntry
|
||||
MAX-ACCESS not-accessible
|
||||
STATUS current
|
||||
DESCRIPTION "Watchdog control table row"
|
||||
INDEX { npPwrChannelN }
|
||||
::= { npPwrTable 1 }
|
||||
|
||||
NpPwrEntry ::= SEQUENCE {
|
||||
npPwrChannelN INTEGER,
|
||||
npPwrStartReset INTEGER,
|
||||
npPwrResetsCounter INTEGER,
|
||||
npPwrRepeatingResetsCounter INTEGER,
|
||||
npPwrMemo DisplayString
|
||||
}
|
||||
|
||||
npPwrChannelN OBJECT-TYPE
|
||||
SYNTAX INTEGER (1..4)
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "The id of watchdog/power channel"
|
||||
::= { npPwrEntry 1 }
|
||||
|
||||
npPwrStartReset OBJECT-TYPE
|
||||
SYNTAX INTEGER (0..2)
|
||||
MAX-ACCESS read-only
|
||||
STATUS obsolete
|
||||
DESCRIPTION "Deprecated in current FW version: Write 1 to start forced reset.
|
||||
On read:
|
||||
0 - normal operation
|
||||
1 - reset is active
|
||||
2 - reboot pause is active or watchdog is inactive"
|
||||
::={npPwrEntry 2}
|
||||
|
||||
npPwrResetsCounter OBJECT-TYPE
|
||||
SYNTAX INTEGER (0..65535)
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION "Counter of watchdog resets
|
||||
Write 0 to clear."
|
||||
::={npPwrEntry 4}
|
||||
|
||||
npPwrRepeatingResetsCounter OBJECT-TYPE
|
||||
SYNTAX INTEGER (0..65535)
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "Counter of continous failed
|
||||
watchdog resets"
|
||||
::={npPwrEntry 5}
|
||||
|
||||
npPwrMemo OBJECT-TYPE
|
||||
SYNTAX DisplayString
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "Watchdog channel memo"
|
||||
::={npPwrEntry 6}
|
||||
|
||||
|
||||
npSmoke OBJECT IDENTIFIER::={lightcom 8200}
|
||||
|
||||
npSmokeTable OBJECT-TYPE
|
||||
SYNTAX SEQUENCE OF NpSmokeEntry
|
||||
MAX-ACCESS not-accessible
|
||||
STATUS current
|
||||
DESCRIPTION "Smoke Sensors Table"
|
||||
::= { npSmoke 1 }
|
||||
|
||||
npSmokeEntry OBJECT-TYPE
|
||||
SYNTAX NpSmokeEntry
|
||||
MAX-ACCESS not-accessible
|
||||
STATUS current
|
||||
DESCRIPTION "Smoke Sensors Table Row"
|
||||
INDEX { npSmokeSensorN }
|
||||
::= { npSmokeTable 1 }
|
||||
|
||||
NpSmokeEntry ::= SEQUENCE {
|
||||
npSmokeSensorN INTEGER,
|
||||
npSmokeStatus INTEGER,
|
||||
npSmokePower INTEGER,
|
||||
npSmokeReset INTEGER,
|
||||
npSmokeMemo DisplayString
|
||||
}
|
||||
|
||||
npSmokeSensorN OBJECT-TYPE
|
||||
SYNTAX INTEGER (1..4)
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "The id of 1Wire Smoke sensor, 1 to 4"
|
||||
::= { npSmokeEntry 1 }
|
||||
|
||||
npSmokeStatus OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
ok(0),
|
||||
alarm(1),
|
||||
off(4),
|
||||
failed(5)
|
||||
}
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "Status of Smoke sensor"
|
||||
::= { npSmokeEntry 2 }
|
||||
|
||||
npSmokePower OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
off(0),
|
||||
on(1)
|
||||
}
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION "Controls power on Smoke sensor current loop"
|
||||
::= { npSmokeEntry 3 }
|
||||
|
||||
npSmokeReset OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION "Write 1 to switch off for approx. 10s to reset sensor"
|
||||
::= { npSmokeEntry 4 }
|
||||
|
||||
npSmokeMemo OBJECT-TYPE
|
||||
SYNTAX DisplayString
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "Smoke sensor memo"
|
||||
::= { npSmokeEntry 6 }
|
||||
|
||||
|
||||
npSmokeTraps OBJECT IDENTIFIER::={npSmoke 2}
|
||||
npSmokeTrapPrefix OBJECT IDENTIFIER::={npSmokeTraps 0}
|
