Commit version 24.12.13800
This commit is contained in:
923
mibs/eaton/EatonSTS-MIB
Normal file
923
mibs/eaton/EatonSTS-MIB
Normal file
@ -0,0 +1,923 @@
|
||||
-- EatonSTS-MIB { iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) eaton(534) sts(10) ats(1) }
|
||||
-- last modified: 02/19/2013
|
||||
EatonSTS-MIB DEFINITIONS ::= BEGIN
|
||||
|
||||
IMPORTS
|
||||
enterprises
|
||||
FROM RFC1155-SMI
|
||||
DisplayString
|
||||
FROM RFC1213-MIB
|
||||
OBJECT-TYPE
|
||||
FROM RFC-1212
|
||||
TRAP-TYPE
|
||||
FROM RFC-1215;
|
||||
--
|
||||
eaton OBJECT IDENTIFIER ::= { enterprises 534 }
|
||||
sts OBJECT IDENTIFIER ::= { eaton 10 }
|
||||
ats OBJECT IDENTIFIER ::= { sts 1 }
|
||||
|
||||
atsAgent OBJECT IDENTIFIER ::= { ats 1 }
|
||||
atsIdent OBJECT IDENTIFIER ::= { ats 2 }
|
||||
atsMeasure OBJECT IDENTIFIER ::= { ats 3 }
|
||||
atsStatus OBJECT IDENTIFIER ::= { ats 4 }
|
||||
atsLog OBJECT IDENTIFIER ::= { ats 5 }
|
||||
atsConfig OBJECT IDENTIFIER ::= { ats 6 }
|
||||
atsUpgrade OBJECT IDENTIFIER ::= { ats 7 }
|
||||
atsTraps OBJECT IDENTIFIER ::= { ats 20 }
|
||||
|
||||
--
|
||||
-- Agent group
|
||||
atsAgentManufacturer OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE(0..16))
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The manufacturer name of SNMP-Agent."
|
||||
::= { atsAgent 1 }
|
||||
|
||||
atsAgentVersion OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE(0..20))
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The firmware version of SNMP-Agent."
|
||||
::= { atsAgent 2 }
|
||||
|
||||
atsAgentModbus OBJECT IDENTIFIER ::= { atsAgent 3 }
|
||||
|
||||
--
|
||||
-- Identification group
|
||||
atsIdentModel OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE(0..16))
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"Device model name."
|
||||
::= { atsIdent 1 }
|
||||
|
||||
atsIdentFWVersion OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE(0..16))
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"Device F/W version."
|
||||
::= { atsIdent 2 }
|
||||
|
||||
atsIdentRelease OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE(0..16))
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The released date."
|
||||
::= { atsIdent 3 }
|
||||
|
||||
atsIdentSerialNumber OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE(0..20))
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"Device serial number"
|
||||
::= { atsIdent 4 }
|
||||
|
||||
atsIdentIDCodes OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE(0..20))
|
||||
ACCESS read-write
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"Device ID codes"
|
||||
::= { atsIdent 5 }
|
||||
|
||||
--
|
||||
-- Identification / Modbus group
|
||||
atsAgentModbusLink OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
linked(1),
|
||||
un-linked(2)
|
||||
}
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The link status of ModBUS communication to ATS device."
|
||||
::= { atsAgentModbus 1 }
|
||||
|
||||
--
|
||||
-- Mesurement group
|
||||
atsInputTable OBJECT-TYPE
|
||||
SYNTAX SEQUENCE OF ATSInputEntry
|
||||
ACCESS not-accessible
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The table of input information."
|
||||
::= { atsMeasure 1 }
|
||||
|
||||
atsOutput OBJECT IDENTIFIER ::= { atsMeasure 2 }
|
||||
|
||||
atsMeasureTemperatureC OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
UNITS "1 Celsius"
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The internal temperature (in Celsius)."
|
||||
::= { atsMeasure 3 }
|
||||
|
||||
atsMeasureTemperatureF OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
UNITS "1 Fahrenheit"
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The internal temperature (in Fahrenheit)."
|
||||
::= { atsMeasure 4 }
|
||||
|
||||
atsMessureRunTime OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
UNITS "1 second"
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The ATS run time."