||||
|
||||
npSmokeTrapSensorN OBJECT-TYPE
|
||||
SYNTAX INTEGER (1..4)
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "The id of 1Wire Smoke sensor, 1 to 4"
|
||||
::= { npSmokeTraps 1 }
|
||||
|
||||
npSmokeTrapStatus OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
ok(0),
|
||||
alarm(1),
|
||||
off(4),
|
||||
failed(5)
|
||||
}
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "New status of Smoke sensor"
|
||||
::= { npSmokeTraps 2 }
|
||||
|
||||
npSmokeTrapMemo OBJECT-TYPE
|
||||
SYNTAX DisplayString
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "Smoke sensor memo"
|
||||
::= { npSmokeTraps 6 }
|
||||
|
||||
npSmokeTrap NOTIFICATION-TYPE
|
||||
OBJECTS {
|
||||
npSmokeTrapSensorN,
|
||||
npSmokeTrapStatus,
|
||||
npSmokeTrapMemo
|
||||
}
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"Status of 1W Smoke sensor has changed"
|
||||
::= { npSmokeTrapPrefix 1 }
|
||||
|
||||
|
||||
|
||||
|
||||
npThermo OBJECT IDENTIFIER::={lightcom 8800}
|
||||
|
||||
npThermoTable OBJECT-TYPE
|
||||
SYNTAX SEQUENCE OF NpThermoEntry
|
||||
MAX-ACCESS not-accessible
|
||||
STATUS current
|
||||
DESCRIPTION "Thermo Sensors Table"
|
||||
::= { npThermo 1 }
|
||||
|
||||
npThermoEntry OBJECT-TYPE
|
||||
SYNTAX NpThermoEntry
|
||||
MAX-ACCESS not-accessible
|
||||
STATUS current
|
||||
DESCRIPTION "Thermo Sensors Table Row"
|
||||
INDEX { npThermoSensorN }
|
||||
::= { npThermoTable 1 }
|
||||
|
||||
NpThermoEntry ::= SEQUENCE {
|
||||
npThermoSensorN INTEGER,
|
||||
npThermoValue INTEGER,
|
||||
npThermoStatus INTEGER,
|
||||
npThermoLow INTEGER,
|
||||
npThermoHigh INTEGER,
|
||||
npThermoMemo DisplayString
|
||||
}
|
||||
|
||||
npThermoSensorN OBJECT-TYPE
|
||||
SYNTAX INTEGER (1..8)
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "The id of temperature sensor, 1 to 8"
|
||||
::= { npThermoEntry 1 }
|
||||
|
||||
npThermoValue OBJECT-TYPE
|
||||
SYNTAX INTEGER (-60..280)
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "Temperature, deg.C"
|
||||
::= { npThermoEntry 2 }
|
||||
|
||||
npThermoStatus OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
failed(0),
|
||||
low(1),
|
||||
norm(2),
|
||||
high(3)
|
||||
}
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "Temperature status (0=fault, 1=underheat, 2=normal, 3=overheat)"
|
||||
::= { npThermoEntry 3 }
|
||||
|
||||
npThermoLow OBJECT-TYPE
|
||||
SYNTAX INTEGER (-60..280)
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "Bottom margin of normal temperature range, deg.C"
|
||||
::= { npThermoEntry 4 }
|
||||
|
||||
npThermoHigh OBJECT-TYPE
|
||||
SYNTAX INTEGER (-60..280)
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "Top margin of normal temperature range, deg.C"
|
||||
::= { npThermoEntry 5 }
|
||||
|
||||
npThermoMemo OBJECT-TYPE
|
||||
SYNTAX DisplayString
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "T channel memo"
|
||||
::= { npThermoEntry 6 }
|
||||
|
||||
|
||||
npThermoTraps OBJECT IDENTIFIER::={npThermo 2}
|
||||
npThermoTrapPrefix OBJECT IDENTIFIER::={npThermoTraps 0}
|
||||
|
||||
npThermoTrapSensorN OBJECT-TYPE
|
||||
SYNTAX INTEGER (1..8)
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "The id of temperature sensor, 1 to 8"
|
||||
::= { npThermoTraps 1 }
|
||||
|
||||
npThermoTrapValue OBJECT-TYPE
|
||||
SYNTAX INTEGER (-60..280)
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "Temperature, deg.C"
|
||||