|
||||
::= { atsMeasure 5 }
|
||||
|
||||
atsMessureTransferedTimes OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The transfered times."
|
||||
::= { atsMeasure 6 }
|
||||
|
||||
atsMessureOperationMode OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
initialization(1),
|
||||
diagnosis(2),
|
||||
off(3),
|
||||
source-1(4),
|
||||
source-2(5),
|
||||
safe(6),
|
||||
fault(7)
|
||||
}
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The operation mode."
|
||||
::= { atsMeasure 7 }
|
||||
|
||||
--
|
||||
-- Mesurement / Input group
|
||||
atsInputEntry OBJECT-TYPE
|
||||
SYNTAX ATSInputEntry
|
||||
ACCESS not-accessible
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The input information of each source input:
|
||||
<node>.1 source-1
|
||||
<node>.2 source-2"
|
||||
INDEX { atsInputIndex }
|
||||
::= { atsInputTable 1 }
|
||||
|
||||
ATSInputEntry ::= SEQUENCE {
|
||||
atsInputIndex INTEGER,
|
||||
atsInputVoltage INTEGER,
|
||||
atsInputFrequency INTEGER
|
||||
}
|
||||
|
||||
atsInputIndex OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
source-1(1),
|
||||
source-2(2)
|
||||
}
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"Index to input."
|
||||
::= { atsInputEntry 1 }
|
||||
|
||||
atsInputVoltage OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
UNITS "0.1 V"
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The input voltage in front of relay."
|
||||
::= { atsInputEntry 2 }
|
||||
|
||||
atsInputFrequency OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
UNITS "0.1 Hz"
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The input frequency."
|
||||
::= { atsInputEntry 3 }
|
||||
|
||||
--
|
||||
-- Mesurement / Output group
|
||||
atsOutputVoltage OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
UNITS "0.1 V"
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The output voltage."
|
||||
::= { atsOutput 1 }
|
||||
|
||||
atsOutputCurrent OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
UNITS "0.1 A"
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The output current."
|
||||
::= { atsOutput 2 }
|
||||
|
||||
--
|
||||
-- Status group
|
||||
atsInputFlowIndicator OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The input flow indicator.
|
||||
[7:0] source-1 (low byte)
|
||||
[15:8] source-2 (high byte)
|
||||
|
||||
bit# --> atsInputFlowTable.1.(#+2).x
|
||||
|
||||
Example:
|
||||
bit1 of low byte --> atsInputFlowTable.1.3.1
|
||||
bit1 of high byte --> atsInputFlowTable.1.3.2"
|
||||
|
||||
::= { atsStatus 1 }
|
||||
|
||||
atsInputFlowTable OBJECT-TYPE
|
||||
SYNTAX SEQUENCE OF ATSInputFlowEntry
|
||||
ACCESS not-accessible
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The table of input flow status."
|
||||
::= { atsStatus 2 }
|
||||
|
||||
atsInputFailureIndicator OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The input failure indicator.
|
||||
[15:0] source-1 (low word)
|
||||
[31:16] source-2 (high word)
|
||||
|
||||
bit# --> atsInputFailureTable.1.(#+2).x
|
||||
|
||||
Example:
|
||||
bit0 of low word --> atsInputFailureTable.1.2.1
|
||||
bit0 of high word --> atsInputFailureTable.1.2.2"
|
||||
|
||||
::= { atsStatus 3 }
|
||||
|
||||
atsInputFailureTable OBJECT-TYPE
|
||||
SYNTAX SEQUENCE OF ATSInputFailureEntry
|
||||
ACCESS not-accessible
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The table of input status."
|
||||
::= { atsStatus 4 }
|
||||
|
||||
atsFailureIndicator OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The failure indicator.