::= { npThermoTraps 2 }
|
||||
|
||||
npThermoTrapStatus OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
failed(0),
|
||||
low(1),
|
||||
norm(2),
|
||||
high(3)
|
||||
}
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "Temperature status (0=fault, 1=underheat, 2=normal, 3=overheat)"
|
||||
::= { npThermoTraps 3 }
|
||||
|
||||
npThermoTrapLow OBJECT-TYPE
|
||||
SYNTAX INTEGER (-60..280)
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "Bottom margin of normal temperature range, deg.C"
|
||||
::= { npThermoTraps 4 }
|
||||
|
||||
npThermoTrapHigh OBJECT-TYPE
|
||||
SYNTAX INTEGER (-60..280)
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "Top margin of normal temperature range, deg.C"
|
||||
::= { npThermoTraps 5 }
|
||||
|
||||
npThermoTrapMemo OBJECT-TYPE
|
||||
SYNTAX DisplayString
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "T channel memo"
|
||||
::= { npThermoTraps 6 }
|
||||
|
||||
npThermoTrap NOTIFICATION-TYPE
|
||||
OBJECTS {
|
||||
npThermoTrapSensorN,
|
||||
npThermoTrapValue,
|
||||
npThermoTrapStatus,
|
||||
npThermoTrapLow,
|
||||
npThermoTrapHigh,
|
||||
npThermoTrapMemo
|
||||
}
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"Status of Thermo sensor is changed (crossing of normal temp. range)"
|
||||
::= { npThermoTrapPrefix 1 }
|
||||
|
||||
|
||||
|
||||
npIo OBJECT IDENTIFIER::={lightcom 8900}
|
||||
|
||||
npIoTable OBJECT-TYPE
|
||||
SYNTAX SEQUENCE OF NpIoEntry
|
||||
MAX-ACCESS not-accessible
|
||||
STATUS current
|
||||
DESCRIPTION "Digital Input/output Table"
|
||||
::= { npIo 1 }
|
||||
|
||||
npIoEntry OBJECT-TYPE
|
||||
SYNTAX NpIoEntry
|
||||
MAX-ACCESS not-accessible
|
||||
STATUS current
|
||||
DESCRIPTION "Digital Input/output Table Row"
|
||||
INDEX { npIoLineN }
|
||||
::= { npIoTable 1 }
|
||||
|
||||
NpIoEntry ::= SEQUENCE {
|
||||
npIoLineN INTEGER,
|
||||
npIoLevelIn INTEGER,
|
||||
npIoLevelOut INTEGER,
|
||||
npIoMemo DisplayString,
|
||||
npIoPulseCounter Counter32,
|
||||
npIoSinglePulseDuration INTEGER,
|
||||
npIoSinglePulseStart INTEGER
|
||||
}
|
||||
|
||||
npIoLineN OBJECT-TYPE
|
||||
SYNTAX INTEGER (1..4)
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "Number of IO line, from 1 to max supported"
|
||||
::= { npIoEntry 1 }
|
||||
|
||||
npIoLevelIn OBJECT-TYPE
|
||||
SYNTAX INTEGER (0..1)
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "Input level, 0 or 1"
|
||||
::= { npIoEntry 2 }
|
||||
|
||||
npIoLevelOut OBJECT-TYPE
|
||||
SYNTAX INTEGER (0..1)
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION "Output level, 0 or 1"
|
||||
::= { npIoEntry 3 }
|
||||
|
||||
npIoMemo OBJECT-TYPE
|
||||
SYNTAX DisplayString
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "IO line memo"
|
||||
::= { npIoEntry 6 }
|
||||
|
||||
npIoPulseCounter OBJECT-TYPE
|
||||
SYNTAX Counter32
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION "Pulse Counter on IO input line (counts positive fronts)
|
||||
Write 0 to reset."
|
||||
::= { npIoEntry 9 }
|
||||
|
||||
npIoSinglePulseDuration OBJECT-TYPE
|
||||
SYNTAX INTEGER (100..25500)
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION "Set duration of single pulse on IO output line,
|
||||
100ms to 25500ms, min. step is 100ms"
|
||||
::= { npIoEntry 12 }
|
||||
|
||||
npIoSinglePulseStart OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION "Write 1 to start single pulse on IO output.
|
||||
Output will be inverted for time, specified by npIoSinglePulseDuration"
|
||||
::= { npIoEntry 13 }
|
||||
|
||||
npIoTraps OBJECT IDENTIFIER::={npIo 2}
|
||||
npIoTrapPrefix OBJECT IDENTIFIER::={npIoTraps 0}
|
||||
|
||||
npIoTrapLineN OBJECT-TYPE
|
||||
SYNTAX INTEGER (1..2)
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "Trap data, Number of IO line"
|
||||
::= { npIoTraps 1 }
|
||||
|
||||
npIoTrapLevelIn OBJECT-TYPE
|
||||
SYNTAX INTEGER (0..1)
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "Trap data, new Input level, 0 or 1"
|
||||
::= { npIoTraps 2 }
|
||||
|
||||
npIoTrapMemo OBJECT-TYPE
|
||||
SYNTAX DisplayString
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "Trap data, IO line memo"
|
||||
::= { npIoTraps 6 }
|
||||
|
||||
npIoTrap NOTIFICATION-TYPE
|
||||
OBJECTS {
|
||||
npIoTrapLineN,
|
||||
npIoTrapLevelIn,
|
||||
npIoTrapMemo
|
||||
}
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"Input state of IO line is changed"
|
||||
::= { npIoTrapPrefix 1 }
|
||||
|
||||
|
||||
|
||||
npRelHumidity OBJECT IDENTIFIER::={lightcom 8400}
|
||||
npRelHumSensor OBJECT IDENTIFIER::={npRelHumidity 2}
|
||||
|
||||
npRelHumSensorStatus OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
error(0),
|
||||
ok(1)
|
||||
}
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "Status of the Rel.Humidity Sensor One
|
||||
1=Normal, 0=Error or Sensor isn't connected"
|
||||
::= { npRelHumSensor 3 }
|
||||
|
||||
npRelHumSensorValueH OBJECT-TYPE
|
||||
SYNTAX INTEGER (0..100)
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "Relative humidity value, %"
|
||||
::= { npRelHumSensor 2 }
|
||||
|
||||
npRelHumSensorValueT OBJECT-TYPE
|
||||
SYNTAX INTEGER (-60..200)
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "Sensor temperature, deg.C"
|
||||
::= { npRelHumSensor 4 }
|
||||
|
||||
npRelHumSensorStatusH OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
sensorFailed(0),
|
||||
belowSafeRange(1),
|
||||
inSafeRange(2),
|
||||
aboveSafeRange(3)
|
||||
}
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "Status of Relative Humiduty"
|
||||
::= { npRelHumSensor 5 }
|
||||
|
||||
npRelHumSafeRangeHigh OBJECT-TYPE
|
||||
SYNTAX INTEGER (0..100)
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "Relative Humidity safe range, top margin, %RH"
|
||||
::= { npRelHumSensor 7 }
|
||||
|
||||
npRelHumSafeRangeLow OBJECT-TYPE
|
||||
SYNTAX INTEGER (0..100)
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "Relative Humidity safe range, bottom margin, %RH"
|
||||
::= { npRelHumSensor 8 }
|
||||
|
||||
npRelHumSensorValueT100 OBJECT-TYPE
|
||||
SYNTAX Integer32
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "Sensor temperature, deg.C * 100 (fixed point two decimal places)
|
||||
Used to get access to the fractional part of T value"
|
||||
::= { npRelHumSensor 9 }
|
||||
|
||||
npRelHumTraps OBJECT IDENTIFIER::={npRelHumidity 9}
|
||||
npRelHumTrapPrefix OBJECT IDENTIFIER::={npRelHumTraps 0}
|
||||
|
||||
npRelHumTrap NOTIFICATION-TYPE
|
||||
OBJECTS {
|
||||
npRelHumSensorStatusH,
|
||||
npRelHumSensorValueH,
|
||||
npRelHumSafeRangeHigh,
|
||||
npRelHumSafeRangeLow
|
||||
}
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"Status of Relative Humidity RH sensor has changed!"
|
||||
::= { npRelHumTrapPrefix 1 }
|
||||
|
||||
|
||||
|
||||
npGsm OBJECT IDENTIFIER::={lightcom 3800}
|
||||
npGsmInfo OBJECT IDENTIFIER::={npGsm 1}
|
||||
|
||||
npGsmFailed OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
ok (0),
|
||||
failed (1),
|
||||
fatalError (2)
|
||||
}
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "Firmware's GSM module status"
|
||||
::= { npGsmInfo 1 }
|
||||
|
||||
npGsmRegistration OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
impossible (0),
|
||||
homeNetwork (1),
|
||||
searching (2),
|
||||
denied (3),
|
||||
unknown (4),
|
||||
roaming (5),
|
||||
infoUpdate (255)
|
||||
}
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "Status of modem registration in GSM network (AT+CREG? result)"
|
||||
::= { npGsmInfo 2 }
|
||||
|
||||
npGsmStrength OBJECT-TYPE
|
||||
SYNTAX INTEGER (0..255)
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "GSM signal strength.