|
||||
bit# --> atsFailure.(#+1)
|
||||
|
||||
Example:
|
||||
bit2 --> atsFailure.3 (atsFailureOutputOC)"
|
||||
::= { atsStatus 5 }
|
||||
|
||||
atsFailure OBJECT IDENTIFIER ::= { atsStatus 6 }
|
||||
|
||||
--
|
||||
-- Status / Input Flow group
|
||||
atsInputFlowEntry OBJECT-TYPE
|
||||
SYNTAX ATSInputFlowEntry
|
||||
ACCESS not-accessible
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The input flow status:
|
||||
<node>.1 source-1
|
||||
<node>.2 source-2"
|
||||
INDEX { atsInputFlowIndex }
|
||||
::= { atsInputFlowTable 1 }
|
||||
|
||||
ATSInputFlowEntry ::= SEQUENCE {
|
||||
atsInputFlowIndex INTEGER,
|
||||
atsInputFlowRelay INTEGER,
|
||||
atsInputFlowSCR INTEGER,
|
||||
atsInputFlowParallelRelay INTEGER
|
||||
}
|
||||
|
||||
atsInputFlowIndex OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
source-1(1),
|
||||
source-2(2)
|
||||
}
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"Index of input entry."
|
||||
::= { atsInputFlowEntry 1 }
|
||||
|
||||
atsInputFlowRelay OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
on(1),
|
||||
off(2)
|
||||
}
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The status of input relay."
|
||||
::= { atsInputFlowEntry 2 }
|
||||
|
||||
atsInputFlowSCR OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
on(1),
|
||||
off(2)
|
||||
}
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The status of input SCR."
|
||||
::= { atsInputFlowEntry 3 }
|
||||
|
||||
atsInputFlowParallelRelay OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
on(1),
|
||||
off(2)
|
||||
}
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The status of input parallel relay."
|
||||
::= { atsInputFlowEntry 4 }
|
||||
|
||||
--
|
||||
-- Status / Input Failure group
|
||||
atsInputFailureEntry OBJECT-TYPE
|
||||
SYNTAX ATSInputFailureEntry
|
||||
ACCESS not-accessible
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The status of input failure:
|
||||
|
||||
<node>.1 source-1
|
||||
<node>.2 source-2"
|
||||
INDEX { atsInputFailureIndex }
|
||||
::= { atsInputFailureTable 1 }
|
||||
|
||||
ATSInputFailureEntry ::= SEQUENCE {
|
||||
atsInputFailureIndex INTEGER,
|
||||
atsInputFailureRelayOpen INTEGER,
|
||||
atsInputFailureRelayShort INTEGER,
|
||||
atsInputFailureSCROpen INTEGER,
|
||||
atsInputFailureSCRShort INTEGER,
|
||||
atsInputFailureSCRThermal INTEGER,
|
||||
atsInputFailureAuxPower INTEGER,
|
||||
atsInputFailureDrop INTEGER,
|
||||
atsInputFailureBrownout INTEGER,
|
||||
atsInputFailureFrequency INTEGER,
|
||||
atsInputFailureNotOperable INTEGER
|
||||
}
|
||||
|
||||
atsInputFailureIndex OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
source-1(1),
|
||||
source-2(2)
|
||||
}
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"Index of entry."
|
||||
::= { atsInputFailureEntry 1 }
|
||||
|
||||
atsInputFailureRelayOpen OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
abnormal(1),
|
||||
normal(2)
|
||||
}
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The status of input relay is OPEN."
|
||||
::= { atsInputFailureEntry 2 }
|
||||
|
||||
atsInputFailureRelayShort OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
abnormal(1),
|
||||
normal(2)
|
||||
}
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The status of input relay is SHORT."
|
||||
::= { atsInputFailureEntry 3 }
|
||||
|
||||
atsInputFailureSCROpen OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
abnormal(1),
|
||||
normal(2)
|
||||
}
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The status of input SCR is OPEN."
|
||||
::= { atsInputFailureEntry 4 }
|
||||
|
||||
atsInputFailureSCRShort OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
abnormal(1),
|
||||
normal(2)
|
||||
}
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The status of input SCR is SHORT."
|
||||
::= { atsInputFailureEntry 5 }
|
||||
|
||||
atsInputFailureSCRThermal OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
abnormal(1),
|
||||
normal(2)
|
||||
}
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The status of input SCR thermal is over."
|
||||
::= { atsInputFailureEntry 6 }
|
||||
|
||||
atsInputFailureAuxPower OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
abnormal(1),
|
||||
normal(2)
|
||||
}
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"Internal axuiliary power is reported as failure."