|
||||
0..31 = 0..100%,
|
||||
99 = unknown or n/a,
|
||||
255 = updating info"
|
||||
::= { npGsmInfo 3 }
|
||||
|
||||
npGsmSendSms OBJECT-TYPE
|
||||
SYNTAX DisplayString
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION "Send arbitrary SMS.
|
||||
Format: [phone_number,phone_number,...] Message
|
||||
One to four destination phone numbers
|
||||
If [] and numbers omitted, mesagge will be sent to preset numbers from SMS setup
|
||||
Only Latin characters allowed in message body"
|
||||
::= { npGsmInfo 9 }
|
||||
|
||||
|
||||
npGsmTraps OBJECT IDENTIFIER::={npGsm 2}
|
||||
npGsmTrapPrefix OBJECT IDENTIFIER::={npGsmTraps 0}
|
||||
|
||||
npGsmTrap NOTIFICATION-TYPE
|
||||
OBJECTS {
|
||||
npGsmFailed,
|
||||
npGsmRegistration,
|
||||
npGsmStrength
|
||||
}
|
||||
STATUS current
|
||||
DESCRIPTION
|
||||
"GSM modem or SMS firmware problems"
|
||||
::= { npGsmTrapPrefix 1 }
|
||||
|
||||
|
||||
|
||||
npBattery OBJECT IDENTIFIER::={ lightcom 3900 }
|
||||
npBatteryInfo OBJECT IDENTIFIER::={npBattery 1}
|
||||
|
||||
npBatteryPok OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
batteryPower (0),
|
||||
externalPower (1)
|
||||
}
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "Power source"
|
||||
::= { npBatteryInfo 1 }
|
||||
|
||||
npBatteryLevel OBJECT-TYPE
|
||||
SYNTAX INTEGER (0..100)
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "Battery charge, approximate value, in percent.
|
||||
Valid only if npBatteryPok = 0"
|
||||
::= { npBatteryInfo 2 }
|
||||
|
||||
npBatteryChg OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
batteryChargingSuspended (0),
|
||||
batteryFastCharging (1)
|
||||
}
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "Battery chargeing status.
|
||||
0 if charging suspended or battery is full,
|
||||
1 while LiPo fast charging."
|
||||
::= { npBatteryInfo 3 }
|
||||
|
||||
|
||||
npIr OBJECT IDENTIFIER::={lightcom 7900}
|
||||
npIrCtrl OBJECT IDENTIFIER::={npIr 1}
|
||||
|
||||
npIrPlayCmd OBJECT-TYPE
|
||||
SYNTAX INTEGER (1..16)
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION "Write IR command number to send IR command"
|
||||
::= { npIrCtrl 1 }
|
||||
|
||||
npIrReset OBJECT-TYPE
|
||||
SYNTAX INTEGER (0..1)
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION "Write 1 to reset IR transiever.
|
||||
After reset, send IR command and check npIrStatus."
|
||||
::= { npIrCtrl 2 }
|
||||
|
||||
npIrStatus OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
commandCompleted (0),
|
||||
protocolError (1),
|
||||
commandAccepted (2),
|
||||
errorUnknown (16),
|
||||
errorBadNumber (17),
|
||||
errorEmptyRecord (18),
|
||||
errorFlashChip (19),
|
||||
errorTimeout (20),
|
||||
errorExtBusBusy (21)
|
||||
}
|
||||
MAX-ACCESS read-only
|
||||
STATUS current
|
||||
DESCRIPTION "IR transiever status"
|
||||
::= { npIrCtrl 3 }
|
||||
|
||||
|
||||
npReboot OBJECT IDENTIFIER::={ lightcom 911 }
|
||||
|
||||
npSoftReboot OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION "Write 1 to reboot device after
|
||||
current operations completition"
|
||||
::= { npReboot 1 }
|
||||
|
||||
npResetStack OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION "Write 1 to re-initialize network
|
||||
stack"
|
||||
::= { npReboot 2 }
|
||||
|
||||
npForcedReboot OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
MAX-ACCESS read-write
|
||||
STATUS current
|
||||
DESCRIPTION "Write 1 to immediate forced reboot"
|
||||
::= { npReboot 3 }
|
||||
|
||||
END
|
Reference in New Issue