|
||||
::= { atsInputFailureEntry 7 }
|
||||
|
||||
atsInputFailureDrop OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
abnormal(1),
|
||||
normal(2)
|
||||
}
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"A voltage drop was detected."
|
||||
::= { atsInputFailureEntry 8 }
|
||||
|
||||
atsInputFailureBrownout OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
abnormal(1),
|
||||
normal(2)
|
||||
}
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"A voltage brownout was detected."
|
||||
::= { atsInputFailureEntry 9 }
|
||||
|
||||
atsInputFailureFrequency OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
abnormal(1),
|
||||
normal(2)
|
||||
}
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The input frequency is out of range."
|
||||
::= { atsInputFailureEntry 10 }
|
||||
|
||||
atsInputFailureNotOperable OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
abnormal(1),
|
||||
normal(2)
|
||||
}
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The input is not operable."
|
||||
::= { atsInputFailureEntry 11 }
|
||||
|
||||
--
|
||||
-- Status / Failure group
|
||||
atsFailureSwitchFault OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
abnormal(1),
|
||||
normal(2)
|
||||
}
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The relay, SCR and thermal switch fail."
|
||||
::= { atsFailure 1 }
|
||||
|
||||
atsFailureNoOutput OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
abnormal(1),
|
||||
normal(2)
|
||||
}
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"There is no output."
|
||||
::= { atsFailure 2 }
|
||||
|
||||
atsFailureOutputOC OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
abnormal(1),
|
||||
normal(2)
|
||||
}
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The output current is over."
|
||||
::= { atsFailure 3 }
|
||||
|
||||
atsFailureOverTemperature OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
abnormal(1),
|
||||
normal(2)
|
||||
}
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The ambient temperature is over."
|
||||
::= { atsFailure 4 }
|
||||
|
||||
--
|
||||
-- Event log Group
|
||||
atsLogNum OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The number of event logs."
|
||||
::= { atsLog 1 }
|
||||
|
||||
atsLogTable OBJECT-TYPE
|
||||
SYNTAX SEQUENCE OF ATSLogEntry
|
||||
ACCESS not-accessible
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The table of event logs."
|
||||
::= { atsLog 2 }
|
||||
|
||||
atsLogEntry OBJECT-TYPE
|
||||
SYNTAX ATSLogEntry
|
||||
ACCESS not-accessible
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The recorded event log"
|
||||
INDEX { atsLogIndex }
|
||||
::= { atsLogTable 1 }
|
||||
|
||||
ATSLogEntry ::= SEQUENCE {
|
||||
atsLogIndex INTEGER,
|
||||
atsLogTime TimeTicks,
|
||||
atsLogCode INTEGER,
|
||||
atsLogTimeText DisplayString
|
||||
}
|
||||
|
||||
atsLogIndex OBJECT-TYPE
|
||||
SYNTAX INTEGER (1..10)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"Index to event log."
|
||||
::= { atsLogEntry 1 }
|
||||
|
||||
atsLogTime OBJECT-TYPE
|
||||
SYNTAX TimeTicks
|
||||
UNITS "1 Second"
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The event time (since 01/01/2000 00:00:00)."
|
||||
::= { atsLogEntry 2 }
|
||||
|
||||
atsLogCode OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The event code."
|
||||
::= { atsLogEntry 3 }
|
||||
|
||||
atsLogTimeText OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE(0..20))
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The event time with form: hh:mm:ss MM/DD/YYYY."
|
||||
::= { atsLogEntry 4 }
|
||||
|
||||
--
|
||||
-- Configuration group
|
||||
atsConfigTime OBJECT IDENTIFIER ::= { atsConfig 1 }
|
||||
|
||||
atsConfigInputTable OBJECT-TYPE
|
||||
SYNTAX SEQUENCE OF ATSConfigInputEntry
|
||||
ACCESS not-accessible
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The table of input configuration."
|
||||
::= { atsConfig 2 }
|
||||
|
||||
atsConfigInputVoltageRating OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
UNITS "0.1 V"
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The input voltage rating."
|
||||
::= { atsConfig 3 }
|
||||
|
||||
atsConfigRandomTime OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
UNITS "0.1 Second"
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"Delay time is calculated by device serial numbers."
|
||||
::= { atsConfig 4 }
|
||||
|
||||
atsConfigPreferred OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
source-1(1),
|
||||
source-2(2)
|
||||
}
|
||||
ACCESS read-write
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The prefered source."
|
||||
::= { atsConfig 5 }
|
||||
|
||||
atsConfigSensitivity OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
high(1),
|
||||
low(2)
|
||||
}
|
||||
ACCESS read-write
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The AC Blackout Sensitivity."
|
||||
::= { atsConfig 6 }
|
||||
|
||||
atsConfigTest OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
active(1),
|
||||
inactive(2)
|
||||
}
|
||||
ACCESS read-write
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The activity of source test."
|
||||
::= { atsConfig 7 }
|
||||
|
||||
--
|
||||
-- Configuration / Time group
|
||||
atsConfigTimeRTC OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
ACCESS read-write
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The RTC timer value (since 1/1/2000 00:00:00)."
|
||||
::= { atsConfigTime 1 }
|
||||
|
||||
atsConfigTimeTextDate OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE(0..10))
|
||||
ACCESS read-write
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The present date in MM/DD/YYYY text format."
|
||||
::= { atsConfigTime 2 }
|
||||
|
||||
atsConfigTimeTextTime OBJECT-TYPE
|
||||
SYNTAX DisplayString (SIZE(0..8))
|
||||
ACCESS read-write
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The present time in hh:mm:ss text format."
|
||||
::= { atsConfigTime 3 }
|
||||
|
||||
--
|
||||
-- Configuration / Input
|
||||
atsConfigInputEntry OBJECT-TYPE
|
||||
SYNTAX ATSConfigInputEntry
|
||||
ACCESS not-accessible
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"Input configuration entry"
|
||||
INDEX { atsConfigInputIndex }
|
||||
::= { atsConfigInputTable 1 }
|
||||
|
||||
ATSConfigInputEntry ::= SEQUENCE {
|
||||
atsConfigInputIndex INTEGER,
|
||||
atsConfigInputTrip INTEGER,
|
||||
atsConfigInputBrownoutLow INTEGER,
|
||||
atsConfigInputBrownoutHigh INTEGER,
|
||||
atsConfigInputRecover INTEGER,
|
||||
atsConfigInputMaxVoltage INTEGER,
|
||||
atsConfigInputMaxTime INTEGER,
|
||||
atsConfigInputDelayTime INTEGER
|
||||
}
|
||||
|
||||
atsConfigInputIndex OBJECT-TYPE
|
||||
SYNTAX INTEGER (1..2)
|
||||
ACCESS read-write
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"Index to input configuration."
|
||||
::= { atsConfigInputEntry 1 }
|
||||
|
||||
atsConfigInputTrip OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
UNITS "0.1 V"
|
||||
ACCESS read-write
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"Setting of input trip voltage."
|
||||
::= { atsConfigInputEntry 2 }
|
||||
|
||||
atsConfigInputBrownoutLow OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
UNITS "0.1 V"
|
||||
ACCESS read-write
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"Setting of input brownout low voltage."
|
||||
::= { atsConfigInputEntry 3 }
|
||||
|
||||
atsConfigInputBrownoutHigh OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
UNITS "0.1 V"
|
||||
ACCESS read-write
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"Setting of input brownout high voltage."
|
||||
::= { atsConfigInputEntry 4 }
|
||||
|
||||
atsConfigInputRecover OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
UNITS "0.1 Second"
|
||||
ACCESS read-write
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"Setting of input recovered time."
|
||||
::= { atsConfigInputEntry 5 }
|
||||
|
||||
atsConfigInputMaxVoltage OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
UNITS "1 V"
|
||||
ACCESS read-write
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"Set the detected delta RMS voltage of fast detected AC blackout by
|
||||
the comparing cycles."
|
||||
::= { atsConfigInputEntry 6 }
|
||||
|
||||
atsConfigInputMaxTime OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
UNITS "0.1 Second"
|
||||
ACCESS read-write
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"Set the detected time of fast detected AC blackout by the
|
||||
comparing cycles."
|
||||
::= { atsConfigInputEntry 7 }
|
||||
|
||||
atsConfigInputDelayTime OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
UNITS "0.1 Second"
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The delay time includes Recovered Time (atsConfigInputRecover) and
|
||||
Random Delay Time."
|
||||
::= { atsConfigInputEntry 8 }
|
||||
|
||||
-- Upgrade group
|
||||
atsUpgradeProcess OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
idle(1),
|
||||
run(2),
|
||||
error(3)
|
||||
}
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The status of upgrade progress."
|
||||
|
||||
::= { atsUpgrade 1 }
|
||||
|
||||
atsUpgradeStep OBJECT-TYPE
|
||||
SYNTAX INTEGER {
|
||||
init(1),
|
||||
fileid(2),
|
||||
auth(3),
|
||||
addr(4),
|
||||
erase(5),
|
||||
program(6),
|
||||
read(7)
|
||||
}
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The step of ATS F/W upgrade."
|
||||
::= { atsUpgrade 2 }
|
||||
|
||||
atsUpgradePercentage OBJECT-TYPE
|
||||
SYNTAX INTEGER
|
||||
UNITS "0.1%"
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION
|
||||
"The percentage of current progress (program or read)."
|
||||
::= { atsUpgrade 3 }
|
||||
|
||||
--
|
||||
-- Traps group
|
||||
atsTrapCommLost TRAP-TYPE
|
||||
ENTERPRISE atsTraps
|
||||
DESCRIPTION
|
||||
"Communication with the ATS failed."
|
||||
::= 1
|
||||
|
||||
atsTrapCommEstablished TRAP-TYPE
|
||||
ENTERPRISE atsTraps
|
||||
DESCRIPTION
|
||||
"Communication with the ATS reestablished."
|
||||
::= 2
|
||||
|
||||
atsTrapConfigChange TRAP-TYPE
|
||||
ENTERPRISE atsTraps
|
||||
DESCRIPTION
|
||||
"The ATS configuration has been changed."
|
||||
::= 3
|
||||
|
||||
atsTrapFlowChange TRAP-TYPE
|
||||
ENTERPRISE atsTraps
|
||||
DESCRIPTION
|
||||
"The Input flow status has been changed."
|
||||
::= 4
|
||||
|
||||
atsTrapInput1Alarm TRAP-TYPE
|
||||
ENTERPRISE atsTraps
|
||||
DESCRIPTION
|
||||
"Alarm of source-1 failure(s)."
|
||||
::= 5
|
||||
|
||||
atsTrapInput1AlarmRecover TRAP-TYPE
|
||||
ENTERPRISE atsTraps
|
||||
DESCRIPTION
|
||||
"Recover from source-1 failure(s)."
|
||||
::= 6
|
||||
|
||||
atsTrapInput2Alarm TRAP-TYPE
|
||||
ENTERPRISE atsTraps
|
||||
DESCRIPTION
|
||||
"Alarm of source-2 failure(s)."
|
||||
::= 7
|
||||
|
||||
atsTrapInput2AlarmRecover TRAP-TYPE
|
||||
ENTERPRISE atsTraps
|
||||
DESCRIPTION
|
||||
"Recover from source-2 failure(s)."
|
||||
::= 8
|
||||
|
||||
atsTrapAlarm TRAP-TYPE
|
||||
ENTERPRISE atsTraps
|
||||
DESCRIPTION
|
||||
"Alarm of failure(s)."
|
||||
::= 9
|
||||
|
||||
atsTrapAlarmRecover TRAP-TYPE
|
||||
ENTERPRISE atsTraps
|
||||
DESCRIPTION
|
||||
"Recover from failure(s)."
|
||||
::= 10
|
||||
|
||||
atsTrapUpgradeBegin TRAP-TYPE
|
||||
ENTERPRISE atsTraps
|
||||
DESCRIPTION
|
||||
"Start to upgrade ATS firmware."
|
||||
::= 11
|
||||
|
||||
atsTrapUpgradeEnd TRAP-TYPE
|
||||
ENTERPRISE atsTraps
|
||||
DESCRIPTION
|
||||
"End of upgrade progress."
|
||||
::= 12
|
||||
END
|